TRANSFORMER PROTECTION - aht.com.pkaht.com.pk/downloads/tp.pdf · Transformer faults Winding...
-
Upload
truongxuyen -
Category
Documents
-
view
303 -
download
22
Transcript of TRANSFORMER PROTECTION - aht.com.pkaht.com.pk/downloads/tp.pdf · Transformer faults Winding...
TRANSFORMER PROTECTION
Extent of damage
Fault level
Duration of fault
Transformer faults
Winding failures
Voltage regulating load
changers
Transformer bushing failure
Transformer core problem
Miscellaneous failures
Condition leading to faults
Insulation breakdown
Ageing of insulation
Time
Temperature
Improve cooling system of possible
Reduced load Over heating
due to excitation
Oil contamination%
& oil leakage
Reduced cooling
FAULT OF TRANSFORMER
Earth fault on H.V external connection Phases to phase fault on H.V external connection Internal earth fault on H.V windings Internal phase to phase fault on H.V windings. Short circuit between turns L.V windings. Earth fault on L.V external winding Phase to phase fault on L.V external connection. Internal earth fault on L.V windings Internal phase to phase fault on L.V winding Short circuit b/w turn L.V windings Earth fault on tertiary windings Short circuit b/W turns tertiary windings Sustained system phase to phase fault Sustained system earth fault
132KV/11KV POWER TRANSFORMER
Differential relay
L.V side three phase over current and earth fault relay
H.V side three phases over current and earth fault relay
D.C trip circuit supervision relay
Trip and lock out relay
220/132/11KV AUTO TRANSFORMER
Percentage biased Transformer
differential relay
High REF impedance Circulating current
differential protection
HV side over current and earth fault relay
LV side over current and earth fault relay
Over excitation relay
Thermal over load relay
Overall percentage biased differential
relay
L.H&H.V Connection circulating protection
Tertiary over current protection
D.C trip circuit supervision relay
500/220KV AUTO TRANSFORMER
Percentage biased Transformer
differential relay
High REF impedance Circulating current
differential protection
HV side over current and earth fault
relay
LV side over current and earth fault
relay
Over excitation relay
Thermal over load relay
Overall percentage biased differential
relay
L.H&H.V Connection circulating protection
Tertiary over current protection
D.C trip circuit supervision relay
Over voltage relay
MECHANICAL PROTECTION:
Transformer buchhloz relay
Tap changer buchhloz relay
Winding Temperature
0IL temperature
Pressure relieve valve
• Factors:
• The shape, magnitude and duration of the inrush current depend on the factors:
• Size of power transformer
• Source Impendence
• The magnetic properties of the core i.e. saturation density
• The remanence of core
• Resistance in power system from source to transformer.
• The moment when transformer is switch on.
Effect of magnetising current
Appears on one side of transformer only
Seen as fault by differential relay
Normal steady state magnetising current is less than relay setting
Transient magnetising inrush could cause relay to operate
• The vector group shows the connection of windings of transformer and numerical index (hour numbers) for displacement of vector of two star voltages.
• Capital Letter DY11 Small letter ( clock dial reference)
• The first capital letter donates the connection of high voltage winding of transformer
• The small letter represent the connection of low voltage secondary winding of transformer
• Yy0d5
•
• The first capital letter Y is referred to H.V or primary winding, the second letter y is referred as secondary winding and third letter is referred as tertiary winding.
• Primary winding is taken as phase referred ‘O’ means that phase angle b/W H.V and M.V winding is zero. Whereas ‘5’ denotes that phase angle b/W H.V and tertiary winding is 150 (5x30)
OVER CURRENT PROTECTION
As it names implies, relay will pick up when it exceeds its present value
TYPES:
The types of over current relay are based on the relay characteristics over can be classified into three groups.
• Definite current or instantaneous
• Definite time
• Inverse time
Vécurent Relay Applied to a Transformer
HV2
51 51 51
LV HV1
Time LV
HV1 HV2
Current IF(LV)
1.2IF(LV) IF(HV)
Use of Instantaneous Overcurrent Protection
Source LV
50
51
Differential Protection
• Overall differential protection may be justified for larger transformers (generally > 5MVA).
• Provides fast operation on any winding
• Measuring principle :
• Based on the same circulating current principle as the restricted earth fault protection
• However, it employs the biasing technique, to maintain stability for heavy thro’ fault current
• Biasing allows mismatch between CT outputs.
• It is essential for transformers with tap changing facility.
• Another important requirement of transformer differential protection is immunity to magnetising inrush current.
LV
R
HV
PROTECTED ZONE
• Correct application of differential protection requires CT ratio and winding connections to match those of transformer.
• CT secondary circuit should be a “replica” of primary system.
• Consider :
• (1) Difference in current magnitude
• (2) Phase shift
• (3) Zero sequence currents
Biased Differential Scheme
Bias = Differential (or Spill)
Current Mean Through Current
BIAS BIAS I2 I1
OPERATE I1 - I2
Differential
Current
OPERATE
RESTRAIN
Mean Thro Current
I1 + I2
2
I1 - I2
Restricted E/F Protection Low Voltage Windings (1)
A B C N
LV restricted E/F
protection trips both HV and LV breaker
Recommended setting : 10% rated
Restricted E/F Protection Low Voltage Windings (2)
A B C N
LV restricted E/F protection trips both HV and LV breaker Recommended setting : 10% rated
Delta Winding Restricted Earth Fault
Protected zone REF
Source
Delta winding cannot supply zero
sequence current to system
Stability : Consider max LV fault level
Recommended setting : less than 30% minimum
earth fault level
Protection of Auto-Transformer
by High Impedance Differential
Relays (2)
(b) Phase and Earth Fault Scheme
A
B
C
a b c
87 87 87
n
`
Combined Differential and Restricted Earthfault Protection
To differential relay S2
S1
P1
P2 REF
S2
S1 P1
P2
S2 S1 P1 P2 a2 a1 A1 A2
Integral Vectorial and Ratio Compensation
Power transformer
Differential element Virtual interposing CT
Vectorial correction
Ratio correction
Virtual interposing CT
In Zone Earthing Transformer P2 P1
a2 a1
A2 A1 P1 P2
S1 S2
P2 P1 S1 S2 T1 T2
Three Winding Transformer 25MVA 11KV
63MVA 132KV
1600/5 300/5
50MVA 33KV
1000/5
4.59
2.88
10.33
2.88
5.51
5
5
All interposing C.T. ratio’s refer to common MVA base (63MVA
Transformer Magnetising Characteristic
Twice
Normal
Flux
Normal
Flux
Normal No
Load Current
No Load Current at
Twice Normal Flux
Parallel Transformers A N T1
T2
C B
Inter-Turn Fault
Nominal turns ratio
Fault turns ratio
Current ratio
- 11,000 / 240
- 11,000 / 1
- 1 / 11,000
Requires Buchholz relay
CT E
Shorted turn
Load
Buchholz Relay Installation
5 x internal pipe
diameter (minimum)
3 x internal pipe
diameter (minimum)
Transformer
3 minimum
Oil conservator
Conservator
Buchholz Relay
Petcock
Counter balance weight
Oil level
From transformer
Aperture adjuster
Deflector plate Drain plug
Trip bucket
To oil conservator
Mercury switch
Alarm bucket
Low frequency
High voltage
Geomagnetic disturbances
m
Tripping of differential element (Transient overfluxing)
Damage to transformers (Prolonged overfluxing)
2
I e
m Causes
Effects
V = kf
Overfluxing Basic Theory
EFFECTS OF OVER FLUXING:
• Increase in magnetizing current
• Increase in winding temperature
• Increase in noise and vibration
• Overheating of laminations and metal parts (cause by stray flux)
V f K
Trip and alarm outputs for clearing prolonged overfluxing
Alarm : Definite time characteristic to initiate corrective action
Trip : IDMT or DT characteristic to clear overfluxing condition
Settings
Pick-up 1.5 to 3.0 i.e. 110V x 1.05 = 2.31
50Hz
DT setting range 0.1 to 60 seconds
V/Hz Overfluxing Protection
V/H CHARACTERISTIC:
RL AVR
Ex
VT
G
Over-fluxing Relay
THERMAL OVERLOAD:
• EFFECT OF OVER LOAD ON TRANSFORMER INSULATION LIFE:
I load
TD setting
I load Top oil of power transformer
Heater
Thermal replica
Temperature sensing resistor
Remote
Temp. indication Local
Off
On
Off
On
Alarm
Trip
Pump control
Fan control
Overheating Protection
• Overcurrent protection designed for fault condition
• Thermal replica provides better protection for overload
– Current based – Flexible characteristics – Single or dual time constant – Reset facility – Non-volatile
Current
Time
Overload Protection
ZA
10000
1000
100
10
1 2 3 4 5 6
Trip time (s)
Current (multiple of thermal setting)
Single characteristic:
= 120 mins
Dual characteristic
Single characteristic:
= 5 mins
Thermal Overload Oil Filled Transformers
DIGITAL RELAYS FOR TRANSFORMER THERMAL WINDING PROTECTION