Testing of Line Differential Protection
VOLUME 11 / ISSU
A PUBLICATION OF OMICRON 20
WORLD LEADER IN INNOVATIVE POWER SYSTEM TESTING SOLUTIONS
neDifferentialProtection
NewFeaturesofTU2.11
estBaseTM
eproducibilityofRAMeasurements
ComicRon
vents
MajorityTakeover-mtronix
NSIDE
MICRONelectronicsGmbH
eresRied16833Klaus,Austria
one:+435523507-0
:+435523507-999
ww.omicron.at
MICRONelectronicsAsiaLtd.
te2006,20/F,Tower2
eGateway,HarbourCity,
wloon,HongKongS.A.R.
one:+85226340377
:+85226340390
ww.omicron.at
MICRONelectronicsCorp.USA
GreenwayPlaza,Suite1510
uston,Texas77046
one:+1713-830-4660
0-OMICRON
+1713-830-4661
ww.omicronusa.com
Differentiallineprotectiondevicescomparethephasecurrents (or relatedproperties) of the line ends andcheck fordeviations indicatingan internal fault.Highcurrentsresultingfromathrough-fault(faultoutsidetheprotectedzone)willincreasetheabsolutemeasurementerrorthuscreatinganapparentdifferentialcurrentthatcouldleadtofalsetripping.Thisiswhythedifferentialcurrentisbiased,forexample,bythesumofabsolutecurrentvaluesof thelineends.Therelaysat thelineends communicate for current comparison and biascalculation,formingadistributedprotectionsystem.
It is widely accepted that a proper relay test shouldpreferablybedonewithsettingsforon-siteoperation,verifyingallparametersshapingthecharacteristic.
Aneasywaytomakedifferentialrelaystripfortestingpurposesistoinjectcurrentsfromjustonesidesincethey will be seen as 100 % difference. This seemsespeciallyattractiveforlinedifferentialrelayssincetestsignalsarenotneededattheremotelocation,allowingaverysimpletestsetup.Thedisadvantageisthatusuallythe test result is restricted to a single point on therelaycharacteristicwherethesingle-injectiontrajectory
crosses the characteristic. Settings defining the e.g.multi-slope characteristics, important for high faultcurrents,canthereforenotbeverifiedbythistest.
Some relays select the highest biasing value of allphasesascommonbiasingquantity,allowingcontrolofthediff/biasrelationbyinjectingonecurrentinonephaseandadifferentoneinanotherphase.Amuchmoreversatileapproachistoinjectthecurrentsfor all line ends. This is the standard procedure fortestingtransformerdifferentialrelayswithmoderntestequipment delivering e.g. six test currents, allowingfull controlof thediff/bias relation for characteristics
verification. For a full on-site commissioning test adistributedsetupisrequired(seeFig.1).Thecurrentsatallendsmustbetightlyinsynchronisminordertoallowproperassessmentbytherelayswithinthedesiredtolerances.
The test devices are synchronized to a master clockrepresented by the time stamps transmitted by theGlobalPositioningSystem(GPS)satellites.EachtestunitiscontrolledbyadedicatedGPSreceiver.
Foreachtestshotalltestdeviceswaitforatimepulsefrom the GPS receiver. This ensures highly accuratesignal synchronism of all generated currents in the
rangeofmicroseconds.
Fig. 1: End-to-end test injection
For the benefit of a dedicated user interface andreportingforline-differentialtestsOMICRONhasnowintroduced GPS synchronization into its AdvancedDifferential test modules. This allows direct diff/biasplaneoperationjustlikethatfortransformerdifferential
relay testing, thus also supporting line differentialrelayswithatransformer intheprotectedzone.NewcheckboxesactivatetheGPSmodeandselectthepropercurrent triple for each end. The "GPS Configuration"buttonofthetestmoduleallowsforthesettingofthestarttimeandtheshotrate.
SampleTestResultFig.2showsasampletestresultwithSiemens7SD610linedifferentialrelay.ThechosencharacteristicfortheDifferential Operating Characteristic diagram is theclassic current difference versus the sum of currentamplitudesrepresentation.
Fig. 2: Sample Idiff/Ibias result with 7SD610
-
7/27/2019 TSNVolume11_3.pdf
2/4
Everydayprotectionengineersareconfrontedwiththechallengesofshorterandshorterinnovationcycles.Protectiverelaysbecomemorepowerfulandmorecomplex;relaysofdifferentgenerationsandfromdifferentsuppliers,areusedsidebysideandtheseareonlysomeofthereasonswhythetestandmaintenanceofprotectionrelaysremainachallengingtaskforengineersandtechnicians.
TestBase isapowerfuldatabaseformaintenancemanagement andtestautomation.Itsusereleasesstafffrommanyoftheadministrativetasks and paperwork associatedwith this work. It is designed forprotectiontestingwiththeTUsoftwareandCMCtestequipment,butcanbeusedformanyotherapplicationsandwithtestequipmentfrom
manymajormanufacturers.
UsefulApplications
1) Management of Protection Relay Settings The user caneasily compare nominal and actual settings and directly importsettings from the relay operating software. These settings can beautomaticallytransferredintotheTUtesttemplatefortestingwiththeCMCtestequipment.
2) AdministrationofTestTemplatesandTestResultsTestBaseensurestheselectionoftherighttesttemplatesforaspecifiedrelay.ExcelchecklistscanbefilledautomaticallywithindividualrelaymasterdatawhentheyarelaunchedfromTestBaseandalltestresultsareautomaticallystoredinthedatabase.
3) TestAutomationForanumberoftestapplications(e.g.routinetestingofdistancerelays)andrelaytypes,fullyautomatedtesttemplatesareavailable.
4) MaintenancePlanningSupportAlarmsignalsinthesoftwareshowobjectsdueoroverdueformaintenance.
5) Document management With the integrated documentmanagement facility the user gets easy access to the informationrequiredduringtesting(e.g.relaymanuals,testspecifications,safetyinstructions,certificates,individualnotes,etc.).
6) Management of other assets within power utilities Inadditiontoprotectiverelays,TestBasesupportsinstrumenttransformersandbatteries.Furtherequipmentcanbemodeledintothesystembytheuser.
7) Offline mode with data replications TestBase allowsautomatedsynchronizationwhenconnected tothe server. Theuserhasaccesstoallfeatureswhenworkingonsiteevenwithoutserverconnection.
TestBaseisavailableinawiderangeofformats;forsingleormulti-user;asastandardadd-onproducttotheOMICRONTestUniverse;orasanindividuallytailoredsolutionformaintenacemanagement.
FormoreinformationaboutTestBasepleasegetintouchwithyourlocaldistributorortheOMICRONofficenearestyou.
(Continuedfrompage1)
SomeHints:
Insearchmode thetestmoduleneeds consistentbehavior ofthetripsignal.Allendsmusttripatthesametimetoavoiddivergingiterations. So all relays must use the transfer trip function ifsynchronoustrippingisnotinherenttotherelayfunction.
Relays that allow different characteristics per end can be testedsequentiallybyenablingoneendtripatatimetogetherwithtransfertripping,thustestingeachcharacteristicaccordingtoitssettings.
ForanextendedversionofthisarticlepleasevisittheSupportsectionofwww.omicron.at.
TestBaseThe Administration Tool for ProtectionTesting with Test Universe
New features of TestUniverse 2.11Wearepleasedtoannouncetheavailabilityofthe2.11releaseofTestUniverseSoftwarewhichoffersmanyusefulenhancements:
GPS-synchronizedLine-Differentialtesting:Seealsothetitlestoryfortheapplicationofthispowerfulfeature.
XMLdataexport:ThismoderndataformatisaddedasanalternativetotheexistingCSVexportallowingeasyintegrationofexternalapplicationsand databases. XML can beexported fromOCC filesaswellas from
individualtestmodules.ApplicationexamplenotesareincludedtoshowhowtomakeuseofXMLdatatransferandtestresultanalysisinMicrosoftOfficeapplicationsand.NETprogramming.
The new software also provides changes and enhancements in thefollowingmodules:
GOOSEConfiguration:SupportofthefrequentlyusedEnumerationtypeandotherenhancementsincludingimprovedSCLimport.
AdvancedTransPlay:AsinesimulationwithdefinablelengthcannowbeinsertedbeforetheactualCOMTRADEplaybacktoallowextendedpre-faultdurationinadditiontotheloopingcapabilityofthetool.
CMGPS:Enhanced status information (e.g.AlmanacandUTCupdateprogress)andRestoreDefaults toquickly equalize thesettings onall
ends.
Ramping: Added(X+Y)/2function,e.g.forMTAassessment.
NetSim:Twonewtestcasesfordoubleearthfaultsimulation(single-anddual-segmentlinewithfreelyassignablefaultlocations).
ThisreleaseisavailablenowonCDandonourwebsitefordownloadfrom the Customer Area.Thedownload isanUpdate version, i.e. itcomeswithoutalicensefileandcanbeinstalledontopofanexistingTU2.x installation.Users are invited tocontact theirOMICRON salespartner for a free update from TU2.x licensed components, orusetheonlineorderformprovidedintheCustomerAreaoftheOMICRONwebsite.Thelicensekeysstaythesamefortheseversions.
Formoreinformationincludingthedetailed"WhatsNew"documentforthis releaseuserscan getmore information fromthe CustomerAreaatwww.omicron.at.
-
7/27/2019 TSNVolume11_3.pdf
3/4
Transformers have to withstand a high level of mechanical stressduring through-faults with high currents. Themagnetic flux in the
straychannelcauseshighforcesbetweentheturnsofthewindings.Inparticular,whentheclampingpressureisnotcapableofrestrainingtheforces involved, substantialpermanentwinding deformationor evencollapsecanoccur.Oftenthedeformationoftransformerwindingsisnotrecognizedandthetransformersremaininservice.Inmanycasesdeformedwindings have a reduced ability towithstandhigh forcessubsequentlyandsohighthrough-faultscanleadtoanunpredictablebreakdownofthewholetransformer.
Frequencyresponseanalysis (FRA)providesapowerful toolto detectdeformationanddisplacementofwindingsbymeasuringthetransferfunctionofwindings over a wide frequency range. Changes in themeasured transfer function can be very small. Comparisons to theothertwophasesortosisterunitsareoftennothelpfulduetophysicaldifferences. Therefore a reference (fingerprint) measurement of thewindingsinagoodconditionisveryimportant.Toguaranteethatthemeasurements have good reproducibility, it is necessary to followsomeimportantguidelinesformaking thereferenceandsubsequentmeasurements.Thetestcircuitshouldbemadeexactlyinthesamewayforbothmeasurements,usingthesameequipmentoratleastequipmentwith the same measuring behavior. Important parameters are themeasuringprinciple,theinputimpedance,thecablesandparticularlythegroundingconcept.The groundingof themeasuringsystemandthecoaxialmeasuringcablescan greatlyaffectthemeasurement.Tominimizetheinfluenceoftheconnectionleadsitisveryimportanttoconnectthescreensofthe coaxial cableswith theminimumlevelofinductanceaspossibleandalwaysinthesamemanner.
Thefigureontherightsidepresentsacomparativetesttoinvestigatethe influence of different grounding concepts on the repeatabilityof the measurement. The first example used old-style connectiontechniques.Thepositionoftheinstrumentwaschangedwhich,inturn,changedthepositionofthemeasuringleadsrelativetothetransformerterminals.Changesinthesignaldampingwereobservedforfrequenciesof700kHzandaboveshowinglargechangesinthesignaltracesforhigherfrequencies.Usingtheadvancedbraidconnectionsinplaceofwiresthemeasurementsarestableoverthecompletefrequencyrange.Itcanbeseenintheexamplethatwherethenewbraidisusedfortheconnection,theredandbluetracesarenearlycoincident. Thiseffectis of importance for the practical use of FRA,because it is unlikelythat exactly the same arrangement ofmeasurement leads and FRAinstrumentwillbeachievedforsubsequentmeasurementsonthesametransformerorforsimilartransformersinothersubstations.
Theexample shows the importanceof the connection technique forreproducible FRA measurements. With the innovative connectiontechnique, OMICRON offers an important tool for professionalmeasurements.
FRA curves with wire and braid grounding. The results showing clearadvantage of grounding braids regarding wires.
Innovative OMICRON lead and grounding connection concept
Reproducibility of FRA Measurements
-
7/27/2019 TSNVolume11_3.pdf
4/4
PCOMING EVENTSQ: Weneedtodosometests,forexamplethetapchangertest,onourtransformersona
commonbasis.PreparingtheCPCtestcardsrequiredforthesetestsdoestakesometime.Furthermoreyouneedtohavecertainknowledgeaboutthewholetechnique.Isthereasolutiontosimplifythepreparationofthetests?
A: Especiallyfortestsusedregularly,wehavegeneratedstandard"templates"tosimplifytheprocess.
Insteadofgeneratingalltherequiredtestcardsmanuallytheuserjustneedstoinputsomesettingsinthetemplates.Thisimprovesefficiencyoverallbyreducingtheamountofworkandtime.
Templatescompriseofoneormoretestcardsandaresuitableforthemostcommonrequirements.CPCExplorerallowsforthetestmeasurementstobeeasilydownloadedtoaPC.Also,sinceeachtemplateisactuallyatemplatepair,whichconsistsofanExceltemplateandaCPCtemplate,thetestreportwillbegeneratedautomaticallybyloadingthecorrespondingExceltemplate.Thistestreportiscompletelyadaptabletoyourneeds.Thenexttimeyouneedyour,moredetailedreportagain,youonlyhavetoloadthemeasurementdataintoyourpersonallyadaptedtemplate.Thereforeyouhave
tocreateyour"reporttemplate"onlyoncebutareabletouseitfrequently.
OMICRONprovidestemplatesforthemostcommonapplications.ThesetemplatesareautomaticallyinstalledwiththeCPCExplorer.YoucanfindtheminStart\Programms\CPCExplorer\Templates.TotakeadvantageoftheCPCtemplatesconcept,they(*.xmt)mustbeuploadedtotheCPC100priortothetest.TheyarealsoavailableintheCustomerAreaontheOMICRONhomepageandcanbedownloadedfromthesection"PrimaryTestingCPLine/CPC100andAccessories"forfree.
Q: Mynotebookisfairlynewanditdoesn'thaveaparallelport(DB25connector).WhatcanIdotostillusetheCMCwithaparallelportconnection?
A: ToaddaparallelporttoanycomputerwithaPCMCIAinterface,anextensioncardcanbeused.
ThereisabigrangeonthemarketofparallelportPCMCIACards.Mostoftheseextensioncardscanbeeasilyinstalledontothenotebook.Someofthemdonotevenneeddriversbutthecompatibility
mostlydependsontheoperatingsystemanditsversion.
WehavetestedanumberofcardsfortheparallelportconnectiontotheCMCusingPCMCIA.WefoundavarietyofusablecardsbutourspecificrecommendationisthetypeSPP-100fromQuatech.Thiscard canbeorderedatOMICRON.Further informationabout thisParallel PortPCMCIA cardisavailable in the "OMICRONCMLine catalogue" and aswell on our homepage, in the section"SecondaryTestingCMLine/Hardware/Accessories
FORTHERECORDWITHAseriesofquestionsmostcommonlyasked,andresponsesfromOMICRONsrenownedtestGuru...
COMICRON
CCigreExhibitionforelectricalipementchRotanaHotel&Toweroth#A8uDhabi,UnitedArabEmiratesvember29-30,2006w.ifpqatar.com
oTechConwnePlazaHotelester,UnitedKingdomvember28-30,2006
hcon.tjh2b.com/EuroTechCon06/index.htm
Automation&Control(ELEC)cdesExpositionsl6/5aL148sNordVillepinte,Francecember5-8,2006ww.scs-automation.com
rgyGenerationConferencemarck,ND,USAuary30-February1,2007
tribuTechDiegoConventionCenteroth#1625Diego,CA,USAruary4-6,2007
ddleEastElectricitybaiInternationalExhibitionntrebai,UnitedArabEmiratesruary11-14,2007
ww.middleeastelectricity.com
hConneysCoronadoSpringsResorteBuenaVista,FL,USAruary28-March2,2007
noverFairnover,Germanyril16-20,2007ww.hannovermesse.de
Majority Takeover of Berlin-based HighTech Company mtronix
Thechemistryisperfect!,saysMartinPfanner,ManagingDirectorofOMICRONelectronicsGmbH,andcontinues:BytakingoverthemajorityoftheGermanbusinessmtronix,wenotonlyextendourrangeofservicesinthefieldoftestandmeasurementengineeringforelectricalpowersystems,butwealsogainaccesstonewmarketsegments.mtronix,foundedin1997byateamofhighlymotivatedexperts,specializesinthefieldofpartialdischargemeasurementwhereitquicklybecameinternationaltechnologicalleaderwithinafewyears.Thisremindsusstronglyofourownbusinessdevelopment,inwhichOMICRONmanagedto takea leaptobecome theworldsmarket leader throughhighlyinnovativesolutions.
Thispartnershipwillallowusto:
Expandtechnologicallyinthedirectionofpartialdischargeanalysis
Deliverbetterandmorecomprehensivesolutionstoour
customers
Findoutmoredetailsonwww.omicron.at.