    Trouble Shooting

    Protective

    and

    supervisory

    instruments

    various

    components

    fault Possible cause Remedial measure

    Buchhoz

    relay

    Alarm at buchholz

    relay

    1. Oil loss2. Gas generation due to

    inside failure

    3. Accumulation of air4. Violent vibration5. Fault tripping

    Transformer operation must only be continued

    when a check shows that there is no internal

    fault.

    The following tests and examinations for

    analysis of the warning should be made

    1. Check oil level, pipes, position of valves2. Check tripping mechanism of the buchholz

    relay

    3. Check if gas in buchhoz relay isinflammable. Inflammability indicates an

    internal transformer fault.

    4. Analyze and evaluate buchholz relay gas5. Analyze and evaluate the oil taken from top

    oil sampling valve

    6. Undo all bushing connections and make thefollowing measurements.

    6.1 measure the insulation resistance betweenthe systems and against earth

    6.2 measure ratio between the systems in allpositions of the OLTC

    6.3 Measure the winding resistance in allpositions of the OLTC

    6.4 Measure the no-load current by applyinglow voltage and compare the results with

    data given in the transformer test

    certificate or in the O&M manual

    7. Check all electrical connections8. Vent transformer tank and piping and put it

    back into operation.

    9. if faults cannot be found or faults havebeen eliminated. If one fault occurs

    frequently, contact CTSS.

    Buchholz relay

    tripping

    1. Oil loss2. Violent oil surge due to

    inside flashover

    3. Violent gas generation dueto inside failure

    4. Violent vibration5. Fault tripping

    1. Maintain the shutdown status!2. Carry out tests and measurements as

    described under point 1 to 7

    3. Vent transformer tank and piping and put itback into operation if faults cannot be

    found or faults have been eliminated.

    4. If one fault occurs frequently, contact CTSS.Pressure

    relay/

    Tripping due to strong

    oil surge

    Surge produced through a fault

    in the diverter switch

    1. Maintain the shutdown status.2. Check the tripping mechanism.

  • 7/29/2019 transformer trouble shooting

    2/4

    protective

    relay for

    OLTC

    3. Remove and check the diverter switch.4. Reset the tripping mechanism and put the

    transformer into operation.

    Resistance

    thermometer

    Thermostat

    Dial-type

    thermometer

    for oil or

    winding

    Oil temperature too

    high

    Winding or oil temp.

    too high

    1. Transformer overloaded orinadequate cooling

    2. Incorrect temperatureadjustment

    1. Reduce load of the transformer2. Put fans or cooling equipment in service3. Clean the cooling equipment4. Check the position of butterfly valves5. Adjust incorrect temperature setting.6. Check the thermometer by comparative

    measurements.

    7. Check the electrical connections and thetripping mechanism

    8. Check control devices for coolingequipment

    9. Check current transformers andthermometers

    Oil levelindicator

    Oil level too low Not enough oil (low temp. oroil loss)

    Check for tightnessTop-up oil

    Oil flow

    monitor

    No oil flow 1. Gate valve closed2. Pipe clogged3. Pipe leaky4. Oil circulation pump

    faulted(no voltage or

    voltage too low defective

    winding incorrect direction

    of rotation, bearing

    damage)

    1. Open gate valve2. Clean pipe3. Seal pipe leaks4. Repair oil circulating pump(check fuses,

    and direction of rotation)

    5. Check the over current tripping feature6. Check the electrical connections and the

    tripping mechanism.

    Water flow

    monitor

    No water-flow or

    reduced water flow

    1. Leaks in the water coolingsystem

    2. Reduction of cooling waterquantity

    1. Top-up cooling water to the required level2. Check the electrical connections

    Pressure

    relief device

    Internal tank pressure

    too high

    1. Conservator pipe shut-offor clogged

    2. Electric flashover insidethe tank

    1. Check the pipes and shut-off devices2. Check the transformer as described in

    buchholz relay(1-7)

    Motor drivefor OLTC

    Drive cannot beoperated electrically

    1. No voltage supply atmotor protective switch

    2. Motor protective switchnot in operating position

    3. Motor contactor does notpick up

    4. Motor contactor stuck5. Brake contactor does not

    pick up

    6. Open circuit an one ormore motor phases

    1. Check supply feeders2. Close motor protective switch3. Check supply feeders and contactors, and

    replace if necessary

    4. Clean or replace5. Check contactor, clean or replace if

    necessary

    Drive keeps on

    running

    Brake contactor stuck Clean or replace

    Motor protective 1. Emergency stop button is 1. Repair or replace emergency stop button

  • 7/29/2019 transformer trouble shooting

    3/4

    switch trips during

    operation of motor

    drive

    on or stuck

    2. Motor current excessivedue to overload or phase

    failure

    2. Check drive for stillness with crack handle3. Request a factory engineer. If a mechanical

    fault in the tap-changer is suspected.

    Off-circuit

    tap changer

    1. Operation notpossible

    2. Gas in buchholzrelay

    1. Adjusting device detective2. Carbon formation on

    contacts

    1. Repair adjusting device, operate multiplethe tap changer once a year over all

    positions (extraction points)

    2. Check the transformer as described for thebuchholz relay(1-7)

    Dehydrating

    breather

    1. The colour of thedrying crystals

    changes from

    below

    2. Changes from top3. In general

    1. High atmospherichumidity.

    Glass cylinder leaky

    2. Moisture in conservatorPipe leaky

    Glass cylinder leaky

    3. Glass cylinder burst,maintenance intervals toolong

    1. Replace dehydrating agentReplacing glass cylinder or seal properly

    2. Seal pipe leaks, check the oil for moisturecontent

    3. Flush the conservator with dry air

    Electrical

    breakdown

    voltage of

    the oil

    1. Breakdownvoltage too low

    2. Water content toohigh

    1. Breather inoperable oftransformer in service very

    long time

    2. Leaks in water coolingsystem

    3. Water pressure reducerinoperable

    1. Put breather into operation2. Seal or repair coolers3. Contact manufacturer4. Dry the oil if necessary

    Terminal lugs

    on bushing

    control

    Discoloration of

    connecting parts

    Poor contact making Clear the contact faces

    Tighten the screws

    Control

    cabinet

    1. Electricalapparatus does

    not operate

    properly

    2. Contactscommanded or

    contaminated

    3. Apparatushousing bend

    1. Excision humidity incontrol cabinet

    2. Water or dust inside thecabinet

    3. Excessive hightemperature in the cabinet

    1. Set the cabinet heater to a highertemperature

    2. Seal the cabinet door. Fit a dust cleaner ifnecessary

    3. Protect the cabinet against solar irradiation,provide for better ventilation

    Earthing

    connection

    Earthing line

    interrupted

    1. Excessive current due toexternal flash overs

    2. Impermissible currentloops through multiple

    earthing

    1. Clean the contacts tighten the screws andcheck the electrical distances.

    2. Open up current loops3. Only one earthing with a sufficient cross

    section.

    Pressure

    gauge for

    HV-bushing

    Oil pressure in

    HV-bushing too high

    1. Incorrect contactadjustment

    2. Bushing over-loaded, oiltemperature too high due

    to solar irradiation

    1. Correct the contact adjustment2. Check the reading3. Check the bushing, reduce the transformer

    load, increase the cooling effect

    Pressure

    monitor for

    Oil pressure in

    HV-bushing too high

    1. Incorrect contactadjustment

    4. Correct the contact adjustment5. Check the pressure monitor and reset the

  • 7/29/2019 transformer trouble shooting

    4/4

    HV-bushing 2. Bushing over-loaded, oiltemperature too high due

    to solar irradiation

    3. Violent vibration ontransformer

    auxiliary switch

    6. Check the bushings, reduce the transformerload, increase the cooling

    Air flow

    monitor

    No air flow or reduced

    air flow

    1. Protective screen iced upor clogged.

    2. Cooler clogged or verydirty

    3. Fan motor faulty (windingdefective or over-heated.

    Bearing damage)

    4. Incorrect direction ofrotation

    1. Clean the screen, open the front flaps2. Clean coolers3. Check the supply leads4. Repair fans5. Correct direction of rotation6. Check over-current tripping features7. Check electrical connection, signaling and

    tripping

    Oil sight roof Traces of oil on the

    water surface

    Leakages in the oil circuit or

    the water cooling system

    Seal and repair coolers