TOWN OF ENFIELD, CT
Transcript of TOWN OF ENFIELD, CT
ENFIELD ANNEXPOOL MECHANICAL
ROOM UPGRADES
85 Devonshire Street, 3rd Floor, Boston, M.A. 02109
SITE LAYOUT AND NOTES
DEMOLITION PLAN
POOL SCHEMATIC AND EQUIPMENT LIST
PROPOSED IMPROVEMENTS
DETAILS
LIST OF DRAWINGS
AQ001
AQD100
AQ100
AQ101
AQ102
124 North Maple St,
Enfield, CT 06082
CONSTRUCTIONDOCUMENTS 09/20/2019
LOCATION PLANN.T.S
CHRISTOPHER W. BROMSONTOWN MANAGER
MICHAEL S. LUDWICKMAYOR
DONALD T. NUNES, MLADIRECTOR OF PUBLIC WORKS
N
Tel. 617-412-4480
www.westonandsampson.com
800.SAMPSON
PROJECT LOCATION PLANN.T.S
N
THE ELECTRICAL CONTRACTOR SHALL GROUND AND BOND ALL ELECTRICAL EQUIPMENT, POOL
REINFORCING, POOL ACCESSORIES, AND PIPING IN ACCORDANCE WITH NATIONAL ELECTRIC CODE
REQUIREMENTS, ARTICLE 680. THE ELECTRICAL CONTRACTOR SHALL OBTAIN A COPY OF ALL
APPLICABLE LOCAL STATE ELECTRICAL CODE REGULATIONS.
TOWN OF ENFIELD, CT
AQ103 DETAILS CONT'D
E100 ELECTRICAL DIAGRAMS AND DETAILS
FM
PROPOSED MECHANICAL ROOM IMPROVEMENTS
SCALE: 1/2" = 1'-0"
Project:
Drawing Title:
TOWN OF ENFIELD, CT
Enfield Annex Pool
Mechanical Room
Upgrades
124 North Main Street
Enfield, CT 06082
Sheet Number:
Consultants:
Rev Date Description
Seal:
CONSTRUCTION
DOCUMENTS
Scale:
Drawn By:
Reviewed By:
Checked By:
Revisions:
Date:
Approved By:
09.20.2019
COPYRIGHT 2019 WESTON & SAMPSON
617.412.4480
www.westonandsampson.com
800.SAMPSON
85 Devonshire Street,
3rd Floor, Boston, MA 02109
THE ELECTRICAL CONTRACTOR SHALL GROUND AND BOND ALL ELECTRICAL EQUIPMENT, POOL
REINFORCING, POOL ACCESSORIES, AND PIPING IN ACCORDANCE WITH NATIONAL ELECTRIC CODE
REQUIREMENTS, ARTICLE 680. THE ELECTRICAL CONTRACTOR SHALL OBTAIN A COPY OF ALL
APPLICABLE LOCAL STATE ELECTRICAL CODE REGULATIONS.
MES
SMB
MPM
CBW
AS NOTED
AQ001
SITE LAYOUT AND NOTES
ENGINEER SEAL:
1. THESE DRAWINGS HAVE BEEN PREPARED FOR EXCLUSIVE USE FOR THE
CLIENT AND ARE NOT INTENDED FOR ANY OTHER PURPOSE. TO THE BEST
OF MY KNOWLEDGE, THESE DRAWINGS MEET THE REQUIREMENTS SET
FORTH BY THE CONNECTICUT DEPARTMENT OF PUBLIC HEALTH (DPH).
2. THE POOL MECHANICAL ROOM THAT IS INCORPORATED INTO THESE
DRAWINGS SHALL BE CONSTRUCTED IN STRICT ACCORDANCE WITH THE
APPROVED DRAWINGS IN ORDER TO QUALIFY FOR A DPH OPERATING
PERMIT. ALL CHANGES SHALL HAVE WRITTEN APPROVAL FROM WESTON &
SAMPSON AND DPH PRIOR TO SUCH CHANGE OR ALTERATION BEING
IMPLEMENTED.
3. ONLY DRAWINGS FROM WESTON & SAMPSON THAT ARE MARKED "FOR
CONSTRUCTION" AND WITH THE DPH APPROVAL NUMBERS AND APPROVAL
DATES AFFIXED SHALL BE USED FOR THE POOL CONSTRUCTION
IMPLEMENTATION.
DEFINITIONS:
1. CONTRACTOR: PERSON OR ENTITY AUTHORIZED TO CONSTRUCT, INSTALL
AND OPERATE A COMMERCIAL POOL, SPA AND THEIR APPURTENANCES.
2. CRITICAL: THIS WORD DESCRIBES DIMENSIONS THAT SHALL NOT BE
SUBJECT TO DEVIATION OR ERRORS FOR ANY REASON. VIOLATION OF A
CRITICAL DIMENSION MIGHT SUBJECT THE POOL TO A POTENTIAL
VARIANCE ACTION OR A PERMANENT WITHHOLDING OF A FUTURE
OPERATING CERTIFICATE. WESTON & SAMPSON CONSIDERS ALL
DIMENSIONS CONTAINED WITH THE DRAWINGS AS VITAL; HOWEVER, THE
WORD CRITICAL IS ADDED TO ATTRACT THE ATTENTION OF THE
CONTRACTOR.
3. PROVIDE: OBTAIN, PURCHASE, SUPPLY, INSTALL, COMMISSION AND
WARRANTY COMPLETELY IN ACCORDANCE WITH ALL CODES, RULES,
REGULATIONS AND THE REQUIREMENTS OF THE DRAWINGS AND
TECHNICAL SPECIFICATIONS.
4. SLIP-RESISTANT: A HORIZONTAL, NON-SKID TEXTURED SURFACE WITH A
COEFFICIENT OF FRICTION RATED AT A MINIMUM 0.6. THE RESPONSIBILITY
FOR VERIFICATION AND CONFIRMATION OF COMPLIANCE WITH THIS
FRICTION REQUIREMENT IS SOLELY THAT OF THE CONTRACTOR.
CERTIFIED MANUFACTURER BROCHURES MAY BE SUBMITTED TO WESTON
& SAMPSON FOR APPROVAL. THE TERM "NON-SLIP" SHALL BE CONSIDERED
THE SAME AS "SLIP-RESISTANT".
PIPING INSTALLATION REQUIREMENTS:
1. ALL PIPING SHALL BE SCHEDULE 80 PVC. ALL PIPING SHALL BE STAMPED
WITH THE MANUFACTURER'S MARKING THAT IT IS APPROVED FOR USE
WITH POTABLE WATER (NSF-PW). PLASTIC PIPE EXPOSED TO SUNLIGHT
SHALL BE COATED FOR UV PROTECTION.
2. THE PIPING DIAGRAMS AND SIZES SHOWN IN THESE DRAWINGS SHALL BE
FOLLOWED WITHOUT EXCEPTION UNLESS WRITTEN AUTHORIZATION FROM
ENGINEER IS PROVIDED.
3. THE PIPING SYSTEMS INDICATED IN THESE DRAWINGS ARE SHOWN IN A
DIAGRAMMATIC VIEW ONLY. THE CONTRACTOR SHALL PROVIDE ALL PIPING
AND FITTINGS REQUIRED FOR THE COMPLETE INSTALLATION.
4. THE CONTRACTOR SHALL PROVIDE AND COMPLY WITH ALL PIPING
INSPECTIONS THAT MAY BE REQUIRED BY DPH AND LOCAL BUILDING
OFFICIALS.
5. THE CONTRACTOR SHALL PROVIDE PIPE HANGER DETAILS TO ENGINEER
FOR WRITTEN APPROVAL PRIOR TO THE INSTALLATION.
6. THE MAIN DRAIN PIPING SHALL BE INSTALLED TO COMPLY WITH THE
FOLLOWING REQUIREMENTS:
A. THE MAIN DRAIN GRAVITY FLOW PIPE SHALL HAVE A SLOPE TOWARD
THE COLLECTOR TANK.
B. AT NO POSITION SHALL THE MAIN DRAIN PIPING CHANGE SLOPES SO
AS TO ALLOW AN AIR POCKET OR TRAP TO OCCUR.
8. THE STATIC PIPING SHALL BE INSTALLED TO COMPLY WITH THE
FOLLOWING REQUIREMENTS:
A. THE STATIC PIPING SHALL BE INSTALLED SO AS TO ALLOW THE
STATIC PIPE TO HAVE A SLOPE DOWNWARD TOWARD THE
COLLECTOR TANK.
9. PIPING PRESSURE TESTING SHALL BE COORDINATED BY THE POOL
CONTRACTOR AND SHALL BE INCLUDED IN HIS COST. THE ENGINEER
SHALL BE ONSITE DURING PRESSURE TESTING. ALL PIPING SHALL
CONFORM TO ACCEPTED WORKMANSHIP STANDARDS AND SHALL BE
TESTED AS FOLLOWS:
A. ALL PIPING SHALL BE TESTED BY MEANS OF WATER PRESSURE.
B. GRAVITY PIPING SHALL BE TESTED TO 10 PSI.
i. GRAVITY PIPING SHALL BE DEFINED AS MAIN DRAIN PIPING,
GUTTER DRAINAGE PIPING, AUTO FILL PIPING OR SENSING
PIPING, OR ANY PIPING WHICH SHALL NOT HAVE FLOW
VELOCITIES THAT EXCEED 3 FEET PER SECOND.
C. PRESSURE PIPING SHALL BE TESTED TO 35 PSI.
i. PRESSURE PIPING SHALL BE DEFINED AS PUMP SUCTION PIPING,
AND ANY PIPING AFTER THE PUMP DISCHARGE, OR ANY PIPING
WHICH WILL HAVE FLOW VELOCITIES EXCEEDING 3 FEET PER
SECOND BUT NOT TO EXCEED 10 FEET PER SECOND.
POOL EQUIPMENT ROOM REQUIREMENTS:
1. CO2 TANKS SHALL BE ANCHORED TO THE WALL WITH CHAINS.
2. IN ORDER TO VIBRATION ISOLATE THE FILTER AND FEATURE PUMPS FROM THE
FLOOR, THE PUMPS SHALL EACH BE MOUNTED TO A 1/4-INCH THICK STAINLESS
STEEL PLATE AND NEOPRENE PADS SHALL BE PLACED BETWEEN THE STAINLESS
STEEL PLATE AND THE FLOOR. NEOPRENE PADS SHALL BE EQUIVALENT TO THE
MASON INDUSTRIES TYPE SUPER W PADS. THE PADS SHALL BE SIZED TO
PROVIDE A MINIMUM OF 0.15-INCH STATIC DEFLECTION UNDER THE WEIGHT OF
THE PUMP.
DESIGN CODE COMPLIANCE:
19-13-B33b. PUBLIC POOLS CONNECTICUT MINIMUM STANDARDS FOR SWIMMING POOLS...........09/21/2004
CT STATE BUILDING CODE...................................................................................................................................2018
CONNECTICUT PUBLIC SWIMMING POOL DESIGN GUIDE............................................................................1/2010
AMERICAN NATIONAL STANDARDS FOR PUBLIC POOLS - ANSI/APSP/ICC-1................................................2014
NATIONAL ELECTRICAL CODE(NFPA 70)............................................................................................................2014
VIRGINIA GRAEME BAKER POOL AND SPA SAFETY ACT................................................................................ 2008
ADA STANDARDS FOR ACCESSIBLE DESIGN.....................................................................................................2010
COORDINATION NOTES:
THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION OF
THE FOLLOWING FEATURES;
· MUNICIPAL WATER SUPPLY TO COLLECTOR TANKS WITH BACK FLOW
PREVENTION.
· WASTEWATER REMOVAL FROM EQUIPMENT ROOM SHALL DISCHARGE TO
MUNICIPAL WASTEWATER SYSTEM.
· CONFIGURE PUMP, BACKWASH PUMP, CONTROLS, UV, AND ALL LINE
VOLTAGE WITH ELECTRICAL CONTRACTOR.
· CONNECT ALL METALLIC ITEMS FOUND WITHIN THE BOUNDS OF THE
EQUIPMENT BOND, INTO THE EQUIPOTENTIAL BOND.
FAILURE TO COORDINATE THESE ISSUES CAN RESULT IN SIGNIFICANT DPH
PENALTIES UPON COMPLETION OF THE PROJECT.
ELECTRIC:
1. ALL WIRING INSIDE THE POOL EQUIPMENT AREA ROOM OR ENCLOSURE SHALL
BE ENCASED IN APPROVED RIGID PVC CONDUIT.
2. ALL ELECTRICAL WORK (GFI'S, TRANSFORMERS, TIMER SWITCHES,
EMERGENCY CUTOFF SWITCHES, GROUNDING, ETC.) SHALL BE PROVIDED BY
THE CONTRACTOR.
3. ALL ELECTRICAL EQUIPMENT AND INSTALLATIONS INCLUDING GROUNDING OF
METAL EQUIPMENT ARE TO MEET OR EXCEED THE NATIONAL ELECTRICAL
CODE, LATEST EDITION. ELECTRICALLY BOND AND GROUND EACH METALLIC
DEVICE WITH A #8 SOLID COPPER "THWN" INSULATED GROUND WIRE IN
ACCORDANCE WITH THE NEC REQUIREMENTS (AS WELL AS LOCAL CODES)
APPLY SCOTCHCAST #2135 POTTING KIT (BY 3M) AT EACH GROUNDING LUG,
EQUIPMENT ATTACHMENT, AND REBAR JUNCTURE. ALL GROUND WIRES SHALL
BE HIDDEN OR DISGUISED.
4. NO OVERHEAD WIRING SHALL BE PLACED WITHIN 10-FEET HORIZONTAL OF
THE INSIDE EDGE OF POOL WALL.
WATER SUPPLY REQUIREMENTS:
1. WATER INTRODUCED INTO THE POOL SYSTEM SHALL BE SUPPLIED
THROUGH AN AIR GAP. THE AIR GAP SHALL BE TWICE THE SIZE OF THE PIPE
DIAMETER WITH A MINIMUM OF 3”, OR AS SHOWN ON CONTRACT PLANS.
THIS IS REQUIRED TO COMPLY WITH THE REQUIREMENTS OF PUBLIC
HEALTH CODE, SECTION 19-13-B37, SECTION 19-13-B38(B), AND SECTION
19-13-B45.
2. PROVIDE AN ACCEPTABLE COLD WATER SUPPLY TO THE FILTRATION
SYSTEM WITH A MINIMUM OF 60-PSI AVAILABLE PRESSURE. POTABLE
WATER QUALITY SHALL COMPLY WITH DPH REQUIREMENTS.
3. ALL PVC PIPING EXPOSED TO SUNLIGHT AND UV RAYS SHALL BE
PROTECTED FROM DEGRADATION BY APPLYING AN ULTRAVIOLET
RESISTANT COATING.
CONCRETE REQUIREMENTS:
1. ALL CONCRETE SHALL CONFORM TO THE BUILDING CODE REQUIREMENTS FOR
REINFORCED CONCRETE (ACI 318). THE STANDARD SPECIFICATION FOR STRUCTURAL
CONCRETE IN BUILDINGS (ACI 301) AND LOCAL BUILDING CODES. ALL CONCRETE
WORK SHALL BE AS SPECIFIED AND RECOMMENDED BY ACI FIELD REFERENCE
MANUAL SP-MNL-15.
2. ALL CONCRETE USED FOR SLABS AND WALLS IN TANKS SHALL HAVE A MINIMUM
COMPRESSION STRENGTH OF 4,000PSI AT 28 DAYS. CONCRETE FOR SLABS AND
WALLS NOT IN TANKS SHALL HAVE A MINIMUM COMPRESSION STRENGTH OF 4,000PSI
AT 28 DAYS.
3. PROVIDE 6%±1% AIR-ENTRAINMENT FOR ALL CONCRETE EXPOSED TO EARTH OR
WEATHER.
4. ALL REINFORCING SHALL BE GAGE 4X4-W4.0X4.0 WWF OR #4 BAR 12" ON CENTER
EACH WAY UNLESS OTHERWISE NOTED.
5. ALL REINFORCING BARS SHALL BE DEFORMED BARS CONFORMING TO
REQUIREMENTS OF ASTM SPECIFICATION A615, GRADE 60.
6. ALL WELDED WIRE FABRIC (WWF) SHALL BE PLAIN, COLD DRAWN, ELECTRICALLY
WELDED REINFORCING CONFORMING TO THE REQUIREMENTS OF ASTM 185. SUPPLY
WELDED WIRE REINFORCING IN FLAT SHEETS, LAP SHEETS 1-1/12 MESH.
7. ALL REINFORCING MARKED CONTINUOUS SHALL HAVE LAPS CONFORMING TO THE
REQUIREMENTS OF ACI 318 AT SPLICES AND CORNERS AND SHALL BE HOOKED OR
EXTENDED A MIN. OF 40 BAR DIAMETERS AT NON-CONTINUOUS ENDS. TOP BARS
SHALL BE LAPPED AT MID SPAN, BOTTOM BARS SHALL BE LAPPED AT SUPPORTS.
8. REINFORCING SHALL BE SECURELY TIED IN ITS PROPER PLACE BEFORE AND DURING
POURING OPERATIONS USING APPROVED CHAIRS AND SPACERS AS REQUIRED.
9. THE CONCRETE CONTRACTOR SHALL INSTALL OR GIVE OTHER TRADES AMPLE
OPPORTUNITY TO INSTALL ALL ANCHORS BOLTS, PLATES, NAILS, SLOTS, CHASES
PIPE SLEEVES ETC. AS REQUIRED BY THESE TRADES. THE CONTRACTOR SHALL
VERIFY ALL DIMENSIONS BEFORE SETTING SCREEDS AND FORMS.
10. DO NOT CUT OR DISPLACE REINFORCING STEEL TO ACCOMMODATE INSTALLATION
OF EMBEDDED ITEMS UNLESS APPROVED BY THE ARCHITECT. COORDINATE
INSTALLATION OF SLEEVES, PIPES AND CONDUIT WITH THE PLACING OF
REINFORCING STEEL TO ENSURE THAT IT DOES NOT NEED TO BE CUT OR DISPLACED.
11. NOTIFY THE ARCHITECT OF ANY CONCRETE PLACEMENT AT LEAST 24 HOURS IN
ADVANCE, TO ALLOW INSPECTION OF THE REINFORCING STEEL. DO NOT PLACE
CONCRETE UNTIL THIS INSPECTION HAS BEEN MADE OR WAIVED BY THE ENGINEER.
12. WATERSTOPS TO BE GREENSTREAK 717, 6" CENTER BULB STYLE.
13. NO ACCELERANT OR RETARDANT ADMIXTURES SHALL BE ADDED TO THE MIX UNLESS
APPROVED BY THE ENGINEER.
14. NO RED BRICK SUPPORTS SHALL BE USED, ONLY CONCRETE BLOCK.
15. AT ALL PENETRATIONS THE CONTRACTOR SHALL INSTALL REBAR ON 45 DEGREE
ANGLES.
REMOVE EXISTING FILTER PUMP
AND TURN OVER TO OWNER
REMOVE AND DISPOSE OF
EXISTING HEAT EXCHANGER
REMOVE AND DISPOSE OF
EXISTING CHEMICAL FEEDER
PROTECT AND MAINTAIN EXISTING
CHEMICAL CONTROLLER
REMOVE AND DISPOSE
OF EXISTING FILTER
REMOVE AND DISPOSE OF EXISTING
CHEMICAL STORAGE TANK
PROTECT AND
MAINTAIN EXISTING
FLOOR DRAIN
REMOVE AND DISPOSE OF
EXISTING PIPING AS NEEDED
TO INSTALL NEW EQUIPMENT
PROTECT AND MAINTAIN
PROTECT AND MAINTAIN
REMOVE AND REINSTALL
REMOVE AND DISPOSE OF
8-IN GUTTER
EXISTING CHEMICAL CONTROLLER
EXISTING CHEMICAL FEEDER
EXISTING HEAT EXCHANGER
EXISTING CHEMICAL STORAGE TANK
10'-6"
36'-0"
EXISTING FILTER
EXISTING CO2 FEEDER
EXISTING
EYEWASH STATION
EXISTING STRAINER
EXISTING BACKWASH LINE
TIES INTO 4-IN DECK DRAIN LINE
EXISTING POOL EMPTYING LINE
TIES INTO 4-IN DECK DRAIN LINE
EXISTING FLOOR DRAIN
EXISTING HOUSEKEEPING PAD
EXISTING HOUSEKEEPING PAD
5'-9"
EXISTING 4-IN
DECK DRAIN LINE
4-IN SYSTEM DRAIN INTO
4-IN DECK DRAIN LINE
6-IN MAIN DRAIN BELOW
6-IN RETURN ABOVE
EXISTING FILTER PUMP
REMOVE AND DISPOSE OF
EXISTING CO2
REGULATOR SYSTEM
EXISTING MECHANICAL
ROOM WALLS
CAP EXISTING
LEAVE PORTION OF
EXISTING PIPE FOR NEW
PIPE TO CONNECT TO
EXISTING DOUBLE DOOR
REMOVE EXISTING CONNECTION AND
CAP OLD BACKWASH LINE
EXISTING MECHANICAL ROOM
SCALE: 1/2" = 1'-0"
Project:
Drawing Title:
TOWN OF ENFIELD, CT
Enfield Annex Pool
Mechanical Room
Upgrades
124 North Main Street
Enfield, CT 06082
Sheet Number:
Consultants:
Rev Date Description
Seal:
CONSTRUCTION
DOCUMENTS
Scale:
Drawn By:
Reviewed By:
Checked By:
Revisions:
Date:
Approved By:
09.20.2019
COPYRIGHT 2019 WESTON & SAMPSON
617.412.4480
www.westonandsampson.com
800.SAMPSON
85 Devonshire Street,
3rd Floor, Boston, MA 02109
THE ELECTRICAL CONTRACTOR SHALL GROUND AND BOND ALL ELECTRICAL EQUIPMENT, POOL
REINFORCING, POOL ACCESSORIES, AND PIPING IN ACCORDANCE WITH NATIONAL ELECTRIC CODE
REQUIREMENTS, ARTICLE 680. THE ELECTRICAL CONTRACTOR SHALL OBTAIN A COPY OF ALL
APPLICABLE LOCAL STATE ELECTRICAL CODE REGULATIONS.
MES
SMB
MPM
CBW
AS NOTED
NOTE: LOOK TO AQ101 FOR ALL PROPOSED EQUIPMENT REPLACEMENTS.
AQD100
DEMOLITION PLAN
NOTES:
1. REMOVE AND DISPOSE OF EXISTING CHEMICAL STORAGE TANK AND CHEMICAL FEEDER.
2. REMOVE AND DISPOSE OF EXISTING SAND FILTER AND SAND MEDIA.
3. REMOVE AND DISPOSE OF ALL EXISTING INTERIOR PIPING, VALVES, FITTINGS, AND HANGERS/PIPE
SUPPORTS UP TO THE BOTTOM OF THE GUTTER CONVERTER.
4. REMOVE AND DISPOSE OF EXISTING PUMP, PUMP DRIVES AND PUMP CONTROLS.
5. REMOVE AND DISPOSE OF ANY CONCRETE PUMP PEDESTALS OR HOUSEKEEPING PADS UTILIZED BY
EXISTING EQUIPMENT.
6. PROTECT EXISTING FLOOR SLAB IN BUILDING.
7. REMOVE AND DISPOSE OF EXISTING MAIN DRAIN GRATES.
8. REMOVE AND DISPOSE OF EXISTING AUTOFILL SYSTEM.
9. POOL CONTRACTOR SHALL DRAIN THE POOL.
10. REMOVE AND DISPOSE OF EXISTING HEATER SYSTEM AND CONTROLS.
11. REMOVE AND DISPOSE OF EXISTING HOUSEKEEPING PADS AND PUMP PEDESTALS.
REMOVE AND DISPOSE
EXISTING
LEGEND:
MECHANICAL ROOM
POOL SUCTION/GRAVITY PIPING & FITTINGS
COMPOUND PRESSURE GAUGE
FLOW METER
MAIN DRAINS
BUTTERFLY VALVE
MANUAL/AUTO MAKEUP WATER
BASKET STRAINER
SYMBOL LEGEND
WALL GUTTER
STAND PIPE/FILL FUNNEL
PRESSURE GAUGE
P
CHECK VALVE
HORIZONTAL PUMPS
FLOOR INLET
SIGHT GLASS
VACUUM GAUGE
V
VERTICAL PUMPS
ANTI-VORTEX PLATE
STAND PIPE
WALL INLET
C
CONTROL/POWER WIRING
FS
FLOW SWITCH
CONE STRAINER
SOLENOID VALVE
POOL RETURN PIPING & FITTINGS
BALL VALVE
EXISTING SEWER (BY OTHERS)
SEWER SYSTEM
FILTER PUMP
PH
SENSOR
ORP
SENSOR
Alarm
Fail/Safe
PPMHRRpH
Off
Man
Auto
Set
Point
SETTINGS
MODE
HRR
pH
PPM
pH Feed
Cl/Br Feed
PrintMenu
Enter
Select
Cal
Reset
FLOW
CELL
CHEMICAL
CONTROLLER
C
P
6-IN FILTER PUMP SUCTION,
450 GPM, 5.64 FPS
1/2
-IN
S
AM
PL
IN
G L
OO
P
1/2
-IN
S
AM
PL
IN
G L
OO
P
6-IN
F
IL
TE
R P
UM
P D
IS
CH
AR
GE
45
0 G
PM
, 5
.6
4 F
PS
6-IN
F
IL
TE
R R
ET
UR
N,
45
0 G
PM
, 5
.6
4 F
PS
6-IN FILTER RETURN,
450 GPM, 5.64 FPS
6-IN AIR GAP
CO2
FEEDER
12-IN x18-IN
EXISTING
FLOOR DRAIN
FLOW SENSOR TO
DISPLAY ON
CHEMICAL
CONTROLLER
1/2
-IN
F
LO
W C
EL
L D
RA
IN
FLOW METER DATA
FILTER VFD CONTROL
VFD
EXISTING FILTER
RETURN LOOP
PH FEEDER POWER
1.5-INCH FILL LINE
8-IN GUTTER DRAIN GRAVITY,
450 GPM, 3.21 FPS
FILTER
P
P
2-IN
CH
F
IL
TE
R V
AC
UU
M C
LE
AN
O
UT
32.1 1423.83 FPS0.003 SQ. FT.
GPM QTYINLET LEGEND
GPM QTY VEL.OPEN AREA
1 1/2-INCH WALL INLET (FILTER)
EXISTING
INLET PIPING
6-IN
F
IL
TE
R R
ET
UR
N,
45
0 G
PM
, 5
.6
4 F
PS
CO2 TANK
3-IN SYSTEM DRAIN
N.C. = NORMALLY CLOSED
N.O. = NORMALLY OPEN
NOTE:
1. NO POWER WIRING IS SHOWN, ONLY CONTROL.
REFER TO ELECTRICAL ENGINEER'S DRAWING
FOR MORE INFORMATION.
2. CHEMICAL CONTROLLER AND CHEMICAL
PUMPS SHALL BE INTERLOCKED WITH POOL
PUMP.
3. OPERATOR SHALL INSPECT BACKWASH TANK
DAILY AND SHALL NOT EXCEED 5 MINUTES OF
BACKWASH.
4. POOL SHALL BE DE-CHLORINATED PRIOR TO
DRAINING.
5. DRAINING OF THE POOL SHALL NOT EXCEED 25
GPM.
6. ALL BURIED PIPING SHALL BE INSULATED. PIPE
INSULATION SHALL BE SUITABLE FOR BURIED
APPLICATION.
BACKUP CL FEEDER
CHLORINE TANK ON
A CONTAINMENT PAD
SODIUM
HYPOCHLORITE
FEEDER
S.W.LSTATIC WATER LEVEL
REDUCER
1.5-INCH POTABLE WATER
LINE WITH BACKFLOW DEVICE
IN POOL EQUIPMENT ROOM
SEE BLDG PLAN -BY OTHERS
AUTO FILL
MANUAL FILL
3/4-IN SOLENOID VALVE
AND MANUAL BYPASS
VALVE MOUNTED ON
WALL IN EQUIPMENT
ROOM
6" A
IR
G
AP
AUTOFILL
CONTROLLER
AUTOFILL
SENSOR
UV REACTOR
UV CONTROL
PANEL
FLOW
METER
UV
STRAINER
P
P
PRESSURE
GAUGE
FLOW
METER
2-IN CPVC TO HEATER CONNECTIONS
SOLENOID
VALVE
S
SUPPLY
BLDG
RETURN
CPVC 180° BLDG
SUPPLY IN
RETURN
HEAT EXCHANGER
REFER TO AQ103 DETAIL 2
TEMP
SENSOR
AQUASTAT
P
P
6-IN MAIN DRAIN, 450 GPM,
5.64 FPS
SIGHT
GLASS
N.C.
4-IN
P
RE
-C
OA
T
N.O.
3/4-IN PRECOAT VENT LINE
PNEUMATIC
BUTTERFLY VALVE
FIL
TE
R V
FD
C
ON
TR
OL
T
O
FIL
TE
R C
ON
TR
OL
P
AN
EL
EXISTING 4-IN SEWER
CONNECTION
3/4
-IN
P
RE
CO
AT
V
EN
T L
IN
E
3-IN
CH
F
IL
TE
R C
LE
AN
O
UT
2-INCH FILTER VACUUM CLEAN OUT
3-INCH FILTER CLEAN OUT
AIR GAP IS ESTABLISHED
ON THE POOL DECK WITH
AN ON DECK GOOSE
NECK FILL SPOUT
NOTE: EXISTING RETURN INLET SYSTEM TO REMAIN.
UV TO BE INSTALLED
AT ALTERNATE TIME
THERMOMETER
6-INCH
PIPING
FOR UV
6-IN MODULATION
VALVE
6-INCH STUBS CAPPED
FOR FUTURE UV
INSTALLATION
EXISTING POOL EXISTING POOL
POOL DATA CHART
DESCRIPTION AMOUNT/RATE
TOTAL POOL SURFACE WATER AREA - SQUARE FEET (SF) 3,150S.F.
TOTAL POOL PERIMETER (FEET)
234 L.F.
TOTAL POOL VOLUME - (GALS) 166,000GALS
POOL TURNOVER (T.O.R.)
6.15 HRS. AT 450 GPM
FLOW RATE - POOL 450 GPM
FILTER AREA 381 S.F.
FILTER APPLICATION RATE 1.18 GPM/S.F.
POOL EQUIPMENT SCHEDULE
FILTER AREA MISCELLANEOUS EQUIPMENT
MARK QTY ITEM MANUFACTURER CAT NO. DESCRIPTION
7
PRESSURE
GAUGE
WEKSLER UA25B4L2-1/2-INCH DIA. FACE, 0-60 PSI
1
COMPOUND
GAUGE
WEKSLER UA25K4L2-1/2-INCH DIA. FACE, 0-30 INCHES HG, 0-60 PSI
1 FLOW METER GF SIGNET 2537
DIGITAL PADDLEWHEEL, 4-20mA SIGNAL CONNECT TO
CHEMICAL CONTROLLER
1 FLOW METER BLUE WHITE F-1000
DIGITAL PADDLEWHEEL DIGITAL BATTERY POWERED
DISPLAY FOR HEAT EXCHANGER
1
EYE WASH
STATION
EXISTING EXISTING EXISTING EYE WASH STATION
1
WATER LEVEL
CONTROLLER
LEVOLOR K-1100
WATER LEVEL CONTROLLER WITH SOLENOID VALVE,
CONNECT BOTH TO PROVIDED CONTROLLER. SLOW
CLOSE SOLENOID VALVE
1
WATER LEVEL
PROBE
WARRICK 3F2E
2-INCH FLANGED PRESSURE-TIGHT FITTING WITH (2)
STAINLESS STEEL PROBES
FILTRATION EQUIPMENT
MARK QTY ITEM MANUFACTURER CAT NO. DESCRIPTION
1
COLLECTOR
TANK
NEPTUNE BENSON 4260BTFG42-IN DIAMETER BALANCE TANK, 414 GALLON
1 FILTER PUMP MARLOW e530C 3-9SC
15HP, 480 VOLT, 3 PHASE, 450 GPM @ 80 TDH. FURNISHED
BY OWNER AND INSTALLED BY CONTRACTOR.
1 STRAINER FLUIDTROL SW116106031 FIBERGLASS STRAINER WITH STAINLESS STEEL BASKET
1 FILTER NEPTUNE BENSON SP-27-48-487
DEFENDER FILTER , F.A. 381 S.F. APPLICATION RATE =
1.05 GPM/SF.
1 COMPRESSOR INGERSOLL-RAND SS3L3
3 HP - 1 PH; 110V AIR COMPRESSOR WITH WATER
SEPARATOR; 11.3 CFM @ 90 PSI - 60 GAL TANK
1 VFD NEPTUNE BENSON GREEN DRIVE15 HP, 480 V, NEMA 12, 3 PHASE
CHEMICAL EQUIPMENT
MARK QTY ITEM MANUFACTURER CAT NO. DESCRIPTION
1
CHEMICAL
CONTROLLER
HAYWARD CAT5000
CHEMICAL CONTROLLER WITH OPTIONS OF FILTER
PUMP CONTROL, FLOW MONITORING,
ETHERNET/INTERNET, REMOTE CONTROL AND WATER
LEVEL CONTROL.
1 CHLORINE PUMP STENNER 85M5
SINGLE HEAD ADJUSTABLE OUTPUT METERING
PERISTALTIC PUMP, 85 GALLONS PER DAY
1
CHEMICAL
STORAGE
ASSMAN IMT 250 250 GAL DOUBLE WALL CHLORINE STORAGE TANK
1
CO₂HAYWARD AC006 DUEL TANK CHANGE OVER. 0-38 SCFH
1 UV ETS ECF-215-6V
UV TO BE INSTALLED AT AN ALTERNATE TIME. ULTRA
VIOLET DISINFECTION WITH IN-LINE STRAINER, 3
PHASE, 220V, CONTROL PANEL SHALL BE NEMA 12
MINIMUM. BUCK BOOSTER INTERNAL TO PANEL.
PROVIDE (1) EXTRA SET OF BULBS.
1
CONTAINMENT
PAD
EAGLE 1633
SPILL CONTAINMENT DRUM PLATFORM, 15 GALLON
CAPACITY
HEATING SYSTEM EQUIPMENT
MARK QTY ITEM MANUFACTURER CAT NO. DESCRIPTION
1
POOL HEAT
EXCHANGER
RAYPAK RP-995
STAINLESS STEEL SHELL AND TUBE HEAT EXCHANGER,
995,000 BTU/HOUR
1AQUASTAT RANCO ETC-111000
ONE STAGE ELECTRIC TEMPERATURE CONTROL -
CONTRACTOR TO COORDINATE VOLTAGE, POOL
CONTRACTOR SHALL COORDINATE WITH EXISTING
MECHANICAL TO CONFIGURE THE TWO STAGE
SETTINGS
1 THERMOMETER PENTAIR SL1DW
IN-LINE THERMOMETER, WITH 1/2" MIP NYLON WELL,
30-130 DEGREES
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
Project:
Drawing Title:
TOWN OF ENFIELD, CT
Enfield Annex Pool
Mechanical Room
Upgrades
124 North Main Street
Enfield, CT 06082
Sheet Number:
Consultants:
Rev Date Description
Seal:
CONSTRUCTION
DOCUMENTS
Scale:
Drawn By:
Reviewed By:
Checked By:
Revisions:
Date:
Approved By:
09.20.2019
COPYRIGHT 2019 WESTON & SAMPSON
617.412.4480
www.westonandsampson.com
800.SAMPSON
85 Devonshire Street,
3rd Floor, Boston, MA 02109
THE ELECTRICAL CONTRACTOR SHALL GROUND AND BOND ALL ELECTRICAL EQUIPMENT, POOL
REINFORCING, POOL ACCESSORIES, AND PIPING IN ACCORDANCE WITH NATIONAL ELECTRIC CODE
REQUIREMENTS, ARTICLE 680. THE ELECTRICAL CONTRACTOR SHALL OBTAIN A COPY OF ALL
APPLICABLE LOCAL STATE ELECTRICAL CODE REGULATIONS.
MES
SMB
MPM
CBW
AS NOTED
AQ100
PIPING SCHEMATIC AND
EQUIPMENT LIST
CO2 TANKS
CHEMICAL FEEDER
10'-6"
36
'-0
"
CO2 FEEDER
EXISTING STRAINER
UV TO BE INSTALLED AT
AN ALTERNATE TIME
EXISTING
DOUBLE DOOR
EXISTING
EYEWASH STATION
FM
1
AQ102
FILTER
3
AQ102
FUTURE UV
2
AQ102
HEAT EXCHANGER
9
AQ102
CHEMICAL TANK
10
AQ102
BALANCE TANK
CONTAINMENT PAD
5'-0
"2
'-6
"
EXISTING 1-FT BY
1.5-FT FLOOR DRAIN
11
AQ102
AUTOFILL SENSOR
3-IN FILTER
CLEANOUT LINE
4-IN TANK VENT LINE
HOUSEKEEPING PAD
5
AQ102
PUMP
TEES AND VALVES
FOR FUTURE UV
ELECTRIC ACTUATED
VALVE
TEES AND VALVES
FOR FUTURE UV
6-IN MAIN DRAIN
CORE VENT LINE
THROUGH INTERIOR WALL
TO EXTERIOR AND 90
DEGREE UP TO 2-FT
ABOVE POOL STATIC
WATER LEVEL AND CAP
TIE INTO EXISTING
PIPING OVERHEAD
TIE INTO EXISTING
PIPING BELOW
EXISTING CHEMICAL CONTROLLER
EXISTING MECHANICAL
ROOM WALLS
8-IN GUTTER
6-IN RETURN
EXISTING DOMESTIC FILL PIPING.
MODIFY TO INCORPORATE AND
CONFIGURE INTO THE AUTO FILL
SYSTEM
PIPING TO BE HUNG
FROM CEILING
AUTO FILL CONTROLLER
CHECK VALVE IN VERTICAL
ST
RA
IG
HT
R
UN
C
LE
AR
AN
CE
4
AQ102
FLOW METER
5'-9"
PROPOSED MECHANICAL ROOM IMPROVEMENTS
SCALE: 1/2" = 1'-0"
POOL MECHANICAL REQUIREMENTS:
1. THE EQUIPMENT ROOM OR ENCLOSURE SHALL BE LOCKABLE.
2. THE EQUIPMENT ROOM ACCESS SHALL BE CAPABLE OF FITTING ALL EQUIPMENT THAT IS
REMOVABLE.
3. ALL GAUGES SHALL HAVE 2 1/2 -IN DIAL.
4. IN ORDER TO ISOLATE VIBRATION THE FILTER AND FEATURE PUMPS FROM THE FLOOR, THE
PUMPS SHALL EACH BE MOUNTED TO NEOPRENE PADS PLACED BETWEEN THE PUMP AND THE
CONCRETE EQUIPMENT PAD. NEOPRENE PADS SHALL BE EQUIVALENT TO THE MASON
INDUSTRIES TYPE SUPER W PADS. THE PADS SHALL BE SIZED TO PROVIDE A MINIMUM OF
0.15-INCH STATIC DEFLECTION UNDER THE WEIGHT OF THE PUMP.
5. TAG ALL VALVES, LABEL ALL PIPES AND POST OPERATING INSTRUCTION INSIDE THE ROOM.
6. ELECTRICALLY OPERATED CHEMICAL FEEDER SHALL BE INTERLOCKED WITH THE FILTER PUMP.
7. THE CHEMICAL SOLUTION TANK SHALL BE LABELED ACCORDING TO THE CONTENTS.
8. SECURE ALL CHEMICAL FEEDER TUBING SO THERE IS NO LOOSE TUBING.
9. SUPPORT ALL PIPING WITH UNISTRUT FRAME FROM EQUIPMENT FLOOR OR ATTACHED TO
CEILING AS NEEDED FOR PROPER PIPE SUPPORT OR EQUIVALENT.
Project:
Drawing Title:
TOWN OF ENFIELD, CT
Enfield Annex Pool
Mechanical Room
Upgrades
124 North Main Street
Enfield, CT 06082
Sheet Number:
Consultants:
Rev Date Description
Seal:
CONSTRUCTION
DOCUMENTS
Scale:
Drawn By:
Reviewed By:
Checked By:
Revisions:
Date:
Approved By:
09.20.2019
COPYRIGHT 2019 WESTON & SAMPSON
617.412.4480
www.westonandsampson.com
800.SAMPSON
85 Devonshire Street,
3rd Floor, Boston, MA 02109
THE ELECTRICAL CONTRACTOR SHALL GROUND AND BOND ALL ELECTRICAL EQUIPMENT, POOL
REINFORCING, POOL ACCESSORIES, AND PIPING IN ACCORDANCE WITH NATIONAL ELECTRIC CODE
REQUIREMENTS, ARTICLE 680. THE ELECTRICAL CONTRACTOR SHALL OBTAIN A COPY OF ALL
APPLICABLE LOCAL STATE ELECTRICAL CODE REGULATIONS.
MES
SMB
MPM
CBW
AS NOTED
AQ101
PROPOSED
IMPROVEMENTS
NOTE: ACCESS TO THE DOUBLE DOORS IS THROUGH
A GARAGE BAY WITH A 8-FT X 10-FT GARAGE DOOR.
PLAN VIEW
3 LEGS PER TANK
FILTER DATA
MEDIA REQUIREMENTS
3'-0"
86"
16"
UNIT CAPACITY: 159 GALS
3'-0"
2'-3"
7'-11"
Ø2'-3"
Ø
8
"
CONTROL
PANEL
FILTER AREA = 381 SQ.FT.
CONCRETE BEARING PRESSURE=42PSI
UNIT WEIGHT: 1,650 LBS. - DRY
OPERATING WEIGHT: 2,970 LBS.
NOTES:
FILTER TANK IS TO BE FACTORY CONSTRUCTED OF HIGH QUALITY A36
CARBON STEEL, INTERIOR OF TANK IS LINED WITH FLEXSOL 3000.
EXTERIOR IS COATED WITH 5-8 MILS OF HIGH SOLIDS ENAMEL. NO WELDING
OR EXTREME HEAT IS TO BE APPLIED TO TANK AFTER LINING OR COATING
PROCESS IS DONE.
2. ELECTRICAL REQUIREMENTS: 120V - 120VAC-1Ø-60HZ, 30 AMP CIRCUIT
PROTECTION
240V - 240VAC-1Ø-50HZ, 15 AMP CIRCUIT PROTECTION
3. LOCATE ALL ELECTRICAL ITEMS IN A NON-HAZARDOUS LOCATION.
4. MEDIA QUANTITIES ARE INDICATED FOR INFORMATIONAL PURPOSES
ONLY.
5. ALL PNEUMATIC TUBING AND FILTER AIR COMPRESSOR BY SUB
CONTRACTOR.
6. DRAIN VALVE MUST BE A BUTTERFLY VALVE AND INSTALLED DIRECTLY
ON THE BOTTOM TANK HEAD.
7. BACKWASH PUMP SUPPLIED WITH FILTER
PERLITE 30 LBS. (13.61kg)
4" DIA VIEWING
WINDOW
VACUUM
BLOWER
VACUUM
TRANSFER PIPING
BLOWER
INLET
FILTER
BALL VALVE
GROUNDING LUG
(SIDE OF LEG
HOSE TO
MEDIA
3-IN DRAIN
FLANGE
1/4-IN FPT (FARSIDE) FOR INFLUENT
PRESSURE GAUGE CONNECTION
REQUIRED FLANGE
BREAK FOR INFLUENT
DISTRIBUTION SYSTEM
INSPECTION/CLEANING
FILTER/REGULATOR
6-IN INLET
CONNECTION
1 1/2-IN FPT HOSE
CONNECTION
(VACUUM TRANSFER)
CONTROL PANEL
4-IN DIA VIEWING WINDOW
& GUAGE PANEL
FILTER/REGULATOR
6-IN INLET CONNECTION
6-IN OUTLET CONNECTION
GROUNDING LUG LOCATION
INSTALLING CONTRACTOR MUST
CONNECT TO PROVIDED GROUNDING
AREA LOCATED ON THE LEG(S)
CONTROL PANEL
DAVIT
1 1/2-IN FLANGE CONN.
VACUUM TRANSFER
6-IN OUTLET
CONNECTION
1 1/2-IN FLANGE CONN.
UPPER HEAD ASSEMBLY
BUMPING AGITATION MECHANISM
16-IN MIN. FOR TANK HEAD REMOVAL
1/4-IN FPT (FARSIDE) FOR EFFLUENT
PRESSURE GAUGE CONNECTION
REQUIRED FLANGE BREAK
FOR HEAD REMOVAL
6-IN AIR GAP
EXISTING FLOOR DRAIN
HOUSE KEEPING PAD AS REQUIRED FOR
FILTER CLEAN OUT LINE 6-IN AIR GAP
3-IN FILTER
CLEAN OUT
DIMENSION (INCHES)
HEAT
TRANSFER
AREA (sq ft)
PART
NUMBER
NOMINAL
CAPACITY
BTU/HR
A B C
POOL
CONN
NPT
F
BOILER
CONN
NPT
G
LENGTH
L
DIAMETER
ØD
RP-995995,000
9-9/16" 26-5/8" 4-5/16" 2" 2" 35-3/16" 5-1/2" 21.50
A
G
HEAT SOURCE WATER IN
POOL WATER OUT
CB
ØD
L
POOL WATER IN
HEAT SOURCE
WATER OUT
UV UNIT INSTALLATION ELEVATION
4-IN EQUIPMENT PAD
DRAIN PLUG
GROUNDING/BONDING LUG
FUTURE
UV DISINFECTION UNIT
PRESSURE GAUGE
THROTTLING VALVE
STAINLESS STEEL SCREEN
ON A WAFFER PROVIDED
WITH UV UNIT
PVC FLANGED
SPOOL
CUT OFF VALVES
ALLOWS FOR UV-UNIT
MAINTENANCE
P
P
CONCENTRIC REDUCERS
AS REQUIRED.
FL
OW
FL
OW
FROM FILTER
TO POOL
ALL PIPING SHALL BE
BRACED TO WALL OR
FLOOR WITH NON
CORROSIVE SUPPORTS
FLOOR
FUTURE FUTURE
DIRECTION
OF FLOW
UNION NUT
FLOW METER
STRAP ON SADDLE
LABEL INDICATING
FLOW
VARIES
UPSTREAM
VARIES
DOWNSTREAM
NOTES:
1. DIMENSIONS REPRESENT A MINIMUM UNOBSTRUCTED HORIZONTAL STRAIGHT PIPE MOUNTING
REQUIREMENT FOR FLOW SENSOR. FLOW SENSOR SHALL BE INSTALLED PER MANUFACTURER'S
RECOMMENDATION.
2. MOUNT FLOW SENSOR IN THE TOP OF THE PIPE.
IF TOP OF PIPE IS NOT ACCESSIBLE, MOUNT AT 45° ANGLE AS SHOWN.
3. FLOW SENSOR DISPLAY SHALL BE VISIBLE BY THE OPERATOR FROM THE GROUND.
D
I
R
E
C
T
I
O
N
O
F
F
L
O
W
1
0
X
D
I
A
M
E
T
E
R
O
F
P
I
P
E
5
X
D
I
A
M
E
T
E
R
O
F
P
I
P
E
PADDLE WHEEL FLOW METER
CONNECT TO CHEMICAL
CONTROLLER
PLASTIC TIE STRAP (TYP.)
FLOWSENSOR
STRAP ON SADDLE
FLOW
SENSOR
RETURN
LINE
SADDLE
4
5
°
SENSOR
MOUNTING
PLAN VIEW
MANHOLE 14"
X 18"
LIFTING
LUG (2X)
6" DIA. ACCESS
HOLE TYP. (4X)
4" VENT
AND FILL
6" PUMP
SUCTION
2" DRAIN
3'-0"
3'-4"
6"
2'-5
1 2
"
2'-6
"2
'-6
"
5'-0
"
LIFTING LUG
2" DRAIN
ASSEMBLY
2
1 2
"
7'-5
1 2
"
5'-8
1 2
"
1'-1
0"
8" GUTTER
DRAIN
6" PUMP
SUCTION
4" VENT AND FILL
(2) 2" FOR SENSOR
REFER TO DETAIL 12
4'-0
"
6" MAIN
DRAIN
8" GUTTER DRAIN
6" MAIN DRAIN
MARLOW
MODEL
SUCTION
A.S.A. 125
LB FLANGE
DISCHARGE
A.S.A. 125
LB FLANGE
MOTOR
FRAME
SPEEDDISCHARGE
SUCTION
PHASE
CP
O
B
D
F L
Y
H
A
2E
AB Z
XD
D
3-9SC 3 254JP 1750 RPM
4 5
HF2EDCPBABA
12-1/2 10-3/4 10-3/4 34-3/8 6-1/4 10 8-1/4 17/32
OL
19 13-1/8
PLACE 1/2-INCH THICK NEOPRENE
PAD BETWEEN STRAP AND PIPE
STAINLESS STEEL UNISTRUT
CHANNEL AND STRAP
CONCRETE SLAB
BY OTHERS
PIPE SIZE VARIES
(SEE PLANS)
DRILL AND EPOXY ANCHOR BOLTS - SIZE
AS REQUIRED- 2 PER CHANNEL
MINIMUM PER MANUFACTURER
UNISTRUT CHANNEL
SUPPORT PIPING TO FLOOR OR CEILING.
THESE SUPPORTS SHALL BE USED TO
EXCEPT AS INDICATED.
ALL MATERIALS SHALL BE CARBON STEEL,
NOTE:
WITH 6" MIN. EMBEDMENT
1/2" S.S. EXPANSION BOLTS
12"x12"X3/4" THICK
WELD ROD TO SADDLE
1/2"x2" PIPE CRADLE
DI PIPE (12"Ø MAX.)
5/8" MIN. Ø U-BOLT
VA
RIE
S
N.T.S.
PIPE SUPPORT DETAIL (CEILING)
FLANGED PIPE SUPPORT
BRACKET NO. 2
3 1/2"
5/8"Ø EXPANSION BOLTS
WITH 5" EMBEDMENT (TYP)
(2 REQUIRED)
TOP OF CONCRETE
BRIDGE SLAB
WELDED STEEL BRACKET
SIMILAR TO GRINNEL FIG. 194
5/8"Ø U-BOLTS
1" MIN.
1'-1"
11"
STANDARD U-BOLT FIG. 137
LOCK WASHER & NUT (TYP)
ALUMINUM JACKET
2 1/2" INSULATION
2 1/2" PVC FORCEMAIN
HEAT TRACING WIRE
(2 SEPARATE RUNS)
SIMILAR TO GRINNEL
1'-1"
PIPE HANGER DETAIL
N.T.S.
FLOW POOL
RETURN LINE
CHEMICAL
ANALYZER
CO2
FEEDER
CO2 TANK
NAOCL
EAGLE SPILL CONTAINMENT BASIN
PROVIDE STAINLESS
STEEL CHAIN FOR
ANCHORING TO THE
WALL
DUAL CHANGE OVER
1
3
4
"DEEP
PUMP SHELF
0°
90°
180°
270°
1'-6
3
4
"
1'-5"
10"
1'-8
3
4
"
3'-11"
5
1 2
"7
1 4
"
2'-10"
11"
4'-9
3 4
"
3'-6
1
4
"
5'-1"
7-IN ACCESS LID
WATER MAKE-UP NOTES:
1. WATER MAKE-UP SUPPLIER TO PROVIDE
SOLENOID VALVE, ELECTRODE UNIT,
SENSING WELL PROBES, AND PROBE
HANGING WIRE.
2. POOL CONTRACTOR TO INSTALL
SENSING WELL AND SET PROBES.
3/4-IN SLOW CLOSING
SOLENOID VALVE IS
TO BE FURNISHED BY
MANUFACTURER
& INSTALLED
BY THE PLUMBER
3/4-IN CLOSE NIPPLE
FEMALE ADAPTER
3/4-IN UNION
3/4-IN BALL VALVE
3/4-IN STRAINER
3/4-IN CLOSE NIPPLE
FEMALE ADAPTER
PIPING BY-PASS
3/4-IN UNION
3/4-IN BALL
VALVE
WATER
SUPPLY
BALL VALVE
CONDUIT W/ THREE
CONDUCTOR SENSING
CABLES (BY
ELECTRICIAN)
FILL PIPE TO EXISTING EDGE OF POOL
SHALL BE 6-IN ABOVE WATER LEVEL
LOCATE IN EXISTING POOL ALCOVE
SIDE VIEW
LEVELOR K-1100
SENSOR IN PIPE
2-IN CLEAR SCH.
80 PVC PIPE
SCH. 80 PVC
PIPE
1-IN DRAIN VALVE
4-IN HOUSEKEEPING PAD
K-1100 AUTOFILL WITH
TWO PROBES
FILTER
SCALE: NOT TO SCALE
1
Project:
Drawing Title:
TOWN OF ENFIELD, CT
Enfield Annex Pool
Mechanical Room
Upgrades
124 North Main Street
Enfield, CT 06082
Sheet Number:
Consultants:
Rev Date Description
Seal:
CONSTRUCTION
DOCUMENTS
Scale:
Drawn By:
Reviewed By:
Checked By:
Revisions:
Date:
Approved By:
09.20.2019
COPYRIGHT 2019 WESTON & SAMPSON
617.412.4480
www.westonandsampson.com
800.SAMPSON
85 Devonshire Street,
3rd Floor, Boston, MA 02109
THE ELECTRICAL CONTRACTOR SHALL GROUND AND BOND ALL ELECTRICAL EQUIPMENT, POOL
REINFORCING, POOL ACCESSORIES, AND PIPING IN ACCORDANCE WITH NATIONAL ELECTRIC CODE
REQUIREMENTS, ARTICLE 680. THE ELECTRICAL CONTRACTOR SHALL OBTAIN A COPY OF ALL
APPLICABLE LOCAL STATE ELECTRICAL CODE REGULATIONS.
MES
SMB
MPM
CBW
AS NOTED
AQ102
DETAILS
HEAT EXCHANGER
SCALE: NOT TO SCALE
2
UV
SCALE: NOT TO SCALE
3
BALANCE TANK
SCALE: NOT TO SCALE
10
FLOW METER
SCALE: NOT TO SCALE
4
FILTER PUMP
SCALE: NOT TO SCALE
5
PIPE HANGER DETAIL
SCALE: NOT TO SCALE
7
PIPE SUPPORT DETAIL - WALL AND CEILING
SCALE: NOT TO SCALE
8
CHEMICAL STORAGE TANK
SCALE: NOT TO SCALE
9
CHEMICAL SCHEMATIC
SCALE: NOT TO SCALE
6
AUTO FILL
SCALE: NOT TO SCALE
11
BLDG SIDEPOOL SIDE
TO POOL
RETURN
FROM
FILTER
AQUASTAT
3-WAY SOLENOID VALVE
SUPPLIED BY PLUMBING
CONTRACTER
HEAL EXCHANGERS POOL SIDE
TEMPERATURE SENSOR
HEAT
EXCHANGER
T
IN
OUT
IN
OUT
Project:
Drawing Title:
TOWN OF ENFIELD, CT
Enfield Annex Pool
Mechanical Room
Upgrades
124 North Main Street
Enfield, CT 06082
Sheet Number:
Consultants:
Rev Date Description
Seal:
CONSTRUCTION
DOCUMENTS
Scale:
Drawn By:
Reviewed By:
Checked By:
Revisions:
Date:
Approved By:
09.20.2019
COPYRIGHT 2019 WESTON & SAMPSON
617.412.4480
www.westonandsampson.com
800.SAMPSON
85 Devonshire Street,
3rd Floor, Boston, MA 02109
THE ELECTRICAL CONTRACTOR SHALL GROUND AND BOND ALL ELECTRICAL EQUIPMENT, POOL
REINFORCING, POOL ACCESSORIES, AND PIPING IN ACCORDANCE WITH NATIONAL ELECTRIC CODE
REQUIREMENTS, ARTICLE 680. THE ELECTRICAL CONTRACTOR SHALL OBTAIN A COPY OF ALL
APPLICABLE LOCAL STATE ELECTRICAL CODE REGULATIONS.
MES
SMB
MPM
CBW
AS NOTED
AQ103
DETAILS
HEAT EXCHANGER SCHEMATIC
SCALE: NOT TO SCALE
12
CONT'D
WALL MOUNTED LINE VOLTAGE THERMOSTAT MOUNTED 54"AFF.
THERMOSTAT FURNISHED BY HVAC AND INSTALLED BY
ELECTRICAL CONTRACTOR.
1,3 LP1B
ELECTRICAL LEGEND
DUPLEX CONVENIENCE OUTLET RATED 20A, 125V, U-SLOT
GROUNDED TYPE . REFER TO RECEPTACLE ABBREVIATIONS FOR
SPECIAL PURPOSE RECEPTACLES.
GROUND BUS WALL MOUNTED CHATSWORTH MODEL NO.
10622-020 EXTEND A 1/2"C, 1-#6 INSULATED GROUND TO
THE BUILDING GROUND SYSTEM
FUSIBLE SAFETY SWITCH - RATING AND TYPE AS NOTED
ON THE DRAWING. (30 AMP, 20 AMP FUSE, 3 POLE)
SAFETY SWITCH - RATING AND TYPE AS NOTED ON
THE DRAWING.
MOTOR, NUMERAL DENOTES HORSE POWER
PANELBOARD-SURFACE MOUNTED
JUNCTION BOX WITH BLANK COVERPLATE, SIZE AS
REQUIRED BY N.E.C.
SURFACE MOUNTED LED CABINET LIGHT FIXTURE. MANUFACTUERED BY
SIMKAR CATALOG #VAPLED-C-11-50-U1 OR APPROVED EQUAL
RACEWAY RUN UNDERGROUND
RACEWAY RUN EXPOSED OR ABOVEGROUND
HOMERUN TO PANELBOARD, NUMBER OF TICKS INDICATES NUMBER OF
#12 AWG CONDUCTORS CONTAINED IN RACEWAY. TWO (2) #12 AWG SHALL
NOT BE INDICATED BY TICKS, NUMERALS 1 AND 3 INDICATE CIRCUITS IN
PANELBOARD. RACEWAYS LARGER THAN 1/2" AND CONDUCTORS LARGER
THAN #12 AWG SHALL BE INDICATED ON THE DRAWINGS. PROVIDE AN
INSULATED GREEN GROUND WIRE IN ALL RACEWAYS MINIMUM SIZE TO BE
#12AWG.
ABBREVIATIONS
WATTS OR WIREW
4-WIRE SOLID NEUTRAL4WSN
WP WEATHERPROOF
ELECTRIC WATER HEATER
POLYVINYL CHLORIDE CONDUIT
RIGID GALVANIZED STEEL CONDUIT
TRF
EWH
TEL
RSC
V
SF
SS
TELEPHONE
TRANSFORMER
VOLTS
SUPPLY FAN
SAFETY SWITCH
PVC
NTS
NIC
PNL
PH
NA
NO
NC
NOT TO SCALE
PANELBOARD
PHASE
NOT IN CONTRACT
NORMALLY CLOSED
NORMALLY OPEN
NOT APPLICABLE
NON-METALLIC CONDUIT
MECHANICAL CONTRACTOR
GROUND FAULT INTERRUPTER
MAIN CIRCUIT BREAKER
KILOVOLT AMPERESKVA
NMC
MTD
MTG
MCB
MLO
MC
KW
MOUNTED
MOUNTING
KILOWATT
MAIN LUGS ONLY
HOA
GND
JB
IG
HP
GFI
GC
HAND OFF AUTOMATIC
HORSEPOWER
JUNCTION BOX
ISOLATED GROUND
GROUND
GENERAL CONTRACTOR
AUTOMATIC TRANSFER SWITCH
AUTOMATIC TEMPERATURE CONTROLS
ELECTRICAL CONTRACTOR
ABOVE FINISHED FLOOR
ELECTRIC METALLIC TUBING
ELECTRIC WATER COOLER
ALTERNATING CURRENT
CONDUITC
FLA
EMT
EWC
CKT
FL
EF
CB
EC
FLOOR
FULL LOAD AMPERE
EXHAUST FAN
CIRCUIT
CIRCUIT BREAKER
ATC
BKR
ATS
AFF
A
AC
AMPERE
BREAKER
GFI
WP
RECEPTACLE ABBREVIATIONS
GROUND FAULT CIRCUIT INTERUPTER,
PERSONAL PROTECTION
WEATHERPROOF RECEPTACLE WITH
COVERPLATE LISTED FOR WET
LOCATION WITH AN ATTACHMENT
PLUG INSERTED.
DISTRIBUTION PANEL
PULL BOX
WEATHERPROOF SINGLE-POLE SWITCH
FLOW METER
VARIABLE SPEED DRIVE
WATTHOUR METER
S
GROUND - SYSTEM AND/OR EQUIPMENT
3 PHASE, 3 WIRE DELTA CONNECTION
3 PHASE, 3 WIRE WYE CONNECTION (UNGROUNDED)
3 PHASE, 4 WIRE WYE CONNECTION (GROUNDED
NEUTRAL)
CIRCUIT BREAKER
CONDUIT
GROUT SLEEVE IN A
NEAT AND WORKMANLIKE
MANNER WITH SMOOTH
SURFACES
WATERTIGHT SEAL AS
SPECIFIED
BRICK OR CMU WALL
OPENING IN BRICK OR
CMU SHALL HAVE EDGES
AS SMOOTH AND STRAIGHT
AS POSSIBLE
DIAMETER AS REQUIRED BY
SEAL MANUFACTURER
PVC SLEEVE WITH WATERSTOP,
PACK AND SEAL
CONDUIT
CONCRETE WALL
PACK AND SEAL OPENING
PVC SLEEVE, DIAMETER
AS REQUIRED BY SEAL
MANUFACTURER
WATERTIGHT
MECHANICAL
SEAL AS SPECIFIED
WATERTIGHT CONDUIT PENETRATIONS
NO SCALE
1
TVSS
TRANSIENT SURGE SUPRESSION UNIT
GENERAL NOTES
1. DRAWINGS ARE DIAGRAMMATIC ONLY. THE EXACT LOCATION, MOUNTING HEIGHTS, SIZE OF
EQUIPMENT AND ROUTING OF RACEWAYS SHALL BE COORDINATED AND DETERMINED IN THE
FIELD.
2. WORK SHALL CONFORM TO THE NATIONAL ELECTRICAL CODE AND CONNECTICUT BUILDING
CODE AND REQUIREMENTS OF LOCAL AUTHORITIES HAVING JURISDICTION.
3. THE WORD "CONTRACTOR" AS USED IN THE "ELECTRICAL WORK" SHALL MEAN THE ELECTRICAL
CONTRACTOR.
4. CONTRACTOR SHALL PAY FOR ALL PERMITS, INSURANCE AND TESTS, AND SHALL PROVIDE
LABOR AND MATERIAL TO COMPLETE THE ELECTRICAL WORK SHOWN.
5. CONTRACTOR SHALL PAY ELECTRIC UTILITY COMPANY BACKCHARGES AND PROVIDE
COORDINATION WITH SAME.
6. EXCEPT AS OTHERWISE NOTED, THE ELECTRICAL WORK SHALL INCLUDE PANELBOARDS,
CIRCUIT BREAKERS, FEEDERS, WIRING, RACEWAYS, LIGHTING FIXTURES, DEVICES, SAFETY
SWITCHES, MOUNTING AND WIRING, TRANSFORMERS AND CONNECTIONS NECESSARY TO
OPERATE ALL EQUIPMENT.
7. THE CONTRACTOR SHALL PROVIDE ALL TEMPORARY LIGHTING AND POWER AND PAY ALL
ENERGY CHARGES.
8. DURING CONSTRUCTION, THE ELECTRICAL CONTRACTOR SHALL KEEP HIS PORTION OF THE
WORK NEAT, CLEAN AND ORDERLY.
9. ALL SYSTEMS SHALL BE TESTED FOR SHORT CIRCUIT AND GROUNDS PRIOR TO ENERGIZING
AND ANY DEFECTS SHALL BE CORRECTED.
10. ALL CUTTING AND PATCHING REQUIRED FOR ELECTRICAL WORK SHALL BE INCLUDED AS PART
OF THIS SECTION.
11. COMPLETE SHOP DRAWINGS SHALL BE SUBMITTED FOR ELECTRICAL EQUIPMENT. WHERE
SPECIFIED, ELECTRICAL EQUIPMENT IS SUBSTITUTED. THE ELECTRICAL CONTRACTOR SHALL
SUBMIT COMPLETE SPECIFICATIONS ON THE SUBSTITUTE AS WELL AS THE ITEM ORIGINALLY
SPECIFIED.
12. MATERIALS SHALL BE SPECIFICATION GRADE AND UL LISTED.
13. WHERE MATERIAL IS CALLED OUT IN THE LEGEND BY MANUFACTURER, TYPE OR CATALOG
NUMBER, SUCH DESIGNATIONS ARE TO ESTABLISH STANDARDS OR DESIRED QUALITY.
ACCEPTANCE OR REJECTIONS OF PROPOSED SUBSTITUTIONS SHALL BE SUBJECT TO THE
APPROVAL OF THE OWNER.
14. WORK SHALL BE COORDINATED WITH THAT OF OTHER TRADES TO ELIMINATE INTERFERENCES.
15. ELECTRICAL WORK SHALL BE GUARANTEED FOR A PERIOD OF ONE YEAR FROM DATE OF
WHICH SYSTEM IS PUT INTO SERVICE.
16. WORK SHALL BE GROUNDED IN ACCORDANCE WITH CODE REQUIREMENTS. COMPLETE
EQUIPMENT (INSULATED GREEN WIRE) GROUNDING SYSTEM SHALL BE INSTALLED.
17. PANELBOARDS SHALL BE DEAD FRONT, THERMAL MAGNETIC BOLT-ON CIRCUIT BREAKER TYPE,
DESIGNED FOR SURFACE MOUNTING AS INDICATED ON PLAN, AND HAVING CONNECTIONS TO
120/208 VOLT, 3 PHASE, 4 WIRE SERVICE. ALL BUS BARS SHALL BE COPPER. CABINETS SHALL
BE MADE OF CODE GAUGE GALVANIZED SHEET STEEL, WITH A MINIMUM OF 4 INCH GUTTERS,
DOOR IN DOOR CONSTRUCTION, LOCKED DOOR, AND FLUSH HINGES. TYPEWRITTEN INDEX
SHALL BE MOUNTED ON DOOR INSIDE TRANSPARENT COVER INDICATING LOAD SERVED.
PANELS SHALL INCLUDE SEPARATE EQUIPMENT GROUND BUS.
18. CONDUIT RUNS AS SHOWN ON THE PLANS ARE DIAGRAMMATIC ONLY; EXACT LOCATION AND
METHOD OF SUPPORT SHALL BE DETERMINED IN THE FIELD.
19. CONTRACTOR SHALL CHECK EXISTING CONDITIONS TO DETERMINE EXACT EXTENT OF WORK
TO BE PERFORMED PRIOR TO BIDDING. DIMENSIONS RELEVANT TO EXISTING WORK SHALL BE
VERIFIED IN THE FIELD.
20. PROVIDE AS-BUILT "CADD" DRAWINGS AT THE COMPLETION OF THE PROJECT.
WIRING DIAGRAMS2
FM
3
4
"C., 2/C#16 TWISTED
SHIELDED PAIR (4-20mA) TO
CHEMICAL CONTROL PANEL
NO SCALE
VFD
3
4
"C., 3#8 & 1#8 TO FILTER
PUMP MOTOR
3
4
"C., 3#8 & 1#8TO
POWER PANEL
FLOW METER
FILTER PUMP VFD
20 AMP BREAKER REQUIRED
Project:
Drawing Title:
TOWN OF ENFIELD, CT
Enfield Annex Pool
Mechanical Room
Upgrades
124 North Main Street
Enfield, CT 06082
Sheet Number:
Consultants:
Rev Date Description
Seal:
CONSTRUCTION
DOCUMENTS
Scale:
Drawn By:
Reviewed By:
Checked By:
Revisions:
Date:
Approved By:
09.20.2019
COPYRIGHT 2019 WESTON & SAMPSON
617.412.4480
www.westonandsampson.com
800.SAMPSON
85 Devonshire Street,
3rd Floor, Boston, MA 02109
THE ELECTRICAL CONTRACTOR SHALL GROUND AND BOND ALL ELECTRICAL EQUIPMENT, POOL
REINFORCING, POOL ACCESSORIES, AND PIPING IN ACCORDANCE WITH NATIONAL ELECTRIC CODE
REQUIREMENTS, ARTICLE 680. THE ELECTRICAL CONTRACTOR SHALL OBTAIN A COPY OF ALL
APPLICABLE LOCAL STATE ELECTRICAL CODE REGULATIONS.
MES
SMB
MPM
CBW
AS NOTED
ELECTRICAL
DIAGRAMS
AND DETAILS
E100
Project:
Drawing Title:
TOWN OF ENFIELD, CT
Enfield Annex Pool
Mechanical Room
Upgrades
124 North Main Street
Enfield, CT 06082
Sheet Number:
Consultants:
Rev Date Description
Seal:
CONSTRUCTION
DOCUMENTS
Scale:
Drawn By:
Reviewed By:
Checked By:
Revisions:
Date:
Approved By:
09.20.2019
COPYRIGHT 2019 WESTON & SAMPSON
617.412.4480
www.westonandsampson.com
800.SAMPSON
85 Devonshire Street,
3rd Floor, Boston, MA 02109
THE ELECTRICAL CONTRACTOR SHALL GROUND AND BOND ALL ELECTRICAL EQUIPMENT, POOL
REINFORCING, POOL ACCESSORIES, AND PIPING IN ACCORDANCE WITH NATIONAL ELECTRIC CODE
REQUIREMENTS, ARTICLE 680. THE ELECTRICAL CONTRACTOR SHALL OBTAIN A COPY OF ALL
APPLICABLE LOCAL STATE ELECTRICAL CODE REGULATIONS.
MES
SMB
MPM
CBW
AS NOTED