Universal Gland Flameproof System Size Ref (Conduit Size) Part No.Gland BodyGland NutMetric/ NPT Max...
-
Upload
karley-rutland -
Category
Documents
-
view
220 -
download
2
Transcript of Universal Gland Flameproof System Size Ref (Conduit Size) Part No.Gland BodyGland NutMetric/ NPT Max...
Universal GlandFlameproof System
Size Ref(Conduit
Size)
Part No. Gland Body Gland Nut Metric/NPT
Max Dia.Over Cores
Max Dia.Over Single
Core
Max No.Of Cores
OverallLength
A/F A/C A/F A/C Thread
16 – 3/8”HAM*0304U
28.6 31.0 32.0 34.0M16 M20
10.5 10.0 956.0
HAA*0304U 3/8” ½” 60.0
20 – ½”HAM*0404U
28.6 31.0 32.0 34.0M20 M20
13.0 13.0 1556.0
HAA*0404U ½” ½” 60.0
25 – ¾”HAM*0505U
34.0 37.034.0
34.9 SS37.0
M25 M2517.9 17.9 28
56.0
HAA*0505U 3/4” ¾” 65.4
32 – 1”HAM*0606U
42.0 45.042.0
42.5 SS45.0
M32 M3224.0 20.0 50
56.0
HAA*0606U 1” 1” 65.4
40 – 1 ¼”HAM*0707U
50.0 54.0 52.0 57.0M40 M40
32.0 32.0 7560.0
HAA*0707U 1 ¼” 1 ¼” 71.0
50 – 1 ½”HAM*0808U
60.0 64.0 60.0 64.0M50 M50
35.0 35.0 8063.0
HAA*0808U 1 ½” 1 ½” 71.0
63 – 2”HAM*0909U
70.0 76.070.0
69.8 SS76.0
M63 M6345.0 45.0 100
74.0
HAA*0909U 2” 2” 81.0
Description - Group 1 Flameproof Barrier Gland For use with all conduit types via female threaded entry
IP66, -60°C to +130°C
Exd I&IIC Exe I&II Extb IIIC
Intended Use - Groups I and II
Zones 1, 2, 21 and 22
Class I Div I BCD (Rigid Conduit Only)
Class II Div I EFG
Exde I Mb
Exde IIC Gb
Extb IIIC Db
Material - Manufactured in Brass, Nickel Plated Brass and Stainless Steel 316
HA* - Brass HA*M – Nickel Plated Brass HA*S – Stainless Steel
Compatible Conduits - Suitable for all conduits including:
Rigid - Metallic - Non Metallic
Approvals - ATEX directive 94/9/EC (ATEX 95) to standardsIEC60079-0:2007 Ed 5, IEC60079-1:2007 Ed 6, IEC60079-7:2007 Ed 4, IEC60079-31:2008 Ed 1
EN60079-0:2009 EN60079-1:2007 EN60079-7:2007 EN60079-31:2008
Certifications - ATEX IECEx CSA
SIRA09ATEX1231X IECEx SIRA09.0103X 2310045
The Company’s policy is one of continuous improvement and reserves the right to change specifications at any time without prior notice.
NON METALLIC (SILICON) PARTS HAVE PASSED THE REQUIREMENTS OF IEC/EN60079-0 FOR AGE TESTING AND ARE THIRD PARTY APPROVED.
9/5/12
Gland comes complete with two part epoxy putty, gloves and fitting instructions.Putty can be obtained separately if required in 50g and 75g sizes. Part codes EXEP/50 & EXEP/75
Universal GlandFlameproof System
Size Ref(Conduit
Size)
Part No. Gland Body 90° Elbow Metric/NPT
Max Dia.Over Cores
Max Dia.Over Single
Core
Max No.Of Cores
OverallLength
A/F A/C A/F Conduit
16 – 3/8”HAM*0304E
28.6 31.0 32.0 16mmM20
10.5 10.0 9 90.0HAA*0304E ½”
20 – ½”HAM*0404E
28.6 31.0 32.0 20mmM20
13.0 13.0 15 90.0HAA*0404E ½”
25 – ¾”HAM*0505E
34.0 37.034.0
34.9 SS25mm
M2517.9 17.9 28 104.0
HAA*0505E ¾”
32 – 1”HAM*0606E
42.0 45.042.0
42.5 SS32mm
M3224.0 20.0 50 114.0
HAA*0606E 1”
40 – 1 ¼”HAM*0707E
50.0 54.0 52.0 40mmM40
32.0 32.0 75 180.0HAA*0707E 1 ¼”
50 – 1 ½”HAM*0808E
60.0 64.0 60.0 50mmM50
35.0 35.0 80 146.0HAA*0808E 1 ½”
63 – 2”HAM*0909E
70.0 76.070.0
69.8 SS63mm
M6345.0 45.0 100 169.0
HAA*0909E 2”
Description - Group 1 Flameproof Barrier Gland For use with Liquid Tight Flexible Conduits
IP66
-60°C to +130°C
Exd I&IIC Exe I&II Extb IIIC
Intended Use - Groups I and IIZones 1, 2, 21 and 22
Class I Div I BCD (Rigid Conduit Only)
Class II Div I EFG
Exde I Mb
Exde IIC Gb
Extd IIIC Db
Material - Manufactured in Brass, Nickel Plated Brass and Stainless Steel 316
HA* - Brass HA*M – Nickel Plated Brass HA*S – Stainless Steel
Compatible Conduits - EXLB, EXLT, EXLH, EXLLH, EXLBBT, EXLHC EXSB, EXST, EXSH, EXSLLH, EXSBBT, EXSLHC
Approvals - ATEX directive 94/9/EC (ATEX 95) to standardsIEC60079-0:2007 Ed 5, IEC60079-1:2007 Ed 6, IEC60079-7:2007 Ed 4, IEC60079-31:2008 Ed 1
EN60079-0:2009 EN60079-1:2007 EN60079-7:2007 EN60079-31:2008
Certifications - ATEX IECEx CSA
SIRA09ATEX1231X IECEx SIRA09.0103X 2310045
The Company’s policy is one of continuous improvement and reserves the right to change specifications at any time without prior notice.
NON METALLIC (SILICON) PARTS HAVE PASSED THE REQUIREMENTS OF IEC/EN60079-0 FOR AGE TESTING AND ARE THIRD PARTY APPROVED.
11/04/23
Gland comes complete with two part epoxy putty, gloves and fitting instructions.Putty can be obtained separately if required in 50g and 75g sizes. Part codes EXEP/50 & EXEP/75
Universal GlandFlameproof System
Size Ref(Conduit
Size)
Part No. Gland Body Gland Nut Metric/NPT
Max Dia.Over Cores
Max Dia.Over Single
Core
Max No.Of Cores
OverallLength
A/F A/C A/F A/C
16 – 3/8”HAM*0304G1
28.6 31.0 32.0 34.0M20
10.5 10.0 9 50.0HAA*0304G1 ½”
20 – ½”HAM*0404G1
28.6 31.0 32.0 34.0M20
13.0 13.0 15 50.0HAA*0404G1 ½”
25 – ¾”HAM*0505G1
34.0 37.034.0
34.9 SS37.0
M2517.9 17.9 28 50.0
HAA*0505G1 ¾”
32 – 1”HAM*0606G1
42.0 45.042.0
42.5 SS45.0
M3224.0 20.0 50 50.0
HAA*0606G1 1”
40 – 1 ¼”HAM*0707G1
50.0 54.0 52.0 57.0M40
32.0 32.0 75 57.0HAA*0707G1 1 ¼”
50 – 1 ½”HAM*0808G1
60.0 64.0 60.0 64.0M50
35.0 35.0 80 58.0HAA*0808G1 1 ½”
63 – 2”HAM*0909G1
70.0 76.070.0
69.8 SS76.0
M6345.0 45.0 100 70.0
HAA*0909G1 2”
Description - Group 1 Flameproof Barrier Gland For use with Liquid Tight Flexible Conduits
IP66, -60°C to +130°C
Exd I&IIC Exe I&II Extb IIIC
Intended Use - Group I and II
Zones 1, 2, 21 & 22
Class I Div II ABCD
Class II Div I EFG
Exde I Mb
Exde IIC Gb
Extb IIIC Db
Material - Manufactured in Brass, Nickel Plated Brass and Stainless Steel 316
HA* - Brass HA*M – Nickel Plated Brass HA*S – Stainless Steel
Compatible Conduits - EXLB, EXLT, EXLH, EXLLH, EXLBBT, EXLHC EXSB, EXST, EXSH, EXSLLH, EXSBBT, EXSLHC
Approvals - ATEX directive 94/9/EC (ATEX 95) to standardsIEC60079-0:2007 Ed 5, IEC60079-1:2007 Ed 6, IEC60079-7:2007 Ed 4, IEC60079-31:2008 Ed 1
EN60079-0:2009 EN60079-1:2007 EN60079-7:2007 EN60079-31:2008
Certifications - ATEX IECEx CSA
SIRA09ATEX1231X IECEx SIRA09.0103X 2310045
The Company’s policy is one of continuous improvement and reserves the right to change specifications at any time without prior notice.
NON METALLIC (SILICON) PARTS HAVE PASSED THE REQUIREMENTS OF IEC/EN60079-0 FOR AGE TESTING AND ARE THIRD PARTY APPROVED.
9/5/12
Gland comes complete with two part epoxy putty, gloves and fitting instructions.Putty can be obtained separately if required in 50g and 75g sizes. Part codes EXEP/50 & EXEP/75