Up to 60 A Class H(K) 250 V and 600 V ferrule power ... · Technical Data 10490 Effective June 2016...

11
Technical Data 10490 Effective June 2016 Up to 60 A Class H(K) 250 V and 600 V ferrule power distribution fuse blocks Catalog symbols: HM25060-_MW_ HM60030-_MW_ HM60060-_MW_ Description: Bussmann ® series 250 V and 600 V Class H(K) fuse block features power distribution capability. This patented design simplifies panel layouts and uses up to 57 percent less panel space. Additionally, it lowers inventory costs while reducing installation time and labor by an average of 33 percent. Furthermore, this design uses fewer wire connections, reducing watts loss and overall operating temperature of the panel. Features and benefits: Combination power distribution block and fuse block reduces wire connections and total panel components, using up to 57 percent less panel space and reducing installation time and labor by an average of 33 percent when compared with traditional fuse block/power distribution block solutions. Optional see-through cover enhances safety with IP20 finger-safe protection, lockout/tagout capability and open circuit indication. Available in 1-, 2- and 3-pole configurations to meet stocking requirements. To reduce inventory, assembly time and labor, modular single-pole blocks snap-together for tool-less assembly of multiple poles at point of use. DIN-Rail and panel mount versatility allows one product to be used for multiple applications without incurring additional inventory cost. 600 volt 30 and 60 amp modular blocks. 250 volt 60 amp modular blocks.

Transcript of Up to 60 A Class H(K) 250 V and 600 V ferrule power ... · Technical Data 10490 Effective June 2016...

Page 1: Up to 60 A Class H(K) 250 V and 600 V ferrule power ... · Technical Data 10490 Effective June 2016 Up to 60 A Class H(K) 250 V and 600 V ferrule power distribution fuse blocks Catalog

Technical Data 10490 Effective June 2016

Up to 60 A Class H(K) 250 V and 600 V ferrule power distribution fuse blocks

Catalog symbols:• HM25060-_MW_• HM60030-_MW_• HM60060-_MW_

Description:Bussmann® series 250 V and 600 V Class H(K) fuse block features power distribution capability.

This patented design simplifies panel layouts and uses up to 57 percent less panel space. Additionally, it lowers inventory costs while reducing installation time and labor by an average of 33 percent.

Furthermore, this design uses fewer wire connections, reducing watts loss and overall operating temperature of the panel.

Features and benefits:• Combination power distribution block and fuse

block reduces wire connections and total panel components, using up to 57 percent less panel space and reducing installation time and labor by an average of 33 percent when compared with traditional fuse block/power distribution block solutions.

• Optional see-through cover enhances safety with IP20 finger-safe protection, lockout/tagout capability and open circuit indication.

• Available in 1-, 2- and 3-pole configurations to meet stocking requirements.

• To reduce inventory, assembly time and labor, modular single-pole blocks snap-together for tool-less assembly of multiple poles at point of use.

• DIN-Rail and panel mount versatility allows one product to be used for multiple applications without incurring additional inventory cost.

600 volt 30 and 60 amp modular blocks.

250 volt 60 amp modular blocks.

Page 2: Up to 60 A Class H(K) 250 V and 600 V ferrule power ... · Technical Data 10490 Effective June 2016 Up to 60 A Class H(K) 250 V and 600 V ferrule power distribution fuse blocks Catalog

2

Technical Data 10490Effective June 2016

Class H(K) 250 V and 600 V ferrule power distribution fuse blocks

Eaton.com/bussmannseries

Specifications:Fuse class

• Class H(K)

Ratings

• Volts:• 250 V

• 600 V

• Amps: up to 60 A• Withstand ratign (SCCR): 10 kA Sym RMS

Agency information

• Blocks:• UL® Listed E14853 – IZLT

• CSA® Certified 47235 — 6225-01

• Covers: UL Listed UL E58836 – JDVS

• RoHS compliant

Poles

• 1-, 2-, 3-pole

Flammability ratings

• Blocks: UL 94V0, self-extinguishing• Covers: UL 94HB, self-extinguishing

Operating and storage temperature range

• Blocks: -40°C to +120°C• Covers:

• Non-indicating -40°C to +120°C

• Indicating -20°C to +90°C

Materials

• Base: Thermoplastic• Terminals: Tin-plated aluminum

Conductors

• 75°C Cu/Al (unless otherwise noted)

Accessories:• Optional IP20 finger-safe covers in indicating and non-indicating

versions. Order one for each pole.• Universal marker labels, Bussmann series catalog number

TM26CB.• DIN-Rail end stops, Bussmann series catalog numbers BRKT-ND

or BRKT-NDSCRW2.

Recommended fuses (order separately)

Description Volts Data sheet no.Basic protection general purpose NON 250 V 1030Basic protection general purpose NOS 600 V 1030

Recommended accessories for 30 and 60 amp blocks:

Description Catalog no.

DIN-Rail end stopsBRKT-NDBRKT-NDSCREW2

Marker labels TM26CB

Probe holes for easy testing without removing cover

DIN-Rail or panel mounting on each pole provides installation flexibility

Standard phase barriers for additional safety

Finger grips on cover for easy removal

Optional open fuse indication speeds troubleshooting

Lockout/tagout feature improves safety

Vent slots improve cooling (no fuse derating necessary)

Tool-less interlocking modular design for easy point-of-use assembly

Optional see-through, snap-on cover for easy visual inspection

Available two-port lineside lug for easy daisy-chain wiring configuration

Multi-port loadside lug for power distribution to multiple branch circuit connections

Marker label provision for easy circuit identificationPorts on power distribution lugs rated for

dual-wire application, increasing the number of branch circuit connections (see catalog number table for details)

Page 3: Up to 60 A Class H(K) 250 V and 600 V ferrule power ... · Technical Data 10490 Effective June 2016 Up to 60 A Class H(K) 250 V and 600 V ferrule power distribution fuse blocks Catalog

3

Technical Data 10490 Effective June 2016

Class H(K) 250 V and 600 V ferrule power distribution fuse blocks

Eaton.com/bussmannseries

Catalog numbers:

Catalog no.Optional covers*

Fuse amp range Poles

Lineside (conductors per port) Loadside (conductors per port)

ConductorsPorts/pole Torque AWG

N•m (lb-in) Conductors

Ports/pole

Torque AWG

N•m (lb-in)

250 Volts

HM25060-1MW12

N/A

35 - 60

1

Cu 2-14Al 2-8 2

2-4 5.6 (50)

Cu 2-14Al 2-8 1

2-3 5.6 (50)

HM25060-2MW12 2 6-10 4.5 (40) 4-6 5.1 (45)

HM25060-3MW12 3 12-14 1.7 (15)8 4.5 (40)

10-14 4.0 (35)

HM25060-1MW14

CVR-RH-25060CVRI-RH-25060**

1

Cu 2-14Al 2-8 1

2-3 5.6 (50)Cu (1) 8-14Cu (2) 12-14***Al (1) 8 StrAl (1) 10 Sol

4

Cu (1) 8 3.4 (30)

HM25060-2MW14 2 4-6 5.1 (45) Cu (1) 10-14 2.8 (25)

HM25060-3MW14 38 4.5 (40) Cu (2) 12-14 3.4 (30)

10-14 4.0 (35) Al (1) 8-10 3.4 (30)

HM25060-1MW24†

N/A

1

Cu 2-14Al 2-8 2

2-4 5.6 (50)Cu (1) 8-14Cu (2) 12-14***Al (1) 8 StrAl (1) 10 Sol

4

Cu (1) 8 3.4 (30)

HM25060-2MW24† 2 6-10 4.5 (40) Cu (1) 10-14 2.8 (25)

HM25060-3MW24† 3 12-14 1.7 (15)Cu (2) 12-14 3.4 (30)

Al (1) 8-10 3.4 (30)

600 Volts

HM60030-1MW14†

N/A up to 30

1

Cu 2-14Al 2-8 1

2-3 5.6 (50)Cu (1) 8-14Cu (2) 12-14***Al (1) 8 StrAl (1) 10 Sol

4

Cu (1) 8 3.4 (30)

HM60030-2MW14† 2 4-6 5.1 (45) Cu (1) 10-14 2.8 (25)

HM60030-3MW14† 38 4.5 (40) Cu (2) 12-14 3.4 (30)

10-14 4.0 (35) Al (1) 8-10 3.4 (30)

HM60060-1MW12

CVR-RH-60060CVRI-RH-60060** 35-60

1

Cu 2-14Al 2-8 2

2-4 5.6 (50)

Cu 2-14Al 2-8 1

2-3 5.6 (50)

HM60060-2MW12 2 6-10 4.5 (40) 4-6 5.1 (45)

HM60060-3MW12 3 12-14 1.7 (15)8 4.5 (40)

10-14 4.0 (35)

HM60060-1MW14 1

Cu 2-14Al 2-8 1

2-3 5.6 (50)Cu (1) 8-14Cu (2) 12-14***Al (1) 8 StrAl (1) 10 Sol

4

Cu (1) 8 3.4 (30)

HM60060-2MW14 2 4-6 5.1 (45) Cu (1) 10-14 2.8 (25)

HM60060-3MW14 38 4.5 (40) Cu (2) 12-14 3.4 (30)

10-14 4.0 (35) Al (1) 8-10 3.4 (30)

HM60060-1MW24† 1

Cu 2-14Al 2-8 2

2-4 5.6 (50)Cu (1) 8-14Cu (2) 12-14***Al (1) 8 StrAl (1) 10 Sol

4

Cu (1) 8 3.4 (30)

HM60060-2MW24† 2 6-10 4.5 (40) Cu (1) 10-14 2.8 (25)

HM60060-3MW24† 3 12-14 1.7 (15)Cu (2) 12-14 3.4 (30)

Al (1) 8-10 3.4 (30)

* Order one cover per pole.** With open fuse indication. 90 V minimum and closed circuit required for illumination.*** Dual wire rated lugs with same wire size and stranding.† Rated for use with 75°C/90°C Cu/Al conductors.

250 volt 60 amp modular blocks with single port lineside lugs and four port loadside lugs with optional finger-safe IP20 covers.

600 volt 30 amp modular blocks with single port lineside lugs and four port loadside lugs.

600 volt 60 amp modular blocks with single port lineside lugs and four port loadside lugs and optional finger-safe IP20 covers.

600 volt 60 amp modular blocks with dual port lineside lugs and four port loadside lugs.

Page 4: Up to 60 A Class H(K) 250 V and 600 V ferrule power ... · Technical Data 10490 Effective June 2016 Up to 60 A Class H(K) 250 V and 600 V ferrule power distribution fuse blocks Catalog

4

Technical Data 10490Effective June 2016

Class H(K) 250 V and 600 V ferrule power distribution fuse blocks

Eaton.com/bussmannseries

250 V, 60 A dimensions — mm (in)Catalog nos. HM25060-(poles)MW12 — Two ports in, one port out (covers not available)

15.8.62

15.7.62

2.8.11

107.94.25

108.14.26

35.41.40

7.0.28

7.2.28

34.01.34

69.42.73

34.01.34

103.44.07

31.71.25

18.7.74

12.7.50

21.3.84

34.01.34

Page 5: Up to 60 A Class H(K) 250 V and 600 V ferrule power ... · Technical Data 10490 Effective June 2016 Up to 60 A Class H(K) 250 V and 600 V ferrule power distribution fuse blocks Catalog

5

Technical Data 10490 Effective June 2016

Class H(K) 250 V and 600 V ferrule power distribution fuse blocks

Eaton.com/bussmannseries

250 V, 60 A dimensions — mm (in)Catalog nos. HM25060-(poles)MW14 — One port in, four ports out

107.94.25

109.64.32

15.8.62

15.8.62

2.8.11

35.41.40

R2.8.11

5.6.22

7.0.28

4.3.17

69.42.73

34.01.34

103.44.07

34.01.34

34.01.34

8.0.31

26.01.02

18.7.74

31.71.25

6.5.26

135 [5.3]

With optional cover, see catalog number table on page three for available versions

Page 6: Up to 60 A Class H(K) 250 V and 600 V ferrule power ... · Technical Data 10490 Effective June 2016 Up to 60 A Class H(K) 250 V and 600 V ferrule power distribution fuse blocks Catalog

6

Technical Data 10490Effective June 2016

Class H(K) 250 V and 600 V ferrule power distribution fuse blocks

Eaton.com/bussmannseries

250 V, 60 A dimensions — mm (in)Catalog nos. HM25060-(poles)MW24 — Two ports in, four ports out (covers not available)

109.94.33

107.94.25

15.8.62

15.7.62

2.8.11

35.41.40

69.42.73

7.0.28

4.3.17

R2.8.11

5.5.22

34.01.34

103.44.07

34.01.34

31.71.25

31.71.25

6.5.26

12.7.50

21.3.84

8.0.31

26.01.02

Page 7: Up to 60 A Class H(K) 250 V and 600 V ferrule power ... · Technical Data 10490 Effective June 2016 Up to 60 A Class H(K) 250 V and 600 V ferrule power distribution fuse blocks Catalog

7

Technical Data 10490 Effective June 2016

Class H(K) 250 V and 600 V ferrule power distribution fuse blocks

Eaton.com/bussmannseries

600 V, 30 A dimensions — mm (in)Catalog nos. HM60030-(poles)MW14 — One port in, four ports out (covers not available)

2.0.08

2.1.08

R3.5.14

7.1.28

4.0.16

158.86.25

160.06.30

30.81.21

39.81.56

39.81.56

60.22.37

29.41.16

29.41.16

89.63.53

15.5.61

28.51.12

6.5.26

29.41.16

21.4.84

45.81.80

Page 8: Up to 60 A Class H(K) 250 V and 600 V ferrule power ... · Technical Data 10490 Effective June 2016 Up to 60 A Class H(K) 250 V and 600 V ferrule power distribution fuse blocks Catalog

8

Technical Data 10490Effective June 2016

Class H(K) 250 V and 600 V ferrule power distribution fuse blocks

Eaton.com/bussmannseries

600 V, 60 A dimensions — mm (in)Catalog nos. HM60060-(poles)MW12 — Two ports in, one port out

41.01.61

8.4.33

3.4

.13

5.0.20

39.61.56

30.11.18

17.1.67

5.0.20

R3.6.14

38.31.51

7.1.28

38.31.51

77.93.07

12.7.50

25.61.01

53.52.11

38.31.51

116.14.57

202 [8.0]

With optional cover, see catalog number table on page three for available versions

Page 9: Up to 60 A Class H(K) 250 V and 600 V ferrule power ... · Technical Data 10490 Effective June 2016 Up to 60 A Class H(K) 250 V and 600 V ferrule power distribution fuse blocks Catalog

9

Technical Data 10490 Effective June 2016

Class H(K) 250 V and 600 V ferrule power distribution fuse blocks

Eaton.com/bussmannseries

600 V, 60 A dimensions — mm (in)Catalog nos. HM60060-(poles)MW14 — One port in, four ports out

41.01.61

8.4.33

3.4

.13

5.0.20

171.66.75

173.76.84

39.61.56

7.1.28

R3.6.14

38.31.51

38.31.51

77.93.07

116.14.57

17.1.67

30.11.18

6.5.26

38.31.51

30.31.19

65.52.58

53.52.11

202 [8.0]

With optional cover, see catalog number table on page three for available versions

Page 10: Up to 60 A Class H(K) 250 V and 600 V ferrule power ... · Technical Data 10490 Effective June 2016 Up to 60 A Class H(K) 250 V and 600 V ferrule power distribution fuse blocks Catalog

10

Technical Data 10490Effective June 2016

Class H(K) 250 V and 600 V ferrule power distribution fuse blocks

Eaton.com/bussmannseries

600 V, 60 A dimensions — mm (in)Catalog nos. HM60060-(poles)MW24 — Two ports in, four ports out

8.4.33

3.4.13

5.0.20

41.01.61

171.66.75

174.36.86

39.61.56

5.0.20

R3.6.14

7.1.28

38.31.51

77.93.07

38.31.51

116.14.57

30.11.18

30.11.18

6.5.26

12.7.50

25.61.01

8.0.31

30.31.19

53.52.11

202 [8.0]

With optional cover, see catalog number table on page three for available versions

Page 11: Up to 60 A Class H(K) 250 V and 600 V ferrule power ... · Technical Data 10490 Effective June 2016 Up to 60 A Class H(K) 250 V and 600 V ferrule power distribution fuse blocks Catalog

11 Eaton.com/bussmannseries

Class H(K) 250 V and 600 V ferrule power distribution fuse blocksTechnical Data 10490Effective June 2016

Eaton and Bussmann are valuable trademarks of Eaton in the U.S. and other countries. You are not permitted to use the Eaton trademarks without prior written consent of Eaton.

CSA is a registered trademark of the Canadian Standards Group.NEC is a registered trademark of the National Fire Protection Association, Inc.UL is a registered trademark of the Underwriters Laboratories, Inc.

Eaton1000 Eaton BoulevardCleveland, OH 44122Eaton.com

Bussmann Division114 Old State RoadEllisville, MO 63021United StatesEaton.com/bussmannseries

© 2016 EatonAll Rights ReservedPrinted in USAPublication No. 10490 — BU-MC16068June 2016

Follow us on social media to get the latest product and support information.

For Eaton’s Bussmann series product information, call 1-855-287-7626 or visit:Eaton.com/bussmannseries

The only controlled copy of this data sheet is the electronic read-only version located on the Eaton network drive. All other copies of this document are by definition uncontrolled. This bulletin is intended to clearly present comprehensive product data and provide technical information that will help the end user with design applications. Eaton reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of any products. Eaton also reserves the right to change or update, without notice, any technical information contained in this bulletin. Once a product has been selected, it should be tested by the user in all possible applications.

Installing/removing covers on 30 and 60 amp blocks

Install cover: Position cover over block and push straight down until it snaps/clicks into place.

Open cover: Using both outside handles, pull straight up.

A

Detail A

For larger conductors, trim center tabat notch as show in detail A.

Trim tabhere

Installing 30 and 60 amp blocks on a 35mm DIN-Rail

2. Rotate and push block down to deflect rail clips.

1. Place one edge of DIN-Rail into rail clips on one side of the block.

3. Continue rotating block until remaining rail clips snap into place.