Unit III Transformers

download Unit III Transformers

of 80

Transcript of Unit III Transformers

  • 7/28/2019 Unit III Transformers

    1/80

    1

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/ EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    2/80

    22

    Output Equations Main Dimensions - KVA output forsingle and three phase transformers Window spacefactor Overall dimensions Operating characteristics Regulation No load current Temperature rise inTransformers Design of Tank -Methods of cooling ofTransformers.

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/ EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    3/80

    33

    INTRODUCTION:

    A transformer is essentially a static electromagnetic

    device consisting of two or more windings which link witha common magnetic field.

    The primary is connected to an alternating voltagesource, an alternating flux is produced whose amplitudedepends on the primary voltage and the no. of turns.

    A transformer is not an energy conversion device, but adevice that transforms electrical energy from one ormore primary a.c circuits to one or more secondary a.ccircuits with changed values of voltage and current.

    The transformer is extremely important as a componentin many different types of electric circuits, from small-signal electronic circuits to high voltage powertransmission systems.

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/ EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    4/80

    44

    IMPORTANT FUNCTIONS OF A TRANSFORMER:

    Changing voltage and current level in anelectric system.

    Matching source and load impedances for

    maximum power transfer in electronic andcontrol circuitry.

    Electrical isolation.

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/ EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    5/80

    55

    PARTS OF A TRANSFORMER

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/ EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    6/80

    66

    TYPES OF CORES

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/ EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    7/80

    77

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/ EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    8/80

    88

    CLASSIFICATION:

    Based on construction,

    i. Core type and

    ii. Shell type

    Based on application,

    i. Distribution and

    ii. Power transformers.

    CORE TYPE:

    The magnetic core is built of laminations to form a

    rectangular frame.

    The windings are arranged concentrically with each otheraround the legs or limbs.

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/ EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    9/80

    99

    The top and bottom horizontal portion of the core are

    called yoke.

    The yokes connect the 2 limbs and have a cross-

    sectional area >or =to that of limbs.

    Each limb carries one half of primary and secondary.

    The 2 windings are closely coupled together to reduce

    the leakage reactance.

    The low voltage winding is wound near the core and the

    h.v winding is wound away from the core in order to

    reduce the amount of insulating materials required.

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/ EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    10/80

    1010

    SHELL TYPE:

    The windings arte put around the central limb & the

    flux path is completed through the 2 side limbs.

    Central limb carries total mutual flux.

    Side limbs form a part of a parallel magnetic circuit& carry half the total flux.

    The cross-sectional area of the central limb is twice

    that of each side limbs.

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/ EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    11/80

    1111

    DISTRIBUTION TRANSFORMER:

    These are transformers upto 200kVA(or 500kVA)

    are used to step down distribution voltage to a

    standard service voltage.

    They are kept in operation all the 24 hours a daywhether carrying any load or not.

    The load varies from time to time & it will be on no

    load most of the time.

    So copper loss is more compared to core loss.

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/ EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    12/80

    1212

    Distribution transformers are designed with less

    iron loss and have a maximum efficiency at a load

    much lesser than the full load.

    It should have good regulation to maintain the

    variation of supply voltage within limits. So it is

    designed with small value of leakage reactance.

    POWER TRANSFORMER:

    Used in sub-stations and generating stations & have

    ratings above 200kVA.

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/ EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    13/80

    1313

    A substation has number of transformers working

    in parallel.

    During heavy loads all the transformers are put inoperation & during light loads some of them are

    disconnected.

    So power transformers should be designed to have

    a maximum efficiency at or near full load.

    Designed to have a greater leakage reactance to

    limit fault current.

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/ EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    14/80

    1414

    COMPARISON OF CORE TYPE AND SHELL TYPE:

    CORE TYPE SHELL TYPE1. Easy in design and

    construction.

    2. Has low mechanical

    strength due to non-

    bracing of windings.

    3. Reduction of leakage

    reactance is not easily

    possible.

    4. The assembly can beeasily dismantled for

    repair work.

    1. Comparatively complex.

    2. High mechanical

    strength .

    3. Reduction of leakage

    reactance is not highly

    possible.

    4. The assembly cannot be

    easily dismantled forrepair work.

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/ EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    15/80

    1515

    5. Better heat dissipation from

    windings.

    6. Has longer mean length of

    core and shorter mean

    length of coil turn, hence

    best suited for EHVrequirements.

    5. Heat is not easily

    dissipated from windings,since it is surrounded by

    core.

    6. It is not suitable for EHV

    requirements.

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/ EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    16/80

    1616

    LOW VOLTAGE WINDING HIGH VOLTAGE

    WINDING

    HH L HL H L HLH HL L

    CORECORE

    HIGH VOLTAGE AND LOW VOLTAGE WINDING OF A TRANSFORMER

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/ EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    17/80

    1717

    CROSS SECTION OF SINGLE PHASE TRANSFORMER

    Ww

    Hw

    Ww Ww

    Hw

    CROSS SECTION OF CORE

    TYPE SINGLE PHASE

    TRANSFORMER

    CROSS SECTION OF SHELL

    TYPE SINGLE PHASE

    TRANSFORMER

    WINDOW

    AREA

    WINDOW

    AREAWINDOW

    AREA

    CORE CORE

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/ EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    18/80

    1818

    OUTPUT EQUATION OF SINGLE-PHASE TRANSFORMERS

    The equation which relates the rated kVA output of

    a transformer to the area of core and window is

    called output equation.

    In transformers the output kVA depends on fluxdensity & ampere turns.

    The flux density is related to the core area and the

    ampere-turns is related to the window area.

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/ EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    19/80

    1919

    The induced emf in a transformer, E= 4.44fmT voltEmf per turn, Et = E/T

    = 4.44fm volts

    The window in a single-phase transformer contains oneprimary and one secondary winding.

    Window space factor Kw is the ratio of conductor area inwindow to the total area.

    Kw = Ac / Aw

    Conductor area in window, Ac = Kw Aw

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/ EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    20/80

    2020

    The current density is the same for both the windings.

    So current density, = Ip/ ap = Is / as

    Area of cross section of primary conductor, ap = Ip/ and

    Area of cross section of primary conductor, as = Is /

    Ampere turns, AT= TpIp = TsIsAw = total window area ;

    Kw = window space factor = Ac / AwAc = conductor area = K w Aw

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/ EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    21/80

    2121

    The total copper area in the window:

    Ac = Copper area of primary winding+ Copper area ofsecondary winding

    = (no. of primary turns area of cross section of primaryconductor)+ (no. of secondary turns area of crosssection of secondary conductor)

    Ac = Tpap + Tsas= Tp Ip /+ Ts Is / (since ap = Ip/ & as

    = Is / )= ( TpIp+ Ts Is)/= 1/ (AT+AT)

    = 2AT/

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/ EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    22/80

    2222

    On equating equation (1) & (2), we get

    KwAw = 2AT/

    Ampere turns, AT = KwAw /2

    KVA OUTPUT OF SINGLE PHASE TRANSFORMER:

    Rating in kVA ,Q = Vp Ip x 10-3

    (1) = Ep Ip x 10 -3

    = Ep ( Tp Ip )/ Tp x 10-3

    = Et AT x 10-3

    On substituting the value of Et & AT,

    Q = 4.44 f m (Kw Aw ) /2 x 10 -3

    where m = Bm AiQ = 2.22 f Bm Ai Kw Aw x 10 -3

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/ EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    23/80

    2323

    OUTPUT EQUATION OF THREE-PHASE TRANSFORMERS

    The induced emf in a transformer, E= 4.44fm

    T volt

    Voltage per turn, Et = E/T

    = 4.44fm volt In case of a three-phase transformer, each window contains

    two primary and two secondary windings.

    The total copper area in the window:

    Ac = 2Tpap + 2Tsas = ( TpIp+ Ts Is)2/= 4AT/

    since ap = Ip/ and as = Is / since AT= TpIp = TsIs ( neglecting magnetizing current)

    Aw = total window area ;Kw = window space factor = Ac / AwAc = conductor area = Kw Aw

    = 4AT/ ampere turns, AT = KwAw /4

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/ EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    24/80

    2424

    KVA OUTPUT OF THREE PHASE TRANSFORMER:

    Rating in kVA ,Q = 3 x Vp Ip x 10-3

    = 3 x Ep Ip x 10 -3

    = 3 x Ep ( Tp Ip )/ Tp x 10-3

    = 3 x Et AT x 10-3

    Q= 3 x 4.44 f m (Kw Aw ) /4 x 10 -3

    where m = Bm Ai= 3.33 f Bm Ai Kw Aw x 10 -3

    Using the output equation it can also be shown that

    E t = K kVAwhere K = 4.44 f r x 10 -3

    r = m / ATr is a constant for transformer of a given type ,service andmethod of connection, since m determines the core sectionand AT fixes the total copper area.

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/ EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    25/80

    25

    Value of K

    ( 1.0 to 1.2) for single phase shell type

    1.3 for three-phase shell type (power)

    (0.75 to 0.85) for single phase core type

    (0.6 to 0.7) for three phase core type (power)

    0.45 for three-phase core type (distribution)

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/ EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    26/80

    2626

    Output Equations Main Dimensions - KVA output forsingle and three phase transformers Window spacefactor Overall dimensions Operating characteristics Regulation No load current Temperature rise inTransformers Design of Tank -Methods of cooling ofTransformers.

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/ EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    27/80

  • 7/28/2019 Unit III Transformers

    28/80

    28

    MAIN DIMENSIONS

    (i) Design of core.

    (ii) Design of yoke.(iii)Design of winding

    28IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/ EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    29/80

    2929

    DESIGN OF CORES

    The core section of the core type transformer may be

    rectangular, square or stepped.

    Shell type transformers use cores with rectangular cross

    section.

    In core type transformers with rectangular core the ratio of

    depth to width of the core is 1.4 to 2. In shell type transformers with rectangular core the width of

    the central limb is 2 to 3 times the depth of the core.

    When circular coils are required forhigh voltage transformers

    ,square and stepped cores are used .

    Circular coils are preferred because of their superior

    mechanical characteristics.

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/ EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    30/80

    3030

    CROSS-SECTION OF TRANSFORMER CORES

    RECTANGULAR

    CORE

    SQUARE

    CORE

    STEPPED CORE

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/ EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    31/80

    3131

    SQUARE CORE:

    Let d= diameter of the

    circumscribing circle.

    Also d=diagonal of the square

    a= side of the square

    Diameter of the circumscribing circle,d = a2+a2= 2a2 = 2a

    Side of the square, a= d/2

    Gross area of the square, Agi = area of the square=a2 =

    (d/2)2 = 0.5d2

    Let stacking factor, Sf=0.9

    a

    a

    aad

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/ EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    32/80

    3232

    Net core area, Ai=Stacking factor Gross core area

    = 0.9 0.5d2

    = 0.45 d2

    Gross core area is the area including the insulation

    area.

    Net core area is the area of iron alone excludinginsulation area.

    Area of circumscribing circle = /4d2

    The ratio, Net core area/ Area of

    circumscribing circle

    = 0.45d2/( /4d2) = 0.58

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/ EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    33/80

    3333

    The ratio, Gross core area/ Area of

    circumscribing circle

    = 0.5d2 /( /4d2) = 0.64

    Core area factor is the ratio of net core area and

    square of the circumscribing circle.

    Core area factor= Net core area/square of thecircumscribing circle

    = Ai/d2 = 0.45d2 /d2

    = 0.45

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/ EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    34/80

  • 7/28/2019 Unit III Transformers

    35/80

    3535

    b

    d

    b

    a

    a

    b

    d

    b

    a

    b

    a-b/2

    a-b/2

    b

    bd

    CROSS SECTION OF TWO

    STEPPED CORE

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/ EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    36/80

    3636

    The maximum core area for a given d is obtained

    when is maximum.

    Cos= a/d; so a=dcos (1)

    sin = b/d; so b=dsin (2)

    The 2 stepped core can be divided into 3 rectangles.

    The area of three rectangles give the gross core area.

    Gross core area, Agi = ab+[(a-b)/2]b+[(a-b)/2]b

    = ab+ab-b2

    = 2ab-b

    2

    (3)

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/ EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    37/80

  • 7/28/2019 Unit III Transformers

    38/80

    3838

    So d2cos22- d22cossin =0

    d22cossin = d2cos22

    d2 sin2 = d2cos22

    sin2/cos2 =2

    tan2= 2; 2=tan-12

    = 1/2 tan-12 = 31.72When = 31.72, the dimensions of the core will give

    the maximum area for the core for a specified d.

    a=d cos ; b=d sin

    = d cos31.72; = d sin31.72

    = 0.85d; = 0.53d

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/ EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    39/80

    3939

    Substitute the values of a &b in equation (3) we get,

    Gross core area, Agi = 2ab-b2

    = 0.618d2

    Let stacking factor, Sf=0.9

    Net core area, Ai=Stacking factor Gross core

    area

    = 0.9 0.618d2

    = 0.56d2

    The ratio, Net core area/ Area of

    circumscribing circle= 0.56d2 /( /4d2)= 0.71

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/ EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    40/80

    4040

    The ratio, Gross core area/ Area of

    circumscribing circle= 0.618d2 /( /4d2) = 0.79

    Core area factor= Net core area/square of the

    circumscribing circle

    = Ai/d2 = 0.56d2 /d2

    = 0.56

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/ EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    41/80

    4141

    CHOICE FLUX DENSITY and CURRENT DENSITY ( Bmand )

    Bm determines the core area. Higher Bm smaller area smaller Lmt saving in

    the costof iron and copper.

    Buthigher Bm increases the iron loss and temp rise.

    For Distribution transformerBm =1.1 to 1.35 Wb/m2

    . For Power transformerBm =1.25 to 1.45 Wb/m

    2.

    The area of conductors for the primary and secondarywindings determined after choosing a suitable value for which depends on the methodof cooling.

    Current density value depends on method of cooling andrange is 1.1 to 2.2 A/mm2

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/ EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    42/80

    4242

    TYPES OF WINDINGS

    Cylindrical winding with circular conductors.Crossover winding with circular or rectangular

    conductors.

    Continuous disc type winding with rectangularconductors.

    Helical winding.

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/ EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    43/80

    4343

    DESIGN OF WINDING

    The design of winding involves the determination of

    no. of turns & area of cross section of the conductorused.

    The no. of turns is estimated using voltage rating &

    e.m.f per turns.

    The area of cross section is estimated using ratedcurrent & current density.

    Usually the no. of turns of L.V winding is estimated

    first using the given data & it is corrected to the

    nearest integer.

    Then the no. of turns of H.V winding are chosen to

    satisfy the voltage rating of the transformer.

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/ EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    44/80

    4444

    Number of turns in a low voltage winding,

    TLV

    = VLV

    / Et

    or AT/ILV

    where,

    VLV = rated voltage of low voltage winding.

    ILV = rated current of low voltage winding.

    Number of turns in a high voltage winding,

    THV = TLV VHV / VLV

    where,

    VHV = rated voltage of high voltage winding.Rated current in a winding =

    kVA per phase 103 /voltage rating of the winding

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/ EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    45/80

    45

    DESIGN OF YOKE

    The purpose of the yoke is to connect the legs

    providing a least reluctance path. In order to limit the

    iron loss in the yoke, operating flux density is

    reduced by increasing the yoke area.

    Generally yoke area is made 20% more than the legarea.

    In case of rectangular yoke ,

    depth of yoke = the depth of core.

    In square or stepped ,depth of core =width of largest stampings

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/ EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    46/80

    46

    DESIGN OF YOKE

    Area of yoke =depth of yoke x height of yoke= Dy x Hy

    Dy= width of largest core stamping = a

    Hy=(1.15 to 1.25) Agi for transformers using grainoriented steel

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/ EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    47/80

    4747

    OVERALL DIMENSIONS OF A TRANSFORMER

    The main dimensions of a transformer are:

    Height of the window (Hw) and

    Width of the window (Ww)

    Other important dimensions are:

    Width of the largest stamping(a)

    Diameter of the circumscribing circle(d)

    Distance between the core centres(D)

    Height of the yoke(Hy)

    Depth of the yoke(Dy)

    Overall height of transformer frame(H)

    Overall width of transformer frame(W)

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/ EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    48/80

    4848

    OVERALL DIMENSIONS

    a = width of the largest stamping ;

    d = diameter of the circumscribing circle;

    D = distance between centres of adjacent limbs;

    Ww, Hw = width and height of the window ( length of thewindow);

    Hy = height of the yoke;

    Forcore type: D = d + Ww ; Dy=a,

    W = D+a ;

    H = Hw + 2 HyWidth over two limbs=D + outer diameter of h.v.windings

    Width over one limbs=outer diameter of h.v.windings

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/ EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    49/80

    4949

    Forthree phase transformers :

    D= d + Ww , Dy=a,

    H=Hw+2Hy ;

    W=2D+a;

    Width over 3 limbs=2D+outer diameter of h.v.winding

    Width over one limb = outer diameter of h.v.winding

    For Single phase shell type :

    Dy = b ;

    Hy = a ;W = 2Ww+4a ;

    H = H w+ 2a

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/ EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    50/80

  • 7/28/2019 Unit III Transformers

    51/80

  • 7/28/2019 Unit III Transformers

    52/80

    52

    Leakage reactance of winding

    The estimation of leakage reactance is the primarily the

    estimation of the distribution of leakage flux and the resultingflux leakages of the primary and secondary windings

    The distribution of leakage flux depends upon the geometrical

    configuration of the coils and the neighboring iron masses and

    permeability of the latter

    Leakage reactance of core type transformer

    Leakage reactance of sandwich coils

    Leakage reactance of core type transformer

    Per unit leakage reactance

    23

    p smtx o

    t c

    b bLATf aE L

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    53/80

    53

    Note on Reactance:

    Useful flux: It is the flux that links with both

    primary and secondary windings and is responsiblein transferring the energy Electro-magnetically fromprimary to secondary side. The path of the usefulflux is in the magnetic core.

    Leakage flux: It is the flux that links only with theprimary or secondary winding and is responsible inimparting inductance to the windings. The path ofthe leakage flux depends on the geometrical

    configuration of the coils and the neighboring ironmasses.

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    54/80

    54

    Leakage reactance of sandwich coils

    The idealized flux distribution in shell type transformers

    Each of n coils is sandwiched between two coils of L.v.winding.

    Per unit reactance

    6

    p so mtx

    t

    b bf LATa

    n E w

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    55/80

    55

    Output Equations Main Dimensions - KVA output forsingle and three phase transformers Window spacefactor Overall dimensions Operating characteristics Regulation No load current Temperature rise inTransformers Design of Tank -Methods of cooling of

    Transformers.

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    56/80

  • 7/28/2019 Unit III Transformers

    57/80

    57

    REGULATION

    The p.u regulation, for full load rated output Q and full load

    current Ip is :

    If the regulation is large and the phase shift between Vp and Vp

    is not justified. For this case:

    p

    pppp

    p

    pp

    V

    XIRI

    V

    VV

    sincos,

    sincos pr

    2

    )sincos(2

    1

    sincos rppr

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    58/80

    58

    Output Equations Main Dimensions - KVA output forsingle and three phase transformers Window spacefactor Overall dimensions Operating characteristics Regulation No load current Temperature rise inTransformers Design of Tank -Methods of cooling of

    Transformers.

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    59/80

    59

    ESTIMATION OF NO LOAD CURRENT OF

    TRANSFORMER

    No load current of a transformer has 2 components:

    Magnetizing componentdepends on the mmf required

    to establish the desired flux.

    Loss component depends on the iron losses.

    NO LOAD CURRENT OF A SINGLE PHASE TRANSFORMER:

    Total length of core=2lc

    Total length of yoke= 2ly

    lc=Hw = height of the window

    ly=Ww= width of the window

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    60/80

    60

    mmf for core = mmf/metre for max. flux density in core

    total length of core

    = atc 2lc= 2 atclcmmf for yoke = mmf /metre for max. flux density yoke

    total length of yoke

    = aty 2ly = 2 atyly

    Total magnetizing mmf,AT0=mmf for core + mmf for yoke + mmffor joints

    =2 atclc + 2 atyly + mmf for joints

    Maximum value for magnetizing current = AT0 / Tp If the magnetizing current is sinusoidal, rms value for

    magnetizing current,

    Im= AT0/2Tp

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    61/80

    61

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/EE 2355/DEM/VER 1.0

    NO LOAD CURRENT OF THREE PHASE TRANSFORMER

  • 7/28/2019 Unit III Transformers

    62/80

    62

    NO LOAD CURRENT OF THREE PHASE TRANSFORMER:

    Total length of core=3lcTotal length of yoke= 2ly

    lc=Hw = height of the window

    ly=Ww= width of the window

    mmf for core= mmf/metre for max.flux density in core

    total length of core

    = atc 3lc= 3 atclc

    mmf for yoke = mmf /metre for max. flux density in yoke

    total length of yoke

    = aty 2ly = 2 atyly

    Total magnetizing mmf,AT0=mmf for core + mmf for yoke + mmf

    for joints

    =3 atclc + 2 atyly + mmf for joints

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    63/80

    63

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    64/80

  • 7/28/2019 Unit III Transformers

    65/80

    65

    DESIGN OF INSULATIONBasic consideration in design the insulation

    ELECTRICAL INSULATION: Depends on the operating voltage, eddy

    current loss in the conductors and tank walls.

    MECHANICAL CONSIDERATIONS: depends on the capable to with

    stand mechanical Stresses during fault .

    THERMAL CONSIDERATIONS: depends on Safe operating of

    temperature values and types of cooling employed

    Insulation of transformers divided in to four types

    Major , Minor , insulation relative to tank , insulation between phases

    MAJOR INSULATION : Between windings and core (grounded).

    MINOR INSULATION :Between turns, coils and layers.

    MATERIALS : cotton thread, cotton tape, leatheroid paper,

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    66/80

    66

    TRANSFORMER OIL AS A COOLING MEDIUM

    The specific heat dissipation due to convection ofoil

    conv = 40.3 ( /H) W/m2 - C ;where, = temp difference of the surface relative to the oil, CH = height of the dissipating surface, m.

    Average values 0

    2 0

    20 . . 0.5 1

    80 100 /conv

    C and H to m

    to W m C

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/EE 2355/DEM/VER 1.0

    TEMPERATURE RISE IN PLAIN TANKED WALLS

  • 7/28/2019 Unit III Transformers

    67/80

    67

    TEMPERATURE RISE IN PLAIN TANKED WALLS

    The transformer core and winding is placed inside a containercalledtank

    The tank will dissipate the heat byboth radiation andconvections

    For temperature rise over 400C over the ambient temperature200C,

    The specific heat dissipation are follows,

    Due to radiation 6.0 W/m

    2

    -C and Due to convection 6.5 W/m2-c

    Thus a total of 12.5 W/m2- C is taken.

    ..

    . . . . . . . tan

    .12.5

    i c

    t

    total lossTemperature rise

    sp heat dissipation heat dissipation surface of the k

    P PTemperature rise

    S

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    68/80

    68

    Where,

    St = heat dissipating surface area of the tank.

    = Specific heat dissipation

    Pi = Iron loss; Pc = copper lossHeat dissipating surface of the tank =Total area of vertical sides+

    1/2 area of top cover.

    The area of bottom of the tank should be neglected as it has very

    little cooling effect. Transformers rated for larger outputs must be provided with

    means to improve the conditions of heat dissipation. This achieved

    by providing cooling tubes and radiators.

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    69/80

    69

    Output Equations Main Dimensions - KVA output forsingle and three phase transformers Window spacefactor Overall dimensions Operating characteristics Regulation No load current Temperature rise inTransformers Design of Tank -Methods of cooling of

    Transformers.

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    70/80

    70

    DESIGN OF TANK WITH COOLING TUBES

    For small transformers,plain walled tank is enough todissipate the losses.

    The transformers areprovided with cooling tubes to increase

    the heat dissipating area.

    Tubes mountedon vertical side of the tank

    Other hand, thetube will improve the circulation of oil. This

    improves the dissipation of lossby convection

    The improvement in

    loss dissipation by convection = loss dissipated by 35% of tube surface area.

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    71/80

    71

    Let,

    Dissipating surface of the tank = St

    Dissipating surface of the tubes = xStLoss dissipated by the tank surface = (6+6.5) St=12.5 St

    Loss dissipated by the tubes = (135/100 x 6.5) x Stby convection = 8.8 x St

    Total loss dissipated by the walls and tubes

    = (12.5 St + 8.8 xSt)

    = (12.5 + 8.8 x) St

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    72/80

    72

    Actual total area of tank walls and tubes

    = St + x St= S

    t(1+ x)

    Loss dissipated per m2 of dissipating surface

    =Total loss dissipated/ Total area

    =(12.5 + 8.8x) St / St(1+ x)

    = (12.5 + 8.8x)/(1+x)

    Temperature rise in transformer with cooling tubes,= Total loss/ Total Loss dissipated

    Total loss, Ploss = Pi + PcHence,

    = ( Pi + Pc)/ (12.5 + 8.8x) St12.5 + 8.8x = ( Pi + Pc)/ Stx = [{( Pi + Pc)/ St }-12.5] (1/8.8)

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    73/80

    73

    Total area of cooling tubes = x St= (1/8.8) [ {(Pi + Pc)/ } 12.5 St ] St

    The total number of tubes = nt

    = Total tube area / Area of each tube

    = Total tube area /( dt lt )

    nt = (1/8.8dtlt) [ {(Pi + Pc)/}12.5 St ]

    The arrangement of the tubes on tank side walls should be

    made uniformly with a spacing of usually 75 mm.

    The standard diameter of the cooling tubes is 50 mm and the

    length of the tube depends on the height of the tank.

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    74/80

    74

    The dimensions of the tank are decided by the

    dimensions of the transformer and the clearance

    required on all sides.Let

    C1= clearance between winding & tank along the width

    C2= clearance between winding & tank along the length

    C3= clearance between the transformer frame & the tank at the

    bottom

    C4= clearance between the transformer frame & the tank at the

    top.

    Doc= outer diameterof the coil.

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    75/80

    With reference to the figure we get

  • 7/28/2019 Unit III Transformers

    76/80

    76

    With reference to the figure we get,

    Width of the tank, WT= 2D+ Doc+2 C1(3-phase)

    = D+ Doc+2 C1(1-phase)

    length of the tank, LT= Doc+2 C2

    Height of the tank, HT= H+C3+C4

    The clearance on the sides depends on voltage and power rating

    of the windingVoltage KVA rating Clearance in mm

    C1 C2 C3 c4

    Up to 11KV

  • 7/28/2019 Unit III Transformers

    77/80

    77

    Output Equations Main Dimensions - KVA output forsingle and three phase transformers Window spacefactor Overall dimensions Operating characteristics Regulation No load current Temperature rise inTransformers Design of Tank -Methods of cooling of

    Transformers.

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    78/80

    78

    METHODS OF COOLING OF TRANSFORMERS

    The losses developed in a transformer are converted

    into heat energy & cause heating of correspondingtransformer parts.

    The heat dissipation in a transformer occurs by

    conduction, convection & radiation.

    The path of heat flow in a transformer are:

    From the internal most heated spots of a given

    part(core or winding) to their outer surface in

    contact with the oil by conduction.

    From the outer surface of a transformer part to the

    oil that cools it by convection.

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    79/80

    79

    From the oil to the walls of the cooler by

    convection (Eg. wall of a tank)

    From the walls of the cooler to the coolingmedium air or water by both convection &

    radiation.

    The various methods of cooling transformers are:

    Air natural(AN)

    Air blast(AB)

    Oil natural(ON)

    Oil natural- Air forced(ONAF)

    IFETCE/EEE/M.SUJ ITH/III YEAR/VI SEM/EE 2355/DEM/VER 1.0

  • 7/28/2019 Unit III Transformers

    80/80

    80

    Oil natural- Water forced(ONWF)

    Forced circulation of oil(OF)

    Oil forced-Air natural(OFAN)

    Oil forced-Air forced(OFAF)

    Oil forced - Water forced(OFWF)

    The choice of cooling method depends upon the,size,

    type of application &

    type of conditions obtaining at the site where the

    transformer is installed.Natural cooling is suitable up to 10MVA

    The forced oil and air circulation -30MVA