TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual Page 1 of 57 TQ 4200 SERIES INFRARED REFRIGERANT LEAK DETECTION SYSTEM MKII Serial No’s 20000 onwards © This manual must not be copied or reproduced in part without the express written permission of TQ Environmental PLC. All information contained herein is subject to modification. TQ Environmental Plc, Flanshaw Way, WAKEFIELD, W. Yorks, WF2 9LP 44 (0) 1924 380700 FAX 44 (0) 1924 361700 TQ ENVIRONMENTAL PLC BS EN ISO 9001 Filename: 4200BM1 Date: 12-06/07 Author: G. Thompson

Transcript of TQ 4200 SERIES INFRARED REFRIGERANT LEAK DETECTION · PDF fileINFRARED REFRIGERANT LEAK...

Page 1: TQ 4200 SERIES INFRARED REFRIGERANT LEAK DETECTION · PDF fileINFRARED REFRIGERANT LEAK DETECTION SYSTEM ... provide an alarm output when there is a reduction ... The mains input to

TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual

Page 1 of 57

TQ 4200 SERIES INFRARED

REFRIGERANT LEAK DETECTION SYSTEM

MKII

Serial No’s 20000 onwards

© This manual must not be copied or reproduced in part without the express written permission of TQ Environmental PLC. All information contained herein is subject to modification. TQ Environmental Plc, Flanshaw Way, WAKEFIELD, W. Yorks, WF2 9LP

44 (0) 1924 380700 FAX 44 (0) 1924 361700

TQ ENVIRONMENTAL PLC BS EN ISO 9001

Filename: 4200BM1 Date: 12-06/07 Author: G. Thompson

Page 2: TQ 4200 SERIES INFRARED REFRIGERANT LEAK DETECTION · PDF fileINFRARED REFRIGERANT LEAK DETECTION SYSTEM ... provide an alarm output when there is a reduction ... The mains input to

TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual

Page 2 of 57

Page 3: TQ 4200 SERIES INFRARED REFRIGERANT LEAK DETECTION · PDF fileINFRARED REFRIGERANT LEAK DETECTION SYSTEM ... provide an alarm output when there is a reduction ... The mains input to

TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual

Page 3 of 57

PROPRIETARY

No part of the hardware or documentation may be reproduced, transmitted, transcribed, stored in a retrieval system, or translated into any language or computer language, in any form or by any means, without prior written permission of TQ Environmental PLC

While great efforts have been made to assure the accuracy and clarity of this document, TQ Environmental PLC assumes no liability resulting from any omissions in this document, or from misuse of the information obtained herein. The information in this document has been carefully checked and is believed to be entirely reliable with all of the necessary information included. TQ Environmental PLC reserves the right to make changes to any products described herein to improve reliability, function, or design, and reserves the right to revise this document and make changes from time to time in content hereof with no obligation to notify any persons of revisions or changes. TQ Environmental PLC does not assume any liability arising out of the application or any use of any product or circuit described herein; neither does it convey license under its patent rights or the rights of others.

WARNINGS, CAUTIONS AND NOTES

Warnings identify an operating or maintenance procedure, practice, condition, or statement that, if not strictly followed, could result in death or injury to personnel.

Cautions, which appear elsewhere in this manual, identify an operating or maintenance procedure, practice, condition, or statement that if not strictly followed could result in equipment damage or serious impairment of system operation.

Notes highlight certain operating or maintenance conditions or statements that are essential but not of known hazardous nature as indicated by Warnings and Cautions. Warnings, Cautions and Notes are included throughout this manual, as required. Additionally, this section contains important Warnings that may not be contained elsewhere within this instruction manual.

Page 4: TQ 4200 SERIES INFRARED REFRIGERANT LEAK DETECTION · PDF fileINFRARED REFRIGERANT LEAK DETECTION SYSTEM ... provide an alarm output when there is a reduction ... The mains input to

TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual

Page 4 of 57

SAFETY WARNINGS

• FOR SAFETY REASONS, THE TQ4200 MUST BE INSTALLED, OPERATED AND SERVICED BY QUALIFIED PERSONNEL ONLY. READ AND UNDERSTAND THIS INSTRUCTION MANUAL COMPLETELY BEFORE OPERATING THE TQ4200

• • THE OPERATION DESCRIBED IN THIS DOCUMENT IS THE INTENEDED USE OF

THE TQ4200. TQ ENVIRONMENTAL PLC CANNOT BE HELD RESPONSIBLE IF THE TQ4200 IS USED FOR ANY OTHER PURPOSE OTHER THAN THAT STATED. ANY OTHER USE OF THE TQ4200 WILL CAUSE ANY CERTIFICATES ISSUED TO NOT APPLY.

Page 5: TQ 4200 SERIES INFRARED REFRIGERANT LEAK DETECTION · PDF fileINFRARED REFRIGERANT LEAK DETECTION SYSTEM ... provide an alarm output when there is a reduction ... The mains input to

TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual

Page 5 of 57

CONTENTS

SECTION DESCRIPTION

1.0 Introduction

2.0 Description 2.1 Infrared Sensor 2.2 Pneumatic System 2.2.1 External Catch-Pot 2.2.2 Flow Fail 2.2.3 Pressure Sensor 2.2.4 Solenoid Valves 2.2.5 Sampling Pump 2.2.6 DC Electrical Supplies 2.2.7 Outputs

3.0 System Software

3.1 Start-up 3.2 Power on reset 3.3 System Warm-up 3.4 Normal Operating Mode 3.5 Entering Passwords 3.6 Overview of Menu System 3.6.1 Main Menu - Set Time 3.6.2 - Set Date 3.6.3 - Calibrate 3.6.4 - Change Password 3.6.5 - Parameters 3.6.5.1 - Set Location 3.6.5.2 - Set Gas Type 3.6.5.3 - Parameters - Set Alarm 1 3.6.5.4 - Parameters - Set Alarm 2 & 3

3.6.5.5 - Parameters - Set Alarm 1 Type 3.6.5.6 - Parameters - Set Alarm 2 & 3 Type 3.6.5.7 - Parameters - Set Dwell Time 3.6.5.8 - Parameters - Exit Sub Menu 3.7 Overview of the Alarm Operation 3.7.1 Alarm Control Functions 3.7.1.1 Main Menu - Mute Alarm 3.7.1.2 - Reset Alarm 3.7.1.3 - Display Alarms 3.7.1.4 - Erase Alarms 3.8 Technician Mode 3.8.1 - Set No of Zones 3.8.2 - Skip Zone Number 3.8.3 - Calibrate Pressure 3.9 Main Menu - Exit Menu

Page 6: TQ 4200 SERIES INFRARED REFRIGERANT LEAK DETECTION · PDF fileINFRARED REFRIGERANT LEAK DETECTION SYSTEM ... provide an alarm output when there is a reduction ... The mains input to

TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual

Page 6 of 57

SECTION DESCRIPTION 4.0 Operation

4.1 System Warm-up 4.2 Normal 4.3 Alarms - 4.3.1 - System Fault 4.3.2 - Gas Level Alarms 4.3.2.1 - Mute Alarms 4.3.2.2 - Reset Alarms

5.0 Drawings 6.0 Maintenance 7.0 Parts List 8.0 Fault Finding 8.1 Analyser NVRAM Fault 8.2 OMNICA NVRAM Fault 8.3 Sensor Communications Fault 8.4 OMNICA Communications Fault 8.5 Zero Filter Blocked Fault 8.6 Flow Fail Fault 8.7 No Pressure Fault 8.8 Sensor Drift Fault 8.9 Sensor Fault Appendix ‘A’ Project Specific Information* * See section Sub Index for contents

Page 7: TQ 4200 SERIES INFRARED REFRIGERANT LEAK DETECTION · PDF fileINFRARED REFRIGERANT LEAK DETECTION SYSTEM ... provide an alarm output when there is a reduction ... The mains input to

TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual

Page 7 of 57

1.0 INTRODUCTION

The TQ4200 is an Aspirated Infrared Refrigerant Leak Detection System (IRLDS). This system utilises infrared gas analysing technology to detect the signatures of the designated gas, thus eliminating any nuisance alarms from other gases, a selection of which are mentioned below;

a) Hydrogen b) Carbon Monoxide c) Carbon Dioxide d) Hexane e) Heat resistance aluminium paint fumes f) Epoxy finishing paint fumes. g) Epoxy finish white base paint fumes. h) Bioguard water based paint i) Methane

The TQ4200 system has the capability of monitoring up to 16 sample points by sequentially cycling through each location. Individual sample lines can be configured to detect differing refrigerant gases. The TQ4200 is currently programmed to monitor the following refrigerants:

a) R12 b) R22 c) R114 d) R134a e) R404A f) R407C g) R403B h) R236fa

Each sample point will also have three individual alarm trip levels. Any gas sample concentration reaching the ‘low’, ‘high’ and ‘high-high’ trip levels will operate the common alarm relays and provide an output to actuate audible/visual alarm devices.

The TQ4200 front panel provides the operator interface via four pushbuttons and a backlit LCD display. During normal operation the LCD display will provide the ‘location’, ‘gas type’ and sample ‘concentration’ for each individual location. The TQ4200 also has the ability to store the last twenty alarms which can be displayed in alarm/time/date format in time order. Each of the sample transport lines are constantly monitored for flow restrictions. In the event of a reduction or loss of flow, a ‘system flow alarm’ will be initiated.

Page 8: TQ 4200 SERIES INFRARED REFRIGERANT LEAK DETECTION · PDF fileINFRARED REFRIGERANT LEAK DETECTION SYSTEM ... provide an alarm output when there is a reduction ... The mains input to

TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual

Page 8 of 57

The TQ4200 is available in either ‘top’ or ‘bottom’ entry versions for sample lines and cabling, at 85-264V 50/60 Hz. PART NO DESCRIPTION 370-520 TQ420016-way bottom entry 85-264V

370-522 TQ4200 8-way bottom entry 85-264V

Page 9: TQ 4200 SERIES INFRARED REFRIGERANT LEAK DETECTION · PDF fileINFRARED REFRIGERANT LEAK DETECTION SYSTEM ... provide an alarm output when there is a reduction ... The mains input to

TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual

Page 9 of 57

2.0 DESCRIPTION 2.1 Infrared Sensor (GD134, GD137) The operation of the infrared sensor within the TQ4200 has been developed from the infrared heat source detector utilised in the thermal imaging cameras measuring infrared radiation. These detectors have now developed into non-dispersive infrared analysers. Dispersive analysers use a wide band of infrared to identify a gas, the none-dispersive type narrows the wavelength specific to a gas. The narrow infra red band produced is passed through the gas sample and a gas specific to this wavelength will absorb this infrared depending on the concentration. The electronics converts this absorption of infrared into an electrical signal for processing. The narrowing of the band of infrared light is produced utilising filters made of specific material such as calcium fluoride, sapphire, etc. The light source is modulated by a mechanical chopper to give a high performance on very small signal. This modulated light source together with a reference sensor, which is not exposed to the gas sample, gives a very accurate signal for a concentration of the target gas. 2.2 Pneumatic System The gas sample is brought into the TQ4200 at approximately 4 litres/min from one of the 15 sample lines, into the solenoid bank manifold by a diaphragm pump and presented to the infrared sensor. A particulate filter is fitted before the pump. (Please refer to Figure 3 & 4). 2.2.1 External Catch-Pot The external catch-pot will remove the majority of moisture within the sample line. If the bowl is allowed to fill the catch-pot will automatically shut-off the sample line causing a flow fail alarm. 2.2.2 Flow Fail The flow fail is detected by the PCB mounted differential pressure switch sensing across a differential pressure tube (See Figure 4).This PCB will provide an alarm output when there is a reduction in air flow.

Page 10: TQ 4200 SERIES INFRARED REFRIGERANT LEAK DETECTION · PDF fileINFRARED REFRIGERANT LEAK DETECTION SYSTEM ... provide an alarm output when there is a reduction ... The mains input to

TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual

Page 10 of 57

2.2.3 Pressure Sensor A pressure sensor monitors the air pressure in the vent line of the TQ4200 to provide the electronics with pressure information when calculating the gas concentration. This pressure sensor is also a PCB mounted device. 2.2.4 Solenoid Valves The solenoid valves in either an 8-way or 16-way configuration, are mounted on an eight way common manifold and have 24V DC operating coils. Fitted within the solenoid valve connector covers are back EMF diodes and LED indicators. The common manifold also provides the individual sample line inlet ports. Each port is 1/8” BSP and can be fitted with a union connector to suit the transport tubing. (Note: these inlet connectors are not included with the standard unit). 2.2.5 Sampling Pump The sampling pump is a single ended unit power by 24VDC from the internal power supply. The pump is fitted with viton diaphragm and seals, and requires very little maintenance. Flow rate for this application is 4 litres/hour. The electrical supply to the pump is wired through Fuse 4 (See Figure 5). 2.2.6 DC Electrical Supplies The DC electrical supplies for the TQ4200 are provided by its internal 110 Watt power supply unit. This is a universal input device and will accept an input of 85 to 250 Volts AC. (See Figure 5). The mains input to the TQ4200 unit is connected to TBF-01 and then to a fused isolator via the EMC suppresser. 2.2.7 Outputs Outputs from the TQ4200 are in the form of:-

- Volt Free Contacts for Alarm 1, 2 and 3 and Common Fault

- 24V DC @ 100mA for Visual Alarm - 24V DC @ 100mA for Audible Alarm

- One 4-20mA analogue output RS485 Modbus 4-20ma Output with respect to concentratiom (0-2000ppm) 4-20ma Output with respect to locaction (1ma per location)

Page 11: TQ 4200 SERIES INFRARED REFRIGERANT LEAK DETECTION · PDF fileINFRARED REFRIGERANT LEAK DETECTION SYSTEM ... provide an alarm output when there is a reduction ... The mains input to

TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual

Page 11 of 57

2.2.7 MODBUS O/P The MODBUS bus output can be connected to any MODBUS configurable device. The standard register addresses and communications protocol are defined as follows:-

Input Register (0x04)

Starting Address (High)

Starting Address (Low)

Number of Registers

(High)

Number of Registers

(Low)

Number of Bytes

Station Number Read (0x04) Write (0x10)

0x00 0x10 0x00 0x01 2

Zone 1 Conc. 0x00 0x00 0x00 0x01 2 Zone 2 Conc. 0x00 0x01 0x00 0x01 2 Zone 3 Conc. 0x00 0x02 0x00 0x01 2 Zone 4 Conc. 0x00 0x03 0x00 0x01 2 Zone 5 Conc. 0x00 0x04 0x00 0x01 2 Zone 6 Conc. 0x00 0x05 0x00 0x01 2 Zone 7 Conc. 0x00 0x06 0x00 0x01 2 Zone 8 Conc. 0x00 0x07 0x00 0x01 2 Zone 9 Conc. 0x00 0x08 0x00 0x01 2 Zone 10 Conc. 0x00 0x09 0x00 0x01 2 Zone 11 Conc. 0x00 0x0A 0x00 0x01 2 Zone 12 Conc. 0x00 0x0B 0x00 0x01 2 Zone 13 Conc. 0x00 0x0C 0x00 0x01 2 Zone 14 Conc. 0x00 0x0D 0x00 0x01 2 Zone 15 Conc. 0x00 0x0E 0x00 0x01 2 Zone 16 Conc. 0x00 0x0F 0x00 0x01 2 Discrete Inputs (0x02)

Starting Address (High)

Starting Address (Low)

Number of Registers (High)

Number of Registers (Low)

Number of Bytes

Alarm Status 0x00 0x00 0x00 0x01 2 Input

Number

Alarm 1 0 Alarm 2 1 Alarm 3 2 Fault 3

Communications Protocol Baud Rate Data Bits Parity Stop Bits Transmission Error

Check 19200 8 Even 1 RTU CRC-16

Page 12: TQ 4200 SERIES INFRARED REFRIGERANT LEAK DETECTION · PDF fileINFRARED REFRIGERANT LEAK DETECTION SYSTEM ... provide an alarm output when there is a reduction ... The mains input to

TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual

Page 12 of 57

Page 13: TQ 4200 SERIES INFRARED REFRIGERANT LEAK DETECTION · PDF fileINFRARED REFRIGERANT LEAK DETECTION SYSTEM ... provide an alarm output when there is a reduction ... The mains input to

TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual

Page 13 of 57

3.0 SYSTEM SOFTWARE

This section explains in detail the system set-up and operation of the TQ 4200 main board. Four keys are used to navigate through and access the system software functions, namely: MENU, SELECT, UP, and DOWN.

3.1 System Start-up

When the system is powered on or a hardware system reset occurs, the TQ 4200 main board will boot up showing the Start-up screen in Figure 3-1 below:

TQ ENVIRONMENTAL PlC

TQ4200

Figure 3-1 Start-up Display

3.1.1 NVRAM Test The TQ 4200 will perform an internal non-volatile memory self-test. The result of the test being displayed on the LCD as shown below:

Testing: NVRAM

NVRAM TEST: PASS

Figure 3-2 NVRAM Self Test

3.2 Power-on Reset*

The power-on reset function is used to load the default data into the system. The user must initiate the power-on reset by pressing and holding the SELECT key, UP key, and DOWN key simultaneously for approximately two seconds when the power is turned on.

If the user does not initiate a power-on reset then the system will begin initialisation by downloading the previous parameters into system memory from the non-volatile serial RAM. This stage is indicated on the liquid crystal display by Figure 3-3 shown below:

Page 14: TQ 4200 SERIES INFRARED REFRIGERANT LEAK DETECTION · PDF fileINFRARED REFRIGERANT LEAK DETECTION SYSTEM ... provide an alarm output when there is a reduction ... The mains input to

TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual

Page 14 of 57

DOWNLOADING DATA

…….

Figure 3-3 System Initialisation Display

* The system start up is only required on the very first power up or if any data becomes corrupt.

3.3 System Warm-up

When the TQ 4200 main board is powered on or a hardware reset is applied, the system will undergo a warm-up period. This warm-up period will last no longer than 2 minutes and the liquid crystal display will be as shown in Figure 3-4 below:

SENSOR WARMUP PERIOD

PLEASE WAIT…

Figure 3-4 Warm-up Period Mode

If the warm-up period is unsuccessful and 15 minutes has elapsed since the power has been turned on, the system will select the System Fault mode.

N.B. Due to the temperature changing within the cabinet the sensor will take time to obtain 95% accuracy. After 8 hours the system will reached its peak accuracy. The systems are therefore designed for continuous operation and should not be powered down as necessary.

When the system has settled, any opening of the door on the cabinet will reduce the accuracy again of the system. Therefore several hours are required for true readings to be obtained. This is due to the fact explained in section one where originally these sensors were used for thermal imaging and the difference in temperatures affects their accuracy. Additionally the detector and reference elements in the system have different coefficients of heat dissipation which results in loss of accuracy.

Page 15: TQ 4200 SERIES INFRARED REFRIGERANT LEAK DETECTION · PDF fileINFRARED REFRIGERANT LEAK DETECTION SYSTEM ... provide an alarm output when there is a reduction ... The mains input to

TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual

Page 15 of 57

3.3.1 Internal System Leak Test After the warm-up period is complete the system will initiate a Pressure Test. This will test for any internal leaks within the system.

PRESSURE TEST

PLEASE WAIT…

Figure 3-5 Pressure Test

3.3.2 Sensor Auto-Zero At initial start up the system will initiate a sensor auto-zero. This will then be performed at the end of every cycle.

SENSOR AUTO-ZERO

PLEASE WAIT…

Figure 3-6 Sensor Auto-Zero

3.4 Normal Operating Mode

The TQ 4200 main board has two distinct modes of operation: the Normal Operating Mode and the Menu Mode. After system initialisation, the TQ 4200 main board will automatically select the Normal Operating Mode. In this mode the system will scan each zone location sequentially, displaying on the liquid crystal display the current zone location, the sampled gas, and the sampled gas concentration in parts per million (ppm). This information is displayed as shown in Figure 3-7 below:

ZONE 1

R134A 00000 ppm

Figure 3-7 Normal Operating Mode

Page 16: TQ 4200 SERIES INFRARED REFRIGERANT LEAK DETECTION · PDF fileINFRARED REFRIGERANT LEAK DETECTION SYSTEM ... provide an alarm output when there is a reduction ... The mains input to

TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual

Page 16 of 57

When selecting a particular zone location, its corresponding solenoid is activated in order to sample the gas concentration. At the end of the ‘solenoid on’ sequence the sampled gas concentration is measured and compared with two user defined alarm levels. If the sampled gas concentration has exceeded the stored alarm levels then an appropriate alarm relay will be activated. The display will confirm the alarm condition by displaying the zone location, alarm number, and alarm status. An example of an alarm condition is shown in Figure 3-8 below, together with either the first and second red alarm LED’s.

ZONE 1

ALARM1 ACTIVE

Figure 3-8 Example of Alarm Condition

A more detailed discussion of alarm conditions will be presented in section 4 of this manual.

3.5 Entering Passwords

To gain access to the Menu Mode, the user must enter a password (four-digit code). The numbers must be selected and entered one at a time. The UP and DOWN keys are used to scroll through the numbers. When the desired number is displayed, pressing the SELECT key will ENTER that number. The entered number will be blanked out after the SELECT key is pressed to ensure restricted access to the menu system. The cursor will now move to the next digit to the right of the blanked out digit and pressing the UP and DOWN keys will again change the number as required.

ENTER PASSWORD

****

Figure 3-9 Display Password Prompt

After the four digits have been entered the system will check the entered password against the correct password. If the entered password is correct, the display will indicate this by displaying that the password has been accepted. The system will now select the Menu mode. If the entered password is incorrect the display will indicate this by displaying that the password is invalid. If the entered password is invalid, the user is again prompted to enter a password. (System default Password number is 6197).

Page 17: TQ 4200 SERIES INFRARED REFRIGERANT LEAK DETECTION · PDF fileINFRARED REFRIGERANT LEAK DETECTION SYSTEM ... provide an alarm output when there is a reduction ... The mains input to

TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual

Page 17 of 57

3.6 Overview of the Menu System

The menus are accessed from the Normal Operating Mode by pressing the MENU key. A password must be entered by the user to access the Menu Mode. Once the password has been accepted, the user will be presented with the Menu Screen. The menu may be navigated by pressing the UP and DOWN keys, which will enable the user to scroll through the menu items. The menu items will wrap around from the last menu item to the first menu item and vice-versa. For example, if the UP key is pressed when the last menu item, EXIT MENU, is displayed, the first menu item, SET TIME, will be displayed. Conversely, if the DOWN key is pressed when the first menu item, SET TIME, is displayed, the last menu item, EXIT MENU, will be displayed. To select the desired menu item, the user must press the SELECT key.

3.6.1 Main Menu - Set Time

When the SET TIME menu item is entered from the display, shown below in Figure 3-10, the system time may be altered. This real time clock will remain active and maintain an accurate time even when power to the system is turned off.

MAIN MENU

SET TIME

Figure 3-10 Set Time Menu Option

If the SET TIME menu item is selected the user will be prompted to enter the desired hours and minutes. The time is configured in the 24-hour clock mode. The SET TIME menu item display is shown in Figure 3-11 below. When first entered, the ‘hours’ value will flash indicating that this is the active field. Pressing the UP and DOWN keys will alter this field. To accept the displayed value the user must press the SELECT key. The ‘minutes’ value will now flash enabling the user to alter this field. Pressing the SELECT key again will set the minutes value. The SELECT key in this menu item acts as a toggle between selecting the ‘hours’ field and the ‘minutes’ field. When the desired time has been set the user must press the MENU key to exit the SET TIME menu item and return to the main menu.

Page 18: TQ 4200 SERIES INFRARED REFRIGERANT LEAK DETECTION · PDF fileINFRARED REFRIGERANT LEAK DETECTION SYSTEM ... provide an alarm output when there is a reduction ... The mains input to

TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual

Page 18 of 57

SET TIME

19:04

Figure 3-11 Set Time Menu Item 3.6.2 Main Menu - Set date

When the SET DATE menu item is entered from the display, shown below in Figure 3-12, the system date may be altered. This real time clock will remain active and maintain an accurate date even when power to the system is turned off.

MAIN MENU

SET DATE

Figure 3-12 Set Date Menu Option

If the SET DATE menu item is selected the user will be prompted to ENTER the desired date, month, and year (dd/mm/yy). The date format is as shown in Figure 3-13 below. When first entered, the date value will flash indicating that this is the active field. Pressing the UP and DOWN keys will alter this field. To accept the displayed value the user must press the SELECT key. The month value will now flash enabling the user to alter this field. Pressing the SELECT key again will set the month value. Pressing the SELECT key again will enable the user to set the year value. The SELECT key in this menu item acts as a toggle between selecting the three date fields. When the desired date has been set the user must press the MENU key to exit the SET DATE menu item and return to the main menu.

SET DATE

08/01/00

Figure 3-13 Set Date Menu Item 3.6.3 Main Menu - Channel Functions

Page 19: TQ 4200 SERIES INFRARED REFRIGERANT LEAK DETECTION · PDF fileINFRARED REFRIGERANT LEAK DETECTION SYSTEM ... provide an alarm output when there is a reduction ... The mains input to

TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual

Page 19 of 57

TECHNICIAN MENU

CHANNEL FUNCTIONS

Figure 3-14 Channel Functions When this menu option is selected, the user is provided with a Channel Functions sub-menu. This sub-menu allows the user to select a particular zone location and then Skip, goto, hold, or remove hold that zone location. When the zone location is in the hold state, that particular zone location will be held for a maximum period of 20 minutes before automatically reverting to normal operation. The user may remove the hold state at any time using the Remove Hold sub menu function. Please note, the channel may alarm and be muted while using this function.

The Skip function allows the user to turn off a redundant zone. This can prove useful if the user requires to do any maintenance on that line or if the line becomes obsolete.

3.6.4 Main Menu - Change Password

The user may change the password if desired. (Default 6197). This is achieved through the CHANGE PASSWORD menu option as shown in Figure 3-15 below:

MAIN MENU

CHANGE PASSWORD

Figure 3-15 Change Password Menu Option

When this option is selected the user is prompted to enter the new password. This procedure is carried out in the same manner as entering password explained previously. Once the new password has been entered the user is prompted to re-enter the new password to ensure that it is the desired password, i.e. to ensure that it was entered correctly the first time. If the password was not entered correctly the display will indicate that an invalid password was entered and prompt the user to repeat the procedure. The user will be prompted a maximum of two times and if the password is still invalid the previous password will take effect. The system will return to the main menu mode.

Page 20: TQ 4200 SERIES INFRARED REFRIGERANT LEAK DETECTION · PDF fileINFRARED REFRIGERANT LEAK DETECTION SYSTEM ... provide an alarm output when there is a reduction ... The mains input to

TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual

Page 20 of 57

3.6.5 Main Menu - Parameters

System parameters may be set and edited by entering the PARAMETERS menu option. This option is shown overleaf in Figure 3-16:

MAIN MENU

PARAMETERS

Figure 3-16 Parameters Menu Option

Once entered, the display will prompt the user to select a desired zone location for editing. The user must press the UP and DOWN keys to display the required zone location and then press the SELECT key to accept that zone location.

When a zone location has been selected, the user may cycle through the Parameters Sub Menu using the UP and DOWN keys and select the required Parameters Sub Menu Item using the SELECT key. A detailed description of the Parameters Sub Menu items now follow:

3.6.5.1 Set Location

The 16 zone locations are set by default to ‘ZONE 1’, ‘ZONE 15’. This option will allow the user to change the name of the zone locations to a more meaningful description up to 16 characters in length, including the <SPACE> character. An example of which is shown in Figure 3-17 below:

PARAMETERS

SET LOCATION

Figure 3-17 Example of Zone Description

The user must use the UP and DOWN keys to cycle through the alphanumeric characters, pressing the SELECT key when the display shows the required character. To leave spaces, select the <SPACE> character and press the SELECT key. When the SELECT key has been pressed the next digit on the right will be displayed.

Page 21: TQ 4200 SERIES INFRARED REFRIGERANT LEAK DETECTION · PDF fileINFRARED REFRIGERANT LEAK DETECTION SYSTEM ... provide an alarm output when there is a reduction ... The mains input to

TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual

Page 21 of 57

PARAMETERS

FRUIT STORE 1

Figure 3-18 Example of Location Name To accept the zone location description the user must press the MENU key to exit the PARAMETERS MENU OPTION.

3.6.5.2 Set Gas Type

This option is used to set a particular gas to a particular zone location. (Refer to page 4 of this manual for refrigerant gas list). The current zone location is the one entered at the beginning of the parameters sub menu. To select a particular gas the user must press the UP and DOWN keys to cycle through the available gases. These gases have already been calibrated via the technical menu using sample line 1. When the desired gas is displayed the user must press the SELECT key to make that gas active for that zone location. This is shown in Figure 3-18 below:

PARAMETERS

SET GAS TYPE

Figure 3-19 Set Gas Type Display

3.6.5.3 Set Alarm 1

This option is used to set the alarm level for Alarm 1. The alarm level is set in conjunction with the SET ALARM TYPE option which will be explained in section 3.6.5.5.

PARAMETERS

SET ALARM 1

Figure 3-20 Set Alarm 1 Option

Page 22: TQ 4200 SERIES INFRARED REFRIGERANT LEAK DETECTION · PDF fileINFRARED REFRIGERANT LEAK DETECTION SYSTEM ... provide an alarm output when there is a reduction ... The mains input to

TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual

Page 22 of 57

When selected this option allows the UP and DOWN keys to set the gas Alarm 1 level. This level is displayed in ppm and can be set in the range 0000ppm to 10,000ppm. To select the desired alarm level the user must press the SELECT key. When the desired alarm level is set the system will go back to the PARAMETERS menu option and prompt the user to select another zone location. If the user wishes to exit the Parameters sub menu the user must select a zone location and use the EXIT SUB MENU option to return to normal system operation. (System default for alarm 1 is set to 1000 ppm).

3.6.5.4 Set Alarm 2 & 3

This option is identical to the SET ALARM 1 menu option but corresponds to Alarm 2 & 3 and works in conjunction with the SET ALARM 2 & 3 TYPE option. (System default for alarm 2 is 1250 ppm and alarm 3 is 1500 ppm).

3.6.5.5 Set Alarm 1 Type

This option is used to select whether an alarm is generated when the concentration is rising (+) or falling (-). When selected the user is presented with the display shown in Figure 3-22 below:

PARAMETERS

SET ALARM 1 TYPE

Figure 3-21 Set Alarm 1 Type Option

To change between positive going and negative going alarm levels the user must toggle between (+) and (-) using the UP and DOWN keys. When the required alarm type is displayed the user must press the SELECT key to enter the alarm type. (System default for alarm 1 is (+)).

3.6.5.6 Set Alarm 2 & 3 Type

This option is identical to the SET ALARM 1 & 3 TYPE described above but corresponds to the Alarm 2. (System default for alarm 2 is (+)).

3.6.5.7 Set Dwell Time

This option allows the user to specify the time in seconds that the system will remain in a particular zone location before sequentially incrementing to the next zone location. The dwell time is variable in the range from 0 to 300 seconds. On start up this is always 20 seconds

Page 23: TQ 4200 SERIES INFRARED REFRIGERANT LEAK DETECTION · PDF fileINFRARED REFRIGERANT LEAK DETECTION SYSTEM ... provide an alarm output when there is a reduction ... The mains input to

TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual

Page 23 of 57

PARAMETERS

SET DWELL TIME

Figure 3-22 Set Dwell Time Option

To change the dwell time for a particular zone the user must press the UP and DOWN keys and the SELECT key when the desired dwell time is displayed. (System default dwell time is 20 seconds).

3.6.5.8 Exit Sub Menu

This option will allow the user to return to the Normal Operating mode and continue sampling the zone locations. The user must press the SELECT key to accept this option.

PARAMETERS

EXIT SUB MENU

Figure 3-23 Exit Sub Menu Option

3.7 Overview of the Alarm Operation As explained previously an alarm condition will occur if the sampled gas level exceeds the set alarm level. That is, for a rising (+) alarm type the alarm will be activated if the sampled gas level is greater than the alarm level, and for a falling (-) alarm type the alarm will be activated if the sampled gas level is less than the alarm level.

When an alarm occurs the zone location, alarm number, and alarm status is displayed on the LCD and the relevant alarm relays are activated. The display will freeze on the first alarm activated and the system will then continue scanning the other zone locations sequentially. If a second alarm is detected while the first alarm is still active, the system will store the zone location, alarm number, and alarm status of the second alarm and place this into a queuing system while still only displaying the first alarm conditions on the LCD. Further alarms will continue to be stored up to a maximum value of 20 alarms. The following sections will describe in detail the various functions available to control the alarm status.

Page 24: TQ 4200 SERIES INFRARED REFRIGERANT LEAK DETECTION · PDF fileINFRARED REFRIGERANT LEAK DETECTION SYSTEM ... provide an alarm output when there is a reduction ... The mains input to

TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual

Page 24 of 57

3.7.1 Alarm Control Functions

3.7.1.1 Main Menu - Mute Alarm (Acknowledge)

This option is used to mute the most recent alarm. When selected on the main menu, the system will display for a period of approximately 5 seconds that the alarm has been acknowledged. This is shown in Figure 3-24 and Figure 3-25 below:

ZONE 1

ALARM 1 ACTIVE

Figure 3-24 Example of Alarm 1 Active

When a mute alarm has been selected the display will be as shown in Figure 3-25 below:

ZONE 1

ALARM 1 ACK

Figure 3-25 Example of alarm mute If no other alarms are active the system will resume normal operation and continue scanning the zone locations. However, if another alarm is active the display will show this active alarm until cleared as shown in Figure 3-26 below:

ZONE 1

ALARM 2 ACTIVE

Figure 3-26 Example of Pending Alarm Active after Mute Alarm

When the user has muted an alarm and the system has cycled through the zone locations back to the muted zone location, that muted zone location will be indicated by a flashing alarm status LED to indicate the alarm location has

Page 25: TQ 4200 SERIES INFRARED REFRIGERANT LEAK DETECTION · PDF fileINFRARED REFRIGERANT LEAK DETECTION SYSTEM ... provide an alarm output when there is a reduction ... The mains input to

TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual

Page 25 of 57

been acknowledged but not reset. The only way to clear a muted zone location is to use the RESET ALARM option.

3.7.1.2 Main Menu - Reset Alarm

This option is used to reset the most recent alarm. The RESET ALARM option may be performed on an active alarm or on a muted alarm. The RESET ALARM function is invoked by pressing the SELECT key when the display is as shown in Figure 3-27 below:

MAIN MENU

RESET ALARM

Figure 3-27 Reset Alarm Menu Option

When selected on the main menu, the system will de-activate the relevant alarm relay and display for a period of approximately 5 seconds that the alarm has been acknowledged. This is shown in Figure 3-28 and Figure 3-29 below:

ZONE 2

ALARM 1 ACTIVE

Figure 3-28 Example of Alarm 1 Active When a Reset Alarm has been selected the display will be as shown in Figure 3-29 below:

ZONE 2

ALARM 1 ACK

Figure 3-29 Example of Alarm Reset

If no other alarms are active the system will resume normal operation and continue scanning the zone locations. However, if another alarm is active the display will show this active alarm until cleared as shown in Figure 3-30 below:

Page 26: TQ 4200 SERIES INFRARED REFRIGERANT LEAK DETECTION · PDF fileINFRARED REFRIGERANT LEAK DETECTION SYSTEM ... provide an alarm output when there is a reduction ... The mains input to

TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual

Page 26 of 57

ZONE 4

ALARM 2 ACTIVE

Figure 3-30 Example of Pending Alarm Active after Reset Alarm

When the user has reset an alarm and the system has cycled through the zone locations back to the reset zone location, then that reset zone location will alarm again if the alarm level has been or still is exceeded.

3.7.1.3 Main Menu - Display Alarms

This option is used to display the last 20 stored alarms.

MAIN MENU

DISPLAY ALARMS

Figure 3-31 Display Alarms Menu Option

The information displayed is the date and time of alarm, zone location and the order that the alarm occurred in. This is as shown in Figure 3-32 below:

ZONE 2 ALARM 4

08/01/00 07:14

Figure 3-32 Example of Display Alarms Information In the example shown in Figure 3-32 above, the alarm number is 4. This implies that this was the fourth alarm to become active. Pressing the SELECT key will display the alarm information for the third alarm to become active. Subsequent presses of the SELECT key will display the second alarm to become active, then the first alarm to become active. When Alarm 1 is displayed, pressing the SELECT key again will return the system to the Normal Operating Mode and the system will continue scanning the zone locations.

Page 27: TQ 4200 SERIES INFRARED REFRIGERANT LEAK DETECTION · PDF fileINFRARED REFRIGERANT LEAK DETECTION SYSTEM ... provide an alarm output when there is a reduction ... The mains input to

TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual

Page 27 of 57

3.7.1.4 Main Menu - Erase Alarms

This option is used to erase the stored alarms. To invoke this function the SELECT key must be pressed by the user on the ERASE ALARMS menu option as shown in Figure 3-33 below:

MAIN MENU

ERASE ALARMS

Figure 3-33 Erase Alarms Menu Option

This option will erase all the stored alarms at once. 3.8 Menu - Technician Menu

MENU

TECHNICIAN MODE

Figure 3-34 Technician Menu Option

This allows the user to define the number channels required by the system, calibrate the pressure being drawn thorough the system or skip a redundant zone. Once entered, the display will prompt the user to enter another password as in Section 3.5 (Entering Main Menu). This password however is different from the one mentioned in Section 3.5 and cannot be changed from the default setting: Phone TQ for Password.

ENTER PASSWORD

****

Figure 3-35 Display Password Prompt

Page 28: TQ 4200 SERIES INFRARED REFRIGERANT LEAK DETECTION · PDF fileINFRARED REFRIGERANT LEAK DETECTION SYSTEM ... provide an alarm output when there is a reduction ... The mains input to

TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual

Page 28 of 57

3.8.1 Technician Menu - Set Number of Zones

When the password has been successfully entered the SET NUMBER OF ZONES menu item appears, shown below in figure 3-36

TECHNICIAN MENU

SET NUMBER OF ZONES

Figure 3-36 Display Set Number of Zones Prompt

If the SET NUMBER OF ZONES menu is selected the user will be prompted to ENTER the number of points to be sampled. The system requires ranging from 1-15; remembering that during installation sample line 0 is reserved as a zero calibration line. Pressing the UP and DOWN buttons will alter this field from the default 15 zones. Then to accept the displayed value the user must press the SELECT buttons. From here the user will return to the technical mode menu. (System default is 15 zones)

3.8.2 Technical Menu - Skip Zone Number

This part of the technical menu allows the user to turn off a redundant zone. This can prove useful if the user requires to do any maintenance on that line or if the line becomes obsolete.

TECHNICAL MENU

SKIP ZONE NUMBER

Figure 3-36 Skip Zone Number

When this menu option is selected the user is prompted to select which zone is to be skipped. Using the UP or DOWN keys will scroll through each zone in operation. When the desired zone is highlighted the SELECT key will accept that zone as the one to be ignored.

Page 29: TQ 4200 SERIES INFRARED REFRIGERANT LEAK DETECTION · PDF fileINFRARED REFRIGERANT LEAK DETECTION SYSTEM ... provide an alarm output when there is a reduction ... The mains input to

TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual

Page 29 of 57

SKIP ZONE NUMBER

ZONE 1

Figure 3-37 Select Zone Number

3.8.2 Technician Menu - Calibrate Pressure

This part of the technical menu is used to calibrate the pressure sensor on the Infra red sensor.

TECHNICIAN MENU

CALIBRATE PRESSURE

Figure 3-37 Calibrate Pressure This is already factory set and should not be attempted by anyone other than TQ personnel.

3.8.3 Technician Menu – Calibrate Gas

This option is factory set and will not require any attention from any one other than TQ personnel.

TECHNICIAN MENU

CALIBRATE GAS

Figure 3-38 Calibrate .

3.8.4 Technician Menu - Set Sensor Range

This part of the Technician Menu will allow the range of the sensor to be changed. The default range is factory set at 2000 ppm. This is already factory set and should not be attempted by anyone other than TQ personnel.

Page 30: TQ 4200 SERIES INFRARED REFRIGERANT LEAK DETECTION · PDF fileINFRARED REFRIGERANT LEAK DETECTION SYSTEM ... provide an alarm output when there is a reduction ... The mains input to

TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual

Page 30 of 57

TECHNICIAN MENU

SET SENSOR RANGE

Figure 3-39 Set Sensor Range 3.8.5 Technician Menu – Exit Menu

From here the user can exit from the technical menu back into the main. To exit the Technical menu, the user must use the UP and DOWN keys to display the EXIT MENU option as shown in Figure 3-40 below:

TECHNICIAN MENU

EXIT SUB MENU

Figure 3-40 Exit Menu

The user must press the SELECT key to invoke this function and return to the Main Menu.

3.9 Menu - Exit Menu

This option is used to exit the Main Menu Mode. To exit the main menu, the user must use the UP and DOWN keys to display the EXIT MENU option as shown in Figure 3-41 below:

MENU

EXIT MENU

Figure 3-41 Menu Exit Option

The user must press the SELECT key to invoke this function and return to the Normal Operating Mode to continue scanning the zone locations.

Page 31: TQ 4200 SERIES INFRARED REFRIGERANT LEAK DETECTION · PDF fileINFRARED REFRIGERANT LEAK DETECTION SYSTEM ... provide an alarm output when there is a reduction ... The mains input to

TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual

Page 31 of 57

4.0 OPERATION

This section explains the TQ4200 main functions and gives an overview of how to deal with the alarms.

Page 32: TQ 4200 SERIES INFRARED REFRIGERANT LEAK DETECTION · PDF fileINFRARED REFRIGERANT LEAK DETECTION SYSTEM ... provide an alarm output when there is a reduction ... The mains input to

TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual

Page 32 of 57

4.1 System warm-up

When the TQ4200 is powered up, the system enters a warm-up period. This warm-up period typically takes about five minutes to complete. During this time the liquid crystal display will indicate that the system is in the warm-up period as shown in Figure 4-2 below:

WARM-UP PERIOD

PLEASE WAIT...

Figure 4-2 Warm-up period 4.2 Normal Operating Mode

After the warm-up period is complete, the system enters the Normal Operating Mode. This mode is indicated by the display shown in Figure 4-3 below:

ZONE 1

R22 00000 ppm

Figure 4-3 Normal Operating Mode

The first line of the display indicates the current zone location. On the second line of the display, the left hand side indicates the sampled gas type and the right hand side indicates the sampled gas concentration in parts per million (ppm).

In Normal Operating Mode, the system will cycle through each zone location performing alarm checks at the end of each zone cycle. The following section describes the alarms.

Page 33: TQ 4200 SERIES INFRARED REFRIGERANT LEAK DETECTION · PDF fileINFRARED REFRIGERANT LEAK DETECTION SYSTEM ... provide an alarm output when there is a reduction ... The mains input to

TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual

Page 33 of 57

4.3 Alarms

The system will generate an alarm under two main conditions. 4.3.1 System Fault

The first of these conditions generates an alarm if the warm-up period has not been completed within 45 minutes of power-on. This will be displayed as a system fault as indicated by Figure 4-4 shown below:

SYSTEM FAULT

Figure 4-4 System Fault

The fault alarm will be activated under this condition. 4.3.2 Gas Level Alarms

The second condition generates an alarm if the sampled gas level exceeds the set alarm point for either Alarm 1 to Alarm 3. When an alarm is generated the TQ4200 displays the zone location, the alarm number, and the alarm status. This is shown in Figure 4-5 below:

ZONE 1

ALARM 1 ACTIVE

Figure 4-5 Alarm Status

The TQ4200 then continues to sample normally. The TQ4200 will continue to display the status of the alarm until the user acknowledges the alarm or alarms.

If a second alarm is activated while the first alarm is still active, the TQ4200 will store the zone location, alarm number, and alarm status of the second

Page 34: TQ 4200 SERIES INFRARED REFRIGERANT LEAK DETECTION · PDF fileINFRARED REFRIGERANT LEAK DETECTION SYSTEM ... provide an alarm output when there is a reduction ... The mains input to

TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual

Page 34 of 57

alarm and place this into a queuing system. Further alarms will continue to be stored up to a maximum value of 20 alarms. To perform any action on a zone that is in alarm, the user must enter a password. To enter the password the user must first press the MENU button. The user is then prompted to enter the password as shown in Figure 4-6 below:

ENTER PASSWORD

****

Figure 4-6 Password Prompt

To enter the password the user must press the UP button and/or DOWN button to change the number. When the required number is displayed the user must press the SELECT button to accept the choice. This is repeated for all four password digits. Once the password has been accepted the user enters the menu mode and the required function may be selected by pressing the UP button and/or DOWN button followed by the SELECT button when the required function is displayed. (System default password is 6197).

4.3.2.1 Mute Alarms

Select the mute alarms menu to mute the most recent alarm. When this function is invoked, the alarm relay will be de-activated and the display will show that the alarm has been acknowledged as shown in Figure 4-7 below:

ZONE 1

ALARM 1 ACK

Figure 4-7 Alarm Acknowledged

If no other alarms are active, the system will resume normal operation and continue scanning the zone locations sequentially. However, if an alarm is pending after the mute function has been selected, this alarm will become the active alarm. To mute this alarm the user must repeat the procedure detailed above. When the zones cycle back to a muted alarm the alarm indication LED’s will flash indicating this alarm has not been reset.

Page 35: TQ 4200 SERIES INFRARED REFRIGERANT LEAK DETECTION · PDF fileINFRARED REFRIGERANT LEAK DETECTION SYSTEM ... provide an alarm output when there is a reduction ... The mains input to

TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual

Page 35 of 57

4.3.2.2 Reset Alarms

Select the ‘Reset Alarms’ menu to reset the most recent alarm. This option may be performed on a muted alarm or an active alarm producing the same effect. When ‘Reset Alarms’ is selected on the main menu, the system will de-activate the most recent alarm relay and display for a period of approximately 5 seconds that the alarm has been acknowledged. The system will then resume normal system operation. However, if more than one alarm has been activated, the above procedure will need to be repeated until all active alarms have been reset.

Page 36: TQ 4200 SERIES INFRARED REFRIGERANT LEAK DETECTION · PDF fileINFRARED REFRIGERANT LEAK DETECTION SYSTEM ... provide an alarm output when there is a reduction ... The mains input to

TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual

Page 36 of 57

Page 37: TQ 4200 SERIES INFRARED REFRIGERANT LEAK DETECTION · PDF fileINFRARED REFRIGERANT LEAK DETECTION SYSTEM ... provide an alarm output when there is a reduction ... The mains input to

TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual

Page 37 of 57

5.0 DRAWINGS

DRAWING NO. DESCRIPTION

Figure 1 PANEL OUTLINE

Figure 2 GLAND PLATE OUTLINE

Figure 3 INTERNAL LAYOUT

Figure 4 PNEUMATIC SCHEMATIC

Figure 5 ELECTRICAL TERMINATION

Figure 6 POWER SUPPLY

Figure 7 SOLENOID VALVE CIRCUIT DIAGRAM

Figure 8 FRONT PANEL CIRCUIT DIAGRAM

Figure 9 OUTPUT RELAY WIRING DIAGRAM

Figure 10 SOLENOID DRIVER BOARD

TERMINAL IDENTIFICATION Figure 11 I.R. DRIVER BOARD CONNECTION

DIAGRAM

Page 38: TQ 4200 SERIES INFRARED REFRIGERANT LEAK DETECTION · PDF fileINFRARED REFRIGERANT LEAK DETECTION SYSTEM ... provide an alarm output when there is a reduction ... The mains input to

TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual

Page 38 of 57

200210

450

490

350

4 x

Mou

ntin

g H

oles

8mm

Dia

pos

ition

ed47

5 H

igh

x 29

0 W

ide.

Hin

ge S

ide

Doo

r Fix

ing

SY

STE

MH

EA

LTH

YA

LAR

M 3

ALA

RM

2A

LAR

M 1

ME

NU

TQ4200

TQ E

NVI

RO

NM

ENTA

L PL

C

Flan

shaw

Way

, Wak

efie

ld, W

Yor

ks E

ngla

nd, W

F2 9

LPTe

l: +

44 (0

)192

4 38

0700

Fa

x: +

44

(0)1

924

3617

00

E

mai

l: S

ales

@tq

plc.

com

web

site

:http

://w

ww

.tqpl

c.co

m

Refrigerant Gas Monitoring System

NO

TES:

1) E

nclo

sure

rate

d at

IP21

Figure 1

Page 39: TQ 4200 SERIES INFRARED REFRIGERANT LEAK DETECTION · PDF fileINFRARED REFRIGERANT LEAK DETECTION SYSTEM ... provide an alarm output when there is a reduction ... The mains input to

TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual

Page 39 of 57

SAM

PLE

LIN

ES

89

1011

1213

1415

SAM

PLE

LIN

ES1

23

45

67

0

Mai

ns C

able

Ent

ry

Ven

t 6m

m B

ulkh

ead

WA

RN

ING

Do

not o

bstru

ct

VFC

Cab

le E

ntry

VFC

Cab

le E

ntry

Zero

cal

ibra

tion

line

mus

t be

conn

ecte

d to

cle

an d

ry a

ir sa

mpl

e or

cha

rcoa

l filt

er a

t all

times

.

15 x

6m

m P

ipe

fitin

gs

Figure 2

Page 40: TQ 4200 SERIES INFRARED REFRIGERANT LEAK DETECTION · PDF fileINFRARED REFRIGERANT LEAK DETECTION SYSTEM ... provide an alarm output when there is a reduction ... The mains input to

TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual

Page 40 of 57

1) S

olen

oids

Mou

nted

in e

ither

of o

utlin

ed

P

o siti

ons D

epe n

ding

on

C

ust o

mer

Spe

cif ic

atio

n.

2) C

ross

Re f

er th

e ci

rcle

d

com

pone

n t Id

entif

icat

i on

n

umbe

rs to

the

parts

list

.

NO

TE:

Sole

noid

Ban

k M

ount

ing

Posi

tion

Pt n

o. 3

70-5

20/5

22

Left

Han

d M

ount

ing

Plat

eR

ight

Han

d M

ount

ing

Plat

e 7

11

CA

TCH

POT

4

7 106

8

15

CONTROL PCB

92

3 PSU

T R U N K I N G

PUM

P

GD

134/

137

INFR

A R

EDSE

NSO

R

1

23

1

23

2414

2212

A2

11

RL4

2414

2212

A2

11

RL3

2414

2212

A2

11

RL2

F2F1

2A Isol

ator

N N

3 N

2 E

1 L

2414

2212

A2

11

RL1

A1

A1

A1

A1

2121

2121

F4F3

21 3

4213

4

21 3

4213

4

21 3

4213

4

21 3

4213

44

56

4

56

7

89

7

89

10

1112

10

1112

21

21

Figure 3

Page 41: TQ 4200 SERIES INFRARED REFRIGERANT LEAK DETECTION · PDF fileINFRARED REFRIGERANT LEAK DETECTION SYSTEM ... provide an alarm output when there is a reduction ... The mains input to

TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual

Page 41 of 57

Pum

p

G D 1 3 4

VEN

T

E xte

rnal

Cut

Off

Cat

ch-p

ot

Pres

sure

Diff

eren

ti al

Switc

h

GD

134

P CB

Sam

ple

Line

s

1 2 3 4 5 6 7 8

ZER

OC

ALI

BR

ATI

ON

LIN

E

+Ve

-Ve

Pres

sure

Diff

eren

tial

Usi

ng V

alve

611

-03 4

F1

9 10 11 12 13 14 15 162 x

8 W

aySo

leno

id B

ank

0 Fitte

d in

top

of C

abin

et

Sing

l e W

aySo

leno

id 9

20-1

02

4mm

OD

PV

C T

ubin

g

Figure 4

Page 42: TQ 4200 SERIES INFRARED REFRIGERANT LEAK DETECTION · PDF fileINFRARED REFRIGERANT LEAK DETECTION SYSTEM ... provide an alarm output when there is a reduction ... The mains input to

TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual

Page 42 of 57

NO

TES:

1) F

or T

erm

inal

wi ri

ng

refe

r to

Drg

. 420

0T, Q

, BE

2) V

isua

l Ala

r m O

/P ra

ted

1

00m

A @

24V

dc

3) A

udio

Ala

rm O

/P

Rat

ed a

t 100

mA

24 V

dc

1

23

AL1

AL2

AL3

RL1

VFC

RL2

RL3

TBF-

05

1

23

2414

2212

A2

11

RL4

2414

2212

A2

11

RL3

2414

2212

A2

11

RL2

F2F1

2A Isol

ator

N N

3 N

2 E

1 LTBF-

0 1

240/

110V

AC

50/6

0Hz

2414

2212

A2

11

RL1

FAU

LTRL4

T B-0

1TB

F -03 0v

24v0v

24v

0v4-20mA

Vis

ual

Aud

ible

4-20mA Gas Concentration Output

CONTROL PCBO/P

A1

A1

A1

A1

2121

2121

F4F3

SENSORPUMP

0v4-20mA 4-20mA Location

Output

TBF -

02

21 3

4

T BF-

04 BA 0V

MO

DB

US

RS

485

OU

TPU

T213

4

21 3

4213

4

21 3

4213

4

21 3

4213

44

56

4

56

7

89

7

89

10

1112

10

1112

Figure 5

Page 43: TQ 4200 SERIES INFRARED REFRIGERANT LEAK DETECTION · PDF fileINFRARED REFRIGERANT LEAK DETECTION SYSTEM ... provide an alarm output when there is a reduction ... The mains input to

TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual

Page 43 of 57

RL1

242 221

G/Y1/2/

3 +

5

13 +

24 -0V

L N E

1

ISO

LATO

R

PUM

P

PSU

1 2 3

CO

NN

6

Con

trol B

oard

1 2

TBF-

03

141 7

10

F3(1

A)

F2(2

A)

F 1(1

A)

12

16

17

240/

110V

ac

50/6

0Hz

2AE M

C

SUPR

ESSO

R

Bro

wn

Blu

e

8 5 -

254V

AC

NO

TES:

1) A

ll w

iring

to b

e

UL

1007

20 A

WG

UO

S.

Vio

let

Bla

ck

12

TBF0

1

+24

+50V

7

3

+24

0V +24

LOC

AL

VIS

UA

L

LOC

AL

AU

DIB

L E

19

CO

NN

15

L N E

40V

Gre

en/Y

ello

w

Red

Bla

ck

4/5/

6/7

F4

12

3

CO

NN

1

17

2

45

67

89

1 3

TB-0

10V

17B

lack

1 7

Bla

ck17

Red

Bla

ck

Red

Red

Blk

Red

13R

ed

14R

ed

15R

ed

15

TB- 0

2TO

GD

1 34

See

dwg

4200

BE

1 2

Figure 6

Page 44: TQ 4200 SERIES INFRARED REFRIGERANT LEAK DETECTION · PDF fileINFRARED REFRIGERANT LEAK DETECTION SYSTEM ... provide an alarm output when there is a reduction ... The mains input to

TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual

Page 44 of 57

1 2 3 4 5 6 7 8 9

SOL

#15

SOL

#14

SOL

#13

S OL

#12

SOL

#11

S OL

#10

S OL

#9

12

34

56

78

9

SOL

#8

SOL

#7

SOL

#6

SOL

#5

SOL

#4

SOL

#3

SOL

#2

SOL

#1

CONN 13

CO

NN

3

+24V

CO

NTR

OL

PCB

Red

61

Bla

ck 6

2

Red

59

Bla

ck 6

0R

ed 5

7

Bla

ck 5

8R

ed 5

5

Bla

ck 5

6R

ed 5

3

Bla

ck 5

4R

ed 5

1

Bla

ck 5

2R

ed 4

9

Bla

ck 5

0R

ed 4

7

Bla

ck 4

8

Red

45

Bla

ck 4

6

Red

43

Bla

ck 4

4R

ed 4

1

Bla

ck 4

2R

ed 3

9

Bla

ck 4

0R

ed 3

7

Bla

ck 3

8R

ed 3

5

Bla

ck 3

6R

ed 3

3

Bla

ck 3

4R

ed 3

1

Bla

ck 3

2

ON

LY IN

CL U

DE

THIS

S EC

TIO

N F

OR

16-

WA

YSY

STEM

S

+24V

21

Red

SOL

#16

123456789

CONN 4

+24V

Red

61

Bla

ck 6

2

ZER

O S

OL

Figure 7

Page 45: TQ 4200 SERIES INFRARED REFRIGERANT LEAK DETECTION · PDF fileINFRARED REFRIGERANT LEAK DETECTION SYSTEM ... provide an alarm output when there is a reduction ... The mains input to

TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual

Page 45 of 57

1 2 3 4 5 6 7 8 9CO

NN

1

N.C

Con

trol P

CB

NO

TES:

1) A

l l W

iring

to b

e

UL 1

007

20A

WG

U.O

.S.

2) M

ultic

ore

To B

e 10

Cor

e

7/ 0

.2m

m O

vera

ll Sc

reen

ed

(FEC

119

026 4

)

1 2 3 4 5 6 7 8 9CO

NN

15

+24V

0V

SYST

E M H

EALT

HY

ALA

RM

3

ALA

RM

2

MEN

U

DO

WN

UP

SEL E

CT

TQ 4

200

FRO

NT

DO

OR

Bla

ck

Gre

en

Blu

e

Ora

nge

Vio

let

Bro

wn

Whi

te

1 7 731971

Red

26

IC1 4

TB-0

1

74

ALA

RM

1

Yel

low

7270

4200

T

24 25

Mul

ticor

eC

able

Figure 8

Page 46: TQ 4200 SERIES INFRARED REFRIGERANT LEAK DETECTION · PDF fileINFRARED REFRIGERANT LEAK DETECTION SYSTEM ... provide an alarm output when there is a reduction ... The mains input to

TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual

Page 46 of 57

1 2 3 4 5 6 7 8 9

CONN 15

+24V

CO

NT R

OL

P CB

RL1

RL2

RL3

A1

A2

A1

A2

A1

A2

Bla

ck

Red

74

70

12

3

AL1

8 1

8 1

8 1

45

6

AL2

78

9

AL3

RL4

A1

A2

8 1

7172

731 9

12 1411

12 1411

1 2 1411

8081

8283

8485

8687

88

4200

Q

Whi

teW

hite

TBF-

05TB

F-05

TBF-

05

Whi

te

1011

12

Faul

t

12 1411

8990

91W

hite

TBF-

05

2842

00S

262524

420 0

S

Figure 9

Page 47: TQ 4200 SERIES INFRARED REFRIGERANT LEAK DETECTION · PDF fileINFRARED REFRIGERANT LEAK DETECTION SYSTEM ... provide an alarm output when there is a reduction ... The mains input to

TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual

Page 47 of 57

CO

NN

9

12

34

56

78

9

1 2 3 4 5 6 7 8 9 1 2 3 4 5 6 7 8 9

12

34

56

78

9

9 8 7 6 5 4 3 2 1

12

31

23

12

3

+24V

SOL

15

SOL

14

SOL

13

SOL

12

SOL

11

SOL

10

SOL

9

+24V

SOL 7

SOL 6

SOL 5

SOL 4

SOL 3

SOL 2

SOL 1

MENU

0V

0V

DOWN

UP

0V

0V

SELECT

CO

MM

S

TO G

D 1

34 IN

FRA

RE D

SEN

SOR

( Ref

er T

o D

wg

4200

BE)

DIS

PLA

YO

/P

70 71 19 73 74

Blu

e

See

Drg

's 42

00R

See

Drg

's 42

00Q

See Drg's 4200Q

BA

BA

SOL 8

0V+2

4+5

0V

Blk

Yel

Grn

Red

32

13

21

32

1

60 58 56 54 52 50 48

46

44

42

40

38

36

34

32

Wht

17

17

Brn

Vio

17

17

Orn

72 64 BLK

SOL

0

4-20

mA

5

+SE

CU

RE

WIT

HTY

RA

P B

ASE

& T

YR

AP

3V

4-20

mA

6

63 RED

SOL

0

SOL

1662

Figure 10

Page 48: TQ 4200 SERIES INFRARED REFRIGERANT LEAK DETECTION · PDF fileINFRARED REFRIGERANT LEAK DETECTION SYSTEM ... provide an alarm output when there is a reduction ... The mains input to

TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual

Page 48 of 57

CO

MM

S

FLY

ING

LE A

DS

FOR

CO

MM

UN

ICA

TIO

NS

AN

D P

OW

ER S

UPP

IED

WIT

H S

ENSO

R

RED

BL

12 0V

4-20mA

34 0V

4-20mA

12

12 B

A

34

0V

TBF-

04

0V

2 C

ore

Twis

ted

Pair

With

Ove

rall

S cre

en17

TBF-

02

24V

DC

F30V TB

- 01TB

-02

56

Pink

Pink

Bla

ck

NO

TES:

1) A

ll w

iring

to b

e

UL

1007

20A

WG

UO

S.

Figure 11

Page 49: TQ 4200 SERIES INFRARED REFRIGERANT LEAK DETECTION · PDF fileINFRARED REFRIGERANT LEAK DETECTION SYSTEM ... provide an alarm output when there is a reduction ... The mains input to

TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual

Page 49 of 57

6.0 MAINTENANCE

Preventative maintenance requirements on the system have been designed to be

minimal and limited. The details of this maintenance plan are as follows:-

6.1 Weekly

Check external ‘catchpot’ located on the right hand side of the TQ4200 enclosure for water ingress. (See Figure 1).

To drain off water turn the bleed screw on the bottom of the bowl anti-

clockwise as you look at the bottom of the catchpot. Ensure that the bleed screw is turned full clockwise on completion of draining.

6.2 Annually

6.2.1 Replace the particulate filter (Part No. 420-026).

Power down. Locate filter ‘F1’ loose in the lower right hand side of the cabinet, refer to figure 3, Note the direction of flow arrow on the body. Remove pipe from each side change filter and refit in the reverse of above.

6.2.2 Replace the end of line filters (Part No. 420-006).

Locate filters at the sample points, unscrew the end cap and change filter element, and refit end cap.

6.2.3 Replace the charcoal filter (Part No. 420-004) fitted to the

calibration line on sample inlet ‘O’. Locate the filter fitted to the calibration line and remove by undoing the compression nut. Remove the nut from the old filter and place over the new filter port. Place the new brass 1/4” ferrule set supplied, over the same port with the cone front ferrule pointing towards the bulkhead fitting. Push new filter port into the bulkhead fitting and screw on compression nut until finger tight. Mark the nut and bulkhead fitting and tighten the compression nut ¾ to 1.0 turn.

6.2.4 Replace the pump diaphragm and seals (Part No. 920-031). Locate the sample pump, refer figure 3, remove the four screws securing the square pump housing cover plate. Remove the two seals and diaphragm, fit the new items and refit cover

plate.

Page 50: TQ 4200 SERIES INFRARED REFRIGERANT LEAK DETECTION · PDF fileINFRARED REFRIGERANT LEAK DETECTION SYSTEM ... provide an alarm output when there is a reduction ... The mains input to

TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual

Page 50 of 57

6.3 3 Yearly

6.3.1 Replace sample pump Pt No 920-030.

N.B However, it may be more feasible to adopt a ‘breakdown only’ approach to maintaining the system as the repairs are relatively simple and the system will always fail safe. The expected failures will be water ingress to external catchpot as above, filter blockages and pump failure all of which will generate alarms

Page 51: TQ 4200 SERIES INFRARED REFRIGERANT LEAK DETECTION · PDF fileINFRARED REFRIGERANT LEAK DETECTION SYSTEM ... provide an alarm output when there is a reduction ... The mains input to

TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual

Page 51 of 57

7.0 PARTS LIST

The following pages contain the parts list for the TQ4200 and cross refer to figure 3

ITEM PART NO DESCRIPTION QTY NAME 1. 920-020 Solenoid Bank 2 2. 710-028 PSU 1 3. 710-028A PSU Cover 1 4. 920-030 Sample Pump 1 5. 100-038 Catchpot 1 6. 905-011 Isolator 1 7. 100-041 EMC Suppresser 1 8. 910-009 Relay 4 9. 370-351 4200 Controller PCB 1 10. 420-026 Disposable Filter 1 11. 134-001 GD 134 Infrared Sensor 1 TARGET GAS TO BE

SPECIFIED ON ORDER Figure 12

Page 52: TQ 4200 SERIES INFRARED REFRIGERANT LEAK DETECTION · PDF fileINFRARED REFRIGERANT LEAK DETECTION SYSTEM ... provide an alarm output when there is a reduction ... The mains input to

TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual

Page 52 of 57

Page 53: TQ 4200 SERIES INFRARED REFRIGERANT LEAK DETECTION · PDF fileINFRARED REFRIGERANT LEAK DETECTION SYSTEM ... provide an alarm output when there is a reduction ... The mains input to

TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual

Page 53 of 57

8.0 FAULT FINDING

The TQ 4200 has built in fault diagnostics which constantly monitor the operation of the unit and in the event of detecting a fault will indicate a ‘Fault’ followed by: - ANALYSER NVRAM FAIL - 4200 NVRAM FAIL - SENSOR COMMS FAIL - 4200 COMMS FAIL - ZERO FILTER BLOCKED - FLOW FAIL - NO PRESSURE

- SENSOR DRIFT - SENSOR FAULT

Please note that all fault alarms are latched and require an alarm reset as per section 4.3.2.2. ‘Fault’ will remain displayed until all faults have been cleared.

8.1 Analyser NVRAM Fault

FAULT

ANALYSER NVRAM FAIL

Figure 8.1 Faults – Analyser NVRAM Fail

‘Analyser NVRAM Fail’ will be displayed when the gas analyser board has failed to write or read the correct values to or from its’ non-volatile RAM.

Page 54: TQ 4200 SERIES INFRARED REFRIGERANT LEAK DETECTION · PDF fileINFRARED REFRIGERANT LEAK DETECTION SYSTEM ... provide an alarm output when there is a reduction ... The mains input to

TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual

Page 54 of 57

8.2 4200 NVRAM Fault

FAULT

4200 NVRAM FAIL

Figure 8.2 Faults – OMNICA NVRAM Fail

‘4200 NVRAM Fail’ will be displayed when the TQ 4200 has failed to write or read the correct values to or from its’ non-volatile RAM.

8.3 Sensor Communications Fault

FAULT

SENSOR COMMS FAIL

Figure 8.3 Faults – Sensor Communications Fail

‘Sensor Comms Fail’ will be displayed when there is a communications failure between the infrared sensor and the analyser board.

8.4 4200 Communications Fault

FAULT

4200 COMMS FAIL

Figure 8.4 Faults – OMNICA Communications Fail

‘4200 Comms Fail’ will be displayed when there is a communications failure between the TQ 4200 and the gas analyser board.

Page 55: TQ 4200 SERIES INFRARED REFRIGERANT LEAK DETECTION · PDF fileINFRARED REFRIGERANT LEAK DETECTION SYSTEM ... provide an alarm output when there is a reduction ... The mains input to

TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual

Page 55 of 57

8.5 Zero Filter Blocked Fault

FAULT

ZERO FILTER BLOCKED

Figure 8.5 Faults – Zero Filter Blocked

‘Zero Filter Blocked’ will be displayed when the differential pressure sensor on the gas analyser PCB is not sensing its’ correct air pressures when the Zero line solenoid is activated.

Rectification: - Check pump operation. - Check solenoid valve operation.

- Check for security and integrity of all TQ 4200 internal pipe work and fittings.

- Disconnect the ‘Zero line’ from inlet to TQ 4200.

If ‘Zero Filter Blocked’ clears after an alarm reset, check and replace charcoal filter, if necessary. Please note that the ‘Zero Filter Blocked’ alarm requires an alarm reset as it is a latched alarm.

8.6 Flow Fail Fault

FLOW FAIL

ZONE 4

Figure 8.6 Faults – Flow Fail

‘Flow Fail’ will be displayed when the differential pressure sensor on the gas analyser PCB is not sensing its’ correct air pressures. The zone location where the flow fail happened is displayed and the System Healthy LED will extinguish. The system will continue to sample

Page 56: TQ 4200 SERIES INFRARED REFRIGERANT LEAK DETECTION · PDF fileINFRARED REFRIGERANT LEAK DETECTION SYSTEM ... provide an alarm output when there is a reduction ... The mains input to

TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual

Page 56 of 57

normally but if a gas alarm occurs while still in flow fail, the gas alarm will take precedence over the flow fail alarm, displaying the gas alarm and zone location. The system Healthy LED will however, remain extinguished until a reset has been performed.

Rectification: - Check pump operation. - Check solenoid valve operation.

- Check for security and integrity of all TQ 4200 internal pipe work and fittings.

- Disconnect selected ‘sample line’ from inlet to TQ 4200.

If ‘flow fail’ clears after an alarm reset, check sample line for blockages.

Please note that the ‘flow alarm’ requires an alarm reset as it is a latched alarm.

8.7 No Pressure Fault

FAULT

NO PRESSURE

Figure 8.7 Faults – No Pressure

‘No Pressure’ will be displayed when the TQ 4200 has failed its’ 24 hour pressure test. This indicates a leak within the system. Rectification - Check TQ 4200 internal pipe work for integrity and security of all pipe work and fittings.

Page 57: TQ 4200 SERIES INFRARED REFRIGERANT LEAK DETECTION · PDF fileINFRARED REFRIGERANT LEAK DETECTION SYSTEM ... provide an alarm output when there is a reduction ... The mains input to

TQ ENVIRONMENTAL PLC TQ 4200 Mk II Product Manual

Page 57 of 57

8.8 Sensor Drift Fault

FAULT

SENSOR DRIFT

Figure 8.8 Faults – Sensor Drift

‘Sensor Drift’ will be displayed if the sensor’s base zero level has changed more than a pre-defined percentage change when performing an auto-zero.

8.9 Sensor Fault

FAULT

SENSOR FAULT

Figure 8.9 Faults – Sensor Fault

‘Sensor Fault’ will be displayed when the digital output of the sensor falls below a pre-determined value. This value corresponds to a 2mA output.