Toulouse Aeronautical Test Centre (CEAT) « Fire Safety Department » Serge LE NEVE E-mail : [email protected] DEVELOPMENT OF A REPEATABLE HIDDEN FIRE SOURCE

Transcript of Toulouse Aeronautical Test Centre (CEAT) - FAA Fire Safety · PDF fileToulouse Aeronautical...

Page 1: Toulouse Aeronautical Test Centre (CEAT) - FAA Fire Safety · PDF fileToulouse Aeronautical Test Centre (CEAT) « Fire Safety Department » Serge LE NEVE E-mail : Serge.le-neve@dga.defense.gouv.fr

Toulouse Aeronautical Test Centre (CEAT)« Fire Safety Department »

Serge LE NEVEE-mail : [email protected]

DEVELOPMENTOF A REPEATABLE

HIDDEN FIRE SOURCE

Page 2: Toulouse Aeronautical Test Centre (CEAT) - FAA Fire Safety · PDF fileToulouse Aeronautical Test Centre (CEAT) « Fire Safety Department » Serge LE NEVE E-mail : Serge.le-neve@dga.defense.gouv.fr

IAMFTWorking Group / Atlantic City / October 09 Diapositive N°2 / 31MINISTÈRE DE LA DÉFENSE

Reminder of the full test programReminder of the full test program

CEAT / Fire Safety Department(Toulouse Aeronautical Test Centre)

FIRE BEHAVIOUR OF STRUCTURAL COMPOSITE MATERIALS

Mechanical behaviour of composite materials submitted to a HiddeMechanical behaviour of composite materials submitted to a Hidden Fire Sourcen Fire Source

BurnthroughBurnthrough, Smoke & Toxicity of structural composite materials , Smoke & Toxicity of structural composite materials

Page 3: Toulouse Aeronautical Test Centre (CEAT) - FAA Fire Safety · PDF fileToulouse Aeronautical Test Centre (CEAT) « Fire Safety Department » Serge LE NEVE E-mail : Serge.le-neve@dga.defense.gouv.fr

IAMFTWorking Group / Atlantic City / October 09 Diapositive N°3 / 31MINISTÈRE DE LA DÉFENSE

FIRE BEHAVIOUR OF STRUCTURAL COMPOSITE MATERIALS

In-flight fire Post-crash fire

Hidden fire damagingElectric arc effects

Burnthrough behaviour Environmental effects on cabin

side (smoke / toxicity / heat release)

FULL TEST PROGRAM

To assess the fire behaviour of structural composite materials faced with the following threats :

Page 4: Toulouse Aeronautical Test Centre (CEAT) - FAA Fire Safety · PDF fileToulouse Aeronautical Test Centre (CEAT) « Fire Safety Department » Serge LE NEVE E-mail : Serge.le-neve@dga.defense.gouv.fr

IAMFTWorking Group / Atlantic City / October 09 Diapositive N°4 / 31MINISTÈRE DE LA DÉFENSE

HIDDEN FIRE DAMAGING

Interlaminar Shear Strength (ILSS)

Open Hole Compression (OHC)

Unnotched Tension (UT)

Unnotched Compression (UC)

Assessment of the mechanical behaviour of composite materials submitted to a hidden fire.

4-point-bending test

Clamped beam test

Under load fire tests (to be defined)

Fire damaged area

Fire test sample

Mechanical test specimens

Fire behaviour of structural composite materials

Residual mechanical characteristics Underload mechanical behaviour

CEAT / Fire Safety Department(Toulouse Aeronautical Test Centre)

Page 5: Toulouse Aeronautical Test Centre (CEAT) - FAA Fire Safety · PDF fileToulouse Aeronautical Test Centre (CEAT) « Fire Safety Department » Serge LE NEVE E-mail : Serge.le-neve@dga.defense.gouv.fr

IAMFTWorking Group / Atlantic City / October 09 Diapositive N°5 / 31MINISTÈRE DE LA DÉFENSE

To expose a large surface of the test samples

To submit the materials to various scenarios (various exposure times)

HIDDEN FIRE DAMAGING

4-point-bending test

Clamped beam test

Under load fire tests (to be defined)

Fire damaged area

Fire test sampleMechanical test specimens

Fire behaviour of structural composite materials

We need a repeatable fire source

CEAT / Fire Safety Department(Toulouse Aeronautical Test Centre)

Page 6: Toulouse Aeronautical Test Centre (CEAT) - FAA Fire Safety · PDF fileToulouse Aeronautical Test Centre (CEAT) « Fire Safety Department » Serge LE NEVE E-mail : Serge.le-neve@dga.defense.gouv.fr

IAMFTWorking Group / Atlantic City / October 09 Diapositive N°6 / 31MINISTÈRE DE LA DÉFENSE

Hidden Fire Source

DEVELOPMENTOF A REPEATABLE

HIDDEN FIRE SOURCE

CEAT / Fire Safety Department(Toulouse Aeronautical Test Centre)

Page 7: Toulouse Aeronautical Test Centre (CEAT) - FAA Fire Safety · PDF fileToulouse Aeronautical Test Centre (CEAT) « Fire Safety Department » Serge LE NEVE E-mail : Serge.le-neve@dga.defense.gouv.fr

IAMFTWorking Group / Atlantic City / October 09 Diapositive N°7 / 31MINISTÈRE DE LA DÉFENSE

We designed the fire source on the basis of the FAA foam block fire source characteristics, assuming that these characteristics are representative of a declared hidden fire :

Heat Flux Density / T° : The flame characteristics must be similar to the flame produced by the FAA foam block

Flame size : The fire source to be designed must be capable to produce an homogeneous damaged areacompatible with the mechanical test specimens to be removed (area ~ 150 mm X 300 mm)

SPECIFICATIONS

Hidden Fire Source

CEAT / Fire Safety Department(Toulouse Aeronautical Test Centre)

Page 8: Toulouse Aeronautical Test Centre (CEAT) - FAA Fire Safety · PDF fileToulouse Aeronautical Test Centre (CEAT) « Fire Safety Department » Serge LE NEVE E-mail : Serge.le-neve@dga.defense.gouv.fr

IAMFTWorking Group / Atlantic City / October 09 Diapositive N°8 / 31MINISTÈRE DE LA DÉFENSE

Typical flame profile of the foam block fire

T° at 3 inches from the foam top

0

100

200

300

400

500

600

700

800

0 60 120 180 240 300 360

Temps (s)

Tem

péra

ture

(°C

)

Foam 16kg/m3 + Heptane 10ml - Foam top to HF meter : 3 inches - 24/06/08

0

1

2

3

4

5

6

7

0 60 120 180 240 300 360

Temps (s)

Flux

(W/c

m²)

T° profile / 3 inches

HF profile / 3 inches

Active burn time : ~ 1mn

Hidden Fire Source

CEAT / Fire Safety Department(Toulouse Aeronautical Test Centre)

Secondary burn time :the flames do not impinge the test samplethe HF is low (< 1W/cm²)

Page 9: Toulouse Aeronautical Test Centre (CEAT) - FAA Fire Safety · PDF fileToulouse Aeronautical Test Centre (CEAT) « Fire Safety Department » Serge LE NEVE E-mail : Serge.le-neve@dga.defense.gouv.fr

IAMFTWorking Group / Atlantic City / October 09 Diapositive N°9 / 31MINISTÈRE DE LA DÉFENSE

Repeatability of the foam block fire source

Hidden Fire Source

CEAT / Fire Safety Department(Toulouse Aeronautical Test Centre)

Nouvelle mousse 16kg/m3 + 10ml d' heptane - distance 3 pouces du fluxmètre supérieur (7969) - 05/08/09

0

100

200

300

400

500

600

700

800

900

1000

0 60 120 180 240 300 360 420

Temps (s)

Tem

péra

ture

(°C

)

0

5

10

15

20

25

Puis

sanc

e (k

W)

TH1

TH2TH3

TH4

Ancienne mousse 16kg/m3 + 10ml d' heptane - distance 3 pouces du fluxmètre supérieur (7969) - 05/08/09

0

100

200

300

400

500

600

700

800

900

1000

0 60 120 180 240 300 360 420

Temps (s)

Tem

péra

ture

(°C

)

0

5

10

15

20

25

Puis

sanc

e (k

W)

TH1TH2TH3

TH4

Nouvelle mousse 16kg/m3 + 10ml d' heptane - distance 3 pouces du fluxmètre supérieur (7969) - 06/08/09

0

100

200

300

400

500

600

700

800

900

1000

0 60 120 180 240 300 360 420

Temps (s)

Tem

péra

ture

(°C

)

0

1

2

3

4

5

6

7

8

9

10

Puis

sanc

e (k

W)

TH1TH2TH3

TH4

T ° a t 3 i n c h e s f r o m t h e f o a m t o p

0

1 0 0

2 0 0

3 0 0

4 0 0

5 0 0

6 0 0

7 0 0

8 0 0

0 6 0 1 2 0 1 8 0 2 4 0 3 0 0 3 6 0

T e m p s ( s )

Tem

péra

ture

(°C

)

Fo a m 1 6 k g /m 3 + He p t a n e 1 0 m l - Fo a m to p to HF m e te r : 3 in c h e s - 2 4 /0 6 /0 8

0

1

2

3

4

5

6

7

0 6 0 1 2 0 1 8 0 2 4 0 3 0 0 3 6 0

T e m p s (s )

Flux

(W/c

m²)

Nouvelle mousse 16kg/m3 + 10ml d' heptane - distance 3 pouces du fluxmètre supérieur (7969) - 05/08/09

0

1

2

3

4

5

6

7

0 60 120 180 240 300 360 420

Temps (s)

Flux

(W/c

m²)

TOP

7969

Ancienne mousse 16kg/m3 + 10ml d' heptane - distance 3 pouces du fluxmètre supérieur (7969) - 05/08/09

0

1

2

3

4

5

6

7

0 60 120 180 240 300 360 420

Temps (s)

Flux

(W/c

m²)

TOP

7969

Nouvelle mousse 16kg/m3 + 10ml d' heptane - distance 3 pouces du fluxmètre supérieur (7969) - 06/08/09

0

1

2

3

4

5

6

7

0 60 120 180 240 300 360 420

Temps (s)

Flux

(W/c

m²)

TOP

7969

Good repeatability

Page 10: Toulouse Aeronautical Test Centre (CEAT) - FAA Fire Safety · PDF fileToulouse Aeronautical Test Centre (CEAT) « Fire Safety Department » Serge LE NEVE E-mail : Serge.le-neve@dga.defense.gouv.fr

IAMFTWorking Group / Atlantic City / October 09 Diapositive N°10 / 31MINISTÈRE DE LA DÉFENSE

Effect of the distance on the flame characteristics

Average T° vs Distance from foam top to plate

0

200

400

600

800

1000

0 2 4 6 8 10

Inch°C

max T° Av. T for 30'Av. T for 60'Av. T for 90'

Average Heat Flux vs Distance from foam top to plate

0

2

4

6

8

0 2 4 6 8 10

Inch

W/c

max Heat FluxAv. HF for 30'Av. HF for 60'Av. HF for 90'

Various distances from the foam top to the plate were tested :

• 9 inches• 6 inches• 3 inches• 2 inches

Hidden Fire Source

CEAT / Fire Safety Department(Toulouse Aeronautical Test Centre)

The averages of T° and HF during the active burn time are relatively constant from 2 to 5/6 inches :

Page 11: Toulouse Aeronautical Test Centre (CEAT) - FAA Fire Safety · PDF fileToulouse Aeronautical Test Centre (CEAT) « Fire Safety Department » Serge LE NEVE E-mail : Serge.le-neve@dga.defense.gouv.fr

IAMFTWorking Group / Atlantic City / October 09 Diapositive N°11 / 31MINISTÈRE DE LA DÉFENSE

Final specifications

Av T°C d = 2 inches d = 3 inches d = 6 inches d = 9 inches

30" 697 700 588 447

60" 621 642 492 365

90" 494 495 375 278

Max : 805°C 781°C

Av HF (W/cm²) d = 2 inches d = 3 inches d = 6 inches d = 9 inches

30" 4,35 5 4,33 1,60 to 3,90

60" 4,05 4,75 3,32 0,65 to 2

90" 3,01 3,44 2,4 0,60 to 1,5

Max : 6,14 W/cm² 6,84 W/cm²

Fire source specifications :T° ~ 650 to 700 °CHeat Flux Density ~ 4 to 5 W/cm²

Hidden Fire Source

CEAT / Fire Safety Department(Toulouse Aeronautical Test Centre)

SPECIFICATIONS to be representative of the active fire stage at 2 / 3 inches :

Page 12: Toulouse Aeronautical Test Centre (CEAT) - FAA Fire Safety · PDF fileToulouse Aeronautical Test Centre (CEAT) « Fire Safety Department » Serge LE NEVE E-mail : Serge.le-neve@dga.defense.gouv.fr

IAMFTWorking Group / Atlantic City / October 09 Diapositive N°12 / 31MINISTÈRE DE LA DÉFENSE

ISO 2685 Gas Burner Lowest energetic flame

Heat flux Maping (3 inches above the burner)

The flame T° was too high (950 °C)

The Heat Flux profile was not homogeneous, with a very thin peak of HF.

Diameter = 152 mm

Several settings were tested, the lowest energetic flame was :

Hidden Fire Source

CEAT / Fire Safety Department(Toulouse Aeronautical Test Centre)

Page 13: Toulouse Aeronautical Test Centre (CEAT) - FAA Fire Safety · PDF fileToulouse Aeronautical Test Centre (CEAT) « Fire Safety Department » Serge LE NEVE E-mail : Serge.le-neve@dga.defense.gouv.fr

IAMFTWorking Group / Atlantic City / October 09 Diapositive N°13 / 31MINISTÈRE DE LA DÉFENSE

CEAT Hidden Fire Source

Experimental PROPANE burner made with 5 drilled tubes

(1st design)

Hidden Fire Source

CEAT / Fire Safety Department(Toulouse Aeronautical Test Centre)

Page 14: Toulouse Aeronautical Test Centre (CEAT) - FAA Fire Safety · PDF fileToulouse Aeronautical Test Centre (CEAT) « Fire Safety Department » Serge LE NEVE E-mail : Serge.le-neve@dga.defense.gouv.fr

IAMFTWorking Group / Atlantic City / October 09 Diapositive N°14 / 31MINISTÈRE DE LA DÉFENSE

Characterisation of the CEAT gas burner’s flame

Heat Flux density

T° Flame T° ~ 750 °C

Heat Flux ~ 5,5 W/cm²

The flame characteristics are homogeneous & close to the flame of the

foam block

CEAT Hidden Fire Source

Distance of measurement : 6 inches

Hidden Fire Source

CEAT / Fire Safety Department(Toulouse Aeronautical Test Centre)

Page 15: Toulouse Aeronautical Test Centre (CEAT) - FAA Fire Safety · PDF fileToulouse Aeronautical Test Centre (CEAT) « Fire Safety Department » Serge LE NEVE E-mail : Serge.le-neve@dga.defense.gouv.fr

IAMFTWorking Group / Atlantic City / October 09 Diapositive N°15 / 31MINISTÈRE DE LA DÉFENSE

T300 / 914 Carbon-EpoxyT300J or HTA / RTM6 Carbon-Epoxy

Surface exposed to the flame :

150 x 400 mm

Several tests were performed to compare the profile of T° on the back side of the test samples

Hidden Fire Source

CEAT / Fire Safety Department(Toulouse Aeronautical Test Centre)

Determination of the fire scenario equivalent to the foam block fire

Page 16: Toulouse Aeronautical Test Centre (CEAT) - FAA Fire Safety · PDF fileToulouse Aeronautical Test Centre (CEAT) « Fire Safety Department » Serge LE NEVE E-mail : Serge.le-neve@dga.defense.gouv.fr

IAMFTWorking Group / Atlantic City / October 09 Diapositive N°16 / 31MINISTÈRE DE LA DÉFENSE

Foam block tests (exposure time : 7 mn (complete burning of the foam)) d = 3 inches

Gas burner tests (exposure time : 45 s to 1 mn 30 s) d = 6 inches

Back side T° - foam block test - T300/914 - 24/09/08

0

100

200

300

0 60 120 180 240

Temps (s)

Tem

péra

ture

(°C

)

Back side T° - Foam block - T300/914 - 26/09/08

0

50

100

150

200

250

300

0 60 120 180 240

Temps (s)

Tem

péra

ture

(°C

)

Back side T° - Gas burner test - 60 s - T300/914 - 26/09/08

0

50

100

150

200

250

300

0 60 120 180 240

Temps (s)

Tem

péra

ture

(°C

)

Back side T° - Gas burner test - 1 mn 15 s - T300/914 - 26/09/08

0

50

100

150

200

250

300

0 60 120 180 240

Temps (s)

Tem

péra

ture

(°C

)

Back side T° - Gas burner test - 1 mn 30s - T300/914 - 25/09/08

0

50

100

150

200

250

300

0 60 120 180 240

Temps (s)

Tem

péra

ture

(°C

)

Back side T° - Gas burner test - 45 s - T300/914 - 26/09/08

0

50

100

150

200

250

300

0 60 120 180 240

Temps (s)

Tem

péra

ture

(°C

)

The back side maximum T° are close45 s gas burner test shows the more similar profile of T°

Determination of an equivalent fire scenario Comparison of the damage tests : Foam block / Gas burner

Hidden Fire Source

CEAT / Fire Safety Department(Toulouse Aeronautical Test Centre)

Equivalent scenario :Time of exposure : 45 sDistance burner / test sample : 6 inches

Page 17: Toulouse Aeronautical Test Centre (CEAT) - FAA Fire Safety · PDF fileToulouse Aeronautical Test Centre (CEAT) « Fire Safety Department » Serge LE NEVE E-mail : Serge.le-neve@dga.defense.gouv.fr

IAMFTWorking Group / Atlantic City / October 09 Diapositive N°17 / 31MINISTÈRE DE LA DÉFENSE

Non Destructive Investigation(Ultrasonic Phased Array Analysis)

Test 1 Test 2

45 s 60 s

Comparative damaging tests

Various materials and setting were investigated• T300 / 914 Carbon-Epoxy• HTA / RTM6 Carbon-Epoxy• T300J / RTM6 Carbon-Epoxy

Comparison of the damages : Foam block / Gas burner

Gas burner test

Foam block test

damages are homogeneoushidden fire source is a little bit more severe

Hidden Fire Source

CEAT / Fire Safety Department(Toulouse Aeronautical Test Centre)

Page 18: Toulouse Aeronautical Test Centre (CEAT) - FAA Fire Safety · PDF fileToulouse Aeronautical Test Centre (CEAT) « Fire Safety Department » Serge LE NEVE E-mail : Serge.le-neve@dga.defense.gouv.fr

IAMFTWorking Group / Atlantic City / October 09 Diapositive N°18 / 31MINISTÈRE DE LA DÉFENSE

Good agreement of the maximum T°

FOAM BLOCK Hidden Fire Source

Comparison of the back side T°Comparative damaging tests

Hidden Fire Source

CEAT / Fire Safety Department(Toulouse Aeronautical Test Centre)

5736-C259, 320*175 mm, 6 drilled tubes at 6", 1070 ln/h propane - 06/04/09

0102030405060708090

100110120130140150160170180190200210220230240250

0 30 60 90 120 150 180 210 240 270 300 330 360 390 420

Time (s)

Tem

pera

ture

(°C

) T1

T2 T3

T4 T5

5736-C259, 320*175 mm, Foam block at 3" - 07/04/09

0102030405060708090

100110120130140150160170180190200210220230240250

0 30 60 90 120 150 180 210 240 270 300 330 360 390 420

Time (s)

Tem

pera

ture

(°C

) T1 T2 T3 T4 T5

Back side

Good homogeneity

Page 19: Toulouse Aeronautical Test Centre (CEAT) - FAA Fire Safety · PDF fileToulouse Aeronautical Test Centre (CEAT) « Fire Safety Department » Serge LE NEVE E-mail : Serge.le-neve@dga.defense.gouv.fr

IAMFTWorking Group / Atlantic City / October 09 Diapositive N°19 / 31MINISTÈRE DE LA DÉFENSE

- Quite good homogeneity- Hidden fire source is a little bit more severe

FOAM BLOCKHidden Fire Source

Comparative damaging tests

Hidden Fire Source

CEAT / Fire Safety Department(Toulouse Aeronautical Test Centre)

NDI of the damages

5736 C239 5736 C239

Page 20: Toulouse Aeronautical Test Centre (CEAT) - FAA Fire Safety · PDF fileToulouse Aeronautical Test Centre (CEAT) « Fire Safety Department » Serge LE NEVE E-mail : Serge.le-neve@dga.defense.gouv.fr

IAMFTWorking Group / Atlantic City / October 09 Diapositive N°20 / 31MINISTÈRE DE LA DÉFENSE

- Quite good homogeneity- Hidden fire source is a little bit less severe

FOAM BLOCK Hidden Fire Source

Hidden Fire Source

CEAT / Fire Safety Department(Toulouse Aeronautical Test Centre)

NDI of the damages

5736 C2595736 C259

Comparative damaging tests

Page 21: Toulouse Aeronautical Test Centre (CEAT) - FAA Fire Safety · PDF fileToulouse Aeronautical Test Centre (CEAT) « Fire Safety Department » Serge LE NEVE E-mail : Serge.le-neve@dga.defense.gouv.fr

IAMFTWorking Group / Atlantic City / October 09 Diapositive N°21 / 31MINISTÈRE DE LA DÉFENSE

- Good homogeneity on the left side of the gas test sample- the large delaminated area is probably due to a defect of the material

Hidden Fire Source

CEAT / Fire Safety Department(Toulouse Aeronautical Test Centre)

NDI of the damages

6909 R266909 R26

FOAM BLOCK Hidden Fire Source

Comparative damaging tests

Page 22: Toulouse Aeronautical Test Centre (CEAT) - FAA Fire Safety · PDF fileToulouse Aeronautical Test Centre (CEAT) « Fire Safety Department » Serge LE NEVE E-mail : Serge.le-neve@dga.defense.gouv.fr

IAMFTWorking Group / Atlantic City / October 09 Diapositive N°22 / 31MINISTÈRE DE LA DÉFENSE

- Very good homogeneity- Very good agreement of the damages

Hidden Fire Source

CEAT / Fire Safety Department(Toulouse Aeronautical Test Centre)

NDI of the damages

6919 R266919 R26

FOAM BLOCK Hidden Fire Source

Comparative damaging tests

Page 23: Toulouse Aeronautical Test Centre (CEAT) - FAA Fire Safety · PDF fileToulouse Aeronautical Test Centre (CEAT) « Fire Safety Department » Serge LE NEVE E-mail : Serge.le-neve@dga.defense.gouv.fr

IAMFTWorking Group / Atlantic City / October 09 Diapositive N°23 / 31MINISTÈRE DE LA DÉFENSE

Hidden Fire Source (Propane)

Hidden Fire Source

CEAT / Fire Safety Department(Toulouse Aeronautical Test Centre)

- Burner size : 400mm x 370mm

- 6 drilled tubes of 8mm (inner diam.)

- Diameter of the drillings : 1.5mm

Page 24: Toulouse Aeronautical Test Centre (CEAT) - FAA Fire Safety · PDF fileToulouse Aeronautical Test Centre (CEAT) « Fire Safety Department » Serge LE NEVE E-mail : Serge.le-neve@dga.defense.gouv.fr

IAMFTWorking Group / Atlantic City / October 09 Diapositive N°24 / 31MINISTÈRE DE LA DÉFENSE

Hidden Fire Source (Propane)

Hidden Fire Source

CEAT / Fire Safety Department(Toulouse Aeronautical Test Centre)

- The burner is placed in a steel pan (404mm x 404mm)

- 2 ceramic plates on 2 sides to guide the flames from the lateral tubes

Page 25: Toulouse Aeronautical Test Centre (CEAT) - FAA Fire Safety · PDF fileToulouse Aeronautical Test Centre (CEAT) « Fire Safety Department » Serge LE NEVE E-mail : Serge.le-neve@dga.defense.gouv.fr

IAMFTWorking Group / Atlantic City / October 09 Diapositive N°25 / 31MINISTÈRE DE LA DÉFENSE

Hidden Fire Source

CEAT / Fire Safety Department(Toulouse Aeronautical Test Centre)

Mass Flow Controller

Hidden Fire Source (Propane)

- Gas flow rate : 1000 ln/h (standard conditions)

- Flow rate control : Mass Flow Controler

Page 26: Toulouse Aeronautical Test Centre (CEAT) - FAA Fire Safety · PDF fileToulouse Aeronautical Test Centre (CEAT) « Fire Safety Department » Serge LE NEVE E-mail : Serge.le-neve@dga.defense.gouv.fr

IAMFTWorking Group / Atlantic City / October 09 Diapositive N°26 / 31MINISTÈRE DE LA DÉFENSE

Burnthrough time :

7 mn 38 s

The fire source is very close to the FAA fire source used on wind tunnel test (under static conditions) (FAA burnthrough time is : 9 to 10 mn (thickness 3.175 mm (1/4 inch)):

• an estimation of the burnthrough time using our fire source on an aluminum plate of 3.2 mm thickness is around 9 mn 40 s.

Damaging test on aluminium plateAluminium plate – 2,5 mm

Hidden Fire Source

CEAT / Fire Safety Department(Toulouse Aeronautical Test Centre)

Thickness (mm)

T (mn)

2.5mm 3.175 mm

7 mn 38s

9 mn 40s

Time to burnthrough

Page 27: Toulouse Aeronautical Test Centre (CEAT) - FAA Fire Safety · PDF fileToulouse Aeronautical Test Centre (CEAT) « Fire Safety Department » Serge LE NEVE E-mail : Serge.le-neve@dga.defense.gouv.fr

IAMFTWorking Group / Atlantic City / October 09 Diapositive N°27 / 31MINISTÈRE DE LA DÉFENSE

45° test

Hidden Fire Source

CEAT / Fire Safety Department(Toulouse Aeronautical Test Centre)

- Good agreement for the maximum T°- HF is a little bit lower for the gas burner

Page 28: Toulouse Aeronautical Test Centre (CEAT) - FAA Fire Safety · PDF fileToulouse Aeronautical Test Centre (CEAT) « Fire Safety Department » Serge LE NEVE E-mail : Serge.le-neve@dga.defense.gouv.fr

IAMFTWorking Group / Atlantic City / October 09 Diapositive N°28 / 31MINISTÈRE DE LA DÉFENSE

45° test Test on : Glass-Epoxy / Aramid Honeycomb

Hidden Fire Source

CEAT / Fire Safety Department(Toulouse Aeronautical Test Centre)

Before test After test

- Due to the size of the gas burner, the size of the damaged area is different- The burn lengths are close

Page 29: Toulouse Aeronautical Test Centre (CEAT) - FAA Fire Safety · PDF fileToulouse Aeronautical Test Centre (CEAT) « Fire Safety Department » Serge LE NEVE E-mail : Serge.le-neve@dga.defense.gouv.fr

IAMFTWorking Group / Atlantic City / October 09 Diapositive N°29 / 31MINISTÈRE DE LA DÉFENSE

CONCLUSIONS

The gas fire source (at d=6”) generates the same flame characteristics (T° / Heat Flux) than the FAA foam block fire source (at d=3”)

The repeatability of the flame characteristics and of the damages generated on composite materials has been verified

The damages resulting from the gas fire source and from the FAA foam block are well correlated

Hidden Fire Source

CEAT / Fire Safety Department(Toulouse Aeronautical Test Centre)

Page 30: Toulouse Aeronautical Test Centre (CEAT) - FAA Fire Safety · PDF fileToulouse Aeronautical Test Centre (CEAT) « Fire Safety Department » Serge LE NEVE E-mail : Serge.le-neve@dga.defense.gouv.fr

IAMFTWorking Group / Atlantic City / October 09 Diapositive N°30 / 31MINISTÈRE DE LA DÉFENSE

NEXT WORKS

To run the first fire tests and the mechanical characterisations after a fire exposure

To define the other various scenarios of exposure(from 45s (ignition stage) to a duration to be determined simulating a declared hidden fire)

To define the test procedures for the under load fire test

To run the fabrication of the various composite materials to be tested

Hidden Fire Source

CEAT / Fire Safety Department(Toulouse Aeronautical Test Centre)

Page 31: Toulouse Aeronautical Test Centre (CEAT) - FAA Fire Safety · PDF fileToulouse Aeronautical Test Centre (CEAT) « Fire Safety Department » Serge LE NEVE E-mail : Serge.le-neve@dga.defense.gouv.fr

Toulouse Aeronautical Test Centre (CEAT)« Fire Safety Department »

Serge LE NEVE

E-mail : [email protected]

DEVELOPMENTOF A REPEATABLE

HIDDEN FIRE SOURCE