University of British Columbia Drinking Water Quality Monitoring Report 2015 June 2016

Transcript of University of British Columbiaenergy.sites.olt.ubc.ca/files/2016/10/UBC-WQM-Report-2015.pdf ·...

Page 1: University of British Columbiaenergy.sites.olt.ubc.ca/files/2016/10/UBC-WQM-Report-2015.pdf · University of British Columbia Drinking Water Quality Monitoring Report 2015 May 2016

University of British Columbia

Drinking Water Quality Monitoring Report 2015

June 2016

Page 2: University of British Columbiaenergy.sites.olt.ubc.ca/files/2016/10/UBC-WQM-Report-2015.pdf · University of British Columbia Drinking Water Quality Monitoring Report 2015 May 2016

University of British Columbia Drinking Water Quality Monitoring Report 2015

i

Executive Summary

The University of British Columbia implemented a Drinking Water Quality Monitoring Program in 2002. This monitoring program was developed based on the standard program adopted by Metro Vancouver member municipalities, the Guidelines for Canadian Drinking Water Quality (GCDWQ), and input from the Vancouver Coastal Health Authority. With this approved monitoring program in place, UBC has collected and analyzed water quality data since 2002. This report outlines this program and its results for the year 2015. The implementation of the Drinking Water Quality Monitoring program was a significant commitment made by UBC to monitor the delivery of safe and high quality water. It generates valuable data for gaining understanding of UBC’s water distribution system and for evaluating the historic performance of the system in a reliable and systematic way. Most importantly, it allows for potential health hazards to be identified and consumer’s water concerns to be addressed. The sampling analysis results have demonstrated a satisfactory performance of the UBC distribution system. There were no recorded instances of E. coli detected in 2015. There were four recorded instances of total coliforms in 2015. Two events did not exceed the BC Drinking Water Protection limit for total coliforms. UBC employs a multibarrier approach to protect its water distribution system. In the two instances where total coliforms exceeded the BCDWPR, all other parameters tested were normal and no total coliforms were present in subsequent tests. Concerns in regards to total coliforms were addressed by an increased spot-flushing program. All water quality complaints were responded to by either the Facility Managers or UBC Energy and Water Services (EWS) and were resolved satisfactorily. In most cases issues were internal to a building and the distribution system’s quality was not a factor. A protocol for recording complaints is included in the UBC Emergency Response Plan – Water Utility. UBC is committed to delivery of water of the highest quality, and will continue to make the necessary investment to ensure its continued success.

Page 3: University of British Columbiaenergy.sites.olt.ubc.ca/files/2016/10/UBC-WQM-Report-2015.pdf · University of British Columbia Drinking Water Quality Monitoring Report 2015 May 2016

University of British Columbia Drinking Water Quality Monitoring Report 2015

ii

ACRONYMS

AO Aesthetic Objective (characteristics such as taste, colour, appearance, temperature that are not health related)

BCDWPR British Columbia Drinking Water Protection Regulation

CFU Colony Forming Units

DBP Disinfection By-product

E. coli Escherichia coli

EPA Environmental Protection Agency (USA)

ERP Emergency Response Plan

GCDWQ Guidelines for Canadian Drinking Water Quality

GVWD Greater Vancouver Water District

HAA Halo acetic Acid

HPC Heterotrophic Plate Count

IMAC Interim Maximum Acceptable Concentration

MAC Maximum Acceptable Concentration

MCL

MDA

Maximum Contaminant Level

Minimum Detectable Activity

MDL Method Detection Limit

MF Membrane Filter

mg/L Milligram per litre (0.001 g/L)

g/L Microgram per litre (0.000001 g/L)

mL Milliliter

mJ/cm2 Millijoule per centimeter squared

MPN Most Probable Number

MV

N/A

Metro Vancouver

Not Available

NTU Nephelometric Turbidity Unit

OG Operational Guidance value

pH Measure of acidity or basicity of water; pH 7 is neutral

ppb Parts per Billion (Equivalent of microgram per litre)

ppm Parts per Million (Equivalent of milligram per litre)

SCFP Seymour-Capilano Filtration Plant

THAA5 Total Halo acetic5 Acids

THM Trihalomethane

TOC Total Organic Carbon

TTHM Total Trihalomethane

UBC EWS University of British Columbia Energy and Water Services

UDF Unidirectional Flushing

UEL University Endowment Lands

VCH Vancouver Coastal Health

WHO World Health Organization

WQMRP Water Quality Monitoring and Reporting Plan

Page 4: University of British Columbiaenergy.sites.olt.ubc.ca/files/2016/10/UBC-WQM-Report-2015.pdf · University of British Columbia Drinking Water Quality Monitoring Report 2015 May 2016

University of British Columbia Drinking Water Quality Monitoring Report 2015

iii

Table of Contents

1.0 Introduction ............................................................................................................ 1

2.0 Water Distribution System ................................................................................ 2

3.0 Testing and Monitoring Program .................................................................... 6

3.1 Routine Monitoring ............................................................................................. 6

3.1.1 Sampling Parameters ............................................................................... 6

3.1.2 Sampling Locations ................................................................................ 10

3.1.3 Sampling Frequency .............................................................................. 10

3.2 Non-routine Monitoring .................................................................................... 11

4.0 Sample Analysis Results .................................................................................. 12

5.0 Summary ................................................................................................................ 18

References: ................................................................................................................... 19

APPENDICES: Appendix A Water Sampling Sites Site Map Appendix B Sample Analysis Results Appendix C Metro Vancouver and Municipal Response Procedure Appendix D Source Water Quality Summary Tables for Capilano,

Seymour and Coquitlam Reservoirs

Page 5: University of British Columbiaenergy.sites.olt.ubc.ca/files/2016/10/UBC-WQM-Report-2015.pdf · University of British Columbia Drinking Water Quality Monitoring Report 2015 May 2016

University of British Columbia Drinking Water Quality Monitoring Report 2015

May 2016 Page 1

1.0 Introduction The purpose of this report is to provide a summary of the Drinking Water Quality Monitoring Program during 2015 for the UBC Utilities water distribution system. During 2015 the provision of drinking water was governed by the Drinking Water Protection Regulation (pursuant to the Drinking Water Protection Act). This regulation requires suppliers of drinking water in BC to:

Develop a process to notify the Drinking Water Officer (DWO) of situations or conditions that render or could render the water unfit to drink;

Implement a plan for collecting, shipping and analyzing water samples in compliance with the direction set by the DWO;

Implement a plan for reporting monitoring results to the DWO and to water

users including the preparation of an annual report;

Implement an emergency response and contingency plan. UBC EWS monitors the water quality in the UBC distribution system on a weekly basis in accordance with their Drinking Water Quality Monitoring Program. Appendix B includes a graphic summary of test results for 2015. This document includes a brief introduction to UBC’s water distribution system and its drinking water monitoring and testing program. The remaining parts of this document summarize the results and analysis of water samples collected in 2015 and evaluates the distribution system’s performance in delivering safe and quality drinking water.

Page 6: University of British Columbiaenergy.sites.olt.ubc.ca/files/2016/10/UBC-WQM-Report-2015.pdf · University of British Columbia Drinking Water Quality Monitoring Report 2015 May 2016

University of British Columbia Drinking Water Quality Monitoring Report 2015

May 2016 Page 2

2.0 Water Distribution System UBC receives bulk treated water from Metro Vancouver’s Water District (GVWD) through two supply points via the University Endowment Lands. Water is then supplied to UBC’s customers through its distribution system. UBC has developed a comprehensive operations and maintenance (O&M) program for the water distribution system to ensure the highest quality water is delivered at sufficient quantity and pressure to its customers. The O&M program in 2015 included a water quality testing program and flushing of problem areas; system pressure controls were adjusted to improve flow and chlorination to some areas, as well as installation of new main line pipes and appurtenances in a number of areas. 1. UBC Source Water: UBC’s drinking water comes from three northern mountainous

watersheds managed by Metro Vancouver. The watersheds are protected from urban development, closed to public access and managed as assets of the highest importance to the region. The water in these watersheds originates from rainfall and snow melt and is collected in the three reservoirs: Capilano, Seymour and Coquitlam. Metro Vancouver is responsible for all treatment of source water to meet Health Canada’s Guidelines for Drinking Water Quality. Metro Vancouver also tests and analyses water in their transmission piping and reservoir network to ensure delivery of quality potable water to its member municipalities. Water treatment by disinfection destroys disease-causing pathogenic organisms and secondary chlorine disinfection of water downstream helps to prevent bacterial regrowth in the distribution systems. UBC does not further treat the water. For more information see: http://www.metrovancouver.org/services/water/quality-facilities/facilities-processes/treatment-process/Pages/default.aspx. See appendix D for summary tables of source water quality for Capilano, Seymour and Coquitlam reservoirs.

2. Capital Improvements to the system are made as areas are redeveloped or new

development takes place. Old water mains are replaced, enlarged and or extended, dead ends eliminated and new hydrants, valves and services installed.

a) Centre for Brain Health

As part of the ongoing development of the Centre for Brain Health a new service connection was installed which consisted of 47m of 150mm DI pipe.

b) West Mall at Kenny Building

The student housing expansion project at Ponderosa required upsizing of distribution water piping to meet the increased demands. 91m of 250mm DI pipe was installed to replace the existing 200mm CI pipe on West Mall. Included in the works was replacement of hydrants and new valving.

Page 7: University of British Columbiaenergy.sites.olt.ubc.ca/files/2016/10/UBC-WQM-Report-2015.pdf · University of British Columbia Drinking Water Quality Monitoring Report 2015 May 2016

University of British Columbia Drinking Water Quality Monitoring Report 2015

May 2016 Page 3

c) Wesbrook Mall Switchover On Wesbrook mall near University Blvd., 92m of 150mm DI piping was installed. The existing services were switched over from the existing CI supply main to the new main and the CI main was abandoned.

d) Purdy Pavillion

As part of the Health Precinct improvement project the water distribution system was looped from Wesbrook Mall to Health Sciences Mall. The loop consisted of 164m of 200mm DI piping and 58m of 300mm DI piping in with new hydrants and valves. The loop will result in increased fire flow in the area and water quality will be easier to maintain.

e) War memorial Gym (site B) At the War Memorial Gym (site B) the existing CI service was replaced with a DI service piping. In addition as crews were mobilized on site, the piping in area was reconfigured for future development. Altogether 8m of 150 mm DI, 87 m of 200mm DI pipe and 49m of 250mm DI pipe was installed and the existing CI pipe on Wesbrook Mall was abandoned.

f) East Mall at Hebb Building On East Mall opposite the Hebb Building, 141m of 250mm DI pipe was installed. The DI pipe replaced the existing 200mm CI pipe. The project accomplished both increased fire flow in the area but also improved UBC’s efforts to maintain good water quality.

g) North Parkade Switchover The service to the North Parkade was switched over from the existing CI pipe to a previously installed DI main the CI pipe was then abandoned

h) Public Safety Building At the Public Safety Building on Wesbrook Mall, 47m of 200mm DI pipe was installed to replace the existing CI pipe in the area.

i) Okanagan House At Okanagan House a broken water main prompted emergency replacement of 27m of 200 mm CI pipe with 200mm DI piping.

j) UBC Athletic Sports Field This large distribution system installation is comprised of 478m of 200mm DI pipe, 81m of 150mm DI pipe, 138m of 100mm DI pipe and 38m of 75mm PVC pipe. The project replaced the existing CI distribution piping, supplied services to two new buildings and an irrigation system network.

k) Acadia/Salal Daycare In order to solve a low flow problem in the area of Salal Daycare with resulting water quality concerns, the domestic service was replaced and switched to a DI water main.

Page 8: University of British Columbiaenergy.sites.olt.ubc.ca/files/2016/10/UBC-WQM-Report-2015.pdf · University of British Columbia Drinking Water Quality Monitoring Report 2015 May 2016

University of British Columbia Drinking Water Quality Monitoring Report 2015

May 2016 Page 4

3. UBC Emergency Response Plan – Water Utility The UBC ERP-WU includes different possible emergency scenarios, protocols, procedures and staff responsibilities in emergencies. Revisions to the plan in 2015\2016 included contact name updates and distribution system changes. In addition to these scenarios, if an extraordinary turbidity event occurs, the Metro Vancouver and Municipal Response Procedure will be followed (see Appendix C of the ERP).

4. Cross Connection Control Program - The consolidation of the different programs into UBC EWS’ Cross Connection Control Program occurred in 2007 with a full survey in 2008. At that time a computerized database and tracking system was implemented and 838 devices are now tracked. EWS also oversees the UBC Academic and Hospital CCC Programs. The number of assemblies registered increased by 4% in 2015. The program incorporates testing and annual certification of devices as well as site inspections. EWS also provides advice and oversight on new installations at existing, non-compliant facilities. A full survey of all facilities will be planned for 2015/16. Below is a table of the history of the program.

Year Total Devices Devices Tested Outstanding % Compliance

2008 158 155 3 98%

2009 290 227 63 78%

2010 384 315 69 82%

2011 445 372 73 84%

2012 626 569 57 91%

2013 741 677 64 91%

2014 803 693 110 86%

2015 838 776 62 93% Below is a summary of average annual water purchased by UBC over the last 10 years. After a number of water conservation initiatives in the early part of the decade, overall consumption at UBC is on the rise again due to increased population; mainly at the South Campus neighbourhood area.

Page 9: University of British Columbiaenergy.sites.olt.ubc.ca/files/2016/10/UBC-WQM-Report-2015.pdf · University of British Columbia Drinking Water Quality Monitoring Report 2015 May 2016

University of British Columbia Drinking Water Quality Monitoring Report 2015

May 2016 Page 5

Page 10: University of British Columbiaenergy.sites.olt.ubc.ca/files/2016/10/UBC-WQM-Report-2015.pdf · University of British Columbia Drinking Water Quality Monitoring Report 2015 May 2016

University of British Columbia Drinking Water Quality Monitoring Report 2015

May 2016 Page 6

3.0 Testing and Monitoring Program Drinking water quality is a function of source water quality, water treatment, and water quality changes after treatment. As a result, monitoring of drinking water quality consists of three components: source water monitoring, monitoring after treatment, and monitoring in the distribution system. While Metro Vancouver’s Water District carries out testing of water at the source and testing after treatment, UBC’s Drinking Water Quality Monitoring Program is focused on monitoring the water quality within its own water distribution system. The monitoring and testing program consists of routine monitoring, for obtaining an accurate overview of water quality within the distribution system, and non-routine monitoring, for handling complaint and emergency situations. Monitoring includes two components: collection of the sample and laboratory analysis of the sample. 3.1 Routine Monitoring The collection of water samples was completed as part of an annual contract with CARO Environmental Services from sampling sites within UBC on a regular basis. These water samples were then forwarded to laboratories for analysis. The collection, transportation and analysis of samples were performed in accordance with the Standard Methods for the Examination of Water and Wastewater 21st Edition. All analyses were conducted by laboratories that are approved by Canadian Association of Environmental Analytical Laboratories or an equivalent certification program for the other tests performed. All testing parameters except vinyl chloride were analyzed by the laboratories of Metro Vancouver. Analysis of vinyl chloride, a volatile organic compound, was tested by the laboratory of CARO Analytical Services. 3.1.1 Sampling Parameters The parameters that were analyzed are summarized in the following table:

Table 1. Sampling Parameters

PARAMETERS

Microbiological Total Coliforms, E. coli, Heterotrophic Plate Count (HPC)

Chemical and Physical Turbidity, Temperature, Free Chlorine Residual, pH, Aluminium, Copper, Iron, Lead, Zinc, Halo acetic Acids (HAAs), Trihalomethanes (THMs), Vinyl Chloride Odour/Taste (complaint basis)

Radiological None

Page 11: University of British Columbiaenergy.sites.olt.ubc.ca/files/2016/10/UBC-WQM-Report-2015.pdf · University of British Columbia Drinking Water Quality Monitoring Report 2015 May 2016

University of British Columbia Drinking Water Quality Monitoring Report 2015

May 2016 Page 7

Guidelines for chemical and physical parameters are: 1. (MAC) – Health based and listed as a maximum acceptable concentration. 2. (AO) – Based on aesthetic considerations and listed as an aesthetic objective; or 3. (OG) – Established based on operational considerations and listed as an operational

guidance value. The significance of the parameters of most relevance is briefly discussed below. Further details regarding the parameters listed in the above table can be found by accessing the supporting documents of the GCDWQ through the following web site, http://www.hc-sc.gc.ca/ewh-semt/water-eau/drink-potab/guide/index_e.html, or by contacting Health Canada at (613) 957-2991. Total and E. coli Coliforms One of the primary concerns in water quality is the growth of coliform bacteria. The presence of total coliforms indicates that treatment is inadequate or that the distribution system is experiencing regrowth of the bacteria in distribution system biofilms or intrusion of untreated water. Exceedances of the distribution system goal should be investigated. The presence of E. coli indicates a possibility of fecal contamination. Escherichia coli (E. coli) is used as an indicator of the microbiological safety of drinking water; if detected, enteric pathogens may also be present. Heterotrophic Plate Counts Heterotrophic Plate Counts (HPC) are used to estimate the general bacterial population. Historically the HPC test has been used to indicate when conditions in the distribution system are favourable for the growth of bacteria. It was felt that if the growth of heterotrophs is controlled, growth of coliforms should also be controlled. However there is uncertainty as to the significance of the HPC test. The Canadian Drinking Water Quality Guidelines removed HPCs as an indicator of drinking water quality. Monitoring for HPCs has been maintained to assist in understanding changes in operational conditions to the system. Unlike other indicators such as Escherichia coli or total coliforms, low concentrations of HPC organisms will still be present after drinking water treatment. In distribution systems HPC provides some indication of stagnation, tuberculation, chlorine residual, and available nutrients for bacterial growth. High HPC measurements have not been found to correlate with illness incidence and no outbreaks have been directly linked to elevated concentrations of HPC flora in tap water; however a sudden rise in HPC measurements collected from a site that has traditionally had low counts is an indicator that something has changed in the system and should be investigated. UBC uses the historical figure of 500 CFU/100mL as a baseline measurement that will trigger investigation into possible changes in the distribution system.

Page 12: University of British Columbiaenergy.sites.olt.ubc.ca/files/2016/10/UBC-WQM-Report-2015.pdf · University of British Columbia Drinking Water Quality Monitoring Report 2015 May 2016

University of British Columbia Drinking Water Quality Monitoring Report 2015

May 2016 Page 8

Free Chlorine Residual Free chlorine residual provides a good indication of water quality within the distribution system. Low chlorine residual may indicate deteriorating water quality as a result of bacterial regrowth or stagnant water. Maintaining a free chlorine residual of at least 0.2 mg/L in the distribution system has been observed to reduce the level of HPC. Turbidity Turbidity in water is caused by suspended matter, such as clay, slit, organic and inorganic matter. Controlling turbidity is important for both health and aesthetic reasons. Bacteria, viruses and protozoa can adhere to suspended particles in turbid water and thus be protected from disinfection. Also, excessive turbidity detracts from the appearance of treated water and has often been associated with unacceptable tastes and odours.

Disinfection Byproducts

Halo acetic acids (HAAs) and Trihalomethanes (THMs) are disinfection byproducts and are formed in drinking water when chlorine reacts with organic matter that is naturally present in raw water supplies. Research suggests that HAAs have an adverse impact on human health and may possibly be carcinogenic. The most common THM is chloroform. Chloroform is also classified as being possibly carcinogenic to humans. There is a tradeoff between reducing risk from disinfection byproducts and having enough chlorine to provide water safe from bacteria and parasites. Copper Copper is used extensively in plumbing for domestic water systems. Although copper is frequently found in surface water, distributed water contains considerably more copper than the original water supply because of the dissolution of copper from copper piping. Copper can stain laundry and plumbing fixtures and cause an undesirable bitter taste in water. Copper intake at extremely high doses can result in adverse health effects. Iron Iron is naturally present in food and drinking water. However, there is no evidence to indicate that concentrations of iron commonly found in food or water constitute any hazard to human health. Iron can stain laundry and plumbing fixtures and cause undesirable tastes in beverages. The precipitation of excessive iron imparts an objectionable reddish-brown color to the water. Iron may also promote the growth of certain microorganisms, which can lead to the deposition of a slimy coat in piping. Lead Lead was used in drinking water plumbing and as solder in distribution systems. Older distribution systems may also be made from lead pipe. Lead is present in tap water as a result of dissolution from natural sources or from household plumbing systems. Lead is a cumulative general poison and has been classified as being potentially carcinogenic to humans. Fetuses, infants, young children and pregnant women are most susceptible to adverse health effects. In order to minimize exposure to lead introduced into drinking water from plumbing systems, it is recommended that only cold water be used, after an

Page 13: University of British Columbiaenergy.sites.olt.ubc.ca/files/2016/10/UBC-WQM-Report-2015.pdf · University of British Columbia Drinking Water Quality Monitoring Report 2015 May 2016

University of British Columbia Drinking Water Quality Monitoring Report 2015

May 2016 Page 9

appropriate period of flushing to rid the system of standing water, for sampling, drinking, beverage preparation and cooking. Vinyl Chloride The presence of vinyl chloride in potable water is associated mainly with the use of polyvinyl chloride (PVC) water pipes manufactured with incompletely polymerized vinyl chloride monomer. Acute exposure or chronic inhalation exposure results in a variety of adverse effects in humans. Sufficient evidence has accumulated to implicate vinyl chloride as a human and animal carcinogen. Zinc Although zinc is present in surface waters at low concentrations, levels in tap water can be considerably higher due to the use of zinc in plumbing materials. Water containing zinc in excess concentrations has an undesirable astringent taste and may develop a greasy film upon boiling. Long-term ingestion of zinc in quantities considerably in excess of the daily requirement has not resulted in adverse effects. pH pH is controlled in water to minimize corrosion and incrustation. Corrosion may increase below 6.5 and incrustation and scaling may increase above pH 8.5. There is also a decrease in the efficiency of chlorine disinfection processes with increasing pH levels. In addition, through discussions with Metro Vancouver, it was noted that pH assists in the interpretation of sampling results for disinfection by-products, and thus should be sampled at the same time.

Page 14: University of British Columbiaenergy.sites.olt.ubc.ca/files/2016/10/UBC-WQM-Report-2015.pdf · University of British Columbia Drinking Water Quality Monitoring Report 2015 May 2016

University of British Columbia Drinking Water Quality Monitoring Report 2015

May 2016 Page 10

3.1.2 Sampling Locations Sampling locations are distributed in different areas within UBC so as to obtain an accurate overview of water quality of the distribution system. The 16 locations were strategically selected based on land use and system configuration. They include residential area supply, high-density residential area supply, institutional area supply, and water source supply. These locations are illustrated in Figure 1 in Appendix A. To date 15 of the stations are installed and operational with the remaining station to be installed with proposed system upgrades.

Site

Location Flow Category

Description

WQB7-001 Iona Drive at Theology Mall

Low VST Residences

WQC3-002 NW Marine east of West Mall

Low Supply to Residences

WQD2-003 Place Vanier west of Lower Mall

Low Place Vanier Residences

WQH3A-004 Lower Mall south of Agronomy Rd.

Low Totem Park Residences

WQH3B-005 Tap in Totem Park Service Connection

WQL3-006 Stadium Rd. east of Main Mall

Medium Thunderbird Stadium

WQJ5-007 Thunderbird Crescent Low Thunderbird Residences

WQG6-008 Health Sciences Mall Medium Hospital Supply

WQF7B-009 Wesbrook Mall south of Univ. Blvd.

Medium Hospital Supply

WQF7A-010 (future) Univ. Blvd. At Wesbrook Mall

Source Main Pump Station Supply

WQJ10-011 Fairview Place west of Acadia Rd.

Medium Acadia Residences and PVC in area

WQM8-012 Hampton Place Low Hampton Place Residences

WQN9-013 16th Ave. at UBC border Source Low Pressure Feed

WQQ6-014 Animal Science Low Animal Science Area

WQQ7-015 Wesbrook Mall at BC Research

Medium Supply to BC Research and Triumph

WQT7-016 Nurseries Road at Triumf

Dead End Supply to Environment Services

3.1.3 Sampling Frequency UBC, as a purveyor of drinking water to a maximum population of approximately 50,000-60,000 is required to test at least 40 samples per 30 day period as outlined in the Drinking Water Protection Regulation. In general, parameters that have greater effects on health were sampled and analyzed more often than those that only affect the

Page 15: University of British Columbiaenergy.sites.olt.ubc.ca/files/2016/10/UBC-WQM-Report-2015.pdf · University of British Columbia Drinking Water Quality Monitoring Report 2015 May 2016

University of British Columbia Drinking Water Quality Monitoring Report 2015

May 2016 Page 11

aesthetic quality. The sampling frequency of different parameters from different sampling locations is summarized in Table 3. In 2016 sampling frequency has been increased to 50 samples per 30 day period to compensate for the population increase as UBC continues to grow.

Table 3. Sampling Frequency

Frequency: WEEKLY QUARTERLY SEMI-ANNUALLY

Parameters: Total coliforms E. coli HPCs Free chlorine residual Turbidity Temperature

Halo acetic Acids pH Temperature Trihalomethanes

Copper Zinc Lead Iron Temperature Vinyl chloride

Site Category: Various Campus Areas Various Campus Areas Tap in Building and Campus Areas

3.2 Non-routine Monitoring CARO Environmental Services was on-call for monitoring water quality complaints and emergency situations. The UBC Emergency Response Plan – Water Utility includes a protocol for recording consumer complaints to ensure efficient response and follow up. In any emergency situation the procedures outlined in the UBC Emergency Response Plan were followed. Water Quality Complaints Four water quality complaints were received by UBC in 2015.

1. After an investigation the first instance was determined to be an internal building problem and the owner was directed to call a testing lab if the problem continued.

2. The second complaint involved an internal renovation causing water quality concerns for residents. UBC flushed mains in area as a precaution. The contractor was instructed to flush the building distribution system.

3. The third complaint involved a daycare service connected to an aging CI pipe which also had low flow characteristics. The problem was resolved by reconnecting the service to a DI main.

4. The last case was the result of routine hydrant maintenance resulting in a temporary discolouration of the water supply to a library.

In each case local distribution mains were flushed and water retested to confirm good water quality.

Page 16: University of British Columbiaenergy.sites.olt.ubc.ca/files/2016/10/UBC-WQM-Report-2015.pdf · University of British Columbia Drinking Water Quality Monitoring Report 2015 May 2016

University of British Columbia Drinking Water Quality Monitoring Report 2015

May 2016 Page 12

4.0 Sample Analysis Results A total of 603 samples were taken from the water distribution system during 2015. Most samples did not exceed the limits set out in the BCDWPR or the GCDWQ. The sample analysis results are summarized in Table 4 below, and some of the parameters worth noting are discussed in this section. It should be noted that the limits contained within the GCDWQ are recommendations only and representative of best practices. These can become requirements if the Drinking Water Officer places a condition on the Operating Permit for UBC. At present there are no such conditions placed on UBC.

Table 4. Summary of Analysis Results *

Sample StationSamples

Taken

Positive

Coliform

Tests

Positive E.

coli tests

Low Average High Low Average High Low Average High

WQB7-001 (UBC-001) 52 2 16.1 150 0.3 0.6 1.3 0.1 0.2 1.1 None None

WQC3-002 (UBC-002) 51 2 7.3 30 0.4 0.5 1.1 0.1 0.2 2.0 None None

WQD2-003 (UBC-003) 52 2 8.5 32 0.4 0.5 1.1 0.1 0.3 1.4 1 None

WQH3A-004 (UBC-004) 52 2 9.7 28 0.5 0.6 1.0 0.1 0.3 3.2 1 None

WQL3-006 (UBC-006) 26 2 2.0 2 0.5 0.6 0.8 0.1 0.2 0.4 None None

WQJ5-007 (UBC-007) 26 4 32.7 80 0.4 0.6 0.8 0.1 0.2 0.5 None None

WQG6-008 (UBC-008) 31 2 26.3 80 0.4 0.6 0.4 0.1 0.3 2.7 None None

WQF713-009 (UBC-009) 51 2 5.5 30 0.3 0.6 1.3 0.1 0.2 3.0 None None

WQJ10-011 (UBC-011) 52 2 3.6 8 0.4 0.6 1.4 0.1 0.2 1.0 None None

WQM8-012 (UBC-012) 30 2 30.0 12 0.4 0.7 1.3 0.1 0.2 0.4 None None

WQN9-013 (UBC-013) 52 2 4.3 14 0.4 0.7 0.9 0.1 0.2 0.6 None None

WQQ6-014 (UBC-014) 50 2 5.8 40 0.4 0.6 1.2 0.1 0.3 3.1 1 None

WQQ7-015 (UBC-015) 52 2 20.2 110 0.4 0.6 0.9 0.1 0.2 1.2 1 None

WQT7-016 (UBC-016) 26 2 8.8 64 0.4 0.6 1.1 0.1 0.5 4.1 None None

UBC Average 12.9 0.6 0.2

UBC Total 603 4 0

< 10 < 1

GCDWQ < 500 > 0.2 < 1

BCDWPR

Standard Limits

HPC CFU/ml Free Chlorine Residual mg/L Turbidity NTU

*For reporting averages, test results below the detectable limit are given a value of 0. Coliform The BCDWPR requires that (1) no sample should contain Escherichia coli (E. coli) and that (2) no sample should contain more than 10 total coliform per 100 millilitre and not more than 10% of samples from the distribution system in a given calendar month should show the presence of total coliform bacteria. Of the 603 samples analyzed for microbiological criteria in 2015, no E. coli was detected. There were four recorded instances of total coliforms during 2015. Although the presence of total coliforms (in the absence of E.coli) is of no immediate public health significance, total coliform detection above 10 per 100mg/l as regulated by the BCDWPR triggers an immediate investigation and corrective actions taken in order to maintain the overall bacteriological quality of the water.

Page 17: University of British Columbiaenergy.sites.olt.ubc.ca/files/2016/10/UBC-WQM-Report-2015.pdf · University of British Columbia Drinking Water Quality Monitoring Report 2015 May 2016

University of British Columbia Drinking Water Quality Monitoring Report 2015

May 2016 Page 13

UBC uses a multi-barrier approach to maintaining good water quality using a number of indicators such as free chlorine, HPC, turbidity, pH, temperature and total coliforms. Abnormal changes to any of these parameters are considered as indication that something has changed in the distribution system and an investigation is conducted to determine the cause. In these instances all other parameters appeared to be normal. Although only two of the four samples exceeded the total coliform limit set by the BCDWPR, UBC immediately carried out spot flushing and retested all four stations. The lab results after retesting proved negative and subsequent samples have shown no presence of total coliforms and indicate water of good quality. The presence of total coliform bacteria in water in the distribution system in isolated non-consecutive tests normally indicates bacterial re-growth in the system. Re-growth is a phenomenon seen in many water distribution systems even though there has been no loss of primary treatment or loss of system integrity, which might result in contamination. Total coliform bacteria are frequently detected in distribution water samples, particularly those samples with low free chlorine residuals. In Metro Vancouver and member water utilities, re-growth typically occurs when the water warms up in the late summer and early fall. During this period it is critical to maintain adequate chlorine residual to as many areas as possible. As UBC has no re-chlorination stations, this is accomplished through spot flushing to draw in fresh water to sensitive areas identified by monitoring chlorine residuals. The maintenance of chlorine residual is dependent on a number of factors:

The amount of chlorine in the source water (from Metro Vancouver) The chlorine demand in the water

- Amount of organics - Water temperature

Residence time of the water in the distribution system. Heterotrophic Plate Count, HPC * Elevated levels of HPC’s can be used as an indicator of possible changes in the conditions in a water distribution system. In 2015, there were no higher than normal HPC readings recorded. HPC has been removed as an indicator of drinking water quality, by the GCDWQ, however, based on historical data, UBC has retained a figure of 500 CFU/100 ml as a baseline measurement in order to assess possible changes in the distribution system.

* see explanation for HPC (p.6) Turbidity The GCDWQ guidelines recommend that water entering the distribution system have turbidity levels of 1.0 Nephelometric Turbidity Unit (NTU) or less. However, UBC’s monitoring program tests only water within its distribution system. Although turbidity measurements cannot automatically be used to interpret the safety of water in the distribution system, a turbidity level below 1.0 NTU has been identified as one potential

Page 18: University of British Columbiaenergy.sites.olt.ubc.ca/files/2016/10/UBC-WQM-Report-2015.pdf · University of British Columbia Drinking Water Quality Monitoring Report 2015 May 2016

University of British Columbia Drinking Water Quality Monitoring Report 2015

May 2016 Page 14

goal for utilities to use for routine monitoring and operations. Localized turbidity events can be caused by water main flushing or higher velocity draws from the distribution system as a result of construction, firefighting, water main breaks, etc. In 2015 the average turbidity at UBC was 0.31. Turbidity levels above the target of 1.0 NTU were briefly observed on eleven occasions; however these events showed no signs of bacteriological impairment and were not repeated at the next test. Free Chlorine Residual Free chlorine residual levels tested in UBC’s distribution system were within the recommended levels. In 2015 no sampling station within UBC fell below the average free chlorine residual concentration target of 0.2 mg/L. As with HPC levels, low chlorine residual is a warning sign and not an indication of bacteriological impairment. Chlorine levels are regulated by Metro Vancouver, and at UBC’s request has increased chlorine levels to compensate for the longer transmission distance to the campus. With the launch of the Seymour/Capilano Filtration Plant recently, and improvements to UBC’s distribution system, there have been no low chlorine events in the last year. Disinfection By-products The source water at WQN9-013 was tested four times for disinfection by-product concentration. See the table below for analysis results.

Extra

Bro

mo

dic

hlo

rom

eth

ane

Bro

mo

form

Ch

loro

dib

rom

om

eth

ane

Ch

loro

form

To

tal T

rih

alo

met

han

es

Total THM

Quarterly

Average

(Guileline Limit

100ppb/mL) Dib

rom

oac

etic

Aci

d

Dic

hlo

roac

etic

Aci

d

Mo

no

bro

mo

acet

ic A

cid

Mo

no

chlo

roac

etic

Aci

d

Tri

chlo

roac

etic

Aci

d

To

tal H

alo

acet

ic A

cid

Total HAA

Quarterly

Average

(Guileline Limit

80ppb/mL) pH

un

its

PH

UBC-013 2015-02-17 00:00 <1 <1 <1 23 23.1 23 <0.5 12 <1 4 12.8 29.2 29 7.3

UBC-013 2015-05-19 00:00 <1 <1 <1 23 23.1 23 <0.5 9 <1 4 9.7 23.3 26 7.5

UBC-013 2015-08-18 00:00 2 <1 <1 23 24.3 24 <0.5 8 <1 5 6.4 21.4 25 5.9

UBC-013 2015-11-24 00:00 <1 <1 <1 18 20.1 23 <0.5 9 <1 3 7.4 19.9 23 7.3

23 26 7.0

Average Average Average

Sample Date Sampled

THM (ppb) HAA (ppb)

The annual average THM concentration of 23 ppb (0.02 mg/L) is well below the GCDWQ recommended maximum of 100 ppb (0.1 mg/L). The Canadian guideline level for the Halo acetic group (HAA) is 80 ppb (0.08 mg/L.). The average HAA concentration of 26 ppb is 54 ppb below the recommended maximum and is measured at the source water from Metro Vancouver as it enters UBC’s distribution system. Some studies have indicated that as water approaches the extremities of the distribution system, HAA levels decrease as residence times increase, especially during summer months as temperature levels rise.

Vinyl Chloride Vinyl chloride concentration was tested twice during 2015. The tests were both below the detection limit of 1 ppb, which is below the GCDWQ recommended 2 ppb (0.002mg/L).

Page 19: University of British Columbiaenergy.sites.olt.ubc.ca/files/2016/10/UBC-WQM-Report-2015.pdf · University of British Columbia Drinking Water Quality Monitoring Report 2015 May 2016

University of British Columbia Drinking Water Quality Monitoring Report 2015

May 2016 Page 15

pH The Aesthetic objective for pH set out by GCDWQ is 6.5 - 8.5. Grab samples taken from WQN9-013, tested for pH at 5.9 – 7.5 throughout 2015. Since pH is largely determined by source water characteristics, water entering from Metro Vancouver controls its magnitude. Higher than normal pH levels were discovered in a localized area in the South Campus. With regular flushing normal readings are maintained. The pH readings were not high enough to be a health concern nor is the area affected in a residential neighborhood. Historical low pH problems at UBC have improved with the construction of the new water filtration plant at the Seymour watershed. The addition of Ash Soda at that plant maintains the pH levels above 6.5. It was concluded that the high pH events at the “dead end” location on campus were the result of undissolved Ash Soda carried within the water mains eventually dissolving over time. A weekly testing program at this location is ongoing. Should an increased pH be found, the area is flushed and retested until pH is reduced.

Metals Three sample locations were tested a total of six times for metals during 2015. (See table)

Sample Name Date Sampled

Aluminum Total

µg/L

Copper Total

µg/L

Iron Total

µg/L

Lead Total

µg/L

Zinc Total

µg/L

UBC-003 5/5/2015 11:51 26 7.5 31 <0.5 <3

UBC-003 10/20/2015 11:20 19 9.7 36 <0.5 <3

UBC-005 5/5/2015 11:35 25 46.3 21 <0.5 3.0

UBC-005 10/20/2015 11:10 43 25.6 23 <0.5 <3

UBC-008 5/5/2015 10:57 25 2.1 16 <0.5 <3

UBC-008 10/20/2015 10:40 22 3.7 8 0.5 <3

CGDWQ Health Guidelines N/A N/A N/A 10 N/A

CGDWQ Aesthetic Objective N/A 1000 300 N/A 5000

CGDWQ Operational Guidance Values 200 N/A N/A N/A N/A

All metal levels fall below the recommended guidelines outlined in the GCDWQ.

Page 20: University of British Columbiaenergy.sites.olt.ubc.ca/files/2016/10/UBC-WQM-Report-2015.pdf · University of British Columbia Drinking Water Quality Monitoring Report 2015 May 2016

University of British Columbia Drinking Water Quality Monitoring Report 2015

May 2016 Page 16

Page 21: University of British Columbiaenergy.sites.olt.ubc.ca/files/2016/10/UBC-WQM-Report-2015.pdf · University of British Columbia Drinking Water Quality Monitoring Report 2015 May 2016

University of British Columbia Drinking Water Quality Monitoring Report 2015

May 2016 Page 17

Page 22: University of British Columbiaenergy.sites.olt.ubc.ca/files/2016/10/UBC-WQM-Report-2015.pdf · University of British Columbia Drinking Water Quality Monitoring Report 2015 May 2016

University of British Columbia Drinking Water Quality Monitoring Report 2015

May 2016 Page 18

5.0 Summary The University of British Columbia implemented a Drinking Water Quality Monitoring Program in 2002. This monitoring program was developed based on the standard program adopted by Metro Vancouver member municipalities, the Guidelines for Canadian Drinking Water Quality (GCDWQ), and input from the Vancouver Coastal Health Authority. With this approved monitoring program in place, UBC has collected and analyzed water quality data since 2002. The implementation of the Drinking Water Quality Monitoring program was a significant commitment made by UBC to deliver to consumers safe and good quality water. It generates valuable data for gaining understanding of UBC’s water distribution system and for evaluating the past performance of the system in a reliable and systematic way. Most importantly, it allows for potential health hazards to be identified and consumer’s water concerns to be addressed. The sampling analysis results have demonstrated a satisfactory performance of the UBC distribution system. There were no recorded instances of E. coli detected in 2015. There were four recorded instances of total coliforms in 2015. Two events did not exceed the BC Drinking Water Protection limit for total coliforms. Concerns in regards to total coliforms were addressed by increased flushing and testing. With the recent launch of the Seymour/Capilano Filtration Plant and improvements to UBC’s distribution system, there has been a marked reduction in low chlorine and low pH events in the last year. A protocol for recording complaints has been developed and is included in the UBC Emergency Response Plan – Water Utility. UBC is committed to delivery of water of the highest quality, and will continue to make the necessary investment to ensure its continued success.

Page 23: University of British Columbiaenergy.sites.olt.ubc.ca/files/2016/10/UBC-WQM-Report-2015.pdf · University of British Columbia Drinking Water Quality Monitoring Report 2015 May 2016

University of British Columbia Drinking Water Quality Monitoring Report 2015

May 2016 Page 19

References: British Columbia Drinking Water Protection Regulation. Drinking Water Protection Act Reg. 200/2003, 2003 Guidelines for Canadian Drinking Water Quality – Health Canada, Sixth Edition, 1996 with updated summary table, October 2014. Water Quality Monitoring and Reporting Plan for the METRO VANCOUVER and Member Municipalities, Regional Engineers Advisory Committee (REAC), May 2000 Contact Information For more information on the contents of this report please contact: UBC Energy & Water Services 2040 West Mall Vancouver, BC V6T 1Z2 Phone: 604 822 4179 FAX: 604 822 8833 www.energy.ubc.ca

Page 24: University of British Columbiaenergy.sites.olt.ubc.ca/files/2016/10/UBC-WQM-Report-2015.pdf · University of British Columbia Drinking Water Quality Monitoring Report 2015 May 2016

University of British Columbia Drinking Water Quality Monitoring Report 2015

APPENDIX A

Water Sampling Sites Site Map

Page 25: University of British Columbiaenergy.sites.olt.ubc.ca/files/2016/10/UBC-WQM-Report-2015.pdf · University of British Columbia Drinking Water Quality Monitoring Report 2015 May 2016
Page 26: University of British Columbiaenergy.sites.olt.ubc.ca/files/2016/10/UBC-WQM-Report-2015.pdf · University of British Columbia Drinking Water Quality Monitoring Report 2015 May 2016

University of British Columbia Drinking Water Quality Monitoring Report 2015

APPENDIX B

Sample Analysis Results

Page 27: University of British Columbiaenergy.sites.olt.ubc.ca/files/2016/10/UBC-WQM-Report-2015.pdf · University of British Columbia Drinking Water Quality Monitoring Report 2015 May 2016

Sample Point WQB7‐001 (UBC‐001)

Sampling 

point

Sampled 

date

Chlorine Free 

mg/L

Total Coliform MF/100 mLs

Total Coliform 

MPN/100 mL

Ecoli MF/100mLs

E Coli MPN/100 mL

HPC CFU/mls

Temper‐

ature °C

Turbidity 

NTU pH

Conductivity

uS/cm

UBC‐001 6‐Jan‐15 0.49 <1 <1 <2 8.6 0.17 7.8 27

UBC‐001 13‐Jan‐15 0.44 <1 <1 2 6.7 0.17 7.2 28

UBC‐001 20‐Jan‐15 0.5 <1 <1 <2 7.6 0.11 7.7 28

UBC‐001 27‐Jan‐15 0.49 <1 <1 <2 7.7 0.25 7.3 28

UBC‐001 3‐Feb‐15 0.4 <1 <1 30 8.2 0.11 7.3 28

UBC‐001 10‐Feb‐15 0.41 <1 <1 150 8.7 0.14 7.1 28

UBC‐001 17‐Feb‐15 0.55 <1 <1 10 8.7 0.15 7.0 24

UBC‐001 24‐Feb‐15 0.42 <1 <1 2 8.5 0.89 7.4 26

UBC‐001 3‐Mar‐15 0.59 <1 <1 <2 8.1 0.14 6.9 26

UBC‐001 10‐Mar‐15 0.62 <1 <1 <2 8.2 1.1 7.1 26

UBC‐001 17‐Mar‐15 0.3 <1 <1 2 9 0.13 7.1 28

UBC‐001 24‐Mar‐15 0.69 <1 <1 2 9.4 0.09 7.4 27

UBC‐001 31‐Mar‐15 0.42 <1 <1 <2 9.1 0.13 7.2 27

UBC‐001 7‐Apr‐15 0.72 <1 <1 <2 9.8 0.12 7.1 27

UBC‐001 14‐Apr‐15 0.4 <1 <1 <2 8.3 0.12 7.1 27

UBC‐001 21‐Apr‐15 0.62 <1 <1 6 11 0.15 7.7 36

UBC‐001 28‐Apr‐15 0.5 <1 <1 <2 9.8 0.15 6.9 27

UBC‐001 5‐May‐15 0.45 <1 <1 <2 11 0.1 7.6 28

UBC‐001 12‐May‐15 0.5 <1 <1 26 11 0.14 7.6 28

UBC‐001 19‐May‐15 0.7 <1 <1 10 12 0.16 7.8 24

UBC‐001 26‐May‐15 0.48 <1 <1 2 11 0.16 7.1 28

UBC‐001 2‐Jun‐15 0.31 <1 <1 16 12 0.12 6.9 32

UBC‐001 9‐Jun‐15 0.44 <1 <1 8 13 0.11 7.1 30

UBC‐001 16‐Jun‐15 0.46 <1 <1 <2 16 0.35 7.1 31

UBC‐001 23‐Jun‐15 0.66 <1 <1 <2 15 0.12 6.9 31

UBC‐001 30‐Jun‐15 0.64 <1 <1 2 18 0.16 7.3 31

UBC‐001 7‐Jul‐15 0.66 <1 <1 2 17 0.13 6.9 32

UBC‐001 14‐Jul‐15 0.59 <1 <1 2 19 0.15 7.0 33

UBC‐001 21‐Jul‐15 0.57 <1 <1 <2 18 0.17 6.8 34

UBC‐001 28‐Jul‐15 0.58 <1 <1 <2 19 0.3 6.9 35

UBC‐001 4‐Aug‐15 0.65 <1 <1 <2 18 0.25 7.0 33

UBC‐001 11‐Aug‐15 0.63 <1 <1 <2 19 0.35 6.9 34

UBC‐001 18‐Aug‐15 0.67 <1 <1 <2 19 0.24 6.6 33

UBC‐001 25‐Aug‐15 0.62 <1 <1 <2 19 0.19 7.4 35

UBC‐001 1‐Sep‐15 0.6 <1 <1 <2 18 0.38 7.6 34

UBC‐001 8‐Sep‐15 0.44 <1 <1 <2 16 0.17 7.5 24

UBC‐001 15‐Sep‐15 0.6 <1 <1 <2 15 0.37 7.4 36

UBC‐001 22‐Sep‐15 0.44 <1 <1 <2 15 0.13 7.4 36

UBC‐001 29‐Sep‐15 0.5 <1 <1 <2 15 0.22 7.3 35

UBC‐001 6‐Oct‐15 0.62 <1 <1 2 15 0.15 7.4 33

UBC‐001 13‐Oct‐15 0.69 <1 <1 <2 14 0.8 7.4 36

UBC‐001 20‐Oct‐15 0.63 <1 <1 <2 14 0.24 7.3 37

UBC‐001 27‐Oct‐15 0.6 <1 <1 <2 14 0.12 7.3 33

UBC‐001 3‐Nov‐15 0.6 <1 <1 <2 12 0.2 7.3 35

UBC‐001 10‐Nov‐15 0.66 <1 <1 <2 11 0.22 6.4 31

UBC‐001 17‐Nov‐15 0.48 <1 <1 <2 11 0.14 7.2 29

UBC‐001 24‐Nov‐15 0.58 <1 <1 <2 8.6 0.15 7.3 30

UBC‐001 1‐Dec‐15 0.54 <1 <1 <2 8.8 0.1 6.7 29

UBC‐001 8‐Dec‐15 0.75 <1 <1 <2 9.3 0.15 7.5 25

UBC‐001 15‐Dec‐15 1.3 <1 <1 <2 8.6 0.24 7.5 25

UBC‐001 22‐Dec‐15 0.63 <1 <1 NA 8.2 0.16 7.2 26

UBC‐001 29‐Dec‐15 0.53 <1 <1 NA 7 0.11 7.6 26

Analyses by Metro Vancouver Laboratory‐2015

Page 28: University of British Columbiaenergy.sites.olt.ubc.ca/files/2016/10/UBC-WQM-Report-2015.pdf · University of British Columbia Drinking Water Quality Monitoring Report 2015 May 2016

Sample Point WQB7-001 (UBC-001)

0

20

40

60

80

100

120

140

160

0

0.2

0.4

0.6

0.8

1

1.2

1.4

HP

C C

FU/m

L

CI2

Fre

e m

g/L

Free CI2 and HPC at Sample Point UBC-001

CI2

HPC

00.10.20.30.40.50.60.70.80.91

00.10.20.30.40.50.60.70.80.9

1

6-J

an-1

5

6-F

eb

-15

6-M

ar-1

5

6-A

pr-

15

6-M

ay-1

5

6-J

un

-15

6-J

ul-

15

6-A

ug-

15

6-S

ep

-15

6-O

ct-1

5

6-N

ov-

15

6-D

ec-1

5

E C

oli

MF/

10

0 m

L

T C

oli

MF/

10

0 m

L

Total and Faecal Coliforms at Sample Point UBC-001

Total Coliform

E Coli

0

0.2

0.4

0.6

0.8

1

1.2

02468

101214161820

Turb

idit

y N

TU

Tem

pe

ratu

re D

egr

ee

s

Temperature and Turbidity at Sample Point UBC-001

TemperatureTurbidity

0

5

10

15

20

25

30

35

40

0.01.02.03.04.05.06.07.08.09.0

Co

nd

uct

ivit

y u

S/cm

pH

pH and Conductivity at Sample Point UBC-001

pHConductivity

Page 29: University of British Columbiaenergy.sites.olt.ubc.ca/files/2016/10/UBC-WQM-Report-2015.pdf · University of British Columbia Drinking Water Quality Monitoring Report 2015 May 2016

Sample Point WQC3‐002 (UBC‐002)

Sampling 

point

Sampled 

date

Chlorine Free 

mg/L

Total Coliform MF/100 mLs

Total Coliform 

MPN/100 mL

Ecoli MF/100mLs

E Coli MPN/100 mL

HPC CFU/mls

Temper‐

ature °C

Turbidity 

NTU pH

Conductivity

uS/cm

UBC‐002 6‐Jan‐15 0.51 <1 <1 <2 8 0.12 7.8 27

UBC‐002 13‐Jan‐15 0.5 <1 <1 2 6.3 0.13 7.1 29

UBC‐002 20‐Jan‐15 0.54 <1 <1 <2 6.9 0.22 7.5 29

UBC‐002 27‐Jan‐15 0.51 <1 <1 <2 7.1 0.14 7.0 29

UBC‐002 3‐Feb‐15 0.45 <1 <1 <2 8.1 0.11 7.1 28

UBC‐002 10‐Feb‐15 0.4 <1 <1 4 8.4 0.1 7.1 28

UBC‐002 17‐Feb‐15 0.61 <1 <1 2 8.6 0.11 7.2 25

UBC‐002 24‐Feb‐15 0.41 <1 <1 <2 8.1 0.11 7.2 26

UBC‐002 3‐Mar‐15 0.6 <1 <1 <2 7.7 0.11 7.0 26

UBC‐002 10‐Mar‐15 0.58 <1 <1 <2 7.7 0.7 7.2 26

UBC‐002 24‐Mar‐15 0.53 <1 <1 <2 9.9 0.13 7.2 27

UBC‐002 31‐Mar‐15 0.5 <1 <1 6 8.8 0.11 7.4 27

UBC‐002 7‐Apr‐15 0.67 <1 <1 <2 10 0.13 7.2 28

UBC‐002 14‐Apr‐15 0.51 <1 <1 <2 8.6 0.11 7.4 27

UBC‐002 21‐Apr‐15 0.56 <1 <1 2 10 0.15 7.9 28

UBC‐002 28‐Apr‐15 0.58 <1 <1 <2 9.8 0.12 6.9 28

UBC‐002 5‐May‐15 0.54 <1 <1 <2 11 0.15 7.7 28

UBC‐002 12‐May‐15 0.43 <1 <1 30 12 0.13 7.6 28

UBC‐002 19‐May‐15 0.67 <1 <1 <2 13 0.89 7.7 25

UBC‐002 26‐May‐15 0.51 <1 <1 <2 11 0.14 7.4 28

UBC‐002 2‐Jun‐15 0.42 <1 <1 14 12 0.12 7.0 30

UBC‐002 9‐Jun‐15 0.51 <1 <1 <2 14 0.11 6.9 30

UBC‐002 16‐Jun‐15 0.65 <1 <1 <2 14 0.13 7.2 32

UBC‐002 23‐Jun‐15 0.6 <1 <1 <2 15 0.14 6.7 31

UBC‐002 30‐Jun‐15 0.58 <1 <1 <2 16 0.13 7.2 30

UBC‐002 7‐Jul‐15 0.63 <1 <1 <2 16 0.11 7.0 32

UBC‐002 14‐Jul‐15 0.6 <1 <1 <2 18 0.22 7.3 34

UBC‐002 21‐Jul‐15 0.58 <1 <1 2 17 0.22 6.8 34

UBC‐002 28‐Jul‐15 0.49 <1 <1 <2 19 0.22 7.0 34

UBC‐002 4‐Aug‐15 0.47 <1 <1 <2 19 0.28 7.0 34

UBC‐002 11‐Aug‐15 0.55 <1 <1 <2 20 2 6.9 34

UBC‐002 18‐Aug‐15 0.49 <1 <1 <2 19 0.25 6.3 34

UBC‐002 25‐Aug‐15 0.51 <1 <1 <2 18 0.24 7.5 35

UBC‐002 1‐Sep‐15 0.46 <1 <1 <2 18 0.22 7.6 33

UBC‐002 8‐Sep‐15 0.6 <1 <1 <2 16 0.25 7.4 24

UBC‐002 15‐Sep‐15 0.51 <1 <1 <2 16 0.19 7.4 37

UBC‐002 22‐Sep‐15 0.48 <1 <1 <2 16 0.17 7.3 37

UBC‐002 29‐Sep‐15 0.48 <1 <1 <2 15 0.35 7.4 36

UBC‐002 6‐Oct‐15 0.45 <1 <1 <2 16 0.14 7.4 35

UBC‐002 13‐Oct‐15 0.54 <1 <1 <2 15 0.12 7.4 36

UBC‐002 20‐Oct‐15 0.45 <1 <1 <2 15 0.15 7.2 38

UBC‐002 27‐Oct‐15 0.49 <1 <1 <2 14 0.19 7.3 34

UBC‐002 3‐Nov‐15 0.64 <1 <1 <2 13 0.15 7.3 35

UBC‐002 10‐Nov‐15 0.63 <1 <1 <2 12 0.47 6.3 32

UBC‐002 17‐Nov‐15 0.4 <1 <1 <2 12 0.37 7.3 29

UBC‐002 24‐Nov‐15 0.58 <1 <1 <2 9.7 0.15 7.3 30

UBC‐002 1‐Dec‐15 0.52 <1 <1 <2 9.8 0.13 6.6 29

UBC‐002 8‐Dec‐15 0.62 <1 <1 4 10 0.15 7.5 25

UBC‐002 15‐Dec‐15 1.1 <1 <1 <2 9.6 0.17 7.1 24

UBC‐002 22‐Dec‐15 0.57 <1 <1 NA 9.1 0.13 7.3 25

UBC‐002 29‐Dec‐15 0.51 <1 <1 NA 8.5 0.15 7.5 26

Analyses by Metro Vancouver Laboratory‐2015

Page 30: University of British Columbiaenergy.sites.olt.ubc.ca/files/2016/10/UBC-WQM-Report-2015.pdf · University of British Columbia Drinking Water Quality Monitoring Report 2015 May 2016

Sample Point WQC3-002 (UBC-002)

0

5

10

15

20

25

30

35

0

0.2

0.4

0.6

0.8

1

1.2

HP

C C

FU/m

L

CI2

Fre

e m

g/L

Free CI2 and HPC at Sample Point UBC-002

CI2

HPC

00.10.20.30.40.50.60.70.80.91

00.10.20.30.40.50.60.70.80.9

1

E C

oli

MF/

10

0 m

L

T C

oli

MF/

10

0 m

L

Total and Faecal Coliforms at Sample Point UBC-002

Total Coliform

E Coli

0

0.5

1

1.5

2

2.5

0

5

10

15

20

25Tu

rbid

ity

NTU

Tem

pe

ratu

re D

egr

ee

s

Temperature and Turbidity at Sample Point UBC-002

Temperature

Turbidity

0

5

10

15

20

25

30

35

40

0.01.02.03.04.05.06.07.08.09.0

Co

nd

uct

ivit

y u

S/cm

pH

pH and Conductivity at Sample Point UBC-002

pH

Conductivity

Page 31: University of British Columbiaenergy.sites.olt.ubc.ca/files/2016/10/UBC-WQM-Report-2015.pdf · University of British Columbia Drinking Water Quality Monitoring Report 2015 May 2016

Sample Point WQD2‐003 (UBC‐003)

Sampling 

point

Sampled 

date

Chlorine Free 

mg/L

Total Coliform MF/100 mLs

Total Coliform 

MPN/100 mL

Ecoli MF/100mLs

E Coli MPN/100 mL

HPC CFU/mls

Temper‐

ature °C

Turbidity 

NTU pH

Conductivity

uS/cm

UBC‐003 6‐Jan‐15 0.54 <1 <1 <2 8.1 0.1 7.2 27

UBC‐003 13‐Jan‐15 0.58 <1 <1 2 6.8 0.15 7.7 29

UBC‐003 20‐Jan‐15 0.58 <1 <1 <2 7.3 0.12 7.7 28

UBC‐003 27‐Jan‐15 0.51 <1 <1 <2 7.3 0.14 7.1 29

UBC‐003 3‐Feb‐15 0.53 <1 <1 32 7.9 0.09 7.2 28

UBC‐003 10‐Feb‐15 0.42 <1 <1 14 8.6 0.14 7.0 28

UBC‐003 17‐Feb‐15 0.6 <1 <1 2 8.4 0.13 7.2 24

UBC‐003 24‐Feb‐15 0.48 <1 <1 4 8.4 1.4 7.2 26

UBC‐003 3‐Mar‐15 0.58 <1 <1 <2 7.8 0.1 7.0 26

UBC‐003 10‐Mar‐15 0.58 <1 <1 <2 7.7 0.68 7.1 26

UBC‐003 17‐Mar‐15 0.53 <1 <1 4 9.6 0.16 7.0 27

UBC‐003 24‐Mar‐15 0.5 <1 <1 <2 10 0.13 7.2 27

UBC‐003 31‐Mar‐15 0.5 <1 <1 12 8.7 0.13 7.4 27

UBC‐003 7‐Apr‐15 0.59 <1 <1 <2 11 0.16 6.9 27

UBC‐003 14‐Apr‐15 0.51 <1 <1 4 7.9 0.15 7.4 27

UBC‐003 21‐Apr‐15 0.68 <1 <1 <2 11 0.34 7.7 29

UBC‐003 28‐Apr‐15 0.51 <1 <1 <2 9.7 0.14 6.9 27

UBC‐003 5‐May‐15 0.52 <1 <1 <2 12 0.17 7.6 28

UBC‐003 12‐May‐15 0.48 <1 <1 <2 11 0.13 7.4 29

UBC‐003 19‐May‐15 0.5 <1 <1 <2 13 0.41 7.6 28

UBC‐003 26‐May‐15 0.43 <1 <1 2 11 0.11 7.6 27

UBC‐003 2‐Jun‐15 0.41 61 <1 22 12 0.17 7.2 31

UBC‐003 9‐Jun‐15 0.51 <1 <1 <2 13 0.13 7.0 31

UBC‐003 16‐Jun‐15 0.46 <1 <1 <2 14 0.14 7.1 31

UBC‐003 23‐Jun‐15 0.6 <1 <1 8 15 0.18 6.7 31

UBC‐003 30‐Jun‐15 0.54 <1 <1 <2 16 0.24 7.2 30

UBC‐003 7‐Jul‐15 0.57 <1 <1 <2 16 0.13 7.0 31

UBC‐003 14‐Jul‐15 0.61 <1 <1 <2 18 0.18 6.8 33

UBC‐003 21‐Jul‐15 0.63 <1 <1 <2 17 0.18 6.9 34

UBC‐003 28‐Jul‐15 0.52 <1 <1 <2 18 0.24 6.9 35

UBC‐003 4‐Aug‐15 0.49 <1 <1 <2 19 0.74 7.0 32

UBC‐003 11‐Aug‐15 0.49 <1 <1 <2 19 0.78 6.8 35

UBC‐003 18‐Aug‐15 0.47 <1 <1 2 19 0.27 6.2 34

UBC‐003 25‐Aug‐15 0.47 <1 <1 <2 18 0.44 7.5 35

UBC‐003 1‐Sep‐15 0.44 <1 <1 <2 18 0.23 7.6 33

UBC‐003 8‐Sep‐15 0.63 <1 <1 <2 16 0.45 7.4 24

UBC‐003 15‐Sep‐15 0.46 <1 <1 2 16 0.27 7.4 36

UBC‐003 22‐Sep‐15 0.49 <1 <1 <2 16 0.26 7.4 37

UBC‐003 29‐Sep‐15 0.42 <1 <1 <2 15 0.55 7.4 35

UBC‐003 6‐Oct‐15 0.45 <1 <1 <2 15 0.16 7.4 34

UBC‐003 13‐Oct‐15 0.5 <1 <1 <2 15 0.2 7.4 36

UBC‐003 20‐Oct‐15 0.45 <1 <1 <2 15 0.14 7.2 38

UBC‐003 27‐Oct‐15 0.52 <1 <1 <2 14 0.17 7.3 33

UBC‐003 3‐Nov‐15 0.63 <1 <1 <2 14 0.16 7.3 35

UBC‐003 10‐Nov‐15 0.55 <1 <1 <2 12 0.58 6.1 31

UBC‐003 17‐Nov‐15 0.44 <1 <1 <2 12 0.18 7.3 29

UBC‐003 24‐Nov‐15 0.54 <1 <1 <2 9.8 0.15 7.1 30

UBC‐003 1‐Dec‐15 0.54 <1 <1 <2 9.8 0.2 6.9 29

UBC‐003 8‐Dec‐15 0.64 <1 <1 <2 11 0.16 7.5 25

UBC‐003 15‐Dec‐15 1.1 <1 <1 <2 9.7 0.25 7.1 24

UBC‐003 22‐Dec‐15 0.55 <1 <1 NA 9 0.15 7.3 26

UBC‐003 29‐Dec‐15 0.4 <1 <1 NA 7.9 0.18 7.7 27

Analyses by Metro Vancouver Laboratory‐2015

Page 32: University of British Columbiaenergy.sites.olt.ubc.ca/files/2016/10/UBC-WQM-Report-2015.pdf · University of British Columbia Drinking Water Quality Monitoring Report 2015 May 2016

Sample Point WQD2-003 (UBC-003)

0

5

10

15

20

25

30

35

0

0.2

0.4

0.6

0.8

1

1.2

HP

C C

FU/m

L

CI2

Fre

e m

g/L

Free CI2 and HPC at Sample Point UBC-003

CI2

HPC

00.10.20.30.40.50.60.70.80.91

0

10

20

30

40

50

60

70

6-J

an-1

5

6-F

eb

-15

6-M

ar-1

5

6-A

pr-

15

6-M

ay-1

5

6-J

un

-15

6-J

ul-

15

6-A

ug-

15

6-S

ep

-15

6-O

ct-1

5

6-N

ov-

15

6-D

ec-1

5

E C

oli

FM/1

00

mL

T C

oli

FM/1

00

mL

Total and Faecal Coliforms at Sample Point UBC-003

Total Coliform

E Coli

0

0.2

0.4

0.6

0.8

1

1.2

1.4

1.6

02468

101214161820

Turb

idit

y N

TU

Tem

pe

ratu

re D

egr

ee

s

Temperature and Turbidity at Sample Point UBC-003

Temperature

Turbidity

0

5

10

15

20

25

30

35

40

0.01.02.03.04.05.06.07.08.09.0

Co

nd

uct

ivit

y u

S/cm

pH

pH and Conductivity at Sample Point UBC-003

pH

Conductivity

Page 33: University of British Columbiaenergy.sites.olt.ubc.ca/files/2016/10/UBC-WQM-Report-2015.pdf · University of British Columbia Drinking Water Quality Monitoring Report 2015 May 2016

Sample Point WQH3A‐004 (UBC‐004)

Sampling 

point

Sampled 

date

Chlorine Free 

mg/L

Total Coliform MF/100 mLs

Total Coliform 

MPN/100 mL

Ecoli MF/100mLs

E Coli MPN/100 mL

HPC CFU/mls

Temper‐

ature °C

Turbidity 

NTU pH

Conductivity

uS/cm

UBC‐004 6‐Jan‐15 0.47 <1 <1 2 8.4 0.18 7.8 28

UBC‐004 13‐Jan‐15 0.51 <1 <1 <2 6.4 0.17 7.2 29

UBC‐004 20‐Jan‐15 0.6 <1 <1 2 7.1 0.17 7.4 29

UBC‐004 27‐Jan‐15 0.46 <1 <1 <2 7.2 0.24 7.1 28

UBC‐004 3‐Feb‐15 0.5 <1 <1 <2 7.6 0.13 7.3 28

UBC‐004 10‐Feb‐15 0.48 <1 <1 28 9.1 0.14 7.1 28

UBC‐004 17‐Feb‐15 0.52 <1 <1 <2 8.6 0.13 7.3 24

UBC‐004 24‐Feb‐15 0.51 <1 <1 <2 8.3 0.11 7.1 26

UBC‐004 3‐Mar‐15 0.61 <1 <1 <2 8 0.11 6.7 26

UBC‐004 10‐Mar‐15 0.6 <1 <1 <2 7.9 1.4 7.2 26

UBC‐004 17‐Mar‐15 0.62 <1 <1 <2 9 0.25 7.1 28

UBC‐004 24‐Mar‐15 0.6 <1 <1 <2 9.3 0.16 7.1 27

UBC‐004 31‐Mar‐15 0.53 <1 <1 <2 9.5 0.14 7.5 26

UBC‐004 7‐Apr‐15 0.66 <1 <1 [Contamination] LA 9.8 0.18 6.7 27

UBC‐004 14‐Apr‐15 0.56 <1 <1 <2 8.2 0.13 7.6 27

UBC‐004 21‐Apr‐15 0.67 <1 <1 <2 9.9 0.41 8.0 29

UBC‐004 28‐Apr‐15 0.5 <1 <1 <2 9.5 0.14 7.1 28

UBC‐004 5‐May‐15 0.59 <1 <1 <2 10 0.12 7.0 28

UBC‐004 12‐May‐15 0.54 <1 <1 <2 11 0.15 7.7 29

UBC‐004 19‐May‐15 0.57 <1 <1 2 12 0.22 7.6 25

UBC‐004 26‐May‐15 0.48 <1 <1 <2 11 0.12 7.5 28

UBC‐004 2‐Jun‐15 0.48 57 <1 22 12 0.18 7.1 32

UBC‐004 9‐Jun‐15 0.55 <1 <1 <2 12 0.1 7.1 31

UBC‐004 16‐Jun‐15 0.64 <1 <1 <2 14 0.12 7.1 32

UBC‐004 23‐Jun‐15 0.68 <1 <1 <2 14 0.15 6.7 31

UBC‐004 30‐Jun‐15 0.64 <1 <1 <2 16 0.2 7.2 29

UBC‐004 7‐Jul‐15 0.69 <1 <1 <2 16 0.12 7.0 32

UBC‐004 14‐Jul‐15 0.65 <1 <1 <2 18 0.22 6.8 33

UBC‐004 21‐Jul‐15 0.56 <1 <1 2 18 0.2 7.0 34

UBC‐004 28‐Jul‐15 0.66 <1 <1 <2 18 0.21 6.9 35

UBC‐004 4‐Aug‐15 0.52 <1 <1 <2 19 0.47 7.0 33

UBC‐004 11‐Aug‐15 0.6 <1 <1 <2 19 0.74 6.8 33

UBC‐004 18‐Aug‐15 0.62 <1 <1 <2 18 0.26 6.6 34

UBC‐004 25‐Aug‐15 0.55 <1 <1 <2 18 0.34 7.4 35

UBC‐004 1‐Sep‐15 0.64 <1 <1 <2 18 0.21 7.6 32

UBC‐004 8‐Sep‐15 0.6 <1 <1 <2 16 0.27 7.4 24

UBC‐004 15‐Sep‐15 0.59 <1 <1 <2 15 0.25 7.4 34

UBC‐004 22‐Sep‐15 0.59 <1 <1 <2 15 0.16 7.4 37

UBC‐004 29‐Sep‐15 0.59 <1 <1 <2 14 0.33 7.4 35

UBC‐004 6‐Oct‐15 0.55 <1 <1 <2 14 0.16 7.4 34

UBC‐004 13‐Oct‐15 0.64 <1 <1 <2 14 0.16 7.3 37

UBC‐004 20‐Oct‐15 0.56 <1 <1 <2 14 0.68 7.3 37

UBC‐004 27‐Oct‐15 0.68 <1 <1 <2 13 0.25 7.3 33

UBC‐004 3‐Nov‐15 0.75 <1 <1 <2 13 0.18 7.3 35

UBC‐004 10‐Nov‐15 0.67 <1 <1 <2 11 0.91 6.1 31

UBC‐004 17‐Nov‐15 0.55 <1 <1 <2 11 3.2 7.0 29

UBC‐004 24‐Nov‐15 0.63 <1 <1 <2 9 0.17 7.1 30

UBC‐004 1‐Dec‐15 0.62 <1 <1 <2 8.8 0.12 7.3 29

UBC‐004 8‐Dec‐15 0.72 <1 <1 <2 9.2 0.12 7.5 25

UBC‐004 15‐Dec‐15 0.98 <1 <1 <2 8.6 0.21 7.0 23

UBC‐004 22‐Dec‐15 0.63 <1 <1 NA 8.2 0.12 7.2 26

UBC‐004 29‐Dec‐15 0.5 <1 <1 NA 8.1 0.13 7.9 29

Analyses by Metro Vancouver Laboratory‐2015

Page 34: University of British Columbiaenergy.sites.olt.ubc.ca/files/2016/10/UBC-WQM-Report-2015.pdf · University of British Columbia Drinking Water Quality Monitoring Report 2015 May 2016

Sample Point WQH3A-004 (UBC-004)

0

5

10

15

20

25

30

0

0.2

0.4

0.6

0.8

1

1.2

HP

C C

FU/m

L

CI2

Fre

e m

g/L

Free CI2 and HPC at Sample Point UBC-004

CI2

HPC

00.10.20.30.40.50.60.70.80.91

0

10

20

30

40

50

60

6-J

an-1

5

6-F

eb

-15

6-M

ar-1

5

6-A

pr-

15

6-M

ay-1

5

6-J

un

-15

6-J

ul-

15

6-A

ug-

15

6-S

ep

-15

6-O

ct-1

5

6-N

ov-

15

6-D

ec-1

5

E C

oli

MF/

10

0 m

L

T C

oli

MF/

10

0 m

L

Total and Faecal Coliforms at Sample Point UBC-004

Total Coliform

E Coli

0

0.5

1

1.5

2

2.5

3

3.5

02468

101214161820

Turb

idit

y N

TU

Tem

pe

ratu

re D

egr

ee

s

Temperature and Turbidity at Sample Point UBC-004

Temperature

Turbidity

0

5

10

15

20

25

30

35

40

0.01.02.03.04.05.06.07.08.09.0

Co

nd

uct

ivit

y u

S/cm

pH

pH and Conductivity at Sample Point UBC-004

pH

Conductivity

Page 35: University of British Columbiaenergy.sites.olt.ubc.ca/files/2016/10/UBC-WQM-Report-2015.pdf · University of British Columbia Drinking Water Quality Monitoring Report 2015 May 2016

Sample Point WQL3‐006 (UBC‐006)

Sampling 

point

Sampled 

date

Chlorine Free 

mg/L

Total Coliform MF/100 mLs

Total Coliform 

MPN/100 mL

Ecoli MF/100mLs

E Coli MPN/100 mL

HPC CFU/mls

Temper‐

ature °C

Turbidity 

NTU pH

Conductivity

uS/cm

UBC‐006 6‐Jan‐15 0.51 <1 <1 2 8.1 0.3 7.3 28

UBC‐006 20‐Jan‐15 0.52 <1 <1 <2 7 0.14 7.8 29

UBC‐006 3‐Feb‐15 0.49 <1 <1 <2 7.8 0.12 7.1 28

UBC‐006 17‐Feb‐15 0.6 <1 <1 <2 8.8 0.19 7.1 25

UBC‐006 3‐Mar‐15 0.51 <1 <1 <2 8.2 0.11 6.6 26

UBC‐006 17‐Mar‐15 0.6 <1 <1 <2 8.6 0.16 7.0 27

UBC‐006 31‐Mar‐15 0.5 <1 <1 2 9.5 0.12 7.4 27

UBC‐006 14‐Apr‐15 0.54 <1 <1 2 8.6 0.11 7.1 27

UBC‐006 28‐Apr‐15 0.55 <1 <1 <2 9.5 0.18 6.7 26

UBC‐006 12‐May‐15 0.5 <1 <1 <2 11 0.26 7.0 28

UBC‐006 26‐May‐15 0.47 <1 <1 <2 11 0.11 7.6 27

UBC‐006 9‐Jun‐15 0.55 <1 <1 2 12 0.19 7.2 31

UBC‐006 23‐Jun‐15 0.75 <1 <1 <2 14 0.34 6.7 30

UBC‐006 7‐Jul‐15 0.74 <1 <1 <2 16 0.13 7.6 32

UBC‐006 21‐Jul‐15 0.55 <1 <1 2 18 0.23 6.9 34

UBC‐006 4‐Aug‐15 0.72 <1 <1 <2 18 0.33 7.0 32

UBC‐006 18‐Aug‐15 0.65 <1 <1 2 18 0.27 6.5 34

UBC‐006 1‐Sep‐15 0.64 <1 <1 <2 17 0.21 7.6 35

UBC‐006 15‐Sep‐15 0.76 <1 <1 <2 15 0.4 7.4 36

UBC‐006 29‐Sep‐15 0.66 <1 <1 <2 14 0.24 7.4 34

UBC‐006 13‐Oct‐15 0.71 <1 <1 <2 14 0.14 7.4 36

UBC‐006 27‐Oct‐15 0.76 <1 <1 <2 13 0.33 7.3 34

UBC‐006 10‐Nov‐15 0.69 <1 <1 <2 10 0.17 6.0 31

UBC‐006 24‐Nov‐15 0.64 <1 <1 <2 8.1 0.12 7.1 30

UBC‐006 8‐Dec‐15 0.72 <1 <1 <2 8.4 0.1 7.5 25

UBC‐006 22‐Dec‐15 0.68 <1 <1 NA 7.1 0.16 7.3 26

Analyses by Metro Vancouver Laboratory‐2015

Page 36: University of British Columbiaenergy.sites.olt.ubc.ca/files/2016/10/UBC-WQM-Report-2015.pdf · University of British Columbia Drinking Water Quality Monitoring Report 2015 May 2016

Sample Point WQL3-006 (UBC-006)

0

0.5

1

1.5

2

2.5

0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

HP

C C

FU/m

L

CI2

Fre

e m

g/L

Free CI2 and HPC at Sample Point UBC-006

CI2

HPC

00.10.20.30.40.50.60.70.80.91

00.10.20.30.40.50.60.70.80.9

1

6-J

an-1

5

6-F

eb

-15

6-M

ar-1

5

6-A

pr-

15

6-M

ay-1

5

6-J

un

-15

6-J

ul-

15

6-A

ug-

15

6-S

ep

-15

6-O

ct-1

5

6-N

ov-

15

6-D

ec-1

5

E C

oli

MF/

10

0 m

L

T C

oli

MF/

10

0 m

L

Total and Faecal Coliforms at Sample Point UBC-006

Total Coliform

E Coli

00.050.10.150.20.250.30.350.40.45

02468

101214161820

Turb

idit

y N

TU

Tem

pe

ratu

re D

egr

ee

s

Temperature and Turbidity at Sample Point UBC-006

Temperature

Turbidity

0

5

10

15

20

25

30

35

40

0.01.02.03.04.05.06.07.08.09.0

Co

nd

uct

ivit

y u

S/cm

pH

pH and Conductivity at Sample Point UBC-006

pH

Conductivity

Page 37: University of British Columbiaenergy.sites.olt.ubc.ca/files/2016/10/UBC-WQM-Report-2015.pdf · University of British Columbia Drinking Water Quality Monitoring Report 2015 May 2016

Sample Point WQJ5‐007 (UBC‐007)

Sampling 

point

Sampled 

date

Chlorine Free 

mg/L

Total Coliform MF/100 mLs

Total Coliform 

MPN/100 mL

Ecoli MF/100mLs

E Coli MPN/100 mL

HPC CFU/mls

Temper‐

ature °C

Turbidity 

NTU pH

Conductivity

uS/cm

UBC‐007 6‐Jan‐15 0.5 <1 <1 14 8.3 0.26 7.6 27

UBC‐007 20‐Jan‐15 0.61 <1 <1 <2 7.4 0.12 8.1 29

UBC‐007 3‐Feb‐15 0.45 <1 <1 <2 7.2 0.13 7.4 28

UBC‐007 17‐Feb‐15 0.53 <1 <1 <2 8.5 0.11 7.2 25

UBC‐007 3‐Mar‐15 0.43 <1 <1 <2 7.9 0.11 6.5 26

UBC‐007 17‐Mar‐15 0.65 <1 <1 <2 8.4 0.15 7.1 27

UBC‐007 31‐Mar‐15 0.48 <1 <1 <2 9.3 0.16 7.6 27

UBC‐007 14‐Apr‐15 0.5 <1 <1 4 8.2 0.12 7.7 26

UBC‐007 28‐Apr‐15 0.51 <1 <1 <2 9.5 0.11 6.9 27

UBC‐007 12‐May‐15 0.47 <1 <1 <2 12 0.1 7.6 27

UBC‐007 26‐May‐15 0.4 <1 <1 <2 11 0.12 7.8 29

UBC‐007 9‐Jun‐15 0.59 <1 <1 80 12 0.09 7.4 30

UBC‐007 23‐Jun‐15 0.69 <1 <1 <2 13 0.15 6.7 31

UBC‐007 7‐Jul‐15 0.66 <1 <1 <2 16 0.11 8.0 32

UBC‐007 21‐Jul‐15 0.58 <1 <1 <2 18 0.31 6.9 34

UBC‐007 4‐Aug‐15 0.76 <1 <1 <2 18 0.28 7.0 32

UBC‐007 18‐Aug‐15 0.68 <1 <1 <2 18 0.24 6.4 33

UBC‐007 1‐Sep‐15 0.71 <1 <1 <2 17 0.31 7.6 35

UBC‐007 15‐Sep‐15 0.69 <1 <1 <2 15 0.44 7.4 36

UBC‐007 29‐Sep‐15 0.64 <1 <1 <2 14 0.18 7.3 34

UBC‐007 13‐Oct‐15 0.74 <1 <1 <2 14 0.21 7.4 36

UBC‐007 27‐Oct‐15 0.72 <1 <1 <2 13 0.11 7.3 33

UBC‐007 10‐Nov‐15 0.72 <1 <1 <2 10 0.18 6.2 31

UBC‐007 24‐Nov‐15 0.68 <1 <1 <2 7.9 0.1 7.1 30

UBC‐007 8‐Dec‐15 0.73 <1 <1 <2 8.9 0.15 7.5 25

UBC‐007 22‐Dec‐15 0.66 <1 <1 NA 7.3 0.49 7.2 25

Analyses by Metro Vancouver Laboratory‐2015

Page 38: University of British Columbiaenergy.sites.olt.ubc.ca/files/2016/10/UBC-WQM-Report-2015.pdf · University of British Columbia Drinking Water Quality Monitoring Report 2015 May 2016

Sample Point WQJ5-007 (UBC-007)

0102030405060708090

0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

HP

C C

FU/m

L

CI2

Fre

e m

g/L

Free CI2 and HPC at Sample Point UBC-007

CI2

HPC

00.10.20.30.40.50.60.70.80.91

00.10.20.30.40.50.60.70.80.9

1

6-J

an-1

5

6-F

eb

-15

6-M

ar-1

5

6-A

pr-

15

6-M

ay-1

5

6-J

un

-15

6-J

ul-

15

6-A

ug-

15

6-S

ep

-15

6-O

ct-1

5

6-N

ov-

15

6-D

ec-1

5

E C

oli

MF/

10

0 m

L

T C

oli

MF/

10

0 m

L

Total and Faecal Coliforms at Sample Point UBC-007

Total Coliform

E Coli

0

0.1

0.2

0.3

0.4

0.5

0.6

02468

101214161820

Turb

idit

y N

TU

Tem

pe

ratu

re D

egr

ee

s

Temperature and Turbidity at Sample Point UBC-007

Temperature

Turbidity

0

5

10

15

20

25

30

35

40

0.01.02.03.04.05.06.07.08.09.0

Co

nd

uct

ivit

y u

S/cm

pH

pH and Conductivity at Sample Point UBC-007

pH

Conductivity

Page 39: University of British Columbiaenergy.sites.olt.ubc.ca/files/2016/10/UBC-WQM-Report-2015.pdf · University of British Columbia Drinking Water Quality Monitoring Report 2015 May 2016

Sample Point WQG6‐008 (UBC‐008)

Sampling 

point

Sampled 

date

Chlorine Free 

mg/L

Total Coliform MF/100 mLs

Total Coliform 

MPN/100 mL

Ecoli MF/100mLs

E Coli MPN/100 mL

HPC CFU/mls

Temper‐

ature °C

Turbidity 

NTU pH

Conductivity

uS/cm

UBC‐008 6‐Jan‐15 0.57 <1 <1 80 7.7 0.3 7.6 27

UBC‐008 20‐Jan‐15 0.54 <1 <1 36 6.5 0.25 7.4 29

UBC‐008 3‐Feb‐15 0.45 <1 <1 14 7.2 0.19 7.6 28

UBC‐008 17‐Feb‐15 0.62 <1 <1 58 8.1 0.34 6.9 24

UBC‐008 3‐Mar‐15 0.61 <1 <1 <2 7.8 0.1 6.5 26

UBC‐008 17‐Mar‐15 0.58 <1 <1 4 8.8 0.13 7.1 27

UBC‐008 31‐Mar‐15 0.53 <1 <1 <2 8.9 0.19 7.5 27

UBC‐008 14‐Apr‐15 0.48 <1 <1 14 8 0.42 7.2 27

UBC‐008 28‐Apr‐15 0.56 <1 <1 <2 9.6 0.13 6.9 26

UBC‐008 12‐May‐15 0.57 <1 <1 <2 12 0.28 7.5 28

UBC‐008 26‐May‐15 0.43 <1 <1 <2 11 0.12 7.4 28

UBC‐008 9‐Jun‐15 0.43 <1 <1 <2 13 2.7 7.3 30

UBC‐008 23‐Jun‐15 0.8 <1 <1 <2 12 0.16 6.8 31

UBC‐008 7‐Jul‐15 0.65 <1 <1 <2 15 0.36 7.1 30

UBC‐008 21‐Jul‐15 0.59 <1 <1 <2 17 0.28 6.9 34

UBC‐008 4‐Aug‐15 0.77 <1 <1 <2 18 0.41 7.0 32

UBC‐008 18‐Aug‐15 0.74 <1 <1 <2 18 0.3 6.5 33

UBC‐008 1‐Sep‐15 0.65 <1 <1 2 17 0.36 7.5 34

UBC‐008 15‐Sep‐15 0.62 <1 <1 <2 15 0.41 7.4 36

UBC‐008 29‐Sep‐15 0.51 <1 <1 <2 14 0.31 7.3 34

UBC‐008 13‐Oct‐15 0.7 <1 <1 <2 14 0.17 7.4 37

UBC‐008 20‐Oct‐15 0.69 <1 <1 <2 14 0.19 7.2 36

UBC‐008 27‐Oct‐15 0.64 <1 <1 <2 13 0.11 7.3 33

UBC‐008 10‐Nov‐15 0.67 <1 <1 2 10 0.18 6.0 31

UBC‐008 17‐Nov‐15 0.55 <1 <1 <2 10 0.15 6.8 29

UBC‐008 24‐Nov‐15 0.68 <1 <1 <2 7.9 0.13 7.1 31

UBC‐008 1‐Dec‐15 0.6 <1 <1 <2 7.9 0.1 7.1 29

UBC‐008 8‐Dec‐15 0.72 <1 <1 <2 8.5 0.11 7.5 25

UBC‐008 15‐Dec‐15 0.95 <1 <1 <2 7.9 0.24 7.2 23

UBC‐008 22‐Dec‐15 0.63 <1 <1 NA 7.4 0.38 7.2 26

UBC‐008 29‐Dec‐15 0.63 <1 <1 NA 6.9 0.11 7.8 26

Analyses by Metro Vancouver Laboratory‐2015

Page 40: University of British Columbiaenergy.sites.olt.ubc.ca/files/2016/10/UBC-WQM-Report-2015.pdf · University of British Columbia Drinking Water Quality Monitoring Report 2015 May 2016

Sample Point WQG6-008 (UBC-008)

0102030405060708090

00.10.20.30.40.50.60.70.80.9

1

HP

C C

FU/m

L

CI2

Fre

e m

g/L

Free CI2 and HPC at Sample Point UBC-008

CI2

HPC

00.10.20.30.40.50.60.70.80.91

00.10.20.30.40.50.60.70.80.9

1

6-J

an-1

5

6-F

eb

-15

6-M

ar-1

5

6-A

pr-

15

6-M

ay-1

5

6-J

un

-15

6-J

ul-

15

6-A

ug-

15

6-S

ep

-15

6-O

ct-1

5

6-N

ov-

15

6-D

ec-1

5

E C

oli

MF/

10

0 m

L

T C

oli

MF/

10

0 m

L

Total and Faecal Coliforms at Sample Point UBC-008

Total Coliform

E Coli

0

0.5

1

1.5

2

2.5

3

02468

101214161820

Turb

idit

y N

TU

Tem

pe

ratu

re D

egr

ee

s

Temperature and Turbidity at Sample Point UBC-008

Temperature

Turbidity

0

5

10

15

20

25

30

35

40

0.01.02.03.04.05.06.07.08.09.0

Co

nd

uct

ivit

y u

S/cm

pH

pH and Conductivity at Sample Point UBC-008

pH

Conductivity

Page 41: University of British Columbiaenergy.sites.olt.ubc.ca/files/2016/10/UBC-WQM-Report-2015.pdf · University of British Columbia Drinking Water Quality Monitoring Report 2015 May 2016

Sample Point WQF713‐009 (UBC‐009)

Sampling 

point

Sampled 

date

Chlorine Free 

mg/L

Total Coliform MF/100 mLs

Total Coliform 

MPN/100 mL

Ecoli MF/100mLs

E Coli MPN/100 mL

HPC CFU/mls

Temper‐

ature °C

Turbidity 

NTU pH

Conductivity

uS/cm

UBC‐009 6‐Jan‐15 0.6 <1 <1 <2 7.4 0.17 7.3 28

UBC‐009 13‐Jan‐15 0.55 <1 <1 <2 7.3 0.2 7.0 28

UBC‐009 20‐Jan‐15 0.52 <1 <1 30 6.3 0.18 7.4 29

UBC‐009 27‐Jan‐15 0.53 <1 <1 <2 7.2 0.12 7.0 29

UBC‐009 3‐Feb‐15 0.49 <1 <1 <2 7.9 0.16 7.6 28

UBC‐009 10‐Feb‐15 0.41 <1 <1 <2 8.9 0.11 7.4 28

UBC‐009 17‐Feb‐15 0.49 <1 <1 <2 8.3 0.15 7.1 25

UBC‐009 24‐Feb‐15 0.48 <1 <1 <2 8.7 0.19 7.3 27

UBC‐009 3‐Mar‐15 0.69 <1 <1 2 8.1 0.18 6.4 26

UBC‐009 10‐Mar‐15 0.63 <1 <1 <2 8.3 3 7.2 26

UBC‐009 17‐Mar‐15 0.63 <1 <1 2 8.7 0.15 7.1 27

UBC‐009 24‐Mar‐15 0.69 <1 <1 <2 8.7 0.11 7.2 27

UBC‐009 31‐Mar‐15 0.58 <1 <1 <2 9.4 0.12 7.8 27

UBC‐009 7‐Apr‐15 0.71 <1 <1 <2 9.4 0.14 6.6 27

UBC‐009 14‐Apr‐15 0.58 <1 <1 <2 8.3 0.13 7.8 27

UBC‐009 21‐Apr‐15 0.67 <1 <1 <2 9 0.15 8.0 28

UBC‐009 28‐Apr‐15 0.56 <1 <1 <2 9.7 0.15 7.0 28

UBC‐009 5‐May‐15 0.59 <1 <1 <2 9.6 0.12 6.8 28

UBC‐009 12‐May‐15 0.51 <1 <1 <2 12 0.11 7.1 30

UBC‐009 19‐May‐15 0.64 <1 <1 <2 12 0.32 7.5 24

UBC‐009 26‐May‐15 0.45 <1 <1 2 11 0.1 7.3 28

UBC‐009 2‐Jun‐15 0.55 <1 <1 <2 12 0.1 7.1 31

UBC‐009 9‐Jun‐15 0.59 <1 <1 2 12 0.12 6.9 30

UBC‐009 16‐Jun‐15 0.47 <1 <1 <2 13 0.13 7.2 32

UBC‐009 30‐Jun‐15 0.55 <1 <1 2 18 0.13 7.2 30

UBC‐009 7‐Jul‐15 0.26 <1 <1 <2 19 0.29 8.3 32

UBC‐009 14‐Jul‐15 0.48 <1 <1 <2 18 0.11 6.8 33

UBC‐009 21‐Jul‐15 0.57 <1 <1 <2 18 0.16 6.9 34

UBC‐009 28‐Jul‐15 0.51 <1 <1 <2 18 0.28 6.9 34

UBC‐009 4‐Aug‐15 0.72 <1 <1 <2 19 0.29 7.0 33

UBC‐009 11‐Aug‐15 0.58 <1 <1 2 19 0.21 6.7 34

UBC‐009 18‐Aug‐15 0.57 <1 <1 2 19 0.28 6.5 33

UBC‐009 25‐Aug‐15 0.64 <1 <1 <2 19 0.19 7.5 36

UBC‐009 1‐Sep‐15 0.69 <1 <1 <2 18 0.37 7.5 32

UBC‐009 8‐Sep‐15 0.57 <1 <1 <2 15 0.28 7.4 24

UBC‐009 15‐Sep‐15 0.68 <1 <1 <2 15 0.58 7.3 35

UBC‐009 22‐Sep‐15 0.69 <1 <1 <2 15 0.11 7.4 36

UBC‐009 29‐Sep‐15 0.65 <1 <1 <2 14 0.15 7.3 34

UBC‐009 6‐Oct‐15 0.67 <1 <1 <2 15 0.15 7.4 29

UBC‐009 13‐Oct‐15 0.69 <1 <1 <2 14 0.18 7.4 35

UBC‐009 20‐Oct‐15 0.7 <1 <1 <2 14 0.1 7.2 37

UBC‐009 27‐Oct‐15 0.85 <1 <1 <2 13 0.1 7.2 33

UBC‐009 3‐Nov‐15 0.75 <1 <1 <2 12 0.13 7.3 34

UBC‐009 10‐Nov‐15 0.76 <1 <1 <2 11 0.12 5.8 30

UBC‐009 17‐Nov‐15 0.52 <1 <1 <2 10 0.18 6.6 29

UBC‐009 24‐Nov‐15 0.61 <1 <1 <2 8.1 0.11 7.2 30

UBC‐009 1‐Dec‐15 0.59 <1 <1 <2 8.2 0.09 6.5 29

UBC‐009 8‐Dec‐15 0.74 <1 <1 <2 8.9 0.14 7.5 25

UBC‐009 15‐Dec‐15 1.3 <1 <1 <2 8.2 0.29 7.2 25

UBC‐009 22‐Dec‐15 0.67 <1 <1 NA 7.7 0.15 7.3 26

UBC‐009 29‐Dec‐15 0.66 <1 <1 NA 6.6 0.1 7.9 26

Analyses by Metro Vancouver Laboratory‐2015

Page 42: University of British Columbiaenergy.sites.olt.ubc.ca/files/2016/10/UBC-WQM-Report-2015.pdf · University of British Columbia Drinking Water Quality Monitoring Report 2015 May 2016

Sample Point WQF713-009 (UBC-009)

0

5

10

15

20

25

30

35

0

0.2

0.4

0.6

0.8

1

1.2

1.4

HP

C C

FU/m

L

CI2

Fre

e m

g/L

Free CI2 and HPC at Sample Point UBC-009

CI2

HPC

00.10.20.30.40.50.60.70.80.91

00.10.20.30.40.50.60.70.80.9

1

6-J

an-1

5

6-F

eb

-15

6-M

ar-1

5

6-A

pr-

15

6-M

ay-…

6-J

un

-15

6-J

ul-

15

6-A

ug-

15

6-S

ep

-15

6-O

ct-1

5

6-N

ov-

15

6-D

ec-1

5

E C

oli

MF/

10

0 m

L

T C

oli

MF/

10

0 m

L

Total and Faecal Coliforms at Sample Point UBC-009

Total Coliform

E Coli

0

0.5

1

1.5

2

2.5

3

3.5

02468

101214161820

Turb

idit

y N

TU

Tem

pe

ratu

re D

egr

ee

s

Temperature and Turbidity at Sample Point UBC-009

Temperature

Turbidity

0

5

10

15

20

25

30

35

40

0.01.02.03.04.05.06.07.08.09.0

Co

nd

uct

ivit

y u

S/cm

pH

pH and Conductivity at Sample Point UBC-009

pH

Conductivity

Page 43: University of British Columbiaenergy.sites.olt.ubc.ca/files/2016/10/UBC-WQM-Report-2015.pdf · University of British Columbia Drinking Water Quality Monitoring Report 2015 May 2016

Sample Point WQJ10‐011 (UBC‐011)

Sampling 

point

Sampled 

date

Chlorine Free 

mg/L

Total Coliform MF/100 mLs

Total Coliform 

MPN/100 mL

Ecoli MF/100mLs

E Coli MPN/100 mL

HPC CFU/mls

Temper‐

ature °C

Turbidity 

NTU pH

Conductivity

uS/cm

UBC‐011 6‐Jan‐15 0.51 <1 <1 <2 7.8 0.19 7.8 28

UBC‐011 13‐Jan‐15 0.51 <1 <1 <2 6.9 0.13 7.4 29

UBC‐011 20‐Jan‐15 0.64 <1 <1 4 6.9 0.13 8.2 30

UBC‐011 27‐Jan‐15 0.42 <1 <1 <2 7.3 0.14 7.0 29

UBC‐011 3‐Feb‐15 0.44 <1 <1 <2 7.6 0.14 7.5 28

UBC‐011 10‐Feb‐15 0.41 <1 <1 <2 8.5 0.11 7.4 28

UBC‐011 17‐Feb‐15 0.55 <1 <1 <2 8.5 0.11 6.9 24

UBC‐011 24‐Feb‐15 0.5 <1 <1 <2 8.8 0.14 7.2 27

UBC‐011 3‐Mar‐15 0.62 <1 <1 <2 8.1 0.1 6.3 26

UBC‐011 10‐Mar‐15 0.57 <1 <1 <2 8 0.26 7.2 26

UBC‐011 17‐Mar‐15 0.64 <1 <1 <2 8.7 1 7.1 27

UBC‐011 24‐Mar‐15 0.56 <1 <1 2 8.8 0.1 7.1 27

UBC‐011 31‐Mar‐15 0.51 <1 <1 8 9.3 0.11 7.6 27

UBC‐011 7‐Apr‐15 0.62 <1 <1 <2 9.6 0.12 6.5 28

UBC‐011 14‐Apr‐15 0.52 <1 <1 6 8.1 0.14 7.4 27

UBC‐011 21‐Apr‐15 0.6 <1 <1 <2 9.8 0.17 7.9 31

UBC‐011 28‐Apr‐15 0.48 <1 <1 <2 9.6 0.12 6.9 28

UBC‐011 5‐May‐15 0.63 <1 <1 <2 9.9 0.11 7.0 28

UBC‐011 12‐May‐15 0.52 <1 <1 6 11 0.1 6.9 29

UBC‐011 19‐May‐15 0.6 <1 <1 <2 12 0.1 7.5 25

UBC‐011 26‐May‐15 0.41 <1 <1 <2 11 0.15 7.3 28

UBC‐011 2‐Jun‐15 0.49 <1 <1 <2 12 0.11 7.0 31

UBC‐011 9‐Jun‐15 0.56 <1 <1 <2 13 0.12 6.8 30

UBC‐011 16‐Jun‐15 0.56 <1 <1 4 14 0.14 7.1 30

UBC‐011 23‐Jun‐15 0.75 <1 <1 <2 14 0.12 6.8 31

UBC‐011 30‐Jun‐15 0.57 <1 <1 2 15 0.18 7.2 30

UBC‐011 7‐Jul‐15 0.6 <1 <1 2 16 0.12 7.3 31

UBC‐011 14‐Jul‐15 0.6 <1 <1 2 17 0.12 6.8 33

UBC‐011 21‐Jul‐15 0.54 <1 <1 <2 17 0.19 6.8 35

UBC‐011 28‐Jul‐15 0.52 <1 <1 <2 17 0.24 6.9 35

UBC‐011 4‐Aug‐15 0.61 <1 <1 <2 18 0.2 7.0 33

UBC‐011 11‐Aug‐15 0.6 <1 <1 <2 18 0.24 6.7 36

UBC‐011 18‐Aug‐15 0.6 <1 <1 <2 18 0.24 6.2 34

UBC‐011 25‐Aug‐15 0.61 <1 <1 <2 18 0.15 7.4 35

UBC‐011 1‐Sep‐15 0.66 <1 <1 <2 18 0.23 7.6 33

UBC‐011 8‐Sep‐15 0.53 <1 <1 2 16 0.14 7.4 25

UBC‐011 15‐Sep‐15 0.65 <1 <1 <2 15 0.22 7.3 38

UBC‐011 22‐Sep‐15 0.56 <1 <1 <2 15 0.11 7.3 37

UBC‐011 29‐Sep‐15 0.62 <1 <1 <2 14 0.13 7.4 35

UBC‐011 6‐Oct‐15 0.61 <1 <1 <2 14 0.17 7.3 34

UBC‐011 13‐Oct‐15 0.62 <1 <1 <2 14 0.11 7.3 36

UBC‐011 20‐Oct‐15 0.63 <1 <1 <2 14 0.13 7.1 38

UBC‐011 27‐Oct‐15 0.69 <1 <1 <2 13 0.09 7.3 32

UBC‐011 3‐Nov‐15 0.73 <1 <1 <2 12 0.1 7.3 35

UBC‐011 10‐Nov‐15 0.9 <1 <1 <2 11 0.14 5.6 31

UBC‐011 17‐Nov‐15 0.59 <1 <1 <2 10 0.12 6.5 29

UBC‐011 24‐Nov‐15 0.73 <1 <1 <2 8.1 0.14 7.2 31

UBC‐011 1‐Dec‐15 0.62 <1 <1 <2 8.6 0.09 6.4 29

UBC‐011 8‐Dec‐15 0.61 <1 <1 2 8.7 0.2 7.5 25

UBC‐011 15‐Dec‐15 1.4 <1 <1 <2 8.5 0.26 7.3 25

UBC‐011 22‐Dec‐15 0.72 <1 <1 NA 8 0.17 7.3 26

UBC‐011 29‐Dec‐15 0.65 <1 <1 NA 7.3 0.11 7.8 27

Analyses by Metro Vancouver Laboratory‐2015

Page 44: University of British Columbiaenergy.sites.olt.ubc.ca/files/2016/10/UBC-WQM-Report-2015.pdf · University of British Columbia Drinking Water Quality Monitoring Report 2015 May 2016

Sample Point WQJ10-011 (UBC-011)

0123456789

0

0.2

0.4

0.6

0.8

1

1.2

1.4

1.6

HP

C C

FU/m

L

CI2

Fre

e m

g/L

Free CI2 and HPC at Sample Point UBC-011

CI2

HPC

00.10.20.30.40.50.60.70.80.91

00.10.20.30.40.50.60.70.80.9

1

6-J

an-1

5

6-F

eb

-15

6-M

ar-1

5

6-A

pr-

15

6-M

ay-…

6-J

un

-15

6-J

ul-

15

6-A

ug-

15

6-S

ep

-15

6-O

ct-1

5

6-N

ov-

15

6-D

ec-1

5

E C

oli

MF/

10

0 m

L

T C

oli

MF/

10

0 m

L

Total and Faecal Coliforms at Sample Point UBC-011

Total Coliform

E Coli

0

0.2

0.4

0.6

0.8

1

1.2

02468

101214161820

Turb

idit

y N

TU

Tem

pe

ratu

re D

egr

ee

s

Temperature and Turbidity at Sample Point UBC-011

Temperature

Turbidity

0

5

10

15

20

25

30

35

40

0.01.02.03.04.05.06.07.08.09.0

Co

nd

uct

ivit

y u

S/cm

pH

pH and Conductivity at Sample Point UBC-011

pH

Conductivity

Page 45: University of British Columbiaenergy.sites.olt.ubc.ca/files/2016/10/UBC-WQM-Report-2015.pdf · University of British Columbia Drinking Water Quality Monitoring Report 2015 May 2016

Sample Point WQM8‐012 (UBC‐012)

Sampling 

point

Sampled 

date

Chlorine Free 

mg/L

Total Coliform MF/100 mLs

Total Coliform 

MPN/100 mL

Ecoli MF/100mLs

E Coli MPN/100 mL

HPC CFU/mls

Temper‐

ature °C

Turbidity 

NTU pH

Conductivity

uS/cm

UBC‐012 6‐Jan‐15 0.63 <1 <1 6 7.1 0.12 7.6 28

UBC‐012 20‐Jan‐15 0.52 <1 <1 <2 7.3 0.13 7.5 29

UBC‐012 3‐Feb‐15 0.42 <1 <1 <2 7.7 0.11 7.4 28

UBC‐012 17‐Feb‐15 0.63 <1 <1 12 8.7 0.12 7.1 24

UBC‐012 3‐Mar‐15 0.59 <1 <1 <2 8.1 0.1 6.2 26

UBC‐012 17‐Mar‐15 0.6 <1 <1 <2 8.7 0.22 7.2 27

UBC‐012 31‐Mar‐15 0.6 <1 <1 <2 9.5 0.12 7.9 27

UBC‐012 14‐Apr‐15 0.5 <1 <1 <2 8 0.15 7.0 27

UBC‐012 28‐Apr‐15 0.5 <1 <1 <2 9.7 0.14 6.8 26

UBC‐012 12‐May‐15 0.54 <1 <1 4 11 0.1 7.4 28

UBC‐012 26‐May‐15 0.48 <1 <1 <2 11 0.17 7.8 27

UBC‐012 9‐Jun‐15 0.52 <1 <1 2 13 0.11 7.3 31

UBC‐012 23‐Jun‐15 0.81 <1 <1 <2 13 0.13 6.9 31

UBC‐012 7‐Jul‐15 0.7 <1 <1 <2 15 0.35 7.3 31

UBC‐012 21‐Jul‐15 0.63 <1 <1 <2 17 0.21 6.8 34

UBC‐012 4‐Aug‐15 0.59 <1 <1 <2 18 0.32 6.9 34

UBC‐012 18‐Aug‐15 0.61 <1 <1 <2 18 0.21 6.0 35

UBC‐012 1‐Sep‐15 0.7 <1 <1 <2 18 0.19 7.6 32

UBC‐012 15‐Sep‐15 0.71 <1 <1 <2 15 0.18 7.4 37

UBC‐012 29‐Sep‐15 0.68 <1 <1 2 14 0.14 7.3 35

UBC‐012 13‐Oct‐15 0.84 <1 <1 <2 15 0.28 7.3 37

UBC‐012 27‐Oct‐15 0.81 <1 <1 <2 13 0.1 7.3 33

UBC‐012 10‐Nov‐15 0.9 <1 <1 <2 11 0.13 5.7 31

UBC‐012 17‐Nov‐15 0.62 <1 <1 <2 11 0.28 6.0 30

UBC‐012 24‐Nov‐15 0.84 <1 <1 <2 8.4 0.13 7.3 31

UBC‐012 1‐Dec‐15 0.65 <1 <1 <2 8.9 0.1 6.3 29

UBC‐012 8‐Dec‐15 0.6 <1 <1 <2 9 0.16 7.5 25

UBC‐012 15‐Dec‐15 1.3 <1 <1 <2 8.7 0.23 7.3 25

UBC‐012 22‐Dec‐15 0.76 <1 <1 NA 7.4 0.11 7.2 26

UBC‐012 29‐Dec‐15 0.68 <1 <1 NA 7.4 0.11 7.7 29

Analyses by Metro Vancouver Laboratory‐2015

Page 46: University of British Columbiaenergy.sites.olt.ubc.ca/files/2016/10/UBC-WQM-Report-2015.pdf · University of British Columbia Drinking Water Quality Monitoring Report 2015 May 2016

Sample Point WQM8-012 (UBC-012)

0

2

4

6

8

10

12

14

0

0.2

0.4

0.6

0.8

1

1.2

1.4

HP

C C

FU/m

L

CI2

Fre

e m

g/L

Free CI2 and HPC at Sample Point UBC-012

CI2

HPC

00.10.20.30.40.50.60.70.80.91

00.10.20.30.40.50.60.70.80.9

1

6-J

an-1

5

6-F

eb

-15

6-M

ar-1

5

6-A

pr-

15

6-M

ay-1

5

6-J

un

-15

6-J

ul-

15

6-A

ug-

15

6-S

ep

-15

6-O

ct-1

5

6-N

ov-

15

6-D

ec-1

5

E C

oli

MF/

10

0 m

L

T C

oli

MF/

10

0 m

L

Total and Faecal Coliforms at Sample Point UBC-012

Total coliform

E Coli

0

0.05

0.1

0.15

0.2

0.25

0.3

0.35

0.4

02468

101214161820

Turb

idit

y N

TU

Tem

pe

ratu

re D

egr

ee

s

Temperature and Turbidity at Sample Point UBC-012

Temperature

Turbidity

0

5

10

15

20

25

30

35

40

0.01.02.03.04.05.06.07.08.09.0

Co

nd

uct

ivit

y u

S/cm

pH

pH and Conductivity at Sample Point UBC-012

pH

Conductivity

Page 47: University of British Columbiaenergy.sites.olt.ubc.ca/files/2016/10/UBC-WQM-Report-2015.pdf · University of British Columbia Drinking Water Quality Monitoring Report 2015 May 2016

Sample Point WQN9‐013 (UBC‐013)

Sampling 

point

Sampled 

date

Chlorine Free 

mg/L

Total Coliform MF/100 mLs

Total Coliform 

MPN/100 mL

Ecoli MF/100mLs

E Coli MPN/100 mL

HPC CFU/mls

Temper‐

ature °C

Turbidity 

NTU pH

Conductivity

uS/cm

UBC‐013 6‐Jan‐15 0.54 <1 <1 <2 8.2 0.14 7.9 31

UBC‐013 13‐Jan‐15 0.57 <1 <1 <2 6.6 0.09 7.9 30

UBC‐013 20‐Jan‐15 0.57 <1 <1 <2 6 0.09 7.8 29

UBC‐013 27‐Jan‐15 0.54 <1 <1 <2 7.1 0.13 6.9 29

UBC‐013 3‐Feb‐15 0.45 <1 <1 <2 8.1 0.12 7.4 28

UBC‐013 10‐Feb‐15 0.4 <1 <1 2 8.7 0.09 7.2 28

UBC‐013 17‐Feb‐15 0.66 <1 <1 <2 7.8 0.1 7.3 26

UBC‐013 24‐Feb‐15 0.41 <1 <1 <2 8.3 0.09 7.1 27

UBC‐013 3‐Mar‐15 0.59 <1 <1 <2 7.3 0.09 6.6 26

UBC‐013 10‐Mar‐15 0.67 <1 <1 <2 7.4 0.58 7.2 26

UBC‐013 17‐Mar‐15 0.68 <1 <1 <2 7.8 0.1 7.3 27

UBC‐013 24‐Mar‐15 0.68 <1 <1 <2 7.9 0.08 7.2 27

UBC‐013 31‐Mar‐15 0.55 <1 <1 2 9.6 0.11 7.8 26

UBC‐013 7‐Apr‐15 0.66 <1 <1 <2 9 0.12 6.4 27

UBC‐013 14‐Apr‐15 0.53 <1 <1 <2 8 0.15 7.1 27

UBC‐013 21‐Apr‐15 0.7 <1 <1 <2 8.6 0.14 8.0 28

UBC‐013 28‐Apr‐15 0.54 <1 <1 <2 9.7 0.08 7.1 28

UBC‐013 5‐May‐15 0.65 <1 <1 <2 9 0.11 6.9 28

UBC‐013 12‐May‐15 0.54 <1 <1 14 10 0.12 7.0 28

UBC‐013 19‐May‐15 0.66 <1 <1 2 10 0.28 7.5 24

UBC‐013 26‐May‐15 0.57 <1 <1 <2 11 0.13 7.5 28

UBC‐013 2‐Jun‐15 0.55 <1 <1 <2 12 0.17 6.5 30

UBC‐013 9‐Jun‐15 0.52 <1 <1 <2 31 0.12 7.8 29

UBC‐013 16‐Jun‐15 0.64 <1 <1 <2 12 0.13 7.2 32

UBC‐013 23‐Jun‐15 0.78 <1 <1 <2 12 0.16 6.9 30

UBC‐013 30‐Jun‐15 0.73 <1 <1 <2 14 0.21 7.5 29

UBC‐013 7‐Jul‐15 0.69 <1 <1 <2 15 0.12 7.4 30

UBC‐013 14‐Jul‐15 0.7 <1 <1 <2 16 0.14 6.7 32

UBC‐013 21‐Jul‐15 0.47 <1 <1 <2 16 0.14 6.9 35

UBC‐013 28‐Jul‐15 0.6 <1 <1 <2 17 0.58 6.9 34

UBC‐013 4‐Aug‐15 0.79 <1 <1 <2 17 0.35 7.0 32

UBC‐013 11‐Aug‐15 0.77 <1 <1 <2 17 0.31 6.6 33

UBC‐013 18‐Aug‐15 0.78 <1 <1 <2 17 0.22 5.9 32

UBC‐013 25‐Aug‐15 0.84 <1 <1 <2 17 0.25 7.4 35

UBC‐013 1‐Sep‐15 0.75 <1 <1 <2 17 0.23 7.6 31

UBC‐013 8‐Sep‐15 0.63 <1 <1 <2 15 0.14 7.4 25

UBC‐013 15‐Sep‐15 0.81 <1 <1 <2 14 0.51 7.4 37

UBC‐013 22‐Sep‐15 0.62 <1 <1 <2 14 0.17 7.4 35

UBC‐013 29‐Sep‐15 0.67 <1 <1 4 14 0.24 7.4 34

UBC‐013 6‐Oct‐15 0.75 <1 <1 <2 14 0.18 7.1 33

UBC‐013 13‐Oct‐15 0.71 <1 <1 <2 14 0.2 7.2 36

UBC‐013 20‐Oct‐15 0.74 <1 <1 <2 13 0.21 7.1 36

UBC‐013 27‐Oct‐15 0.88 <1 <1 <2 12 0.16 7.2 34

UBC‐013 3‐Nov‐15 0.76 <1 <1 <2 12 0.16 7.3 35

UBC‐013 10‐Nov‐15 0.82 <1 <1 <2 10 0.16 5.9 30

UBC‐013 17‐Nov‐15 0.52 <1 <1 <2 9.2 0.15 6.0 29

UBC‐013 24‐Nov‐15 0.68 <1 <1 <2 7 0.11 7.3 30

UBC‐013 1‐Dec‐15 0.68 <1 <1 2 7.4 0.09 6.2 30

UBC‐013 8‐Dec‐15 0.76 <1 <1 <2 7.6 0.15 7.5 25

UBC‐013 15‐Dec‐15 0.79 <1 <1 <2 7.5 0.21 7.2 22

UBC‐013 22‐Dec‐15 0.8 <1 <1 NA 6.6 0.1 7.2 26

UBC‐013 29‐Dec‐15 0.83 <1 <1 NA 6 0.09 7.7 30

Analyses by Metro Vancouver Laboratory‐2015

Page 48: University of British Columbiaenergy.sites.olt.ubc.ca/files/2016/10/UBC-WQM-Report-2015.pdf · University of British Columbia Drinking Water Quality Monitoring Report 2015 May 2016

Sample Point WQN9-013 (UBC-013)

0

2

4

6

8

10

12

14

16

00.10.20.30.40.50.60.70.80.9

1

HP

C C

FU/m

L

CI2

Fre

e m

g/L

Free CI2 and HPC at Sample Station UBC-013

CI2

HPC

00.10.20.30.40.50.60.70.80.91

00.10.20.30.40.50.60.70.80.9

1

6-J

an-1

5

6-F

eb

-15

6-M

ar-1

5

6-A

pr-

15

6-M

ay-1

5

6-J

un

-15

6-J

ul-

15

6-A

ug-

15

6-S

ep

-15

6-O

ct-1

5

6-N

ov-

15

6-D

ec-1

5

E C

oli

MF/

10

0 m

L

T C

oli

MF/

10

0 m

L

Total and Faecal Coliforms at Sample Point UBC-013

Total Coliform

E Coli

0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0

5

10

15

20

25

30

35Tu

rbid

ity

NTU

Tem

pe

ratu

re D

egr

ee

s

Temperature and Turbidity at Sample Point UBC-013

Temperature

Turbidity

0

5

10

15

20

25

30

35

40

0.01.02.03.04.05.06.07.08.09.0

Co

nd

uct

ivit

y u

S/cm

pH

pH and Conductivity at Sample Point UBC-013

pH

Conductivity

Page 49: University of British Columbiaenergy.sites.olt.ubc.ca/files/2016/10/UBC-WQM-Report-2015.pdf · University of British Columbia Drinking Water Quality Monitoring Report 2015 May 2016

Sample Point WQQ6‐014 (UBC‐014)

Sampling 

point

Sampled 

date

Chlorine Free 

mg/L

Total Coliform MF/100 mLs

Total Coliform 

MPN/100 mL

Ecoli MF/100mLs

E Coli MPN/100 mL

HPC CFU/mls

Temper‐

ature °C

Turbidity 

NTU pH

Conductivity

uS/cm

UBC‐014 6‐Jan‐15 0.58 <1 <1 <2 7.9 0.15 7.6 27

UBC‐014 13‐Jan‐15 0.56 <1 <1 <2 7.3 0.41 7.4 28

UBC‐014 20‐Jan‐15 0.51 <1 <1 <2 6.1 0.14 7.6 29

UBC‐014 27‐Jan‐15 0.52 <1 <1 2 8.4 0.17 7.2 29

UBC‐014 3‐Feb‐15 0.38 <1 <1 2 8.4 0.15 7.1 28

UBC‐014 10‐Feb‐15 0.45 <1 <1 2 9.1 0.29 7.4 28

UBC‐014 17‐Feb‐15 0.48 <1 <1 2 7.9 0.13 7.2 27

UBC‐014 24‐Feb‐15 0.51 <1 <1 <2 8.8 0.11 7.2 26

UBC‐014 3‐Mar‐15 0.55 <1 <1 <2 8.8 0.12 7.0 27

UBC‐014 10‐Mar‐15 0.53 <1 <1 <2 8.5 0.23 7.4 27

UBC‐014 17‐Mar‐15 0.58 <1 <1 <2 8.5 0.14 7.4 28

UBC‐014 24‐Mar‐15 0.57 <1 <1 <2 9 0.11 7.2 29

UBC‐014 31‐Mar‐15 0.51 <1 <1 2 9.6 0.12 7.8 27

UBC‐014 7‐Apr‐15 0.55 <1 <1 <2 9.6 0.35 6.2 27

UBC‐014 14‐Apr‐15 0.51 <1 <1 <2 8.8 0.18 7.1 26

UBC‐014 21‐Apr‐15 0.66 <1 <1 2 10 0.18 7.9 30

UBC‐014 28‐Apr‐15 0.52 <1 <1 <2 9.7 0.15 6.6 27

UBC‐014 5‐May‐15 0.51 <1 <1 <2 10 0.11 6.7 29

UBC‐014 12‐May‐15 0.64 <1 <1 <2 12 0.14 7.0 28

UBC‐014 19‐May‐15 0.66 <1 <1 2 11 0.34 7.5 25

UBC‐014 26‐May‐15 0.51 <1 <1 6 11 0.13 7.1 27

UBC‐014 2‐Jun‐15 0.48 <1 <1 6 12 0.14 6.8 29

UBC‐014 9‐Jun‐15 0.57 <1 <1 40 13 0.09 7.5 30

UBC‐014 16‐Jun‐15 0.69 <1 <1 <2 13 0.16 7.3 32

UBC‐014 23‐Jun‐15 0.68 <1 <1 <2 13 0.19 6.9 32

UBC‐014 30‐Jun‐15 0.69 <1 <1 <2 15 0.32 7.4 30

UBC‐014 7‐Jul‐15 0.66 <1 <1 <2 15 0.13 7.3 31

UBC‐014 14‐Jul‐15 0.67 <1 <1 <2 18 0.17 7.0 33

UBC‐014 21‐Jul‐15 0.46 <1 <1 2 17 0.21 6.8 36

UBC‐014 28‐Jul‐15 0.51 <1 <1 <2 17 0.18 7.0 36

UBC‐014 4‐Aug‐15 0.59 <1 <1 <2 17 0.25 7.0 34

UBC‐014 11‐Aug‐15 0.88 <1 <1 2 17 1 6.6 34

UBC‐014 18‐Aug‐15 0.63 1 <1 <2 17 0.2 6.0 35

UBC‐014 25‐Aug‐15 0.63 <1 <1 <2 17 0.24 7.5 38

UBC‐014 1‐Sep‐15 0.52 <1 <1 <2 17 0.19 7.6 33

UBC‐014 8‐Sep‐15 0.68 <1 <1 <2 16 0.13 7.6 25

UBC‐014 15‐Sep‐15 0.56 <1 <1 <2 15 0.15 7.1 38

UBC‐014 22‐Sep‐15 0.56 <1 <1 <2 15 0.13 7.4 37

UBC‐014 29‐Sep‐15 0.59 <1 <1 <2 14 0.15 7.4 36

UBC‐014 6‐Oct‐15 0.64 <1 <1 <2 14 0.12 7.2 35

UBC‐014 13‐Oct‐15 0.7 <1 <1 <2 14 0.1 7.0 36

UBC‐014 20‐Oct‐15 0.84 <1 <1 <2 14 3.1 7.1 38

UBC‐014 27‐Oct‐15 0.62 <1 <1 <2 13 0.23 7.0 34

UBC‐014 3‐Nov‐15 0.76 <1 <1 <2 13 0.12 7.2 35

UBC‐014 10‐Nov‐15 0.91 <1 <1 <2 11 0.17 5.8 32

UBC‐014 17‐Nov‐15 0.82 <1 <1 <2 10 0.24 5.8 31

UBC‐014 24‐Nov‐15 0.62 <1 <1 <2 8.7 0.13 7.5 31

UBC‐014 1‐Dec‐15 0.64 <1 <1 <2 9.3 0.12 6.3 30

UBC‐014 8‐Dec‐15 0.62 <1 <1 <2 9.6 0.16 7.6 26

UBC‐014 15‐Dec‐15 1.2 <1 <1 <2 8.9 0.21 7.2 25

Analyses by Metro Vancouver Laboratory‐2015

Page 50: University of British Columbiaenergy.sites.olt.ubc.ca/files/2016/10/UBC-WQM-Report-2015.pdf · University of British Columbia Drinking Water Quality Monitoring Report 2015 May 2016

Sample Point WQQ6-014 (UBC-014)

051015202530354045

0

0.2

0.4

0.6

0.8

1

1.2

1.4

6-J

an-1

5

6-F

eb

-15

6-M

ar-1

5

6-A

pr-

15

6-M

ay-1

5

6-J

un

-15

6-J

ul-

15

6-A

ug-

15

6-S

ep

-15

6-O

ct-1

5

6-N

ov-

15

6-D

ec-1

5

HP

C C

FU/m

L

CI2

Fre

e m

g/L

Free CI2 and HPC at Sample Point UBC-014

CI2

HPC

00.10.20.30.40.50.60.70.80.91

0

0.2

0.4

0.6

0.8

1

1.2

E C

oli

MF/

10

0 m

L

T C

oli

MF/

10

0 m

L

Total and Faecal Coliforms at Sample Point UBC-014

Total Coliform

E Coli

0

0.5

1

1.5

2

2.5

3

3.5

02468

101214161820

Turb

idit

y N

TU

Tem

pe

ratu

re D

egr

ee

s

Temperature and Turbidity at Sample Point UBC-014

Temperature

Turbidity

0

5

10

15

20

25

30

35

40

0.01.02.03.04.05.06.07.08.09.0

Co

nd

uct

ivit

y u

S/cm

pH

pH and Conductivity at Sample Point UBC-014

pH

Conductivity

Page 51: University of British Columbiaenergy.sites.olt.ubc.ca/files/2016/10/UBC-WQM-Report-2015.pdf · University of British Columbia Drinking Water Quality Monitoring Report 2015 May 2016

Sample Point WQQ7‐015 (UBC‐015)

Sampling 

point

Sampled 

date

Chlorine Free 

mg/L

Total Coliform MF/100 mLs

Total Coliform 

MPN/100 mL

Ecoli MF/100mLs

E Coli MPN/100 mL

HPC CFU/mls

Temper‐

ature °C

Turbidity 

NTU pH

Conductivity

uS/cm

UBC‐015 6‐Jan‐15 0.51 <1 <1 4 8 0.15 7.8 28

UBC‐015 13‐Jan‐15 0.51 <1 <1 40 6.9 0.11 7.8 27

UBC‐015 20‐Jan‐15 0.55 <1 <1 <2 6.8 0.1 7.6 35

UBC‐015 27‐Jan‐15 0.47 <1 <1 6 8.7 0.36 7.2 29

UBC‐015 3‐Feb‐15 0.43 <1 <1 <2 8.1 0.15 7.0 28

UBC‐015 10‐Feb‐15 0.51 <1 <1 18 8.8 0.35 7.1 29

UBC‐015 17‐Feb‐15 0.53 <1 <1 <2 8.4 0.14 7.4 29

UBC‐015 24‐Feb‐15 0.42 <1 <1 <2 9.9 0.3 7.5 26

UBC‐015 3‐Mar‐15 0.46 <1 <1 <2 8.3 0.11 7.5 31

UBC‐015 11‐Mar‐15 0.57 <1 <1 <2 8.7 0.14 7.3 28

UBC‐015 17‐Mar‐15 0.64 <1 <1 <2 8.5 0.13 7.6 29

UBC‐015 24‐Mar‐15 0.62 <1 <1 <2 8.6 0.09 7.1 28

UBC‐015 31‐Mar‐15 0.51 <1 <1 <2 10 0.11 7.4 26

UBC‐015 7‐Apr‐15 0.58 <1 <1 12 9.6 0.35 6.1 27

UBC‐015 14‐Apr‐15 0.54 <1 <1 <2 8.4 0.14 7.3 27

UBC‐015 21‐Apr‐15 0.71 <1 <1 <2 9.5 0.15 7.9 30

UBC‐015 28‐Apr‐15 0.52 <1 <1 28 9.7 0.15 7.0 27

UBC‐015 5‐May‐15 0.63 <1 <1 26 10 0.1 6.7 29

UBC‐015 12‐May‐15 0.62 <1 <1 8 12 0.84 6.7 27

UBC‐015 19‐May‐15 0.64 <1 <1 18 11 0.29 7.3 25

UBC‐015 26‐May‐15 0.53 <1 <1 <2 11 0.13 7.2 28

UBC‐015 2‐Jun‐15 0.53 <1 <1 110 12 0.3 6.3 31

UBC‐015 9‐Jun‐15 0.48 <1 <1 6 13 0.12 7.1 31

UBC‐015 16‐Jun‐15 0.62 <1 <1 34 13 0.19 7.2 31

UBC‐015 23‐Jun‐15 0.63 <1 <1 <2 12 0.15 7.1 32

UBC‐015 30‐Jun‐15 0.74 <1 <1 20 14 0.21 7.4 29

UBC‐015 7‐Jul‐15 0.67 <1 <1 <2 15 0.11 7.2 33

UBC‐015 14‐Jul‐15 0.73 <1 <1 28 17 0.14 6.9 32

UBC‐015 21‐Jul‐15 0.48 <1 <1 14 18 0.18 6.8 36

UBC‐015 28‐Jul‐15 0.6 <1 <1 <2 17 0.28 6.9 34

UBC‐015 4‐Aug‐15 0.75 <1 <1 <2 18 0.34 7.4 31

UBC‐015 11‐Aug‐15 0.7 <1 <1 <2 18 0.49 6.4 34

UBC‐015 18‐Aug‐15 0.71 1 <1 2 17 0.24 5.7 34

UBC‐015 25‐Aug‐15 0.78 <1 <1 <2 17 0.36 7.4 35

UBC‐015 1‐Sep‐15 0.65 <1 <1 <2 17 0.25 7.2 34

UBC‐015 8‐Sep‐15 0.68 <1 <1 10 15 0.16 7.5 24

UBC‐015 15‐Sep‐15 0.65 <1 <1 <2 15 0.32 6.9 38

UBC‐015 22‐Sep‐15 0.55 <1 <1 <2 15 0.15 7.4 35

UBC‐015 29‐Sep‐15 0.62 <1 <1 <2 14 0.36 7.4 33

UBC‐015 6‐Oct‐15 0.68 <1 <1 2 14 0.2 7.1 32

UBC‐015 13‐Oct‐15 0.73 <1 <1 32 14 0.17 6.5 36

UBC‐015 20‐Oct‐15 0.74 <1 <1 24 14 0.3 6.8 36

UBC‐015 27‐Oct‐15 0.67 <1 <1 8 13 1.2 6.6 35

UBC‐015 3‐Nov‐15 0.77 <1 <1 2 12 0.2 7.1 33

UBC‐015 10‐Nov‐15 0.62 <1 <1 20 10 0.13 5.5 31

UBC‐015 17‐Nov‐15 0.58 <1 <1 24 10 0.29 5.8 30

UBC‐015 24‐Nov‐15 0.62 <1 <1 26 7.4 0.1 7.4 30

UBC‐015 1‐Dec‐15 0.68 <1 <1 <2 7.7 0.12 6.1 29

UBC‐015 8‐Dec‐15 0.7 <1 <1 <2 8 0.1 7.5 27

UBC‐015 15‐Dec‐15 0.88 <1 <1 2 7.8 0.24 7.0 22

UBC‐015 22‐Dec‐15 0.71 <1 <1 NA 6.7 0.12 7.2 27

UBC‐015 29‐Dec‐15 0.59 <1 <1 NA 6.1 0.09 7.7 26

Analyses by Metro Vancouver Laboratory‐2015

Page 52: University of British Columbiaenergy.sites.olt.ubc.ca/files/2016/10/UBC-WQM-Report-2015.pdf · University of British Columbia Drinking Water Quality Monitoring Report 2015 May 2016

Sample Point WQQ7-015 (UBC-015)

0

20

40

60

80

100

120

00.10.20.30.40.50.60.70.80.9

1

HP

C C

FU/m

L

CI2

Fre

e m

g/L

Free CI2 and HPC at Sample Point UBC-015

CI2

HPC

00.10.20.30.40.50.60.70.80.91

0

0.2

0.4

0.6

0.8

1

1.2

E C

oli

MF/

10

0 m

L

T C

oli

MF/

10

0 m

L

Total and Faecal Coliforms at Sample Point UBC-015

Total Coliforms

E Coli

0

0.2

0.4

0.6

0.8

1

1.2

1.4

02468

101214161820

Turb

idit

y N

TU

Tem

pe

ratu

re D

egr

ee

s

Temperature and Turbidity at Sample Station UBC-015

Temperature

Turbidity

0

5

10

15

20

25

30

35

40

0.01.02.03.04.05.06.07.08.09.0

Co

nd

uct

ivit

y u

S/cm

pH

pH and Conductivity at Sample Point UBC-015

pH

Conductivity

Page 53: University of British Columbiaenergy.sites.olt.ubc.ca/files/2016/10/UBC-WQM-Report-2015.pdf · University of British Columbia Drinking Water Quality Monitoring Report 2015 May 2016

Sample Point WQT7‐016 (UBC‐016)

Sampling 

point

Sampled 

date

Chlorine Free 

mg/L

Total Coliform MF/100 mLs

Total Coliform 

MPN/100 mL

Ecoli MF/100mLs

E Coli MPN/100 mL

HPC CFU/mls

Temper‐

ature °C

Turbidity 

NTU pH

Conductivity

uS/cm

UBC‐016 13‐Jan‐15 0.48 <1 <1 2 6.9 0.27 7.8 28

UBC‐016 27‐Jan‐15 0.51 <1 <1 2 8.7 0.44 7.1 31

UBC‐016 10‐Feb‐15 0.42 <1 <1 6 9.1 0.39 7.1 28

UBC‐016 24‐Feb‐15 0.47 <1 <1 <2 10 0.29 7.3 28

UBC‐016 10‐Mar‐15 0.55 <1 <1 <2 8.8 0.24 7.6 27

UBC‐016 24‐Mar‐15 0.49 <1 <1 <2 9.5 0.38 7.1 29

UBC‐016 7‐Apr‐15 0.49 <1 <1 2 9.8 0.46 6.1 28

UBC‐016 21‐Apr‐15 0.62 <1 <1 2 10 0.15 7.9 30

UBC‐016 5‐May‐15 0.6 <1 <1 <2 10 0.12 6.7 29

UBC‐016 19‐May‐15 0.66 <1 <1 4 12 0.31 6.6 25

UBC‐016 2‐Jun‐15 0.43 <1 <1 64 12 0.45 6.2 31

UBC‐016 16‐Jun‐15 0.64 <1 <1 <2 13 0.44 7.1 32

UBC‐016 30‐Jun‐15 0.53 <1 <1 <2 15 0.18 7.3 27

UBC‐016 14‐Jul‐15 0.63 <1 <1 <2 18 0.25 6.9 33

UBC‐016 28‐Jul‐15 0.48 <1 <1 2 17 0.25 6.9 36

UBC‐016 11‐Aug‐15 0.72 <1 <1 2 18 2 6.1 35

UBC‐016 25‐Aug‐15 0.64 <1 <1 <2 18 0.35 7.4 36

UBC‐016 8‐Sep‐15 0.71 <1 <1 <2 16 0.16 7.1 24

UBC‐016 22‐Sep‐15 0.56 <1 <1 <2 16 0.12 7.4 38

UBC‐016 6‐Oct‐15 0.54 <1 <1 <2 15 0.14 6.8 35

UBC‐016 20‐Oct‐15 0.87 <1 <1 <2 14 4.1 6.7 37

UBC‐016 3‐Nov‐15 0.66 <1 <1 2 13 0.13 6.6 35

UBC‐016 17‐Nov‐15 0.56 <1 <1 <2 12 0.14 5.8 34

UBC‐016 1‐Dec‐15 0.62 <1 <1 <2 9.6 0.11 6.2 30

UBC‐016 15‐Dec‐15 1.1 <1 <1 <2 9.2 0.25 7.4 24

UBC‐016 29‐Dec‐15 0.55 <1 <1 NA 8.7 0.14 6.4 25

Analyses by Metro Vancouver Laboratory‐2015

Page 54: University of British Columbiaenergy.sites.olt.ubc.ca/files/2016/10/UBC-WQM-Report-2015.pdf · University of British Columbia Drinking Water Quality Monitoring Report 2015 May 2016

Sample Point WQT7-016 (UBC-016)

0

10

20

30

40

50

60

70

0

0.2

0.4

0.6

0.8

1

1.2

HP

C C

FU/m

L

CI2

Fre

e m

g/L

Free CI2 and HPC at Sample Station UBC-016

CI2

HPC

00.10.20.30.40.50.60.70.80.91

00.10.20.30.40.50.60.70.80.9

1

E C

oli

MF/

10

0 m

L

T C

oli

MF/

10

0 m

L

Total and Faecal Coliforms at Sample Point UBC-016

Total Coliforms

E Coli

00.511.522.533.544.5

02468

101214161820

Turb

idit

y N

TU

Tem

pe

ratu

re D

egr

ee

s

Temperature and Turbidity at Sample Point UBC-016

Temperature

Turbidity

0

5

10

15

20

25

30

35

40

0.01.02.03.04.05.06.07.08.09.0

Co

nd

uct

ivit

y u

S/cm

pH

pH and Conductivity at Sample Point UBC-016

pH

Conductivity

Page 55: University of British Columbiaenergy.sites.olt.ubc.ca/files/2016/10/UBC-WQM-Report-2015.pdf · University of British Columbia Drinking Water Quality Monitoring Report 2015 May 2016

University of British Columbia Drinking Water Quality Monitoring Report 2015

APPENDIX C

Metro Vancouver and Municipal Response Procedure

Page 56: University of British Columbiaenergy.sites.olt.ubc.ca/files/2016/10/UBC-WQM-Report-2015.pdf · University of British Columbia Drinking Water Quality Monitoring Report 2015 May 2016

Metro Vancouver and Municipal Response Procedures

Action will be initiated by LCOC control room operator based on information received through the SCADA system or from field staff

Control room will immediately notify:

Utility Systems Control Superintendent (or designate)

Developing Situation

High alarm limits reached at river or A at in-lake buoys.

Imminent Situation

B intake.

Control room will immediately notify: Utility

Systems Control Superintendent (or designate)

Utility Systems Control

Superintendent (or designate)

Utility Systems Control Superintendent (or designate)

Monitor situation and evaluate potential impacts. Notify the following Division Managers (or designates) as required: Quality Control, Utility Systems Operations, Water Treatment Operations and Watershed Management.

Immediate Actions: Notify Utility System Operations, Water Treatment Operations and Quality Control Division Managers (or designates.) Minimize flow from affected source and consider the need to isolate the source.

Priority Notification (immediately following steps above): Operations staff of affected municipalities.

Superintendent

of Utility Systems

Operations (or designate)

Water Treatment Operations

Division Manager (or designate)

Watershed

Management Division Manager

(or designate)

Superintendent of Utility Systems

Operations (or designate)

Water Treatment Operations

Division Manager (or designate)

Quality Control

Division Manager (or designate)

Watershed

Management Division Manager

(or designate)

Prepare operations field crews to isolate source if necessary.

Increase chlorine residual up to a level as high as 1.5 mg/L, if possible, at both primary and secondary disinfection stations.

Increase ozone CT at Coquitlam if possible.

Notify affected municipalities of treatment changes.

Investigate cause of the turbidity event.

Advise Utility Systems Control Superintendent (or designate) as required.

Make further adjustments to water treatment as required taking changes made under A into account. Confirm treatment changes with Quality Control. Prepare to assist with isolating source.

Evaluate and monitor situation - collect water quality information as required. Notify: Metro Vancouver MHO (or delegate) and other DWOs (or DWO delegates) for extraordinary turbidity events. Notify: Metro Vancouver Communications, O&M Department Manager, Commissioner and Water Quality Contacts of affected municipalities.

Situation escalates (confirmation of rising turbidity readings, visual

confirmation of slides etc.).

GVRD Communications

If Required: Notify: Board Chair, Water Committee Chair and Board members of affected municipalities. For extraordinary turbidity events, notify public by issuing press release.

*UBC Emergency Response Procedure Scenarios W4 & W6

Municipalities*

Increase Cl2 residual at existing municipal secondary disinfection stations by up to 0.5

mg/L above usual treatment levels, if possible. For extraordinary turbidity events, notify local

public health contacts. Updated October 2007

Isolate source (as directed) with the assistance of Water Treatment.

Investigate cause of the turbidity event. Advise Manager of Utility Systems Operations and the Quality Control Division Manager (or designates) of findings.

Situation ends (readings fall, no

evidence of slides, etc.).

Superintendent (or designate)

Page 57: University of British Columbiaenergy.sites.olt.ubc.ca/files/2016/10/UBC-WQM-Report-2015.pdf · University of British Columbia Drinking Water Quality Monitoring Report 2015 May 2016

University of British Columbia Drinking Water Quality Monitoring Report 2015

APPENDIX D

Source Water Quality Summary Tables for Capilano, Seymour and Coquitlam Reservoirs

Page 58: University of British Columbiaenergy.sites.olt.ubc.ca/files/2016/10/UBC-WQM-Report-2015.pdf · University of British Columbia Drinking Water Quality Monitoring Report 2015 May 2016

28

18285901

Page 59: University of British Columbiaenergy.sites.olt.ubc.ca/files/2016/10/UBC-WQM-Report-2015.pdf · University of British Columbia Drinking Water Quality Monitoring Report 2015 May 2016

29

18285901

Page 60: University of British Columbiaenergy.sites.olt.ubc.ca/files/2016/10/UBC-WQM-Report-2015.pdf · University of British Columbia Drinking Water Quality Monitoring Report 2015 May 2016

30

18285901