Traffic Light Legend - Stanford University Light Legend NOTE: Colored borders around graphs indicate...
Transcript of Traffic Light Legend - Stanford University Light Legend NOTE: Colored borders around graphs indicate...
BUILDING SYSTEM FLOOR COMPONENT ZONE
Y2E2 AHU 1
BASEMENT
1ST FLOOR
2nd FLOOR
3rd FLOOR
CV B-1-3 ECV B-12-18 VAV B-1-4 EVAV B-12-14
B12 Teaching Lab
B19 Materials Storage
B26 Equipment Room
B27 Equipment Room
ECV 1-12-1 CV 1-1-3
103A Food Service
111 Lecture
ECV 2-12-1 CV 2-1-3
220 Men’s Room 293 John Kunz’ Office
SF 3-1 ECV 3-12-1 CV 3-1-4
Plenum
318 Men’s Room
324 Open Office
LEGEND
System served (arrow points away from it)
System serving (arrow points to it)
3
GREEN LIGHT: System functioning as intended. No attention necessary and no risk of personal or financial harm. YELLOW LIGHT: Data indicate system performance is not as expected. Professional attention advised and possible risk of personal or financial harm. RED LIGHT: Data indicate that either sensors or system not functioning as expected. Professional attention necessary, as there is probable risk of personal or financial harm.
Traffic Light Legend
NOTE: Colored borders around graphs indicate lowest level of proper system functioning (i.e. if there is any yellow within the data, a yellow border is applied and likewise if there is any red, a red border is applied).
4
Hot Water
Previous Graph - Colored entirely green - Hard to read - 60 minute interval
Revised Graph - Green border - Easier to read - 1 minute interval - More accurate analysis
5
Chilled Water Flow Before
After
Before Further Investigation - Incomplete status assessment - Unsolved yellow lights After Further Investigation - Complete status assessment! - Yellow lights turned green - Insignificant discrepancy 6
Before
After
1
Before Further Investigation - Neglected areas of concern - Undeserving status assessment
After Further Investigation - Exposed area of concern - Discrepancy significant - Complete status assessment!
Hot Water Flow
7
Heating in Representative Office 371
All Clear - Interval at 1 minute
makes an already clear graph even clearer
- Heating system in 371 is working perfectly
- Status assessment: GREEN!
8
1
2
2
Before
After Before Verification - Unsolved yellow lights - HW turns on too early After Further Investigation - Time series plot refutes problem - Problem in SEEIT: not in the system - Status assessment: Green!
HW Flow in Representative Office 371
9
Heat Recovery
2009 problem: • Heat recovery
cooling mode doesn’t coincide with coil cooling mode
2011 update: • Cooling coil valve
no longer open when heat recovery bypass damper is open
10
Supply vs. Return Temp.
2009 problem: • Active beam hot
water supply & return water temps reversed & values inconsistent with hot water system level temperatures
2011 update: • Hot water supply &
return temps have correct relationship; correct system temperature level
11
Heating Coil Valve Position
2009 problem: • Heating coil valve
cycles open and closed rapidly
2011 update: • Problem fixed
12
Wiki Explained Cont’d.
• Step 2: Use our table of contents to navigate
• One continuous page for your convenience
14
Recommendations
• All inconsistencies marked as “yellow” should be further examined to determine whether they are “red” or “green.”
– Hot Water Flow Rate vs. Active Beam Heating Valve Position
15