Transformer on Site Repair Report

1
LTL Transformers (Pvt) Limited A Subsidiary of LTL Holdings (Pvt) Ltd. 154/1 1, Railway Station Road, Angulana, Moratuwa, Sri Lanka. Telephone: (+94 11) 260 5101-3 Fax: (+p4 ll)260 7312 E-mail: [email protected] Transformer on site repair report Customer Location Repaired date Transformer serial number CapacityNoltage Manufactured year Observations . Slight Corrosion observed on radiator fins near stiffeners and base skid of the transformer. Repair Work Carried Out . The corroded areas were initially treated with emery paper to clean up. Then the residue corrosion was cleaned by applying "sunphos I 17" rust remover. Then as the anti-corrosive treatment CRC single component zinc rich compound with epoxy binder was applied to build up the primer coat to 70pm. Then RAL 9002 was used to build up the top coat to atotal of 140 pm by spray painting. Dimo(Pvt) Ltd Kosgoda 0511212014 T001R513 1s00 kvA 1 1kv 2014 {bk Prathaj Haputhanthri (Electrical engineer) tu.12/2912- Date Registered Office: 67, Park Sheet, Colombo 02, Sri Lanka Telephone Fax E-mai1 Intemet : (+94 l1) 269 5007,267 9916 : (+94 l1) 2684900 : [email protected] :www.ltl.lk Q***ffiffiffi

description

Site Repair Report

Transcript of Transformer on Site Repair Report

Page 1: Transformer on Site Repair Report

LTL Transformers (Pvt) LimitedA Subsidiary of LTL Holdings (Pvt) Ltd.154/1 1, Railway Station Road, Angulana, Moratuwa, Sri Lanka.

Telephone: (+94 11) 260 5101-3 Fax: (+p4 ll)260 7312 E-mail: [email protected]

Transformer on site repair report

Customer

Location

Repaired date

Transformer serial number

CapacityNoltage

Manufactured year

Observations

. Slight Corrosion observed on radiator fins near stiffeners and baseskid of the transformer.

Repair Work Carried Out. The corroded areas were initially treated with emery paper to clean

up. Then the residue corrosion was cleaned by applying "sunphosI 17" rust remover. Then as the anti-corrosive treatment CRC singlecomponent zinc rich compound with epoxy binder was applied tobuild up the primer coat to 70pm. Then RAL 9002 was used to buildup the top coat to atotal of 140 pm by spray painting.

Dimo(Pvt) Ltd

Kosgoda

0511212014

T001R513

1s00 kvA 1 1kv

2014

{bkPrathaj Haputhanthri(Electrical engineer)

tu.12/2912-Date