Transformer Differential Application Notes.pdf

download Transformer Differential Application Notes.pdf

of 30

Transcript of Transformer Differential Application Notes.pdf

  • 8/10/2019 Transformer Differential Application Notes.pdf

    1/30

    MiCOM 30 SeriesTransformer Differential Protection

    Application GuideIssue B, February 2001

  • 8/10/2019 Transformer Differential Application Notes.pdf

    2/30

    TransformerDifferential ApplicationGuide EN b.doc 2

    Contents

    1 Introduction .............................................................................................4

    2 Mode of Operation and Basic Setting Instructions ........................................5

    2.1 Amplitude Matching ..................................................................................................... 5

    2.2 Vector Group Matching and Zero-Sequence Current Filtering................................... 8

    2.3 Tripping Characteristic...............................................................................................122.3.1 Definition of Idand IR.................................................................................................122.3.2 First Section of the Tripping Characteristic ...............................................................132.3.3 Second Section of the Tripping Characteristic .........................................................14

    2.3.4 Third Section of the Tripping Characteristic .............................................................152.3.5 Algorithmic Treatment of Idand IR.............................................................................17

    3 Setting Instructions for Special Applications............................................... 18

    3.1 Unfavorable Primary Nominal Transformer Current ................................................18

    3.2 In-Zone Grounding Transformer................................................................................19

    3.3 Tap-Changing Transformers ......................................................................................20

    4 Instructions for Commissioning and Testing...............................................23

    4.1 Checking the Phase Angle of the Phase Currents......................................................23

    4.2 Checking the Basic Threshold Value of the Tripping Characteristic.........................244.2.1 Single-End, Three-Phase Symmetrical Infeed...........................................................244.2.2 Single-End, Single-Phase Infeed ...............................................................................24

    Appendix

    A Vector Groups and Transformer Configurations

  • 8/10/2019 Transformer Differential Application Notes.pdf

    3/30

    3 TransformerDifferential ApplicationGuide EN b.doc

    Symbols and Subscripts

    SymbolsI Current phasor

    a Operator for phase rotation of +120

    V Voltage

    Angle

    S Power

    k Matching factor

    Subscripts

    prim Primary quantity sec Secondary quantity

    rel Variable within relay

    nom Nominal quantity

    ref Reference quantity

    max Maximum value

    max-1 Second largest value

    mid Mean value

    min Minimum value

    CT Main current transformer (set)

    A, B, C Phase A, B, or C

    x Dummy variable for phase A, B, or C

    x+1 Dummy variable for the lagging phase in the cycle with respect to phase A, B, orC

    x-1 Dummy variable for the leading phase in the cycle with respect to phase A, B, orC

    amp Amplitude-matched

    vec Amplitude-matched and vector-group-matched (including zero-sequence

    current filtering)zero Zero-sequence component

    pos Positive-sequence component

    neg Negative-sequence component

    1, 2, 3 Measuring system 1, 2, or 3

    y Dummy variable for measuring system 1, 2, or 3

    a, b, c, d End or winding a, b, c, or d of the protected object

    z Dummy variable for end or winding a, b, c, or d of the protected object

    d Differential variable

    R Restraining variable

  • 8/10/2019 Transformer Differential Application Notes.pdf

    4/30

    TransformerDifferential ApplicationGuide EN b.doc 4

    1 Introduction

    Protection devices in the MiCOM 30 series are described in detail in the respectiveoperating manuals as regards technical properties, functional characteristics, and properhandling during installation, connection, commissioning, and operation. However, theoperating manuals do not provide any information regarding the philosophy behind eachspecific product or the way in which the functional possibilities of a particular protectiondevice can be used to handle special applications.

    The present application guide is intended to close this gap. For the transformer differentialprotection function group of MiCOM P63x devices, the purpose is to give the reader abetter understanding of the design of the individual function blocks and then to providerelated instructions for settings, commissioning, and testing.

  • 8/10/2019 Transformer Differential Application Notes.pdf

    5/30

    5 TransformerDifferential ApplicationGuide EN b.doc

    2 Mode of Operation and Basic Setting Instructions

    Transformer differential protection is based on the principle of comparison of measuredvariables, i.e., the instantaneous values of the phase currents of all ends are compared withone another. Both the absolute value and the phase of the measured variables in questionare included in the current comparison.

    2.1 Amplitude Matching

    Before the phase currents of the individual windings or ends can be compared, they mustfirst be matched with respect to the absolute value transformations resulting from the ratedtransformation ratios of the transformer and the main current transformer.

    kamp,a

    kamp,b

    A

    B

    C

    A

    B

    C

    Winding a Winding b

    a,x,amp)rel(

    a,x(sec)

    a,x)prim(

    a,x IIII )prim(

    b,x(sec)

    b,x)rel(

    b,xb,x,amp IIII

    The goal of amplitude matching is that in fault-free operation under idealized conditionsthe corresponding phase currents of the individual ends will be scaled so that they areequivalent in absolute value. Phase currents that have been matched so as to be equal inabsolute value are referred to as amplitude-matched phase currents:

    b,x,ampa,x,amp II =

    Scaling to produce identical absolute values is achieved by means of one amplitude-matching factor kampfor each end:

    )rel(b,xb,am p

    )rel(a,xa,amp IkIk =

    The phase current in the relays can be expressed as primary phase current for each end by

    means of the individual rated transformation ratios, i.e., via the nominal current of the relayand the secondary and primary nominal current of the main current transformer:

  • 8/10/2019 Transformer Differential Application Notes.pdf

    6/30

    TransformerDifferential ApplicationGuide EN b.doc 6

    b,rel,nom(sec)b,CT,nom

    )prim(b,CT,nom

    )prim(b,x

    b,amp

    a,rel,nom(sec)a,CT,nom

    )prim(a,CT,nom

    )prim(a,x

    a,amp

    b,rel,nom

    (sec)b,x

    b,ampa,rel,nom

    (sec)a,x

    a,amp

    )rel(b,xb,amp

    )rel(a,xa,amp

    II

    I

    Ik

    II

    I

    Ik

    I

    Ik

    I

    Ik

    IkIk

    =

    =

    =

    Under the condition that for each end the nominal current of the relay and the secondarynominal current of the main current transformer agree, we obtain:

    )prim(b,CT,nom

    )prim(b,x

    b,amp)prim(a,CT,nom

    )prim(a,x

    a,ampI

    Ik

    I

    Ik =

    The ratio of the primary currents is obtained from the ratio of the nominal transformervoltages as follows:

    )prim(a,nom

    )prim(b,nom

    )prim(b,CT,noma,amp

    )prim(a,CT,nomb,amp

    )prim(b,x

    )prim(a,x

    V

    V

    Ik

    Ik

    I

    I=

    =

    As one can see, the equation does not determine the absolute values of the individual

    amplitude-matching factors but rather the ratio of these factors:

    )prim(b,CT,nom

    )prim(b,nom

    )prim(a,CT,nom

    )prim(a,nom

    b,amp

    a,amp

    IV

    IV

    k

    k

    =

    The absolute value of the amplitude-matching factors in each case is now definedadvantageously so that matching results in scaling to the nominal transformer currents. Thisis done by introducing reference power Srefas a common reference quantity for all ends:

    )prim(b,ref

    )prim(b,CT,nom

    )prim( a,ref

    )prim(a,CT,nom

    )prim(b,nom

    )prim(ref

    )prim(b,CT,nom

    )prim( a,nom

    )prim(ref

    )prim(a,CT,nom

    )prim(b,nom

    )prim(b,CT,nom

    )prim( a,nom

    )prim(a,CT,nom

    )prim(b,CT,nom

    )prim(b,nom

    )prim( a,CT,nom)prim( a,nom

    b,amp

    a,amp

    I

    I

    I

    I

    V3

    S

    I

    V3

    S

    I

    V

    1

    I

    V

    1

    I

    IV

    IVkk =

    ===

    Scaling to the nominal transformer currents is thus only possible in cases in which thenominal powers of the individual windings of all ends are equal and can thus be set to bethe common reference power Sref. In three-winding transformers, the nominal powers of theindividual windings generally differ. In such cases it is recommended that the nominalpower of the highest-power winding be set as the reference power Sref.

  • 8/10/2019 Transformer Differential Application Notes.pdf

    7/30

    7 TransformerDifferential ApplicationGuide EN b.doc

    In each case, a commonreference power Srefmust be set for allends. The amplitude-matching factors are obtained in each case as follows:

    )prim(z,nom

    )prim(ref

    )prim( z,CT,nom

    )prim(z,ref

    )prim( z,CT,nomz,amp

    V3

    S

    I

    I

    Ik

    ==

    The amplitude-matched phase currents are formed by scalar multiplication, whereby theindividual phase currents are multiplied by the corresponding amplitude-matching factor:

    z,x

    )prim(z,nom

    )prim(ref

    )prim(z,CT,nom

    z,x)prim(z,ref

    )prim(z,CT,nom

    z,xz,ampz,x,amp I

    V3

    S

    II

    I

    IIkI

    ===

    Setting the amplitude-matching function is very simple and does not require anycalculations. Only the following primary nominal values need to be set:

    A

    B

    C

    Winding a Winding b

    A

    B

    C

    )prim(a,CT,no m

    I )prim( a,nomV )prim(

    b,no mV )prim(

    b,CT,no mI

    )prim(max,nom

    )prim(ref

    SS =

    The amplitude-matching factors are calculated automatically by the protection device. Thedevice also checks automatically to see whether the resulting amplitude-matchingfactors kamp,zare within the limits specified by requirements of numerical processing:

    None of the amplitude-matching factors kamp,zmust exceed a value of 5:

    5k z,amp

    The ratio of the maximum amplitude-matching factor kamp,maxto the second-largestamplitude-matching factor kamp,max-1must not exceed a value of 3:

    3k

    k

    1max,amp

    max,amp

    The second-largest amplitude-matching factor kamp,max-1must not fall below a value of0.7:

    0.7k 1max,amp

  • 8/10/2019 Transformer Differential Application Notes.pdf

    8/30

    TransformerDifferential ApplicationGuide EN b.doc 8

    2.2 Vector Group Matching and Zero-Sequence Current Filtering

    Since the phase of the measured variables is also included in the current comparison, thephase relations of the amplitude-matched phase currents of the ends in question must alsobe matched in accordance with the respective vector group. Basically, this matchingoperation can be carried out regardless of the phase winding connections, since the phaserelation is described unambiguously by the characteristic vector group number.

    Vector group matching is therefore performed solely by mathematical phasor operationson the amplitude-matched phase currents of the low-voltage sidein accordance with thecharacteristic vector group number. This is shown in the following figure for vector groupcharacteristic number 5, where vector group Yd5 is used as the example:

    Iamp,A,a

    Iamp,B,aIamp,C,a

    Iamp,A,b

    Iamp,B,b

    Iamp,C,b

    - Iamp,A,bIamp,C,b- Iamp,A,b

    1/3(Iamp,C,b- Iamp,A,b)

    530

    A

    B

    C

    A

    B

    C

    Winding a Winding b

    No operation is carried out on the high-voltage side in connection with vector groupmatching. However, one should note that the phase windings are connected in a wyeconfiguration, the neutral of which is operationally grounded. In the event of system faults toground, the circuit for the zero-sequence component of the fault current would close via thegrounded neutral that lies within the transformer differential protection zone and would thus

    appear in the measuring systems as differential current. The consequence would beundesirable tripping.

  • 8/10/2019 Transformer Differential Application Notes.pdf

    9/30

    9 TransformerDifferential ApplicationGuide EN b.doc

    For this reason the zero-sequence component of the three-phase system must be eliminatedfrom the phase currents on the high-voltage side. In accordance with its definition, the zero-sequence current is determined as follows from the amplitude-matched phase currents:

    ( )z,C,ampz,B,ampz,A,ampz,zero,amp III3

    1I ++=

    On the low-voltage side, the zero-sequence current in the example shown above isautomatically filtered out based on the mathematical phasor operations. This is not alwaysnecessary and also not always desired, but is basically the result of any subtraction of twophase current phasors:

    ( ) ( )( ) ( )( ) ( )

    z,neg,amp2

    z,pos,ampz,A,ampz,C,amp

    z,neg,amp2

    z,pos,amp2

    z,C,ampz,B,amp

    z,neg,ampz,pos,amp2

    z,B,ampz,A,amp

    z,neg,amp2

    z,pos,ampz,zero,ampz,C,amp

    z,neg,ampz,pos,amp

    2

    z,zero,ampz,B,amp

    z,neg,ampz,pos,ampz,zero,ampz,A,amp

    I1aI1aII

    IaaIaaII

    Ia1Ia1II

    IaIaII

    IaIaII

    IIII

    +=

    +=

    +=

    ++=

    ++=

    ++=

    The following tables show that for all odd-numbered vector group characteristics the zero-sequence current on the low-voltage side is basically always filtered out, whereas for even-numbered vector group characteristics the zero-sequence current on the low-voltage side is

    basically never filtered out automatically. The latter is also true for the high-voltage sidesince in that case, as explained above, no mathematical phasor operations are performed.

    Vector group matching and zero-sequence current filtering must therefore always be viewedin combination. The following tables list all the mathematical phasor operations.

    Mathematical operations on the high-voltage side:

    With Izerofiltering Without Izerofiltering

    z,zero,ampz,x,ampz,y,vec III = z,x,ampz,y,vec II =

  • 8/10/2019 Transformer Differential Application Notes.pdf

    10/30

    TransformerDifferential ApplicationGuide EN b.doc 10

    Mathematical operations on the low-voltage side for an even-numbered vector groupcharacteristic:

    Vector Group With Izerofiltering Without Izerofiltering

    0 z,zero,ampz,x,ampz,y,vec III = z,x,ampz,y,vec II =

    2 z,zero,ampz,1x,ampz,y,vec III = + z,1x,ampz,y,vec II +=

    4 z,zero,ampz,1x,ampz,y,vec III = z,1x,ampz,y,vec II =

    6 z,zero,ampz,x,ampz,y,vec III = z,x,ampz,y,vec II =

    8 z,zero,ampz,1x,ampz,y,vec III = + z,1x,ampz,y,vec II +=

    10 z,zero,ampz,1x,ampz,y,vec III = z,1x,ampz,y,vec II =

    Mathematical operations on the low-voltage side for an odd-numbered vector groupcharacteristic:

    Vector Group

    1 ( )z,1x,ampz,x,ampz,y,vec II3

    1I +=

    3 ( )z,1x,ampz,1x,ampz,y,vec

    II3

    1I

    +

    =

    5 ( )z,x,ampz,1x,ampz,y,vec II3

    1I =

    7 ( )z,x,ampz,1x,ampz,y,vec II3

    1I = +

    9 ( )z,1x,ampz,1x,ampz,y,vec II3

    1I + =

    11 ( )z,1x,ampz,x,ampz,y,vec II31I =

  • 8/10/2019 Transformer Differential Application Notes.pdf

    11/30

    11 TransformerDifferential ApplicationGuide EN b.doc

    Setting the vector group matching function is very simple and does not require anycalculations. Only the characteristic vector group number needs to be set:

    0, 1, 2, 3, 4, 5, 6, 7, 8, 9, 10 or 11

    Winding a Winding b

    A

    B

    C

    A

    B

    C

    Setting the zero-sequence current filtering function is very simple and does not require anycalculations. Zero-sequence current filtering should only be activated for those ends wherethere is operational grounding of a neutral point:

    with I0filtering without I0filtering

    A

    B

    C

    A

    B

    C

    Winding a Winding b

  • 8/10/2019 Transformer Differential Application Notes.pdf

    12/30

    TransformerDifferential ApplicationGuide EN b.doc 12

    2.3 Tripping Characteristic

    After the currents of the individual ends have been matched, the transformer beingprotected can be viewed as a current node as defined by the first Kirchhoff law. Accordingto this law, the sum of the current phasors of all ends is equal to zero in fault-free operationunder idealized conditions. Only an internal fault in the protection zone of differentialprotection will generate a phasor sum of end currents that differs from zero, namely thedifferential current Id. The magnitude of the differential current Idcan therefore be used asthe criterion for detecting an internal fault.

    In practice, however, differential currents even occur in fault-free operation and can beattributed essentially to the following influencing factors:

    Magnetizing transformer current, which flows only from the infeed end and thereforeappears as differential current

    Current-dependent transformation errors of the participating current transformer sets,which also result in a differential current

    Whereas the magnetizing current is determined by the level of the system voltage and cantherefore be viewed as constant, irrespective of load level, the transformation errors of theparticipating current transformer sets are a function of the respective current level. Thethreshold value of a transformer differential protection device is therefore not implementedas a constant differential current threshold but is formed as a function of the restrainingcurrent IR. The restraining current corresponds to the current level in the transformer beingprotected. The function Id= f(IR) is represented as the tripping characteristic in the I d-IRplane.

    2.3.1 Definition of Idand IR

    According to the first Kirchhoff law, the differential current Idis always defined as the phasorsum of the end currents:

    K+++= c,y,vecb,y,veca,y,vecy,d IIII

    The restraining current IRrepresents the through-current of the transformer being protected,and for two-winding differential protection it is defined as the phasor difference, as follows:

    b,y,veca,y,vecy,R II2

    1

    I =When the infeed to an internal fault from both ends is exactly equal as regards amplitudeand angle, then both currents cancel one another out, i.e., the restraining current becomeszero and the restraining effect disappears. Disappearance of the restraining effect whenthere is an internal fault is a desirable result since in this case transformer differentialprotection attains maximum sensitivity.

    In the case of transformer differential protection for more than two ends, we must work witha different definition of restraining current IRsince the phasor difference between more thantwo variables is not defined:

    ( )K+++= c,y,vecb,y,veca,y,vecy,R III21I

  • 8/10/2019 Transformer Differential Application Notes.pdf

    13/30

    13 TransformerDifferential ApplicationGuide EN b.doc

    In this case the restraining effect never disappears when there is an internal fault; therestraining effect is even reinforced in the case of multi-end infeed. However, the restrainingcurrent factor means that the differential current I

    d

    has twice the value of the restrainingcurrent IRso that safe and reliable tripping is also guaranteed in the case of multi-endinfeed.

    2.3.2 First Section of the Tripping Characteristic

    The first section represents the most sensitive region of the tripping characteristic in the formof the settable basic threshold value Id>. The default setting of 0.2 takes into account themagnetizing current of the transformer, which flows even in a no-load condition and isgenerally less than 5% of the nominal transformer current.

    The first section of the tripping curve runs horizontally until it reaches the load line for single-end infeed. This is advantageous for commissioning and testing. In the case of single-endinfeed, the desired characteristic value is always identical to the set basic thresholdvalue Id> so that in this regard no special calculation of the characteristic threshold value isnecessary.

    1 2 3 4

    1

    2

    3

    0

    Id

    IR

    Load linefor single-end infeed

    Magnetizing currentcharacteristic

    Id>

    First section oftripping characteristic

  • 8/10/2019 Transformer Differential Application Notes.pdf

    14/30

    TransformerDifferential ApplicationGuide EN b.doc 14

    The line of the first section of the tripping curve corresponds to the horizontal line ofdifferential current, given the basic threshold value Id>. The characteristic equation for thefirst section of the tripping characteristic is as follows:

    >= dy,Ry,d III

    The intersection of the first section of the tripping curve with the load line occurs at arestraining current IH,m1, which is a function of the setting of the basic threshold value Id>:

    >= d2m,R I5,0I

    2.3.3 Second Section of the Tripping Characteristic

    The second section of the tripping curve covers the load current range, so that in this section

    we must reckon not only with the transformer magnetizing current, which appears asdifferential current, but also with differential currents that can be attributed to thetransformation errors of the current transformer sets.

    If we calculate the "worst case" with Class 10P current transformers, then the maximumallowable amplitude error according to DIN EN 60044-1 is 3 % for nominal current. Thephase-angle error can be assumed to be 2 for nominal current. The maximum allowabletotal error for nominal current is then obtained, in approximation, as (0.0-

    3 + sin 2) 6.5 %. If the current is increased to the nominal accuracy limit current, then thetotal error for Class 10P current transformers can be 10 % maximum. Beyond the nominalaccuracy limit current, the transformation error can be of any magnitude.

    The dependence of the total error of a current transformer on current is therefore non-linear.In the operating current range, i.e., in the current range below the nominal accuracy limitcurrent, we can expect a "worst case" total error of approximately 10 % per currenttransformer set.

    The second section of the tripping characteristic forms a straight line, the slope of whichshould correspond to the cumulative total error of the participating current transformer sets.The curve slope m1 can be set. The default setting for m1is defined as 0.3 with respect toprotection of three-winding transformers.

  • 8/10/2019 Transformer Differential Application Notes.pdf

    15/30

    15 TransformerDifferential ApplicationGuide EN b.doc

    1 2 3 4

    1

    2

    3

    0

    Id

    IR

    Load linefor single-end infeed

    Transformation errorcharacteristics

    for two or threecurrent transformer sets

    Id>

    Second section of

    tripping characteristic

    m1

    First knee point oftripping characteristic

    The line of the second section of the tripping characteristic runs through the intersection ofthe load line for single-end infeed with the line of the first section of the trippingcharacteristic. The characteristic equation for the second section of the trippingcharacteristic is as follows:

    ( )1dy,R1y,Ry,d m5,01IImII >+=

    A parallel shift of the first section of the tripping curve resulting from a change in the basicthreshold value Id> also brings about a parallel shift of the second section of the trippingcurve.

    2.3.4 Third Section of the Tripping Characteristic

    The second knee point of the tripping characteristic determines the end of the overcurrentzone in the direction of increasing restraining current in fault-free operation. It can be ashigh as four times the nominal current in certain operating cases such as when a paralleltransformer has failed.

    Therefore, the second knee point can be set (IR,m2) for a default setting of 4I ref. IR,m2must beset in accordance with the maximum possible operating current.

  • 8/10/2019 Transformer Differential Application Notes.pdf

    16/30

    TransformerDifferential ApplicationGuide EN b.doc 16

    1 2 3 4

    1

    2

    3

    0

    Id

    IR

    Load linefor single-end infeed

    Id>

    Third section oftripping characteristic

    IR,m2

    m1

    m2Second knee point oftripping characteristic

    Restraining currents that go beyond the set knee point are then evaluated as continuousfault currents. For truly continuous fault currents, the third section of the trippingcharacteristic could therefore be given an infinitely large slope. Since, however, we alsoneed to take into account the possibility that a fault can occur in the transformer differentialprotection zone as the result of the system fault, a finite slope m2is provided for the thirdsection of the tripping curve. The default setting for m 2is 0.7.

    The line of the third section of the tripping characteristic runs through the intersection of the

    vertical restraining current line at IR,m2with the line for the second section of the trippingcharacteristic. The characteristic equation for the third section of the tripping characteristic isas follows:

    ( ) ( )212m,R1dy,R2y,Ry,d mmIm5,01IImII +>+=

    A parallel shift of the first section of the tripping characteristic resulting from a change in thebasic threshold value Id> also brings about a parallel shift of the third section of thetripping characteristic.

  • 8/10/2019 Transformer Differential Application Notes.pdf

    17/30

    17 TransformerDifferential ApplicationGuide EN b.doc

    2.3.5 Algorithmic Treatment of Idand IR

    For evaluating differential current Idand restraining current IRin the Id-IRplane, theinstantaneous values of the rectified quantities are not used since they do not guaranteestable tripping under all conditions.

    Differential current Idand restraining current IRtherefore undergo numerical smoothing. Onepurpose of this smoothing is to provide the lowest possible residual ripple; it should also becharacterized by the shortest possible settling time (transient recovery time). Since the tworequirements are contradictory in nature, a balance must be struck between the two. Doublesmoothing of differential current Idand restraining current IRis achieved as the result ofcomplicated algorithmic analysis.

    The rectified differential current Idand the rectified restraining current IRfirst undergo half-period, non-recursive smoothing, which has a very fast settling time. The starting quantities

    for this first smoothing operation are referred to as singly smoothed quantities.

    In a subsequent second smoothing operation, the singly smoothed quantities undergo anadditional recursive smoothing process. The starting quantities for this second smoothingoperation are referred to as doubly smoothed quantities.

  • 8/10/2019 Transformer Differential Application Notes.pdf

    18/30

    TransformerDifferential ApplicationGuide EN b.doc 18

    3 Setting Instructions for Special Applications

    3.1 Unfavorable Primary Nominal Transformer Current

    Amplitude Matching

    In rare cases, there may be the problem that one of the conditions for the amplitudematching factors is no longer satisfied. The following example shows one such case:

    Winding a Winding b

    400 / 1 A

    1000 / 1 A

    1000 / 1 A

    52.5 kV 10.5 kV

    36 MVA

    Iref,prim,a

    = 396 A

    kamp,a

    = 1.010

    Sref,prim

    = 36 MVA

    Iref,prim,b

    = 1979 A

    kamp,b

    = 0.505

    Iref,prim,a

    = 275 A

    kamp,a

    = 1.455

    Sref,prim= 25 MVA

    Iref,prim,b

    = 1375 A

    kamp,b

    = 0.727

    kamp,a

    / kamp,b

    = 2

    kamp,a

    / kamp,b

    = 2

    Dy7

    If one selects the nominal power Snomof the transformer as the reference power Sref, as is

    recommended, then the condition kamp0.7 is not satisfied on the low-voltage side. This isdue to the unusually large difference between the primary nominal current of the maincurrent transformer set, which is only 1000 A, and the nominal and reference current of thetransformer low-voltage winding, which is 1979 A.One solution is to vary the reference power. The ratio of the amplitude matching factor

    calculated above to the minimum required amplitude matching factor is0.505 / 0.7 = 0.72. If we reduce the reference power that was set above by at least this

    factor to 0.7236 MVA = 25.9 MVA 25 MVA, then amplitude matching is possible withoutany problem.

    Tripping Characteristic

    One should note, however, that due to amplitude matching, which differs from the nominaltransformer quantities, the phase currents are rated more highly by a factor of1.455 / 1.010 = 1.44. For this reason, the basic threshold value Id> of the tripping

    characteristic should be increased by the same factor to 1.440.2 = 0.288 0.3.

  • 8/10/2019 Transformer Differential Application Notes.pdf

    19/30

    19 TransformerDifferential ApplicationGuide EN b.doc

    3.2 In-Zone Grounding Transformer

    Vector Group Matching and Zero-Sequence Current Filtering

    If there is a grounding transformer on one end of the transformer within the zone ofprotection, then zero-sequence current filtering must always be activated on this end. Thisapplies even if the phase windings on the grounding transformer end are delta-connected.Basically, zero-sequence current filtering must always be enabled if there is operationalneutral grounding in the zone of protection on the end in question.The following diagram shows the current distribution for such a configuration in the event ofan external single-phase-to-ground fault:

    A

    B

    C

    Winding a Winding b

    A

    B

    C

    On the high-voltage side, zero-sequence current filtering remains deactivated because theneutral point is not grounded, so that no current phasor operation is necessary for forming

    the vector-group-matched current variables.Worthy of note on the low-voltage side are both zero-sequence current filtering and vectorgroup matching for the characteristic vector group number 5, in connection with the fact

    that the phase currents of the low-voltage side must be set to be a factor of 3 smaller thanthe phase currents of the high-voltage side. This means that for the phase C measuringsystem the matched currents of both sides are zero and that for the phase A and Bmeasuring systems the matched currents of the two sides cancel one another out.

  • 8/10/2019 Transformer Differential Application Notes.pdf

    20/30

    TransformerDifferential ApplicationGuide EN b.doc 20

    In the case of an internal single-phase fault, on the other hand, transformer differentialprotection will be tripped. The following diagram shows the corresponding currentdistribution in the case of single-end infeed of the fault from the high-voltage side:

    A

    B

    C

    Winding a Winding b

    A

    B

    C

    In the case of single-end infeed of the fault from the high-voltage side, the currenttransformer set on the low-voltage side remains at zero current. When the phase currents onthe high-voltage side in Phases A and B are of sufficient intensity, they lead to tripping oftransformer differential protection.

    3.3 Tap-Changing Transformers

    Amplitude Matching

    The infeed transformer is equipped with a tap changer on its high-voltage end forregulating the voltage of the input system. The rated transformation ratio of the transformeris changed by adjusting the tap changer, i.e., the nominal voltage on the high-voltage sideand also the corresponding nominal current on the high-voltage side are not constant butare determined by a range which corresponds to the range of adjustment of the tapchanger.

  • 8/10/2019 Transformer Differential Application Notes.pdf

    21/30

    21 TransformerDifferential ApplicationGuide EN b.doc

    A

    B

    C

    A

    B

    C

    Winding a Winding bIx,a

    Ix,b

    )prim(max,a,no m

    )prim(mi n,a,no m VV K

    )prim(b,no mV

    )prim(mi n,a,no m

    )prim(max,a,no m II K

    )prim(b,no mI

    Amplitude matching can therefore only occur for a mean nominal voltage on the high-voltage side that still needs to be defined. Depending on the actual tap-change position,there appears a differential current Idthat is more or less large and increases linearly withthe restraining current IR. An adjustment of the tap changer brings about a change in theslope of this tap changer characteristic.

    1 2 3 4

    1

    0

    Id

    IR

    Id>

    IR,m2

    m1

    m2

    Tap changer characteristicat a given tap position

    With regard to the tripping characteristic of differential protection, amplitude matchingmust be carried out by selecting a suitable mean value for the nominal voltage on the high-voltage side such that the slope of the tap changer curve is identical for the two outermosttapping positions:

    b,y,vecmin,a,y,vec

    b,y,vecmin,a,y,vec

    b,y,vecmax,a,y,vec

    b,y,vecmax,a,y,vec

    II2

    1

    II

    II2

    1

    II

    +=

    +

  • 8/10/2019 Transformer Differential Application Notes.pdf

    22/30

    TransformerDifferential ApplicationGuide EN b.doc 22

    For a load flow from the high-voltage side a in the direction of the low-voltage side b,Ivec,y,a= Ivec,y,aand Ivec,y,b= -Ivec,y,b:

    b,y,vecmin,a,y,vec

    b,y,vecmin,a,y,vec

    b,y,vecmax,a,y,vec

    b,y,vecmax,a,y,vec

    II2

    1

    II

    II2

    1

    II

    +

    =+

    Furthermore, Ivec,y,a,max> Ivec,y,band Ivec,y,a,min< Ivec,y,b:

    b,y,vecmin,a,y,vec

    min,a,y,vecb,y,vec

    b,y,vecmax,a,y,vec

    b,y,vecmax,a,y,vec

    II

    II

    II

    II

    +

    =

    +

    With the desired mean value Ivec,y,a,mid= Ivec,y,b, amplitude matching is complete:

    min,a,y,vecmax,a,y,vecmid,a,y,vec

    min,a,y,vecmax,a,y,vec2

    mid,a,y,vec

    2mid,a,y,vecmin,a,y,vecmid,a,y,vecmin,a,y,vecmax,a,y,vecmid,a,y,vecmax,a,y,vec

    2mid,a,y,vecmin,a,y,vecmid,a,y,vecmid,a,y,vecmax,a,y,vecmin,a,y,vecmax,a,y,vec

    mid,a,y,vecmin,a,y,vec

    min,a,y,vecmid,a,y,vec

    mid,a,y,vecmax,a,y,vec

    mid,a,y,vecmax,a,y,vec

    III

    II2I2

    IIIIIII

    IIIIIII

    II

    II

    II

    II

    =

    =

    +=

    =+

    +

    =

    +

    For amplitude matching, therefore, the geometric mean of the minimum and maximumnominal voltage must be set on the high-voltage side:

    )prim(max,a,nom

    )prim(min,a,nom

    )prim(mid,a,nom

    VVV =

    Tripping Characteristic

    Slope m1of the second section of the tripping characteristic must be increased inaccordance with the slope of the tap changer characteristic for the outermost tappingposition, i.e., the setting for m1must be increased by the following value:

    ( ))prim( mid,a,nom)prim( max,a,nom

    )prim(mid,a,nom

    )prim(max,a,nom

    II21

    II

    +

    or ( ))prim( mid,a,nom)prim( min,a,nom

    )prim(min,a,nom

    )prim(mid,a,nom

    II21

    II

    +

  • 8/10/2019 Transformer Differential Application Notes.pdf

    23/30

    23 TransformerDifferential ApplicationGuide EN b.doc

    4 Instructions for Commissioning and Testing

    4.1 Checking the Phase Angle of the Phase Currents

    It is possible to make an estimate regarding correct connection of the phase currents byusing the phase angles that are provided as measured operating values.

    With an ideally symmetrical load through the transformer, the phase angles between thephase currents of a given end must be displayed as follows, depending on the rotary fielddirection in the system:

    Clockwise Rotating Field Counterclockwise Rotating Field

    === 120z,CAz,BCz,AB === 120z,CAz,BCz,AB

    The setting of the function parameter for direction of rotating field has no effect in this case.

    The phase angles of a given phase between the phase currents of two ends must bedisplayed as follows, depending on the transformer vector group and the direction ofrotating field in the system:

    Vector Group Clockwise Rotating Field Counterclockwise Rotating Field

    0 = 180za,x = 180za,x

    1 = 150za,x = 150za,x

    2 = 120za,x = 120za,x

    3 = 90za,x = 90za,x

    4 = 60za,x = 60za,x

    5 = 30za,x = 30za,x

    6 = 0za,x = 0za,x

    7 = 30za,x = 30za,x

    8 = 60za,x = 60za,x

    9 = 90za,x = 90za,x

    10 = 120za,x = 120za,x

    11 = 150za,x = 150za,x

    The settings for the function parameter for direction of rotating field and for the vectorgroup have no effect in this case. On the other hand, a change in the setting of the functionparameter for the connection direction of a given main current transformer set affects the

    corresponding measured operating value by 180.

  • 8/10/2019 Transformer Differential Application Notes.pdf

    24/30

    TransformerDifferential ApplicationGuide EN b.doc 24

    4.2 Checking the Basic Threshold Value of the Tripping Characteristic

    The basic threshold value Id> of the tripping characteristic can be easily checked by meansof single-end current infeed (s. Section 2.3.2).

    4.2.1 Single-End, Three-Phase Symmetrical Infeed

    For single-end, three-phase symmetrical infeed, the operate current Ix,zis obtained asfollows, taking into account the amplitude matching factor kamp,z:

    z,nomz,amp

    dz,x I

    k

    II

    >=

    The differential and restraining currents displayed as measured operating values areobtained as follows:

    z,nom

    z,xz,ampy,R

    z,nom

    z,xz,ampy,d

    I

    Ik

    2

    1I

    I

    IkI

    =

    =

    4.2.2 Single-End, Single-Phase Infeed

    In the case of single-end, single-phase infeed, it is necessary to consider not only theamplitude matching factor kamp,zbut also another matching factor kvec,zcorresponding to thevector group matching and zero-sequence current filter settings. The tripping current Ix,zisthen obtained as follows:

    z,nomz,vecz,amp

    dz,x I

    kk

    II

    >=

    The corresponding matching factor kvec,zcan be taken from the following tables.

    The differential and restraining currents displayed as measured operating values are

    obtained as follows:

    z,nom

    z,xz,vecz,ampy,R

    z,nom

    z,xz,vecz,ampy,d

    I

    Ikk

    2

    1I

    I

    IkkI

    =

    =

  • 8/10/2019 Transformer Differential Application Notes.pdf

    25/30

    25 TransformerDifferential ApplicationGuide EN b.doc

    Matching factor kvec,zfor the individual measuring systems y as a function of the suppliedphase x for the high-voltage side:

    x = A x = B x = C

    y = 1 y = 2 y = 3 y = 1 y = 2 y = 3 y = 1 y = 2 y = 3

    1/0.67 0/0.33 0/0.33 0/0.33 1/0.67 0/0.33 0/0.33 0/0.33 1/0.67

    Without Izero-filtering / with Izerofiltering

    Matching factor kvec,zfor the individual measuring systems y as a function of the suppliedphase x and as a function of the set vector group for the low-voltage side in question:

    x = A x = B x = CVector Group

    y = 1 y = 2 y = 3 y = 1 y = 2 y = 3 y = 1 y = 2 y = 3

    0 1/0.67 0/0.33 0/0.33 0/0.33 1/0.67 0/0.33 0/0.33 0/0.33 1/0.67

    1 0.58 0 0.58 0.58 0.58 0 0 0.58 0.58

    2 0/0.33 0/0.33 1/0.67 1/0.67 0/0.33 0/0.33 0/0.33 1/0.67 0/0.33

    3 0 0.58 0.58 0.58 0 0.58 0.58 0.58 0

    4 0/0.33 1/0.67 0/0.33 0/0.33 0/0.33 1/0.67 1/0.67 0/0.33 0/0.33

    5 0.58 0.58 0 0 0.58 0.58 0.58 0 0.58

    6 1/0.67 0/0.33 0/0.33 0/0.33 1/0.67 0/0.33 0/0.33 0/0.33 1/0.67

    7 0.58 0 0.58 0.58 0.58 0 0 0.58 0.58

    8 0/0.33 0/0.33 1/0.67 1/0.67 0/0.33 0/0.33 0/0.33 1/0.67 0/0.33

    9 0 0.58 0.58 0.58 0 0.58 0.58 0.58 0

    10 0/0.33 1/0.67 0/0.33 0/0.33 0/0.33 1/0.67 1/0.67 0/0.33 0/0.33

    11 0.58 0.58 0 0 0.58 0.58 0.58 0 0.58

    Without Izero-filtering / with Izerofiltering

  • 8/10/2019 Transformer Differential Application Notes.pdf

    26/30

    TransformerDifferential ApplicationGuide EN b.doc 26

    Appendix

    A Vector Groups and Transformer Configurations

    The vector group identifies the connection of the windings and the phase relation of thevoltage phasors assigned to them. It consists of code letters that specify the connection ofthe phase windings and a code number that defines the phase displacement.

    For three-phase alternating current, a distinction is made between the following phasewinding connections:

    Delta connection (D,d)

    Wye connection (Y,y)

    Zigzag connection (Z,z)

    The upper-case letters are used for the high-voltage windings, and the lower-case letters forthe medium and low-voltage windings. The upper-case letter appears first in the vectorgroup. If several windings have the same nominal voltages, the upper-case letter isassigned to the winding having the highest nominal power, and if the windings haveidentical nominal powers, the upper-case letter is assigned to the winding that is firstaccording to the order of connections given above. If the neutral point of a winding is wye-connected or zigzag-connected, then the identifying symbol is YN or ZN or yn or zn,respectively.

    For phase displacement, the phasor of the high-voltage winding is considered to be the

    reference quantity. The code number, when multiplied by 30, specifies the angle by whichthe phasor of the low-voltage winding lags behind the phasor of the high-voltage winding.For multi-winding transformers, the phasor of the high-voltage winding is the referencequantity; the symbol for this winding is given first. The other symbols follow in the order ofdecreasing nominal winding voltages.

    By definition, therefore, the vector group is a function of the viewing direction. The vectorgroups related to the two viewing directions are complementary and add up to thenumber 12.

    Vector groups for which the corresponding phase windings belong to the same phase arereferred to as "true" vector groups. The following listing includes only"true" vector groups; it

    also contains allthe "true" vector groups that are possible.

    "Untrue" vector groups are formed from the "true" vector groups by cyclical reversal ortransposition of phases.

    By transposing phases A with C, B with A, and C with B, we obtain the following:

    from the "true" vector group Yy0: the "untrue" vector group Yy4 from the "true" vector group Yy6: the "untrue" vector group Yy10 from the "true" vector group Yy5: the "untrue" vector group Yy9

    By transposing phases A with B, B with C, and C with A, we obtain the following:

    from the "true" vector group Yy0: the "untrue" vector group Yy8

    from the "true" vector group Yy6: the "untrue" vector group Yy2 from the "true" vector group Yy7: the "untrue" vector group Yy3

  • 8/10/2019 Transformer Differential Application Notes.pdf

    27/30

    27 TransformerDifferential ApplicationGuide EN b.doc

    All "true" vector groups with Yy connections:

    A

    B

    C

    A

    B

    C

    Yy0

    Yy0

    A

    B

    C

    A

    B

    C

    Yy6

    Yy6

    All "true" vector groups with Dy or Yd connections:

    A

    B

    C

    Dy11

    Yd1

    A

    B

    C

    A

    B

    C

    Dy1

    Yd11

    A

    B

    C

    A

    B

    C

    Dy7

    Yd5

    A

    B

    C

    A

    B

    C

    Dy5

    Yd7

    A

    B

    C

  • 8/10/2019 Transformer Differential Application Notes.pdf

    28/30

    TransformerDifferential ApplicationGuide EN b.doc 28

    All "true" vector groups with Yz or Zy connections:

    A

    B

    C

    A

    B

    C

    Yz11

    Zy1

    A

    B

    C

    A

    B

    C

    Yz1

    Zy11

    A

    B

    C

    Yz7

    Zy5

    A

    B

    C

    A

    B

    C

    A

    B

    C

    Yz5

    Zy7

  • 8/10/2019 Transformer Differential Application Notes.pdf

    29/30

    29 TransformerDifferential ApplicationGuide EN b.doc

    All "true" vector groups with Dz or Zd connections:

    A

    B

    C

    Dz10

    Zd2

    A

    B

    C

    A

    B

    C

    Dz0

    Zd0

    A

    B

    C

    A

    B

    C

    Dz8

    Zd4

    A

    B

    C

    A

    B

    C

    Dz2

    Zd10

    A

    B

    C

    A

    B

    C

    A

    B

    C

    Dz6

    Zd6

    A

    B

    C

    A

    B

    C

    Dz4

    Zd8

  • 8/10/2019 Transformer Differential Application Notes.pdf

    30/30