Trainee Report Ntpc[1]

download Trainee Report Ntpc[1]

of 38

Transcript of Trainee Report Ntpc[1]

  • 8/6/2019 Trainee Report Ntpc[1]

    1/38

    PROJECT REPORT ( N.T.P.C. BADARPUR, NEW DELHI )INDUSTRIAL TRAINING REPORT

    (SUBMITTED IN PARTIAL FULFILLMENT OF THE REQUIRMENT OF THE

    COURSE OF B.TECH.)

    UNDERTAKEN ATN.T.P.C. BADARPUR, NEW DELHI

    FROM:13th JUNE to 23 JULY 2011

    SUBMITTED BY:navneet kumarN.T.P.C. Badarpur

  • 8/6/2019 Trainee Report Ntpc[1]

    2/38

    B.Tech 3rd YearElectrical Engineeringjiet jodhpur

    Acknowledgement

    With profound respect and gratitude, I take the opportunity to convey my thanks to

    complete the training here.

    I do extend my heartfelt thanks to Mr Manmohan Singh Singh for providing me

    this opportunity to be a part of this esteemed organization.

    I am extremely grateful to all the technical staff of BTPS/NTPC for their co-

    operation and guidance that helped me a lot during the course of training. I have

    learnt a lot working under them and I will always be indebted of them for this value

    addition in me.

    I would also like to thank the HOD of RIMT IET and all the faculty member of

    Electrical department for their effort of constant co-operation. Which have beensignificant factor in the accomplishment of my industrial training.

  • 8/6/2019 Trainee Report Ntpc[1]

    3/38

    CONTENT

    1. Introduction to the Company

    2. Project Report

    b. EMD I

    i. Electrical Motorii. Switchgear

    c. EMD II

    i. Generatorii. Protectioniii. Transformer

  • 8/6/2019 Trainee Report Ntpc[1]

    4/38

    Introduction to theCompanyNTPC, the largest power Company in India, was setup in 1975 to accelerate power

    development in the country. It is among the worlds largest and most efficient power

    generation companies. In Forbes list of Worlds 2000 Largest Companies for the

    year 2007, NTPC occupies 411th place.

    NTPC has installed capacity of 29,394 MW. It has 15 coal based power stations

    (23,395 MW), 7 gas based power stations (3,955 MW) and 4 power stations in Joint

    Ventures (1,794 MW). The company has power generating facilities in all major

    regions of the country. It plans to be a 75,000 MW company by 2017.

    NTPC has gone beyond the thermal power generation. It has diversified into hydro

    power, coal mining, power equipment manufacturing, oil & gas exploration, power

    trading & distribution. NTPC is now in the entire power value chain and is poised

    to become an Integrated Power Major.NTPC's share on 31 Mar 2008 in the total installed capacity of the country was

    19.1% and it contributed 28.50% of the total power generation of the country

    during 2007-08. NTPC has set

    new benchmarks for the power industry both in the area of power plant

    construction and

    operations.

  • 8/6/2019 Trainee Report Ntpc[1]

    5/38

    In November 2004, NTPC came out with its Initial Public Offering (IPO) consisting of 5.25% as

    fresh issue and 5.25% as offer for sale by Government of India. NTPC thus became a listed

    company with Government holding 89.5% of the equity share capital and rest held by

    Institutional Investors and Public. The issue was a resounding success. NTPC is among the

    largest five companies in India in terms of market capitalization.

    Recognizing its excellent performance and vast potential, Government of the India has

    identified NTPC as one of the jewels of Public Sector 'Navratnas'- a potential global giant.

    Inspired by its glorious past and vibrant present, NTPC is well on its way to realize its vision of

    being "A world class integrated power major, powering India's growth, with increasing global

    presence".

  • 8/6/2019 Trainee Report Ntpc[1]

    6/38

    Environment Management

    All stations of NTPC are ISO 14001 certified

    Various groups to care of environmental issues

    The Environment Management Grou

    Ash Utilization Division

    Afforestation Group

    Centre for Power Efficiency & Environment Protection

    Group on Clean Development Mechanism

    N TPC is the second largest owner of trees in the country after the Forest department

  • 8/6/2019 Trainee Report Ntpc[1]

    7/38

    THERMAL POWER PLANT

    A Thermal Power Station comprises all of the equipment and a

    subsystem required to produce electricity by using a steam generating

    boiler fired with fossil fuels or befouls to drive an electrical generator.

    Some prefer to use the term ENERGY CENTER because such facilities

    convert forms of energy, like nuclear energy, gravitational potential

    energy or heat energy (derived from the combustion of fuel) into

    electrical energy. However, POWER PLANT is the most common term in

    the united state; While POWER STATION prevails in many

    Commonwealth countries and especially in the United Kingdom.

    Such power stations are most usually constructed on a very large scale

    and designed for continuous operation.

    Typical diagram of a coal fired thermal power station

    1. Cooling water pump

    2. Three-phase transmission line

    3. Step up transformer

    4. Electrical Generator

    5. Low pressure steam

    6. Boiler feed water pump

    7. Surface condenser

    8. Intermediate pressure steam turbine

    9. Steam control valve

    10. High pressure steam turbine

    11. Deaerator Feed water heater

    12. Coal conveyor

    13. Coal hopper

    14. Coal pulverizer

    15. boiler steam drum

    16. Bottom ash hoper

    17. Super heater

    18. Forced draught(draft) fan

    19. Reheater

    20. Combustion air intake

    21. Economizer

    22. Air preheater

    23. Precipitator

  • 8/6/2019 Trainee Report Ntpc[1]

    8/38

    24. Induced draught(draft) fan

    25. Fuel gas stack

    The description of some of the components written above is described

    as follows:

    1. Cooling towers

    Cooling Towers are evaporative coolers used for cooling water or other

    working medium to near the ambivalent web-bulb air temperature.

    Cooling tower use evaporation of water to reject heat from processes

    such as cooling the circulating water used in oil refineries, Chemical

    plants, power plants and building cooling, for example. The tower vary

    in size from small roof-top units to very large hyperboloid structures

    that can be up to 200 meters tall and 100 meters in diameter, or

    rectangular structure that can be over 40 meters tall and 80 meters

    long. Smaller towers are normally factory built, while larger ones are

    constructed on site.

    The primary use of large , industrial cooling tower system is to remove

    the heat absorbed in the circulating cooling water systems used in

    power plants , petroleum refineries, petrochemical and chemical plants,

    natural gas processing plants and other industrial facilities . The

    absorbed heat is rejected to the atmosphere by the evaporation of

    some of the cooling water in mechanical forced-draft or induced draft

    towers or in natural draft hyperbolic shaped cooling towers as seen at

    most nuclear power plants.

    2.Three phase transmission line

    Three phase electric power is a common method of electric power

    transmission. It is a type of polyphase system mainly used to power

    motors and many other devices. A Three phase system uses less

    conductor material to transmit electric power than equivalent singlephase, two phase, or direct current system at the same voltage. In a

    three phase system, three circuits reach their instantaneous peak

    values at different times. Taking one conductor as the reference, the

    other two current are delayed in time by one-third and two-third of one

    cycle of the electrical current. This delay between phases has the

  • 8/6/2019 Trainee Report Ntpc[1]

    9/38

    effect of giving constant power transfer over each cycle of the current

    and also makes it possible to produce a rotating magnetic field in an

    electric motor.

    At the power station, an electric generator converts mechanical power

    into a set of electric currents, one from each electromagnetic coil or

    winding of the generator. The current are sinusoidal functions of time,

    all at the same frequency but offset in time to give different phases. In

    a three phase system the phases are spaced equally, giving a phase

    separation of one-third one cycle. Generators output at a voltage that

    ranges from hundreds of volts to 30,000 volts. At the power station,

    transformers: step-up this voltage to one more suitable for

    transmission.

    After numerous further conversions in the transmission and distribution

    network the power is finally transformed to the standard mains voltage

    (i.e. the household voltage).

    The power may already have been split into single phase at this point or

    it may still be three phase. Where the step-down is 3 phase, the output

    of this transformer is usually star connected with the standard mains

    voltage being the phase-neutral voltage. Another system commonly

    seen in North America is to have a delta connected secondary with a

    center tap on one of the windings supplying the ground and neutral.

    This allows for 240 V three phase as well as three different single phase

    voltages( 120 V between two of the phases and neutral , 208 V between

    the third phase ( known as a wild leg) and neutral and 240 V between

    any two phase) to be available from the same supply.

    3.Electrical generator

    An Electrical generator is a device that converts kinetic energy to

    electrical energy, generally using electromagnetic induction. The task

    of converting the electrical energy into mechanical energy is

    accomplished by using a motor. The source of mechanical energy may

    be a reciprocating or turbine steam engine, , water falling through theturbine are made in a variety of sizes ranging from small 1 hp (0.75 kW)

    units (rare) used as mechanical drives for pumps, compressors and

    other shaft driven equipment , to 2,000,000 hp(1,500,000 kW) turbines

    used to generate electricity. There are several classifications for

    modern steam turbines.

  • 8/6/2019 Trainee Report Ntpc[1]

    10/38

    Steam turbines are used in all of our major coal fired power stations to

    drive the generators or alternators, which produce electricity. The

    turbines themselves are driven by steam generated in Boilers or

    steam generators as they are sometimes called.

    Electrical power station use large stem turbines driving electric

    generators to produce most (about 86%) of the worlds electricity.

    These centralized stations are of two types: fossil fuel power plants and

    nuclear power plants. The turbines used for electric power generation

    are most often directly coupled to their-generators .As the generators

    must rotate at constant synchronous speeds according to the frequency

    of the electric power system, the most common speeds are 3000 r/min

    for 50 Hz systems, and 3600 r/min for 60 Hz systems. Most large nuclear

    sets rotate at half those speeds, and have a 4-pole generator rather

    than the more common 2-pole one.

    Energy in the steam after it leaves the boiler is converted into

    rotational energy as it passes through the turbine. The turbine normally

    consists of several stage with each stages consisting of a stationary

    blade (or nozzle) and a rotating blade. Stationary blades convert the

    potential energy of the steam into kinetic energy into forces, caused by

    pressure drop, which results in the rotation of the turbine shaft. The

    turbine shaft is connected to a generator, which produces the electrical

    energy.

    4.Boiler feed water pump

    A Boiler feed water pump is a specific type of pump used to pump water

    into a steam boiler. The water may be freshly supplied or retuning

    condensation of the steam produced by the boiler. These pumps are

    normally high pressure units that use suction from a condensate return

    system and can be of the centrifugal pump type or positive

    displacement type.

    Construction and operation

    Feed water pumps range in size up to many horsepower and the electric

    motor is usually separated from the pump body by some form of

    mechanical coupling. Large industrial condensate pumps may also serve

    as the feed water pump. In either case, to force the water into the

  • 8/6/2019 Trainee Report Ntpc[1]

    11/38

  • 8/6/2019 Trainee Report Ntpc[1]

    12/38

    6. Control valves

    Control valves are valves used within industrial plants and elsewhere to

    control operating conditions such as temperature,pressure,flow,and

    liquid Level by fully partially opening or closing in response to signals

    received from controllers that compares a set point to a process

    variable whose value is provided by sensors that monitor changes in

    such conditions. The opening or closing of control valves is done by

    means of electrical, hydraulic or pneumatic systems

    7. Deaerator

    A Dearator is a device for air removal and used to remove dissolved

    gases (an alternate would be the use of water treatment chemicals)

    from boiler feed water to make it non-corrosive. A dearator typically

    includes a vertical domed deaeration section as the deaeration boiler

    feed water tank. A Steam generating boiler requires that the circulating

    steam, condensate, and feed water should be devoid of dissolved gases,

    particularly corrosive ones and dissolved or suspended solids. The

    gases will give rise to corrosion of the metal. The solids will deposit on

    the heating surfaces giving rise to localized heating and tube ruptures

    due to overheating. Under some conditions it may give to stress

    corrosion cracking.

    Deaerator level and pressure must be controlled by adjusting control

    valves- the level by regulating condensate flow and the pressure by

    regulating steam flow. If operated properly, most deaerator vendors

    will guarantee that oxygen in the deaerated water will not exceed 7 ppb

    by weight (0.005 cm3/L)

    8. Feed water heater

    A Feed water heater is a power plant component used to pre-heat water

    delivered to a steam generating boiler. Preheating the feed waterreduces the irreversible involved in steam generation and therefore

    improves the thermodynamic efficiency of the system.[4] This reduces

    plant operating costs and also helps to avoid thermal shock to the

    boiler metal when the feed water is introduces back into the steam

    cycle.

  • 8/6/2019 Trainee Report Ntpc[1]

    13/38

    In a steam power (usually modeled as a modified Ranking cycle), feed

    water heaters allow the feed water to be brought up to the saturation

    temperature very gradually. This minimizes the inevitable

    irreversibilitys associated with heat transfer to the working fluid

    (water). A belt conveyor consists of two pulleys, with a continuous loop

    of material- the conveyor Belt that rotates about them. The pulleys

    are powered, moving the belt and the material on the belt forward.

    Conveyor belts are extensively used to transport industrial and

    agricultural material, such as grain, coal, ores etc.

    9. Pulverizer

    A pulverizer is a device for grinding coal for combustion in a furnace in

    a fossil fuel power plant.

    10. Boiler Steam Drum

    Steam Drums are a regular feature of water tube boilers. It is reservoir

    of water/steam at the top end of the water tubes in the water-tube

    boiler. They store the steam generated in the water tubes and act as a

    phase separator for the steam/water mixture. The difference in

    densities between hot and cold water helps in the accumulation of the

    hotter-water/and saturated steam into steam drum. Made from high-

    grade steel (probably stainless) and its working involves temperatures

    390C and pressure well above 350psi (2.4MPa). The separated steam is

    drawn out from the top section of the drum. Saturated steam is drawn

    off the top of the drum. The steam will re-enter the furnace in through a

    super heater, while the saturated water at the bottom of steam drum

    flows down to the mud-drum /feed water drum by down comer tubes

    accessories include a safety valve, water level indicator and fuse plug.

    A steam drum is used in the company of a mud-drum/feed water drum

    which is located at a lower level. So that it acts as a sump for thesludge or sediments which have a tendency to the bottom.

    11. Super Heater

    A Super heater is a device in a steam engine that heats the steam

  • 8/6/2019 Trainee Report Ntpc[1]

    14/38

    generated by the boiler again increasing its thermal energy and

    decreasing the likelihood that it will condense inside the engine. Super

    heaters increase the efficiency of the steam engine, and were widely

    adopted. Steam which has been superheated is logically known as

    superheated steam; non-superheated steam is called saturated steam

    or wet steam; Super heaters were applied to steam locomotives in

    quantity from the early 20th century, to most steam vehicles, and so

    stationary steam engines including power stations.

    12. Economizers

    Economizer, or in the UK economizer, are mechanical devices intended

    to reduce energy consumption, or to perform another useful function

    like preheating a fluid. The term economizer is used for other purposes

    as well. Boiler, power plant, and heating, ventilating and air

    conditioning. In boilers, economizer are heat exchange devices that

    heat fluids , usually water, up to but not normally beyond the boiling

    point of the fluid. Economizers are so named because they can make

    use of the enthalpy and improving the boilers efficiency. They are a

    device fitted to a boiler which saves energy by using the exhaust gases

    from the boiler to preheat the cold water used the fill it (the feed

    water). Modern day boilers, such as those in cold fired power stations,

    are still fitted with economizer which is decedents of Greens original

    design. In this context they are turbines before it is pumped to the

    boilers. A common application of economizer is steam power plants is to

    capture the waste hit from boiler stack gases (flue gas) and transfer

    thus it to the boiler feed water thus lowering the needed energy input ,

    in turn reducing the firing rates to accomplish the rated boiler output .

    Economizer lower stack temperatures which may cause condensation of

    acidic combustion gases and serious equipment corrosion damage if

    care is not taken in their design and material selection.

    13. Air Preheater

    Air preheater is a general term to describe any device designed to heat

    air before another process (for example, combustion in a boiler). The

    purpose of the air preheater is to recover the heat from the boiler flue

    gas which increases the thermal efficiency of the boiler by reducing the

  • 8/6/2019 Trainee Report Ntpc[1]

    15/38

    useful heat lost in the fuel gas. As a consequence, the flue gases are

    also sent to the flue gas stack (or chimney) at a lower temperature

    allowing simplified design of the ducting and the flue gas stack. It also

    allows control over the temperature of gases leaving the stack.

    14. Precipitator

    An Electrostatic precipitator (ESP) or electrostatic air cleaner is a

    particulate device that removes particles from a flowing gas (such As

    air) using the force of an induced electrostatic charge. Electrostatic

    precipitators are highly efficient filtration devices, and can easily

    remove fine particulate matter such as dust and smoke from the air

    steam.

    ESPs continue to be excellent devices for control of many industrial

    particulate emissions, including smoke from electricity-generating

    utilities (coal and oil fired), salt cake collection from black liquor boilers

    in pump mills, and catalyst collection from fluidized bed catalytic

    crackers from several hundred thousand ACFM in the largest coal-fired

    boiler application.

    The original parallel plate-Weighted wire design (described above) has

    evolved as more efficient ( and robust) discharge electrode designs

    were developed, today focusing on rigid discharge electrodes to which

    many sharpened spikes are attached , maximizing corona production.

    Transformer rectifier systems apply voltages of 50-100 Kilovolts at

    relatively high current densities. Modern controls minimize sparking

    and prevent arcing, avoiding damage to the components. Automatic

    rapping systems and hopper evacuation systems remove the collected

    particulate matter while on line allowing ESPs to stay in operation for

    years at a time.

    15. Fuel gas stack

    A Fuel gas stack is a type of chimney, a vertical pipe, channel or similar

    structure through which combustion product gases called fuel gases are

    exhausted to the outside air. Fuel gases are produced when coal, oil,

    natural gas, wood or any other large combustion device. Fuel gas is

  • 8/6/2019 Trainee Report Ntpc[1]

    16/38

    usually composed of carbon dioxide (CO2) and water vapor as well as

    nitrogen and excess oxygen remaining from the intake combustion air.

    It also contains a small percentage of pollutants such as particulates

    matter, carbon mono oxide, nitrogen oxides and sulfur oxides. The flue

    gas stacks are often quite tall, up to 400 meters (1300 feet) or more, so

    as to disperse the exhaust pollutants over a greater aria and thereby

    reduce the concentration of the pollutants to the levels required by

    governmental environmental policies and regulations.

    When the fuel gases exhausted from stoves, ovens, fireplaces or other

    small sources within residential abodes, restaurants , hotels or other

    stacks are referred to as chimneys.

  • 8/6/2019 Trainee Report Ntpc[1]

    17/38

  • 8/6/2019 Trainee Report Ntpc[1]

    18/38

    ELECTRIC MOTORSAn electric motor uses electrical energy to produce mechanical energy. The reverse process

    that of using mechanical energy to produce electrical energy is accomplished by a generator or

    dynamo. Traction motors used on locomotives and some electric and hybrid automobiles often

    performs both tasks if the vehicle is equipped with dynamic brakes.

    Categorization of Electrical Motors

    The classic division of electric motors has been that of Direct Current (DC) types vs Alternating

    Current (AC) types. The ongoing trend toward electronic control further muddles the

    distinction, as modern drivers have moved the commutator out of the motor shell. For this new

    breed of motor, driver circuits are relied upon to generate sinusoidal AC drive currents, or

    some approximation of. The two best examples are: the brushless DC motor and the stepping

    motor, both being polyphase AC motors requiring external electronic control.

    There is a clearer distinction between a synchronous motor and asynchronous types. In the

    synchronous types, the rotor rotates in synchrony with the oscillating field or current (eg.

    permanent magnet motors). In contrast, an asynchronous motor is designed to slip; the most

    ubiquitous example being the common AC induction motor which must slip in order to

    generate torque.

  • 8/6/2019 Trainee Report Ntpc[1]

    19/38

  • 8/6/2019 Trainee Report Ntpc[1]

    20/38

    Induction Motor

    An electric motor converts electrical power to mechanical power in its rotor

    (rotating part). There are several ways to supply power to the rotor. In a DC motor

    this power is supplied to the armature directly from a DC source, while in an AC

    motor this power is induced in the rotating device. An induction motor is sometimes

    called a rotating transformer because the stator (stationary part) is essentially the

    primary side of the transformer and the rotor (rotating part) is the secondary side.Induction motors are widely used, especially polyphase induction motors, which are

    frequently used in industrial drives.

    Induction motors are now the preferred choice for industrial motors due to their

    rugged construction, lack of brushes (which are needed in most DC Motors) and

    thanks to modern power electronics the ability to control the speed of the motor.

    Construction

  • 8/6/2019 Trainee Report Ntpc[1]

    21/38

    The stator consists of wound 'poles' that carry the supply current that induces a

    magnetic field in the conductor. The number of 'poles' can vary between motor

    types but the poles are always in pairs (i.e. 2, 4, 6 etc). There are two types of rotor:

    1. Squirrel-cage rotor

    2. Slip ring rotor

    The most common rotor is a squirrel-cage rotor. It is made up of bars of either solid

    copper (most common) or aluminum that span the length of the rotor, and are

    connected through a ring at each end. The rotor bars in squirrel-cage induction

    motors are not straight, but have some skew to reduce noise and harmonics.

    The motor's phase type is one of two types:

    1. Single-phase induction motor

    2. 3-phase induction motor

    Principle of Operation

    The basic difference between an induction motor and a synchronous AC motor is

    that in the latter a current is supplied onto the rotor. This then creates a magnetic

    field which, through magnetic interaction, links to the rotating magnetic field in the

    stator which in turn causes the rotor to turn. It is called synchronous because at

    steady state the speed of the rotor is the same as the speed of the rotating magnetic

    field in the stator.

    By way of contrast, the induction motor does not have any direct supply onto the

    rotor; instead, a secondary current is induced in the rotor. To achieve this, stator

    windings are arranged around the rotor so that when energised with a polyphase

    supply they create a rotating magnetic field pattern which sweeps past the rotor.

    This changing magnetic field pattern can induce currents in the rotor conductors.

    These currents interact with the rotating magnetic field created by the stator and

    the rotor will turn.

    However, for these currents to be induced, the speed of the physical rotor and the

    speed of the rotating magnetic field in the stator must be different, or else the

    magnetic field will not be moving relative to the rotor conductors and no currents

    will be induced. If by some chance this happens, the rotor typically slows slightly

    until a current is re-induced and then the rotor continues as before. This difference

    between the speed of the rotor and speed of the rotating magnetic field in the stator

    is called slip. It has no unit and the ratio between the relative speed of the magnetic

    field as seen by the rotor to the speed of the rotating field. Due to this an induction

    motor is sometimes referred to as an asynchronous machine.

    Types:

    Based on type of phase supply

    1. three phase induction motor (self starting in nature)

    2. single phase induction motor (not self starting)

    Other

    1. Squirrel cage induction motor

    2. Slip ring induction motor

  • 8/6/2019 Trainee Report Ntpc[1]

    22/38

    SWITCHGEARThe term switchgear, used in association with the electric power system, or grid, refers to the

    combination of electrical disconnects, fuses and/or circuit breakers used to isolate electrical

    equipment. Switchgear is used both to de-energize equipment to allow work to be done and toclear faults downstream.

    The very earliest central power stations used simple open knife switches, mounted on

    insulating panels of marble or asbestos. Power levels and voltages rapidly escalated, making

    open manually-operated switches too dangerous to use for anything other than isolation of a

    de- energized circuit. Oil-filled equipment allowed arc energy to be contained and safely

    controlled. By the early 20th century, a switchgear line-up would be a metal-enclosed structure

    with electrically-operated switching elements, using oil circuit breakers. Today, oil-filled

    equipment has largely been replaced by air-blast, vacuum, or SF6 equipment, allowing large

    currents and power levels to be safely controlled by automatic equipment incorporating digital

    controls, protection, metering and communications.

    A view of switcgear at Power Plant

  • 8/6/2019 Trainee Report Ntpc[1]

    23/38

    Functions

    One of the basic functions of switchgear is protection, which is interruption of short-

    circuit and overload fault currents while maintaining service to unaffected circuits.

    Switchgear also provides isolation of circuits from power supplies. Switchgear also

    is used to enhance system availability by allowing more than one source to feed a

    load.

    Switchgear makes or breaks an electrical circuit.

    1. Isolation: - A device which breaks an electrical circuit when circuit is switched on

    to no load. Isolation is normally used in various ways for purpose of isolating a

    certain portion when required for maintenance.

    2. Switching Isolation: - It is capable of doing things like interrupting transformer

    magnetized current, interrupting line charging current and even perform load

    transfer switching. The main application of switching isolation is in connection withtransformer feeders as unit makes it possible to switch out one transformer while

    other is still on load.

    3. Circuit Breakers: - One which can make or break the circuit on load and even on

    faults is referred to as circuit breakers. This equipment is the most important and is

    heavy duty equipment mainly utilized for protection of various circuits and

    operations on load. Normally circuit breakers installed are accompanied by

    isolators

    4. Load Break Switches: - These are those interrupting devices which can make or

    break circuits. These are normally on same circuit, which are backed by circuitbreakers.

    5. Earth Switches: - Devices which are used normally to earth a particular system,

    to avoid any accident happening due to induction on account of live adjoining

    circuits. These equipments do not handle any appreciable current at all. Apart from

    this equipment there are a number of relays etc. which are used in switchgear.

    LT Switchgear

    It is classified in following ways:-

    1. Main Switch:- Main switch is control equipment which controls or disconnects

    the main supply. The main switch for 3 phase supply is available for tha range 32A,

  • 8/6/2019 Trainee Report Ntpc[1]

    24/38

    63A, 100A, 200Q, 300A at 500V grade.

    2. Fuses: - With Avery high generating capacity of the modern power stations

    extremely heavy carnets would flow in the fault and the fuse clearing the fault

    would be required to withstand extremely heavy stress in process.

    It is used for supplying power to auxiliaries with backup fuse protection. Rotary

    switch up to 25A. With fuses, quick break, quick make and double break switch

    fuses for 63A and 100A, switch fuses for 200A, 400A, 600A, 800A and 1000A are

    used.

    3. Contractors: - AC Contractors are 3 poles suitable for D.O.L Starting of motors

    and protecting the connected motors.

    4. Overload Relay: - For overload protection, thermal over relay are best suited for

    this purpose. They operate due to the action of heat generated by passage of current

    through relay element.

    5. Air Circuit Breakers: - It is seen that use of oil in circuit breaker may cause a fire.

    So in all circuits breakers at large capacity air at high pressure is used which is

    maximum at the time of quick tripping of contacts. This reduces the possibility of

    sparking. The pressure may vary from 50-60 kg/cm^2 for high and mediumcapacity circuit breakers.

    HT SWITCH GEAR

    High voltage switchgear is any switchgear and switchgear assembly of rated voltage

    higher than

    1000 volts.

    High voltage switchgear is any switchgear used to connect or to disconnect a part of

    a high voltage power system.These switchgears are essential elements for the protection and for a safety

    operating mode without interruption of a high voltage power system. This type of

    equipment is really important because it is directly linked to the quality of the

    electricity supply.

    The high voltage is a voltage above 1000 V for alternating current and above 1500 V

    for direct current.

  • 8/6/2019 Trainee Report Ntpc[1]

    25/38

    HT Switch Gear

    1. Minimum oil Circuit Breaker: - These use oil as quenching medium. It comprises

    of simple dead tank row pursuing projection from it. The moving contracts are

    carried on an iron arm lifted by a long insulating tension rod and are closed

    simultaneously pneumatic operating mechanism by means of tensions but throw off

    spring to be provided at mouth of the control the main current within the controlled

    device.

    Type-HKH 12/1000c

    Rated Voltage-66 KV

    Normal Current-1250A

    Frequency-5Hz

    Breaking Capacity-3.4+KA Symmetrical

    3.4+KA Asymmetrical

    360 MVA Symmetrical

    Operating Coils-CC 220 V/DC

    FC 220V/DC

    Motor Voltage-220 V/DC

    2. Air Circuit Breaker: - In this the compressed air pressure around 15 kg per cm^2

    is used for extinction of arc caused by flow of air around the moving circuit . The

    breaker is closed by applying pressure at lower opening and opened by applying

    pressure at upper opening. When contacts operate, the cold air rushes around the

    movable contacts and blown the arc.

    It has the following advantages over OCB:-

  • 8/6/2019 Trainee Report Ntpc[1]

    26/38

    i. Fire hazard due to oil are eliminated.

    ii. Operation takes place quickly.

    iii. There is less burning of contacts since the duration is short and consistent.

    iv. Facility for frequent operation since the cooling medium is replaced constantly.

    Rated Voltage-6.6 KV

    Current-630 A

    Auxiliary current-220 V/DC

    3. SF6 Circuit Breaker: - This type of circuit breaker is of construction to dead tank

    bulk oil to circuit breaker but the principle of current interruption is similar o thatof air blast circuit breaker. It simply employs the arc extinguishing medium namely

    SF6. the performance of gas . When it is broken down under an electrical stress it

    will quickly reconstitute itself

    Circuit Breakers-HPA

    Standard-1 EC 56

    Rated Voltage-12 KV

    Insulation Level-28/75 KV

    Rated Frequency-50 Hz

    Breaking Current-40 KA

    Rated Current-1600 A Making Capacity-110 KA

    Rated Short Time Current 1/3s -40 A

    Mass Approximation-185 KG

    Auxiliary Voltage

    Closing Coil-220 V/DC

    Opening Coil-220 V/DC

    Motor-220 V/DC

    SF6 Pressure at 20 Degree Celsius-0.25 KG

    SF6 Gas Per pole-0.25 KG

    4. Vacuum Circuit Breaker: - It works on the principle that vacuum is used to savethe purpose of insulation and it implies that pr. Of gas at which breakdown voltage

    independent of pressure. It regards of insulation and strength, vacuum is superior

    dielectric medium and is better that all other medium except air and sulphur which

    are generally used at high pressure.

    Rated frequency-50 Hz

    Rated making Current-10 Peak KA

    Rated Voltage-12 KV

    Supply Voltage Closing-220 V/DC

    Rated Current-1250 A

    Supply Voltage Tripping-220 V/DC

    Insulation Level-IMP 75 KVP Rated Short Time Current-40 KA (3 SEC)

    Weight of Breaker-8 KG

  • 8/6/2019 Trainee Report Ntpc[1]

    27/38

  • 8/6/2019 Trainee Report Ntpc[1]

    28/38

    GENERATOR

    The basic function of the generator is to convert mechanical power, delivered from

    the shaft of the turbine, into electrical power. Therefore a generator is actually arotating mechanical energy converter. The mechanical energy from the turbine is

    converted by means of a rotating magnetic field produced by direct current in the

    copper winding of the rotor or field, which generates three-phase alternating

    currents and voltages in the copper winding of the stator (armature). The stator

    winding is connected to terminals, which are in turn connected to the power system

    for delivery of the output power to the system.

    A 210 MW Turbine Generator at Badarpur Thermal Power Station, New Delhi

    The class of generator under consideration is steam turbine-driven

    generators,commonly called turbo generators. These machines are generally used in

    nuclear and fossil fueled power plants, co-generation plants,and combustion turbine

  • 8/6/2019 Trainee Report Ntpc[1]

    29/38

    units.They range from relatively small machines of a few Megawatts (MW) to very

    large generators with ratings up to 1900 MW. The generators particular to this

    category are of the two- and four-pole design employing round-rotors, with

    rotational operating speeds of 3600 and 1800 rpm in North America, parts of Japan,

    and Asia (3000 and 1500 rpm in Europe, Africa, Australia, Asia, and South

    America). At Badarpur Thermal Power Station 3000 rpm, 50 Hz generators are

    used of capacities 210 MW and 95 MW.

    As the system load demands more active power from the generator, more steam (orfuel in a combustion turbine) needs to be admitted to the turbine to increase power

    output. Hence more energy is transmitted to the generator from the turbine, in the

    form of a torque. This torque is mechanical in nature, but electromagnetically

    coupled to the power system through the generator. The higher the power output,

    the higher the torque between turbine and generator. The power output of the

    generator generally follows the load demand from the system. Therefore the

    voltages and currents in the generator are continually changing based on the load

    demand. The generator design must be able to cope with large and fast load

    changes, which show up inside the machine as changes in mechanical forces and

    temperatures. The design must therefore incorporate electrical current-carrying

    materials (i.e., copper), magnetic flux-carrying materials (i.e., highly permeablesteels), insulating materials (i.e., organic), structural members (i.e., steel and

    organic), and cooling media (i.e., gases and liquids), all working together under the

    operating conditions of a turbo generator

    An open Electric Generator at Power Plant

    Working Principle

    The A.C. Generator or alternator is based upon the principle of electromagnetic

  • 8/6/2019 Trainee Report Ntpc[1]

    30/38

    induction and consists generally of a stationary part called stator and a rotating

    part called rotor. The stator housed the armature windings. The rotor houses the

    field windings. D.C. voltage is applied to the field windings through slip rings. When

    the rotor is rotated, the lines of magnetic flux (viz magnetic field) cut through the

    stator windings. This induces an electromagnetic force (e.m.f.) in the stator

    windings.

    The magnitude of this e.m.f. is given by the following expression.

    E = 4.44 /O FN volts0 = Strength of magnetic field in Webers.

    F = Frequency in cycles per second or Hertz.

    N = Number of turns in a coil of stator winding

    F = Frequency = Pn/120

    Where P = Number of poles

    n = revolutions per second of rotor.

    From the expression it is clear that for the same frequency, number of poles

    increases with decrease in speed and vice versa. Therefore, low speed hydro turbine

    drives generators have 14 to 20 poles where as high speed steam turbine driven

    generators have generally 2 poles. Pole rotors are used in low speed generators,because the cost advantage as well as easier construction.

    Generator component

    This Chapter deals with the two main components of the Generator viz. Rotor, its

    winding & balancing and stator, its frame, core & windings.

    Rotor

    The electrical rotor is the most difficult part of the generator to design. It revolves in

    most modern generators at a speed of 3,000 revolutions per minute. The problem of

    guaranteeing the dynamic strength and operating stability of such a rotor iscomplicated by the fact that a massive non-uniform shaft subjected to a multiplicity

    of differential stresses must operate in oil lubricated sleeve bearings supported by a

    structure mounted on foundations all of which possess complex dynamic be

    behavior peculiar to themselves. It is also an electromagnet and to give it the

    necessary magnetic strength the windings must carry a fairly high current. The

    passage of the current through the windings generates heat but the temperature

    must not be allowed to become so high, otherwise difficulties will be experienced

    with insulation. To keep the temperature down, the cross section of the conductor

    could not be increased but this would introduce

    another problems. In order to make room for the large conductors, body and this

    would cause mechanical weakness. The problem is really to get the maximumamount of copper into the windings without reducing the mechanical strength. With

    good design and great care in construction this can be achieved. The rotor is a cast

    steel ingot, and it is further forged and machined. Very often a hole is bored

    through the centre of the rotor axially from one end of the other for inspection. Slots

    are then machined for windings and ventilation.

    Rotor winding

  • 8/6/2019 Trainee Report Ntpc[1]

    31/38

    Silver bearing copper is used for the winding with mica as the insulation between

    conductors. A mechanically strong insulator such as micanite is used for lining the

    slots. Later designs of windings for large rotor incorporate combination of hollow

    conductors with slots or holes arranged to provide for circulation of the cooling gas

    through the actual conductors. When rotating at high speed. Centrifugal force tries

    to lift the windings out of the slots and they are contained by wedges. The end rings

    are secured to a turned recess in the rotor body, by shrinking or screwing and

    supported at the other end by fittings carried by the rotor body. The two ends of

    windings are connected to slip rings, usually made of forged steel, and mounted on

    insulated sleeves.

    Rotor balancing

    When completed the rotor must be tested for mechanical balance, which means that

    a check is made to see if it will run up to normal speed without vibration. To do this

    it would have to be uniform about its central axis and it is most unlikely that this

    will be so to the degree necessary for perfect balance. Arrangements are therefore

    made in all designs to fix adjustable balance weights around the circumference at

    each end.

    Stator

    Stator frame: The stator is the heaviest load to be transported. The major part of

    this load is the stator core. This comprises an inner frame and outer frame. Theouter frame is a rigid fabricated structure of welded steel plates, within this shell is a

    fixed cage of girder built circular and axial ribs. The ribs divide the yoke in the

    compartments through which hydrogen flows into radial ducts in the stator core

    and circulate through the gas coolers housed in the frame. The inner cage is usually

    fixed in to the yoke by an arrangement of springs to dampen the double frequency

    vibrations inherent in 2 pole generators. The end shields of hydrogen cooled

    generators must be strong enough to carry shaft seals. In large generators the frame

    is constructed as two separate parts. The fabricated inner cage is inserted in the

    outer frame after the stator core has been constructed and the winding completed.

    Stator core: The stator core is built up from a large number of 'punching" or

    sections of thin steel plates. The use of cold rolled grain-oriented steel can contributeto reduction in the weight of stator core for two main reasons:

    a) There is an increase in core stacking factor with improvement in lamination cold

    Rolling and in cold buildings techniques.

    b) The advantage can be taken of the high magnetic permeance of grain-oriented

    steels of work the stator core at comparatively high magnetic saturation without

    fear or excessive iron loss of two heavy a demand for excitation ampere turns

    from the generator rotor.

    Stator WindingsEach stator conductor must be capable of carrying the rated current without

    overheating. The insulation must be sufficient to prevent leakage currents flowing

    between the phases to earth. Windings for the stator are made up from copper

    strips wound with insulated tape which is impregnated with varnish, dried under

    vacuum and hot pressed to form a solid insulation bar. These bars are then place in

    the stator slots and held in with wedges to form the complete winding which is

    connected together at each end of the core forming the end turns. These end turns

  • 8/6/2019 Trainee Report Ntpc[1]

    32/38

    are rigidly braced and packed with blocks of insulation material to withstand the

    heavy forces which might result from a short circuit or other fault conditions. The

    generator terminals are usually arranged below the stator. On recent generators

    (210 MW) the windings are made up from copper tubes instead of strips through

    which water is circulated for cooling purposes. The water is fed to the windings

    through plastic tubes.

    TRANFORMER& SWITCHYARD

    A transformer is a device that transfers electrical energy from one circuit to another

    by magnetic coupling with out requiring relative motion between its parts. It usually

    comprises two or more coupled windings, and in most cases, a core to concentrate

    magnetic flux. An alternating voltage applied to one winding creates a time-varying

    magnetic flux in the core, which includes a voltage in the other windings. Varying

    the relative number of turns between primary and secondary windings determines

    the ratio of the input and output voltages, thus transforming the voltage by stepping

    it up or down between circuits. By transforming electrical power to a high-voltage,_low-current form and back again, the transformer greatly reduces energy

    losses and so enables the economic transmission of power over long distances. It has

    thus shape the electricity supply industry, permitting generation to be located

    remotely from point of demand. All but a fraction of the worlds electrical power

    has passed trough a series of transformer by the time it reaches the consumer.

    Basic principles

    The principles of the transformer are illustrated by consideration of a hypothetical

    ideal transformer consisting of two windings of zero resistance around a core of

    negligible reluctance. A voltage applied to the primary winding causes a current,

    which develops a magneto motive force (MMF) in the core. The current required to

    create the MMF is termed the magnetizing current; in the ideal transformer it is

    considered to be negligible, although its presence is still required to drive flux

    around the magnetic circuit of the core. An electromotive force (MMF) is induced

    across each winding, an effect known as mutual inductance. In accordance with

    faradays law of induction, the EMFs are proportional to the rate of change of flux.

    The primary EMF, acting as it does in opposition to the primary voltage, is

    sometimes termed the back EMF. Energy losses An ideal transformer would have

    no energy losses and would have no energy losses, and would therefore be 100%

    efficient. Despite the transformer being amongst the most efficient of electrical

    machines with ex the most efficient of electrical machines with experimental models

    using superconducting windings achieving efficiency of 99.85%, energy is dissipated

    in the windings, core, and surrounding structures. Larger transformers are

    generally more efficient, and those rated for electricity distribution usually perform

    better than 95%. A small transformer such as plug-in power brick used for low-

    power consumer electronics may be less than 85% efficient. Transformer losses are

    attributable to several causes and may be differentiated between those originated in

    the windings, some times termed copper loss, and those arising from the magnetic

    circuit, sometimes termed iron loss. The losses vary with load current, and may

  • 8/6/2019 Trainee Report Ntpc[1]

    33/38

    furthermore be expressed as no load or full load loss, or at an intermediate

    loading. Winding resistance dominates load losses contribute to over 99% of the no-

    load loss can be significant, meaning that even an idle transformer constitutes a

    drain on an electrical supply, and lending impetus to development of low-loss

    transformers. Losses in the transformer arise from: Winding resistance Current

    flowing trough the windings causes resistive heating of the conductors. At higher

    frequencies, skin effect and proximity effect create additional winding resistance

    and losses. Hysteresis losses Each time the magnetic field is reversed, a small

    amount of energy is lost due to hysteresis within the core. For a given core material,

    the loss is proportional to the frequency, and is a function of the peak flux density to

    which it is subjected. Eddy current Ferromagnetic materials are also goodconductors, and a solid core made from such a material also constitutes a single

    short-circuited turn trough out its entire length. Eddy currents therefore circulate

    with in a core in a plane normal to the flux, and are responsible for resistive heating

    of the core material. The eddy current loss is a complex function of the square of

    supply frequency and inverse square of the material thickness. Magnetostriction

    Magnetic flux in a ferromagnetic material, such as the core, causes it to physically

    expand and contract slightly with each cycle of the magnetic field, an effect known

    as magnetostriction. This produces the buzzing sound commonly associated with

    transformers, and in turn causes losses due to frictional heating in susceptible cores.

    Mechanical losses In addition to magnetostriction, the alternating magnetic field

    causes fluctuating electromagnetic field between primary and secondary windings.These incite vibration with in near by metal work, adding to the buzzing noise, and

    consuming a small amount of power. Stray losses Leakage inductance is by itself

    loss less, since energy supplied to its magnetic fields is returned to the supply with

    the next half-cycle. However, any leakage flux that intercepts nearby conductive

    material such as the transformers support structure will give rise to eddy currents

    and be converted to heat. Cooling system Large power transformers may be

    equipped with cooling fans, oil pumps or water-cooler heat exchangers design to

    remove heat. Power used to operate the cooling system is typically considered part

    of the losses of the transformer.

  • 8/6/2019 Trainee Report Ntpc[1]

    34/38

    A 220 kV Transformer at Power Plant

    PROTECTION

    The protection system of any modern electric power grid is the most crucial

    function in the system. Protection is a system because it comprises discrete devices(relays, communication means, etc.) and an algorithm that establishes a coordinated

    method of operation among the protective devices. This is termed coordination.

    Thus, for a protective system to operate correctly, both the settings of the individual

    relays and the coordination among them must be right. Wrong settings might result

    in no protection to the protected equipment and systems, and improper

    coordination might result in unwarranted loss of production. The key function of

    any protective system is to minimize the possibility of physical damage to equipment

    due to a fault anywhere in the system or from abnormal operation of the equipment(over speed, under voltage, etc.). However, the most critical function of any

    protective scheme is to safeguard those persons who operate the equipment that

    produces, transmits, and utilizes electricity.

    Protective systems are inherently different from other systems in a power plant (or

    for that matter any other place where electric power is present). They are called to

  • 8/6/2019 Trainee Report Ntpc[1]

    35/38

  • 8/6/2019 Trainee Report Ntpc[1]

    36/38

    Typically it will alarm, but it can also be set to trip the unit. Protections function

    can also be divided into short- circuit protection functions. The short-circuit

    protection comprises impedance, distance, and current differential protection.

    Multi-function Generator Protection Device

    GENERATOR PROTECTIVE FUNCTION

    Protection devices are designed to monitor certain conditions, and subsequently, to

    alarm or trip if a specified condition is detected. The condition is represented by a

    function or protective function code. Thus there is a relay for every protective

    function. If a relay only monitors and thus protects against a single set of conditions,

    it is said that the relay is a single-function device. In the past most relays were

    single-function devices. With the advent of solid-state electronics, manufacturers

    have combined several functions in one unit or device.

    These multi-function relays or protective devices offer specific protective

    functions designed for certain types of apparatus. Some multi-function relays are

    dedicated to transformers, others to motors, and others to generators. Advances in

    solid-state electronics have led to less costly devices. Today a multi-function solid-

    state device with, for instance, five protective functions, is less expensive than five

    separate relays for five protective functions.

  • 8/6/2019 Trainee Report Ntpc[1]

    37/38

    The number of functions covered by different relays and the number of

    multifunction devices are decided, among other things, by the expected losses of all

    the protective functions covered by the multi-functional relay, if that particular

    device becomes faulty. A multi-functional relay containing all the protective

    functions required for the protection of a generator can be combined with a few

    discrete relays providing backup protection for critical functions. Alternatively, two

    or more multi-functional relays can be applied, providing partial or comprehensive

    redundancy. There are many combinations of these discrete and multi-functional

    relays that can be adopted, depending on when the power plant was build, the size

    of the units, system conditions, the idiosyncrasy of the designer, and many other

    factors. Alternatively, two or more multi-functional relays can be applied, providing

    partial or comprehensive redundancy. There are many combinations of these

    discrete and multi-functional relays that can be adopted, depending on when the

    power plant was build, the size of the units, system conditions, the idiosyncrasy of

    the designer, and many other factors.

    Relays or protection devices are divided into two categories according to how they

    process data. The first category is that of analog relays; the second is that of

    numerical (also called digital) relays. Bear in mind that a relay can be electronic but

    still process the data in an analog manner. The advantages of numerical processing

    are various. Accuracy is enhanced. So is flexibility in use. For instance, a numerical

    relay offers user-shaped protection widows such that the user can change the shape

    of the operation/non-operation areas for a specific function of the relay.

    Furthermore the shape of the region of operation may change according to system

    conditions (adaptive function).

    Finally, there is rather a newstill evolvingapproach (from the early 1990s) for

    protecting large generating units by the so-called expert protection systems. The

    idea is to protect the unit based not only on the basic protective functions (given

    below), but also as a combination of protective and monitoring data and built-in

    expertise in the form of diagnostic prescriptions. Invariably, building the expertise

    base of these systems consists in expressing probable causes for a particular

    combination of symptoms, expressed as a probabilistic tree.

    A number, according to a worldwide-accepted nomenclature, identifies protectivefunctions. The functions shown in table are typical of generation protection. A

    number of the functions included in table are so important that they will always find

    their way into the protection scheme of any generator (e.g., 25, 59, and 87). Others

    may be omitted in some applications (e.g., 49). The larger and more expensive the

  • 8/6/2019 Trainee Report Ntpc[1]

    38/38