Troubleshooting Training Course. Visual and General Test Perform System Test (Mode Perform System...

25
Equalizer & Activar Troubleshooting Training Course

Transcript of Troubleshooting Training Course. Visual and General Test Perform System Test (Mode Perform System...

Page 1: Troubleshooting Training Course.  Visual and General Test  Perform System Test (Mode  Perform System Test)  Identify The Error  If you need Technical.

Equalizer & Activar

Troubleshooting

Training Course

Page 2: Troubleshooting Training Course.  Visual and General Test  Perform System Test (Mode  Perform System Test)  Identify The Error  If you need Technical.

Visual and General Test

Perform System Test (Mode Perform System Test)

Identify The Error

If you need Technical support write down the results of this test before you contact technical support

Trouble ShootingPrimary Actions

Page 3: Troubleshooting Training Course.  Visual and General Test  Perform System Test (Mode  Perform System Test)  Identify The Error  If you need Technical.

Automatic Error Detection

Automatic and manual self test that test all errors and can locate the exact phase and group of the fault.

Self Diagnostic System

Page 4: Troubleshooting Training Course.  Visual and General Test  Perform System Test (Mode  Perform System Test)  Identify The Error  If you need Technical.

E3– Unable to Connect Capacitor Group

E5- Misfiring

E6- Network Synchronization

E7- Over Temperature

E10-Resonance

The Errors

Page 5: Troubleshooting Training Course.  Visual and General Test  Perform System Test (Mode  Perform System Test)  Identify The Error  If you need Technical.

Errors that do not disable the system completely will be indicated in the upper section of the controller screen and will indicate to which group the error is associated.

Error Identification

Page 6: Troubleshooting Training Course.  Visual and General Test  Perform System Test (Mode  Perform System Test)  Identify The Error  If you need Technical.

Errors that disable all of the system operation will be displayed on the main section of the controller screen.

Error Identification

Page 7: Troubleshooting Training Course.  Visual and General Test  Perform System Test (Mode  Perform System Test)  Identify The Error  If you need Technical.

Unable to connect Error Monitored Signals: X (reactance) of the connected capacitor(s), on all three

phases.

Averaging/Delay: 8 consecutive network cycles of exceeding the limit.

Limits: 10% from nominal value.

What action is taken: The particular group is disconnected and disabled.

Error Reset: Automatically (see below) or manually by activating self test.

Automatic Reset Delay: The system repeats the self test on defective groups only, after 1 minute. If the same groups are detected faulty again, the test repeats after 2 minutes and the interval is doubled each test until maximum 10 repeats (with delay of 512 minutes = 8.5 hours). If the result of each test is not identical to the previous one – the repeat interval is set back to 1 minute.

Error 3

Page 8: Troubleshooting Training Course.  Visual and General Test  Perform System Test (Mode  Perform System Test)  Identify The Error  If you need Technical.

Find Errors and Locate the source of the fault (group and phase )

Mode Perform System Test

System Test

Mode of Operation Menu

Measuring Screen

Page 9: Troubleshooting Training Course.  Visual and General Test  Perform System Test (Mode  Perform System Test)  Identify The Error  If you need Technical.

System Test

Group Test Report Screen Group Details Screen - Group OK

Group Details Screen - Group with Error 3 Background Readings

Page 10: Troubleshooting Training Course.  Visual and General Test  Perform System Test (Mode  Perform System Test)  Identify The Error  If you need Technical.

Block Diagram

controller

Switching Module

Firing

Fuse

Bus bars

Fuse

Power Supply

Page 11: Troubleshooting Training Course.  Visual and General Test  Perform System Test (Mode  Perform System Test)  Identify The Error  If you need Technical.

Led Tester Firing signals are the signals that the controller sends to the

Switching modules in order to open the Thyristors

How to test the firing ?

Page 12: Troubleshooting Training Course.  Visual and General Test  Perform System Test (Mode  Perform System Test)  Identify The Error  If you need Technical.

Misfiring Monitored Signals: THD of capacitor current in the first two phases.

Averaging/Delay: 2 consecutive network cycles of exceeding the limit.

Limits: 300%.

What action is taken: The particular group is disconnected and disabled. If detected during normal operation – self test is activated.

Error Reset: Automatically (see below) or manually by activating self test.

Automatic Reset Delay: The system repeats the self test on defective groups only after 1 minute. If the same groups are detected faulty again, the test repeats after 2 minutes and the interval is doubled each test until maximum 10 repeats (with delay of 512 minutes = 8.5 hours). If the result of each test is not identical to the previous one – the repeat interval is set to 1 minute.

Error 5

Page 13: Troubleshooting Training Course.  Visual and General Test  Perform System Test (Mode  Perform System Test)  Identify The Error  If you need Technical.

Test all the relevant firing cables and connectors disconnect and reconnect the connectors and test the system again.

Disable E5 and test if the system works properly now, test the Thd of the network if it is very high maybe the E5 should be disabled .

If this is not the case the controller firing card or the SWM firing card are the next suspects.

Sometimes because of E3 in one phase E5 can be detected but the cause is E3, reactors shortcut can also cause E5.

Error 5 handling

Page 14: Troubleshooting Training Course.  Visual and General Test  Perform System Test (Mode  Perform System Test)  Identify The Error  If you need Technical.

Network synchronization

Monitored Signals: L1-L2 Voltage (in three phase system).

Averaging/Delay: 500 consecutive network cycles of internal PLL synchronization error.

Limits: Internal PLL failed to synchronize to signal.

What action is taken: System disconnects.

Error Reset: Automatically.

Automatic Reset Delay: 250 consecutive network cycles of error-free PLL operation.

Error 6

Page 15: Troubleshooting Training Course.  Visual and General Test  Perform System Test (Mode  Perform System Test)  Identify The Error  If you need Technical.

Test the voltage in L1- L2 terminals of the controller (with a multimeter) a valid voltage signal Should be detected.

If a valid voltage is not detected make sure that the controller will receive the signal.

If there is a valid voltage in the terminals the controller should be checked.

Error 6 Handling

Page 16: Troubleshooting Training Course.  Visual and General Test  Perform System Test (Mode  Perform System Test)  Identify The Error  If you need Technical.

Over Temperature

Monitored Signals: External Thermostats.

Averaging/Delay: Immediate.

Limits: Depends on external thermostats.

What action is taken: System disconnects.

Error Reset: Automatically.

Automatic Reset Delay: Immediate.

Error 7

Page 17: Troubleshooting Training Course.  Visual and General Test  Perform System Test (Mode  Perform System Test)  Identify The Error  If you need Technical.

55° Thermostat Activates an Deactivate the SWM Fan

85°C and 120°C Thermostats Deactivate the whole System

Error 7 wiring

controller

Switching Module

55°C Thermostat

85°C N.O Thermostat

120°C N.C ThermostatsReactors

Page 18: Troubleshooting Training Course.  Visual and General Test  Perform System Test (Mode  Perform System Test)  Identify The Error  If you need Technical.

Resonance Monitored Signals: Mains and Load current, on all three phases and 63 harmonics.

Averaging/Delay: 10 consecutive network cycles of exceeding the limit, counted for each phase and harmony separately.

Limits: IMAIN-ILOAD>X%*ICAP(NOMINAL). X% is 50% for normal limit and 30% for sensitive limit.

What action is taken: System disconnects.

Error Reset: Automatically.

Automatic Reset Delay: The system disconnects for 10 seconds for first occurrence and doubles the time for each occurrence happened within 20 seconds from the end of previous disconnection, until a maximum of 3000 seconds.

Error 10

Page 19: Troubleshooting Training Course.  Visual and General Test  Perform System Test (Mode  Perform System Test)  Identify The Error  If you need Technical.

Measurements must be performed and analyzed to understand the source of resonance.

Error 10 Handling

Page 20: Troubleshooting Training Course.  Visual and General Test  Perform System Test (Mode  Perform System Test)  Identify The Error  If you need Technical.

Menu System Setup Site Installation Modify The Above Next few times in Error Detection screen chose Customize disable the needed Errors

Disabling The Error’s

Page 21: Troubleshooting Training Course.  Visual and General Test  Perform System Test (Mode  Perform System Test)  Identify The Error  If you need Technical.

L C M – Load Caps Mains What is it used for? To see if the system is connected and

measuring correctly. Menu L C M Combined Total KVAr Meters Mode Manual insert one group manually Expected results after inserting the group: Load should not change Caps should show the expected KVAr from this group Mains should show the former value minus the Caps Value

L C M KVAr Test

Page 22: Troubleshooting Training Course.  Visual and General Test  Perform System Test (Mode  Perform System Test)  Identify The Error  If you need Technical.

Test that the measured currents match the expected currents

L C M Current Test

Page 23: Troubleshooting Training Course.  Visual and General Test  Perform System Test (Mode  Perform System Test)  Identify The Error  If you need Technical.

Menu System Information Events The Events log, saves all system events,

Errors, changes in status changes in setup, power losses, etc… And the time and date of these events.

The Events log can help us understand the source of a problem

The Events log can be downloaded into a computer

System Events Log

Page 24: Troubleshooting Training Course.  Visual and General Test  Perform System Test (Mode  Perform System Test)  Identify The Error  If you need Technical.

The controller needs to have a communication Card, if there is no communication card use the Service Card

The communication protocol is RS-485

Connecting A PC to the Controller

Com to RS485 Adapter PCMCI to RS485 Adapter

Service Card

Page 25: Troubleshooting Training Course.  Visual and General Test  Perform System Test (Mode  Perform System Test)  Identify The Error  If you need Technical.

Tools Led tester Service card Laptop Computer Communication Adapter for the Laptop Multimeter Current clamp Fuse for the Switching module Fuse for control module Power Fuse Optional: firing cards, switching module, Capacitors

Trouble Shooting Kit