Trans Stab Paper

6
7/28/2019 Trans Stab Paper http://slidepdf.com/reader/full/trans-stab-paper 1/6 Power System Transient Stability Analysis Using ETAP Software Jignesh S. Patel P.G. Student of Electrical Power System B.V.M. Engineering College V.V.Nagar, Gujarat  [email protected] Manish N. Sinha Assistant Professor in EE Department B.V.M. Engineering College V.V.Nagar, Gujarat [email protected]   AbstractPower-system stability is a term applied to alternating-current electric power systems, denoting a condition in which the various synchronous machines of the system remain in synchronism, or "in step," with each other. Conversely, instability denotes a condition involving loss of synchronism, or falling "out of step". Occurrence of a fault in a power system causes transients. To stabilize the system load flow analysis is done. Actually in practice the fault generally occurs in the load side. As we controlling load side which will lead to complex problem in order to avoid that we are controlling the generator side. This paper covers the transient stability analysis of 400 kV substation of Soja. A three phase fault is located at specified bus to analyze the effect of fault location in critical clearing time on the system stability.  Keywords- critical clearing time, ETAP, three phase fault,  transient, transient stability. I. INTRODUCTION Successful operation of a power system depends largely on the engineer's ability to provide reliable and uninterrupted service to the loads. The reliability of the power supply implies much more than merely being available. Ideally, the loads must be fed at constant voltage and frequency at all times. The first requirement of reliable service is to keep the synchronous generators running in parallel and with adequate capacity to meet the load demand. Synchronous machines do not easily fall out of step under normal conditions. A second requirement of reliable electrical service is to maintain the integrity of the power network. The high-voltage transmission system connects the generating stations and the load centers. Power-system stability is a term applied to alternating-current electric power systems, denoting a condition in which the various synchronous machines of the system remain in synchronism, or "in step," with each other. Conversely, instability denotes a condition involving loss of synchronism, or falling "out of step." For convenience of analysis, stability problems are generally divided into two major categories:  Steady-state stability  Transient stability Steady-state stability refers to the ability of the power system to regain synchronism after small and slow disturbances, such as ground power changes. An extension of the steady-state stability is known as the dynamic stability. Transient stability studies deal with the effects of large, sudden disturbances, such as the occurrence of the fault, the sudden outage of a line [1] [2]. Transient stability entails the evaluation of a power system’s ability to withstand large disturbances, and to survive transition to a normal operating condition. These disturbances can be faults such as: a short circuit on a transmission line, loss of a generator, loss of a load, gain of load or loss of a portion of transmission network. Large number of simulations is carried out regularly during planning stages to gain knowledge of this system. Yet, even a well designed and normally operated system may face the threat of transient instability [3]. On the platform of ETAP, a worldwide-used simulation tool for power system analysis, the electric grid is settled up for the modeling of generators, transformers, lines, cables, loads, the external equivalent grid, etc. Eleven typical load flow operations, including operation structures under normal, maintenance and extreme conditions, are set up as base cases for the detailed study, including inter-connected situation and isolated operation, or some key electric equipment out of service. With the units’ number increasing, the system presents rotor angle stability. With the multiple voltage levels in the system, voltage profile is sensitive to the system structure and operation point. It is critical for the case that most of the loads are large motors. Although the system is connected to the bulk system under normal condition, it may operate isolated at extremely fault contingency. Then the system faces the demanding requirement of frequency stability and control [4]. The aim of the investigation is to analyze the behavior of the synchronous machine in particular the angular position of the rotor with respect to time after the fault occurs in the system. Section II is the study of transient stability analysis. Section III describes the development of system model. Section IV is short circuit analysis of the model. Section V describes the results for transient stability. Section VI concludes the paper. II. TRANSIENT STABILITY ANALYSIS  A. Transient stability Each generator operates at the same synchronous speed and frequency of 50 hertz while a delicate balance between the 13-14 May 2011 B.V.M. Engineering College, V.V.Nagar,Gujarat,India National Conference on Recent Trends in Engineering & Technology

Transcript of Trans Stab Paper

  • 7/28/2019 Trans Stab Paper

    1/6

    Power System Transient Stability Analysis Using

    ETAP Software

    Jignesh S. Patel

    P.G. Student of Electrical Power SystemB.V.M. Engineering College

    V.V.Nagar, Gujarat

    [email protected]

    Manish N. Sinha

    Assistant Professor in EE DepartmentB.V.M. Engineering College

    V.V.Nagar, Gujarat

    [email protected]

    Abstract Power-system stability is a term applied toalternating-current electric power systems, denoting a condition

    in which the various synchronous machines of the system remain

    in synchronism, or "in step," with each other. Conversely,

    instabilitydenotes a condition involving loss of synchronism, or

    falling "out of step". Occurrence of a fault in a power system

    causes transients. To stabilize the system load flow analysis is

    done. Actually in practice the fault generally occurs in the load

    side. As we controlling load side which will lead to complex

    problem in order to avoid that we are controlling the generator

    side. This paper covers the transient stability analysis of 400 kV

    substation of Soja. A three phase fault is located at specified bus

    to analyze the effect of fault location in critical clearing time on

    the system stability.

    Keywords- critical clearing time, ETAP, three phase fault,

    transient, transient stability.

    I. INTRODUCTIONSuccessful operation of a power system depends largely on

    the engineer's ability to provide reliable and uninterrupted

    service to the loads. The reliability of the power supplyimplies much more than merely being available. Ideally, the

    loads must be fed at constant voltage and frequency at all

    times. The first requirement of reliable service is to keep the

    synchronous generators running in parallel and with adequate

    capacity to meet the load demand. Synchronous machines do

    not easily fall out of step under normal conditions. A second

    requirement of reliable electrical service is to maintain the

    integrity of the power network. The high-voltage transmission

    system connects the generating stations and the load centers.

    Power-system stability is a term applied to alternating-current

    electric power systems, denoting a condition in which the

    various synchronous machines of the system remain in

    synchronism, or "in step," with each other. Conversely,instability denotes a condition involving loss of synchronism,

    or falling "out of step."

    For convenience of analysis, stability problems are

    generally divided into two major categories:

    Steady-state stability Transient stability

    Steady-state stability refers to the ability of the power

    system to regain synchronism after small and slow

    disturbances, such as ground power changes. An extension of

    the steady-state stability is known as the dynamic stability.

    Transient stability studies deal with the effects of large,

    sudden disturbances, such as the occurrence of the fault, the

    sudden outage of a line [1] [2].Transient stability entails the evaluation of a power

    systems ability to withstand large disturbances, and to survive

    transition to a normal operating condition. These disturbances

    can be faults such as: a short circuit on a transmission line,

    loss of a generator, loss of a load, gain of load or loss of aportion of transmission network. Large number of simulationsis carried out regularly during planning stages to gain

    knowledge of this system. Yet, even a well designed and

    normally operated system may face the threat of transient

    instability [3].

    On the platform of ETAP, a worldwide-used simulation tool

    for power system analysis, the electric grid is settled up for themodeling of generators, transformers, lines, cables, loads, the

    external equivalent grid, etc. Eleven typical load flow

    operations, including operation structures under normal,

    maintenance and extreme conditions, are set up as base cases

    for the detailed study, including inter-connected situation and

    isolated operation, or some key electric equipment out ofservice. With the units number increasing, the system

    presents rotor angle stability. With the multiple voltage levels

    in the system, voltage profile is sensitive to the system

    structure and operation point. It is critical for the case that

    most of the loads are large motors. Although the system is

    connected to the bulk system under normal condition, it may

    operate isolated at extremely fault contingency. Then the

    system faces the demanding requirement of frequency stability

    and control [4].

    The aim of the investigation is to analyze the behavior of

    the synchronous machine in particular the angular position of

    the rotor with respect to time after the fault occurs in the

    system. Section II is the study of transient stability analysis.Section III describes the development of system model.

    Section IV is short circuit analysis of the model. Section V

    describes the results for transient stability. Section VI

    concludes the paper.

    II. TRANSIENT STABILITY ANALYSISA. Transient stability

    Each generator operates at the same synchronous speed and

    frequency of 50 hertz while a delicate balance between the

    13-14 May 2011 B.V.M. Engineering College, V.V.Nagar,Gujarat,India

    National Conference on Recent Trends in Engineering & Technology

  • 7/28/2019 Trans Stab Paper

    2/6

    input mechanical power and output electrical power is

    maintained. Whenever generation is less than the actual

    consumer load, the system frequency falls. On the other hand,whenever the generation is more than the actual load, the

    system frequency rise. The generators are also interconnected

    with each other and with the loads they supply via high

    voltage transmission line.

    The power system is routinely subjected to a variety of

    disturbances. Even the act of switching on an appliance in thehouse can be regarded as a disturbance. However, given the

    size of the system and the scale of the perturbation caused by

    the switching of an appliance in comparison to the size and

    capability of the interconnected system, the effects are not

    measurable. Large disturbance do occur on the system. These

    include severe lightning strikes, loss of transmission linecarrying bulk power due to overloading. The ability of power

    system to survive the transition following a large disturbance

    and reach an acceptable operating condition is called transient

    stability.Any disturbance in the system will cause the imbalance

    between the mechanical power input to the generator and

    electrical power output of the generator to be affected. As aresult, some of the generators will tend to speed up and somewill tend to slow down. If, for a particular generator, thistendency is too great, it will no longer remain in synchronismwith the rest of the system and will be automaticallydisconnected from the system. This phenomenon is referred toas a generator going out of step.

    B. Elementary view of transient stability analysis

    Fig.1.Simple two machine power system

    Fig.2.Phasor diagram of the different parameters

    Consider the very simple power system of Fig.1, consisting

    of a synchronous generator supplying power to a synchronous

    motor over a circuit composed of series inductive reactance

    XL. Each of the synchronous machines may be represented, at

    least approximately, by a constant-voltage source in series

    with a constant reactance. Thus the generator is represented by

    Eg and Xg; and the motor, by EMand XM. Upon combining

    the machine reactance and the line reactance into a single

    reactance, we have an electric circuit consisting of two

    constant-voltage sources, Eg and EM, connected through

    reactanceX=XG +XL +XM. It will be shown that the power

    transmitted from the generator to the motor depends upon the

    phase difference of the two voltagesEG andEM. Since these

    voltages are generated by the flux produced by the field

    windings of the machines, their phase difference is the same as

    the electrical angle between the machine rotors. The vectordiagram of voltages is shown in Fig.2 Vectorially,

    EG =EM + jXI (1)

    Hence the current is,

    = (2)The power output of the generator and likewise the power

    input of the motor, since there is no resistance in the line isgiven by,

    =

    = (3)Where Re means the real part of and means theconjugate of .Now let,

    = 0And

    = Then

    =

    (4)So,

    = 090 = 90 90 = cos90 = sin (5)This equation shows that the power P transmitted from the

    generator to the motor varies with the sine of the displacement

    angle between the two rotors, as plotted in Fig.2.

    The curve P versus is known as thepower angle curve and is

    shown in fig.3. The maximum power that can be transmittedin the steady state with the given reactance X and the given

    internal voltagesEG andEMis,

    = And occurs at a displacement angle = 90. The value of

    maximum power may be increased by rising either of the

    internal voltages or by decreasing the circuit reactance [1].

    13-14 May 2011 B.V.M. Engineering College, V.V.Nagar,Gujarat,India

    National Conference on Recent Trends in Engineering & Technology

  • 7/28/2019 Trans Stab Paper

    3/6

    Fig.3. Power-angle curve of the system.

    C. Swing equationThe electromechanical equation describing the relative

    motion of the rotor load angle () with respect to the statorfield as a function of time is known as Swing equation. The

    swing equation in terms of the inertia constant becomes,

    = (6)Where,

    M = inertia constant, it is not really constant when the rotorspeed deviates from the synchronous speed.

    Pm = Shaft power input, corrected for windage and friction

    losses.

    Pe = Pa sin = electrical power output, corrected for electrical

    losses.

    Pa = amplitude for the power angle curve.

    m = mechanical power angle.

    Swing equation in terms of electrical angle is,

    = (7)

    D.Equal-area criterianThe transient stability studies involve the determination of

    whether or not synchronism is maintained after the machine

    has been subjected to sever disturbance. This may be sudden

    application of load, loss of generation, loss of large load, or a

    fault on the system. In most disturbances, oscillations are ofsuch magnitude that linearization is not permissible and the

    nonlinear swing equation must be solved. A method known as

    the equal-area criterion can be used for a quick prediction of

    stability. This method is based on the graphical interpretation

    of the energy stored in the rotating mass as an aid to determine

    if the machine maintains its stability after a disturbance. Themethod is only applicable to a one-machine system connected

    to an infinite bus or a two-machine system.

    Consider a synchronous machine connected to an infinite

    bus. The swing equation with damping neglected is given by,

    = = (8)

    Where Pa is the accelerating power.

    From the above equation, we have

    = (9)

    Fig.4. Equal-area criterion (sudden change of load).

    Consider the machine operating at the equilibrium point 0,corresponding to the mechanical power input Pm0 = Pe0 as

    shown in figure 4. Consider a sudden step increase in input

    power represented by horizontal line Pm1. Since Pm1 > Pe0, the

    accelerating power on the rotor is positive and the power angle

    increases. The excess energy stored in the rotor during the

    initial acceleration is

    = = (10)With increase in , the electrical power increases, and when

    = 1, the electrical power matches the new input power Pm1.

    Even though the acceleration power is zero at this point, therotor is running above synchronous speed; hence, and

    electrical power Pe will continue to increase. Now Pm < Pe,

    causing the rotor to decelerate toward synchronous speed until

    = max.According to Equation for stability,

    = 0 (11)The rotor must swing past point b until an equal amount of

    energy is given up by the rotating masses. The energy given

    up by the rotor as it decelerates back to synchronous speed is,

    =

    = (12)The result is that the rotor swings to point b and theangle ,at which point| | = | | (13)This is known as the equal-area criterion. The rotor angle

    would then oscillate back and forth between 0and maxat its

    natural frequency. The damping present in the machine willcause these oscillations to subside and the new steady state

    operation would be established at point b [5].

    13-14 May 2011 B.V.M. Engineering College, V.V.Nagar,Gujarat,India

    National Conference on Recent Trends in Engineering & Technology

  • 7/28/2019 Trans Stab Paper

    4/6

    III. SYSTEM MODELThe Gujarat Energy Transmission Corporation has

    established a 400kV SOJA sub-station. it is 1.5 km between

    from Gojariya-Gandhinagar highway. It has a land of higher

    bearing capacity. Due to the higher requirement of agricultural

    as well as bulk power requirement of industrial area the soja

    center is so chosen. It covers total 50acres land, in which theconstruction of 400kV, 220kV and 33kV switchyard, control

    room and also staff quarters etc. The incoming line of 400kV

    at Soja s/s is from Wanakbori and PGCIL 400kV s/s which is

    single circuit type transmission line .The tower required for

    erection of 400kV transmission line which is coming from

    Wanakbori and PGCIL s/s are of three type i.e., A, type C and

    type D tower. The total number of tower required between

    Wanakbori & PGCIL and soja s/s is 412. The line has charged

    since 28th January 1987 In single line diagram two incoming

    lines from Wanakbori and PGCIL of 400kV, and two

    incoming line from Gandhinagar of 220kV.

    Fig. 5 One line diagram of 400 kV substation of Soja

    A power system must be modeled as a nonlinear system

    for large disturbances. Although power system stability may

    be broadly defined according to different operating conditions,an important problem which is frequently considered is the

    problem of transient stability. It concerns the maintenance of

    synchronism between generators following a severe

    disturbance. By the excitation control in a generating unit

    transient stability can be greatly enhanced. Another important

    issue of power system control is to maintain steady acceptable

    voltage under normal operating and disturbed conditions,

    which is referred as the problem of voltage regulation [5].

    IV. SHORT CIRCUIT ANALYSIS OF SYSTEM MODELA. System model in ETAP

    The case example is modeled in ETAP and shown in

    fig.6. ETAP is chosen as the simulation tool, which isdeveloped by OTI, a comprehensive analysis platform for the

    design, simulation, and operation of generation, transmission,

    distribution, and industrial power systems [5]. It supplies acalculations for load flow, short circuit, transient stability, etc,

    which are beneficial to explore the characteristics of

    simulated systems.

    Fig. 6 system model in ETAP

    B. Short circuit study

    The short circuit view of the system in ETAP is shownin figure 7. In ETAP, the report can be generated for LLL,

    LL, LG, LLG LLLG (symmetrical and asymmetrical both)fault.

    Fig. 7 Short circuit view in ETAP

    13-14 May 2011 B.V.M. Engineering College, V.V.Nagar,Gujarat,India

    National Conference on Recent Trends in Engineering & Technology

  • 7/28/2019 Trans Stab Paper

    5/6

    V. TRANSIENT STABILITY ANALYSIS OF THE SYSTEMMODEL IN ETAP

    The ETAP Transient Stability Analysis program is designed

    to investigate the system dynamic responses and stability

    limits of a power system before, during, and after system

    changes or disturbances. The program models dynamic

    characteristics of a power system, implements the user-definedevents and actions, solves the system network equation and

    machine differential equations interactively to find out system

    and machine responses in time domain.

    The different plot for generator 1&2 when fault on bus-6 at

    0.5sec and cleared at 1sec are shown below in fig.8 (a), (b),

    (c), (d), (e), (f), (g) & (h).

    Fig. 8 (a) Generator Exciter current

    Fig.8 (a) shows the result of the exciter current (Per unit vs.

    Time (sec)) for generator 1&2.

    Fig. 8 (b) Impedance Z

    Fig.8 (b) shows the impedance plot (X in % machine base vs.

    R in % machine base).

    Fig. 8 (c) Generator Reactive power

    Fig. 8 (c) shows the reactive power plot (Mvar vs. Time (sec))

    for generator 1&2.

    Fig. 8 (d) Generator Electrical Power

    Fig. 8 (d) gives the plot of electrical power (MW vs. Time

    (sec)) for generator 1&2.

    Fig. 8 (e) Generator Speed

    Fig. 8 (e) shows the plot for speed variation (Rpm vs. Time

    (sec)) for generator 1&2.

    13-14 May 2011 B.V.M. Engineering College, V.V.Nagar,Gujarat,India

    National Conference on Recent Trends in Engineering & Technology

  • 7/28/2019 Trans Stab Paper

    6/6

    Fig. 8 (f) Generator Relative Power Angle

    Fig. 8(f) is the plot for relative power angle (Degree vs. Time

    (sec)). We can see the result for generator 1&2.

    Fig. 8(g) Generator Terminal Current

    Fig. 8(g) is the plot of Generator Terminal Current (Amp vs.

    Time (sec)) for generator 1&2.

    Fig. 8 (h) Generator Absolute Power angle

    Fig. 8(h) shows the plot of Generator Absolute Power Angle

    (Degree vs. Time (sec)) for generator 1&2.

    VI. CONCLUSIONDynamic performance of a power system is significant in

    the design and operation of the system. The transient stabilitystudy determines the machine power angles and speed

    deviations, system electrical frequency, real and reactivepower flows of the machines, power flows of lines and

    transformers, as well as the voltage levels of the buses in the

    system. These system conditions provide indications for

    system stability assessments. The results are displayed on theone-line diagram, and also can be printed or plotted. For

    transient stability studies, you should model particular groups

    of machines in the system , which are known to have

    important influences on the system operation. The total

    simulation time for each study case should be sufficiently

    long to obtain a definite stability conclusion.

    Power system stability is the property of a power system

    that insures the system remains in electromechanical

    equilibrium throughout any normal and abnormal operating

    conditions.

    Because the power system stability is an electromechanical

    phenomenon, it is thus defined as the ability of designated

    synchronous machines in the system to remain in

    synchronism with one another following disturbance such as

    fault and fault removal at various locations in the system.

    This paper presents the study of transient stability analysis

    and also the transient stability analysis using ETAP. It shows

    the different graph of voltage, current, power angle and speed

    in the ETAP.

    ACKNOWLEDGMENT

    I would like to thank to B.V.M Engineering College for

    allowing the project work and procure the licensed package of

    ETAP software and kind support during project work.

    REFERENCES

    [1] Ankit Jha, Lalthangliana Ralte, Ashwinee Kumar, Pinak Ranjan PatiTRANSIENT STABILITY ANALYSIS USING EQUAL AREA

    CRITERION USING SIMULINKMODEL, Department of Electrical

    Engineering National Institute of Technology Rourkela, 2008-09.[2] Pranamita Basu, Aiswarya Harichandan, POWER SYSTEM STABILITY

    STUDIES USING MATLAB, National Institute of Technology Rourkela-

    769008, Orissa..[3] P.K. Iyambo, R. Tzonova, Transient Stability Analysis of the IEEE 14-

    Bus Electrical Power System, IEEE Conf. 2007.

    [4] Liang Wang, Li Li, Shanshan Shi, Yiwei Zhang, Zongxiang Lu, JunliangZhangG. Eason, B. Noble, and I. N. Stability and Security Assessment for an

    Industrial Electric Grid with Enterprise-owned Power Plants,DRPT2008 6-9April 2008 Nanjing China 1563.[5] Hadi Saadat, Power System Analysis, Tata McGraw-Hill Publishing

    Comp. Ltd, New Delhi, Sixteenth reprint 2009.

    [6] ETAP version 7.5.0.

    13-14 May 2011 B.V.M. Engineering College, V.V.Nagar,Gujarat,India

    National Conference on Recent Trends in Engineering & Technology