Training - Control
-
Upload
islam-deif -
Category
Documents
-
view
224 -
download
0
Transcript of Training - Control
7/27/2019 Training - Control
http://slidepdf.com/reader/full/training-control 1/30
Level 1 - Fundamental Training Control
Power Point Presentation Handouts
1Phase I - Control Fundamental
Level 1
Fundamentals TrainingFundamentals Training
Level 1 - Control
2
Topics: Slide No:
• Process Control Terminology 3 - 10
• Control Principles 11 - 18
• Basic Control Loop 19 - 23
• Advance Control Loop 24 - 31
• Control Algorithm 32 - 46
• Control System 47 - 54
• Exercise 55 - 59
ContentsContents
7/27/2019 Training - Control
http://slidepdf.com/reader/full/training-control 2/30
Level 1 - Fundamental Training Control
Power Point Presentation Handouts
Level 1 - Control
3
Any operation or sequence of operations involving a
change in the substance being t reated.
Examples:
A change of energy state - hot to cold, liquid to
gas
A change of composi tion - a chemical reaction
A change of dimens ion - grinding coal
Process Control TerminologyProcess Control Terminology
What is a PROCESS ?What is a PROCESS ?
Types of PROCESS VARIABLE:Types of PROCESS VARIABLE:
Pressure Specific Gravity of liquid
Flow Density
Level Mass
Temperature ConductivityL iquid In ter face Compos it ion
Moles
Level 1 - Control
4
A combination of instruments or functions that are
interconnected to measure and control a process
variable with feedback.
Process Control TerminologyProcess Control Terminology
What is a CLOSED LOOP ?What is a CLOSED LOOP ?
PROCESSinput output
A SystemSystem
withithFeedbackeedback
FINALCONTROL
ELEMENTMEASUREMENT
CONTROLLER
7/27/2019 Training - Control
http://slidepdf.com/reader/full/training-control 3/30
Level 1 - Fundamental Training Control
Power Point Presentation Handouts
Level 1 - Control
5
• A device that registers a non-electrical parameter (eg.
process variable) and outputs a corresponding useable
electrical signal.
– Pressure to Capacitance
– Pressure to Resistance or mV
– Temperature to Resistance
– Temperature to mV
• Example:
– Capacitance pressure sensor module
– Piezo-resistive pressure sensor module – RTD
– Thermocouple
Process Control TerminologyProcess Control Terminology
What is a TRANSDUCERWhat is a TRANSDUCER
Level 1 - Control
6
• A device that will translate the transducers interpretation
of the measured variable into a standard transmission
signal.
– 3 - 15 psi pneumatic signal
– 4-20 mA dc electrical signal
– 1-5 V dc electrical signal
Process Control TerminologyProcess Control Terminology
What is a TRANSMITTERWhat is a TRANSMITTER
7/27/2019 Training - Control
http://slidepdf.com/reader/full/training-control 4/30
7/27/2019 Training - Control
http://slidepdf.com/reader/full/training-control 5/30
Level 1 - Fundamental Training Control
Power Point Presentation Handouts
Level 1 - Control
9Process Control TerminologyProcess Control Terminology
What is a SIGNAL ?What is a SIGNAL ?
• An event that conveys data from one point to another.
What is an INDICATOR ?What is an INDICATOR ?
• An instrument which visually shows the value of the variable.
What is a RECORDER ?What is a RECORDER ?
• An instrument that makes and displays a continuous graphic, acoustic
or magnetic record of a measured variable.
What is a DCS ?What is a DCS ?
• Distributed Control System consisting of functional integrated
subsystems. The subsystems are connected by a communication
linkage (eg) data bus,data highway.
Level 1 - Control
10
Process Control TerminologyProcess Control Terminology
• The last control element in the process control loop
that manipulates the process variable.
– Control Valves
» modulates flow rate
» operated by actuator
– Louvers and Dampers
» operated by pneumatic actuators – Variable Speed Drives
» operated by electronic control signals
♦ 4 - 20 mA
What is a FINAL CONTROL ELEMENT?What is a FINAL CONTROL ELEMENT?
7/27/2019 Training - Control
http://slidepdf.com/reader/full/training-control 6/30
Level 1 - Fundamental Training Control
Power Point Presentation Handouts
Level 1 - Control
11Control PrincipleControl Principle
Level 1 - Control
12
SPPV
Control PrincipleControl Principle
Control theory can be encapsulated as the matching of a
measured variable (PV) to the plant requirement (SP).
PROCESS
CORRECTING
UNIT
CONTROLLING
UNIT
MEASURING
UNIT
OPERATOR
FEED PRODUCT
Proportional band % = % = x 100%1
K Gain
100 IO
O/P
A controller implements a Control Algorithm so that an outputsignal (O/P) activates a correcting unit. The ratio of output signal
(O) to input signals (I) is Gain (K).
7/27/2019 Training - Control
http://slidepdf.com/reader/full/training-control 7/30
Level 1 - Fundamental Training Control
Power Point Presentation Handouts
Level 1 - Control
13Control PrincipleControl Principle
• Process Variable (PV) – the actual measurement of the state of the process
• Set Point (SP) – the desired state of the process variable
• Control Algorithm – the predefined response of the controller to PV-SP
• Controller Output (O/P) – a signal determined by the control algorithm
• Offset – the value of PV-SP when the system is in equilibrium
• Direct Acting Controllers – as the value of the measured variable increases, the
output of the controller increases.
• Reverse Acting Controllers – as the value of the measured variable increases, theoutput of the controller decreases.
Level 1 - Control
14
• A plant possesses inherent
regulation when, in the absence
of a controller, equilibrium is re-
established after a disturbance.
– For example, a tank with constant
inflow is in equilibrium.
– The outflow valve is then opened
a little more.
– The outflow pressure decreasesas the tank level falls unti l inflow
again equals outflow.
– Manipulation o f the outflow valve
result in different, unique
equilibrium states.
Inherent RegulationInherent Regulation
Control PrincipleControl Principle
7/27/2019 Training - Control
http://slidepdf.com/reader/full/training-control 8/30
Level 1 - Fundamental Training Control
Power Point Presentation Handouts
Level 1 - Control
15
Example Instruments
TT
FIC
TE
Temperature Transmitter
Flow Indicating Controller
Temperature Element
(Thermocouple, RTD)
I/P Current-to-Pressure
Transducer
Pressure Transmitter
Pressure-to-Pressure
Transducer
PT
P/P
Local
Mounting
Panel Front
Mounting
Panel Rear,
or Rack Mounting
Instrument Location
Instrument SymbolsInstrument Symbols
Control PrincipleControl Principle
Level 1 - Control
16
First Letter Succeeding LettersMeasured or InitiatingVariable
Modi fier Readout or PassiveFunction
OutputFunction
A Analysis AlarmC User's Choice ControlD User's Choice DifferentialF Flow Rate Ratio
(Fraction)I Current
(Electrical)Indicate
L Level Light
P Pressure,Vacuum
Point (TestConnection)
Q Quantity Integrate,Totalize
R Radiation RecordT Temperature TransmitV Vibration Valve, Damper,
Louver
Letter Designations
Instrument SymbolsInstrument Symbols
Control PrincipleControl Principle
7/27/2019 Training - Control
http://slidepdf.com/reader/full/training-control 9/30
Level 1 - Fundamental Training Control
Power Point Presentation Handouts
Level 1 - Control
17
Connection to Process,Instrument Supply,or Direct Mechanical Link
Pneumatic Signal
Electric Signal
Signal Types (ISA)Signal Types (ISA)
Control PrincipleControl Principle
Level 1 - Control
18
Control PrincipleControl Principle
• Pneumatic
• Analog
• Digital
– Single Loop Controllers
– Distributed Control System
– Fieldbus Control System
Controller TypesController Types
7/27/2019 Training - Control
http://slidepdf.com/reader/full/training-control 10/30
Level 1 - Fundamental Training Control
Power Point Presentation Handouts
Level 1 - Control
19
I/P
PT
PIC • Pressure Loop Issues: – May be a Fast Process
» Liquid
» Small Volume
– May Require Fast Equipment
Basic Control LoopBasic Control Loop
Pressure Control LoopPressure Control Loop
Level 1 - Control
20
Steam
ColdWater
HotWater
Load
Disturbance
Basic Control LoopBasic Control LoopTemperature Control LoopTemperature Control Loop
• Temperature Loop Issues: – Fluid response slowly to change in input heat
– Requires advanced control strategies
» Feedforward Control
TT
TIC
I/P
7/27/2019 Training - Control
http://slidepdf.com/reader/full/training-control 11/30
Level 1 - Fundamental Training Control
Power Point Presentation Handouts
Level 1 - Control
21
I/P FIC
TTFT
Basic Control LoopBasic Control Loop
Flow Control LoopFlow Control Loop
• Flow Loop Issues: – May be a Very Fast Process
» “Noise” in Measurement Signal
• May Require Filtering
» May Require Fast-Responding Equipment
– Typically Requires Temperature Compensation
Level 1 - Control
22
I/P LIC
LT
Basic Control LoopBasic Control LoopLevel Control Loop (Inflow)Level Control Loop (Inflow)
• Level Loop Issues: – Control At Inflow or Outflow
– Non-Self Regulating
7/27/2019 Training - Control
http://slidepdf.com/reader/full/training-control 12/30
Level 1 - Fundamental Training Control
Power Point Presentation Handouts
Level 1 - Control
23
I/PLIC
LT
Basic Control LoopBasic Control Loop
Level Control Loop (Outflow)Level Control Loop (Outflow)
Level 1 - Control
24
Advance Control Loop Advance Control Loop
Consist of one controller (primary, or master) controlling the variable
that is to be kept at a constant value, and a second controller
(secondary, or slave) controlling another variable that can cause
fluctuations in the first variable. The primary controller positions the
set point of the secondary, and it, in turn, manipulates the control
valve.
What is CASCADE CONTROL ?What is CASCADE CONTROL ?
FBC FBC
Secondary
ProcessPrimary
Process
Secondary
controller
Primary
controller
Disturbancer 1 r 2 m
c1 c2
Multi-Variable Control
7/27/2019 Training - Control
http://slidepdf.com/reader/full/training-control 13/30
Level 1 - Fundamental Training Control
Power Point Presentation Handouts
Level 1 - Control
25 Advance Control Loop Advance Control Loop
Example of CASCADE CONTROLExample of CASCADE CONTROL
The temperature of the liquid in the vessel is controlled by
regulating the steam pressure in the jacket around the vessel.
Temperature
transmitter Temperature
controller Measurement
Output
SteamValve
Jacket
IN
OUT
SINGLE-LOOP CONTROL
Pressure
transmitter
Measurement Pressure
controller
Cascade Control Loop
Level 1 - Control
26 Advance Control Loop Advance Control Loop
Temperature
Process
Steam Flow
Process
Load A
(Demand)
TIC
FT
TT
FC
Load B
(Header Pressu re)
SP RSP
_ _
I/P
TT
TIC
Steam
ColdWater
Hot
Water Condensate
Major Load A:Outflow Rate(Demand)
Major Load B:Steam Header
Pressure
Steam
Header
FT
FC
RSP
_
Implementing Cascade ControlImplementing Cascade Control
7/27/2019 Training - Control
http://slidepdf.com/reader/full/training-control 14/30
Level 1 - Fundamental Training Control
Power Point Presentation Handouts
Level 1 - Control
27
Levelindicating
controller
Flow
controller
Boiler
Feedwater FT
Applies to a system in which a balance between supply and
demand is achieved by measuring both demand potential and
demand load and using this data to govern supply. It gives a
smoother and stable control than feedback control.
Advance Control Loop Advance Control Loop
What is FEED FORWARD CONTROL ?What is FEED FORWARD CONTROL ?
FT LT
Steam
SP
PV O/P
Multi-Variable Control
Feed
forwardSP
Level 1 - Control
28 Advance Control Loop Advance Control Loop
I/P
TT
FeedforwardLoop
TIC
Steam
ColdWater
HotWater
FT
FFD
FeedforwardEquations
SummingJunction
FeedbackLoop
ImplementingImplementing FeedforwardFeedforward ControlControl
7/27/2019 Training - Control
http://slidepdf.com/reader/full/training-control 15/30
Level 1 - Fundamental Training Control
Power Point Presentation Handouts
Level 1 - Control
29
An uncontrolled flow determines a second flow so that a desired ratio
is maintained between them.
The ratio factor is set by a ratio relay or multiplying unit which would be
located between the wild flow transmitter and the flow controller set
point. Flow B is controlled in a preset ratio to flow A.
Advance Control Loop Advance Control Loop
What is RATIO CONTROL ?What is RATIO CONTROL ?
Ratio
relayWild
flow, A
Controlled
flow, B
Remote -
set
controller
Output = A x ratio
SP
Output
Wild flow, A
Controlled
flow, B
Ratio
controller
Output
Multi-Variable Control
SP
Level 1 - Control
30
Advance Control Loop Advance Control Loop
Example of RATIO CONTROLExample of RATIO CONTROL
Other Application : Fuel/air ratio control system on
combustion equipment, e.g. boilers.
Acidsupply
Magneticflowmeter
Pickle tank
Flowtransmitter
FT FC
Control valve
Flow BFlow AWater
Manualwater regulator
MeasurementSet
√
Pickling Process
7/27/2019 Training - Control
http://slidepdf.com/reader/full/training-control 16/30
Level 1 - Fundamental Training Control
Power Point Presentation Handouts
Level 1 - Control
31
O/P
The more important condition between two or more candidates is
selected. They are used mainly to provide protection to a piece of
equipment which could suffer damage as a result of abnormal
operating conditions.
Advance Control Loop Advance Control Loop
What is SELECTIVE CONTROL ?What is SELECTIVE CONTROL ?
Speed
ControlPIC
PIC
RS
Low select
PV
Pump
O/PO/P
PV
Multi-Variable Control
Level 1 - Control
32
Control AlgorithmControl Algorithm
•• On/Off On/Off
•• MultiMulti--stepstep
•• ProportionalProportional
•• IntegralIntegral
•• DerivativeDerivative
7/27/2019 Training - Control
http://slidepdf.com/reader/full/training-control 17/30
Level 1 - Fundamental Training Control
Power Point Presentation Handouts
Level 1 - Control
33Control AlgorithmControl Algorithm
It is a two-position control, merely a switch arranged to be off
(or on as required) when the error is positive and on (or off as
required) when the error is negative. Ex.. Oven & Alarm control.
OnOn--Off Contro lOff Control
differentialMeasured
variable
Controller
output
Time
Level 1 - Control
34
A controller action that may initiate more than two positioning of
the control valve with respect to the respective predetermined
input values.
Control AlgorithmControl Algorithm
MultiMulti--Step ActionStep Action
Multi-step actionTime
Time
V a l v e
p o s i t i o n
I n p u t
1234
7
5
8
0
8
5
7/27/2019 Training - Control
http://slidepdf.com/reader/full/training-control 18/30
Level 1 - Fundamental Training Control
Power Point Presentation Handouts
Level 1 - Control
35
It is the basis for the 3-mode controller. The controller output (O/P)
is proportional to the difference between Process Variable (PV)
and the Set Point (SP).
Control AlgorithmControl Algorithm
Proportional Action (P)Proportional Action (P)
Process
Load
Controller
Output
SP
PV
Open-loop response of proportional mode
Level 1 - Control
36
Control AlgorithmControl Algorithm
Proportional Action (P)Proportional Action (P)
When a disturbance alters the process away from the set-point, the
controller acts to restore initial conditions. In equilibrium, offset (PV-
SP = constant) results.
The Algorithm is :
O/P- (PV - SP)
ProportionalBand
Constant= +
S - PV
O/P %100
(Constant is normally 50% )
50θ
Tan θ = Gain = 100 / Proportional Band
Time
SP
Time
Recovery timeOffset
Many controllers have a ‘manual
reset’. This enables the operators
to manipulate the ‘constant’ term
of the algorithm to eliminate offset.
PV
7/27/2019 Training - Control
http://slidepdf.com/reader/full/training-control 19/30
Level 1 - Fundamental Training Control
Power Point Presentation Handouts
Level 1 - Control
37Control AlgorithmControl Algorithm
0 1 2 3 4 5 6 7 8 9
Time
100
90
80
70
60
50
40
30
20
10
%
SP
PV
Output
E1E0 E2 E3 E4
prop
Low Proport ional Gain: (Closed Loop)Low Proport ional Gain: (Closed Loop)
Level 1 - Control
38Control AlgorithmControl Algorithm
0 1 2 3 4 5 6 7 8 9
Time
100
90
80
70
60
50
40
30
20
10
%
SP
PV
Output
High Proportional Gain: (Closed Loop)High Proportional Gain: (Closed Loop)
7/27/2019 Training - Control
http://slidepdf.com/reader/full/training-control 20/30
Level 1 - Fundamental Training Control
Power Point Presentation Handouts
Level 1 - Control
39
Whilst PV ≠ SP, the controller operates to restore equality. As long as the measurement remains at the set point, there is no
change in the output due to the integral mode in the controller.
The output of the controller changes at a rate proportional to the offset.
The integral time gives indication of the strength of this action. It is the
time taken for integral action to counter the ‘offset’ induced by
Proportional Action alone.
Control AlgorithmControl Algorithm
Integral Action (I)Integral Action (I)
Time
Set
Point
%
Measurement
% OutputTime
Set
Point
a=b
RT
RT = Reset Time min./rpta {
b {
Integral mode Proportional plus Integral mode
Open-loopresponse
Level 1 - Control
40Control AlgorithmControl Algorithm
0 1 2 3 4 5 6 7 8 9
Time
100
90
80
70
60
50
40
30
20
10
%
SP
PV
Proportional
Plus Integral
Output
Proportional
Response
Integral Act ion: (Closed Loop)Integral Action: (Closed Loop)
7/27/2019 Training - Control
http://slidepdf.com/reader/full/training-control 21/30
Level 1 - Fundamental Training Control
Power Point Presentation Handouts
Level 1 - Control
41
As the PV changes, the controller resists the change.
The controllers output is proportional to the rate at which the
difference between the measured and desired value changes.
The derivative time is an indication of this action. It is the time that
the open-loop P+D response is ahead of the response due to P only.
Control AlgorithmControl Algorithm
Derivative Action (D)Derivative Action (D)
Time
Set
Point
%
Measurement
% Output
(I/D)
Derivative mode
Time
Set
Point
DT
DT = Derivative Time (min)
Proportional plus Derivative mode
Open-loopresponseProportional + Derivative
Proportional only
Level 1 - Control
42
0 1 2 3 4 5 6 7 8 9Time
100
90
80
70
60
50
40
30
20
10
%
SP
PV PID Output
Control AlgorithmControl AlgorithmPID Action: (Closed Loop)PID Action: (Closed Loop)
7/27/2019 Training - Control
http://slidepdf.com/reader/full/training-control 22/30
Level 1 - Fundamental Training Control
Power Point Presentation Handouts
Level 1 - Control
43Control AlgorithmControl Algorithm
PID ControlPID Control
A
B
80
60
40
20 % S
c a l e R a n g e
C o n t r o l l e r O u t p u t
o r
V a l v e P o s i t i o n
Measurement
Proportional
Time - minutes
Open-loop response of three-mode controller
Proportional + Integral +
Derivative
Proportional +
Integral
Level 1 - Control
44
I/P
PT
PIC
P
Control AlgorithmControl Algorithm
P & ID Piping & Instrumentation DrawingP & ID Piping & Instrumentation Drawing
Process Vessel
Fluid Pump
Pneumatic
Control
Valve
Compressed Air Pipe
Converter PID
Controller
Pressure
Transmitter
7/27/2019 Training - Control
http://slidepdf.com/reader/full/training-control 23/30
Level 1 - Fundamental Training Control
Power Point Presentation Handouts
Level 1 - Control
45Control AlgorithmControl Algorithm
Controller SelectionController Selection
Can offset be
tolerated ?
Start
Use
P-only
Yes
Use
P+I
Yes
No
Is dead time
excessive ?
No
Use
PID
Yes
Is noise
present ?
No Reaction curve
of measured
variable
CapacityDead Time
C
63.2
%
Time (sec)
Step change in
valve travel
Level 1 - Control
46
Control AlgorithmControl Algorithm
Controller AdjustmentController Adjustment
Time
C o n t r o l l e d V a r i a b l e
Period
P-only
PID
PI
Control loop Proportional band Time constant Derivative
Flow High (250%) Fast (1 to 15 sec) Never
Level Low Capacity dependent Rarely
Temperature Low Capacity dependent Usually
Analytical High Usually slow Sometimes
Pressure Low Usually fast Sometimes
7/27/2019 Training - Control
http://slidepdf.com/reader/full/training-control 24/30
Level 1 - Fundamental Training Control
Power Point Presentation Handouts
Level 1 - Control
47
An automatic control scheme in which the controller is programmed
to evaluate its own effectiveness and modify its own control
parameters to respond to dynamic conditions occurring in or to the
process which affect the controlled variables.
Control SystemControl System
Adaptive Control Adaptive Control
Ex) Digital Controller
- Sensors are run to the computer’s input.
- Servomechanisms are connected to the computer’s output.
- Future changes don’t require re-wiring.
- Changing control functions (P,I, and D) and configurations
(between cascade mode and feedforward mode) will be
made on the computer’s program and not necessarily to anyhardware.
Level 1 - Control
48
Control SystemControl System
A control strategy where the process control computer performs
system control calculations and provides its output to the setpoints
inputs of conventional analog controllers. These analog controllers
actually control the process actuators, not the main-control
computer.
Supervisory ControlSupervisory Control
M.I.SSupervisory
Control
A
S
Controller
S
AController
S
AController
⇒SP1
⇒SP2
⇒SP3
7/27/2019 Training - Control
http://slidepdf.com/reader/full/training-control 25/30
Level 1 - Fundamental Training Control
Power Point Presentation Handouts
Level 1 - Control
49
Measurement
HW andSoftware
Filtering
I/O Rack
Coax
Controller Tools for Process
Anal ysi s, Diagnosti cs.
Sampled
Value
Tools for Process Anal ysi s, Diagnosti cs.
Controller I/O Rack
Control SystemControl System
Today’s DCS SystemToday’s DCS System
Level 1 - Control
50Control SystemControl System
Definition...
Control room
operator stations
Control systems
(DCS or PLC)
A digital, two-way, multi-drop communication link amongintelligent field devices and automation systems.
Fieldbus (Only Digital Signals)
What is a FIELDBUS ?What is a FIELDBUS ?
P
T
L
F
7/27/2019 Training - Control
http://slidepdf.com/reader/full/training-control 26/30
Level 1 - Fundamental Training Control
Power Point Presentation Handouts
Level 1 - Control
51
Gateway HSE
H1
H1
H1
H1
BridgeH2
H1
H1
124
Devices
Work
Systems
H1 - 31.25 Kbit/sHSE - 100 M bit/s
(Fast Ethernet)
(due to address limits) .
Total of approximately 35,000 devices
FieldbusFieldbus Control SystemControl System
Controller
32 Devices
32
Devices
Control SystemControl System
Level 1 - Control
52Control SystemControl System
AI AI
PIDPID
AI AI AO AO
PIDPID
DCS
4 -20 mA 4 -20 mA 4 -20 mA
ADVANCED CONTROL OPTIMIZATION
•• Control in the control roomControl in the control room
Proprietary BusProprietary Bus
7/27/2019 Training - Control
http://slidepdf.com/reader/full/training-control 27/30
Level 1 - Fundamental Training Control
Power Point Presentation Handouts
Level 1 - Control
53
PIDIN
OUT
BKCAL_INFIELDVUE
AO
BKCAL_OUT
CAS_IN
AIOUT
Delta V
Valve
Transmitter
Control SystemControl System
ControlControl
AnywhereAnywhere
Built Built-- In In
FunctionFunction
BlocksBlocks
FoundationFoundation FieldbusFieldbus DevicesDevices
•• Control in the field withControl in the field with fieldbusfieldbus
Level 1 - Control
54
FCS
Loop 1 Loop 2
Digital
PIDPID
DCS
Loop 1 Loop 2
Digital
PID
Anal og
DDC
Anal og
PID
Loop 1 Loop 2
Central
Control Loop
Local Control
Loop
Control in
the field
Control in the
device itself
Look at how the CONTROL migrateLook at how the CONTROL migrate
7/27/2019 Training - Control
http://slidepdf.com/reader/full/training-control 28/30
Level 1 - Fundamental Training Control
Power Point Presentation Handouts
Level 1 - Control
55ExerciseExercise
Which defined term is closest to the description or encompasses the
example given?
A. Controller F. Primary element
B. Converter G. Signal
C. Instrument H. Transducer
D. Point of measurement I. Transmitter
E. Process
1. Process temperature increases the measurable
resistance in a monitored electrical circuit. [ ]
2. Pulsed output from a turbine meter. [ ]
3. Heat-injected plastic molding. [ ]
Level 1 - Control
56
ExerciseExercise
4. Temperature transmitter. [ ]
5. Device which adjusts the measured value of the
process to the requirements of the operator. [ ]
6. Element, flow transmitter, controller and correcting unit. [ ]
7. A pipe piece is tapped for a sample fluid. [ ]
8. A device changes an industry standard pneumaticsignal to an industry standard hydraulic signal. [ ]
7/27/2019 Training - Control
http://slidepdf.com/reader/full/training-control 29/30
Level 1 - Fundamental Training Control
Power Point Presentation Handouts
Level 1 - Control
57ExerciseExercise
9. Identify the components indicated by the Arrows.
Level 1 - Control
58
ExerciseExercise
Which defined term is closest to the description or encompasses theexample given.
A. Cascade control F. GainB. Control algorithm G. OffsetC. Control valve H. Proprietary BusD. Feed-forward control I. Smart DeviceE. Foundation Fieldbus
10. The predefined response of the controller to PV-SP. [ ]
11. The value of PV-SP when the system is in equilibrium. [ ]
12. The ratio of controller’s output to input. [ ]
13. It is a final control element operated by an actuator. [ ]
7/27/2019 Training - Control
http://slidepdf.com/reader/full/training-control 30/30
Level 1 - Fundamental Training Control
Level 1 - Control
59ExerciseExercise
14. Involves master & slave controllers. [ ]
15. The output of the loop drives the input. [ ]
16. A digital communication based control networkwith control action in the controller only. [ ]
17. A digital communication based control network thatallow control in the field. [ ]
18. A device that provide both analog & communicationsignal in its loop wire pair. [ ]