Typical Grounding Arrangement for Above Ground Pipes -

1

description

Typical Grounding Arrangement for Above Ground Pipes in the power plants

Transcript of Typical Grounding Arrangement for Above Ground Pipes -

Page 1: Typical Grounding Arrangement for Above Ground Pipes -
User
Callout
Grounding Riser, which connects between main earth mesh to the pipe flange at starting end pipe portion
User
Callout
Grounding Main Mesh
User
Callout
Grounding Riser, which connects between main earth mesh to the pipe flange at final end pipe portion
User
Callout
Grounding Jumper Wire, which connects between one flange to another flange. Because, inside of flange used the non-conductive SUS (Gasket) material. So, for conductivity of ground fault current purpose, the jumper is connected between one flange to another flange. In this way, the pipe is grounded and connects to the main buried grounding mesh through grounding riser.
User
Text Box
Starting end pipe portion
User
Text Box
Final end pipe portion
User
Text Box
Inbetween pipe portions
User
Text Box
DRAWING FOR ABOVE GROUND FUEL OIL & GAS PIPING TYPICAL VALVE & PIPE CONECTION FOR BONDING
User
Stamp
User
Callout
Non- conductive SUS (Gasket) material