Transcript of Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Page 1: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Transformer Applications & Eco DirectiveCast Resin & Oil Distribution Transfomers

Anton Joseph & Enrique Palomares, Abril 2016

© ABB GroupMay 31, 2016 | Slide 1 | Ver. C

Page 2: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

§ Distribution Transformers

§ Transformer Fundamentals

§ Manufacturing Process

§ Transformer Specification

§ Design Considerations

§ Maintenance

§ Eco Directive

Agenda

Page 3: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

Distribution Transformers

Page 4: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

§ Total 3 Phase Losses = 3 I2 R

§ Active Power, P = √3 VI Cos Ф

§ I = P / (√3 V Cos Ф)

§ Losses = P2 R / (V2 Cos2 Ф)

§ Losses are inversely proportional to the square of Voltage& directly proportional to the square of the Active Power

§ High system voltage reduces transmission losses

§ Requires more expensive lines, cables & transformers

§ Generator transformers are step up

§ Distribution transformers are generally step down

§ Voltage taken down in several steps

§ Lower voltages closer to the consumers

Electricity DistributionWhy HV

Page 5: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

Electricity DistributionInterconnected Electricity System

Page 6: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

Electricity DistributionDistributed Generation

Page 7: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

© ABB GroupMay 31, 2016 | Slide 7

Electricity DistributionApplications

3

Transmission anddistribution

3

3

3

3

Power and distributiontransformers

3

2

Wind & Solar Powergeneration

22

Dry or Specialtransformers

2

2

1

1

1

1

Power transformers

11

Power generation

4

4

Commercial andresidential usage

4

4

Dry and distributiontransformers

5

Railway application

5

5

Dry or Specialtransformers(Traction)

6

Oil & Gasapplication

6

6

Subseatransformers

Transformer TypeApplication

Page 8: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

Transformer Types

10 – 63 MVA upto 170 kV

Up 10 MVA &up to 36 kV

50 – 10,000 kVAup to 36 kV

Up to 800 kV HVDC– 400 Tonnes

Pole Dry

Dry63 MVA72.5 kV

Traction

Page 9: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

§ Receives energy from higher transmission voltages andtransforms for distribution to lower voltage substations ordirectly to consumers

§ Typically from 11 to 0.4 kV in the UK

§ Normal Oil & Dry transformer ratings

§ Up to 10 MVA & 36 kV

§ Cast Resin Dry Transformers§ up to 63 MVA§ up to 72.5kV

Distribution TransformersIntroduction

Page 10: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

Transformer Fundamentals

Page 11: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

§ Faraday’s Law of Electromagnetic Induction

§ Vs / Vp = Ns / Np

§ Step up or step down

§ Isolate one circuit from the other

§ Harmonics are not isolated by the transformer

Transformer FundamentalsMagnetic Circuit

Single Phase

Page 12: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

100% POWER

VOLTAGE 1 VOLTAGE 2

99.7% POWER

Transformer FundamentalsHeat Loss

§ Losses generate heat

§ Removed through air ventilation or oilcirculation

0.3%

Three Phase

Page 13: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

Transformer FundamentalsCooling of Dry Transformers

§ In a dry transformer the heat generated by coilsand core is dissipated to air

Heat generated in coilsand core are transferred bythe air through convection

Cold air entrance from theambient

Hot air exit from thetransformer

§ AN

§ AN/AF

Page 14: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

Transformer FundamentalsCooling of Oil Transformers

§ Mineral or synthetic oil is used for cooling & insulation

§ O Mineral Oil with Flash Point ≤ 300oC,

§ K Flash Point > 300oC & biodegradable

§ Heat dissipated to air in the radiator

Radiators with fans

The cycle starts again: heat is genera-ted at coils and core and transferred tothe liquid

The heat is transferred in the radiatorsto ambient air, cooling thereby the liquid

The colder liquid flows back into thetransformer tank

The hot liquid, coming from coils andcore, flows through the radiators

§ ONAN

§ ONAF

§ OFAF

§ KNAN

§ ……..

Page 15: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

§ Copper or aluminum conductor is used

§ Cu has a higher conductivity (1.7*108Wm) than Al(2.8*108Wm), but a higher density

ÞTransformers with windings made of Cu or somewhatmore compact, but heavier than those made of Al

§ Cu is more expensive than Al and more kg of metal isneeded => transformers with Cu windings are moreexpensive

§ Specific markets or customers may require Cu windings

§ LV and HV coils use mostly the same conductor material,but it can also be different

§ Cu and Al can be used in the shape of wires or foils

Transformer FundamentalsWindings and conductor materials

Page 16: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

§ Transformer components need to be electrically insulated:§ HV coil versus LV coil, phase versus phase, and coils versus core

§ The majority of voltage and the electric field is taken up by air or oil

§ The main purpose of the solid or paper insulation is:§ dielectric insulation§ avoidance of shorts between windings turns due to contamination§ mechanical rigidity and protection for the coils

Transformer FundamentalsInsulation

core

HV coil – Insulation Solid or Paper with OilHV coil - Conductor

LV coil - Insulation – Solid or Paper with OilLV coil - Conductor

Air or Oil insulation between LV and HV

Air or Oil insulation between phases

Page 17: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Transformer FundamentalsLosses and efficiency

Transformers have 2 loss compo-nents:

§ No-load loss in iron core:§ due to hysteresis and eddy

currents§ independent of load

§ Load loss in windings:§ due to resistive and eddy

currents§ increases with square of load§ load loss value is given for

100% load

Transformer efficiency can easily becalculated from the losses§ maximum efficiency is

typically at 40-50% load

0% 20% 40% 60% 80% 100%load

loss

no-load loss P0

load loss Pk

efficiency

96%

97%

98%

99%

100%

0% 20% 40% 60% 80% 100%load

Page 18: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

§ Load loss:§ Load losses must be always referred to the same

temperature

§ Reference temperature for oil transformers is T=75º

and for dry transformers T=120º. (F-class)

§ Formula for recalculating the losses to any temperature:

P120º = P75º x (234,5 +120)/(234,5+75)

Transformer FundamentalsTemperature reference for load loss

Page 19: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

Transformer FundamentalsNo-load loss

§ No-load losses do not depend on the temperature

§ Oil transformers have lower no-load losses than drytransformers for the same rating because the core issmaller (air needs larger clearance).

A BExample1000 KVA:

Example1000 KVA:

No-load lossesfor a drytransformer:2.300 W

No-load lossesfor an oiltransformer:1.700 W

Page 20: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

Manufacturing Process

Page 21: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

Manufacturing ProcessDesign

© ABB GroupMay 31, 2016 | Slide 21

Engineering design capabilitiesAdvanced Design Tools

Common Design System

Page 22: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

Manufacturing ProcessModelling

© ABB GroupMay 31, 2016 | Slide 22

3D Modelling: PTC Creo 2.0§ Awarded 3D software that combines Parametric and Direct modeling.§ Maximize innovation while at the same time ensuring speed,

flexibility, and faster time-to-market.Finite Element Method Analysis (FEM)§ Optimize virtual prototypes in the design process.§ Improve product life cycle, achieving strong electrical and mechanical

designs.FEM Mechanical: MSC Nastran Structures§ Awarded structural analysis software used by our engineers to

perform static and dynamic analyses: Vibrations, Seismic Conditions,Handling of special designs,..

FEM Electrical: MagNet, ThermNet & ElecNet§ Software specialized in magnetic and dielectric fields, which allows to

calculate key electrical parameters: Impedances, losses, temperaturerise & hot-spots, short-circuit forces, prediction of voltagebreakdown...

Page 23: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

Manufacturing ProcessRobotic core stacking cell

© ABB GroupMay 31, 2016 | Slide 23

Page 24: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

Manufacturing ProcessRobotic core stacking

© ABB GroupMay 31, 2016 | Slide 24

§ 52% reduction in stacking labor time compared withmanual stacking.

§ No load losses, noise level and no load current reductioncompared with manual stacking.

§ Improvement in finishing. Improvement of product qualityperception by the customer.

§ Decrease in accidents.

Page 25: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

Manufacturing ProcessHigh Voltage Coil

© ABB GroupMay 31, 2016 | Slide 25

§ High voltage winding consists of a foilwinding in multiple disks.

§ Each disk has several turns.

§ High voltage coil is reinforced withfiberglass net.

Page 26: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

without any patternWire is wound in random

without any pattern

High Voltage CoilRandom Winding

Page 27: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

short circuits

The adjacent wires in a random winding can have high potential differences, thuscreating a large number of critical areas without sufficient insulation distances

This could cause problems with the insulation between turns leading to possibleshort circuits

Return to principal menu

High Voltage CoilRandom Winding

Page 28: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

layers, as shown.Wire is wound in different

layers, as shown.

High Voltage CoilWire in Layers

Page 29: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

The insulating space between two layersis modified progressively, with the aim toassure enough distance in critical areas

High Voltage CoilWire in Layers

Page 30: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

between layers

Spaces between layers areprogressively modified to increasedistances between turns., However

there will be high potential differencebetween layers

High Voltage CoilWire in Layers

Page 31: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

turns.

This system consists of foil windingsin multiple disk. Each disk has several

turns.

High Voltage CoilFoil Disk

Page 32: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

foil disk is made as shownThe connection between two consecutive

foil disk is made as shown

High Voltage CoilFoil Disk

Page 33: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

problems with insulation

There are critical areaslocalized between disks. Wecan allocate enough spaceduring design to eliminateproblems with insulation

High Voltage CoilFoil Disk

Page 34: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

compared to other winding methods.

In a foil disk winding design, the safety insulating space,between critical turns, can be easily guaranteed

compared to other winding methods.

Return to principal menu

High Voltage CoilFoil Disk

Page 35: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

correct positioning of disks

The foil is wound in a specialmachine using laser for thecorrect positioning of disks

High Voltage CoilFoil Disk

Page 36: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

High voltage coilWinding

© ABB GroupMay 31, 2016 | Slide 36

Page 37: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

being encapsulated.Foil disk winding before

being encapsulated.

High Voltage CoilFoil Disk

Page 38: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

High Voltage CoilMoulding

© ABB GroupMay 31, 2016 | Slide 38

Page 39: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

High Voltage CoilCasting

© ABB GroupMay 31, 2016 | Slide 39

§ In horizontal filling system, cavities don’tform between foils disks. This is becausethe air is pushed by the resin mixture inradial direction – from bottom to the top

§ Disks can’t move during the castingprocess. This ensures the insulating levelbetween foils disks to remain constant

Page 40: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

High Voltage CoilDisadvantage of Vertical Casting

© ABB GroupMay 31, 2016 | Slide 40

§ In vertical filling system, the high voltagemold is filled in a vertical position in thecasting chamber.

§ Cavities can form between the foil disks,due to air being pushed by the resinmixture in axial direction – from thebottom to the top.

§ Any air bubbles will lead to increasedpartial discharge

Filling direction

Page 41: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

Manufacturing ProcessLow Voltage Coil

© ABB GroupMay 31, 2016 | Slide 41

Page 42: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

Manufacturing ProcessLow Voltage Coil

© ABB GroupMay 31, 2016 | Slide 42

Page 43: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

Manufacturing ProcessLow Voltage Coil - Curing

© ABB GroupMay 31, 2016 | Slide 43

Option:Low voltageSealed or Casted

Page 44: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

Manufacturing ProcessOil Transformer Windings

§ Windings are dried in an oven toattain below 1% of moisture content

§ Epoxy resin coated paper providesadhesion of winding layers

§ Filled with filtered and degassedtransformer oil under vacuum

Page 45: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

Manufacturing ProcessOil Transformer Windings§ Prevention of moisture from the ambient is achieved by

§ Hermetically sealed tank§ Separating the tank with a conservator – outside air enters through a

Silica Gel Breather

Page 46: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

Assembly section

© ABB GroupMay 31, 2016 | Slide 46

Firstly Secondly

Page 47: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

Assembly section

© ABB GroupMay 31, 2016 | Slide 47

SensorsPTC 130-150

Page 48: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

Test laboratories

© ABB GroupMay 31, 2016 | Slide 48

Two test roomscertificate ISO / IEC17025 since 2001according to ENAC

(generalrequirements forthe competence oftesting andcalibrationlaboratories)

Page 49: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

The final testRoutine and special tests

© ABB GroupMay 31, 2016 | Slide 49

Routine and specialTests:

FAT

Temperature RiseTest

Lightning Impulsetest

Sound level test

Other special tests…

Page 50: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

Transformer Specification

Page 51: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

§ Rated Power in kVA

§ kW x Power Factor

§ Primary Voltage (± 5% Tolerance)

§ Secondary Voltage at no load

§ Number of phases & Frequency (± 5% Tolerance)

§ Impedance

§ `Resistance to AC circuit with magnitude & phase

§ Altitude (< 1000 m a.s.l.) & ambient temperature (40oC)

§ Cooling type

§ Losses

§ Winding Material

Transformer SpecificationBasic

with AF, rating increases by up to 40%

with Cu about 70% higher price

low loss transformers up to ~50% higher costs

Page 52: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

Transformer SpecificationElectrical insulation system

§ Thermal Class

§ It indicates the maximum temperature that a materialcan admit without changing its characteristics

§ The temperature rise admitted in windings will dependon the insulation material thermal class

thermalclass

max. temp. admitted bythe insulation material

(°C)

average max.temperature rise in

windings (K)

(A) 105 65 Oil

(B) 130 80

(F) 155 100 Dry

(H) 180 125

(C) 220 150

Page 53: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

§ The allowed winding temperature rise depends on the insulationclass, maximum ambient temperature and hot spot

§ Simple consideration: max. ambient T + winding T-rise <=max. T-rise admitted by the insulation class

§ Example: oil transformer:§ Maximum ambient temperature: 40ºC§ Insulation class (A) = 105º C§ Winding temperature rise admitted = 105 – 40 = 65ºC

=> allowed average winding T-rise:60°C

§ Example: dry transformer:§ Maximum ambient temperature: 40ºC§ Insulation class (F) = 155º C§ Winding temperature rise admitted = 155 – 40 = 115ºC

=> allowed average winding T-rise 100°C

§ In practice the transformer is not continuously at 100% load andthe temperature varies (day, month, year). This compensates forincreased temperature during overload periods

Transformer SpecificationWinding temperature rise

Page 54: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

§ Match the transformer to the system

§ Variation in primary or secondary voltage

§ Example + or - 5% Tap for a 11 to 0.4 kV transformer

§ Turns Ratio = 11 / 0.4 = 27.5

§ Increase in Turns Ratio = 1.05 * 27.5 = 28.875

§ Decrease in Turn Ratio = 0.95 * 27.5 = 26.125

§ If Primary Voltage is constant, the secondary voltage at

§ +5% Tap – 11 / 28.875 = 380 V

§ -5% Tap – 11 / 26.125 = 412 V

§ To keep the Secondary Voltage constant with thePrimary Voltage changing

§ +5% Tap – 0.4 * 28.875 = 11.55 k V

§ -5% Tap – 0.4 * 26.125 = 10.45 kV

Transformer SpecificationTap Changer

Page 55: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

Transformer SpecificationOff Line Tap Changer

§ Discrete voltageregulation by varying thenumber of turns

§ Distribution transformersare normally furnishedwith off-load tapchangers

§ The standard number ofpositions is 5 (+/-2x2.5%).More positions can bemanufactured on request

§ Connections are normallybolted for Dry Type

Page 56: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

§ Tap changer located in the tank

Transformer SpecificationOff Line Tap Changer – Oil Type

Page 57: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

Transformer SpecificationOn Line Tap Changer

§ On-Load Tap Changer for frequently varying voltages

Page 58: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

§ Indicates winding configuration and difference in phase angle

§ D, Y, N, d, y, n, 1 to 11 (clock face) – Dyn11 (30o lead)

§ Example YNd11

Transformer SpecificationVector Group

A1

B1

C1

A2

B2

C2

a1

b1

c1

a2

b2

c2

A1

A2

B1

B2C2

C1

a1

a2 c1

c2

b1

b2

Page 59: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

§ Example YNd1

Transformer SpecificationVector Group

A1

B1

C1

A2

B2

C2

a1

b1

c1

a2

b2

c2

A1

A2

B1

B2C2

C1

a1

a2

c1

c2

b1

b2

Page 60: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

§ Some Vector Group are not available

§ Example YNd2

Transformer SpecificationVector Group

A1

B1

C1

A2

B2

C2

a1

b1

c1

a2

b2

c2

A1

A2

B1

B2C2

C1

a1c1

b1

Page 61: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

Transformer SpecificationEnvironmental & Climatic Conditions – Dry Type

Environmental Class:

§ E0 Normal indoor installation, no condensation, noconsiderable pollution

§ E1 Limited pollution, occasional condensation e.g. offcircuit periods

§ E2 Heavy pollution, frequent condensation

Climate Class:

§ C1 Lowest ambient temperatures:§ operation – 5°C

§ storage and transport - 25°C

§ C2 Lowest ambient temperatures:§ operation –25 ºC

§ storage and transport at –25ºC

Page 62: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

Transformer SpecificationFire Resistance – Dry Type

Fire Class:

§ F0 No special requirements except typical characteristicsfor dry-type transformers

§ F1 Increased demands

§ All materials practically free of halogens

§ Limited formation of fumes

§ Limited contribution with calorific energy to thesource of fire

§ Self extinguishing transformer fire

Page 63: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

Cost driversVoltage class and impulse level (BIL)

The transformer must withstand the corresponding BIL levelaccording to the voltage level – Induced Voltage (Separate SourceWithstand) & Lightning Impulse Test

The different standards (IEC, ANSI, etc.) give more than one BILlevel for the same voltage. For example in IEC:

UM F.l. kVef BIL List 1 BIL List 2

1,1 3

3,6 10 20 40

7,2 20 40 60

12 28 60 75

17,5 38 75 95

24 50 95 125

36 70 145 170

52 95 25072,5 140 325

The lower the BIL-level for the sameUM, the lower isthe price

Page 64: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

Transformer SpecificationEnclosure and IP Classification

§ The “IP” classification describes the degree of protectionprovided by enclosures

§ Explanation of numbers: IP23§ 1st number: protection against solid foreign objects: e.g. 2

corresponds to openings of max. 12.5 mm diameter(=finger).

§ 2nd number: protection against water: e.g. 3 providesprotection against sprayed water

Page 65: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

Dry transformers - accessoriesEnclosures

§ Dry transformers can be used for indoor or outdoor installations

§ for outdoor installations an enclosure is always necessary (so far)

§ for indoor applications customer may want an enclosure due to:§ safety reasons (energized transformers are not allowed to be

touched)§ ambient conditions (e.g. dust, water,..)

Page 66: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

Dry transformers - accessoriesEnclosures

IP-classification -Enclosures

A dry transformeris normally usedfor indooroperation withIP00 protection

BUT

Any kind of IPprotection can besupplied with drytransformers

IP31

IP23

IP44

IP00

Page 67: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

§ Ventilated and non-ventilated enclosures (for high IP) needto be distinguished

§ In case of dirty or contaminated ambient, non-ventilatedenclosures should be used

§ Non-ventilated enclosures could need a heat exchanger

§ Heat exchangers can be air-to-air or air-to-water heatexchangers

§ Recently a more compact thermosiphon-based air-to-airheat exchanger was introduced

§ Additionally the direct-water cooled technology is nowavailable and allows to take out heat directly from thetransformer without the need to pass via a heat exchanger

Dry transformers - accessoriesEnclosure and cooling

Page 68: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

Dry transformers - accessoriesEnclosure and cooling

§ When a dry transformer is defined with enclosure, thetemperature rise for windings needs to be lower than for IP00transformers, because the air temperature inside theenclosure is higher.

§ A complete air temperature calculation is required. The largerthe IP degree, the lower the winding temperature rise ispermitted

The winding temperaturerise depends on themaximum ambienttemperature.

OutdoorAir temp40ºC

internalair temp> 40ºC

Page 69: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

Page 70: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

Page 71: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

Oil transformers - accessoriesBuchholz Relay

§ Protective device sensitive to effects of dielectric failure fittedto the conservator

§ Small accumulation of gas produced by decomposition ofthe insulating oil accumulates at the top providing awarning§ Accumulated gases on the top can be analysed

§ Electric arc produces rapid oil flow providing a trip signal

Page 72: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

Design Considerations

Page 73: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

§ Primary & Secondary Voltages with tapping

§ Measure, Calculate and confirm

§ Maximum Coincident Load + contingency for planned &unplanned growth

§ kVA = kV x A x 1.732 (square root of 3)

§ Harmonics

§ < 5% THD

§ K Factors – weighting for harmonics

§ K 1 is linear load

§ K 4, 9 & 13 are common – transformer Is de-ratedaccordingly

§ Harmonic Filtering

Design ConsiderationsBasic Requirements

Page 74: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

§ Short circuit secondary windings

§ Increase voltage on primary windings until full load currentflows on the secondary

§ Impedance Voltage is due to winding resistance andleakage current

§ Z in % - (Impedance Voltage / Rated Voltage)

§ Short circuit Impedance is the percentage of drop inVoltage due to winding resistance and leakage reactanceto the rated Voltage

Design ConsiderationsImpedance Measurement

Page 75: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

§ Typical values 4 to 6% depending on the transformer size

§ Impedance is specified at 100% load

§ For ANAF rating it is at AN rating & not at AF

§ Determines the maximum value of current under faultconditions

§ Impacts on the design of the protection system

§ Impedance increases with the number of turns and thethickness of the coil

§ Impedance reduces with core area and the height of thetransformer

§ Design is a compromise between losses andimpedance

Design ConsiderationsImpedance

Page 76: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

§ Centralised or Distributed

§ Redundancy

§ Distributed with parallel operation

§ Same Voltage ratios, frequency, phase sequence andpolarity

§ Transformer should have the same phase displacementbetween primary & secondary voltages

§ Example – Dyn11 & Yd11

§ Same Impedance

§ A tolerance of 10% between the transformers

§ Load is shared in proportion to the MVA ratings

§ Unequal impedance will cause the lower impedancetransformer to be overloaded

§ Power Ratio of maximum 2:1 defined in IEC 676-8

Design ConsiderationsParallel Operation

Page 77: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

§ Space constraints

§ Eco Directive transformer are bigger and heavier

§ No specific advantage between Al or Copper

§ Cu transformers are shorter, fatter and heavier butmore expensive

§ It may be possible to change the design toaccommodate size constraints

Design ConsiderationsSize

Winding Length Width Height Weight PriceAluminium 1,700 801 2,076 3,105 100%Copper 1,850 1,010 1,850 4,300 175%% 109% 126% 89% 138%

Sizes for the Same Rating - Al vs Cu

Page 78: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

§ Outdoor / Indoor, Dusty, Salty

§ Indoor – preferably dry transformers

§ Self extinguishing and environmentally friendly

§ Lower maintenance

§ Outdoors

§ Dry transformers can be installed with IP44enclosure

§ C4H painting, Sealing of low voltage coil andspace heaters

§ Oil transformers are suitable for external installationwith harsh environmental conditions

Design ConsiderationsLocation

Page 79: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

§ Storage of more than 200 litres of oil

§ 500 kVA ONAN 11 to 0.4 kV transformer containsaround 500 to 900 litres

§ Additional guidance required if it is less than 10 m awayfrom any inland freshwater or coastal waters or less than50 m away from a well or borehole – Source ProtectionZones

§ Secondary Containment System Storage capacity shouldnot be than 110%

§ Minimum height of bund wall 150 mm to allow for rainfalland firefighting foam

§ Equipped with oil separation and pump to removerainwater

§ Fire Risk Assessment

§ Separation, Fire Extinguishing Systems, Barriers

Design ConsiderationsSpillage & Fire Containment

Page 80: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

Maintenance

Page 81: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

§ Low maintenance

§ Annual or quarterly for harsh environments such as dust orfumes or exposed to vibrations

§ Check for tightness of screws and bolts

§ Clean dusty surfaces with vacuum clearer or with dryair / Nitrogen

§ Insulation Resistance Test

MaintenanceDry Transformers

Page 82: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

MaintenancePartial discharges

§ If the insulation of a winding has a defect, partial dischargeappears.

§ In a vacuum cast transformer this defect can originate from anair bubble generated during the resin filling process.

§ This air cavity creates small electrical discharges, e.g. due tothe potential difference between two turns. With time itdestroys the insulation.

Cavity inbubbleshape Shortcircuit

Resin (Insulation)

Wndg. turns Partial dischargePartial dischargesmust bemeasured.Standard valuesare below 10 pC

Page 83: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

§ Check oil leaks and oil level at regular intervals

§ Oil including Midel are hygroscopic – will absorbatmospheric moisture

§ Maintenance of Silica Gel Breather - monthly

§ Annual Oil Sampling

§ Increase frequency if highly loaded

§ Serviceability of oil – dielectric strength & watercontent

§ Insulation system – deterioration of oil & paperproduces combustible gases – Dissolved GasAnalysis

§ Maintenance of accessories

MaintenanceOil Transformers

Page 84: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

MaintenanceOil Reclamation

Oil InletGate Valve

InletPump

Filter

Heating

DegassingChamber

DischargePump

VacuumPump

VacuumGauge

Oil OutletGate Valve

Page 85: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

Eco Directive

Page 86: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

Eco DirectiveOil Transformers

Page 87: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

Eco DirectiveDry Transformers

Page 88: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

Eco DirectiveTier 1 vs Tier 2

Size & weight between Tier 1 & Tier 2: 5 to 10% impact

Load No Load Load No LoadOil 11,000 950 9,500 855Dry 11,000 1,800 11,000 1,620

Eco Directive Losses in Watts for 1250 kVA

TypeTier 1 Tier 2

Page 89: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

Eco DirectivePeak Efficiency Index

Page 90: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

Eco DirectivePeak Efficiency Index

Page 91: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

§ Up to 40% increase in power with fans for emergencyoperation only

§ Increase in load is not part of normal duty cycle

§ Temporary increase in load due to failure of anothertransformer

§ N-1 operation mode

§ Transformer will comply with Eco Directive at AN ratingand not on AF rating

§ If the increased load is part of the normal duty cycle, thenAF rating losses should be complied with

Eco DirectiveANAF

Page 92: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

Eco DirectiveANAF

Power NLL LL1202000 2600 160002800 3423 20384

Comply at AN/AF Comply at AN Comply at AFLoad (kVA) No load lossesLoad Losses Load (kVA) No load losses Load Losses Load (kVA) No load losses Load Losses

0% 0 2600 0 0% 0 2600 0 0% 0 3423 010% 200 2600 104 10% 200 2600 160 10% 280 3423 20415% 300 2600 234 15% 300 2600 360 15% 420 3423 45925% 500 2600 650 25% 500 2600 1000 25% 700 3423 127430% 600 2600 936 30% 600 2600 1440 30% 840 3423 183540% 800 2600 1664 40% 800 2600 2560 40% 1120 3423 326150% 1000 2600 2600 50% 1000 2600 4000 50% 1400 3423 509660% 1200 2600 3744 60% 1200 2600 5760 60% 1680 3423 733871% 1429 2600 5309 71% 1429 2600 8168 71% 2000.6 3423 1040675% 1500 2600 5850 75% 1500 2600 9000 75% 2100 3423 1146680% 1600 2600 6656 80% 1600 2600 10240 80% 2240 3423 1304695% 1900 2600 9386 95% 1900 2600 14440 95% 2660 3423 18397

100% 2000 2600 10400 100% 2000 2600 16000 100% 2800 3423 20384140% 2800 2600 20384 140% 2800 2600 31360 31.7%

53.8%

Page 93: Transformer Applications & Eco Directive Cast Resin & Oil Distribution Transfomers

Course Ref: 382T1

Eco DirectiveANAF

Power NLL LL1202000 2600 160002800 3423 20384