Uae Tse Reuse
-
Upload
ocean220220 -
Category
Documents
-
view
227 -
download
0
Transcript of Uae Tse Reuse
-
8/10/2019 Uae Tse Reuse
1/40
BENEFICIAL RE-USEOF
TREATED SEWAGE EFFLUENT
Presented
By
Mohammed Abdul Aziz Najem Al Awadhi
Director of Sewage Treatment Plant Department
Dubai Municipality
-
8/10/2019 Uae Tse Reuse
2/40
TSE reuse in 4 x application directions:
1. Discharge of TSE to the creeks, rivers,natural lakes and the sea to maintain
natural balance of water.
2. Irrigation water for greenery covered areas( gardens, lawns, parks ).
3. Industrial water for chilled water network
of extended air conditioning systems.
4. Decorative facilities like park pools,
ponds of golf clubs, lakes of prestigeous buildings.
-
8/10/2019 Uae Tse Reuse
3/40
-
8/10/2019 Uae Tse Reuse
4/40
-
8/10/2019 Uae Tse Reuse
5/40
Screen Building (JASTP)
-
8/10/2019 Uae Tse Reuse
6/40
Screens
1. STP must be safeguarded by Coarse
Screens ( 10 15 mm spacing ).
2. Fine Screening Requirement:
A. 6 mm bar spacing or punched holes
for conventional STP
B. MBR Plant preferred:
-
8/10/2019 Uae Tse Reuse
7/40
Efficient Screening and how it
works (at 6 mm perforation)
-
8/10/2019 Uae Tse Reuse
8/40
Primary Settling Tank (WSTP)
-
8/10/2019 Uae Tse Reuse
9/40
Invent Aeration (JASTP)
-
8/10/2019 Uae Tse Reuse
10/40
Surface Aerators (WSTP)
-
8/10/2019 Uae Tse Reuse
11/40
RAS Screw Pumps (WSTP)
-
8/10/2019 Uae Tse Reuse
12/40
Secondary Settling Tank (WSTP)
-
8/10/2019 Uae Tse Reuse
13/40
Sand Filtration and Disinfection
Gallery of Sand Filters, each of them
filled with layers of sand in different
particle size
Residual suspended solids will be
removed from the bio- treated
effluent.
-
8/10/2019 Uae Tse Reuse
14/40
Sand Filter (JASTP)
-
8/10/2019 Uae Tse Reuse
15/40
Sand Filter (JASTP)
-
8/10/2019 Uae Tse Reuse
16/40
Disinfection can be achieved
by application of facilities asfollows:
1. Traditional Chlorination.
1. Ozonation ( by generation of Ozone ).
2. Ultra Violet ( UV ) Radiation.
-
8/10/2019 Uae Tse Reuse
17/40
Chlorination usually consists of two stages:
1. Pre-chlorination is done:
A.Before or after sand filters.
B.Prior to effluent storage basins.
2. Post chlorination, which maintains residual
chlorine just before pumping the water for
irrigation to the city.
-
8/10/2019 Uae Tse Reuse
18/40
Chlorination (WSTP)
-
8/10/2019 Uae Tse Reuse
19/40
UV Lamps (JASTP)
-
8/10/2019 Uae Tse Reuse
20/40
UV Disinfection (JASTP)
-
8/10/2019 Uae Tse Reuse
21/40
UV Lamps (JASTP)
-
8/10/2019 Uae Tse Reuse
22/40
Quality ofTreated Sewage Effluent
( TSE ) Filtered Waterfrom Biological Activated
Sludge Process Plantas follows:
-
8/10/2019 Uae Tse Reuse
23/40
Parameter
STP Eff.
Jabel Ali DM Standard
Drip Spray
pH 7.2 6 - 8 6 - 8
Suspended solids (mg/L)
-
8/10/2019 Uae Tse Reuse
24/40
Dubai City Landscaping
-
8/10/2019 Uae Tse Reuse
25/40
Public Parks & Neighborhood
-
8/10/2019 Uae Tse Reuse
26/40
Market Price Comparison:
S.NO. Water Type Price (Dhs )
per Cubic Meter
1 STP Effluent 1.1
2 Potable (drinking) water from DEWA 7.7
-
8/10/2019 Uae Tse Reuse
27/40
Filtered ( 10 micrometers )TSE fromtraditional Sewage Treatment Plant
(STP) or final product of Membrane Bio-
Reactor (MBR ) process may go for
further treatment by Reverse Osmosis
( RO ) to receive high quality Permeate.
-
8/10/2019 Uae Tse Reuse
28/40
-
8/10/2019 Uae Tse Reuse
29/40
Typical MBR Plant
RAS Flow
Aeration
Effluent Flow
MembraneAeration
Anoxic Mixers
Biological Process
-
8/10/2019 Uae Tse Reuse
30/40
MBR Modules
-
8/10/2019 Uae Tse Reuse
31/40
MBR Modules
-
8/10/2019 Uae Tse Reuse
32/40
Reverse Osmosis (RO) Plant
-
8/10/2019 Uae Tse Reuse
33/40
Effluent Parameters of MBR followed by
RO.
Permeate is suitable to fill decorative
lake.
Water Parameter Units MBR TSE RO PermeateTDS mg/L 1500 100
Total Hardness CaCO3 mg/L 400 5
Calcium mg/L 64 4
Chloride mg/L 800 40T-alkalinity mg/L 70 60
PH ( dimensionless ) 6-8 7.5-8.0
Electrical Conductivity (S/cm) 250 130
-
8/10/2019 Uae Tse Reuse
34/40
Dubai Lake
-
8/10/2019 Uae Tse Reuse
35/40
Parameter IrrigationWater
DecorativeWaters
MarinaWater
E. Coli (per 100 mls) 2.2
-
8/10/2019 Uae Tse Reuse
36/40
Parameter Irrigation Discharge
Rate
Effluent
Quality
Turbidity (NTU)
-
8/10/2019 Uae Tse Reuse
37/40
Cooling water Make-up Effluent
QualityParameter Value
Chlorides (ppm) 80-90
Alkalinity (ppm) 60-70
Ca Hardness (ppm) 50-70
El. Conductivity (S/cm) 400-500
pH 7.5-8.0
TDS (ppm) 270-350
Total Hardness (CaCO3) - ppm 75-85
-
8/10/2019 Uae Tse Reuse
38/40
Chilled Water System (WSTP)
-
8/10/2019 Uae Tse Reuse
39/40
Decorative Pool (WSTP)
-
8/10/2019 Uae Tse Reuse
40/40
Thank you forAttention