Underground Distribution System Design Standards
Transcript of Underground Distribution System Design Standards
STD-E&O-005 Underground Distribution System Design Standards Electrical District No. 3 of Pinal County Engineering & Operations Department 41630 W. Louis Johnson Drive Maricopa, AZ 85138
Revision 1 Effective Date: 08/11/2021 Review Level: 1
Underground Distribution System Design Standards STD-E&O-005 Rev(1) Effective 08/11/2021 Page 2 of 60
Electrical District No. 3 of Pinal County, Arizona Standards Approval
The signature of the Assistant General Manager & Director of Engineering & Operations authorizes the use of these standards for ED3 operations. He acknowledges that he is responsible for its implementation, training personnel on its requirements, and employee compliance.
Reviewed By:
Scott Kelly, Distribution Design Manager Date
Reviewed By:
Greg Ellis, Engineering Manager Date
Reviewed By:
Evan McCullough, Operations Manager Date
Approved By:
Mike Bristol, Assistant GM & Director of E&O Date
APPROVAL SIGNATURES ON FILE
Underground Distribution System Design Standards STD-E&O-005 Rev(1) Effective 08/11/2021 Page 3 of 60
Revision History
Revision Date Description Approved 0 05/05/2021 Original Document
MJB1 08/11/2021 Added 612 Switch Vault
MJB
Underground Distribution System Design Standards STD-E&O-005 Rev(1) Effective 08/11/2021 Page 4 of 60
Introduction
Electrical District No. 3 of Pinal County (ED3) has prepared this set of underground distribution installation standards to better provide a safe, consistent, and reliable underground power distribution system. These standards must be used by all parties involved in the design or installation of underground power distribution systems within the ED3 service territory. These standards were created as a general guide for the construction of ED3 underground facilities. Not all standards will apply in all situations as circumstances differ from job to job. ED3 encourages users of these standards to review the plans provided and resolve any concerns prior to starting the job. Users in need of help with these standards, should notify ED3 Engineering at [email protected].
ED3 Underground Infrastructure Inspectors utilize these standards during inspection and certification of underground power distribution system installations. Closing trenches prior to inspection or performing any other action that precludes system inspection is grounds for immediate inspection failure. In such a case, the user shall restore the system to an inspectable state at their sole expense.
These standards are subject to regular revision as national, state, and local codes change. All users of these standards shall verify they are using the latest version by checking the ED3 Website (www.ed3online.org).
Design Standards Drawings Index
NUMBER DATE DRAWING TITLE UG 01 03/30/21 CONDUIT INSTALLATION, 600V JUNCTION BOX UG 02 01/07/21 CONDUIT INSTALLATION, STREET LIGHT JUNCTION BOX UG 03 03/30/21 CONDUIT INSTALLATION, SECONDARY DETAIL UG 04 03/30/21 CONDUIT INSTALLATION, PRIMARY DETAIL UG 05 03/30/21 CONDUIT INSTALLATION, MARKER BALL DETAIL UG 06 01/24/18 CONDUIT INSTALLATION, SINGLE-PHASE RISER UG 07 01/24/18 CONDUIT INSTALLATION, THREE-PHASE RISER UG 08 01/22/18 CONDUIT INSTALLATION, SINGLE-PHASE TRANSFORMER UG 09 01/22/18 CONDUIT INSTALLATION, THREE-PHASE TRANSFORMER UG 10 11/29/17 CONDUIT INSTALLATION, PAD-MOUNT OPEN DELTA UG 11 12/17/18 CONDUIT INSTALLATION, JUNCTION CABINET UG 12 01/24/18 CONDUIT INSTALLATION, GROUND SLEEVE UG 13 11/21/17 CONDUIT INSTALLATION, CAPACITOR BANK UG 14 01/24/18 CONDUIT INSTALLATION, 56x56 PULLING VAULT UG 15 11/28/17 CONDUIT INSTALLATION, 510 PULLING VAULT (1 of 2)
CONDUIT INSTALLATION, 510 PULLING VAULT (2 of 2) UG 16 11/28/17 CONDUIT INSTALLATION, 610 SWITCH VAULT (1 of 2)
CONDUIT INSTALLATION, 610 SWITCH VAULT (2 of 2) UG 17 09/19/18 TRENCH DETAIL, ENCASED CONDUIT
Underground Distribution System Design Standards STD-E&O-005 Rev(1) Effective 08/11/2021 Page 5 of 60
Design Standards Drawings Index (cont.)
NUMBER DATE DRAWING TITLE UG 18 08/07/17 TRENCH DETAIL, DIRECT-BURIED CONDUIT UG 19 09/19/18 TRENCH DETAIL, ENCASED SINGLE-CIRCUIT CONDUIT UG 20 11/29/17 TRENCH DETAIL, BELOW GRADE PROFILE UG 21 11/30/17 TRENCH DETAIL, RETENTION SLOPE UG 22 03/31/21 TRENCH DETAIL, STORM DRAIN UG 23 11/29/17 CLEARANCE DETAIL, TRANSFORMER PLACEMENT UG 24 12/12/17 CLEARANCE DETAIL, TRANSFORMER CLEARANCE UG 25 01/10/18 CLEARANCE DETAIL, HAND HOLE PLACEMENT UG 26 03/31/21 CLEARANCE DETAIL, STREETLIGHT PLACEMENT UG 27 03/31/21 CLEARANCE DETAIL, PME WORKING CLEARANCES UG 28 03/31/21 CLEARANCE DETAIL, EQUIPMENT BOLLARDS UG 29 11/29/17 DIMENSIONS, TRANSFORMER PADS UG 30 06/04/18 DIMENSIONS, 63x72 TRANSFORMER PAD UG 31 09/30/20 DIMENSIONS, 75x88 TRANSFORMER PAD UG 32 11/21/17 DIMENSIONS, 100x102 TRANSFORMER PAD UG 33 06/04/21 DIMENSIONS, 84x84 CAPACITOR PAD UG 34 12/17/18 DIMENSIONS, JUNCTION CABINET UG 35 01/22/17 DIMENSIONS, 36x48 PULLING VAULT – FOR REFERENCE ONLY UG 36 01/22/18 DIMENSIONS, 56x56 PULLING VAULT UG 37 11/27/17 DIMENSIONS, 60x108 PULLING VAULT
DIMENSIONS, 60x108 PULLING VAULT UG 38 11/27/17 DIMENSIONS, 510 PULLING VAULT
DIMENSIONS, 510 PULLING VAULT UG 39 11/27/17 DIMENSIONS, 610 SWITCH VAULT
DIMENSIONS, 610 SWITCH VAULT UG 40 01/11/18 DIMENSIONS, 68x71 VAULT LID UG 41 07/27/21 DIMENSIONS, 612 SWTICH VAULT
DIMENSIONS, 612 SWTICH VAULT SL 01 12/18/20 STREETLIGHT, STANDARD HEIGHTS SL 02 12/18/20 STREETLIGHT, STANDARD ARM ATTACHMENT SL 03 03/15/21 STREETLIGHT, 4-BOLT BASE, DECORATIVE SL 04 03/15/21 STREETLIGHT, 4-BOLT BASE WITH HANDHOLE SL 05 03/15/21 STREETLIGHT, 4-BOLT BASE WITHOUT HANDHOLE SL 06 03/20/21 STREETLIGHT, 3-BOLT BASE, DECORATIVE – OBSOLETE SL 07 04/21/21 STREETLIGHT, DECORATIVE STREET LIGHT
Underground Distribution System Design Standards STD-E&O-005 Rev(1) Effective 08/11/2021 Page 6 of 60
Attachment 1, Underground Distribution System Design Standards Drawings
ELECTRIC
SIDE VIEW
TOP VIEW
36
"
COVER
2"
2"
ELECTRICAL DISTRICT #3-ENGINEERING Date: 3-30-21
Dwn by:
Dwn No:
1 of 1
600V JUNCTION BOX
GE
UG 01
3District No.
Electrical
CONDUIT INSTALLATION
1. ALL CONDUIT SHALL BE SCHEDULE 40
2. ALL BENDS SHALL BE 36" RADIUS
3. TOP OF JUNCTION BOX SHALL BE 2" ABOVE GRADE
4. SEE PROJECT DRAWING FOR CONDUIT SIZE AND QUANTITY
NOTES:
UNDERGROUND DISTRIBUTION. SYSTEM DESIGN STANDARDS
ELECTRIC
SIDE VIEW
TOP VIEW
36"
COVER
2"
2"
ELECTRICAL DISTRICT #3-ENGINEERING Date: 1-07-21
Dwn by:
Dwn No:
1 of 1
STREET LIGHT JUNCTION BOX
JG
UG 02
3District No.
Electrical
CONDUIT INSTALLATION
1. ALL CONDUIT SHALL BE SCHEDULE 40
2. ALL BENDS SHALL BE 36" RADIUS
3. TOP OF JUNCTION BOX SHALL BE 2" ABOVE GRADE
4. SEE PROJECT DRAWING FOR CONDUIT SIZE AND QUANTITY
NOTES:
UNDERGROUND DISTRIBUTION. SYSTEM DESIGN STANDARDS
FINAL GRADE
36
" M
IN
12"
ELECTRICAL DISTRICT #3-ENGINEERING
UNDERGROUND DISTRIBUTION. SYSTEM DESIGN STANDARDS
Date: 3-30-21
Dwn by:
Dwn No:
1 of 1
SECONDARY DETAIL
GE
UG 03
3District No.
Electrical
CONDUIT INSTALLATION
1. ALL CONDUIT SHALL BE SCHEDULE 40
2. SEE PROJECT DRAWING FOR CONDUIT SIZE AND QUANTITY
NOTES:
FINAL GRADE
60
" M
IN
12"
ELECTRICAL DISTRICT #3-ENGINEERING Date: 3-30-21
Dwn by:
Dwn No:
1 of 1
PRIMARY DETAIL
GE
UG 04
3District No.
Electrical
CONDUIT INSTALLATION
1. ALL CONDUIT SHALL BE SCHEDULE 40
2. SEE PROJECT DRAWING FOR CONDUIT SIZE AND QUANTITY
NOTES:
UNDERGROUND DISTRIBUTION. SYSTEM DESIGN STANDARDS
TIE LOCATING BALL
AT END OF CENTER CONDUIT
FINAL GRADE
24"
LOCATING BALLPE
R
DE
SIG
N
ELECTRICAL DISTRICT #3-ENGINEERING Date: 3-30-21
Dwn by:
Dwn No:
1 of 1
MARKER BALL DETAIL
GE
UG 05
3District No.
Electrical
CONDUIT INSTALLATION
NOTE:
1. LOCATING BALL CAN NOT BE DEEPER THAN 48" FROM FINAL GRADE.
UNDERGROUND DISTRIBUTION. SYSTEM DESIGN STANDARDS
36" MIN
FINAL GRADE
TOP VIEW
SIDE VIEW
12"
ELECTRICAL DISTRICT #3- ENGINEERING Date: 1-24-18
Dwn by:
Dwn No:
1 of 1
CONDUIT INSTALLATION
GE
UG 06
3District No.
Electrical
SINGLE PHASE RISER
1. ALL CONDUIT SHALL BE SCHEDULE 40
2. ALL BENDS SHALL BE 36" RADIUS
3. CONDUIT SHALL EXTEND 12" ABOVE GRADE
4. CONDUIT SHALL BE INSTALLED DIRECTLY AGAINST THE UTILITY POLE
5. SEE PROJECT DRAWING FOR CONDUIT SIZE AND QUANTITY
NOTES:
UNDERGROUND DISTRIBUTION. SYSTEM DESIGN STANDARDS
60" M
IN
FINAL GRADE
TOP VIEW
SIDE VIEW
12"
ELECTRICAL DISTRICT #3- ENGINEERING Date: 1-24-18
Dwn by:
Dwn No:
1 of 1
CONDUIT INSTALLATION
GE
UG 07
3District No.
Electrical
3 PHASE RISER
1. ALL CONDUIT SHALL BE SCHEDULE 40
2. ALL BENDS SHALL BE 36" RADIUS
3. CONDUIT SHALL EXTEND 12" ABOVE GRADE
4. CONDUIT SHALL BE INSTALLED DIRECTLY AGAINST THE UTILITY POLE
5. SEE PROJECT DRAWING FOR CONDUIT SIZE AND QUANTITY
NOTES:
UNDERGROUND DISTRIBUTION. SYSTEM DESIGN STANDARDS
PRIMARY CONDUIT
60" M
IN
.
36" M
IN
.
PRIMARY CONDUIT
SERVICE CONDUIT
3.5"
2"
FINAL GRADE
APPROXIMATE GROUND
ROD LOCATION
6"
10"
4"
42"
25"
42"
12"
8"
7"
FRONT OF TRANSFORMER
(SOURCE)
(LOAD)
BACK OF TRANSFORMER
ELECTRICAL DISTRICT #3- ENGINEERING Date: 1-22-18
Dwn by:
Dwn No:
1 of 1
CONDUIT INSTALLATION
GE
UG 08
3District No.
Electrical
SINGLE PHASE TRANSFORMER
1. ALL FILL BELOW ELECTRIC UTILITY FIXTURE FOUNDATION PADS SHALL BE 60/40 SRP BACKFILL
2. SEE PROJECT DRAWING FOR CONDUIT SIZE AND QUANTITY
3. ALL CONDUIT SHALL BE SCHEDULE 40
4. ALL BENDS SHALL BE 36" RADIUS
5. THERE SHALL BE A 2" GAP BETWEEN ALL CONDUIT AND INSIDE PAD WINDOW TO ALLOW FOR
ADJUSTMENT
NOTES:
UNDERGROUND DISTRIBUTION. SYSTEM DESIGN STANDARDS
3"
3"
6"
75"
TOP VIEW
FRONT VIEW
SIDE VIEW
PRIMARY SECONDARY
IN OUT
36" 24"
7
1
2
"
60"
7
1
2
"
64"
18"
6"
15"
58"
15"
(BACK OF TRANSFORMER)
88"
6" 18" 64"
2"
GROUND ROD
GROUND ROD
GROUND ROD
FOR DELIVERED PAD ONLY:
(4) 3/4" FERRULE LOOP INSERTS
ELECTRICAL DISTRICT #3- ENGINEERING Date: 1-22-18
Dwn by:
Dwn No:
1 of 1
CONDUIT INSTALLATION
GE
UG 09
3District No.
Electrical
THREE PHASE TRANSFORMER
1. ALL FILL BELOW ELECTRIC UTILITY FIXTURE FOUNDATION PADS SHALL BE 60/40 SRP BACKFILL
2. SEE PROJECT DRAWING FOR CONDUIT SIZE AND QUANTITY
3. ALL CONDUIT SHALL BE SCHEDULE 40
4. ALL BENDS SHALL BE 36" RADIUS
5. THERE SHALL BE A 2" GAP BETWEEN ALL CONDUIT AND INSIDE PAD WINDOW TO ALLOW FOR
ADJUSTMENT
6. 75X88 PAD TO BE USED FOR 150-1000KVA TRANSFORMER SIZES
NOTES:
UNDERGROUND DISTRIBUTION. SYSTEM DESIGN STANDARDS
36" M
IN
60" M
IN
SECONDARY TIE
SERVICE CONDUIT
PRIMARY CONDUIT
ELECTRICAL DISTRICT #3- ENGINEERING Date: 11-29-17
Dwn by:
Dwn No:
1 of 1
CONDUIT INSTALLATION
JG
UG 10
3District No.
Electrical
PAD MOUNT OPEN DELTA
1. ALL FILL BELOW ELECTRIC UTILITY FIXTURE FOUNDATION PADS SHALL BE 60/40 SRP BACKFILL
2. SEE PROJECT DRAWING FOR CONDUIT SIZE AND QUANTITY
3. ALL CONDUIT SHALL BE SCHEDULE 40
4. ALL BENDS SHALL BE 36" RADIUS
5. THERE SHALL BE A 2" GAP BETWEEN ALL CONDUIT AND INSIDE PAD WINDOW TO ALLOW FOR
ADJUSTMENT
6. REFERENCE ED3 DRAWING UG08 FOR PAD DIMENSIONS
NOTES:
UNDERGROUND DISTRIBUTION. SYSTEM DESIGN STANDARDS
FINAL GRADE
JUNCTION CABINET SLEEVE
60
"
12
"
TOP VIEW
SIDE VIEW
A B C
A B C
GROUND ROD
ELECTRICAL DISTRICT #3- ENGINEERING Date: 12-17-18
Dwn by:
Dwn No:
1 of 1
CONDUIT INSTALLATION
JG
UG 11
3District No.
Electrical
JUNCTION CABINET
1. ALL FILL BELOW ELECTRIC UTILITY FIXTURE SHALL BE 60/40 SRP BACKFILL
2. SEE PROJECT DRAWING FOR CONDUIT SIZE AND QUANTITY
3. ALL CONDUIT SHALL BE SCHEDULE 40
4. ALL BENDS SHALL BE 36" RADIUS
NOTES:
UNDERGROUND DISTRIBUTION. SYSTEM DESIGN STANDARDS
PME SWITCHINGCABINET SLEEVE
67"
75"
14"
14"
FINAL GRADE
TOP VIEW
SIDE VIEW
CABINETOUTLINE OF
C
L
L
C
2"
24
"2
4"
12
"2
5"
60
"
2"2"
ELECTRICAL DISTRICT #3- ENGINEERING Date: 1-24-18
Dwn by:
Dwn No:
1 of 1
CONDUIT INSTALLATION
GE
UG 12
3District No.
Electrical
GROUND SLEEVE
1. ALL FILL BELOW ELECTRIC UTILITY FIXTURE SHALL BE 60/40 SRP BACKFILL
2. SEE PROJECT DRAWING FOR CONDUIT SIZE AND QUANTITY
3. ALL CONDUIT SHALL BE SCHEDULE 40
4. ALL BENDS SHALL BE 36" RADIUS
NOTES:
UNDERGROUND DISTRIBUTION. SYSTEM DESIGN STANDARDS
SIDE VIEW
TOP VIEW
FRONT VIEW
2" M
IN
4" M
IN
4" M
IN
2 1/2" SCH40 PVC
(2) 6" LONG P3200 UNISTRUT
18"x50" WINDOW
GROUND ROD
(TYP)
6" M
IN
GROUND ROD
GROUND ROD
84"
84
"
7"
6"
7"18" 59"
17" 50" 17"
84"
84"
6"
ELECTRICAL DISTRICT #3- ENGINEERING Date: 11-21-17
Dwn by:
Dwn No:
1 of 1
CONDUIT INSTALLATION
JG
UG 13
3District No.
Electrical
CAPACITOR BANK
NOTES:
1. FRONT OF PAD SHALL FACE STREET.
2. ALL PAD ELEVATIONS SHALL BE ESTABLISHED BY SURVEY (BLUE TOP) AND TOP OF PAD SHALL
BE 4" ABOVE FINAL GRADE IN IMMEDIATE AREA.
3. PAD MUST BE LEVEL BEFORE INSTALLING EQUIPMENT.
4. AREA UNDER PAD MUST BE COMPACTED PER TRENCH SPECIFICATIONS ON DESIGN DRAWINGS.
5. CONDUIT INSTALLED AND CAPPED 6" BELOW PAD WINDOW WHEN BEING PROVIDED FOR
FUTURE.
6.ALL FILL BELOW ELECTRIC UTILITY FIXTURE SHALL BE SRP 60/40 MIX
UNDERGROUND DISTRIBUTION. SYSTEM DESIGN STANDARDS
Plan View
Side View
VAULT U-506
73
"
4'-8"
4'-8
"
(4) 24" x 30" KNOCKOUTS
(1) EACH SIDE
SUMP INDENT IN FLOOR
8" DIA. X 4" DEEP
ROD KNOCKOUTS
(2) 2 1/2" DIA. GROUND
1'
LOCKING STEEL COVER
COVER WEIGHT
BASE WEIGHT - 5350 LBS
- 1335 LBS
TOTAL WEIGHT - 6685 LBS
6"
CONCRETE CONDUIT
INTO VAULT
BELL END
ELECTRICAL DISTRICT #3- ENGINEERING Date: 1-24-18
Dwn by:
Dwn No:
1 of 1
CONDUIT INSTALLATION
GE
UG 14
3District No.
Electrical
56X56 PULLING VAULT
1. ALL FILL BELOW ELECTRIC UTILITY FIXTURE SHALL BE 60/40 SRP BACKFILL
2. SEE PROJECT DRAWING FOR CONDUIT SIZE AND QUANTITY
3. ALL CONDUIT SHALL BE SCHEDULE 40
4. ALL BENDS SHALL BE 36" RADIUS
5. EXCAVATED BASE SHALL INCLUDE 6" LAYER OF 3/4" WASHED ROCK
6. WASHED ROCK SHALL HAVE A 3" LAYER OF PEA GRAVEL FOR LEVELING
NOTES:
UNDERGROUND DISTRIBUTION. SYSTEM DESIGN STANDARDS
5"10'-0"5"
6"
8'-0
" O
VE
RA
LL
H
EIG
HT
6"
7'-0
" IN
SID
E H
EIG
HT
10'-0" NSIDE LENGTH
10'-10" OUTSIDE LENGTH
11'-6" RIBBING LENGTH
5'-0
" IN
SID
E W
ID
TH
5'-1
0" O
UT
SID
E W
ID
TH
6'-6
" R
IB
BIN
G W
ID
TH
TOP VIEW
SIDE VIEW
5'-3" 1'-3" 2'-10"7" 1"
GROUND ROD HOLE
BELL END
BELL END
SEE CONSTRUCTION
PLANS FOR SIZE AND
QUANTITY OF CONDUITS
12" DIA. SUMP TO BE
CLEARED BEFORE
INSTALLATION
CONCRETE
CONDUIT
INTO VAULT
12" DIA. SUMP TO BE
CLEARED BEFORE
INSTALLATION
SEALANT
REQUIRED
AT JOINT
SEE CONSTRUCTION
PLANS FOR SIZE AND
QUANTITY OF
CONDUITS
ELECTRICAL DISTRICT #3- ENGINEERING Date: 11-28-17
Dwn by:
Dwn No:
1 of 2
CONDUIT INSTALLATION
JG
UG 15
3District No.
Electrical
510 PULLING VAULT
UNDERGROUND DISTRIBUTION. SYSTEM DESIGN STANDARDS
5"5'-0"5"
END VIEW
2'-10"1'-1" 1'-1"
1'-7
1
2
"
GROUND ROD HOLE
SEALANT
REQUIRED
AT JOINT
6" OF COMPACTED
CRUSHED ROCK 3/4" MIN.
1 1/ 2" MAX CONDUITS
ELECTRICAL DISTRICT #3- ENGINEERING Date: 11-28-17
Dwn by:
Dwn No:
2 of 2
CONDUIT INSTALLATION
JG
UG 15
3District No.
Electrical
510 PULLING VAULT
1. ALL FILL BELOW ELECTRIC UTILITY FIXTURE SHALL BE 60/40 SRP BACKFILL
2. SEE PROJECT DRAWING FOR CONDUIT SIZE AND QUANTITY
3. ALL CONDUIT SHALL BE SCHEDULE 40
4. ALL BENDS SHALL BE 36" RADIUS
5. EXCAVATED BASE SHALL INCLUDE 6" LAYER OF 3/4" WASHED ROCK
6. WASHED ROCK SHALL HAVE A 3" LAYER OF PEA GRAVEL FOR LEVELING
NOTES:
UNDERGROUND DISTRIBUTION. SYSTEM DESIGN STANDARDS
10'-0" INSIDE LENGTH
11'-1 1/2" OUTSIDE LENGTH
6'-0
" IN
SID
E W
ID
TH
7'-1
1
/2
" O
UT
SID
E W
ID
TH
TOP VIEW
SIDE VIEW
61" x 61" Opening
GROUND ROD HOLE
BELL END
UNISTRUT
2'-10"1'-5"5'-1"
6"
10'-0"
2"
7'-0
" IN
SID
E H
EIG
HT
8'-0
" O
UT
SID
E H
EIG
HT
12" DIA. SUMP TO BE
CLEARED BEFORE INSTALLATION
BELL END
SEE CONSTRUCTION PLANS
FOR SIZE AND QUANTITY OF
CONDUITS
SEE CONSTRUCTION PLANS
FOR SIZE AND QUANTITY OF
CONDUITS
SEALANT REQUIRED AT JOINT
CONCRETE
CONDUIT INTO
VAULT
6" OF WASHED ROCK 3/4" MIN.
+ 3" PEA GRAVEL
12" DIA. SUMP TO BE CLEARED
BEFORE INSTALLATION
NOTE: BLUE-TOP MUST BE 6" ABOVE
FINAL GRADE
ELECTRICAL DISTRICT #3- ENGINEERING Date: 11-28-17
Dwn by:
Dwn No:
1 of 2
JG
UG 16
3District No.
Electrical
CONDUIT INSTALLATION 610 SWITCH VAULT
UNDERGROUND DISTRIBUTION. SYSTEM DESIGN STANDARDS
END VIEW
5'-0" 6"6"
6'-0"
6 3/4" 6 3/4"
2'-7
1
2
"
SEALANT REQUIRED AT JOINT
6" OF WASHED ROCK 3/4" MIN.
+ 3" PEA GRAVEL
ELECTRICAL DISTRICT #3- ENGINEERING Date: 11-28-17
Dwn by:
Dwn No:
2 of 2
CONDUIT INSTALLATION
JG
UG 16
3District No.
Electrical
610 SWITCH VAULT
1. ALL FILL BELOW ELECTRIC UTILITY FIXTURE SHALL BE 60/40 SRP BACKFILL
2. SEE PROJECT DRAWING FOR CONDUIT SIZE AND QUANTITY
3. ALL CONDUIT SHALL BE SCHEDULE 40
4. ALL BENDS SHALL BE 36" RADIUS
5. EXCAVATED BASE SHALL INCLUDE 6" LAYER OF 3/4" WASHED ROCK
6. WASHED ROCK SHALL HAVE A 3" LAYER OF PEA GRAVEL FOR LEVELING
NOTES:
UNDERGROUND DISTRIBUTION. SYSTEM DESIGN STANDARDS
FINAL GRADE
79" M
IN
36"
12"
28"
73" M
IN
36"
12"
22"
81" M
IN
MIN
.
36"
15"
12
60" M
IN
33"
15"
REQUIRED BACKFILL
OTHER UTILITY
OTHER UTILITY
36" M
IN
15"
12"
STREET SIDE
81" M
IN
.
GAS
6"
6"
6"
6"
VARIES
1
2
"
M
I
N
C
L
E
A
R
TELECOMMUNICATION PROVIDERS
(CENTURYLINK & ORBITEL)
30"
CONDUIT
SPACER
VARIES
VARIES
VARIES
ELECTRIC
HIGH VOLTAGE
28"
MIN
24"
MIN
28"
MIN
22"
MIN
ELECTRIC
HIGH VOLTAGE
ELECTRIC
HIGH VOLTAGE
ELECTRIC
LOW VOLTAGE
ELECTRIC
HIGH VOLTAGE
OTHER UTILITY
1 2 3
4
5
FINAL GRADE FINAL GRADE
FINAL GRADE
FINAL GRADE
STREET SIDE
STREET SIDE
STREET SIDE
STREET SIDE
REQUIRED BACKFILL
OTHER UTILITY
REQUIRED BACKFILL
OTHER UTILITY
REQUIRED BACKFILL
12"
REQUIRED BACKFILL
ELECTRIC
HIGH VOLTAGE
ELECTRICAL DISTRICT #3- ENGINEERING Date: 9-19-18
Dwn by:
Dwn No:
1 of 1
TRENCH DETAIL
GE
UG 17
3District No.
Electrical
ENCASED CONDUIT
JOINT TRENCH NOTES:
1. CHECK WITH THE LOCAL GAS COMPANY FOR BEDDING, CONDUIT, & DEPTH REQUIREMENTS
2. GAS TO MAINTAIN MIN. 12" VERTICAL SEPARATION FROM ALL ELECTRIC CONDUITS.
3. CONTACT "OTHER UTILITY" FOR SPECIFIC REQUIREMENTS
4. A MIN. OF 36" COVER IS REQUIRED OVER ALL FACILITIES IN CITY & COUNTY RIGHT OF WAYS.
ELECTRICAL TRENCH NOTES
5. CUSTOMER TO INSTALL ELECTRONIC MARKERS AT ALL CONDUIT STUBOUTS
6. ALL CONDUITS SHALL BE SCHEDULE 40
7. CONDUIT SHALL NOT OCCUPY MORE THAN 30 INCHES OF HORIZONTAL WIDTH.
8.STEEL WIRE OR REBAR ARE NOT ACCEPTABLE FOR SECURING CONDUIT, THIS WILL CREATE HEAT.
9. ALL ENCASED CONDUITS SHALL USE SRP 60/40 MIX
10. ALL HIGH VOLTAGE TRENCH REQUIRES MARKING TAPE TO BE PLACED 12" ABOVE CONDUIT.
11.SEE PROJECT DRAWING FOR CONDUIT SIZE AND QUANTITY.
12.MINIMUM OF 2" SEPARATION BETWEEN ENCASED CONDUITS
UNDERGROUND DISTRIBUTION. SYSTEM DESIGN STANDARDS
STREET SIDE
GAS
GAS
GAS
FINAL GRADE
FINAL GRADE
FINAL GRADE
OTHER UTILITY
OTHER UTILITY
OTHER UTILITY
ELECTRIC HIGH VOLTAGE
ELECTRIC HIGH VOLTAGE
ELECTRIC HIGH VOLTAGE
ELECTRIC LOW VOLTAGE
6
7
8
STREET SIDE
STREET SIDE
36
"1
2"
12
"1
0"
76
" M
IN
REQUIRED BACKFILL
24"
12
"1
2"
REQUIRED BACKFILL
16"
67
" M
IN
24"
12
"1
2"
60
" M
IN
REQUIRED BACKFILL
ELECTRICAL DISTRICT #3- ENGINEERING Date: 8-07-17
Dwn by:
Dwn No:
1 of 1
TRENCH DETAIL
GE
UG 18
3District No.
Electrical
DIRECT BURIED CONDUIT
JOINT TRENCH NOTES:
1. CHECK WITH THE LOCAL GAS COMPANY FOR BEDDING, CONDUIT, & DEPTH REQUIREMENTS
2. GAS TO MAINTAIN MIN. 12" VERTICAL SEPARATION FROM ALL ELECTRIC CONDUITS.
3. CONTACT "OTHER UTILITY" FOR SPECIFIC REQUIREMENTS
4. A MIN. OF 36" COVER IS REQUIRED OVER ALL FACILITIES IN CITY & COUNTY RIGHT OF WAYS.
ELECTRICAL TRENCH NOTES
5. CUSTOMER TO INSTALL ELECTRONIC MARKERS AT ALL CONDUIT STUBOUTS.
6. ALL CONDUITS SHALL BE SCHEDULE 40
7. CONDUIT SHALL NOT OCCUPY MORE THAN 30 INCHES OF HORIZONTAL WIDTH.
8. CONDUITS SHALL NOT BE STACKED MORE THAN 2 LAYERS HIGH. LARGER DIAMETER
CONDUITS SHALL BE PLACED AT BOTTOM OF TRENCH WHEN POSSIBLE
9. ALL CONDUITS SHALL BE SECURED FROM "FLOATING" DUE TO BACKFILL.
10.STEEL WIRE OR REBAR ARE NOT ACCEPTABLE FOR SECURING CONDUIT, THIS WILL CREATE HEAT.
11.MECHANICAL COMPACTION IS NOT ALLOWED WITHIN 6" OF ELECTRICAL CONDUITS.
12.ALL HIGH VOLTAGE TRENCH REQUIRES MARKING TAPE TO BE PLACED 12" ABOVE CONDUIT.
13.SEE PROJECT DRAWING FOR CONDUIT SIZE AND QUANTITY
UNDERGROUND DISTRIBUTION. SYSTEM DESIGN STANDARDS
GRADEFINAL
ELECTRIC HIGH VOLTAGE
3-2.5" SCHEDULE 40
60" M
IN
45"
15"
22" MIN
ELECTRICAL DISTRICT #3- ENGINEERING Date: 9-19-18
Dwn by:
Dwn No:
1 of 1
TRENCH DETAIL
GE
UG 19
3District No.
Electrical
ENCASED SINGLE CIRCUIT CONDUIT
TRENCH NOTES
1.CUSTOMER TO INSTALL ELECTRONIC MARKERS AT ALL CONDUIT STUBOUTS.
2.ALL CONDUITS SHALL BE SCHEDULE 40
3.CONDUIT SHALL NOT OCCUPY MORE THAN 30 INCHES OF HORIZONTAL WIDTH.
4.CONDUITS SHALL NOT BE STACKED MORE THAN 2 LAYERS HIGH. LARGER DIAMETER
CONDUITS SHALL BE PLACED AT BOTTOM OF TRENCH WHEN POSSIBLE
5.ALL CONDUITS SHALL BE SECURED FROM "FLOATING" DUE TO BACKFILL.
6.STEEL WIRE OR REBAR ARE NOT ACCEPTABLE FOR SECURING CONDUIT, THIS WILL CREATE HEAT.
7.MECHANICAL COMPACTION IS NOT ALLOWED WITHIN 6" OF ELECTRICAL CONDUITS.
8.ALL HIGH VOLTAGE TRENCH REQUIRES MARKING TAPE TO BE PLACED 12" ABOVE CONDUIT.
9.SEE PROJECT DRAWING FOR CONDUIT SIZE AND QUANTITY
10.MINIMUM OF 2" SEPARATION BETWEEN ENCASED CONDUITS
UNDERGROUND DISTRIBUTION. SYSTEM DESIGN STANDARDS
36"
36"
L
P
5'-0"
RE
F
TR
EN
CH
PUBLIC UTILITY EASEMENT
L
P
L
P
10'-0"
8'-0"
TELCO
1
2
"
1
2
"
10'-0"
24"
CH
AM
FE
R
IS
O
PT
IO
NA
L
21"
SEE PROFILE VIEW BELOW
TRANSFORMER INSTALLATION DETAIL (PROFILE)
TELCO SERVICE
DROP
BACK OF
EASEMENT
FINAL
GRADE
18"
36"
24"
12"
3-1/4"
STUB-OUT
W / ELECTRONIC
MARKER
5'-0" REF
XFMR PAD
#6 CU TELCO
GROUND NOTE
8'-0" EASEMENT
36"
42" REF
L
C
1-1/2"
30"
PROPERTY
CORNER PIN
9'-0"
APPROX.
SIDEWALK
3'-6"
10"
2" CATV CONDUIT
W
ASPHALT
STREET
CURB AND
GUTTER
60"
18"
18"
6"
DEPTH IS IMPACTED BY WATER
AND SEWER LINE LOCATIONS
W M
TE
LC
O
18"
L
P
L
C
ST
RE
ET
GROUND ROD
W M
W M
GROUND
ROD
TELCO
ELECTRICAL DISTRICT #3- ENGINEERING Date: 11-29-17
Dwn by:
Dwn No:
1 of 1
TRENCH DETAIL
JG
UG 20
3District No.
Electrical
BELOW GRADE PROFILE
NOTES:
1. MAINTAIN A MINIMUM 12" CROSSING SEPARATION BETWEEN ED-3 CONDUIT AND TELCO/CATV.
2. TELCO/CATV MUST NOT PASS UNDER TRANSFORMER.
3. GAS LINE TO MAINTAIN A MINIMUM 12" HORIZONTAL SEPARATION FROM OUTSIDE EDGE OF
TRANSFORMER PAD.
4. TELCO TO SUPPLY GROUND WIRE WHICH MAY BE COILED/SECURED AROUND A CONDUIT SWEEP
DURING TENCH BACKFILL. THIS GROUND WILL LATER BE ATTACHED TO THE TRANSFORMER PAD.
UNDERGROUND DISTRIBUTION. SYSTEM DESIGN STANDARDS
32'-0"
SEE DESIGN FOR CONDUIT
SIZE AND QUANTITY
SLOPE = TBD BY DEVELOPER PLANS
12"
MATCH SIDEWALK GRADE
2'-0" MIN. (TYP)
SIDE VIEW
ELECTRICAL DISTRICT #3- ENGINEERING Date: 11-30-17
Dwn by:
Dwn No:
1 of 1
TRENCH DETAIL
JG
UG 21
3District No.
Electrical
RETENTION SLOPE
TRENCH NOTES
1. CUSTOMER TO INSTALL ELECTRONIC MARKERS AT ALL CONDUIT STUBOUTS.
2. ALL CONDUITS SHALL BE SCHEDULE 40
3. CONDUIT SHALL NOT OCCUPY MORE THAN 30 INCHES OF HORIZONTAL WIDTH.
4. CONDUITS SHALL NOT BE STACKED MORE THAN 2 LAYERS HIGH. LARGER DIAMETER
CONDUITS SHALL BE PLACED AT BOTTOM OF TRENCH WHEN POSSIBLE
5. ALL CONDUITS SHALL BE SECURED FROM "FLOATING" DUE TO BACKFILL.
6.STEEL WIRE OR REBAR ARE NOT ACCEPTABLE FOR SECURING CONDUIT, THIS WILL CREATE HEAT.
7.MECHANICAL COMPACTION IS NOT ALLOWED WITHIN 6" OF ELECTRICAL CONDUITS.
8.ALL HIGH VOLTAGE TRENCH REQUIRES MARKING TAPE TO BE PLACED 12" ABOVE CONDUIT.
9.SEE PROJECT DRAWING FOR CONDUIT SIZE AND QUANTITY
UNDERGROUND DISTRIBUTION. SYSTEM DESIGN STANDARDS
ED3
TELCO/TV/GAS
FINAL GRADE
TOP CONDUIT
SLOPE=20:1 MAX.
N.T.S.
FINAL GRADE
MIN
.
2'
STORM DRAIN
OR BOX CULVERT
ELECTRICAL DISTRICT #3- ENGINEERING Date: 3-31-21
Dwn by:
Dwn No:
1 of 1
TRENCH DETAIL
GE
UG 22
3District No.
Electrical
STORM DRAIN
TRENCH NOTES
1. CUSTOMER TO INSTALL ELECTRONIC MARKERS AT ALL CONDUIT STUBOUTS.
2. ALL CONDUITS SHALL BE SCHEDULE 40
3. CONDUIT SHALL NOT OCCUPY MORE THAN 30 INCHES OF HORIZONTAL WIDTH.
4. CONDUITS SHALL NOT BE STACKED MORE THAN 2 LAYERS HIGH. LARGER DIAMETER
CONDUITS SHALL BE PLACED AT BOTTOM OF TRENCH WHEN POSSIBLE
5. ALL CONDUITS SHALL BE SECURED FROM "FLOATING" DUE TO BACKFILL.
6.STEEL WIRE OR REBAR ARE NOT ACCEPTABLE FOR SECURING CONDUIT, THIS WILL CREATE HEAT.
7.MECHANICAL COMPACTION IS NOT ALLOWED WITHIN 6" OF ELECTRICAL CONDUITS.
8.ALL HIGH VOLTAGE TRENCH REQUIRES MARKING TAPE TO BE PLACED 12" ABOVE CONDUIT.
9.SEE PROJECT DRAWING FOR CONDUIT SIZE AND QUANTITY
UNDERGROUND DISTRIBUTION. SYSTEM DESIGN STANDARDS
METER
10'
3'
3'
3'
45
3'
TYP.
METER
10'
3'
3'
ST
RE
ET
=TRANSFORMER PAD
454'
5'
3'
10'
L
C
P
L
L
P
ELECTRICAL DISTRICT #3- ENGINEERING Date: 11-29-17
Dwn by:
Dwn No:
1 of 1
CLEARANCE DETAIL
JG
UG 23
3District No.
Electrical
TRANSFORMER PLACEMENT
NOTES
1. 24" MINIMUM SEPARATION BETWEEN TRANSFORMER AND WATER METER BOXES
2. 24" MINIMUM SEPARATION BETWEEN TRANSFORMER AND COMMUNICATION PEDS
3. 24" MINIMUM SEPARATION BETWEEN TRANSFORMER AND STREET LIGHT POLES
4. SEE CLEARANCE DETAIL (TRANSFORMER CLEARANCE) FOR PLACEMENT DETAILS
UNDERGROUND DISTRIBUTION. SYSTEM DESIGN STANDARDS
T
36"
36"
21"
24"12"
MAINTAIN A 24" MINIMUM
SEPERATION BETWEEN
TRANSFORMER AND
COMMUNICATION PEDESTAL.
60"
C
L
48"
R/W
TRENCH
10'
MIN
IM
UM
CLE
AR
AN
CE
TV
G
E
STREET SIDE
COMMUNICATIONS PEDESTAL
MAY ONLY BE LOCATED WITHIN
THE REAR 21" OF THE TRANSFORMER
PAD AS SHOWN. (TYP.)
CENTERLINE
OF PAD
GROUND ROD
TE
LC
O
PE
D
CA
TV
PE
D
ELECTRICAL DISTRICT #3- ENGINEERING Date: 12-12-17
Dwn by:
Dwn No:
1 of 1
CLEARANCE DETAIL
JG
UG 24
3District No.
Electrical
TRANSFORMER CLEARANCE
NOTES
1. 24" MINIMUM SEPARATION BETWEEN TRANSFORMER AND WATER METER BOXES
2. 24" MINIMUM SEPARATION BETWEEN TRANSFORMER AND COMMUNICATION PEDS
3. 24" MINIMUM SEPARATION BETWEEN TRANSFORMER AND STREET LIGHT POLES
4. 10' MINIMUM CLEARANCE IN FRONT OF ALL UTILITY TRANSFORMERS
5. 36" MINIMUM CLEARANCE FROM ANY BUILDING
UNDERGROUND DISTRIBUTION. SYSTEM DESIGN STANDARDS
=J-BOX
ELECTRIC METER
TYP.
36"
45
36"
36"
60"
ST
RE
ET
ELECTRIC METER
36
"
36"
R/W
C
L
10'
60"
R/W
WATER
METER
BOX
60"
ELECTRICAL DISTRICT #3- ENGINEERING Date: 1-10-18
Dwn by:
Dwn No:
1 of 1
CLEARANCE DETAIL
GE
UG 25
3District No.
Electrical
HAND HOLE PLACEMENT
NOTES
1. 24" MINIMUM SEPARATION BETWEEN J-BOX AND WATER METER BOXES
2. 24" MINIMUM SEPARATION BETWEEN J-BOX AND COMMUNICATION PEDS
3. 60" MINIMUM SEPARATION BETWEEN J-BOX AND FIRE HYDRANTS
UNDERGROUND DISTRIBUTION. SYSTEM DESIGN STANDARDS
SIDE OF STREET
- DESIGNATES POLE WITH ST. LIGHT
ADJACENT TO A TRANSFORMER:
SIDEWALK)
(XFMR DOOR
OPENS TOWARDS
P
L
- DESIGNATES J-BOX
ON A CORNER:
P.C.
OR CURB
OF S/W
TRENCH LINE
SOURCE ON OPPOSITE
4' MIN.
S/W
SIDE OF STREET
SOURCE ON SAME
1'
4' MIN.
S/W
1'
AT LOT LINE:
TRENCH LINE
P
L
P
L
PAD
1'
XFMR.
SERVICE
J-BOX
TAP FROM
TRENCH LINE
L
3'
P
P
L
1'
CHECK WITH LOCAL CITY OF MARICOPA
FOR STREET LIGHT REQUIREMENTS.
L
P
ELECTRICAL DISTRICT #3- ENGINEERING Date: 3-31-21
Dwn by:
Dwn No:
1 of 1
GE
UG 26
3District No.
Electrical
CLEARANCE DETAIL STREETLIGHT PLACEMENT
NOTES
1. J-BOX TO BE LOCATED ON BACK SIDE OF POLE
2. IF SOURCE IS ON OPPOSITE SIDE OF STREET THEN LOCATE J-BOX ON SIDE OF TRAFFIC
3. LOCATE POLE 12" BACK OF SIDEWALK
4. IF SIDEWALK IS MEANDERING OR DETACHED FROM CURB, LOCATE POLE 48" BACK OF CURB
5. CUSTOMER TO CHECK WITH CITY STREET LIGHT REQUIREMENTS ON ALL JOBS
UNDERGROUND DISTRIBUTION. SYSTEM DESIGN STANDARDS
SW ENCLCAP BANK
DOORS
S
DOORS
10'
10'
10'
DOOR
10'
CAP
5' 5' 5'
TRANSFORMER
DOOR
10'
5'
5'
5'
DOOR
ELECTRICAL DISTRICT #3- ENGINEERING Date: 3-31-21
Dwn by:
Dwn No:
1 of 1
CLEARANCE DETAIL
GE
UG 27
3District No.
Electrical
PME WORKING CLEARANCES
NOTES
1. 10' MINIMUM CLEARANCE IN FRONT OF ANY PAD MOUNTED EQUIPMENT DOOR
2. 5' MINIMUM CLEARANCE AROUND ALL SIDES OF ANY PAD MOUNTED EQUIPMENT
3. MINIMUM CLEARANCES INCLUDE ALL SPRINKLER AND IRRIGATION ZONES
4.CUSTOMER SHALL PROVIDE 20' DRY ZONE LANDSCAPING FOR ALL PAD MOUNTED EQUIPMENT
UNDERGROUND DISTRIBUTION. SYSTEM DESIGN STANDARDS
FRONT OF EQUIPMENT
18
"
10"
18
"
10"
(VULNERABLE FROM FRONT)
FRONT OF EQUIPMENT
18"
10
"
(V
UL
NE
RA
BL
E F
RO
M S
ID
E
18"
10
"
ELECTRICAL DISTRICT #3- ENGINEERING Date: 3-31-21
Dwn by:
Dwn No:
1 of 1
GE
UG 28
3District No.
Electrical
CLEARANCE DETAIL EQUIPMENT BOLLARDS
NOTES
1. INSTALL WHERE NECESSARY TO PROTECT PAD MOUNT EQUIPMENT
2. DO NOT INSTALL POST WHICH WOULD RESTRICT ACCESS TO THE EQUIPMENT
2. DO NOT INSTALL POST WHICH WOULD RESTRICT ANY DOOR FROM FULLY OPENING
4. INSTALL ON EACH SIDE EXPOSED TO PROTECT AGAINST VEHICLES
5. BACKFILL POST WITH CONCRETE MIX
6. APPLY REFLECTIVE TAPE 18" AND 30" ABOVE GROUND LINE
UNDERGROUND DISTRIBUTION. SYSTEM DESIGN STANDARDS
ELECTRICAL DISTRICT #3- ENGINEERING Date: 11-29-17
Dwn by:
Dwn No:
1 of 1
DIMENSIONS
JG
UG 29
3District No.
Electrical
TRANSFORMER PADS
NOTES
1. R-PROVISION FOR GROUND ROD
2. PAD MUST BE A MINIMUM OF 6" THICK
3. ALL CONDUITS SHALL BE SCHEDULE 40
4. ALL BENDS SHALL BE 36" RADIUS
5. SEE PROJECT DRAWING FOR CONDUIT SIZE AND QUANTITY
6. ALL SERVICE ENTRANCE SECTIONS LARGER THAN 1600AMPS ARE TO BE APPROVED BY ED3
7. ED3 WILL DETERMINE TRANSFORMER SIZING FOR ALL LOADS GREATER THAN 2500AMPS
UNDERGROUND DISTRIBUTION. SYSTEM DESIGN STANDARDS
63
"
72"
11"50"11"
5"
15
"4
3"
12
"3
9"
12
"3
"3
"
6"
2" C
lr.
72"
63"
TOP VIEW
FRONT VIEW
SIDE VIEW
(4) 3/4" FERRULE LOOP INSERTS
(2 EACH SIDE)
PRIMARY SECONDARY
IN OUT
#4 REBAR
GROUND ROD
ELECTRICAL DISTRICT #3- ENGINEERING Date: 6-4-18
Dwn by:
Dwn No:
1 of 1
DIMENSIONS
GE
UG 30
3District No.
Electrical
63X72 TRANSFORMER PAD
NOTES
1. ALL CONCRETE PADS SHALL BE 3000PSI RATING
2. REINFORCING STEEL SHALL BE ASTM-A615 GRADE 60
3. REINFORCING STEEL SHALL BE SPACED 6" O.C EACH AND AND BE SECURELY TIED
4. MINIMUM CONCRETE COVERAGE OVER REINFORCEMENT STEEL SHALL BE 2"
5. ALL FILL BELOW AND AROUND ELECTRIC UTILITY FIXTURE FOUNDATION PADS SHALL BE SRP 60/40
6. A 2" GAP BETWEEN PAD AND ALL CONDUITS IS REQUIRED FOR PAD ADJUSTMENTS
UNDERGROUND DISTRIBUTION. SYSTEM DESIGN STANDARDS
3"
3"
6"
88"
TOP VIEW
FRONT VIEW
PRIMARY SECONDARY
IN OUT
32" 20"
18" 52" 18"
45"
15"
52 1/2"
16 1/2"
(BACK OF TRANSFORMER)
75"
6" 16 1/2" 52 1/2"
2"
GROUND ROD
GROUND ROD
GROUND ROD
FOR DELIVERED PAD ONLY:
(4) 3/4" FERRULE LOOP INSERTS
88"
75"
6"
15"
SIDE VIEW
ELECTRICAL DISTRICT #3- ENGINEERING Date: 9-30-20
Dwn by:
Dwn No:
1 of 1
DIMENSIONS
GE
UG 31
3District No.
Electrical
75X88 TRANSFORMER PAD
NOTES
1. ALL CONCRETE PADS SHALL BE 3000PSI RATING
2. REINFORCING STEEL SHALL BE ASTM-A615 GRADE 60
3. REINFORCING STEEL SHALL BE SPACED 6" O.C EACH AND AND BE SECURELY TIED
4. MINIMUM CONCRETE COVERAGE OVER REINFORCEMENT STEEL SHALL BE 2"
5. ALL FILL BELOW AND AROUND ELECTRIC UTILITY FIXTURE FOUNDATION PADS SHALL BE SRP 60/40
6. A 2" GAP BETWEEN PAD AND ALL CONDUITS IS REQUIRED FOR PAD ADJUSTMENTS
UNDERGROUND DISTRIBUTION. SYSTEM DESIGN STANDARDS
TOP VIEW
FRONT VIEW
SIDE VIEW
BACK OF TRANSFORMER
PRIMARY SECONDARY
IN OUT
(4) 3/4" Ferrule Loop Inserts
(2 Each Side)
100"
6" 16 1/2" 77 1/2"
77 1/2"
16 1/2"
6"
18"
64"
18"
25" 52" 25"
30" 22"
3"
3"
6"
102"
GROUND ROD
GROUND ROD
2"
GROUND ROD
102"
100"
ELECTRICAL DISTRICT #3- ENGINEERING Date: 11-21-17
Dwn by:
Dwn No:
1 of 1
DIMENSIONS
JG
UG 32
3District No.
Electrical
100X102 TRANSFORMER PAD
NOTES
1. ALL CONCRETE PADS SHALL BE 3000PSI RATING
2. REINFORCING STEEL SHALL BE ASTM-A615 GRADE 60
3. REINFORCING STEEL SHALL BE SPACED 6" O.C EACH AND AND BE SECURELY TIED
4. MINIMUM CONCRETE COVERAGE OVER REINFORCEMENT STEEL SHALL BE 2"
5. ALL FILL BELOW AND AROUND ELECTRIC UTILITY FIXTURE FOUNDATION PADS SHALL BE SRP 60/40
6. A 2" GAP BETWEEN PAD AND ALL CONDUITS IS REQUIRED FOR PAD ADJUSTMENTS
UNDERGROUND DISTRIBUTION. SYSTEM DESIGN STANDARDS
84
"
TOP VIEW
6"
84"
FRONT VIEW
84"
7"
SIDE VIEW
(4) 3/4" Ferrule Loop Inserts
3"
(2) 6" Long P3200 Unistrut
7" 18" 59"
17" 50" 17"
50" x 18" Blockout
84"
17" 17"50"
12
"1
2"
60
"
ELECTRICAL DISTRICT #3- ENGINEERING Date: 6-4-21
Dwn by:
Dwn No:
1 of 1
DIMENSIONS
GE
UG 33
3District No.
Electrical
84X84 CAPACITOR PAD
NOTES
1. ALL CONCRETE PADS SHALL BE 3000PSI RATING
2. REINFORCING STEEL SHALL BE ASTM-A615 GRADE 60
3. REINFORCING STEEL SHALL BE SPACED 6" O.C EACH AND AND BE SECURELY TIED
4. MINIMUM CONCRETE COVERAGE OVER REINFORCEMENT STEEL SHALL BE 2"
5. ALL FILL BELOW AND AROUND ELECTRIC UTILITY FIXTURE FOUNDATION PADS SHALL BE SRP 60/40
6. A 2" GAP BETWEEN PAD AND ALL CONDUITS IS REQUIRED FOR PAD ADJUSTMENTS
UNDERGROUND DISTRIBUTION. SYSTEM DESIGN STANDARDS
B CA
4321 4
321 4321
432
1
TOP VIEW
SIDE VIEW
END VIEW
(2) 5/8"S8' GROUND RODS ED3 TO PROVIDE
CUSTOMER TO INSTALL
ELECTRICAL DISTRICT #3- ENGINEERING Date: 12-17-18
Dwn by:
Dwn No:
1 of 1
DIMENSION
JG
UG 34
3District No.
Electrical
JUNCTION CABINET
NOTES
1. ALL FILL BELOW AND AROUND ELECTRIC UTILITY FIXTURE FOUNDATION PADS SHALL BE SRP 60/40
2. A 2" GAP BETWEEN PAD AND ALL CONDUITS IS REQUIRED FOR SLEEVE ADJUSTMENTS
3. ALL CONDUIT SHALL BE SCHEDULE 40
4. ALL BENDS SHALL BE 36" RADIUS
5. SEE PROJECT DRAWING FOR CONDUIT SIZE AND QUANTITY
UNDERGROUND DISTRIBUTION. SYSTEM DESIGN STANDARDS
3'-0
"
4'-0" (2) Pulling Irons(Recessed In Floor)
2436 Bolt Down GalvanizedFrame and Cover
2'-0
"3'
-0"
3'-4
"1'
-4"
10"
612"2'-11"61
2"
(2) P3200 Unistrut (2'-6")(1 Each Side)
8" Dia. ThruSump Hole In Floor
(4) 10" x 10" Knockouts(2 Each End)
(2) 16" x 16" Knockouts(1 Each End)
3'-1
0"10
"10
"
6"4'
-83 4"
31 4"
5'-6
"
612"1'-11"61
2"
TOP VIEW
End View
Section View
(2) 2 1/2" Dia. Ground Rod Knockouts(Opposite Corners)
ASTM C-857 "MINIMUM STRUCTURAL DESIGNLOADING FOR UNDERGROUND PRECAST CONCRETE
STRUCTURAL NOTES:1. CONCRETE: 28 DAY COMPRESSIVE STRENGTH F'C = 5000 PSI2. REBAR: ASTM A-615 GRADE 603. MESH: ASTM A-185 GRADE 654. DESIGN: ACI-318-99 BUILDING CODE
GENERAL NOTES:1. ALL JOINTS SHALL BE SEALED USING CONSEAL CS-101 BUTYL RUBBER ROPE
UTILITY STRUCTURES"
80 PCF LATERAL SOIL PRESSURE BELOW WATER TABLESOIL: 40 PCF LATERAL SOIL PRESSURE ABOVE WATER TABLE80 PSF LATERAL LIVE LOAD SURCHARGE - UP TO 8'-0" DEPTH
7. WATER TABLE: 5'-0" BELOW GRADE6. SOIL COVER: 0' TO 5' (MAX.)
120 PCF SOIL DENSITY
5. LOADS: HS20 WHEEL LOADING IN OFF-STREET LOCATIONS WHERE NOTSUBJECTED TO HIGH DENSITY TRAFFIC
2. ALL FILL BELOW AND AROUND ELECTRIC UTILITY FIXTURE FOUNDATIONS SHALL BE 60/40 SRP FILL
ELECTRICAL DISTRICT #3- ENGINEERING Date: 1-22-17
Dwn by:
Dwn No:
1 of 1
DIMENSIONS
GE
UG 353District No.Electrical
36X48 PULLING VAULT
FOR
REFERENCE
ONLY
(4) P4000 Unistrut (36")
(1 Each Face)
6"
60"
7"
40"
FRONT VIEW
56"
56"
TOP VIEW
(4) Pulling Irons
(1 Each Side)
(2) 2
1
2
" Dia. x 5" Deep
Ground Rod Knockouts
Frame & Cover
56"
47"
31"
73"
12"
30"
(4) 24" x 30" Knockout
(1 Each Face)
4
1
2
"
SIDE VIEW
4
1
2
"
(1) 8" Dia. x 4
1
2
" Deep
Sump Hole in Floor
73"
6" OF COMPACTED CRUSHED
ROCK 3/4" MIN. - 11/2"MAX
CONDUITS
6"
ELECTRICAL DISTRICT #3- ENGINEERING Date: 1-22-18
Dwn by:
Dwn No:
1 of 1
DIMENSIONS
GE
UG 36
3District No.
Electrical
56X56 PULLING VAULT
NOTES
1. ALL FILL BELOW AND AROUND ELECTRIC UTILITY FIXTURE FOUNDATION PADS SHALL BE SRP 60/40
2. SEE PROJECT DRAWING FOR CONDUIT SIZE AND QUANTITY
3. TOP MUST BE 6" ABOVE STAKED BLUETOP MARKERS
UNDERGROUND DISTRIBUTION. SYSTEM DESIGN STANDARDS
1'-6" 1'-6"
2'-3
"3
'-0
"2
'-9
"
10"1'-6"4'-4"1'-6"10"
1'-4
"4
'-1
0"
8'-4" Inside Length
4" 4"
8'-0
" O
utsid
e H
eig
ht
9'-0" Outside Length
5'-0
" O
utsid
e W
id
th
TOP VIEW
FRONT VIEW
(3) US West Pulling Irons In Base
(4) 1
1
4
" Rocket Inserts
For Cable Pulling Eye Bolts
(1 Each Corner)
(2) 2
1
2
" Dia. x 3" Deep
Ground Rod Knockouts
12" Dia. x 2
1
2
" Deep Sump
With Indent Plastic Grate
3672 Galvanized Double Torsion Door
(8) P4000 Unistrut (4'-0")
(3 Each Side)(1 Each End)
(8) 18" x 18" Knockouts
(4 Each Side)
1'-1
0"
ELECTRICAL DISTRICT #3- ENGINEERING Date: 11-27-17
Dwn by:
Dwn No:
1 of 2
DIMENSIONS
JG
UG 37
3District No.
Electrical
60X108 PULLING VAULT
UNDERGROUND DISTRIBUTION. SYSTEM DESIGN STANDARDS
2'-2"
1'-6"
1'-6"
2'-8"
10"1'-6"1'-6"10"
8"
7'-0" Inside H
eight
4"
4"4'-4" Inside Width4"
SIDE VIEW
(4) 18" x 36" Knockouts
(2 Each End)
Shallow Top Weight
4,360 lbs.
Riser Weight
5,900 lbs.
Deep Base Weight
5,200 lbs.
2"
4"
ELECTRICAL DISTRICT #3- ENGINEERING Date: 11-27-17
Dwn by:
Dwn No:
2 of 2
DIMENSIONS
JG
UG 37
3District No.
Electrical
60X108 PULLING VAULT
1. ALL FILL BELOW ELECTRIC UTILITY FIXTURE SHALL BE 60/40 SRP BACKFILL
2. SEE PROJECT DRAWING FOR CONDUIT SIZE AND QUANTITY
3. ALL CONDUIT SHALL BE SCHEDULE 40
4. ALL BENDS SHALL BE 36" RADIUS
5. EXCAVATED BASE SHALL INCLUDE 6" LAYER OF 3/4" WASHED ROCK
6. WASHED ROCK SHALL HAVE A 3" LAYER OF PEA GRAVEL FOR LEVELING
7. TOP MUST BE 6" ABOVE BLUETOP MARKERS
NOTES:
UNDERGROUND DISTRIBUTION. SYSTEM DESIGN STANDARDS
5"5'-0"5"
7"1'-6"1'-8"1'-6"7"
2'-0
"1
'-6
"
1'-0
"
1'-6
"2
'-0
"
4'-0
" T
op
H
eig
ht
4'-0
" B
ase
H
eig
ht
10'-0" Inside Length
10'-10" Outside Length
11'-6" Ribbing Length
5'-0
" In
sid
e W
id
th
5'-1
0" O
utsid
e W
id
th
6'-6
" R
ib
bin
g W
id
th
1'-6
"1
'-6
"
C
L
C
L
TOP VIEW
SIDE VIEW
(8) Pulling Irons
(2 Each Top End)
(2 Each Base End)
(4) 2 1/2" Dia.
Ground Rod
Knockouts In Floor
(2) 332P Covers
(16) 18" x 18" Knockouts
(4 Each Wall)
4'-0"4'-0"
4'-2" 2'-10" 6"
(2) Galvanized Steps With
Galvanized Hook Ladders
1'-0
"
6"
(4) 1/2" Dia. Bronze
Grounding Inserts
(2 Each End)
2'-10"1'-1" 1'-1"
6" 2'-10"
(4) P3200 Unistrut (1'-9")
(2 Each End)
ELECTRICAL DISTRICT #3- ENGINEERING Date: 11-27-17
Dwn by:
Dwn No:
1 of 2
DIMENSIONS
JG
UG 38
3District No.
Electrical
510 PULLING VAULT
UNDERGROUND DISTRIBUTION. SYSTEM DESIGN STANDARDS
5"10'-0"5"
1'-6"9" 1'-6" 6'-4" 9"
6"
8'-0" O
verall H
eight
6"
7'-0" Inside H
eight
1'-10
1 2
"1'-10
1 2
"1'-10
1 2
"
FRONT VIEW
12" Dia. x 5" Deep Sump Knockout
With Indent And Plastic Grate
(8) P3200 Unistrut (6'-0")
(4 Each Side)
4'-2" 2'-10" 1"
Racking Package
20 - 7 1/2" Hooks
16 - 1/2" Spring Nuts And Bolt
4 - 47 Hole Rack
1" 2'-10"
6" of Compacted Crushed Rock
3/4" Min. - 1 1/2" Max Conduits
ELECTRICAL DISTRICT #3- ENGINEERING Date: 11-27-17
Dwn by:
Dwn No:
2 of 2
DIMENSIONS
JG
UG 38
3District No.
Electrical
510 PULLING VAULT
1. ALL FILL BELOW ELECTRIC UTILITY FIXTURE SHALL BE 60/40 SRP BACKFILL
2. SEE PROJECT DRAWING FOR CONDUIT SIZE AND QUANTITY
3. ALL CONDUIT SHALL BE SCHEDULE 40
4. ALL BENDS SHALL BE 36" RADIUS
5. EXCAVATED BASE SHALL INCLUDE 6" LAYER OF 3/4" WASHED ROCK
6. WASHED ROCK SHALL HAVE A 3" LAYER OF PEA GRAVEL FOR LEVELING
7. TOP MUST BE 6" ABOVE BLUETOP MARKERS
NOTES:
UNDERGROUND DISTRIBUTION. SYSTEM DESIGN STANDARDS
11'-112" Outside Length
7'-1
1 2" Out
side
Wid
th
10'-0" Inside Length
6'-0
" Ins
ide
Wid
th
TOP VIEW
FRONT VIEW
60" X 61"CLEAR OPENING
(2) 2 1/2" Dia. GroundRod Knockouts In Floor
10'-0"
1'-5"5'-1" 2'-10"
6"
7'-0
"6"
8'-0
"
41 4"
Optional Pedestrian RatedTemp. Cover
5'-9"
5"
1'-1
01 2"
412"2'-0"5'-3"2'-0"41
2"
1'-0
"1'
-81 2"
1'-1
11 2"2'
-6"
(4) P3200 Unistrut (4'-0")(2 Each Side Wall)
1'-0
3 4"
1'-034"
6"
634"2"63
4" 6"
834"
12" Dia. x 5" Deep Sump KnockoutWith Indent For Plastic Grate
6" OF COMPACTED CRUSHEDROCK 3/4" MIN. - 1 1/2" MAXCONDUITS
ELECTRICAL DISTRICT #3- ENGINEERING
SPECIFICATIONS
Date: 11-27-17
Dwn by:
Dwn No:
1 of 2
DIMENSIONS
JG
UG 393District No.Electrical
610 SWITCH VAULT
5'-0"(4) 1/2" Dia. BronzeGrounding Inserts(2 Each Top End)
6"(4) 1/2" Inserts(2 Each Top End)6"
5'-8"
4'-1
11 2"
412"41
2" 1'-3"2'-0" 2'-0" (8) 24" x 30" Knockouts(2 Each Wall)
3'-0
1 2"(8) Recessed Pulling Irons
(4 Each End)
Galvanized Step WithGalvanized Hook Ladder
Racking Package
20 - 7 1/2" Hooks
8 - 1/2" Spring Nuts And Bolt
4 - 47 Hole Rack
SIDE VIEW
ELECTRICAL DISTRICT #3- ENGINEERING
SPECIFICATIONS
Date: 11-27-17
Dwn by:
Dwn No:
2 of 2
DIMENSIONS
JG
UG 393District No.Electrical
610 SWITCH VAULT
1. ALL FILL BELOW ELECTRIC UTILITY FIXTURE SHALL BE 60/40 SRP BACKFILL2. SEE PROJECT DRAWING FOR CONDUIT SIZE AND QUANTITY3. ALL CONDUIT SHALL BE SCHEDULE 404. ALL BENDS SHALL BE 36" RADIUS5. EXCAVATED BASE SHALL INCLUDE 6" LAYER OF 3/4" WASHED ROCK6. WASHED ROCK SHALL HAVE A 3" LAYER OF PEA GRAVEL FOR LEVELING7. TOP MUST BE 6" ABOVE BLUETOP MARKERS
NOTES:
71"
68"
FRONT VIEW
SIDE VIEW
TOP VIEW
71"
5"
68"
(R
2) 9 S
paces @
6" O
.C
.
4
1 2
"4
1 2
"
(R1) 11 Spaces @ 6" O.C.
8"
3 4
"
3/4" x 8" Keyway
Both Sides Of Slab
2"
Typ.
3"
Typ.
Tie #4 Scrap Bars
On Top Of Inserts
As Shown
DETAIL 1
14"
Typ.
40"
Typ.
14"
Typ.
(4) 3/4" Ferrule Loop Inserts
With Scrap Bars
(See Detail 1)
1
1 2
"C
lr.
Typ.
Not To Scale
3/4"
Clr.
6" 59" 6"
52" 8"
3/4" x 6" Keyway
Both Ends Of Slab
ELECTRICAL DISTRICT #3- ENGINEERING Date: 1-11-18
Dwn by:
Dwn No:
1 of 1
DIMENSIONS
GE
UG 40
3District No.
Electrical
68X71 VAULT LID
NOTES
1. ALL CONCRETE PADS SHALL BE 3000PSI RATING
2. REINFORCING STEEL SHALL BE ASTM-A615 GRADE 60
3. REINFORCING STEEL SHALL BE SPACED 6" O.C EACH AND AND BE SECURELY TIED
4. MINIMUM CONCRETE COVERAGE OVER REINFORCEMENT STEEL SHALL BE 2"
5. ALL FILL BELOW AND AROUND ELECTRIC UTILITY FIXTURE FOUNDATION PADS SHALL BE SRP 60/40
6. A 2" GAP BETWEEN PAD AND ALL CONDUITS IS REQUIRED FOR PAD ADJUSTMENTS
UNDERGROUND DISTRIBUTION. SYSTEM DESIGN STANDARDS
6"
156"
144"
6" B6"
A A84" 72"
6" BPLAN VIEW
8"
50"44"
99" 84"
40" 49"
7" 24"x24"x3.5"DEEP THINWALL
KNOCKOUTS(2) EACH LONG
WALL
4
SECTION A-A
ELECTRICAL DISTRICT #3- ENGINEERING
SPECIFICATIONS
Date: 7-27-21
Dwn by:
Dwn No:
1 of 2
DIMENSIONS
GE
UG 413District No.Electrical
612 SWITCH VAULT
18"x18"x3.5"DEEP THINWALL
KNOCKOUTS(2) EACH LONG
WALLSECTION B-B
ELECTRICAL DISTRICT #3- ENGINEERING
SPECIFICATIONS
Date: 7-27-21
Dwn by:
Dwn No:
2 of 2
DIMENSIONS
GE
UG 413District No.Electrical
612 SWITCH VAULT
1. ALL FILL BELOW ELECTRIC UTILITY FIXTURE SHALL BE 60/40 SRP BACKFILL2. SEE PROJECT DRAWING FOR CONDUIT SIZE AND QUANTITY3. ALL CONDUIT SHALL BE SCHEDULE 404. ALL BENDS SHALL BE 36" RADIUS5. EXCAVATED BASE SHALL INCLUDE 6" LAYER OF 3/4" WASHED ROCK6. WASHED ROCK SHALL HAVE A 3" LAYER OF PEA GRAVEL FOR LEVELING7. TOP MUST BE 6" ABOVE BLUETOP MARKERS
NOTES:
LIG
HT
HE
IG
HT
13'A
B
C
D
E
18'
23'
32'
32'
*
POLE
HEIGHT
LIGHT
HEIGHT
15'
20'
25'
35'
35'
ARM
LENGTH
6'
6'
8'
6'
8'
PO
LE
HE
IG
HT
ARM
LENGTH
ELECTRICAL DISTRICT #3- ENGINEERING Date: 12-18-20
Dwn by:
Dwn No:
1 of 1
STREETLIGHT
JG
SL 01
3District No.
Electrical
STANDARD HEIGHTS
1. ALL CONDUIT SHALL BE SCHEDULE 40
2. ALL BENDS SHALL BE 36" RADIUS
3. BLUE-TOP TO BE 3" ABOVE CURB OR SIDEWALK
4. SEE PROJECT DRAWING FOR CONDUIT SIZE AND QUANTITY
NOTES:
UNDERGROUND DISTRIBUTION. SYSTEM DESIGN STANDARDS
35°
2
15
16
"
1
7
16
"
1
2
"
4
3
8
"
4
3
4
"
7
8
"
1
4
"
1
4
"
4
1
2
"
1
2
"
ELECTRICAL DISTRICT #3- ENGINEERING Date: 12-18-20
Dwn by:
Dwn No:
1 of 1
STREETLIGHT
JG
SL 02
3District No.
Electrical
STANDARD ARM ATTACHMENT
UNDERGROUND DISTRIBUTION. SYSTEM DESIGN STANDARDS
6"
1"
2"
4"
GRADE
60"
24"
24"
GROUNDING PLATE
24"
ST
RE
ET
CU
RB
36"
TO ST LT
J-BOX
ANCHOR BOLTS
(1"X 3')
#6 SOLID CU
GROUND WIRE
4 BOLT
CIRCLE
(10-1/2")
HANDHOLE
ELECTRICAL DISTRICT #3- ENGINEERING Date: 3-15-21
Dwn by:
Dwn No:
1 of 1
STREETLIGHT
JG
SL 03
3District No.
Electrical
4 BOLT BASE DECORATIVE
1. ALL CONDUIT SHALL BE SCHEDULE 40
2. ALL BENDS SHALL BE 36" RADIUS
3. BLUE-TOP TO BE 3" ABOVE CURB OR SIDEWALK
4. SEE PROJECT DRAWING FOR CONDUIT SIZE AND QUANTITY
5. ABOVE GROUND J-BOLTS TO BE GROUTED AFTER INSTALLATION
NOTES:
UNDERGROUND DISTRIBUTION. SYSTEM DESIGN STANDARDS
36"
6"
1"
2"
4"
GRADE
60"
24"
24"
GROUNDING PLATE
#6 SOLID CU GROUND WIRE
ANCHOR BOLTS (1"X 3')
24"
JUNCTION
BOX
2"
2"
ST
RE
ET
CU
RB
36"
4 BOLT
CIRCLE
(10-1/2")
ELECTRICAL DISTRICT #3- ENGINEERING Date: 3-15-21
Dwn by:
Dwn No:
1 of 1
STREETLIGHT
JG
SL 04
3District No.
Electrical
4 BOLT BASE WITH HANDHOLE
1. ALL CONDUIT SHALL BE SCHEDULE 40
2. ALL BENDS SHALL BE 36" RADIUS
3. BLUE-TOP TO BE 3" ABOVE CURB OR SIDEWALK
4. SEE PROJECT DRAWING FOR CONDUIT SIZE AND QUANTITY
5. ABOVE GROUND J-BOLTS TO BE GROUTED AFTER INSTALLATION
NOTES:
UNDERGROUND DISTRIBUTION. SYSTEM DESIGN STANDARDS
6"
1"
2"
4"
GRADE
60"
24"
24"
GROUNDING PLATE
24"
ST
RE
ET
CU
RB
36"
TO ST LT
J-BOX
ANCHOR BOLTS
(1" 0 X 3'-0")
#6 SOLID CU
GROUND WIRE
4 BOLT
CIRCLE
(10-1/2")
ELECTRICAL DISTRICT #3- ENGINEERING Date: 3-15-21
Dwn by:
Dwn No:
1 of 1
STREETLIGHT
JG
SL 05
3District No.
Electrical
4 BOLT BASE WITHOUT HANDHOLE
1. ALL CONDUIT SHALL BE SCHEDULE 40
2. ALL BENDS SHALL BE 36" RADIUS
3. BLUE-TOP TO BE 3" ABOVE CURB OR SIDEWALK
4. SEE PROJECT DRAWING FOR CONDUIT SIZE AND QUANTITY
5. ABOVE GROUND J-BOLTS TO BE GROUTED AFTER INSTALLATION
NOTES:
UNDERGROUND DISTRIBUTION. SYSTEM DESIGN STANDARDS
36" R
6"
GROUNDING PLATE
GROUND WIRE
CONCRETE (CLASS A)ANCHOR BOLTS (1" O X 3'-0")
(2 1/2" SCH 40)
GRADE
1 1/2" GROUT UNDER 1" CHAMFER
CURB
HANDHOLE
HANDHOLES SIDE ARE 90 PERPENDICULAR TO CURB.
2'
3'
HANDHOLE
14" DIA. 3 BOLT PATTERN
JUNCTIONBOX
TO JUNCTION BOX
BOLT HOLES ON THE
ENTIRE BASE
PVC CONDUIT
I
3" CL
5'
ELECTRICAL DISTRICT #3- ENGINEERING
SPECIFICATIONS
Date: 3-20-21
Dwn by:
Dwn No:
1 of 1
STREETLIGHT
JG
SL 063District No.Electrical
3 BOLT BASE DECORATIVE
OBSOLETE
A
C
B
D
UNIT DESCRIPTION PART NUMBER
A 18FT 5" ROUND POLE CRB511-18
A 30FT 5" ROUND POLE CRB511-30
B DECORATIVE BASE WDN2093D9MDBZ
C DECORATIVE ARM TRA60
D 116WATT FIXTURE 20A1021APRM2272L5004K73DB
D 70WATT FIXTURE 15A1045PRM2T3965LED4
ELECTRICAL DISTRICT #3- ENGINEERING Date: 4-21-21
Dwn by:
Dwn No:
1 of 1
STREETLIGHT
GE
SL 07
3District No.
Electrical
DECORATIVE STREET LIGHT
1. FOUNDATION AND CONDUIT PER ED3 SPEC SL03
2. ALL STRUCTURES TO BE APPROVED BY CITY OF MARICOPA PRIOR TO CONSTRUCTION
NOTES:
UNDERGROUND DISTRIBUTION. SYSTEM DESIGN STANDARDS