Total Changes Content 821 - tn.gov

63
file://NoURLProvided[1/28/2021 5:10:02 PM] Styling and Annotations 0 Styling 0 Annotations 1/28/2021 5:10:02 PM Compare Results Total Changes 821 Text only comparison Content 486 Replacements 225 Insertions 110 Deletions Go to First Change (page 1) Old File: ust_si-process_technical-chapter-4- 1_corrosion-protection.pdf 49 pages (1.77 MB) 9/24/2015 8:54:12 AM versus New File: TC 4.1 - Corrosion Chapter Final DRAFT_20210128_noblueline.pdf 62 pages (2.70 MB) 1/28/2021 5:01:22 PM

Transcript of Total Changes Content 821 - tn.gov

Page 1: Total Changes Content 821 - tn.gov

file://NoURLProvided[1/28/2021 5:10:02 PM]

Styling andAnnotations

0 Styling

0 Annotations

1/28/2021 5:10:02 PM

Compare Results

Total Changes

821Text only comparison

Content

486 Replacements

225 Insertions

110 Deletions

Go to First Change (page 1)

Old File:

ust_si-process_technical-chapter-4-1_corrosion-protection.pdf

49 pages (1.77 MB)9/24/2015 8:54:12 AM

versus

New File:

TC 4.1 - Corrosion Chapter FinalDRAFT_20210128_noblueline.pdf

62 pages (2.70 MB)1/28/2021 5:01:22 PM

Page 2: Total Changes Content 821 - tn.gov

DRAFT

Corrosion Protection Standardized Inspection Manual

Technical Chapter 4.1

Tennessee Department of Environment & Conservation

Division of Underground Storage Tanks

Rules Effective October 13, 2018

Document Last Edited: 1/28/2021

Text Inserted�
Text
"Corrosion Protection"
Text Inserted�
Text
"DRAFT"
Text Inserted�
Text
"Standardized Inspection Manual Technical Chapter 4.1 Tennessee Department of Environment & Conservation Division of Underground Storage Tanks Rules Effective October 13, 2018 Document Last Edited: 1/28/2021"
Page 3: Total Changes Content 821 - tn.gov

DRAFT

This page intentionally left blank

Text Inserted�
Text
"DRAFT"
Text Deleted�
Text
"1"
Page 4: Total Changes Content 821 - tn.gov

DRAFT

i

Table of Contents

1. DISCLAIMER 1

2. PURPOSE 1

3. AUTHORITY 1

4. APPLICABILITY 2

5. REQUIREMENTS 3

a. General Design and Construction of Tanks .......................................................................................... 3

b. General Design and Construction of Piping ......................................................................................... 4

1. Non-Metallic (Rigid or Flexible) ........................................................................................................ 4

2. Metallic ................................................................................................................................................ 4

6. Corrosion System Design and Construction 4

a. Corrosion Expert ...................................................................................................................................... 4

b. Cathodic Protection Tester ..................................................................................................................... 5

7. Methods of Corrosion Protection 5

a. Galvanic Systems ...................................................................................................................................... 6

1. Design and Construction .................................................................................................................. 6

2. Operation and Maintenance/Inspection ........................................................................................ 6

3. Repairs ................................................................................................................................................ 6

4. Testing ................................................................................................................................................. 7

5. Recordkeeping ................................................................................................................................... 9

b. Impressed Current Systems ................................................................................................................. 10

1. Design and Construction ................................................................................................................ 10

2. Operation and Maintenance/Inspection ...................................................................................... 10

3. Repairs .............................................................................................................................................. 12

4. Testing ............................................................................................................................................... 13

5. Recordkeeping ................................................................................................................................. 14

8. Corrosion Protection for Flexible (flex) Connectors and Short Sections of Metal Piping 15

a. Isolation ................................................................................................................................................... 15

b. Cathodic Protection & Testing Flex Connectors and Short Sections of Metal Piping* ................. 18

1. Electrically Isolated Flex Connectors ............................................................................................. 19

2. Electrically Shorted (Continuous) Flex Connectors ..................................................................... 20

3. Flex Connectors in Contact with Water Inside Containment Sump(s) ..................................... 20

4. Flex Connectors Not In Contact with Water Inside Containment Sump (or the Sump is Dry) and an Anode Is Attached .............................................................................................................. 21

5. Flex Connector(S)/Piping in a “Partially Contained Sump” ......................................................... 21

6. Short STP Piping Sections: .............................................................................................................. 22

Text Inserted�
Text
"Table of Contents 1. DISCLAIMER 1 PURPOSE 1 AUTHORITY 1 PLICABILITY 2 REQUIREMENTS 3 2. 3. 4. AP 5. a. General Design and Construction of Tanks .......................................................................................... 3 b. General Design and Construction of Piping ......................................................................................... 4 1. Non-Metallic (Rigid or Flexible) ........................................................................................................ 4 2 . Metallic"
Text Inserted�
Text
"DRAFT"
Text Inserted�
Text
"................................................................................................................................................ 4 6. Corrosion System Design and Construction 4 a. Corrosion Expert ...................................................................................................................................... 4 b. Cathodic Protection Tester ..................................................................................................................... 5 7. Methods of Corrosion Protection 5 a. Galvanic Systems ...................................................................................................................................... 6 1. Design and Construction .................................................................................................................. 6 2. Operation and Maintenance/Inspection ........................................................................................ 6 3 . Repairs ................................................................................................................................................ 6 4 . Testing ................................................................................................................................................. 7 5. Rec ordkeeping ................................................................................................................................... 9 b. I mpressed Current Systems ................................................................................................................. 10 1. Design and Construction ................................................................................................................ 10 2. Operation and Maintenance/Inspection ...................................................................................... 10 3 . Repairs .............................................................................................................................................. 12 4 . Testing ............................................................................................................................................... 13 5. Rec ordkeeping ................................................................................................................................. 14 8. Corrosion Protection for Flexible (flex) Connectors and Short Sections of Metal Piping 15 a. I solation ................................................................................................................................................... 15 b. Cathodic Protection & Testing Flex Connectors and Short Sections of Metal Piping* ................. 18 1. Electrically Isolated Flex Connectors ............................................................................................. 19 2. Electrically Shorted (Continuous) Flex Connectors ..................................................................... 20 3. Flex Connectors in Contact with Water Inside Containment Sump(s) ..................................... 20 4. Flex Connectors Not In Contact with Water Inside Containment Sump (or the Sump is Dry) and an Anode Is Attached .............................................................................................................. 21 5. Flex Connector(S)/Piping in a “Partially Contained Sump” ......................................................... 21 6. Short STP Piping Sections: .............................................................................................................. 22"
Text Inserted�
Text
"i"
Page 5: Total Changes Content 821 - tn.gov

DRAFT

ii

9. Internally Lined Tanks 22

a. For internally lined tanks with a CP system (tanks with a properly operating CP system do not require periodic inspections of the internal lining) ........................................................................... 22

b. Internal Lining of Tanks as a Tank Repair ........................................................................................... 22

c. Lining And Relining Tanks to Assure Compatibility with Alternative Fuels .................................... 24

REFERENCES 25

APPENDICES 26

APPENDIX 1: STRUCTURE-TO-SOIL TEST PROCEDURE FOR GALVANIC CATHODIC PROTECTION SYSTEMS 27

APPENDIX 2: CONTINUITY TESTING PROCEDURE FOR CATHODIC PROTECTION SYSTEMS 30

APPENDIX 3: STRUCTURE-TO-SOIL TEST PROCEDURE FOR IMPRESSED CURRENT CATHODIC PROTECTION SYSTEMS 32

APPENDIX 4: TEST PROCEDURE FOR FLEX CONNECTORS (INCLUDING SHORT SECTIONS OF METAL PIPING) 35

APPENDIX 5: COMMONLY USED DEFINITIONS 38

APPENDIX 6: IMPRESSED CURRENT CATHODIC PROTECTION TESTING SURVEY 41

APPENDIX 7: GALVANIC CATHODIC PROTECTION TESTING SURVEY 51

APPENDIX 8: IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM 60-DAY RECORD OF RECTIFER OPERATION FORM 60

Text Inserted�
Text
"9. Internally Lined Tanks 22 a. For internally lined tanks with a CP system (tanks with a properly operating CP system do not require periodic inspections of the internal lining) ........................................................................... 22 b. Internal Lining of Tanks as a Tank Repair ........................................................................................... 22 c. Lining And Relining Tanks to Assure Compatibility with Alternative Fuels .................................... 24 REFERENCES 25 APPENDICES 26 APPENDIX 1 : STRUCTURE-TO-SOIL TEST PROCEDURE FOR GALVANIC CATHODIC PROTECTION SYSTEMS 27 APPENDIX 2 : CONTINUITY TESTING PROCEDURE FOR CATHODIC PROTECTION SYSTEMS 30 APPENDIX 3 : STRUCTURE-TO-SOIL TEST PROCEDURE FOR IMPRESSED CURRENT CATHODIC PROTECTION SYSTEMS 32 APPENDIX 4 : TEST PROCEDURE FOR FLEX CONNECTORS (INCLUDING SHORT SECTIONS OF METAL PIPING)"
Text Inserted�
Text
"DRAFT"
Text Inserted�
Text
"35 APPENDIX 5 : COMMONLY USED DEFINITIONS 38 APPENDIX 6 : IMPRESSED CURRENT CATHODIC PROTECTION TESTING SURVEY 41 APPENDIX 7 : GALVANIC CATHODIC PROTECTION TESTING SURVEY 51 APPENDIX 8 : IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM 60-DAY RECORD OF RECTIFER OPERATION FORM 60 ii"
Page 6: Total Changes Content 821 - tn.gov

DRAFT

1

STATE OF TENNESSEE DEPARTMENT OF ENVIRONMENT AND CONSERVATION

DIVISION OF UNDERGROUND STORAGE TANKS

TECHNICAL CHAPTER 4.1 CORROSION PROTECTION

1. DISCLAIMER

This document is guidance only and does not affect legal rights or obligations. Agency decisions in any particular case will be made applying applicable laws and regulations to the specific facts. Mention of trade names or commercial products does not constitute an endorsement or recommendation for use.

2. PURPOSE

The purpose of this technical chapter is to assist Division of Underground Storage Tanks (Division) staff in understanding the requirements for Underground Storage Tank (UST) system corrosion protection design, construction, operation/maintenance, repair, testing, and recordkeeping. Evaluating the performance of these systems, whether during operational inspections by the State or during the periodically required testing by vendors, has resulted in some inconsistencies in understanding and application of testing practices. State policies and regulations have historically deferred to industry standards without specifics in regard to inspection and testing practices. A primary goal of this technical chapter is to standardize the performance evaluation of these systems by detailing specific policies and guidelines that will create a uniformity of understanding and consistency of practice among Division inspectors, testers, and service providers. This technical chapter contains the current policy of the Division based on the statute and regulations governing the Tennessee Petroleum Underground Storage Tank program. This document supersedes all previously published versions. The most current version of this technical chapter will be posted on the Division’s website https://www.tn.gov/environment/program-areas/ust-underground-storage-tanks.html.

3. AUTHORITY All rules referred to in this technical chapter are contained in Chapter 0400-18-01 and are available on the Division of Underground Storage Tanks website at https://publications.tnsosfiles.com/rules/0400/0400-18/0400-18.htm

Text Replaced�
Text
[Old]: "EFFECTIVE DATE – October 1, 2015" [New]: "1. DISCLAIMER This document is guidance only and does not affect legal rights or obligations. Agency decisions in any particular case will be made applying applicable laws and regulations to the specific facts. Mention of trade names or commercial products does not constitute an endorsement or recommendation for use. 2." Font "Open Sans,Bold" changed to "OpenSans-Bold".Font-size "11.04" changed to "12".
Text Inserted�
Text
"DRAFT"
Text Replaced�
Text
[Old]: "and always available on the Division’s website." [New]: "on the Division’s website https://www.tn.gov/environment/program-areas/ust-underground-storage-tanks.html. 3." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "http://www.state.tn.us/sos/rules/0400/0400-18/0400-1801.20130121.pdf" [New]: "https://publications.tnsosfiles.com/rules/0400/0400-18/0400-18.htm" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "2" [New]: "1" Font "Times New Roman" changed to "OpenSans".Font-size "12" changed to "10.98".
Page 7: Total Changes Content 821 - tn.gov

DRAFT

2

4. APPLICABILITY Rules .02(4)(a), .02(4)(b) and 02(4)(c)1. require that all corrosion protection systems be designed, constructed, operated and maintained to continuously provide corrosion protection to the metal components of that portion of the tank and/or piping that “routinely contains petroleum” and is in contact with the ground. The United States Environmental Protection Agency, for the purpose of corrosion protection, interprets the term “ground” to be any naturally occurring substance (e.g., soil, sand, water, gravel, etc.) that can serve as an electrolyte and thereby result in corrosion to a metallic object. These components include, but are not limited to1:

a. Any bare steel (no dielectric coating) tanks or piping*;

b. STI-P3® tank systems with depleted anodes;

c. All below-grade piping (including piping that is partially above-grade if continuous with below grade piping, remote fill piping, and connecting piping for manifolded tanks);

d. Metal flexible connectors (including any section of piping between dispensers or submersible turbine pump (STP) heads and the respective flexible connectors regardless of length);

e. Any tank or piping with a coating that is determined not to be acceptable by the Division as a “suitable dielectric coating” (Note: dielectric coatings alone are not adequate corrosion protection)*;

f. Tank systems constructed with suitable dielectric coatings (i.e., fiberglass or urethane, ACT-100® tanks, etc.) that a corrosion expert requires to be bonded into the same cathodic protection system of other tanks within or near the same tankhold; or

g. Any other system component that could potentially cause a release of petroleum into the environment as a result of corrosion failure unless a corrosion expert determines corrosion protection (CP) is not required.

1 Required by Rule 0400-18-01-.02(4)(c)1

Text Inserted�
Text
"4."
Text Replaced�
Text
[Old]: "Rule .02(4)(c)1. requires that all corrosion protection systems must" [New]: "Rules .02(4)(a), .02(4)(b) and 02(4)(c)1. require that all corrosion protection systems" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "operated," [New]: "operated" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "and" [New]: "and/or" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "the ground and/or any liquid. These components include: 1." [New]: "the ground. The United States Environmental Protection Agency, for the purpose of corrosion protection, interprets the term “ground” to be any naturally occurring substance (e.g., soil, sand, water, gravel, etc.) that can serve as an electrolyte and thereby result in corrosion to a metallic object. These components include, but are not limited to" Font "Open Sans,Bold" changed to "OpenSans".
Text Inserted�
Text
"DRAFT"
Text Inserted�
Text
"1 : a."
Text Replaced�
Text
[Old]: "piping* 2. STI-P3® tank systems which original anodes have become depleted 3." [New]: "piping*; b. STI-P3 ® tank systems with depleted anodes; c." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "piping) including remote fill piping 4. Metal flexible connectors including any sections" [New]: "piping, remote fill piping, and connecting piping for manifolded tanks); d. Metal flexible connectors (including any section" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "STP" [New]: "submersible turbine pump (STP)" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "length. 5." [New]: "length); e." Font "Open Sans,Bold" changed to "OpenSans-Bold".
Text Replaced�
Text
[Old]: "protection)* 6." [New]: "protection)*; f." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "(such as" [New]: "(i.e.," Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "tanks)" [New]: "tanks, etc.)" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "tankhold. 7. Or, any" [New]: "tankhold; or g. Any" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "CP is not required. * This only applies to" [New]: "corrosion protection (CP) is not required. 1 Required by Rule 0400-18-01-.02(4)(c)1" Font "Open Sans" changed to "OpenSans".
Text Deleted�
Text
"CORROSION SYSTEM DESIGN AND CONSTRUCTION A Corrosion Expert must design all “field installed” corrosion protection systems as required by rules .02(4)(a)2.(ii) and .02(4)(b)2.(ii). (Field Installed systems include the original or subsequent installation of anodes or modification to a galvanic corrosion protection system or an Impressed Current System.) This does not include anodes installed on isolated flexible connectors that may be in STP sumps or under dispensers. Documentation that the cathodic protection system is designed by a corrosion expert as required by rules .02(4)(a)2.(ii) and .02(4)(b)2.(ii) must be maintained by the owner and/or operator for inspection by the Division."
Text Replaced�
Text
[Old]: "3" [New]: "2" Font "Times New Roman" changed to "OpenSans".Font-size "12" changed to "10.98".
Page 8: Total Changes Content 821 - tn.gov

DRAFT

3

*Any tank or piping system meeting this criterion that was not upgraded by the Federal deadline of December 1998 (Tennessee, December 1999) is considered substandard and shall be immediately and permanently closed by removal or closure-in-place as required by rule .07(2). The Division does not require corrosion protection on the following components of an underground tank system:

a. Automatic Tank Gauge (ATG) risers;

b. Vapor recovery risers;

c. Fill risers (only if the fill riser is fitted with a drop tube - see rule .02(4)(b)5);

d. Vent lines;

e. The STP riser including the STP head;

f. Interstitial Monitoring risers or any other riser not routinely containing petroleum;

g. Manifold piping siphon assist lines; or

h. Vapor recovery assist lines.

5. REQUIREMENTS

a. General Design and Construction of Tanks Tanks must be properly designed and constructed as required by rule .02(4)(a), so that any portion underground that routinely contains petroleum and is in contact with the ground is protected from corrosion by one of the following:

1. Fiberglass-Tank is constructed of fiberglass-reinforced plastic - rule .02(4)(a)1;

2. Steel tank with Cathodic Protection-Tank is constructed of steel and is protected from corrosion by a cathodic protection system by either galvanic cathodic protection or impressed current cathodic protection - rule .02(4)(a)2;

3. Composite (Clad)-Tank is constructed of a steel-fiberglass-reinforced-plastic composite - rule .02(4)(a)4;

4. Jacketed-Tank is constructed with a fiberglass-reinforced plastic jacket, which has an interstitial space between the inner tank and the outer jacket - rule .02(4)(a)4;

5. The tank is constructed of metal without additional corrosion protection measures provided that the tank is installed at a site that is determined by a corrosion expert not to be corrosive enough to cause it to have a release due to corrosion during its operational life - rule .02(4)(a)5; or

6. The tank construction and corrosion protection are determined by the Division to be designed to prevent the release of any petroleum in a manner that is no less protective than any of the previously mentioned methods of corrosion protection - rule .02(4)(a)6.

Text Replaced�
Text
[Old]: "tank systems that were required to be" [New]: "*Any tank or piping system meeting this criterion that was not" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "1999). Existing tank systems and piping currently in operation that did not meet the upgrading requirements by these dates cannot be upgraded and are" [New]: "1999) is" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "1." [New]: "a." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "risers and 2. Vapor recovery risers 3. Fill risers, but only" [New]: "risers; b. Vapor recovery risers; c. Fill risers (only" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "tube. See rule .02(4)(b)5. If there is no drop tube, the fill riser must be corrosion protected 4. Vent lines 5. The STP riser including the STP head 6. Interstitial Monitoring risers or any other riser not routinely containing petroleum" [New]: "tube -see rule .02(4)(b)5); d. Vent lines; e. The STP riser including the STP head; f. Interstitial Monitoring risers or any other riser not routinely containing petroleum; g. Manifold" Font "Open Sans" changed to "OpenSans".
Text Deleted�
Text
"REQUIREMENTS"
Text Replaced�
Text
[Old]: "CORROSION EXPERT Corrosion Expert is defined in rule .01(4) and means a person who, by reason of thorough knowledge of the physical sciences and the principles of engineering and mathematics acquired by a professional education and related practical experience, is qualified to engage in the practice of corrosion control on buried or submerged metal piping systems and metal tanks. Such a person must submit documentation for review by the Division that they have accreditation or certification as a Corrosion Specialist or Cathodic Protection Specialist by the National Association of Corrosion Engineers (NACE)." [New]: "piping siphon assist lines; or h. Vapor recovery assist lines." Font "Open Sans,Bold" changed to "OpenSans".Font-size "11.04" changed to "10.02".
Text Deleted�
Text
"If it is determined by the Division that a person has sufficient experience and education to be qualified to take responsible charge in corrosion control of buried or submerged metal piping systems and metal tanks, then that person shall be classified by the Division as a corrosion expert."
Text Deleted�
Text
"The Division currently maintains a list of known corrosion experts that may be provided to owner/operators. To date, the Division has not made any determinations other than those made by NACE regarding who is qualified to be a corrosion expert."
Text Deleted�
Text
"Some examples of situations requiring corrosion expert review:"
Text Replaced�
Text
[Old]: "Design of Field-Installed Cathodic Protection Systems. 2. Any modification (including repairs) of the Cathodic Protection System, such as addition of supplemental anodes or other changes in the design or construction of the Cathodic Protection System. 3." [New]: "REQUIREMENTS a. General Design" Font "Open Sans" changed to "OpenSans-Bold".Font-size "9.96001" changed to "12".
Text Deleted�
Text
"Review of Cathodic Protection System test results indicating anomalies, such as: if stray currents are affecting metallic structures, inconclusive CP test results, and any other system test results that the Division determines to require additional expert review."
Text Replaced�
Text
[Old]: "CATHODIC PROTECTION TESTER A Cathodic Protection Tester is defined in rule .01(4) and means a person who can demonstrate an understanding of the principles and measurements of all common types of cathodic protection systems as applied to buried or submerged metal piping systems and metal tanks." [New]: "and Construction of Tanks" Font "Open Sans,Bold" changed to "OpenSans-Bold".Font-size "11.04" changed to "12".
Text Deleted�
Text
"At a minimum, such persons must have education and experience in soil resistivity, stray current, structure-to-soil potential, and component electrical isolation measurements of buried metal piping and tank systems."
Text Deleted�
Text
"Testing cathodic protection systems is not required to be performed by a corrosion expert to comply with rule .02(4)(c)2."
Text Deleted�
Text
"The Division requires that all cathodic protection testing performed by a person meeting the qualifications of a Cathodic Protection Tester."
Text Replaced�
Text
[Old]: "All testing must be conducted in accordance with the guidelines as detailed in this technical chapter and all results shall be recorded on the official Tennessee Cathodic Protection Testing Survey Forms (CN-1140 and CN-1309) as required by rule .02(4)(c)2.(iii) and .03(2)(b)2 . GENERAL DESIGN AND CONSTRUCTION OF TANKS Tanks must be properly designed and constructed as required by rule .02(4)(a), so that any portion underground that routinely contains petroleum and is in contact with the ground and/or liquid is protected from corrosion by one of the following: 1) Fiberglass-Tank is constructed of fiberglass-reinforced plastic-rule .02(4)(a)1." [New]: "Tanks must be properly designed and constructed as required by rule .02(4)(a), so that any portion underground that routinely contains petroleum and is in contact with the ground is protected from corrosion by one of the following: 1. Fiberglass-Tank is constructed of fiberglass-reinforced plastic -rule .02(4)(a)1;" Font "Open Sans" changed to "OpenSans".
Text Deleted�
Text
"4"
Text Replaced�
Text
[Old]: "(either" [New]: "by either" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "protection)-rule .02(4)(a)2." [New]: "protection -rule .02(4)(a)2;" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "composite-rule .02(4)(a)4." [New]: "composite rule .02(4)(a)4;" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "jacket-rule .02(4)(a)4." [New]: "jacket -rule .02(4)(a)4;" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"DRAFT"
Text Replaced�
Text
[Old]: "life.-rule .02(4)(a)5." [New]: "life -rule .02(4)(a)5; or" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "protection.-rule" [New]: "protection -rule" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"3"
Page 9: Total Changes Content 821 - tn.gov

DRAFT

4

b. General Design and Construction of Piping Piping must be properly designed and constructed, as required by rule .02(4)(b), so that any portion that routinely contains petroleum and is in contact with the ground and/or liquid is protected from corrosion by one of the following methods:

1. Non-Metallic (Rigid or Flexible)

If installed on or after November 1, 2005, shall meet or exceed the Standard for Safety established by Underwriters Laboratory in UL 971 - “Non-Metallic Underground Piping for Flammable Liquids”, July 1, 2005. This requirement shall apply to all new and/or replacement piping. - rule .02(4)(b)1.

2. Metallic

i. Dielectrically coated piping: Piping coated with a suitable dielectric material and has cathodic protection. - rule .02(4)(b)2.(i).

ii. Piping with field-installed cathodic protection system: Bare steel or other metal piping to which a galvanic or impressed current system has been added. - rule .02(4)(b)2.(ii).

iii. Isolation: Metallic piping that is never in contact with the ground and/or liquid (e.g., metallic piping that is contained inside of a rubber boot that is sealed on each end, excavation of all soil or earthen material that exposes the entire length of the piping, or installation of a containment device that isolates the piping from the ground and/or liquid, etc.). - rule .02(4)(b)4.

iv. The piping is constructed of metal without additional corrosion protection measures provided that the piping is installed at a site that is determined by a corrosion expert not to be corrosive enough to cause it to have a release due to corrosion during its operational life. - rule .02(4)(b)3.(i).

v. The piping construction and corrosion protection are determined by the Division to be designed to prevent the release or threatened release of any stored petroleum in a manner that is no less protective than any of the previously mentioned methods of corrosion protection. - rule .02(4)(b)4.

6. Corrosion System Design and Construction A Corrosion Expert must design all “field installed” corrosion protection systems as required by rules .02(4)(a)2.(ii) and .02(4)(b)2.(ii). Field Installed systems include the original or subsequent installation of anodes or modification to a galvanic corrosion protection system or an Impressed Current System and does not include the installation of anodes on flexible connectors in STP sumps, transition sumps or under dispensers. Documentation that the cathodic protection system was designed by a corrosion expert as required by rules .02(4)(a)2.(ii) and .02(4)(b)2.(ii) must be maintained by the owner and/or operator and be available for inspection by the Division.

a. Corrosion Expert

Corrosion Expert is defined in rule .01(4) and means a person who, by reason of thorough knowledge of the physical sciences and the principles of engineering and mathematics acquired by a professional education and related practical experience, is qualified to engage in the practice of corrosion control on buried or submerged metal piping systems and metal tanks. Such a person must submit documentation for review by the Division that the person has accreditation or certification as a Corrosion Specialist or Cathodic Protection Specialist by

Text Replaced�
Text
[Old]: "GENERAL DESIGN AND CONSTRUCTION OF PIPING" [New]: "b. General Design and Construction of Piping" Font "Open Sans,Bold" changed to "OpenSans-Bold".Font-size "11.04" changed to "12".
Text Replaced�
Text
[Old]: "Non-metallic (rigid or flexible) a." [New]: "Non-Metallic (Rigid or Flexible)" Font "Open Sans,Bold" changed to "OpenSans-Bold".Font-size "9.96001" changed to "10.98".
Text Replaced�
Text
[Old]: "piping.-rule .02(4)(b)1.(i) b. Pipe marking or labeling shall comply with the Underwriters Laboratory standard as outlined in Division rules.-rule .02(4)(b)1.(ii)" [New]: "piping. -rule .02(4)(b)1." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "a." [New]: "i." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "protection.-rule .02(4)(b)2.(i) b. Bare steel" [New]: "protection." Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"DRAFT"
Text Inserted�
Text
"-rule .02(4)(b)2.(i). ii. Piping with field-installed"
Text Inserted�
Text
"or other metal"
Text Replaced�
Text
[Old]: "added.-rule .02(4)(b)2.(ii) c." [New]: "added. -rule .02(4)(b)2.(ii). iii." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "(such as rubber boots acceptable to the Division," [New]: "(e.g., metallic piping that is contained inside of a rubber boot that is sealed on each end," Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "any" [New]: "a" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "liquids).-rule .02(4)(b)4. d." [New]: "liquid, etc.). -rule .02(4)(b)4. iv." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "life.-rule .02(4)(b)3.(i) e." [New]: "life. -rule .02(4)(b)3.(i). v." Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"release or threatened release of any stored"
Text Replaced�
Text
[Old]: "METHODS OF CORROSION PROTECTION" [New]: "6. Corrosion System Design and Construction A Corrosion Expert must design all “field installed” corrosion protection systems as required by rules .02(4)(a)2.(ii) and .02(4)(b)2.(ii). Field Installed systems include the original or subsequent installation of anodes or modification to a galvanic corrosion protection system or an Impressed Current System and does not include the installation of anodes on flexible connectors in STP sumps, transition sumps or under dispensers. Documentation that the cathodic protection system was designed by a corrosion expert as required by rules .02(4)(a)2.(ii) and .02(4)(b)2.(ii) must be maintained by the owner and/or operator and be available for inspection by the Division. a. Corrosion Expert Corrosion Expert is defined in rule .01(4) and means a person who, by reason of thorough knowledge of the physical sciences and the principles of engineering and mathematics acquired by a professional education and related practical experience, is qualified to engage in the practice of corrosion control on buried or submerged metal piping systems and metal tanks. Such a person must submit documentation for review by the Division that the person has accreditation or certification as a Corrosion Specialist or Cathodic Protection Specialist by" Font "Open Sans,Bold" changed to "OpenSans-Bold".Font-size "11.04" changed to "12".
Text Replaced�
Text
[Old]: "5" [New]: "4" Font "Times New Roman" changed to "OpenSans".Font-size "12" changed to "10.98".
Page 10: Total Changes Content 821 - tn.gov

DRAFT

5

the National Association of Corrosion Engineers (NACE). If it is determined by the Division that a person has sufficient experience and education to be qualified to take responsible charge in corrosion control of buried or submerged metal piping systems and metal tanks, then that person shall be classified by the Division as a corrosion expert. The Division maintains a list of corrosion experts that routinely perform work in the State of Tennessee. This list is available on the Division’s website.

Some examples of situations requiring corrosion expert review:

Design of Field-Installed Cathodic Protection Systems2.

Any modification (including repairs) of the Cathodic Protection System, such as adding or replacing anodes, or other changes in the design or construction of the Cathodic Protection System. 3

Review of Cathodic Protection System test results indicating anomalies, such as: if stray currents are affecting metallic structures, inconclusive CP test results, and any other system test results that the Division determines to require additional expert review.4

b. Cathodic Protection Tester A Cathodic Protection Tester is defined in rule .01(4) and means a person who can demonstrate an understanding of the principles and measurements of all common types of cathodic protection systems as applied to buried or submerged metal piping systems and metal tanks. At a minimum, such persons must have education and experience in soil resistivity, stray current, structure-to-soil potential, and component electrical isolation measurements of buried metal piping and tank systems. Testing cathodic protection systems is not required to be performed by a corrosion expert to comply with rule .02(4)(c)2. The Division requires that all cathodic protection testing performed by a person meeting the qualifications of a Cathodic Protection Tester. All testing must be conducted in accordance with the guidelines detailed in this technical chapter and all results shall be recorded on the official Tennessee Cathodic Protection Testing Survey Forms (CN-1140 and CN-1309) as required by rule .02(4)(c)2.(iii) and the records be maintained in accordance with rule .03(2)(b)5 .

7. Methods of Corrosion Protection There are two acceptable methods available to meet corrosion protection requirements: Galvanic CP Systems and Impressed Current CP Systems.5 Metals corrode naturally by the loss of electrons from the surface of the metallic components out into the ground. Corrosion protection systems reverse this flow of electrons inhibiting the natural process. Galvanic Systems are “passive” corrosion protection systems that utilize anodes made of metals such as magnesium and zinc that corrode instead of the tank or piping. Due to the difference of the innate electric potentials, a naturally occurring electric current flows from the anodes through moisture in the ground to the tank and/or piping resulting in the protection of the metal components. Impressed Current Systems utilize the same principle but with the addition of an external direct current of electricity

2 Required by Rule 0400-18-01-.02(4)(a)2(ii) 3 Required by Rule 0400-18-01-.02(4)(c)1 4 Required by Rule 0400-18-01-.03(2) 5 Required by Rule 0400-18-01-.02(4)(a)2

Text Inserted�
Text
"the National Association of Corrosion Engineers (NACE). If it is determined by the Division that a person has sufficient experience and education to be qualified to take responsible charge in corrosion control of buried or submerged metal piping systems and metal tanks, then that person shall be classified by the Division as a corrosion expert. The Division maintains a list of corrosion experts that routinely perform work in the State of Tennessee. This list is available on the Division’s website. Some examples of situations requiring corrosion expert review: Design of Field-Installed Cathodic Protection Systems 2 . Any modification (including repairs) of the Cathodic Protection System, such as adding or replacing anodes, or other changes in the design or construction of the Cathodic Protection System. 3 Review of Cathodic Protection System test results indicating anomalies, such as: if stray currents are affecting metallic structures, inconclusive CP test results, and any other system test results that the Division determines to require additional expert review."
Text Inserted�
Text
"DRAFT"
Text Replaced�
Text
[Old]: "There are two acceptable methods available to meet corrosion protection requirements: Galvanic CP Systems and Impressed Current CP Systems. Metals corrode naturally by the loss of electrons from the surface of the metallic components out into the surrounding soil." [New]: "4 b. Cathodic Protection Tester A Cathodic Protection Tester is defined in rule .01(4) and means a person who can demonstrate an understanding of the principles and measurements of all common types of cathodic protection systems as applied to buried or submerged metal piping systems and metal tanks. At a minimum, such persons must have education and experience in soil resistivity, stray current, structure-to-soil potential, and component electrical isolation measurements of buried metal piping and tank systems. Testing cathodic protection systems is not required to be performed by a corrosion expert to comply with rule .02(4)(c)2. The Division requires that all cathodic protection testing performed by a person meeting the qualifications of a Cathodic Protection Tester. All testing must be conducted in accordance with the guidelines detailed in this technical chapter and all results shall be recorded on the official Tennessee Cathodic Protection Testing Survey Forms (CN-1140 and CN-1309) as required by rule .02(4)(c)2.(iii) and the records be maintained in accordance with rule .03(2)(b)5 . 7. Methods of Corrosion Protection There are two acceptable methods available to meet corrosion protection requirements: Galvanic CP Systems and Impressed Current CP Systems. 5 Metals corrode naturally by the loss of electrons from the surface of the metallic components out into the ground." Font "Open Sans" changed to "OpenSans".Font-size "9.96001" changed to "6.48".
Text Inserted�
Text
"2 Required by Rule 0400-18-01-.02(4)(a)2(ii) 3 Required by Rule 0400-18-01-.02(4)(c)1 4 Required by Rule 0400-18-01-.03(2) 5 Required by Rule 0400-18-01-.02(4)(a)2"
Text Inserted�
Text
"5"
Page 11: Total Changes Content 821 - tn.gov

DRAFT

6

applied to the system which supplies the flow of electrons necessary to reverse the corrosion process.

a. Galvanic Systems are comprised of sacrificial anodes installed to cathodically protect metallic

components (tanks, piping, ancillary equipment and/or flex connectors) in contact with soil or liquid. Tanks with anodes that were factory installed on the ends of the tank by the tank manufacturer are referred to as a sti-P3® tank(s). Depending on the situation, supplemental anodes can be bonded to a sti-P3® tank(s) when the original anodes have become depleted.

b. Impressed Current Systems are always “Field Installed” systems that are added subsequent

to the original installation of the tank system. These systems are designed to protect previously unprotected steel tanks, tanks with attached anodes (sti-P3® tanks) that have become depleted, or tanks which were previously lined internally. These systems can be installed to protect the tanks as well as electrically continuous metallic piping.

a. Galvanic Systems

1. Design and Construction

Galvanic systems are also known as sacrificial anode systems because an anode (usually zinc or magnesium) corrodes instead of the metal structure (i.e., the anode sacrifices itself (corrodes) to protect the metal to which it is connected). Sacrificial anodes are connected directly to the structure to be protected by either welding or mechanical connection of lead wires. Galvanic systems are generally limited to those tank components that are well coated with a dielectric material (sti-P3® tanks or fusion bonded epoxy coated steel piping) because the available current output of these systems is low.6 Attempts to protect large areas of uncoated tanks or long runs of piping is generally not practical because the useful life of anodes is too short or the number of anodes needed is too great.

2. Operation and Maintenance/Inspection

Operate and maintain all galvanic systems to continuously provide corrosion protection to the metal components of that portion of the tank, piping and underground ancillary equipment that routinely contains petroleum and is in contact with the ground and/or liquid. See rules .02(4)(a)2. and .02(4)(b)2. Periodic testing of galvanic systems is required every three years, rule .02(4)(c)2.(i), to determine if the system is operating properly and the anodes are supplying sufficient protection. Maintenance/repair of galvanic systems is minimal and, if required, is typically limited to such things as repairs to bonding wires for anodes that have been added subsequently to the original installation of the tanks or reburying of visibly exposed wiring.

3. Repairs

i. Repairs include, but are not limited to, the following: replacement of depleted anode(s), repair or replacement of damaged bonding wires, and repair/replacement of system components to achieve isolation. If supplemental anodes are added or new anodes are installed on a sti-P3® tank, all design and construction requirements must comply with Steel Tank Institute’s “Recommended Practice for the Addition of Supplemental Anodes to sti-P3® USTs” (R972) revised December 2010 (or current version). If, based on the design calculations, greater than 30 milliamperes of current

6 Required by Rule 0400-18-01-.02(4)(c)1

Text Replaced�
Text
[Old]: "1)" [New]: "a." Font "Open Sans,Bold" changed to "OpenSans".
Text Replaced�
Text
[Old]: "anodes that were installed on the ends of the tank by the tank manufacturer such as sti-P3® tanks. These systems may include anodes which were added subsequent to installation such as supplemental anodes bonded to sti-P3® tanks when the original anodes have become depleted. Not only can these systems be installed to protect the tanks, but also steel piping which includes flexible connectors. 2)" [New]: "anodes installed to cathodically protect metallic components (tanks, piping, ancillary equipment and/or flex connectors) in contact with soil or liquid. Tanks with anodes that were factory installed on the ends of the tank by the tank manufacturer are referred to as a sti-P3 ® tank(s). Depending on the situation, supplemental anodes can be bonded to a sti-P3 ® tank(s) when the original anodes have become depleted. b." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "that the" [New]: "with" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"that"
Text Replaced�
Text
[Old]: "steel piping. GALVANIC SYSTEMS" [New]: "metallic piping. a. Galvanic Systems" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "structure. Because the anode corrodes instead of the metal it is protecting, the anode sacrifices itself." [New]: "structure (i.e., the anode sacrifices itself (corrodes) to protect the metal to which it is connected)." Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"DRAFT"
Text Inserted�
Text
"6"
Text Deleted�
Text
"the"
Text Replaced�
Text
[Old]: "maintenance/inspection All galvanic systems must be operated and maintained" [New]: "Maintenance/Inspection Operate and maintain all galvanic systems" Font "Open Sans,Bold" changed to "OpenSans-Bold".Font-size "9.96001" changed to "10.98".
Text Replaced�
Text
[Old]: "Since galvanic systems are “passive” corrosion protection systems, rule .02(4)(c)2.(i) requires only periodic testing every three years" [New]: "Periodic testing of galvanic systems is required every three years, rule .02(4)(c)2.(i)," Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "There are usually no maintenance requirements for galvanic systems and are limited to repairs to such things as" [New]: "Maintenance/repair of galvanic systems is minimal and, if required, is typically limited to such things as repairs to" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "tanks. Due to the nature of construction of the original system or subsequently added anodes, there are no components of galvanic systems usually requiring periodic inspection unless the anode bonding wiring is visible and/or accessible as described above. 3) Repairs a. Repairs include but are not limited to the following: replacement of anode(s) if depleted," [New]: "tanks or reburying of visibly exposed wiring. 3. Repairs i. Repairs include, but are not limited to, the following: replacement of depleted anode(s)," Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"supplemental"
Text Replaced�
Text
[Old]: "to a sti-P3® tank with depleted anodes, that constitutes a “Field Installation” and requires that the CP system be designed by" [New]: "or new anodes are installed on a sti-P3® tank, all design and construction requirements must comply with Steel Tank Institute’s “Recommended Practice for the Addition of Supplemental Anodes to sti-P3® USTs” (R972) revised December 2010 (or current version). If, based on the design calculations, greater than 30 milliamperes of current 6 Required by Rule 0400-18-01-.02(4)(c)1" Font "Open Sans" changed to "OpenSans".
Page 12: Total Changes Content 821 - tn.gov

DRAFT

7

is needed to achieve protection as specified in document R972, a corrosion expert will need to design the corrosion system. This will constitute a “Field Installation” – rules .02(4)(a)2.(ii) and .02(4)(b)2.(ii). All documents related to the repair and design approval by a corrosion expert must be maintained for the life of the system and transferred to any new owner of the system - rules .02(4)(c)5(ii), .02(4)(c)5.(iii), .03(2)(b)5 and .03(2)(d).

ii. The Division will allow the addition of an impressed current system, that is designed

by a corrosion expert as required by rules .02(4)(a)2.(ii) and .02(4)(b)2.(ii), to a STI-P3® tank as a repair of the cathodic protection system when the anodes on a tank are depleted. A bare steel tank which never met the 1999 upgrade deadlines may not be upgraded by addition of an impressed current system. Records of this repair must be maintained for the operational life of the UST system as required by rules .02(7)(h) and transferred to any new owner as required by rule .03(2)(d).

iii. Within six (6) months following a repair of a cathodically protected system, the system

shall be tested in accordance with rule .02(7)(f) to ensure that it is operating properly and all results recorded on the official Tennessee Cathodic Protection Testing Survey Forms (CN-1140 and CN-1309) as required by rule .02(4)(c)2.(iii) and .03(2)(b)5.

4. Testing

i. A Cathodic Protection Tester must inspect all galvanic systems for proper operation within six (6) months of installation and at least every three (3) years thereafter and as stated above tested within six (6) months after a repair. The system must be functioning as designed and is effectively preventing corrosion per rule .02(4)(c)2. Perform all testing in accordance with the instructions in Appendix 1 and 2 of this Technical Chapter, and the Galvanic Cathodic Protection Testing Survey Form (CN-1140).7

ii. All UST systems to which anodes have been added for the purpose of replacing or

enhancing an existing galvanic system shall be tightness tested. The tightness test shall be conducted no later than six (6) months, but no sooner than three (3) months, following the addition of the anodes. See rules .02(4)(c)3. and .02(4)(c)5.(iii). The Division generally does not require tightness testing of flex connectors to which anodes have been added. Records must be transferred to any new owner as required by rule .03(2)(d).

iii. Structures utilizing galvanic cathodic protection will be considered adequately

protected when “A negative (cathodic) potential of at least 850 mV with the protective current applied.8 This potential is measured with respect to a saturated copper/copper sulfate reference electrode contacting the electrolyte. Voltage drops other than those across the structure to electrolyte boundary must be considered for valid interpretation of this measurement.” This criterion is also known as “850 on” and is not applicable to impressed current systems. For a more detailed discussion, see “Measurement Techniques Related to Criteria for Cathodic Protection of Underground Storage Tank Systems” (NACE Standard TM0101, Section 8).

7 Required by Rule 0400-18-01-.03(2)(b)5 8 Required by Rule 0400-18-01-.02(4)(c)2

Text Replaced�
Text
[Old]: "a corrosion expert, according to rules" [New]: "is needed to achieve protection as specified in document R972, a corrosion expert will need to design the corrosion system. This will constitute a “Field Installation” – rules ii." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "system. See rules .02(4)(c)5.(iii) and .03(2)(d). For replacing depleted anodes on STIP-3 or steel product tanks, all design and construction requirements shall comply with Steel Tank Institute’s “Recommended Practice for the Addition of Supplemental Anodes to sti-P3® USTs” (R972) revised January 2006 (or later), or have written repair design calculations signed by a corrosion expert. b. The Division will allow the addition of an impressed current system, that is designed by a corrosion expert as required by rules .02(4)(a)2.(ii) and .02(4)(b)2.(ii), to a STI-P3 tank as a repair of the cathodic protection system when the anodes on a cathodically protected" [New]: "system -rules .02(4)(c)5(ii), .02(4)(c)5.(iii), .03(2)(b)5 and .03(2)(d). The Division will allow the addition of an impressed current system, that is designed by a corrosion expert as required by rules .02(4)(a)2.(ii) and .02(4)(b)2.(ii), to a STI-P3® tank as a repair of the cathodic protection system when the anodes on a" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: ".02(7)(f)" [New]: ".02(7)(h)" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "c." [New]: "iii." Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"DRAFT"
Text Replaced�
Text
[Old]: ".02(7)(e)" [New]: ".02(7)(f)" Font "Open Sans" changed to "OpenSans".
Text Deleted�
Text
"shall be"
Text Replaced�
Text
[Old]: ".03(2)(b)2 . 4) Testing a." [New]: ".03(2)(b)5. 4. Testing i." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "corrosion. See rule .02(4)(c)2. Testing shall be performed in accordance with Appendix 1 and as directed according to instructions in state form CN-1140. b. All UST systems to which sacrificial" [New]: "corrosion per rule .02(4)(c)2. Perform all testing in accordance with the instructions in Appendix 1 and 2 of this Technical Chapter, and the Galvanic Cathodic Protection Testing Survey Form (CN1140).7 ii. All UST systems to which" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "may" [New]: "generally does" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "c." [New]: "iii." Font "Times New Roman" changed to "OpenSans".Font-size "12" changed to "10.02".
Text Deleted�
Text
"according to the criterion in Section 8 of NACE TM0101"
Text Inserted�
Text
"8"
Text Inserted�
Text
"For a more detailed discussion, see “Measurement Techniques Related to Criteria for Cathodic Protection of Underground Storage Tank Systems” (NACE Standard TM0101, Section 8). 7 Required by Rule 0400-18-01-.03(2)(b)5 8 Required by Rule 0400-18-01-.02(4)(c)2"
Page 13: Total Changes Content 821 - tn.gov

DRAFT

8

NOTE: A Cathodic Protection Tester may not use a cathodic protection test station (such as PP4®) that was permanently installed during the original installation of tank system to obtain potential measurements during a cathodic protection test.8 Also, a cathodic protection test wire (such as PP2®) may not be used unless it has been demonstrated that the wire is continuous with the tank bottom.8The reason for not using a test station and/or test wire is because of possible continuity issues, unknown location of wire contact point, and/or deterioration of the originally installed reference cell. Any of which can result in incorrect potential readings.

Text Replaced�
Text
[Old]: "(PP4" [New]: "(such as PP4" Font "Open Sans,Bold" changed to "OpenSans".
Text Inserted�
Text
"DRAFT"
Text Inserted�
Text
"8"
Text Replaced�
Text
[Old]: "(PP2" [New]: "(such as PP2" Font "Open Sans,Bold" changed to "OpenSans".
Text Replaced�
Text
[Old]: "This is because of continuity issues, unknown location of wire contact point" [New]: "8 The reason for not using a test station and/or test wire is because of possible continuity issues, unknown location of wire contact point," Font "Open Sans,Bold" changed to "OpenSans-Bold".Font-size "9.96001" changed to "6.48".
Text Replaced�
Text
[Old]: "cell resulting" [New]: "cell. Any of which can result" Font "Open Sans,Bold" changed to "OpenSans".
Page 14: Total Changes Content 821 - tn.gov

DRAFT

9

5. Recordkeeping

Records must be maintained in accordance with the following:

i. The CP system is to be tested every three (3) years and the results of the last two (2) tests must be maintained and made available upon request by the Division. See rules .02(4)(c)5.(i) and .02(4)(c)2.

ii. A record of the addition of sacrificial anodes to an existing Galvanic System must be

retained for the remaining operational life of the underground storage tank system and such records must be transferred to the new owner at the time of ownership transfer. See rules .02(4)(c)5.(ii) and .03(2)(d).

iii. The results of tightness testing required when anodes have been added for the

purpose of replacing or enhancing an existing Galvanic System must be retained for the remaining operational life of the underground storage tank system. Such records must be transferred to the new owner. See rules .02(4)(c)3., .02(4)(c)5.(iii) and .03(2)(d).

iv. The results of any cathodic protection system repairs must be maintained for the

operational life of the system. See rule .02(7)(h).

v. Records Transfer. Upon transfer of ownership, including, but not limited to, sale of the tank system, originals and/or copies of all documents required for recordkeeping of corrosion protection systems shall be transferred to the new owner of the tank system at the time of the ownership transfer. See rule .03(2)(d).

Text Replaced�
Text
[Old]: "5)" [New]: "5." Font "Open Sans,Bold" changed to "OpenSans-Bold".Font-size "9.96001" changed to "10.98".
Text Replaced�
Text
[Old]: "a." [New]: "i." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "b." [New]: "ii." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "in accordance with Division rules" [New]: "to the new owner" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "c." [New]: "iii." Font "Open Sans" changed to "OpenSans".
Text Deleted�
Text
"sacrificial"
Text Inserted�
Text
"DRAFT"
Text Replaced�
Text
[Old]: "in accordance with Division rules at the time of ownership transfer." [New]: "to the new owner." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "d." [New]: "iv." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: ".02(7)(f). e." [New]: ".02(7)(h). v." Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"9"
Page 15: Total Changes Content 821 - tn.gov

DRAFT

10

b. Impressed Current Systems

1. Design and Construction

All Impressed Current Systems are “Field Installed” systems and are required to be designed by a corrosion expert as required by rules .02(4)(a)2.(ii) and .02(4)(b)2.(ii). Rule .02(4)(c)1 requires cathodic protections systems to be operated and maintained in accordance with a corrosion expert whose design and construction requirements must comply with NACE Standards SP0285 for tanks, and SP0169 for piping.

2. Operation and Maintenance/Inspection

i. All Impressed Current Systems must be operated and maintained to continuously provide corrosion protection to the metal components of that portion of the tank, piping and underground ancillary equipment that routinely contains petroleum and is in contact with the ground. See rule .02(4)(c)1.

ii. All Impressed Current Cathodic Protection Systems must be designed to allow

determination of current operating status.

The rectifier must be visually inspected every sixty days, noting that it is turned on and operating properly. See rule .02(4)(c)4.

The results of these inspections must be recorded on the Impressed Current Cathodic Protection System 60-day Record of Rectifier Operation Form CN-1282. See rule .02(4)(c)4.

The 60-day Rectifier Log entries shall include the date of inspection, Rectifier On/Off status, voltage output if available, amperage output, hour meter reading if available, name of person inspecting the equipment, and any applicable comments. See rule .02(4)(c)4.

The last three visual rectifier inspection results (i.e., the last six (6) months) must be maintained by the owner and/or operator. See rules .02(4)(c)4. and .02(4)(c)5.(iv).

The following conditions may indicate that the cathodic protection system is not providing continuous corrosion protection as required by rule .02(4)(c)1and may require investigation and/or repair:

The rectifier meter(s) show either no voltage or current (amperage) at all,

The rectifier meter(s) show voltage or current (amperage) with the switch in the 'off' position,

No electrical power is being supplied to the impressed current system,

The rectifier meter(s) is “spiked” indicating the maximum voltage or current (amperage) rating of the rectifier has been exceeded,

Rectifier logs show a current (amperage) and/or voltage variance of more than 20% from initial reading (as indicated on the most recent cathodic protection survey) to any subsequent readings, or

An otherwise malfunctioning rectifier.

Text Replaced�
Text
[Old]: "IMPRESSED CURRENT SYSTEMS 1) Design and construction" [New]: "b. Impressed Current Systems 1. Design and Construction" Font "Open Sans,Bold" changed to "OpenSans-Bold".Font-size "11.04" changed to "12".
Text Replaced�
Text
[Old]: "thus" [New]: "are" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "All design and construction requirements shall comply with NACE Standards RP 0285 (latest revision) for tanks, and RP 0169 (latest revision) for piping. 2) Operation and maintenance/inspection a." [New]: "Rule .02(4)(c)1 requires cathodic protections systems to be operated and maintained in accordance with a corrosion expert whose design and construction requirements must comply with NACE Standards SP0285 for tanks, and SP0169 for piping. 2. Operation and Maintenance/Inspection i." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "ground and/or liquid." [New]: "ground." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "b." [New]: "ii." Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"DRAFT"
Text Replaced�
Text
[Old]: "inspecting," [New]: "inspecting the equipment," Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"rectifier"
Text Replaced�
Text
[Old]: "rule .02(4)(c)4" [New]: "rules .02(4)(c)4." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "9" [New]: "10" Font "Times New Roman" changed to "OpenSans".Font-size "12" changed to "10.98".
Text Replaced�
Text
[Old]: "not be" [New]: "indicate that the cathodic protection system is not" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: ".02(4)(c)1.: A properly operating rectifier but the gauges show either no voltage or current at all, a malfunctioning rectifier, the rectifier gauges showing voltage or current flow" [New]: ".02(4)(c)1and may require investigation and/or repair: The rectifier meter(s) show either no voltage or current (amperage) at all, The rectifier meter(s) show voltage or current (amperage)" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "the rectifier gauge is spiked indicating the maximum voltage or current flow, or rectifier logs show an amperage and/ or voltage variance of more than 20% from initial reading to subsequent readings." [New]: "No electrical power is being supplied to the impressed current system, The rectifier meter(s) is “spiked” indicating the maximum voltage or current (amperage) rating of the rectifier has been exceeded, Rectifier logs show a current (amperage) and/or voltage variance of more than 20% from initial reading (as indicated on the most recent cathodic protection survey) to any subsequent readings, or An otherwise malfunctioning rectifier." Font "Open Sans" changed to "OpenSans".
Page 16: Total Changes Content 821 - tn.gov

DRAFT

11

i. If the impressed current system(s) has been off or inoperable for less than twelve (12) months, tightness test the tank(s) and line(s) in accordance with rules .04(3)(b) and .04(4)(b).

1. If the results of the tightness test(s) indicate the UST system(s) is in compliance (i.e., both the tank(s) and line(s) pass a tightness test), then:

a. Repair the impressed current system (if necessary);9 b. Place the impressed current system back into operation; c. Tightness test the tank(s) and line(s) between three (3) and six (6) months

of placing the system back into operation.10

2. If the results of the tightness test(s) indicate the UST system(s) is not in compliance (i.e., either the tank(s) or line(s) fail a tightness test), then:

a. A release shall be reported to the Division within 72-hours of discovery,

and b. Investigated per rules .05(1) through .05(4) and .06 if a release is

confirmed. ii. If the impressed current system has been off or inoperable for greater than twelve

(12) months:

1. Permanently close the UST system(s) in accordance with rule .07(2), or

2. The tank owners and/or operators shall submit a written request to the Division justifying why the UST system(s) should not be permanently closed. If the Division determines that circumstances warrant further investigation, the Division will send a written response requiring additional action.11

All repairs (see Section 3 below) to the impressed current system must be designed and approved by a corrosion expert.12 After repairs, test the impressed current system following the procedures described in Section 4 below. Perform this test within six months of completing the repairs.13

9 Required by Rule 0400-18-01-.02(4)(c)1 10 Required by Rule 0400-18-01-.02(4)(c)3 11 Required by Rule 0400-18-01-.02(4)(c)(6)(ii)(II) 12 Required by Rule 0400-18-01-.02(4)(c)1 13 Required by Rule 0400-18-01-.02(4)(c)2(i)

Text Inserted�
Text
"i."
Text Replaced�
Text
[Old]: "Impressed Current System has no electrical power, then it is not providing continuous corrosion protection as required by rule .02(4)(c)1. (Unless otherwise directed by the Division, in accordance with rule .02(4)(c)6.(i), UST systems with impressed current systems which have been turned off or inoperable for a period of less than twelve months, the tanks and lines shall be tightness tested with additional testing thereafter. In accordance with rule .02(4)(c)6.(ii), UST systems with" [New]: "impressed current system(s) has been off or inoperable for less than twelve (12) months, tightness test the tank(s) and line(s) in accordance with rules .04(3)(b) and .04(4)(b). 1. If the results of the tightness test(s) indicate the UST system(s) is in compliance (i.e., both the tank(s) and line(s) pass a tightness test), then: a. Repair the impressed current system (if necessary); 9 b. Place the impressed current system back into operation; c. Tightness test the tank(s) and line(s) between three (3) and six (6) months of placing the system back into operation. 10 2. If the results of the tightness test(s) indicate the UST system(s) is not in compliance (i.e., either the tank(s) or line(s) fail a tightness test), then:" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"DRAFT"
Text Replaced�
Text
[Old]: "impressed current systems which have been turned off or inoperable for a period of twelve months or more, the tanks shall be permanently closed.) A CP tester or corrosion expert must determine the cause of the problem and restore the system to a satisfactory operating condition, and unless directed otherwise by the Division, conduct a test of the CP system to document that the system is protecting the tanks as required in rule .02(4)(c)6. This test will suffice for the post repair test required in the rule." [New]: "a. A release shall be reported to the Division within 72-hours of discovery, and b. Investigated per rules .05(1) through .05(4) and .06 if a release is confirmed. ii. If the impressed current system has been off or inoperable for greater than twelve (12) months: 1. Permanently close the UST system(s) in accordance with rule .07(2), or 2. The tank owners and/or operators shall submit a written request to the Division justifying why the UST system(s) should not be permanently closed. If the Division determines that circumstances warrant further investigation, the Division will send a written response requiring additional action. 11 All repairs (see Section 3 below) to the impressed current system must be designed and approved by a corrosion expert. 12 After repairs, test the impressed current system following the procedures described in Section 4 below. Perform this test within six months of completing the repairs. 13 9 Required by Rule 0400-18-01-.02(4)(c)1 10 Required by Rule 0400-18-01-.02(4)(c)3 11 Required by Rule 0400-18-01-.02(4)(c)(6)(ii)(II) 12 Required by Rule 0400-18-01-.02(4)(c)1 13 Required by Rule 0400-18-01-.02(4)(c)2(i)" Font "Open Sans,Bold" changed to "OpenSans".
Text Replaced�
Text
[Old]: "10" [New]: "11" Font "Times New Roman" changed to "OpenSans".Font-size "12" changed to "10.98".
Page 17: Total Changes Content 821 - tn.gov

DRAFT

12

The following images of a rectifier includes both an ammeter and voltmeter. To verify that the rectifier is on, these meters should have values greater than zero. The readings do not indicate that the system is protecting the tanks and piping, only that the unit is operating.

3. Repairs

Rule .02(7) requires that owners and/or operators of UST systems shall ensure that repairs will prevent releases due to structural failure or corrosion as long as the UST system is used to store petroleum. Rules .02(4)(a)2.(ii) and .02(4)(b)2.(ii) require that field installed cathodic protection systems for tanks and piping be designed by a corrosion expert. The Division has determined that to comply with rules .02(4)(a)2.(ii), .02(4)(b)2.(ii) and .02(7)(a) a corrosion expert must be either involved in the design and installation, approve, oversee, or sign off on all repairs made to cathodic protection systems that affect the operation of the system. Repairs include, but are not limited to, the following list of activities:14

i. Replacing rectifier;

ii. Adding or replacing anodes (except as specified as maintenance – see below);

iii. Replacing broken rectifier components;

iv. Replacing broken ground wires or anode wires;

v. Resolving continuity issues;

vi. Adding additional structures to an existing CP system;

vii. Increasing tap settings on rectifier to achieve passing results; or

viii. Any other system modifications that change the current (amperage) output of the system.

Any of these activities require a retest of the CP system within 6 months following the

14 Required by Rule 0400-18-01-.01(1)(4)

Text Replaced�
Text
[Old]: "CP tester must engage the services of a corrosion expert when restoration of the CP system to proper operating condition requires any changes to its design or adjustment to rectifier output as required by rules .02(4)(a)2.(ii) and .02(4)(b)2.(ii). This rectifier shown on the following page contains both an ammeter and voltmeter. To verify that the rectifier is on, these gauges should have values above zero. The readings do not indicate that the system is protecting the tanks and piping, it only indicates" [New]: "following images of a rectifier includes both an ammeter and voltmeter. To verify that the rectifier is on, these meters should have values greater than zero. The readings do not indicate that the system is protecting the tanks and piping, only" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"DRAFT"
Text Inserted�
Text
"The"
Text Deleted�
Text
"The"
Text Replaced�
Text
[Old]: "1. Replacing rectifier 2. Adding anodes 3. Replacing broken rectifier components 4. Replacing broken ground wires or anode wires 5. Resolving continuity issues when problems identified and system still does not pass 6. Adding additional structures to an existing CP system. 7. Increasing tap settings on rectifier to achieve passing results" [New]: "14 i. Replacing rectifier; ii. Adding or replacing anodes (except as specified as maintenance – see below); iii. Replacing broken rectifier components; iv. Replacing broken ground wires or anode wires; v. Resolving continuity issues; vi. Adding additional structures to an existing CP system; vii. Increasing tap settings on rectifier to achieve passing results; or viii. Any other system modifications that change the current (amperage) output of the system. Any of these" Font "Open Sans" changed to "OpenSans".Font-size "9.96001" changed to "6.48".
Text Replaced�
Text
[Old]: "11" [New]: "12" Font "Times New Roman" changed to "OpenSans".Font-size "12" changed to "10.98".
Text Deleted�
Text
"These"
Text Inserted�
Text
"14 Required by Rule 0400-18-01-.01(1)(4)"
Page 18: Total Changes Content 821 - tn.gov

DRAFT

13

repair of the system to comply with rules .02(7)(f). Activities listed below may be considered maintenance and do not require the approval of a corrosion expert under .02(4)(a)2.(ii), .02(4)(b)2.(ii) and .02(7)(a): Maintenance includes, but is not limited to, the following list of activities:

i. Routine CP Testing;

ii. Turning rectifier on and off for testing;

iii. Replacing blown fuse(s) or voltage/amperage meter in rectifier;

iv. Reburying anode wires that have surfaced; or

v. Adding or replacing a bag or drive-in rod anode to a flex connector(s).

4. Testing

i. A Cathodic Protection Tester must inspect all impressed current systems for proper operation within six (6) months of installation and at least every three (3) years thereafter. The system must be functioning as designed and is effectively preventing corrosion. See rule .02(4)(c)2.

ii. All UST systems to which anodes have been added for the purpose of replacing or

enhancing an existing impressed current system shall be tightness tested. The tightness test shall be conducted no later than six (6) months, but no sooner than three (3) months, following the addition of the anodes per rules .02(4)(c)3. and .02(4)(c)5.(iii). The Division generally does not require tightness testing of flex connectors to which anodes have been added. Records must be transferred to any new owner as required by rule .03(2)(d).

iii. Perform corrosion testing in accordance with the instructions in Appendix 2 and 3, and

the Impressed Current Cathodic Protection Testing Survey Form (CN-1309).15 Structures utilizing impressed current cathodic protection will be considered adequately protected, as required by rules .02(4)(c)1. and 2., and .02(7), if they meet either:16

1. The criterion in Section 9 of NACE TM0101: a negative (cathodic) potential of at

least 850 mV when the voltage drop from the applied protective current has been eliminated. This second meter reading is known as the “instant off” and is measured with the protective current interrupted when the power to the rectifier is cut off, or by using the min/max function on a meter to capture the instant off reading, or

2. The criterion in Section 10 of NACE TM0101: when a minimum of 100 mV of cathodic polarization (either formation or decay, i.e. shift) can be measured on the protected structures. When the current is interrupted, an “instant off” potential is recorded and the structure under cathodic protection is then allowed to depolarize until a change of at least 100 mV in potential is observed.

15 Required by Rule 0400-18-01-.02(4)(c)2(iii) 16 Required by Rule 0400-18-01-.02(4)(c)2

Text Inserted�
Text
"of the system"
Text Replaced�
Text
[Old]: ".02(7)(e)." [New]: ".02(7)(f)." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: ".02(7)(a).:" [New]: ".02(7)(a):" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "1." [New]: "i." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "testing 2." [New]: "Testing; ii." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "testing. 3. Replacing blown fuse in rectifier 4. Reburying anode wires that have surfaced 5. Adding a drive-in rod anode to a single, isolated flex connector. 6. Replacing anodes (limited to same size and location as anode being replaced)" [New]: "testing; iii. Replacing blown fuse(s) or voltage/amperage meter in rectifier; iv. Reburying anode wires that have surfaced; or v. Adding or replacing a bag or drive-in rod anode to a flex connector(s)." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "a." [New]: "i." Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"DRAFT"
Text Replaced�
Text
[Old]: "b." [New]: "ii." Font "Open Sans" changed to "OpenSans".
Text Deleted�
Text
"sacrificial"
Text Replaced�
Text
[Old]: "anodes. See" [New]: "anodes per" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "may" [New]: "generally does" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "c. Testing shall be performed in accordance with Appendix 3 and as directed according to instructions in state form CN-1309." [New]: "iii. Perform corrosion testing in accordance with the instructions in Appendix 2 and 3, and the Impressed Current Cathodic Protection Testing Survey Form (CN-1309).15" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "2." [New]: "2.," Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "i." [New]: "16 1." Font "Open Sans" changed to "OpenSans".Font-size "9.96001" changed to "6.48".
Text Replaced�
Text
[Old]: "ii." [New]: "2." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "decay)" [New]: "decay, i.e. shift)" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"15 Required by Rule 0400-18-01-.02(4)(c)2(iii) 16 Required by Rule 0400-18-01-.02(4)(c)2"
Text Replaced�
Text
[Old]: "12" [New]: "13" Font "Times New Roman" changed to "OpenSans".Font-size "12" changed to "10.98".
Page 19: Total Changes Content 821 - tn.gov

DRAFT

14

Depolarization may take as long as 24 hours in some cases, but should not exceed 72 hours.

5. Recordkeeping

Records must be maintained in accordance with the following:

i. The CP system is to be tested every three (3) years and the results of the last two (2) tests must be maintained and made available upon request by the Division per rules .02(4)(c)2.(i). and .02(4)(c)5.(i).

ii. The results of the sixty (60) day rectifier inspection shall be recorded on the Impressed

Current CP System 60 Day Record of Rectifier Operation Form (CN-1282) and in accordance with rule .02(4)(c)2.(iii). The results of the last three sixty (60) day rectifier inspections must be retained for inspection by the Division as required by rules .02(4)(c)5.(iv) and .03(2)(b)5.

iii. The results of any cathodic protection system repairs must be retained for the

remaining operational life of the underground storage tank system and such records must be transferred at the time of ownership transfer per rules .02(7)(h) and .03(2)(d).

iv. Documentation that the cathodic protection system is designed by a corrosion expert

and that a corrosion expert was involved with repairs made to the system must be maintained by the owner and/or operator for inspection by the Division per rules .02(4)(a)2.(ii), .02(4)(b)2.(ii), .02(7)(h), and .03(2)(b).

v. The results of tightness testing required when anodes have been added for the

purpose of replacing or enhancing an existing Impressed Current System must be retained for the remaining operational life of the underground storage tank system per rules .02(4)(c)5.(ii) and .02(7)(h). Such records must be transferred in accordance with Division rules at the time of ownership transfer per rules.03(2)(d).

Rectifiers used on UST systems are manually controlled for the most part. A corrosion expert will determine the amount of current necessary in the design to protect the metallic structures and set the rectifier output accordingly at installation or during modification of the CP system as required by rules .02(4)(a)2.(ii) and .02(4)(b)2.(ii), and as outlined in the definition of corrosion expert in rule .01(4). If the rectifier is equipped with a voltmeter, 60 day voltage readings made by tank owners should be fairly constant unless the rectifier is a constant current rectifier. The tank owner should record current (amps or milliamps) from an ammeter. The recorded current readings could vary if the anodes are buried shallow or there are wide seasonal variations in soil moisture content. If the anodes are buried at least 8 feet deep, then measured current output should remain fairly constant. Any variation in current and/or voltage of more than 20% from the initial reading (as determined by the most recent 3-year cathodic protection test) to a subsequent reading must be investigated and repaired, if necessary.17

17 Required by Rule 0400-18-01-.02(4)(c)1

Text Replaced�
Text
[Old]: "a." [New]: "i." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "Division. See rule" [New]: "Division per rules" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "b." [New]: "ii." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "CN-1282" [New]: "(CN-1282)" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "Division. As required by rule" [New]: "Division as required by rules" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: ".03(2)(b)2. c." [New]: ".03(2)(b)5. iii." Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"DRAFT"
Text Replaced�
Text
[Old]: "transfer. See rule .02(7)(f) and .03(2)(d). d." [New]: "transfer per rules .02(7)(h) and .03(2)(d). iv." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "Division. See" [New]: "Division per" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: ".02(7)(f)," [New]: ".02(7)(h)," Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "e." [New]: "v." Font "Open Sans" changed to "OpenSans".
Text Deleted�
Text
"sacrificial"
Text Replaced�
Text
[Old]: "system. See rule .02(4)(c)5.(ii) and .02(7)(f)." [New]: "system per rules .02(4)(c)5.(ii) and .02(7)(h)." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "transfer. See rule .02(4)(c)5.(ii) and .03(2)(d). Rectifiers used on USTs" [New]: "transfer per rules.03(2)(d). Rectifiers used on UST systems" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"metallic"
Text Inserted�
Text
"the"
Text Replaced�
Text
[Old]: "to subsequent readings, must be investigated and repaired if necessary. CORROSION PROTECTION FOR FLEXIBLE (FLEX) CONNECTORS" [New]: "(as determined by the most recent 3-year cathodic protection test) to a subsequent reading must be investigated and repaired, if necessary. 17 17 Required by Rule 0400-18-01-.02(4)(c)1" Font "Open Sans,Bold" changed to "OpenSans-Bold".
Text Replaced�
Text
[Old]: "13" [New]: "14" Font "Times New Roman" changed to "OpenSans".Font-size "12" changed to "10.98".
Page 20: Total Changes Content 821 - tn.gov

DRAFT

15

8. Corrosion Protection for Flexible (flex) Connectors and Short Sections of Metal Piping This section does not apply to UST system(s) that utilize Interstitial Monitoring as a method of release detection for product piping because the referenced piping components are required to be in containment sumps that remain dry per rules .02(2)(b)1(ii) and .04(4)(c)1. Flex connectors are braided stainless steel fittings used to make connections from a product line to a dispenser or submersible pump. A braided steel mesh protects an interior plastic or non-metallic hose that carries petroleum. Short sections of metal piping can include swing joints, elbows, valves, STP piping stubs, unions for suction piping, dispenser piping, etc. There are two primary methods to protect flex connectors and short sections of metal piping from corrosion: isolation and cathodic protection.

a. Isolation

The piping components are considered isolated if they are not in contact with the ground and/or water. If a dry sump serves that purpose, then no further action is necessary. If all or part of the piping components are in contact with the ground and/or water at any time (whether in a containment sump or not), then another means of achieving isolation will be necessary to comply with rule .02(4)(b). Isolation boots that prevent the piping component from being in contact with soil and/or water, or removing the soil that is in contact with the piping components can be used to achieve this goal. If the piping components cannot be completely isolated, the addition of cathodic protection is required (see Item #2 below) in accordance with rule .02(4)(b)2 and .02(4)(c)1. Isolation boots are typically constructed of either a plastic or rubber material that wraps around the entire piping component and secured. Isolation boots may be either one piece “sleeves” which slip over a flex connector and are secured at both ends with nylon zip ties, or stainless-steel band clamps, also known as radiator (hose) clamps. Other designs are boots that are heat shrunk directly to a flex connector. Also, some boots are wrapped around the flex connector/pipe and are secured with zippers, nylon ties, or Velcro fasteners. If isolation boots show signs of degradation they must be replaced. Isolation boots must be secured at both ends in a manner that prevents the flex connector from coming in contact with soil or water. Flex connectors which cannot be isolated from contact with soil or water are not corrosion protected; therefore, cathodic protection is required in accordance with rules .02(4)(b)2. and .02(4)(c)1.

Text Inserted�
Text
"8. Corrosion Protection for Flexible (flex) Connectors and Short Sections of Metal Piping This section does not apply to UST system(s) that utilize Interstitial Monitoring as a method of release detection for product piping because the referenced piping components are required to be in containment sumps that remain dry per rules .02(2)(b)1(ii) and .04(4)(c)1."
Text Replaced�
Text
[Old]: "There are two different ways to protect flex connectors" [New]: "Short sections of metal piping can include swing joints, elbows, valves, STP piping stubs, unions for suction piping, dispenser piping, etc. There are two primary methods to protect flex connectors and short sections of metal piping" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "1) Isolation Isolation means keeping a flex connector free from all contact with" [New]: "a. Isolation The piping components are considered isolated if they are not in contact with the" Font "Open Sans,Bold" changed to "OpenSans-Bold".Font-size "9.96001" changed to "12".
Text Inserted�
Text
"DRAFT"
Text Replaced�
Text
[Old]: "sump can be kept free of water so that the flex connector is never exposed to soil and/ or water, then no further action is necessary under rule .02(4)(b). If the flex connector can come in contact with ground and/or water, then another means of achieving isolation, such as isolation boots, will be necessary to comply with rule .02(4)(b). When used in the context of isolation, water in this Technical Chapter is understood to be a synonymous term for electrolyte as used by NACE. Isolation boots are plastic materials made for isolating flex connectors and are placed around the entire flex connector and secured. Isolation boots may be either one piece “sleeves” which slip over a flex connector and are secured at both ends with nylon zip ties, or stainless steel band clamps, also known as radiator clamps. Another design is a boot that is heat shrunk directly to a flex connector. A third kind of isolation boot is a boot that is applied around the pipe and “zipped” or secured with nylon ties, or possibly Velcro fasteners. When boots show signs of degradation they must be replaced. Isolation boots must be secured at both ends in a manner that prevents the flex connector from coming in contact with soil or water to comply with rule .02(4)(b) and .02(4)(c)1. Flex connectors which cannot be isolated from contact with soil or water are not corrosion protected, and cathodic protection is required if isolation cannot be achieved" [New]: "dry sump serves that purpose, then no further action is necessary. If all or part of the piping components are in contact with the ground and/or water at any time (whether in a containment sump or not), then another means of achieving isolation will be necessary to comply with rule .02(4)(b). Isolation boots that prevent the piping component from being in contact with soil and/or water, or removing the soil that is in contact with the piping components can be used to achieve this goal. If the piping components cannot be completely isolated, the addition of cathodic protection is required (see Item #2 below) in accordance with rule .02(4)(b)2 and .02(4)(c)1. Isolation boots are typically constructed of either a plastic or rubber material that wraps around the entire piping component and secured. Isolation boots may be either one piece “sleeves” which slip over a flex connector and are secured at both ends with nylon zip ties, or stainless-steel band clamps, also known as radiator (hose) clamps. Other designs are boots that are heat shrunk directly to a flex connector. Also, some boots are wrapped around the flex connector/pipe and are secured with zippers, nylon ties, or Velcro fasteners. If isolation boots show signs of degradation they must be replaced. Isolation boots must be secured at both ends in a manner that prevents the flex connector from coming in contact with soil or water. Flex connectors which cannot be isolated from contact with soil or water are not corrosion protected; therefore, cathodic protection is required" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "14" [New]: "15" Font "Times New Roman" changed to "OpenSans".Font-size "12" changed to "10.98".
Page 21: Total Changes Content 821 - tn.gov

DRAFT

16

One Piece Isolation Boot Zip Boot

The use of tape wraps as a standalone method of isolating flex connectors and/or other piping components is not an acceptable method of corrosion protection; therefore, tape-wrapped flex connectors (or other piping components) must also have a form of galvanic or impressed current cathodic protection. See rule .02(4)(b)4.

Cathodic Protection

Sacrificial anodes may be attached to piping components under the dispenser or at the submersible pump, for example, to achieve cathodic protection. Typically, sacrificial anodes like a spike anode (drive-in rod anode) or bag anode are added in the field by burying them in the ground adjacent to the piping and connecting a bond wire between the anode and the component that requires cathodic protection. If the piping component that requires protection is only in contact with water, it is recommended that a “bare” anode (not a bag anode) be placed in the water adjacent to the piping and connected as described above. Less common types of anodes are bracelet anodes that are attached with a U-bolt around the piping component or anodes that are factory fitted to the flex connector (donut anodes). Regardless of the type, the anode must be in contact with the ground or water for it to work properly.18 Cathodic protection systems must be tested every three years as required by rule .02(4)(c)2.(i).

18 Required by Rule 0400-18-01-.02(4)(c)1

Text Inserted�
Text
"DRAFT"
Text Replaced�
Text
[Old]: "Zip boot One-piece Isolation boot Following a limited study in 2001 by the Division, a decision was made not to approve the use of tape wraps alone to provide adequate corrosion protection to flex connectors and metallic piping components." [New]: "One Piece Isolation Boot Zip Boot The use of tape wraps as a standalone method of isolating flex connectors and/or other piping components is not an acceptable method" Font "Open Sans" changed to "OpenSans".
Text Deleted�
Text
"See rule .02(4)(b)4."
Text Replaced�
Text
[Old]: "The study showed that exposure to hydrocarbons compromised the integrity of the rubberized tape material. Adhesive tapes provide some protection to metallic surfaces, but under direct burial conditions or exposure to water or other electrolyte, any exposed metal would be subject to corrosion even in the absence of petroleum. Another concern was a reduced likelihood of achieving proper installation under field application conditions, and no assurance that proper application techniques would be used by adequately trained individuals. Tape-wrapped flex connectors must also have a form of galvanic or impressed current cathodic protection, or the flex connector must be situated so that it is never exposed to soil and/or water in order to meet the requirements of rule .02(4)(b)2. and .02(4)(b)4." [New]: "of corrosion protection; therefore, tape-wrapped flex connectors (or other piping components) must also have a form of galvanic or impressed current cathodic protection." Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"See rule .02(4)(b)4."
Text Deleted�
Text
"2)"
Text Replaced�
Text
[Old]: "isolated flex connectors to achieve cathodic protection. A sacrificial anode is a less noble metal like zinc or magnesium alloys intentionally connected to form a galvanic cell with a more noble metal for the purpose of protecting the more noble metal from corrosion. Some flex connectors have a circular piece of anode material attached during manufacturing. If a factory designed anode is not present, cathodic protection can be added in the field. A spike anode (drive-in rod anode) is attached with a clamp, and then driven into the soil/backfill next to the piping. Sacrificial anodes can be connected to the flex connector at the submersible pump or under the dispenser. Also bracelet anodes can be attached with a U-bolt around the flex connector. In all cases the anodes must be in contact with backfill for the anode to work properly." [New]: "piping components under the dispenser or at the submersible pump, for example, to achieve cathodic protection. Typically, sacrificial anodes like a spike anode (drive-in rod anode) or bag anode are added in the field by burying them in the ground adjacent to the piping and connecting a bond wire between the anode and the component that requires cathodic protection. If the piping component that requires protection is only in contact with water, it is recommended that a “bare” anode (not a bag anode) be placed in the water adjacent to the piping and connected as described above. Less common types of anodes are bracelet anodes that are attached with a U-bolt around the piping component or anodes that are factory fitted to the flex connector (donut anodes). Regardless of the type, the anode must be in contact with the ground or water for it to work properly. 18" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"18 Required by Rule 0400-18-01-.02(4)(c)1"
Text Inserted�
Text
"16"
Page 22: Total Changes Content 821 - tn.gov

DRAFT

17

Drive in rod anode

Bracelet Anode

Drive-in rod anode

Note: although this flex connector has a bracelet anode attached, it is ineffective in preventing corrosion. To work properly, the anode must be buried in the ground.

A single drive-in rod, bracelet or bag anode is only designed to provide protection to a single, isolated flex connector or short piece of metallic piping;19 therefore, additional anodes may be required to achieve cathodic protection if the component to be protected is continuous with other metallic components (e.g., STP pump head, dispenser cabinet, electrical conduit, etc.). Flex connectors are also occasionally bonded to the impressed current system to achieve protection. For this design, each flex connector must be continuous with the disconnected rectifier negative cable; otherwise, some other method (isolation, sacrificial anodes, etc.)

19 Required by Rule 0400-18-01-.02(4)(b)2

Text Inserted�
Text
"Drive in rod anode Bracelet Anode"
Text Inserted�
Text
"DRAFT"
Text Deleted�
Text
"anodes Bracelet"
Text Replaced�
Text
[Old]: "15" [New]: "17" Font "Times New Roman" changed to "OpenSans".Font-size "12" changed to "10.98".
Text Replaced�
Text
[Old]: "Note that" [New]: "Note:" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "In order to" [New]: "To" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "soil. Drive-in rod, bracelet or bag anodes are" [New]: "the ground. A single drive-in rod, bracelet or bag anode is only" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "connector. They are not designed to provide adequate protection for flex connectors which are electrically continuous with other structures such as" [New]: "connector or short piece of metallic piping; 19 therefore, additional anodes may be required to achieve cathodic protection if the component to be protected is continuous with other metallic components (e.g., STP pump head, dispenser cabinet, electrical conduit, etc.). Flex connectors are also occasionally bonded to the impressed current system to achieve protection. For this design, each flex connector must be continuous with the disconnected rectifier negative cable; otherwise, some other method (isolation, sacrificial anodes, etc.) 19 Required by Rule 0400-18-01-.02(4)(b)2" Font "Open Sans" changed to "OpenSans".
Page 23: Total Changes Content 821 - tn.gov

DRAFT

18

will be required to achieve corrosion protection.20

b. Cathodic Protection & Testing Flex Connectors and Short Sections of Metal Piping* * The terms flex connector, short section of metal piping and piping component are used interchangeably in the sections below. The most common piping component that requires cathodic protection is a “Flex Connector”; therefore, it is term most commonly used below. ** Document continuity test results for ALL flex connectors and short sections of metal piping on the continuity survey page of either the Impressed Current Cathodic Protection Testing Survey form (CN-1309) or the Galvanic Cathodic Protection Testing Survey form (CN-1140), as appropriate.21 Flex connectors or short sections of metal piping connected to an impressed current system This scenario could exist at a site that has metal tanks protected by impressed current system, non-metallic piping, and flex connectors or short sections of metal piping (i.e., piping components) that have been connected to the impressed current system. To test these piping components: Test continuity using the point-to-point continuity test procedure (see applicable section

in Appendix 2) to confirm that each piping component is continuous with the disconnected rectifier negative cable (impressed current system must be off when performing this procedure). Document the continuity test results in Section XIV of form CN-1309.22 If a piping component(s) is not continuous with the disconnected rectifier negative cable, the referenced piping component will either need to be bonded to the impressed current system or another method of corrosion protection will be required (i.e., isolation, sacrificial anode, etc.).23 NOTE: if any piping component is being bonded to the impressed current system, the involvement of a CP Expert is required (including signing off on the CP Test report).24

If the referenced piping component is continuous with the disconnected rectifier negative

cable, measure the “On” and “Instant Off” voltage in accordance with Appendix 3 (reference electrode/cell must be placed in soil adjacent to the piping component). Document the test results in Section XV on form CN-1309. If multiple piping components (e.g., flex connectors) under a dispenser (for example) are all continuous with the disconnected rectifier negative cable, all flex connectors under that particular dispenser can be tested as “one” piece of metal. Follow the testing procedure in Appendix 3.

NOTE: To avoid depolarizing the piping components, it may be necessary to perform continuity testing after obtaining “On” and “Instant Off” voltages.

20 Required by Rule 0400-18-01-.02(4)(b)2 21 Required by Rule 0400-18-01-.02(4)(b)2(iii) 22 Required by Rule 0400-18-01-.02(4)(c)2(iii) 23 Required by Rule 0400-18-01-.02(4)(b)2 24 Required by Rule 0400-18-01-.02(4)(b)2(ii)

Text Inserted�
Text
"will be required to achieve corrosion protection. 20 b. Cathodic Protection & Testing Flex Connectors and Short Sections of Metal Piping*"
Text Inserted�
Text
"*"
Text Replaced�
Text
[Old]: "the STP, impact valve, dispenser cabinet or other piping components. If a drive-in rod, bracelet or bag anode is used to provide cathodic protection to a flex connector the CP test must determine that the flex connector" [New]: "The terms flex connector, short section of metal piping and piping component are used interchangeably in the sections below. The most common piping component that requires cathodic protection is a “Flex Connector”; therefore, it is term most commonly used below. ** Document continuity test results for ALL flex connectors and short sections of metal piping on the continuity survey page of either the Impressed Current Cathodic Protection Testing Survey form (CN-1309) or the Galvanic Cathodic Protection Testing Survey form (CN-1140), as appropriate. 21 Flex connectors or short sections of metal piping connected to an impressed current system This scenario could exist at a site that has metal tanks protected by impressed current system, non-metallic piping, and flex connectors or short sections of metal piping (i.e., piping components) that have been connected to the impressed current system. To test these piping components: Test continuity using the point-to-point continuity test procedure (see applicable section in Appendix 2) to confirm that each piping component is continuous with the disconnected rectifier negative cable (impressed current system must be off when performing this procedure). Document the continuity test results in Section XIV of form CN-1309." Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"DRAFT"
Text Replaced�
Text
[Old]: "is isolated as required by rule .02(4)(c)2. The Division issued a memo in October 2009 which said that adding a drive-in rod anode to a single, isolated flex connector does not require approval by a corrosion expert. If the flex connector is electrically continuous with other flex connectors or other components, then follow the testing procedures described below: TESTING CATHODIC PROTECTION ON FLEX CONNECTORS Described below are various conditions which may be encountered" [New]: "22 If a piping component(s) is not continuous with the disconnected rectifier negative cable, the referenced piping component will either need to be bonded to the impressed current system or another method of corrosion protection will be required (i.e., isolation, sacrificial anode, etc.). 23 NOTE: if any piping component is being bonded to the impressed current system, the involvement of a CP Expert is required (including signing off on the CP Test report). 24 If the referenced piping component is continuous with the disconnected rectifier negative cable, measure the “On” and “Instant Off” voltage in accordance with Appendix 3 (reference electrode/cell must be placed in soil adjacent to the piping component). Document the test results in Section XV on form CN-1309. If multiple piping components (e.g., flex connectors) under a dispenser (for example) are all continuous with the disconnected rectifier negative cable, all flex connectors under that particular dispenser can be tested as “one” piece of metal. Follow the testing procedure in Appendix 3. NOTE: To avoid depolarizing the piping components, it may be necessary to perform continuity testing after obtaining “On” and “Instant Off” voltages. 20 Required by Rule 0400-18-01-.02(4)(b)2 21 Required by Rule 0400-18-01-.02(4)(b)2(iii) 22 Required by Rule 0400-18-01-.02(4)(c)2(iii) 23 Required by Rule 0400-18-01-.02(4)(b)2 24 Required by Rule 0400-18-01-.02(4)(b)2(ii)" Font "Open Sans" changed to "OpenSans".Font-size "9.96001" changed to "6.48".
Text Inserted�
Text
"18"
Page 24: Total Changes Content 821 - tn.gov

DRAFT

19

Flex connectors or short sections of metal piping with attached sacrificial anode(s) Utilize the following methods when testing flex connectors with attached sacrificial anodes. 25 These methods may also be used to test short sections of metallic piping. Step by step procedures for testing flex connectors are described in Appendix 4. NOTE: To test flex connectors or short sections of metal piping with attached sacrificial anodes, the impressed current system (if applicable) must be turned off.

1. Electrically Isolated Flex connectors

Test continuity between the flex connector and connecting component (i.e., either the STP piping or dispenser piping) by using either the point-to-point or fixed-cell/moving ground (remote reference cell placement) method. If the flex connector is isolated from the connecting component, then both local “on” measurements and “remote” measurements must be taken for each flex connector. Both measurements must pass (–850 mV or more negative) for the flex connector to be cathodically protected. 25 NOTE: When collecting “remote” measurements, the reference cell must be placed at true “remote earth” (see procedure below). If either local “on” or “remote” measurements do not pass, then a local “Instant Off” measurement must be taken by disconnecting the bond wire of the anode. If multiple isolated flex connectors are present, then all other flex connectors not being tested must be disconnected from their respective anodes during the testing to obtain valid “Instant Off” measurements for the flex connector being tested. If “Instant Off” measurements fail, then continue to observe the depolarization to determine whether the 100 mV shift criteria is met. For local “Instant Off” readings, each flex connector must be tested individually by placing the reference cell immediately adjacent to each flex connector (not the anode) and making contact directly with the flex connector while disconnecting the bond wire to the anode.25 NOTE: The use of permanently attached anodes, such as “bracelet” or “donut” anodes, may not allow proper testing of flex connectors if “remote” measurements cannot be obtained or fail. As a result, the instant off/100 mV shift method must be used.25

Disconnecting bracelet or donut anodes is usually not practical; therefore, one solution is to add a spike or bag anode with a bonding wire that can be disconnected to measure the instant off/100 mV shift. True “remote earth”: True “remote earth” is a location away from the protected structure where the potential measurements do not significantly change regardless of how much further away the reference electrode/cell is located from the protected structure. The purpose of obtaining this potential measurement is to overcome the effects of any IR (voltage) drop between the anode and the protected structure. IR drop refers to the voltage produced by an anode to overcome resistance in the soil.

25 Required by Rule 0400-18-01-.02(4)(c)2

Text Replaced�
Text
[Old]: "when testing flex connectors. These methods may also be used to test short sections of isolated metallic piping. Use the applicable method. The Steel Tank Institute’s step by step procedures for testing flex connectors are described in Appendix 4. Isolated flex connectors: Test continuity between flex connector and connecting component (i.e., either the STP piping or dispenser piping) by using either the point-to-point or fixed-cell/moving ground (remote reference cell placement) method. If isolated, then both local “on” measurements and “remote” measurements must be taken and pass (-850 mV)." [New]: "Flex connectors or short sections of metal piping with attached sacrificial anode(s) Utilize the following methods when testing flex connectors with attached sacrificial anodes. 25 These methods may also be used to test short sections of metallic piping. Step by step procedures for testing flex connectors are described in Appendix 4. NOTE: To test flex connectors or short sections of metal piping with attached sacrificial anodes, the impressed current system (if applicable) must be turned off. 1. Electrically Isolated Flex connectors Test continuity between the flex connector and connecting component (i.e., either the STP piping or dispenser piping) by using either the point-to-point or fixed-cell/moving ground (remote reference cell placement) method. If the flex connector is isolated from the connecting component, then both local “on” measurements and “remote” measurements must be taken for each flex connector. Both measurements must pass (–850 mV or more negative) for the flex connector to be cathodically protected." Font "Open Sans" changed to "OpenSans-Bold".
Text Inserted�
Text
"DRAFT"
Text Inserted�
Text
"25"
Text Replaced�
Text
[Old]: "measuring the remote potential, the" [New]: "collecting “remote” measurements, the" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"either"
Text Replaced�
Text
[Old]: "and/or remote" [New]: "or “remote”" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "flexes" [New]: "flex connectors" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "flexes" [New]: "flex connectors" Font "Open Sans" changed to "OpenSans".
Text Deleted�
Text
"in order"
Text Replaced�
Text
[Old]: "Instant Off measurements. If Instant Off measurements fail, then continue to observe the depolarization to obtain a passing 100 mV shift measurement. For local Instant Off readings, each flex" [New]: "“Instant Off” measurements for the flex connector being tested. If “Instant Off” measurements fail, then continue to observe the depolarization to determine whether the 100 mV shift criteria is met. For local “Instant Off” readings, each flex connector" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"connector"
Text Inserted�
Text
"connector"
Text Replaced�
Text
[Old]: "NOTE: Permanently" [New]: "25 NOTE: The use of permanently" Font "Open Sans" changed to "OpenSans".Font-size "9.96001" changed to "6.48".
Text Inserted�
Text
"or “donut”"
Text Replaced�
Text
[Old]: "remote readings" [New]: "“remote” measurements" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "polarization" [New]: "shift" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "Since disconnecting bracelet anodes is difficult, one solution is to replace bracelet" [New]: "25 Disconnecting bracelet or donut anodes is usually not practical; therefore, one solution is to add a" Font "Open Sans" changed to "OpenSans".Font-size "9.96001" changed to "6.48".
Text Replaced�
Text
[Old]: "16" [New]: "19" Font "Times New Roman" changed to "OpenSans".Font-size "12" changed to "10.98".
Text Deleted�
Text
"anodes with"
Text Replaced�
Text
[Old]: "anodes with bonding wires which" [New]: "anode with a bonding wire that" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "in order to conduct" [New]: "to measure" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "polarization." [New]: "shift. True “remote earth”: True “remote earth” is a location away from the protected structure where the potential measurements do not significantly change regardless of how much further away the reference electrode/cell is located from the protected structure. The purpose of obtaining this potential measurement is to overcome the effects of any IR (voltage) drop between the anode and the protected structure. IR drop refers to the voltage produced by an anode to overcome resistance in the soil. 25 Required by Rule 0400-18-01-.02(4)(c)2" Font "Open Sans" changed to "OpenSans".
Page 25: Total Changes Content 821 - tn.gov

DRAFT

20

Procedure to obtain true “remote earth”: Place reference cell at least 25 feet away from structure being tested. Measure the remote potential. Move the reference cell another 10 feet away and measure potential again. If the difference in the two measurements is less than 10 mV, then this location represents true “remote earth” for any structures being tested at the site. If the two measurements are not within 10 mV, then continue to move 10 feet away and measure again until two consecutive measurements are within 10 mV.26

2. Electrically Shorted (Continuous) Flex Connectors

Test continuity between the flex connector and connecting component (i.e., either the STP piping or dispenser piping) by using either the point-to-point or fixed-cell/moving ground (remote reference cell placement) method. If the flex connector is shorted to the connecting component, then only measure local “Instant Off” potentials for each flex connector.26 If multiple flex connectors are shorted together, the ability to disconnect all anode bonding wires at the same time is recommended. This may require the anode bond wires to be bonded to one common point to disconnect during testing. To test, disconnect the common bond wire each time and contact each flex connector separately and conduct separate “Instant Off” tests for the individual flex connectors. This method of bonding all wires together will also make future testing more convenient. Bonding all anode wires to a common point is the recommended practice. Alternatively, bond wires that are attached to each flex connector separately may be tested in the following manner: contact the first flex connector, while all other bond wires are detached, and disconnect its anode bond wire and measure the “Instant Off” potential. Repeat this procedure for each flex connector. Again, if the “Instant Off” potential fails, then continue to observe depolarization to determine whether the 100mV shift criteria is met. NOTE: For local “Instant Off” readings, each flex connector must be tested individually. This is accomplished by (1) placing the reference cell immediately adjacent to each flex connector (not the anode), (2) making contact directly with the flex connector being tested, and (3) disconnecting the bond wire to the anode.

3. Flex Connectors in Contact with Water Inside Containment Sump(s)

If an anode has been attached to a single flex connector in a sump containing water, then only a local “Instant Off” (or 100 mV shift) potential must be measured. If multiple flex connectors/anodes are present, then the procedures previously described for testing isolated (“instant off” or “100 mV shift” portion only) or shorted flex connectors apply. NOTE: In sumps with high water levels, the anode bond wire that is attached directly to a flex connector/piping that is completely submerged may not be accessible in order to disconnect to obtain “Instant Off” measurements. In this scenario, it is best to have the bond wire from the anode and the bond wire from the flex connector/piping terminate at a point above the water surface and then connect these two bond wires together. When testing, connect the positive lead from the voltmeter to the bond wire going to the flex connector and the negative lead to the reference electrode/cell (only submerge tip of reference electrode/cell in water) and then disconnect the two bond wires to collect an

26 Required by Rule 0400-18-01-.02(4)(c)2

Text Inserted�
Text
"Procedure to obtain true “remote earth”: Place reference cell at least 25 feet away from structure being tested."
Text Inserted�
Text
"Measure the remote potential. Move the reference cell another 10 feet away and measure potential again."
Text Inserted�
Text
"If the difference in the two measurements is less than 10 mV, then this location represents true “remote earth” for any structures being tested at the site."
Text Inserted�
Text
"If the two measurements are not within 10 mV, then continue to move 10 feet away and measure again until two consecutive measurements are within 10 mV."
Text Replaced�
Text
[Old]: "Shorted (continuous) flex connectors: Test continuity between" [New]: "26 2. Electrically Shorted (Continuous) Flex Connectors Test continuity between the" Font "Open Sans,Bold" changed to "OpenSans".Font-size "9.96001" changed to "6.48".
Text Replaced�
Text
[Old]: "shorted to connecting component, then local Instant Off potentials only must be measured (no remotes required). If multiple flexes are shorted together in a sump with multiple anodes attached, then" [New]: "the flex connector is shorted to the connecting component, then only measure local “Instant Off” potentials for each flex connector. 26 If multiple flex connectors are shorted together," Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"connector"
Text Replaced�
Text
[Old]: "Instant Off" [New]: "“Instant Off”" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "flexes." [New]: "flex connectors." Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"DRAFT"
Text Inserted�
Text
"connector"
Text Replaced�
Text
[Old]: "Contact" [New]: "contact" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "flex," [New]: "flex connector," Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "conduct Instant Off test. Repeat this procedure for each flex. Again, if Instant Off" [New]: "measure the “Instant Off” potential. Repeat this procedure for each flex connector. Again, if the “Instant Off” potential" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "obtain passing 100mV shift. NOTE: For local Instant Off readings, each flex must be tested individually by" [New]: "determine whether the 100mV shift criteria is met. NOTE: For local “Instant Off” readings, each flex connector must be tested individually. This is accomplished by (1)" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"connector"
Text Replaced�
Text
[Old]: "anode) and" [New]: "anode), (2)" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "being tested while disconnecting the bond wire. Flexes within contained sumps: If an anode has been attached to a flex within a contained sump containing water, then only a local Instant Off" [New]: "connector being tested, and (3) disconnecting the bond wire to the anode. 3. Flex Connectors in Contact with Water Inside Containment Sump(s) If an anode has been attached to a single flex connector in a sump containing water, then only a local “Instant Off”" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "flexes/anodes" [New]: "flex connectors/anodes" Font "Open Sans" changed to "OpenSans".
Text Deleted�
Text
"same"
Text Replaced�
Text
[Old]: "isolated or shorted flexes also apply. Obtaining true “remote earth”: True remote earth is not just placing the reference cell a few feet away from the protected structure. True remote earth must be determined in order to overcome any IR (voltage) drop between the anode and the protected structure. IR drop is the additional voltage produced by the anode in order to overcome resistance in the soil. As a result, the measured voltage for an “on” reading may not be the actual amount of voltage reaching the protected structure." [New]: "testing isolated (“instant off” or “100 mV shift” portion only) or shorted flex connectors apply. NOTE: In sumps with high water levels, the anode bond wire that is attached directly to a flex connector/piping that is completely submerged may not be accessible in order to disconnect to obtain “Instant Off” measurements. In this scenario, it is best to have the bond wire from the anode and the bond wire from the flex connector/piping terminate at a point above the water surface and then connect these two bond wires together. When testing, connect the positive lead from the voltmeter to the bond wire going to the flex connector and the negative lead to the reference electrode/cell (only submerge tip of reference electrode/cell in water) and then disconnect the two bond wires to collect an 26 Required by Rule 0400-18-01-.02(4)(c)2" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "17" [New]: "20" Font "Times New Roman" changed to "OpenSans".Font-size "12" changed to "10.98".
Page 26: Total Changes Content 821 - tn.gov

DRAFT

21

“Instant Off” measurement.26

4. Flex Connectors Not In Contact with Water Inside Containment Sump (Or The Sump is Dry) and an Anode is Attached

If the flex connector cannot be tested because it is not in contact with water, then document accordingly in the flex connector portion of the cathodic protection test form (e.g., unable to test Plus STP flex – not in contact with water, etc.).27

5. Flex connector(s)/piping in a “partially contained sump”

A containment sump is considered partially contained if it is constructed in such a way that it does not fully prevent soil/gravel from being in contact with flex connector(s) and/or metal piping (typically under a dispenser or at a submersible turbine pump). These “sumps” are typically constructed of plastic, wood, or metal. The piping at these sump locations may be in contact with soil/gravel inside the sump as well as soil/gravel outside of the sump walls. The configuration of the sump walls can present challenges in obtaining proper potential measurements on the structure being tested. The following scenarios may be encountered: a. Flex connector/piping is in contact with soil/gravel and is totally contained inside the

walls of the partially contained sump. All previously described testing procedures apply to this scenario. If collecting remote measurements, the sump wall can sometimes cause “shielding” which may inhibit obtaining passing remote measurements. As a result, collecting only local Instant Off/100mV shift measurements may be necessary. Regardless, the applicable data must be obtained individually for each flex connector. If “instant off” measurements are being collected, the reference cell must be placed in the soil inside the sump wall immediately adjacent to each flex connector (not the anode) while obtaining instant off/100 mV shift data using the previously described procedures.

b. Flex connector/piping is in contact with soil inside the walls of the partially contained sump and extends into the soil outside of the sump wall (by going through, around, or under the sump wall). For this scenario, the testing procedure varies depending on whether the flex connector/piping is isolated or shorted (described in earlier sections), and whether the remote measurements, if applicable, pass (–850 mV or more negative) or fail (more positive than –850 mV).

i. If the flex connector/piping is isolated, obtain local “on” and remote measurements while making contact with each flex connector/pipe inside the sump walls. If the local (reference cell inside sump and away from anodes) and remote measurements (reference cell at true remote earth) pass for a given flex connector/piping section, no additional testing is required for that particular flex connector/pipe.

ii. If either the remote measurements fail (which is likely due to “shielding”) or the flex connector/piping is shorted (see earlier section), additional testing will be needed. Specifically, Instant Off/100mV shift measurements will be required for each flex connector/pipe section inside and outside the sump wall. To test the piping section outside the sump, make contact with the piping inside the sump wall and a place

27 Required by Rule 0400-18-01-.02(4)(c)2(iii)

Text Replaced�
Text
[Old]: "The measurement is actually more negative (the measurement appears more negative than -850 mV). For example: you measure -890 mV when the actual amount reaching the protected structure may only be -820 mV. Procedure: Place reference cell at least 25 feet away from structure being tested." [New]: "“Instant Off” measurement. 26 4. Flex Connectors Not In Contact with Water Inside Containment Sump (Or The Sump is Dry) and an Anode is Attached If the flex connector cannot be tested because it is not" Font "Open Sans" changed to "OpenSans".
Text Deleted�
Text
"Measure the remote potential. Move the reference cell another 10 feet away and measure potential again."
Text Replaced�
Text
[Old]: "If the difference in the two measurements is less than 10 mV, then this location represents true remote earth for any structures being tested at the site." [New]: "in contact with water, then document accordingly in the flex connector portion" Font "Open Sans" changed to "OpenSans".
Text Deleted�
Text
"If the two measurements are not within 10 mV, then continue to move 10 feet away and measure again until two consecutive measurements are within 10 mV."
Text Replaced�
Text
[Old]: "Testing of Flex Connectors in “Partially Contained Sump” areas: A partially contained sump is the area surrounding the STP head and associated piping that has a barrier or retaining wall made of plastic, wood, metal, or other material designed to prevent soil/gravel from coming in contact with the pump head/piping. These barriers/walls are not sealed and allow access to the surrounding soil/gravel to a varying degree at the bottom or sides. Part of the STP head and associated flex/piping may be in contact with soil inside as well as outside of these barriers/walls. As a result, flex/piping in contact with soil requires corrosion protection and testing. The configuration of these walls presents some challenges in obtaining proper testing results." [New]: "of the cathodic protection test form (e.g., unable to test Plus STP flex – not in contact with water, etc.). 27 5. Flex connector(s)/piping in a “partially contained sump” A containment sump is considered partially contained if it is constructed in such a way that it does not fully prevent soil/gravel from being in contact with flex connector(s) and/or metal piping (typically under a dispenser or at a submersible turbine pump). These “sumps” are typically constructed of plastic, wood, or metal. The piping at these sump locations may be in contact with soil/gravel inside the sump as well as soil/gravel outside of the sump walls. The configuration of the sump walls can present challenges in obtaining proper potential measurements on the structure being tested." Font "Open Sans,Bold" changed to "OpenSans".
Text Replaced�
Text
[Old]: "1. Flex/piping" [New]: "a." Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"DRAFT"
Text Replaced�
Text
[Old]: "in contact with soil" [New]: "Flex connector/piping is in contact with soil/gravel" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"contained"
Text Replaced�
Text
[Old]: "retaining wall area with the STP head. All previously described testing procedures also" [New]: "walls of the partially contained sump. All previously described testing procedures" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "The retaining wall will sometimes cause “shielding” which inhibits obtaining a remote measurement. As a result, in many cases," [New]: "If collecting remote measurements, the sump wall can sometimes cause “shielding” which may inhibit obtaining passing remote measurements. As a result, collecting" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "can be taken as described previously. The flex/piping is contacted directly and the reference cell placed immediately adjacent to the flex in the soil inside of the retaining wall. 2. Flex/piping in contact with soil inside of the retaining wall area with the STP head and also extends into soil outside of the wall (by going through, around, or under it). All previously described testing procedures also apply to this scenario. A problem occurs when attempting to obtain a remote measurement for the portion of the flex/piping inside the retaining wall area. The retaining wall will sometimes “shield” the ability to obtain this measurement. As a result, only Instant Off/100mV shift measurements can be taken on the portion inside of the retaining wall. The portion of the same flex/piping outside the wall will require separate testing. A remote measurement may be able to be taken here since it is not shielded by the wall. Contact can be made with the flex inside the wall and a separate local “on” measurement obtained with" [New]: "may be necessary. Regardless, the applicable data must be obtained individually for each flex connector. If “instant off” measurements are being collected, the reference cell must be placed in the soil inside the sump wall immediately adjacent to each flex connector (not the anode) while obtaining instant off/100 mV shift data using the previously described procedures. b. Flex connector/piping is in contact with soil inside the walls of the partially contained sump and extends into the soil outside of the sump wall (by going through, around, or under the sump wall). For this scenario, the testing procedure varies depending on whether the flex connector/piping is isolated or shorted (described in earlier sections), and whether the remote measurements, if applicable, pass (–850 mV or more negative) or fail (more positive than –850 mV). i. If the flex connector/piping is isolated, obtain local “on” and remote measurements while making contact with each flex connector/pipe inside the sump walls. If the local (reference cell inside sump and away from anodes) and remote measurements (reference cell at true remote earth) pass for a given flex connector/piping section, no additional testing is required for that particular flex connector/pipe. ii. If either the remote measurements fail (which is likely due to “shielding”) or the flex connector/piping is shorted (see earlier section), additional testing will be needed. Specifically, Instant Off/100mV shift measurements will be required for each flex connector/pipe section inside and outside the sump wall. To test the piping section outside the sump, make contact with the piping inside the sump wall and a place 27 Required by Rule 0400-18-01-.02(4)(c)2(iii)" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"21"
Page 27: Total Changes Content 821 - tn.gov

DRAFT

22

the reference cell outside the sump wall in soil above the piping (if necessary a hole may be drilled in the groundcover to obtain soil access).28

In either scenario, consideration must be given to where the anodes are located. This will affect where the reference electrode/cell is placed during testing as well as determining whether the anode’s location is adequate to protect the piping. Also, consideration must be given to the material of construction of the sump walls when placing the reference cell, because sump wall construction material (e.g., galvanized steel, etc.) may influence the potential measurements. To reduce this influence, the reference cell should be placed as far away from the metal retaining wall (if possible) and anode.

6. Short STP Piping Sections:

Piping sections between STP heads and flex connectors that are in contact with the ground are at risk of failure from corrosion. This short “stub” of piping between the STP head and flex connectors is often overlooked. Although the STP head does not require corrosion protection, the referenced piping stub does require cathodic protection if it is in contact with the ground.29 To achieve protection, the soil or water in contact with the piping stub can be removed, or an anode can be added to protect the stub. If the flex connector is protected with an anode, the piping stub may already be protected if it is electrically continuous with the flex connector. Regardless, if an anode is being used to protect the referenced piping, the piping must be tested to confirm that it is cathodically protected.28

9. Internally Lined Tanks As of December 22, 2012, all internally lined tanks shall have a cathodic protection system added or be permanently closed as required by rule .02(4)(a)3.(v). The lining material must be compatible with the product stored as required by .02(4)(a)3.(i)(II). Records of the lining installation must be maintained for the operational life of the tank as required by rule .02(4)(a)3.(i)(VI) and transferred to any new owners as required by rule .03(2)(d).

a. For internally lined tanks with a CP system (tanks with a properly operating CP system do not require periodic inspections of the internal lining) 1. The tank owner and/or operator must have CP test records required by rule .02(4)(c)2.(iii),

.02(4)(c)5.(i), and .03(2)(b)5. indicating the corrosion protection status. If the tank owner and/or operator does not have the CP records, then they must conduct a CP test as required by rule .02(4)(c)2.

2. An Impressed Current CP system must remain operational for the remaining life of the tank, as required by rule .02(4)(c)1. and records maintained as required by rule .02(4)(c)5. and .03(2).

For testing and recordkeeping of cathodic protection systems, refer to Sections 4 “Testing” and 5 “Recordkeeping” in the “Galvanic Systems” and “Impressed Current Systems” portions of this document.

b. Internal Lining of Tanks as a Tank Repair

28 Required by Rule 0400-18-01-.02(4)(c)2 29 Required by Rule 0400-18-01-.02(4)(b)2

Text Replaced�
Text
[Old]: "placed outside of the wall (by drilling a hole if needed). But, if a remote cannot be obtained in this situation, then an Instant Off/100mV shift measurement is required on the portion outside the wall." [New]: "outside the sump wall in soil above the piping (if necessary a hole may be drilled in the groundcover to obtain soil access). 28" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "cell" [New]: "electrode/cell" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "if" [New]: "whether" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "flex/piping regardless of whether it is all inside the wall or also extends outside the wall. Consideration must be given to the material of construction of these walls, i.e., if made of galvanized steel. This may influence the measurements as well as where the reference cell is placed. Installing anodes: It is important that anodes be attached to the flex connectors properly not only to ensure that the anode is actually bonded to metal continuous with the flex, but to also make future testing more practical. This is especially needed in sumps with high water levels. If the anode bond wire is attached directly to the flex itself and submerged well below the water surface, it may not be accessible in order to conduct Instant Off tests. New anode bond wires, as well as previously installed anodes, may need to have the wire attached to a continuous component (piping or STP head) above the water surface in order to be accessible each successive testing. If the flex is isolated and the wire can only be attached directly to it, then an additional length of bond wire may need to brought above the surface of the water with a connection which can be detached in order to conduct an Instant Off test. Short STP piping sections: Piping sections between STP heads and flex connectors that are in contact with the soil and/or water" [New]: "piping. Also, consideration must be given to the material of construction of the sump walls when placing the reference cell, because sump wall construction material (e.g., galvanized steel, etc.) may influence the potential measurements. To reduce this influence, the reference cell should be placed as far away from the metal retaining wall (if possible) and anode. 6. Short STP Piping Sections: Piping sections between STP heads and flex connectors that are in contact with the ground" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "require CP and an isolated flex connector may be adequately booted" [New]: "require corrosion protection, the referenced piping stub does require cathodic protection if it is in contact with the ground." Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"DRAFT"
Text Replaced�
Text
[Old]: "or have CP added, the stub may be unprotected. If the flex connector is continuous with this stub and if the flex has adequate CP, then it may be sufficient to protect the stub also. Another recommended solution would be to eliminate the soil and/or water contact with this stub. INTERNALLY LINED TANKS As of December 22, 2012, all internally lined tanks shall have a cathodic protection system added or be permanently closed as required by rule .02(4)(a)3.(v). All lined tanks must be compatible with the product stored as required by .02(4) (a)3.(i)(II)." [New]: "29 To achieve protection, the soil or water in contact with the piping stub can be removed, or an anode can be added to protect the stub. If the flex connector is protected with an anode, the piping stub may already be protected if it is electrically continuous with the flex connector. Regardless, if an anode is being used to protect the referenced piping, the piping must be tested to confirm that it is cathodically protected. 28 9. Internally Lined Tanks As of December 22, 2012, all internally lined tanks shall have a cathodic protection system added or be permanently closed as required by rule .02(4)(a)3.(v). The lining material must be compatible with the product stored as required by .02(4)(a)3.(i)(II)." Font "Open Sans" changed to "OpenSans".Font-size "9.96001" changed to "6.48".
Text Replaced�
Text
[Old]: "18" [New]: "22" Font "Times New Roman" changed to "OpenSans".Font-size "12" changed to "10.98".
Text Replaced�
Text
[Old]: "1)" [New]: "a." Font "Open Sans,Bold" changed to "OpenSans-Bold".Font-size "9.96001" changed to "12".
Text Replaced�
Text
[Old]: "a." [New]: "1." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: ".02(4)(c)2.(ii)," [New]: ".02(4)(c)2.(iii)," Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: ".03(2)(b)2." [New]: ".03(2)(b)5." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "b." [New]: "2." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "sections 4 Testing" [New]: "Sections 4 “Testing”" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "Recordkeeping above. 2) Internal lining of tanks as a tank repair" [New]: "“Recordkeeping” in the “Galvanic Systems” and “Impressed Current Systems” portions of this document. b. Internal Lining of Tanks as a Tank Repair 28 Required by Rule 0400-18-01-.02(4)(c)2 29 Required by Rule 0400-18-01-.02(4)(b)2" Font "Open Sans" changed to "OpenSans".
Page 28: Total Changes Content 821 - tn.gov

DRAFT

23

If a tank meets any one of the construction standards in rule .02(4)(a)1. through 5., it may be repaired by lining. The Division will consider the lining or relining to be “in a manner that is no less protective”, as allowed in rule .02(4)(a)6., as long as the tank is lined following the requirements of rule .02(4)(a)3. and .02(7)(a) and the record of the lining is maintained for the operational life of the UST system as required by rule .02(7)(h) and records of the lining are transferred to any new tank owner as required by rule .03(2)(d). Exception: If the tank is constructed of fiberglass, rule .02(7)(b) has the additional requirement mandating:

“Repairs to fiberglass-reinforced plastic tanks shall be made by the manufacturer’s authorized representatives or in accordance with the manufacturer’s specifications.”

Consequently, if the manufacturer of a fiberglass reinforced tank does not allow its tanks to be repaired by lining, rule .02(7)(b) would prevent lining as a repair. The following conditions must be met for tank owners and/or operators using tank lining as a repair: 1. Prior to adding the internal lining, the tank integrity must first be assessed and determined

to be structurally sound in accordance with NLPA Standard 63130 and determined to be suitable for internal lining as required by rule .02(4)(a)3.(i)(III).

2. Rule .02(4)(a)3.(i)(IV) requires linings to be installed in accordance with manufacturer’s instructions. The following standards are allowed by federal rule 40 CFR Part 280.33(a) and (b), and they may be used to comply with rule .02(4)(a)3.(i)(IV) and .02(4)(a)6.:

National Leak Prevention Association Standard 631, Chapter A-Entry, Cleaning, Interior Inspection, Repair, and Lining of Underground Storage Tanks

National Leak Prevention Association Standard 631, Chapter D-Lining of Fiberglass Tanks for Compatibility & Repairs That Are Allowed

The NLPA standards are available at http://www.nlpa-online.org/standards.html and they include requirements like the ones listed below:

i. Internal tank linings must be installed in accordance with NLPA Standard 631 which requires an assessment of the tank shell after cleaning the tank and abrasive blasting of the tank interior. NLPA 631 contains specifications for testing for and repairing tank wall perforations. The procedures for assessing the tank shell in NPLA 631 must be followed and if it is determined the tank does not pass the assessment, the tank is not suitable for lining.

ii. The tank assessment must be performed by a company trained and qualified to perform this work, and the tank lining must be installed in accordance with NLPA 631 and lining manufacturer’s instructions by a company trained and qualified to do tank lining.

3. Rule .02(7)(a) requires that repairs to UST systems be made to prevent releases due to structural failures or corrosion as long as the UST system is used to store petroleum. In accordance with rule .02(4)(a)3.(i)(I), any tank lining must be installed to effectively prevent

30 Required by Rule 0400-18-01-.02(7)(a)

Text Replaced�
Text
[Old]: ".02(7)(f)" [New]: ".02(7)(h)" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "Tank owners may also submit the lining records to the Division for retention in its files, and the Division will maintain the records following the requirements of rule .14(1). Exception: If the tank is constructed of fiberglass, rule .02(7)(b) has the additional requirement mandating: “Repairs to fiberglass-reinforced plastic tanks shall be made by the manufacturers" [New]: "Exception: If the tank is constructed of fiberglass, rule .02(7)(b) has the additional requirement mandating: “Repairs to fiberglass-reinforced plastic tanks shall be made by the manufacturer’s" Font "Open Sans" changed to "OpenSans-BoldItalic".
Text Replaced�
Text
[Old]: "a." [New]: "1." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "631" [New]: "63130" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "b." [New]: "2." Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"DRAFT"
Text Deleted�
Text
"631, Chapter"
Text Replaced�
Text
[Old]: "19" [New]: "23" Font "Times New Roman" changed to "OpenSans".Font-size "12" changed to "10.98".
Text Replaced�
Text
[Old]: "done" [New]: "performed" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "do" [New]: "perform" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"the"
Text Replaced�
Text
[Old]: "instructions," [New]: "instructions" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "c." [New]: "3." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: ".02(4)3.," [New]: ".02(4)(a)3.(i)(I)," Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"30 Required by Rule 0400-18-01-.02(7)(a)"
Page 29: Total Changes Content 821 - tn.gov

DRAFT

24

a release due to corrosion for the operational life of the system.

4. The Division asks to be given sufficient advance notice of the tank entry, cleaning, assessment, repair, and lining installation to have staff on site during every phase of the process. Complete documentation of the repair process is considered a tank repair record and must be maintained for the life of the system as required by rule .02(7)(h) and transferred to any new owner as required by rule .03(2)(d).

c. Lining And Relining Tanks to Assure Compatibility with Alternative Fuels If a tank meets any one of the construction standards in rule .02(4)(a)1. through 5., it may be lined or relined to meet the compatibility requirements of rule .02(5). The Division will consider the lining or relining to be “in a manner that is no less protective”, as allowed in rule .02(4)(a)6., as long as the tank is lined following the requirements of rule .02(4)(a)3. and .02(7)(a) and the record of the lining is maintained for the operational life of the UST system as required by rule .02(7)(h) and records of the lining are transferred to any new tank owner as required by rule .03(2)(d). If records are not maintained, the tank would be considered incompatible with alternative fuels.

Text Replaced�
Text
[Old]: "d." [New]: "4." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: ".02(7)(f)" [New]: ".02(7)(h)" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "3) Lining and relining tanks to assure compatibility with alternative fuels" [New]: "c. Lining And Relining Tanks to Assure Compatibility with Alternative Fuels" Font "Open Sans,Bold" changed to "OpenSans-Bold".Font-size "9.96001" changed to "12".
Text Replaced�
Text
[Old]: ".02(7)(f)" [New]: ".02(7)(h)" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"DRAFT"
Text Deleted�
Text
"Tank owners may also submit the lining records to the Division for retention in its files, and the Division will maintain the records following the requirements of rule .14(1)."
Text Replaced�
Text
[Old]: "20" [New]: "24" Font "Times New Roman" changed to "OpenSans".Font-size "12" changed to "10.98".
Page 30: Total Changes Content 821 - tn.gov

DRAFT

25

REFERENCES

1. Guidelines for the Evaluation of Underground Storage Tank Cathodic Protection Systems.

Mississippi Department of Environmental Quality, Revised February 1, 2019 2. NACE Standard TM0101-2012- “Measurement Techniques Related to Criteria for Cathodic

Protection of Underground Storage Tank Systems” NACE International 3. NACE Standard Practice SP0285- “External Corrosion Control of Underground Storage Tank

Systems by Cathodic Protection” NACE International 4. NACE Standard Practice SP0169- “Control of External Corrosion on Underground or

Submerged Metallic Piping Systems” NACE International 5. Steel Tank Institute (STI) Recommended Practice R892- “Recommended Practice for Corrosion

Protection of Underground Piping Networks Associated with Liquid Storage and Dispensing Systems” Steel Tank Institute

6. Steel Tank Institute (STI) Recommended Practice R972- “Recommended Practice for the

Addition of Supplemental Anodes to sti-P3® UST's” Steel Tank Institute 7. Steel Tank Institute (STI) Recommended Practice R051- “Cathodic Protection Testing

Procedures for sti-P3® UST's” Steel Tank Institute 8. Technical Interpretation and Guidance Regarding the Combination of Cathodic Protection and

Internal Lining, December 4, 1995 Environmental Protection Agency

Text Replaced�
Text
[Old]: "July 1, 2002" [New]: "Revised February 1, 2019" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "TM0101-2012, NACE International 3. NACE Recommended Practice RP 0285-“Corrosion" [New]: "TM0101-2012-“Measurement Techniques Related to Criteria for Cathodic Protection of Underground Storage Tank Systems” NACE International 3. NACE Standard Practice SP0285-“External Corrosion" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "Recommended Practice RP 0169-“Control" [New]: "Standard Practice SP0169-“Control" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "R892 “Recommended" [New]: "R892-“Recommended" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "R972 “Recommended" [New]: "R972-“Recommended" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "Installation" [New]: "Addition" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "for" [New]: "to" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "R051 “Cathodic" [New]: "R051-“Cathodic" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "sti-P3®" [New]: "sti-P3" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"DRAFT"
Text Inserted�
Text
"®"
Text Replaced�
Text
[Old]: "21" [New]: "25" Font "Times New Roman" changed to "OpenSans".Font-size "12" changed to "10.98".
Page 31: Total Changes Content 821 - tn.gov

DRAFT

26

APPENDICES

1. Structure-to-Soil Test Procedure for Galvanic CP Systems 2. Continuity Testing Procedure for CP Systems 3. Structure-to-Soil Test Procedure for Impressed Current CP Systems 4. Test Procedure for Flex Connectors 5. Commonly Used Definitions 6. Impressed Current CP Testing Survey 7. Galvanic CP Testing Survey 8. Impressed Current CP System 60 Day Record of Rectifier Operation Form

Text Inserted�
Text
"DRAFT"
Page 32: Total Changes Content 821 - tn.gov

DRAFT

27

APPENDIX 1: STRUCTURE-TO-SOIL TEST PROCEDURE FOR GALVANIC CATHODIC PROTECTION SYSTEMS

For tank(s) with galvanic cathodic protection systems where the anodes cannot be disconnected, a minimum of three potential measurement must be taken (one local potential measurement at the center of the tank and away from the anodes, and two remote earth potential measurements).1,2 These two remote earth readings can be used to determine the “true” remote earth measurements. Additional local measurements may be collected at the ends of the UST. It is vital that proper equipment and proper techniques be used when testing cathodic protection on UST systems. Proper Copper/Copper Sulfate Reference Electrode/Cell Usage3

Reference electrode/cell may not be placed on concrete or other paving materials to collect potential measurements. Drill holes in concrete to obtain access to soil over tank and piping if necessary.

Ensure that the reference electrode/cell is placed in a vertical position (tip down). Ensure that soil where the reference electrode/cell is placed is moist – add tap water if

necessary. Ensure that soil where the reference electrode/cell is placed is not contaminated with

hydrocarbons. Ensure that the reference electrode/cell window (if applicable) is not exposed to direct

sunlight. Proper Cathodic Protection Measurement Techniques3

Ensure that good metal-to-metal contact is made between the test lead clip/probe and the structure.

Ensure that no corrosion exists where the test lead makes contact with the structure. Ensure that your body does not come into contact with the electrical connections. Ensure that test leads are not submerged in any standing water. Ensure that test lead insulation is in good condition. Ensure that any drop tube that is installed in the tank does not prohibit contact with the tank

bottom. If a metallic probe is used to contact the tank bottom, ensure that the probe does not contact

the fill riser or any other metallic component of the UST system. Mandatory Test Procedure: STI-P3® tanks3

1. Place voltmeter on 2 volt DC scale. 2. Connect voltmeter negative lead to reference electrode/cell. 3. Place reference electrode/cell in clean soil at true remote earth* from the protected structure. 4. Contact tank bottom, external shell or structure being tested with positive voltmeter lead wire.

This may be accomplished by connecting the voltmeter lead wire to a copper or brass test prod (do not used galvanized metal) mounted to the bottom of a wooden gauging stick and lowering the stick to make contact with the structure.

5. Obtain voltage and record in the remote voltage column on Galvanic Cathodic Protection Survey Form CN-1140.

Text Deleted�
Text
"APPENDIX 1 STRUCTURE-TO-SOIL TEST PROCEDURE FOR GALVANIC CATHODIC PROTECTION SYSTEMS"
Text Replaced�
Text
[Old]: "For tanks with galvanic cathodic protection systems in which" [New]: "APPENDIX 1: STRUCTURE-TO-SOIL TEST PROCEDURE FOR GALVANIC CATHODIC PROTECTION SYSTEMS For tank(s) with galvanic cathodic protection systems where" Font "Open Sans" changed to "OpenSans-Bold".Font-size "9.96001" changed to "12".
Text Replaced�
Text
[Old]: "one local potential measurement near the UST center and away from the anodes and one remote potential measurement must be taken. 1,2 Alternatively, three potential measurements, one at each of the UST ends and one near the center of the UST, and one remote potential measurement may be taken. 1,2 It is vital that proper equipment and proper techniques be used when testing cathodic protection on UST systems. Proper Copper/Copper Sulfate Reference Electrode Usage 3 Reference electrode may not be placed on concrete or other paving materials to make potential readings." [New]: "three potential measurement must be taken (one local potential measurement at the center of the tank and away from the anodes, and two remote earth potential measurements). 1,2 These two remote earth readings can be used to determine the “true” remote earth measurements. Additional local measurements may be collected at the ends of the UST. It is vital that proper equipment and proper techniques be used when testing cathodic protection on UST systems. Proper Copper/Copper Sulfate Reference Electrode/Cell Usage 3 Reference electrode/cell may not be placed on concrete or other paving materials to collect potential measurements." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "electrode" [New]: "electrode/cell" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "electrode" [New]: "electrode/cell" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "electrode" [New]: "electrode/cell" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "electrode window" [New]: "electrode/cell window (if applicable)" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"DRAFT"
Text Replaced�
Text
[Old]: "STI-P3®" [New]: "STI-P3 ®" Font "Open Sans,Bold" changed to "OpenSans-Bold".
Text Replaced�
Text
[Old]: "electrode." [New]: "electrode/cell." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "electrode" [New]: "electrode/cell" Font "Open Sans" changed to "OpenSans".
Text Deleted�
Text
"a"
Text Replaced�
Text
[Old]: "Positive voltmeter lead will be used to contact tank bottom, external tank shell or structure being tested." [New]: "Contact tank bottom, external shell or structure being tested with positive voltmeter lead wire." Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"or brass test prod (do not used galvanized metal)"
Text Replaced�
Text
[Old]: "into the tank fill riser." [New]: "to make contact with the structure." Font "Open Sans" changed to "OpenSans".
Text Deleted�
Text
"Tennessee"
Text Replaced�
Text
[Old]: "22" [New]: "27" Font "Times New Roman" changed to "OpenSans".Font-size "12" changed to "10.98".
Page 33: Total Changes Content 821 - tn.gov

DRAFT

28

6. Move reference electrode/cell to a point near the center of the tank along the midline directly over the structure that is being tested to obtain local potential reading(s). More than one local potential reading may be made if desired.

7. Obtain voltage and record in the local voltage column on form CN-1140. Note: If a sti-P3® tank is equipped with a PP4® test station, do not use the test station to collect either local or remote potential measurements.3 If a test lead wire or PP2® test station is utilized to make contact with the tested structure you must ensure that continuity exists between the test lead wire and the structure. This may be accomplished by conducting a point-to-point continuity test.3

Cathodically protected steel or other metallic piping with galvanic anodes3 Steel or other metallic piping is tested by following Steps 1-7 above and making the contact from the positive voltmeter lead wire to a point on the piping. Piping requires potential measurements at each end of the pipe. If more than 100 feet of piping exist between any two anodes, the reference electrode/cell must also be placed at the midpoint between the two anodes that are separated by more than 100 feet. If it is not known where the piping anodes are located, there can be no more than 100 feet of piping between any two test points. * True Remote Earth is determined by placing the reference electrode/cell at least 25 feet away from any structure that is to be tested, taking a potential measurement then moving the reference electrode/cell at least 10 feet farther from the first remote reference electrode/cell test location. If the two measurements are within 10 mV of each other, then true remote earth has been established. If the difference between the two measurements is greater than 10 mV, then move another 10 feet away from the structure and take another measurement. Once two (2) consecutive locations are within 10 mV of each other, either of those locations will be true remote earth. Data Interpretation for Cathodic Protection Testers1,2,3 Pass - If both the local and the remote potential measurements are –850 mV or more negative, the –850 mV on criterion is met and adequate cathodic protection has been demonstrated. Fail - If both the local and the remote potential measurements are more positive than –850 mV, the –850 mV on criterion is not met and adequate cathodic protection has not been demonstrated. Inconclusive - If either the local or the remote potential measurement is more positive than –850 mV for all structures tested, the test result is inconclusive and further testing and/or repairs are necessary. Incomplete - If one or more of the structures tested pass the above criteria and other structures fail the above criteria, the tester may issue an incomplete result on form CN-1140. Structures which do not pass the above criteria are not considered corrosion protected, and further testing and/or repairs are necessary. NOTE: Any NACE certified corrosion expert may evaluate results of the survey or conduct the survey and declare a pass or fail based on their interpretation of the data and professional judgment.

Text Replaced�
Text
[Old]: "More than one remote potential reading may be made if desired. 6. Move reference electrode" [New]: "6. Move reference electrode/cell" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"form"
Text Replaced�
Text
[Old]: "sti-P3®" [New]: "sti-P3 ®" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"®"
Text Replaced�
Text
[Old]: "the PP4 test station is disregarded and potentials must be obtained with a portable reference electrode placed in the soil at both local and remote earth locations. 3 If a test lead wire or PP2" [New]: "do not use the test station to collect either local or remote potential measurements. 3 If a test lead wire or PP2 ®" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"3 Cathodically protected steel or other metallic piping with galvanic anodes"
Text Deleted�
Text
"3 Cathodically protected steel piping with galvanic anodes"
Text Inserted�
Text
"or other metallic"
Text Inserted�
Text
"wire"
Text Replaced�
Text
[Old]: "measurement" [New]: "potential measurements" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "electrode" [New]: "electrode/cell" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "cell" [New]: "electrode/cell" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "reading" [New]: "potential measurement" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "cell" [New]: "electrode/cell" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "cell" [New]: "reference electrode/cell" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "readings" [New]: "measurements" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "readings" [New]: "measurements" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "reading. Once 2 consecutive locations that" [New]: "measurement. Once two (2) consecutive locations" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "other are obtained, that will be true remote earth and the remote structure readings are made with the reference cell in this location." [New]: "other, either of those locations will be true remote earth." Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"DRAFT"
Text Replaced�
Text
[Old]: "Pass-If" [New]: "Pass -If" Font "Open Sans" changed to "OpenSans-Bold".
Text Inserted�
Text
"measurements"
Text Replaced�
Text
[Old]: "-850" [New]: "– 850" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"measurements"
Text Replaced�
Text
[Old]: "the-850" [New]: "the – 850" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "Inconclusive-If" [New]: "Inconclusive -If" Font "Open Sans" changed to "OpenSans-Bold".
Text Inserted�
Text
"measurement"
Text Replaced�
Text
[Old]: "Incomplete-If" [New]: "Incomplete -If" Font "Open Sans,Bold" changed to "OpenSans-Bold".
Text Inserted�
Text
"form"
Text Replaced�
Text
[Old]: "23" [New]: "28" Font "Times New Roman" changed to "OpenSans".Font-size "12" changed to "10.98".
Page 34: Total Changes Content 821 - tn.gov

DRAFT

29

Continuity Testing

If test results are Fail or Inconclusive, a tester may perform continuity testing to determine if the protected structure is shorted. This can help determine why the minimum –850 mV was not achieved. See Appendix 2 for Continuity Testing Procedure. References

a. NACE Standard TM0101-2012, NACE International b. Cathodic Protection Testing Procedures for STI-P3® USTs, R051, Steel Tank Institute, April 2017 c. Guidelines for the Evaluation of Underground Storage Tank Cathodic Protection Systems.

Mississippi DEQ, Revised February 1, 2019.    

Text Replaced�
Text
[Old]: "-850" [New]: "–850" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "1." [New]: "a." Font "Times New Roman" changed to "OpenSans-Bold".
Text Replaced�
Text
[Old]: "2." [New]: "b." Font "Times New Roman" changed to "OpenSans-Bold".
Text Inserted�
Text
"®"
Text Replaced�
Text
[Old]: "January 2006 3." [New]: "April 2017 c." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "July 1, 2002." [New]: "Revised February 1, 2019." Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"DRAFT"
Page 35: Total Changes Content 821 - tn.gov

DRAFT

30

APPENDIX 2: CONTINUITY TESTING PROCEDURE FOR CATHODIC PROTECTION SYSTEMS

(GALVANIC & IMPRESSED CURRENT) Adapted from Mississippi Department of Environmental Quality, Revised February 1, 2019

Fixed Cell – Moving Ground Continuity Test Procedure (not to be used for impressed current systems):

1. Place reference electrode/cell in contact with the soil at true remote earth (see Appendix 1). You must ensure that the remote reference electrode placement is not in proximity to any other cathodic protection systems (e.g. natural gas pipelines) or directly over any buried metallic structure in order to minimize the chances of unwanted interference.

2. Place reference electrode/cell firmly in moist soil and ensure that it is not in contact with any

vegetation.

3. Connect reference electrode/cell to the negative terminal of voltmeter using a long spool of suitable wire.

4. Connect positive lead wire to voltmeter. This lead wire should have a sharp test prod (scratch awl or similar) to ensure good contact with the metallic structures under test.

5. Place voltmeter on 2 volt DC scale.

6. Contact each buried metallic structure with the positive test lead without moving the reference

electrode/cell. Typical structures that would be tested during a continuity survey include: all tanks, tank risers, submersible turbine pump heads, piping, flex connectors/swing joints, vent lines, electrical conduits, dispensers, utilities, etc.

7. Obtain voltage for each component and record on Tennessee cathodic protection survey form.

8. Obtain voltages for each component quickly because observed potential measurements can

change in a relatively short period of time due to conditions in the soil where the reference electrode/cell is placed.

Fixed Cell – Moving Ground Data Interpretation (not to be used for impressed current systems)

If two or more structures exhibit potential measurements that vary by 5 mV or less, the structures are considered to be electrically continuous.

If two or more structures exhibit potential measurements that vary by 10 mV or greater, the structures are considered to be electrically isolated.

If two or more structures exhibit potential measurements that vary by more than 5 mV but less than 10 mV, the result is inconclusive and further testing (point-to-point) is necessary.

Text Deleted�
Text
"APPENDIX 2"
Text Inserted�
Text
"APPENDIX 2:"
Text Replaced�
Text
[Old]: "July 1, 2002" [New]: "Revised February 1, 2019" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "(must not" [New]: "(not to" Font "Open Sans,Bold" changed to "OpenSans-Bold".
Text Replaced�
Text
[Old]: "systems)" [New]: "systems):" Font "Open Sans,Bold" changed to "OpenSans-Bold".
Text Replaced�
Text
[Old]: "electrode" [New]: "electrode/cell" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "a location remote (25 – 100 feet) from all cathodically protected structures." [New]: "true remote earth (see Appendix 1)." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "Be sure that reference electrode is firmly placed in moist soil and" [New]: "Place reference electrode/cell firmly in moist soil and ensure that it" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "electrode" [New]: "electrode/cell" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "in order to assure" [New]: "to ensure" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "electrode. Typical items" [New]: "electrode/cell. Typical structures" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"turbine"
Text Replaced�
Text
[Old]: "Voltages" [New]: "Obtain voltages" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "that is tested must be obtained as quickly as possible since the observed potential can change over time. This is because the conditions in the soil where the reference electrode is placed can change over a relatively short period of time. Fixed Cell – Moving Ground Data Interpretation" [New]: "quickly because observed potential measurements can change in a relatively short period of time due to conditions in the soil where the reference electrode/cell is placed. Fixed Cell – Moving Ground Data Interpretation (not to be used for impressed current systems)" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"DRAFT"
Text Replaced�
Text
[Old]: "potentials" [New]: "potential measurements" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "potentials" [New]: "potential measurements" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "potentials" [New]: "potential measurements" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "24" [New]: "30" Font "Times New Roman" changed to "OpenSans".Font-size "12" changed to "10.98".
Page 36: Total Changes Content 821 - tn.gov

DRAFT

31

Point-to-Point Continuity Test Procedure* (required for impressed current systems; however, may be used with galvanic systems)

1. If testing an impressed current system, turn off power to rectifier and disconnect the negative cable at the rectifier to obtain accurate continuity measurements.

2. Connect test leads to voltmeter. Both test leads should have a sharp test prod or suitable clip

lead to make good contact with tested structures.

3. Place voltmeter on millivolt DC scale. 4. Connect one voltmeter test lead to the structure being tested; connect the other voltmeter

test lead to the other structure being tested (galvanic systems) or to the disconnected negative rectifier wire (impressed current systems). Typical structures that would be tested during a continuity survey include: all tanks, tank risers, submersible turbine pump heads, piping, flex connectors/swing joints, vent lines, electrical conduits, dispensers, utilities, etc.

5. Record voltages observed (millivolt difference) on each of the two structures that are being

compared and record measurements on the Tennessee cathodic protection survey form. Reconnect the negative wire to the rectifier (impressed current systems) when testing is completed.

Testing with this method does not require a reference electrode/cell. The two structures of interest are simply connected in parallel with the voltmeter and a determination made as to whether or not any potential difference exists between them. * For impressed current systems, perform the point-to-point continuity testing AFTER

collecting Instant Off and/or 100 mV shift measurements to ensure the system does not depolarize prior to collecting instant off and/or 100 mV shift data.

Point-to-Point Data Interpretation

If the voltage difference observed between the two structures is 5 mV or less, the two structures are considered to be electrically continuous with each other.

If the voltage difference observed between the two structures is 10 mV or greater, the two structures are considered to be electrically isolated from each other.

If the voltage difference observed between the two structures is greater than 5mV but less than 10 mV, the test result is inconclusive and further testing is necessary.

Text Replaced�
Text
[Old]: "Procedure must be used with impressed current systems;" [New]: "Procedure* (required for impressed current systems; however," Font "Open Sans,Bold" changed to "OpenSans-Bold".
Text Replaced�
Text
[Old]: "Turn off power to rectifier if testing an impressed current system and disconnect the negative cable at the rectifier. This is necessary to obtain accurate results." [New]: "If testing an impressed current system, turn off power to rectifier and disconnect the negative cable at the rectifier to obtain accurate continuity measurements." Font "Open Sans" changed to "OpenSans".
Text Deleted�
Text
"in order"
Text Replaced�
Text
[Old]: "one of the structures for which continuity is" [New]: "the structure" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "or preferably, the negative rectifier lead wire. 5. Record voltages observed (millivolt difference) on each of the two structures that are being compared and record on Tennessee cathodic protection survey form. Reconnect the negative lead wire to the rectifier" [New]: "(galvanic systems) or to the disconnected negative rectifier wire (impressed current systems). Typical structures that would be tested during a continuity survey include: all tanks, tank risers, submersible turbine pump heads, piping, flex connectors/swing joints, vent lines, electrical conduits, dispensers, utilities, etc. 5. Record voltages observed (millivolt difference) on each of the two structures that are being compared and record measurements on the Tennessee cathodic protection survey form. Reconnect the negative wire to the rectifier (impressed current systems)" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "electrode." [New]: "electrode/cell." Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"* For impressed current systems, perform the point-to-point continuity testing AFTER collecting Instant Off and/or 100 mV shift measurements to ensure the system does not depolarize prior to collecting instant off and/or 100 mV shift data."
Text Deleted�
Text
"this indicates that"
Text Deleted�
Text
"this indicates that"
Text Inserted�
Text
"test"
Text Inserted�
Text
"DRAFT"
Text Replaced�
Text
[Old]: "25" [New]: "31" Font "Times New Roman" changed to "OpenSans".Font-size "12" changed to "10.98".
Page 37: Total Changes Content 821 - tn.gov

DRAFT

32

APPENDIX 3: STRUCTURE-TO-SOIL TEST PROCEDURE FOR IMPRESSED CURRENT CATHODIC PROTECTION SYSTEMS

Adapted from Mississippi Department of Environmental Quality, Revised February 1, 2019 For tank(s) with impressed current CP systems, collect a minimum of three local potential measurements, one at each of the UST ends and one near the center of each UST.1 For metal piping, collect one potential measurement at each dispenser, midpoints of steel piping greater than 100 feet in length, and metal piping at STP sumps. Record all necessary information on the Impressed Current Cathodic Protection Survey Form (CN-1309). It is vital that proper equipment and proper techniques be used when testing cathodic protection on UST systems. Proper Copper/Copper Sulfate Reference Electrode/Cell Usage2

Reference electrode/cell may not be placed on concrete or other paving materials to collect potential measurements. Drill holes in concrete to obtain access to soil over tank or piping if necessary.

Ensure that the reference electrode/cell is placed in a vertical position (tip down). Ensure that soil where the reference electrode/cell is placed is moist – add tap water if

necessary. Ensure that soil where the reference electrode/cell is placed is not contaminated with

hydrocarbons. Ensure that the reference electrode/cell window (if applicable) is not exposed to direct

sunlight. Proper Cathodic Protection Measurement Techniques2

Ensure that good metal-to-metal contact is made between the test lead clip/probe and the structure.

Ensure that no corrosion exists where the test lead makes contact with the structure. Ensure that your body does not come into contact with the electrical connections. Ensure that test leads are not submerged in any standing water. Ensure that test lead insulation is in good condition. Ensure that any drop tube that is installed in the tank does not prohibit contact with the tank

bottom. If a metallic probe is used to contact the tank bottom, ensure that the probe does not contact

the fill riser or any other metallic component of the UST system. Mandatory Test Procedure:

1. Inspect rectifier for proper operation and document information on Division Form CN-1309. 2. Measure rectifier output (voltage/amperage) with a multimeter (do not rely on rectifier meter

readings). Measure individual anode circuits if a junction box is present. 3. Place voltmeter on 2-volt DC scale. 4. Connect voltmeter positive lead to structure to be tested and connect voltmeter negative lead to

reference electrode/cell. If the structure being tested has been internally lined, then the positive lead of the voltmeter shall make contact with the exterior of the structure or to any tank system component that is continuous with that structure.

5. Place reference electrode/cell in clean soil directly over the structure that is being tested. Collect at least three (3) potential measurements for each tank. The preferred locations for the potential measurements are at the approximate midpoint and at each end of the tank along the centerline

Text Deleted�
Text
"APPENDIX 3"
Text Inserted�
Text
"APPENDIX 3:"
Text Replaced�
Text
[Old]: "July 1, 2002 For a tank" [New]: "Revised February 1, 2019 For tank(s)" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"collect"
Text Replaced�
Text
[Old]: "UST must be taken." [New]: "UST." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "one reading shall be collected" [New]: "collect one potential measurement" Font "Open Sans" changed to "OpenSans".
Text Deleted�
Text
"Tennessee"
Text Replaced�
Text
[Old]: "Electrode" [New]: "Electrode/Cell" Font "Open Sans,Bold" changed to "OpenSans-Bold".
Text Replaced�
Text
[Old]: "electrode" [New]: "electrode/cell" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "make potential readings." [New]: "collect potential measurements." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "electrode" [New]: "electrode/cell" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "electrode" [New]: "electrode/cell" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "electrode" [New]: "electrode/cell" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "electrode window" [New]: "electrode/cell window (if applicable)" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"DRAFT"
Text Replaced�
Text
[Old]: "(voltage/ amperage)" [New]: "(voltage/amperage)" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "gauge readings). Measurement of" [New]: "meter readings). Measure" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "may also be made if there is a junction box" [New]: "if a junction box is" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "2 volt" [New]: "2-volt" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "electrode. 5. Place reference electrode in clean soil directly over the structure that is being tested. Take at least three (3) measurements for each tank, preferably" [New]: "electrode/cell. If the structure being tested has been internally lined, then the positive lead of the voltmeter shall make contact with the exterior of the structure or to any tank system component that is continuous with that structure. 5. Place reference electrode/cell in clean soil directly over the structure that is being tested. Collect at least three (3) potential measurements for each tank. The preferred locations for the potential measurements are" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "26" [New]: "32" Font "Times New Roman" changed to "OpenSans".Font-size "12" changed to "10.98".
Page 38: Total Changes Content 821 - tn.gov

DRAFT

33

(assuming tank length can be verified). Piping requires collection of potential measurement at each end of the pipe and at midpoints of piping over 100 feet in length.

6. At each location (step 5 above) obtain voltage potential measurements with the protective current applied and record in the “On Voltage” column on form CN-1309.

7. Also, at each location (step 5 above), without moving reference electrode/cell, obtain voltage potential measurements with the protective current temporarily interrupted (instant off*) and record in the “Instant Off Voltage” column on form CN-1309. If any instant off potential reading is more positive than –850 mV, the tank and/or piping may or may not be adequately protected; therefore, a 100 mV shift must be performed (see below).

8. Upon completion of this test procedure, disconnect the rectifier negative cable and perform a point-to-point continuity test (see Appendix 2).

100 mV depolarization (shift) Perform when the instant off potential measurement is more positive than –850 mV at any test location (see Step 7 above). 100 mV of depolarization is determined by measuring the difference in polarization between the instant off potential (see step 7 above) and the depolarized potential. If this change is 100 mV or greater, the 100 mV shift criteria has been met. Depolarization typically takes minutes but may take 24 hour or longer. Regardless do not interrupt the current to the cathodic protection system for more than 72 hours. Calculate voltage change by subtracting final (or ending) voltage from the instant off voltage and record these values in the appropriate columns on form CN-1309. Data Interpretation for Cathodic Protection Testers Pass - one of the following two criteria must be met in order for the structure to be protected: 1. If all instant off potentials are –850 mV or more negative, the –850 off criterion is met and adequate cathodic protection has been demonstrated. Further testing is not necessary. If the instant off potentials are more positive than –850 mV, the tank(s) and/or piping may or may not be adequately protected; therefore, a 100 mV depolarization test must be performed. 2. If the structure exhibits more than 100 mV shift, the 100 mV shift criterion is met and adequate cathodic protection has been demonstrated For impressed current systems, the instant off potential should never be more negative than –1.6 volts (–1600 millivolts) because such high potential measurements can cause coatings to disbond and result in metal embrittlement. Fail – If neither the –850 instant off nor the 100 mV shift criteria are met, adequate cathodic protection has not been demonstrated and repairs/modification will be necessary to achieve cathodic protection. Inconclusive – All test locations meet the instant off or 100 mV shift criteria; however, other unusual factors are discovered that may warrant review by a corrosion expert before a passing or failing result can be determined (such as instant off potential measurements are more negative than –1,600 mV, structures do not appear to be continuous, etc.)

Text Replaced�
Text
[Old]: "if" [New]: "(assuming" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "verified, or for small capacity tanks, one (1) local measurement over the tank top for every 10 feet of tank length. Piping requires measurement at each end of the pipe and at midpoints of piping over 100 feet in length. 6. Obtain voltage potential with the protective current applied and record in the On Voltage column on Form CN1309. 7. Without moving reference electrode from the position it was in during step 6 above, obtain voltage potential with the protective current temporarily interrupted (instant off*) and record in the Instant Off Voltage column on" [New]: "verified). Piping requires collection of potential measurement at each end of the pipe and at midpoints of piping over 100 feet in length. 6. At each location (step 5 above) obtain voltage potential measurements with the protective current applied and record in the “On Voltage” column on form CN-1309. 7. Also, at each location (step 5 above), without moving reference electrode/cell, obtain voltage potential measurements with the protective current temporarily interrupted (instant off*) and record in the “Instant Off Voltage” column on form" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "-850" [New]: "–850" Font "Open Sans,Italic" changed to "OpenSans-Italic".
Text Inserted�
Text
"and/or piping"
Text Replaced�
Text
[Old]: "protected and" [New]: "protected; therefore," Font "Open Sans,Italic" changed to "OpenSans-Italic".
Text Replaced�
Text
[Old]: "performed. See below. 8. Disconnect and make contact with the negative cable of the rectifier and determine continuity for all structures that are required to be protected by impressed current using point-to-point method. See Appendix 2 for Continuity Testing Procedure." [New]: "performed (see below). 8. Upon completion of this test procedure, disconnect the rectifier negative cable and perform a point-to-point continuity test (see Appendix 2)." Font "Open Sans,Italic" changed to "OpenSans-Italic".
Text Replaced�
Text
[Old]: "Must be performed whenever instant off potential of -850 mV or more positive for any reading in step 7 is not observed. 100 mV of polarization is determined by interrupting the polarized potential on the structure until a change of at least 100 mV in the structure-to-soil potential is observed. In calculating the 100 mV decay, the instant off potential obtained in step 7 above is utilized as the starting point (e.g. if instant off = -800 mV, power must be left off until decayed to at least -700 mV for the 100 mV polarization to be demonstrated). Depolarization may take as long as 24 hours in some cases, but cathodic protection power to the structure should not be interrupted for more than 72 hours. Calculate voltage change by subtracting final (or ending) voltage from the instant off voltage and record these values in the appropriate columns on CN-13099." [New]: "Perform when the instant off potential measurement is more positive than –850 mV at any test location (see Step 7 above). 100 mV of depolarization is determined by measuring the difference in polarization between the instant off potential (see step 7 above) and the depolarized potential. If this change is 100 mV or greater, the 100 mV shift criteria has been met. Depolarization typically takes minutes but may take 24 hour or longer. Regardless do not interrupt the current to the cathodic protection system for more than 72 hours. Calculate voltage change by subtracting final (or ending) voltage from the instant off voltage and record these values in the appropriate columns on form CN-1309." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "Pass-one" [New]: "Pass -one" Font "Open Sans,Bold" changed to "OpenSans-Bold".
Text Replaced�
Text
[Old]: "-850" [New]: "–850" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "-850" [New]: "–850" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "demonstrated and further" [New]: "demonstrated." Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"DRAFT"
Text Inserted�
Text
"Further"
Text Replaced�
Text
[Old]: "-850" [New]: "–850" Font "Open Sans,Italic" changed to "OpenSans-Italic".
Text Replaced�
Text
[Old]: "tank" [New]: "tank(s) and/or piping" Font "Open Sans,Italic" changed to "OpenSans-Italic".
Text Replaced�
Text
[Old]: "protected and" [New]: "protected; therefore," Font "Open Sans,Italic" changed to "OpenSans-Italic".
Text Replaced�
Text
[Old]: "polarization test may" [New]: "depolarization test must" Font "Open Sans,Italic" changed to "OpenSans-Italic".
Text Replaced�
Text
[Old]: "polarization," [New]: "shift," Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "polarization" [New]: "shift" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "exceed -1.6 volts (-1600 millivolts). Such high readings" [New]: "be more negative than –1.6 volts (– 1600 millivolts) because such high potential measurements" Font "Open Sans,Italic" changed to "OpenSans-Italic".
Text Replaced�
Text
[Old]: "-If neither the -850" [New]: "– If neither the –850" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "polarization" [New]: "shift" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "-The cathodic protection survey of an impressed current system must be evaluated by a corrosion expert because it cannot be determined that the protected structures are continuous or other factors may result in high readings" [New]: "– All test locations meet the instant off or 100 mV shift criteria; however, other unusual factors are discovered that may warrant review by a corrosion expert before a passing or failing result can be determined (such as instant off potential measurements are more negative than –1,600 mV, structures do not appear to be continuous, etc.)" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "27" [New]: "33" Font "Times New Roman" changed to "OpenSans".Font-size "12" changed to "10.98".
Page 39: Total Changes Content 821 - tn.gov

DRAFT

34

NOTE: A NACE certified corrosion expert may evaluate the results of the cathodic protection survey and determine that cathodic protection is adequate based on their interpretation. *The instant off potential measurement is the second value observed on a digital voltmeter immediately after the current is interrupted. The first number that appears immediately after power interruption must be disregarded. After the second number appears, a rapid decay (depolarization) of the structure will normally occur. Alternately, the instant off potential measurement may be captured by using the min/max function on the voltmeter if the meter is so equipped. To obtain instant off potential measurements, a current interrupter or a second person may be necessary to briefly interrupt the power. If a second person option is utilized, have that person turn the rectifier off for approximately 2 seconds and then back on for approximately 15 seconds. If necessary, repeat this procedure until an accurate instant off reading has been obtained. References

a. NACE Standard TM0101-2012, NACE International b. Guidelines for the Evaluation of Underground Storage Tank Cathodic Protection Systems.

Mississippi DEQ, Revised February 1, 2019.

Text Inserted�
Text
"the"
Text Replaced�
Text
[Old]: "survey or conduct the" [New]: "cathodic protection" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"measurement"
Text Deleted�
Text
"that is"
Text Replaced�
Text
[Old]: "the instant the power" [New]: "immediately after the current" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "reading" [New]: "potential measurement" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "meter" [New]: "voltmeter" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "In order to obtain instant off potentials," [New]: "To obtain instant off potential measurements," Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "necessary. If a current interrupter is not available, have a second person throw the power switch at the rectifier off for 2 seconds and then back on for 15 seconds. Repeat this procedure until you are sure" [New]: "necessary to briefly interrupt the power. If a second person option is utilized, have that person turn the rectifier off for approximately 2 seconds and then back on for approximately 15 seconds. If necessary, repeat this procedure until" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "1." [New]: "a." Font "Open Sans" changed to "OpenSans-Bold".
Text Replaced�
Text
[Old]: "2." [New]: "b." Font "Open Sans" changed to "OpenSans-Bold".
Text Replaced�
Text
[Old]: "July 1, 2002." [New]: "Revised February 1, 2019." Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"DRAFT"
Page 40: Total Changes Content 821 - tn.gov

DRAFT

35

APPENDIX 4: TEST PROCEDURE FOR FLEX CONNECTORS (INCLUDING SHORT SECTIONS OF METAL PIPING)

(adapted from Steel Tank Institute procedure) If the flex connectors are protected by an impressed current system, then test the referenced piping components in accordance with Appendix 2 and 3; otherwise follow the test procedures below for testing flex connectors protected with galvanic anodes. The following procedures will describe how to obtain potential measurements for a flex connector relative to a copper/copper sulfate reference electrode/cell. The flex connector is considered protected if the potential measurements meet one or more of the criteria described below. Results of these tests must be recorded on the Division’s applicable cathodic protection survey form (CN-1140 or CN-1309). The procedure for testing a flex connector will depend on where and how a flex connector is installed. Flex connectors may be directly buried in soil, in contact with water, extend outside the walls of the sump, etc. Regardless of the flex connector configuration, follow either Procedure A or B below (as applicable): Prior to testing flex connectors, determine whether each flex connector is electrically isolated or continuous (shorted) with other pieces of metal (dispenser piping, STP piping stub, etc.) using either the point-to-point or fixed-cell/moving ground (remote reference cell placement) method. A more detailed description on how to determine electrical continuity or isolation is provided in the “Corrosion Protection for Flexible (Flex) Connectors and Short Sections of Metal Piping” section of this Technical Chapter and Appendix 2. Document the continuity test results on the applicable continuity survey page of form CN-1140 or CN-1309 (as applicable). After determining whether each flex connector is electrically continuous or isolated, test each flex connector using the following method (as applicable):

1. Obtaining local and remote potential measurements, (PROCEDURE A)* or 2. Obtaining Instant Off potential measurements and/or 100 mV shift measurements.

(PROCEDURE B)* *If flex connectors are protected with galvanic anodes and other structures at the facility are protected by an impressed current system, the impressed current system must be turned off prior to testing the flex connectors. PROCEDURE A. –850 mV “current on” Criterion This procedure is applicable for testing isolated flex connectors in contact with soil. A total of 3 test measurements (one local and two at remote earth) are required for each flex connector when using the –850 mV current on criterion.

1. Set the voltmeter to the 2 volt DC scale. 2. Make contact to the flex connector** with the positive lead of the voltmeter. 3. Connect the negative lead of the voltmeter to the reference electrode/cell.

Text Deleted�
Text
"APPENDIX 4"
Text Inserted�
Text
"APPENDIX 4:"
Text Replaced�
Text
[Old]: "(adapted from Steel Tank Institute procedure) The following procedures will describe how to determine potential readings for a flex connector relative to a copper/copper sulfate reference electrode. The flex connector may be considered protected if the potential readings meet one or more of the criteria described below for cathodic protection. Results of these tests must be recorded on the applicable Division’s official cathodic protection survey form." [New]: "(INCLUDING SHORT SECTIONS OF METAL PIPING) (adapted from Steel Tank Institute procedure) If the flex connectors are protected by an impressed current system, then test the referenced piping components in accordance with Appendix 2 and 3; otherwise follow the test procedures below for testing flex connectors protected with galvanic anodes. The following procedures will describe how to obtain potential measurements for a flex connector relative to a copper/copper sulfate reference electrode/cell. The flex connector is considered protected if the potential measurements meet one or more of the criteria described below. Results of these tests must be recorded on the Division’s applicable cathodic protection survey form (CN1140 or CN-1309)." Font "Open Sans" changed to "OpenSans-Bold".Font-size "9.96001" changed to "12".
Text Deleted�
Text
"either"
Text Replaced�
Text
[Old]: "soil or submerged in water within a containment sump. All flex connectors must be tested by either: 1. Obtaining passing local and remote measurements, (PROCEDURE A) or 2. Obtaining passing Instant Off and/or 100 mV shift measurements. (PROCEDURE B)" [New]: "soil, in contact with water, extend outside the walls of the sump, etc. Regardless of the flex connector configuration, follow either Procedure A or B below (as applicable): Prior to testing flex connectors, determine whether each flex connector is electrically isolated or continuous (shorted) with other pieces of metal (dispenser piping, STP piping stub, etc.) using either the point-to-point or fixed-cell/moving ground (remote reference cell placement) method. A more detailed description on how to determine electrical continuity or isolation is provided in the “Corrosion Protection for Flexible (Flex) Connectors and Short Sections of Metal Piping” section of this Technical Chapter and Appendix 2. Document the continuity test results on the applicable continuity survey page of form CN-1140 or CN-1309 (as applicable). After determining whether each flex connector is electrically continuous or isolated, test each flex connector using the following method (as applicable): 1. Obtaining local and remote potential measurements, (PROCEDURE A)* or 2. Obtaining Instant Off potential measurements and/or 100 mV shift measurements. (PROCEDURE B)* *If flex connectors are protected with galvanic anodes and other structures at the facility are protected by an impressed current system, the impressed current system must be turned off prior to testing the flex connectors." Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"DRAFT"
Text Replaced�
Text
[Old]: "-850" [New]: "–850" Font "Open Sans" changed to "OpenSans".Font-size "9.75673" changed to "10.02".
Text Replaced�
Text
[Old]: "to flex connectors directly buried in" [New]: "for testing isolated flex connectors in contact with" Font "Open Sans" changed to "OpenSans".
Text Deleted�
Text
"directly buried"
Text Replaced�
Text
[Old]: "-850" [New]: "–850" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "connector" [New]: "connector**" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "electrode." [New]: "electrode/cell." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "28" [New]: "35" Font "Times New Roman" changed to "OpenSans".Font-size "12" changed to "10.98".
Page 41: Total Changes Content 821 - tn.gov

DRAFT

36

4. Place the reference electrode/cell in the soil immediately adjacent to the flex connector and away from any anodes.

5. Record the voltage observed on the voltmeter as the "local" potential. 6. Place the reference electrode/cell in the soil approximately 25 feet away from the flex

connector and any other cathodically protected structure at the facility and note voltage observed on the voltmeter.

7. Move the reference electrode 10 feet further away, place in the soil and observe the voltage. 8. If the voltage observed in Step 6 is within 10 mV of the voltage observed in Step 7, then it

may be assumed that the reference electrode/cell location in S tep 7 is at “true remote earth”.

9. If the voltages observed in Steps 6 and 7 are not within 10 mV of each other, continue moving the reference electrode/cell until the voltages obtained at two different locations are within 10 mV of each other.

**Test each flex connector individually. Determination of PASS/FAIL Pass = All three potential measurements (one local and two remotes) must be –850 mV or more negative. Fail = One or more of the three potential measurements are less than –850 mV. PROCEDURE B. –850 mV instant off or 100 mV Shift Criterion This procedure is applicable for flex connectors in contact with soil, submerged or partially submerged in water in a containment sump, or in situations as described in Procedure A where passing remote potential measurements cannot be obtained.

1. Set the voltmeter to the 2 volt DC scale. 2. Make contact to each flex connector** with the positive lead of the voltmeter. 3. Connect the negative lead of the voltmeter to the reference electrode/cell. 4. Place the reference electrode/cell in the soil or water (only submerge the ceramic tip)

immediately adjacent to the flex connector. 5. Record the voltage observed on the voltmeter as the on potential. 6. Without moving the reference electrode/cell, disconnect the anode lead wire(s) and record

the instant off potential measurement (Note: All other anodes on any other flex connectors in the same sump must be disconnected when obtaining instant off potential measurements or 100 mV shift data.)

7. If the instant off potential measurement is not –850 mV or more negative, then the anode may remain temporarily disconnected and the flex connector allowed to depolarize in an effort to demonstrate a shift in the potential of 100 mV or greater.

**Test each flex connector individually.

Text Replaced�
Text
[Old]: "electrode" [New]: "electrode/cell" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "connector." [New]: "connector and away from any anodes." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "electrode" [New]: "electrode/cell" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "step" [New]: "Step" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "step" [New]: "Step" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "electrode is at “remote" [New]: "electrode/cell location in Step 7 is at “true remote" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "steps" [New]: "Steps" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "electrode" [New]: "electrode/cell" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"**Test each flex connector individually."
Text Replaced�
Text
[Old]: "must be -850" [New]: "(one local and two remotes) must be –850" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "-850 mV. NOTE: There may be situations when a remote earth reading cannot be obtained. This may occur when the flex connector is in contact with water within a sealed containment sump at a STP or dispenser. Also, certain conditions, such as shielding by metallic or non-metallic skirts or retaining walls at sumps or inaccessibility of soil remotely, may prevent obtaining good remote measurements. As a result, if remote measurements cannot be obtained for whatever reason, then Procedure B -Instant Off and/or 100mV shift must be used." [New]: "–850 mV. PROCEDURE B." Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"DRAFT"
Text Deleted�
Text
"PROCEDURE B."
Text Replaced�
Text
[Old]: "-850" [New]: "–850" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "to" [New]: "for" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "directly buried in soil, or to flex connectors submerged or partially submerged underwater within" [New]: "in contact with soil, submerged or partially submerged in water in" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "above where remote measurements cannot be taken." [New]: "in Procedure A where passing remote potential measurements cannot be obtained." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "the flex connector" [New]: "each flex connector**" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "electrode." [New]: "electrode/cell." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "electrode" [New]: "electrode/cell" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"or water (only submerge the ceramic tip)"
Text Replaced�
Text
[Old]: "electrode," [New]: "electrode/cell," Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"measurement"
Text Inserted�
Text
"other"
Text Replaced�
Text
[Old]: "all flex connectors at" [New]: "any other flex connectors in" Font "Open Sans" changed to "OpenSans-Bold".
Text Replaced�
Text
[Old]: "in order to utilize the -850 mV instant off or 100 mV Shift criteria.) 7. If the instant off potential" [New]: "when obtaining instant off potential measurements or 100 mV shift data.) 7. If the instant off potential measurement" Font "Open Sans" changed to "OpenSans-Bold".
Text Replaced�
Text
[Old]: "-850" [New]: "–850" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"**Test each flex connector individually."
Text Replaced�
Text
[Old]: "29" [New]: "36" Font "Times New Roman" changed to "OpenSans".Font-size "12" changed to "10.98".
Page 42: Total Changes Content 821 - tn.gov

DRAFT

37

Determination of PASS/FAIL: Pass = The instant off potential is -850mV or more negative, OR the shift in the potential is 100 mV or greater. Fail = The instant off potential is less than –850 mV (i.e., more positive than –850 mV), OR the shift in the potential is less than 100 mV. Note: When attempting to demonstrate the 100 mV shift criterion has been met, the ending voltage is subtracted from the instant off voltage. For example: If the instant off voltage is recorded as –730 mV and the ending voltage is recorded as –550 mV, then the potential shift would be 180 mV thus indicating that the flex connector is cathodically protected (i.e., Pass). If the instant off voltage is –735 mV and the ending voltage is -680 mV, then the potential shift would only be 55 mV thus indicating that the flex connector is not cathodically protected (i.e., Fail).

Text Replaced�
Text
[Old]: "more," [New]: "more negative," Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "-850 mV," [New]: "–850 mV (i.e., more positive than –850 mV)," Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "-730" [New]: "–730" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "at -550 mV" [New]: "as –550 mV," Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "and the flex connector would pass the test." [New]: "thus indicating that the flex connector is cathodically protected (i.e., Pass)." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "-735" [New]: "–735" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"potential"
Text Replaced�
Text
[Old]: "and the flex connector would fail the test." [New]: "thus indicating that the flex connector is not cathodically protected (i.e., Fail)." Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"DRAFT"
Page 43: Total Changes Content 821 - tn.gov

DRAFT

38

APPENDIX 5: COMMONLY USED DEFINITIONS

Anode—the part of a corrosion cell where oxidation (corrosion) occurs. Electrons flow away from the anode and carry metal ions.

Cathode—the part of a corrosion cell which is protected by the anode. Reduction is the principal reaction occurring at the cathode. Electrons flow toward the cathode in the corrosion cell.

Cathodic protection—a process that reduces the corrosion rate of a metal surface by making that surface the cathode of a corrosion cell.

Conductivity—the measure of the ability of a material to conduct an electric charge. (Conductivity is the reciprocal of resistivity.)

Continuity bond—a metallic connection that provides electrical continuity between structures.

Corrosion—deterioration of a material, usually a metal, that results from a chemical or electrochemical reaction with its environment.

Current—a flow of electric charge or the amount of electric charge flowing past a specified point per unit of time.

Delamination—separation of layers in a material or separation between one or more coats from another coat within a coating system.

Disbondment—the loss of adhesion between a coating and the substrate.

Discontinuity—a condition in which the electrical path through a structure is interrupted by something that acts as a dielectric or insulating fitting.

Corrosion cell—an electrochemical system consisting of an anode and a cathode in metallic contact and immersed in an electrolyte. This process produces an electrochemical reaction involving oxidation of the anode and reduction of the cathode. The anode and cathode may be different metals or dissimilar areas on the same metal surface.

Electrode—a material that conducts electrons, is used to establish contact with an electrolyte, and through which current is transferred to or from an electrolyte.

Electrode potential—the potential of an electrode in an electrolyte as measured against a reference electrode.

Electromotive series—a list of elements arranged according to their standard electrode potentials.

Galvanic anode—a metal that provides sacrificial protection to another metal that is more noble when electrically coupled in an electrolyte. This type of anode is the electron source in one type of cathodic protection.

Galvanic corrosion—accelerated corrosion of a metal because of an electrical contact with a more noble metal or nonmetallic conductor in a corrosive electrolyte.

General corrosion—corrosion that is distributed more-or-less uniformly over the surface of a material.

Half cell—commonly used in the field to refer to a reference electrode. It may be comprised of a copper rod and a copper sulfate solution commonly used for measuring corrosion of steel with respect to copper. It may also be made of a silver and silver chloride solution for measuring in marine environments.

Holiday—a discontinuity in a protective coating that exposes unprotected surface to the environment.

Text Deleted�
Text
"APPENDIX 5"
Text Inserted�
Text
"APPENDIX 5:"
Text Deleted�
Text
"at"
Text Replaced�
Text
[Old]: "Conductivity— the" [New]: "Conductivity—the" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "Current— a" [New]: "Current—a" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "Delamination— separation" [New]: "Delamination—separation" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "cell — an" [New]: "cell—an" Font "Open Sans,Bold" changed to "OpenSans".
Text Inserted�
Text
"DRAFT"
Text Replaced�
Text
[Old]: "corrosion -corrosion" [New]: "corrosion—corrosion" Font "Open Sans,Bold" changed to "OpenSans".
Text Replaced�
Text
[Old]: "electrode," [New]: "electrode." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "30" [New]: "38" Font "Times New Roman" changed to "OpenSans".Font-size "12" changed to "10.98".
Page 44: Total Changes Content 821 - tn.gov

DRAFT

39

Hydrogen embrittlement—metal degradation caused by the presence of hydrogen within a metal or alloy resulting from the application of too much protective current on the structure being protected.

Impressed current—an electric current supplied by a power source that is external to the electrode system. An example is direct current for cathodic protection.

Impressed current anode—a suitable electrode used in an impressed current system.

Instant-off potential—the polarized half-cell potential of an electrode taken immediately after the cathodic protection current is interrupted, which closely approximates the potential without IR drop (i.e., the polarized potential) when the current was on.

Ion—an electrically charged atom or group of atoms.

IR drop—the voltage across a resistance when current is applied in accordance with Ohm’s law.

Lining—a coating or layer of sheet material adhered to the interior surface of a container used to protect the container against corrosion by its contents and/or to protect the contents of the container from contamination by the container material.

Localized corrosion—corrosion at discrete sites also known as pitting or crevice corrosion.

Negative return—a point of connection between the cathodic protection negative cable and the protected structure.

Ohm's Law—the current through a conductor between two points is directly proportional to the potential difference across the two points. Voltage = current x resistance.

Passivation—the process in metal corrosion by which metals become passive generally by having a coating form on the surface that isolates the metal from the electrolyte.

Pinhole—a minute hole through a coat or coats that exposes an underlying coat or the substrate.

Pit—a surface cavity with depth equal to or greater than the minimum dimension at the opening.

Pitting—localized corrosion of a metal surface that is confined to a small area and takes the form of cavities called pits.

Polarization—the change from the corrosion potential as a result of current flow across the electrode/electrolyte interface.

Polarized potential—the potential across the structure/electrolyte interface that is the sum of the corrosion potential and the cathodic polarization.

Protective coating—a coating applied to a surface to protect the substrate from corrosion.

Reference electrode/cell—an electrode/cell having a stable and reproducible potential, used in the measurement of other electrode potentials.

Remote earth—a location on the earth far enough from the affected structure that the soil potential gradients associated with currents entering the earth from the affected structure are insignificant.

Sacrificial (galvanic) protection—reduction of corrosion of a metal by electrically connecting the metal to a galvanic anode (a form of cathodic protection).

Shielding—preventing the cathodic protection current from reaching its destination or diverting it from its natural path.

Stray current—current flowing through paths other than the intended circuit.

Stray-current corrosion—corrosion resulting from stray current.

Text Replaced�
Text
[Old]: "anode— a" [New]: "anode—a" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "Law -the" [New]: "Law—the" Font "Open Sans,Bold" changed to "OpenSans".
Text Inserted�
Text
"DRAFT"
Text Replaced�
Text
[Old]: "potential— the" [New]: "potential—the" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "electrode—an electrode" [New]: "electrode/cell—an electrode/cell" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "31" [New]: "39" Font "Times New Roman" changed to "OpenSans".Font-size "12" changed to "10.98".
Text Replaced�
Text
[Old]: "anode." [New]: "anode" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "Shielding— preventing" [New]: "Shielding—preventing" Font "Open Sans" changed to "OpenSans".
Page 45: Total Changes Content 821 - tn.gov

DRAFT

40

Structure-to-electrolyte potential—the potential difference between the surface of a buried or submerged metallic structure and the electrolyte that is measured with reference to an electrode in contact with the electrolyte.

Structure-to-soil potential—see structure-to-electrolyte potential.

Structure-to-structure potential—the potential difference between metallic structures, or sections of the same structure, in a common electrolyte.

Uniform corrosion—corrosion that proceeds at exactly the same rate over the surface of a material.

Text Inserted�
Text
"DRAFT"
Text Deleted�
Text
"32"
Page 46: Total Changes Content 821 - tn.gov

DRAFT

41

APPENDIX 6: IMPRESSED CURRENT CATHODIC PROTECTION TESTING SURVEY

(Modifications are made to these forms from time to time. Please check the Division’s website for the most current version of the State’s official form)

Text Replaced�
Text
[Old]: "6" [New]: "6:" Font "Open Sans,Bold" changed to "OpenSans-Bold".
Text Inserted�
Text
"DRAFT"
Page 47: Total Changes Content 821 - tn.gov

DRAFT

DRAFT

DEPARTMENT OF ENVIRONMENT AND CONSERVATION DIVISION OF UNDERGROUND STORAGE TANKS

William R Snodgrass Tennessee Tower 312 Rosa L. Parks Avenue, 12th Floor

Nashville, TN 37243 IMPRESSED CURRENT CATHODIC PROTECTION TESTING SURVEY

Utilize this form to evaluate underground storage tank (UST) impressed current cathodic protection systems in the State of Tennessee. Access to the soil directly over the cathodically protected structure that is being evaluated is required.

I. UST FACILITY II. UST OWNERNAME: NAME:

FACILITY ID NUMBER: COMPANY:

ADDRESS: ADDRESS:

CITY: COUNTY: CITY: STATE: III. CP TESTER

TESTER’S NAME: COMPANY:

ADDRESS: LIST CERTIFICATION, IF ANY:

CITY: STATE: PHONE NUMBER:

IV. REASON SURVEY WAS CONDUCTED (mark only one)

□ Routine – 3 year □ Routine – within 6 months of installation □ Re-survey after fail/repair/modification

(required every 3 years).Date next cathodic protection survey must be conducted by: _______________________

V. CATHODIC PROTECTION TESTER’S EVALUATION (mark only one)

□ PASS All protected structures at this facility pass the cathodic protection survey and it is judged that adequate cathodic protection has been provided to the UST system (indicate all applicable criteria by completion of Section VII).

□ FAIL One or more components did not pass the cathodic protection survey.

□ INCONCLUSIVE The cathodic protection survey must be evaluated by a corrosion expert if it cannot be determined that the protectedstructures are continuous, or other factors may result in high readings, etc. (complete Section VI).

CP TESTER’S SIGNATURE: ________________________________________________ DATE CP SURVEY PERFORMED: ________________________________

VI. CORROSION EXPERT’S EVALUATION (mark only one)The survey must be conducted and/or evaluated by a corrosion expert when: a) replacement or addition of anodes, or other changes in the construction or design ofthe impressed current system are made (see also the Repairs section of the Impressed Current portion of Technical Chapter 4.1 “Corrosion Protection –Standardized Inspection Manual”); b) stray current may be affecting buried metallic structures; or c) an inconclusive result was indicated in Section V.

□ PASS (based on above criteria) □ FAIL (based on above criteria)

CORROSION EXPERT’S NAME: COMPANY NAME:

NACE INTERNATIONAL CERTIFICATION NUMBER:

CORROSION EXPERT’S SIGNATURE: _________________________________________________ DATE: _____________________________________

VII. CRITERIA APPLICABLE TO EVALUATION (mark all that apply)

□ 850 OFF Structure-to-soil potential measurements are–850 mV or more negative with respect to a Cu/CuSO4 reference electrode with protective current temporarily interrupted (instant-off).

□ Continuity Structure(s) listed in Section XIV that are to be protected by the impressed current system are continuous with the rectifier negative.

□ 100 mV Shift Structure(s) tested exhibit a shift of at least 100 mV of cathodic polarization.

VIII. ACTION REQUIRED AS A RESULT OF THIS EVALUATION (mark only one)

□ NONE Cathodic protection is adequate. No further action is necessary at this time. Test again no later than the date specified in Section IV.

□ RETEST Cathodic protection may not be adequate. Retest to determine if passing results can be achieved.

□ REPAIR &RETEST Cathodic protection is not adequate. Repair/modification is necessary as soon as practical.

CN-1304 1 RDA-2304

Text Replaced�
Text
[Old]: "This form must be utilized" [New]: "Utilize this form" Font "Times New Roman,Bold" changed to "TimesNewRomanPS-BoldMT".Font-size "8.03999" changed to "8.52".
Text Inserted�
Text
"impressed current"
Text Replaced�
Text
[Old]: "must be provided." [New]: "is required." Font "Times New Roman,Bold" changed to "TimesNewRomanPS-BoldMT".Font-size "8.03999" changed to "8.52".
Text Inserted�
Text
"DRAFT"
Text Inserted�
Text
"3 year □Routine –"
Text Replaced�
Text
[Old]: "□ Re-survey after fail □ Re-survey after repair/modification □ Routine -3 year Date next cathodic protection survey must be conducted by: __________________________ (required within 6 months of installation/repair, or" [New]: "□Re-survey after fail/repair/modification Date next cathodic protection survey must be conducted by: _______________________ (required" Font "Arial,Bold" changed to "Arial-BoldMT".
Text Replaced�
Text
[Old]: "All protected structures at this facility pass the cathodic protection survey and it is judged that adequate cathodic protection has been provided to the UST system (indicate all applicable criteria by completion of Section VII)." [New]: "A pr ll otec protec tion has ted str be uc en pr tures ov at thi ided to th s facil e US ity pas T s sy the c stem ath (indi odi c c ate al protec l appl tion s ica ur bl v e c ey r and i iteria by t is ju com dged that ad pletion of S equ ec ate c tion V athodi II). c" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "The cathodic protection survey must be evaluated by a corrosion expert for such reasons as it cannot be determined that the protected structures are continuous, or other factors may result in high readings, etc. (complete Section VI)." [New]: "T str he c uctur athodi es ar c e c pro o tec ntinuous tion sur , or vey othe mus r fac t be ev tors al m uated ay res by ult i a c n hi or gh r ros eadi ion ex ngs per , etc t if . ( it c com annot b plete S e deter ection V mined th I). at the protected" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "supplemental anodes" [New]: "replacement or addition of anodes," Font "Arial" changed to "ArialMT".
Text Inserted�
Text
"or design"
Text Replaced�
Text
[Old]: "made;" [New]: "made (see also the Repairs section of the Impressed Current portion of Technical Chapter 4.1 “Corrosion Protection – Standardized Inspection Manual”);" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "_________________________________________________________" [New]: "_________________________________________________" Font "Arial,Bold" changed to "Arial-BoldMT".
Text Inserted�
Text
"□ □ □"
Text Replaced�
Text
[Old]: "more negative than –850 mV" [New]: "measurements are–850 mV or more negative" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "□ 100 mV Polarization Structure(s) tested exhibit" [New]: "Continuity Structure(s) listed in Section XIV that are to be protected by the impressed current system are continuous with the rectifier negative. 100 mV Shift Structure(s) tested exhibit a shift of" Font "Arial" changed to "Arial-BoldMT".Font-size "20.04" changed to "9".
Text Deleted�
Text
"by"
Text Deleted�
Text
"CN 1309 RDA 2304"
Text Deleted�
Text
"34"
Page 48: Total Changes Content 821 - tn.gov

DRAFT

DRAFT

IX. DESCRIPTION OF UST SYSTEMFACILITY NAME: FACILITY ID NUMBER:

TANK # PRODUCT CAPACITY TANK MATERIAL

PIPING MATERIAL

FLEX CONNECTORS (Y / N). IF YES, INDICATE LOCATION (STP / DISP / STP AND DISP)

1 2 3 4 5 6 7

If metal flex connectors are present, are they corrosion protected?

□ YES Method:□ Isolation (booted) □ Isolation (not in contact with the ground)□ Attached Anode1 (provided details in comments)

□ NO Action taken: ______________________________________________________________________________________________________________________________________________________________

Comments (e.g., piping brand, specific flex/anode locations, etc.):

1If the flex connectors are protected by sacrificial anodes, test accordingly and include in Section XVI on this form.

X. IMPRESSED CURRENT RECTIFIER DATA (complete all applicable)To conduct an effective evaluation of the cathodic protection system, a complete evaluation of rectifier operation is necessary.

RECTIFIER MANUFACTURER: RATED DC OUTPUT: AMPS VOLTS ______________ _______________

RECTIFIER MODEL: RECTIFIER SERIAL NUMBER:

RECTIFIER OUTPUT AS INITIALLY DESIGNED OR LAST MEASURED (if available): AMPS VOLTS_____________ ________________

EVENT DATE TAP SETTINGS DC OUTPUT

(as indicated on the rectifier meter)

DC OUTPUT (MEASURED using

a voltmeter) HOUR

METER COMMENTS

COARSE FINE VOLTS AMPS VOLTS AMPS

“AS FOUND”

“AS LEFT”

Check all that apply: □ single amp/voltmeter □ dual amp/voltmeter □ red/green indicator light

XI. IMPRESSED CURRENT POSITIVE CIRCUIT MEASUREMENTS (output amperage)

Complete if system design allows such measurements (i.e. individual lead wires for each anode are installed and measurement shunts are present).

CIRCUIT 1 2 3 4 5 6 7 8 8 10 TOTAL (AMPS)

ANODE (+)

XII. DESCRIPTION OF CATHODIC PROTECTION SYSTEM REPAIRS AND/OR MODIFICATION Complete if repairs or modifications to the cathodic protection system are made or are necessary. Certain repairs/modifications as explained in Technical Chapter

4.1 Corrosion Protection, are required to be designed and/or evaluated by a corrosion expert (completion of Section VI required). Attach corrosion expert’s calculations and have corrosion expert sign Section VI.

□ Replacement or addition of anodes for an impressed current system (attach corrosion expert’s design).

□ Repairs or replacement of rectifer (explain in Remarks/Other below).

□ Anode header cables repaired and/or replaced (explain in Remarks/Other below).

□ Impressed current protected tanks/piping not electrically continuous (explain in Remarks/Other below).Remarks/ Other______________________________________________________________________________________________________________________

CN-1304 2 RDA-2304

Text Deleted�
Text
"MATERIAL PIPING MATERIAL"
Text Inserted�
Text
"(Y / N). IF YES, INDICATE LOCATION (STP / DISP / STP AND DISP) MATERIAL MATERIAL"
Text Inserted�
Text
"DRAFT"
Text Replaced�
Text
[Old]: "8 9 10 □ YES Method: □ Isolation (booted) □ Attached Anode 1 □ Isolation (contained in sump or no soil contact) If metal flex connectors are present, are they corrosion protected? □ NO Action taken: ___________________________________________________________________________" [New]: "□Isolation (booted) □Attached Anode 1 (provided details in comments) □Isolation (not in contact with the ground) □ YES Method: If metal flex connectors are present, are they corrosion □ NO Action taken: ____________________________________________________________________ protected?" Font "Arial,Bold" changed to "Arial-BoldMT".Font-size "12" changed to "19.98".
Text Inserted�
Text
"__________________________________________________________________________________________"
Text Inserted�
Text
"Comments (e.g., piping brand, specific flex/anode locations, etc.):"
Text Replaced�
Text
[Old]: "In order to" [New]: "To" Font "Arial" changed to "ArialMT".
Text Deleted�
Text
"RECTIFIER MANUFACTURER:"
Text Inserted�
Text
"RECTIFIER MANUFACTURER:"
Text Replaced�
Text
[Old]: "MEASURED" [New]: "DC OUTPUT" Font "Arial,Bold" changed to "Arial-BoldMT".Font-size "6.96001" changed to "7.5".
Text Deleted�
Text
"EVENT DATE TAP SETTINGS"
Text Inserted�
Text
"(as indicated on (MEASURED using"
Text Inserted�
Text
"TAP SETTINGS"
Text Inserted�
Text
"EVENT DATE"
Text Inserted�
Text
"the rectifier meter) a voltmeter)"
Text Inserted�
Text
"VOLTS AMPS"
Text Inserted�
Text
"(AMPS)"
Text Deleted�
Text
"the text of the Standardized Compliance inspection Manual,"
Text Deleted�
Text
"diagram and"
Text Replaced�
Text
[Old]: "Additional" [New]: "Replacement or addition of" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "tanks/ piping" [New]: "tanks/piping" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "Other________________________________________________________________________________________________________________________" [New]: "Other______________________________________________________________________________________________________________________" Font "Arial" changed to "ArialMT".
Text Deleted�
Text
"_____________________________________________________________________________________________________________________________ ___"
Text Replaced�
Text
[Old]: "35" [New]: "2 RDA-2304 CN-1304" Font "Times New Roman" changed to "Arial".Font-size "12" changed to "9".
Page 49: Total Changes Content 821 - tn.gov

DRAFT

DRAFT

XIII. UST FACILITY SITE DRAWINGAttach detailed legible drawing or use the space provided to draw a sketch of the UST and cathodic protection systems. Sufficient detail must be given to clearly indicate where the reference electrode was placed for each structure-to-soil potential that is recorded on the survey forms. Include details such as the location of all tanks, piping, and dispensers; buildings and streets; anodes and wires; and the rectifier. Each CP test (reference electrode placement) location must be indicated by a code (1,2, T-1, D-1, etc.) corresponding with the appropriate line number in Section XV. of this form.

AN EVALUATION OF THE CATHODIC PROTECTION SYSTEM IS NOT COMPLETE WITHOUT AN ACCEPTABLE SITE DRAWING.

CN-1304 3 RDA-2304

Text Deleted�
Text
"in order"
Text Replaced�
Text
[Old]: "as:" [New]: "as the location of" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "location of" [New]: "the" Font "Arial" changed to "ArialMT".
Text Inserted�
Text
"DRAFT"
Text Deleted�
Text
"36"
Page 50: Total Changes Content 821 - tn.gov

DRAFT

DRAFT

XIV. IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM CONTINUITY SURVEY (Perform Tasks in Section XVbefore completing tasks in this section)

This section will be utilized to record measurements of continuity on UST systems that are protected by impressed current cathodic protectionsystems.

Conduct point-to-point test between the disconnected rectifier negative cable and all other structures. For impressed current systems, each protected structure must be continuous with the disconnected rectifier negative cable to pass the continuity

survey.

FACILITY NAME: FACILITY ID NUMBER:

STRUCTURE “A”1 STRUCTURE “B”2 POINT-TO-

POINT3

VOLTAGE DIFFERENCE

ISOLATED /

CONTINUOUS / INCONCLUSIVE4

(example)

RECTIFIER NEGATIVE CABLE (example)

PLUS STEEL PROD LINE @ STP (example) 11 mV

(example) ISOLATED

(example)

RECTIFIER NEGATIVE CABLE (example)

PLUS STEEL TANK BOTTOM (example) 0 mV

(example) CONTINUOUS

(example)

RECTIFIER NEGATIVE CABLE (example)

PLUS TANK STP (example) 6 mV

(example) INCONCLUSIVE

(example)

RECTIFIER NEGATIVE CABLE (example)

REGULAR TANK TOP (example) 4 mV

(example) CONTINUOUS

COMMENTS: ______________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________

1 Structure “A” should always be the rectifier negative cable after disconnecting from the rectifier (unless you are documenting continuity of flex connectors protected by galvanic anodes).

2 Describe the “other” protected structure “B” that you are attempting to demonstrate is continuous (e.g. plus steel product line @ STP, plus tank bottom, plus tank STP, etc.).

3 Record the voltage difference observed between structure “A” and structure “B” when conducting “point-to-point” testing (e.g. 1 mV). 4 Document whether the test indicated the protected structure was continuous (1 - 5 mV), inconclusive ( 6 - 9 mV), or isolated ( > 10 mV).

CN-1304 4 RDA-2304

Text Deleted�
Text
"XIV. IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM CONTINUITY SURVEY"
Text Replaced�
Text
[Old]: "• This section will be utilized to conduct measurements of continuity on UST systems that are protected by" [New]: "XIV. IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM CONTINUITY SURVEY (Perform Tasks in Section XV before completing tasks in this section) • This section will be utilized to record measurements of continuity on UST systems that are protected by impressed current" Font "Wingdings" changed to "Arial-BoldMT".Font-size "7.56" changed to "10.02".
Text Replaced�
Text
[Old]: "the" [New]: "each" Font "Arial" changed to "ArialMT".Font-size "7.56" changed to "7.98".
Text Replaced�
Text
[Old]: "all other protected structures in order" [New]: "the disconnected rectifier negative cable" Font "Arial" changed to "ArialMT".Font-size "7.56" changed to "7.98".
Text Replaced�
Text
[Old]: "POINT-TO-POINT 3 ISOLATED/ CONTINUOUS/" [New]: "POINT-TO- POINT 3 VOLTAGE ISOLATED / CONTINUOUS /" Font "Arial,Bold" changed to "Arial-BoldMT".
Text Deleted�
Text
"VOLTAGE"
Text Deleted�
Text
"ISOLATED"
Text Inserted�
Text
"ISOLATED"
Text Inserted�
Text
"DRAFT"
Text Inserted�
Text
"(example) (example) (example) (example) CONTINUOUS RECTIFIER NEGATIVE CABLE REGULAR TANK TOP 4 mV"
Text Inserted�
Text
"__________________________________________________________________________________________"
Text Deleted�
Text
"2 3 4"
Text Replaced�
Text
[Old]: "Rectifier" [New]: "rectifier" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "rectifier." [New]: "rectifier (unless you are documenting continuity of flex connectors protected by galvanic anodes). 2" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "etc)." [New]: "etc.). 3" Font "Arial" changed to "ArialMT".
Text Inserted�
Text
"4"
Text Replaced�
Text
[Old]: "37" [New]: "4 RDA-2304 CN-1304" Font "Times New Roman" changed to "Arial".Font-size "12" changed to "9".
Page 51: Total Changes Content 821 - tn.gov

DRAFT

DRAFT

XV. IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM SURVEY This section will be utilized to record structure-to-soil potential measurements obtained from a survey of the impressed current cathodic protection system. The reference electrode must be placed in soil directly over the tested structure and as far away from active anodes as practical to obtain a valid structure-to-soil potential. Both on and instant off potentials must be measured for each structure that is required to be cathodically protected. All instant off potentials must be -850 mV or more negative or the 100 mV shift criterion must be satisfied to pass. Collect at least three potential readings over each tank, one reading at each end of every piping run, and one reading at the midpoint of product lines over 100 feet in length.

FACILITY NAME: FACILITY ID NUMBER:

LOCATION CODE1 STRUCTURE2 CONTACT POINT3

REFERENCE CELL PLACEMENT4 ON VOLTAGE5

INSTANT OFF

VOLTAGE6

100 mV SHIFT PASS / FAIL9 ENDING

VOLTAGE7VOLTAGE CHANGE8

(example) 1

(example) PLUS TANK

(example) TANK

BOTTOM

(example) SOIL @ PLUS TANK STP

(example) -1070 mV

(example) -875 mV

(example) PASS

(example) 2

(example) PLUS PIPING

(example) PLUS PIPING @ DISP 5/6

(example) SOIL UNDER DISP 5/6

(example) -810 mV

(example) -680 mV

(example) -575 mV

(example) 105 mV

(example) PASS

COMMENTS: ________________________________________________________________________________ _________________________________________________________________________________________

1 Designate numerically or by code on the site drawing each “local” reference electrode placement (e.g. 1, 2, 3… T-1, T-2, P-1, P-2…etc.). 2 Describe the structure that is being tested (e.g. plus tank; diesel piping; flex connector; etc.). 3 Describe where the structure being tested is contacted by the test lead (e.g. plus tank bottom, diesel piping @ dispenser 7/8, etc.). 4 Describe exact location where reference electrode is placed for each measurement (e.g., soil @ regular tank STP, soil @ dispenser 5/6, etc.) 5 Record the structure-to-soil potential observed with the current applied (e.g. –1070 mV). 6 Record the structure-to-soil potential observed when the current is interrupted (e.g., –875 mV). 7 (Applies to 100 mV shift only) Record the voltage observed at the end of the test period (e.g., –575 mV) 8 (Applies to 100 mV shift only) Subtract the instant off voltage from the ending voltage (e.g., –575 mV – [–680 mV] = 105 mV change) 9 Indicate if the tested structure passed or failed one of the two acceptable criteria (more negative than –850 mV instant-off or greater than 100 mV shift

criteria).

CN-1304 5 RDA-2304

Text Deleted�
Text
"XV. IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM SURVEY"
Text Replaced�
Text
[Old]: "• This section will be utilized to conduct a survey of an impressed current cathodic protection system by obtaining structure-to-soil potential measurements." [New]: "XV. IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM SURVEY • This section will be utilized to record structure-to-soil potential measurements obtained from a survey of the impressed current cathodic protection system." Font "Wingdings" changed to "Arial-BoldMT".Font-size "6.96001" changed to "10.02".
Text Replaced�
Text
[Old]: "intended" [New]: "required" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "under cathodic protection." [New]: "cathodically protected." Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "polarization" [New]: "shift" Font "Arial" changed to "ArialMT".
Text Deleted�
Text
"in order"
Text Replaced�
Text
[Old]: "At least three readings shall be recorded" [New]: "Collect at least three potential readings" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "dispenser, and mid points of steel product lines more than" [New]: "end of every piping run, and one reading at the midpoint of product lines over" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "POLARIZATION" [New]: "SHIFT CONTACT POINT 3" Font "Arial,Bold" changed to "Arial-BoldMT".
Text Inserted�
Text
"REFERENCE CELL PLACEMENT"
Text Replaced�
Text
[Old]: "ON PASS / LOCATION CODE 1 STRUCTURE 2 CONTACT POINT 3" [New]: "4 STRUCTURE 2 ON VOLTAGE 5 PASS / FAIL 9 LOCATION CODE 1" Font "Arial,Bold" changed to "Arial-BoldMT".Font-size "6.48" changed to "6".
Text Deleted�
Text
"REFERENCE CELL PLACEMENT"
Text Replaced�
Text
[Old]: "4 OFF 5 ENDING FAIL 9 7 VOLTAGE 8 VOLTAGE 6 VOLTAGE VOLTAGE CHANGE" [New]: "OFF ENDING VOLTAGE VOLTAGE 6 VOLTAGE 7 CHANGE 8" Font "Arial,Bold" changed to "Arial-BoldMT".Font-size "6" changed to "6.48".
Text Deleted�
Text
"1 PLUS TANK TANK"
Text Replaced�
Text
[Old]: "REG." [New]: "PLUS" Font "Comic Sans MS,Bold" changed to "ComicSansMS".
Text Inserted�
Text
"1 PLUS TANK"
Text Replaced�
Text
[Old]: "2 PLUS DISPENSER 5/6 UNDER DISPENSER" [New]: "PLUS PIPING PASS 2 PLUS PIPING SOIL UNDER DISP" Font "Comic Sans MS,Bold" changed to "ComicSansMS".
Text Replaced�
Text
[Old]: "PASS" [New]: "@ DISP 5/6" Font "Comic Sans MS,Bold" changed to "ComicSansMS".Font-size "8.03999" changed to "8.52".
Text Inserted�
Text
"DRAFT"
Text Replaced�
Text
[Old]: "etc)." [New]: "etc.)." Font "Arial" changed to "ArialMT".
Text Deleted�
Text
"6 7 8"
Text Inserted�
Text
"6"
Text Replaced�
Text
[Old]: "with" [New]: "when" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "-875 mV)." [New]: "–875 mV). 7" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "polarization" [New]: "shift" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "-575 mV)" [New]: "–575 mV) 8" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "polarization" [New]: "shift" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "-575" [New]: "–575" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "[-680" [New]: "[–680" Font "Arial" changed to "ArialMT".
Text Inserted�
Text
"9"
Text Replaced�
Text
[Old]: "(<-850 mV instant off or >100 mV polarization). 9" [New]: "(more negative than –850 mV instant-off or greater than 100 mV shift criteria)." Font "Arial" changed to "ArialMT".
Text Deleted�
Text
"38"
Page 52: Total Changes Content 821 - tn.gov

DRAFT

DRAFT

XVI. FLEXIBLE CONNECTORS (OR OTHER SHORT SECTIONS OF METAL PIPING) CATHODIC PROTECTION SYSTEM SURVEY This form will be utilized to record structure-to-soil potential measurements for galvanically protected flex connectors (or short piping sections). A total of three (3) potential measurements (one local and two at remote earth to determine True Remote Earth) is required for each flex connector when using the “On” / ”Local Voltage” (-850

mV) criteria. Record the True Remote Earth Voltage on the form below. If either the local or the remote potential measurements fail (more positive than -850 mV), use the instant off or 100 mV shift criteria to determine protective status (i.e. Pass / Fail). The instant

off or 100 mV shift measurements are obtained after disconnecting the anode from the flex connector. See also Appendix 4 of Technical Chapter 4.1, Corrosion Protection. Potential measurements must be obtained for each flex connector.

FACILITY NAME: FACILITY ID NUMBER: Location of Remote Reference Cell Placement, if Applicable (also designate on site drawing):

TANK #, PRODUCT, CAPACITY1 FLEX LOCATION2

WHERE IS ANODE

ATTACHED?

CONTINUOUS OR ISOLATED? 3 (must also

complete Section XIV) CONTACT POINT4 LOCAL

VOLTAGE5

TRUE REMOTE EARTH

VOLTAGE6

INSTANT OFF

VOLTAGE (if necessary)

100 mV SHIFT

PASS/FAIL7 ENDING VOLTAGE

(if necessary) VOLTAGE CHANGE

E X A M P L E S

#2 DIESEL 8,000 DIESEL FLEX AT

STP ON FLEX ISO. ON FLEX -875 mV -760 mV -860 mV PASS

#3 REGULAR 10,000

REG. FLEX AT DISPENSER 3/4

PIPING ABOVE SHEAR VALVE

CONT. PIPING ABOVE SHEAR VALVE -980 mV -845 mV -790 mV 55 mV FAIL

#4 PREMIUM 10,000

PREM. STP FLEX IN CONTAINED

SUMP STP HEAD CONT. STP HEAD -910 mV PASS

COMMENTS:__________________________________________________________________________________________________________________________________________________

______________________________________________________________________________________________________________________________________________________________

1 Designate the number, product, and capacity of the tank with which the flex connector is associated. 2 Indicate location of flex being tested (e.g. REGULAR FLEX AT DISPENSER 3/4, DIESEL FLEX AT STP, etc.) 3 Continuity or isolation of flex connectors must be documented in the Continuity Survey section (XIV) before completion of this section to determine whether to use remote voltage or instant

off/100 mV shift. If testing flex connectors only, include Continuity Survey section (XIV) of this form with this section. 4 Designate exact point of contact when testing flex (i.e., if isolated, must contact only the flex itself. If continuous with another component, can contact either one). 5 Record the structure-to-soil potential measurement for “Local Voltage” in millivolts (e.g. –875 mV, -980 mV, etc.). 6 Record the structure-to-soil potential measurement for “True Remote Earth Voltage” in millivolts. 7 Indicate whether the tested structure passed or failed based on your interpretation of the test data.

CN-1304 6 RDA-2304

Text Replaced�
Text
[Old]: "CONNECTOR CATHODIC PROTECTION SYSTEM" [New]: "CONNECTORS (OR OTHER SHORT SECTIONS OF METAL PIPING) CATHODIC PROTECTION SYSTEM SURVEY" Font "Arial,Bold" changed to "Arial-BoldMT".
Text Replaced�
Text
[Old]: "conduct a survey of galvanic protected flexible connectors by obtaining structure-to-soil potential measurements. • A minimum of one measurement must be made with the reference electrode placed in soil directly over the tested structure (local) and one measurement at a remote earth location, at least 25-100 feet away from the structure. • Flex connectors in contained sumps or continuous with dispenser cabinets or STPs must use instant off or voltage change (100 mV shift) to determine protected status. • If either local or remote reading is more positive than -850 mV, obtain instant off by disconnecting anode. If instant off is more positive than -850 mV, then conduct" [New]: "record structure-to-soil potential measurements for galvanically protected flex connectors (or short piping sections). • A total of three (3) potential measurements (one local and two at remote earth to determine True Remote Earth) is required for each flex connector when using the “On” / ”Local Voltage” (-850 mV) criteria. Record the True Remote Earth Voltage on the form below. • If either the local or the remote potential measurements fail (more positive than -850 mV), use the instant off or 100 mV shift criteria to determine protective status (i.e. Pass / Fail). The instant off or 100 mV shift measurements are obtained after disconnecting the anode from the flex connector. • See also Appendix 4 of Technical Chapter 4.1, Corrosion Protection. • Potential measurements must be obtained for each flex connector. FACILITY NAME: FACILITY ID NUMBER: Location of Remote Reference Cell Placement, if Applicable (also designate on site drawing):" Font "Arial" changed to "ArialMT".Font-size "6.48" changed to "7.98".
Text Inserted�
Text
"______________________________________________________________________________________________________________________________________________________________ DRAFT"
Text Replaced�
Text
[Old]: "polarization and" [New]: "SHIFT TRUE INSTANT WHERE IS CONTINUOUS OR ISOLATED? 3 (must also complete Section XIV) TANK #, PRODUCT, CAPACITY 1 LOCAL REMOTE OFF ENDING FLEX LOCATION 2 CONTACT POINT 4 PASS/FAIL 7 VOLTAGE CHANGE ANODE VOLTAGE VOLTAGE 5 EARTH VOLTAGE ATTACHED? VOLTAGE 6 (if necessary) (if necessary) DIESEL FLEX AT ON FLEX ISO. ON FLEX -875 mV -760 mV -860 mV PASS E X #2 DIESEL 8,000 STP PIPING A M #3 REGULAR REG. FLEX AT ABOVE PIPING ABOVE SHEAR VALVE CONT. -980 mV 845 mV -790 mV 55 mV FAIL - 10,000 DISPENSER 3/4 SHEAR P VALVE L PREM. STP FLEX E #4 PREMIUM IN CONTAINED STP HEAD CONT. STP HEAD -910 mV PASS S 10,000 SUMP COMMENTS:__________________________________________________________________________________________________________________________________________________ 1 Designate the number, product, and capacity of the tank with which the flex connector is associated. 2 Indicate location of flex being tested (e.g. REGULAR FLEX AT DISPENSER 3/4, DIESEL FLEX AT STP, etc.) 3 Continuity or isolation of flex connectors must be documented in the Continuity Survey section (XIV) before completion of this section to determine whether to use remote voltage or instant off/100 mV shift. If testing flex connectors only, include Continuity Survey section (XIV) of this form with this section. 4 Designate exact point of contact when testing flex (i.e., if isolated, must contact only the flex itself. If continuous with another component, can contact either one). 5 Record the structure-to-soil potential measurement for “Local Voltage” in millivolts (e.g. –875 mV, -980 mV, etc.). 6 Record the structure-to-soil potential measurement for “True Remote Earth Voltage” in millivolts. 7 Indicate whether the tested structure passed or failed based on your interpretation of the test data." Font "Arial" changed to "Arial-BoldMT".Font-size "6.48" changed to "7.02".
Text Inserted�
Text
"6 RDA-2304 CN-1304"
Page 53: Total Changes Content 821 - tn.gov

DRAFT

DRAFT

XVI. FLEXIBLE CONNECTORS (OR OTHER SHORT SECTIONS OF METAL PIPING) CATHODIC PROTECTION SYSTEM SURVEY (CONTINUTED) This form will be utilized to record structure-to-soil potential measurements for galvanically protected flex connectors (or short piping sections). A total of three (3) potential measurements (one local and two at remote earth to determine True Remote Earth) is required for each flex connector when using the “On” / “Local Voltage” (-850

mV) criteria. Record the True Remote Earth Voltage on the form below. If either the local or the remote potential measurements fail (more positive than -850 mV), use the instant off or 100 mV shift criteria to determine protective status (i.e. Pass / Fail). The instant

off or 100 mV shift measurements are obtained after disconnecting the anode from the flex connector. See also Appendix 4 of Technical Chapter 4.1, Corrosion Protection. Potential measurements must be obtained for each flex connector.

FACILITY NAME: FACILITY ID NUMBER: Location of Remote Reference Cell Placement, if Applicable (also designate on site drawing):

TANK #, PRODUCT, CAPACITY1 FLEX LOCATION2

WHERE IS ANODE

ATTACHED?

CONTINUOUS OR ISOLATED? 3 (must also

complete Section XIV) CONTACT POINT4 LOCAL

VOLTAGE5

TRUE REMOTE EARTH

VOLTAGE6

INSTANT OFF

VOLTAGE (if necessary)

100 mV SHIFT

PASS/FAIL7 ENDING VOLTAGE

(if necessary) VOLTAGE CHANGE

E X A M P L E S

#2 DIESEL 8,000 DIESEL FLEX AT

STP ON FLEX ISO. ON FLEX -875 mV -760 mV -860 mV PASS

#3 REGULAR 10,000

REG. FLEX AT DISPENSER 3/4

PIPING ABOVE SHEAR VALVE

CONT. PIPING ABOVE SHEAR VALVE -980 mV -845 mV -790 mV 55 mV FAIL

#4 PREMIUM 10,000

PREM. STP FLEX IN CONTAINED

SUMP STP HEAD CONT. STP HEAD -910 mV PASS

COMMENTS:__________________________________________________________________________________________________________________________________________________

______________________________________________________________________________________________________________________________________________________________

1 Designate the number, product, and capacity of the tank with which the flex connector is associated. 2 Indicate location of flex being tested (e.g. REGULAR FLEX AT DISPENSER 3/4, DIESEL FLEX AT STP, etc.) 3 Continuity or isolation of flex connectors must be documented in the Continuity Survey section (XIV) before completion of this section to determine whether to use remote voltage or instant

off/100 mV shift. If testing flex connectors only, include Continuity Survey section (XIV) of this form with this section. 4 Designate exact point of contact when testing flex (i.e., if isolated, must contact only the flex itself. If continuous with another component, can contact either one). 5 Record the structure-to-soil potential measurement for “Local Voltage” in millivolts (e.g. –875 mV, -980 mV, etc.). 6 Record the structure-to-soil potential measurement for “True Remote Earth Voltage” in millivolts. 7 Indicate whether the tested structure passed or failed based on your interpretation of the test data.

CN-1304 7 RDA-2304

Text Replaced�
Text
[Old]: "record ending voltage. If difference between instant off and ending voltage is more than 100 mV, the result is PASS. If difference is less than 100 mV, or either local or remote reading is more positive than -850 mV, then structure is not protected and the result is FAIL." [New]: "XVI. FLEXIBLE CONNECTORS (OR OTHER SHORT SECTIONS OF METAL PIPING) CATHODIC PROTECTION SYSTEM SURVEY (CONTINUTED) • This form will be utilized to record structure-to-soil potential measurements for galvanically protected flex connectors (or short piping sections). • A total of three (3) potential measurements (one local and two at remote earth to determine True Remote Earth) is required for each flex connector when using the “On” / “Local Voltage” (-850 mV) criteria. Record the True Remote Earth Voltage on the form below. • If either the local or the remote potential measurements fail (more positive than -850 mV), use the instant off or 100 mV shift criteria to determine protective status (i.e. Pass / Fail). The instant off or 100 mV shift measurements are obtained after disconnecting the anode from the flex connector. • See also Appendix 4 of Technical Chapter 4.1, Corrosion Protection. • Potential measurements must be obtained for each flex connector." Font "Arial" changed to "Arial-BoldMT".Font-size "6.48" changed to "10.02".
Text Inserted�
Text
"______________________________________________________________________________________________________________________________________________________________ DRAFT"
Text Deleted�
Text
"INSTANT"
Text Replaced�
Text
[Old]: "POLARIZATION WHERE CONTINUOUS OFF TANK #, PRODUCT, CAPACITY 1 FLEX LOCAL REMOTE ENDING CONTACT POINT 4 PASS/FAIL 7 ANODE OR VOLTAGE VOLTAGE LOCATION 2 VOLTAGE 5 VOLTAGE 6 VOLTAGE ISOLATED? 3 ATTACHED? (if necessary) CHANGE" [New]: "SHIFT TRUE INSTANT WHERE IS CONTINUOUS OR ISOLATED? 3 (must also complete Section XIV) TANK #, PRODUCT, CAPACITY 1 LOCAL REMOTE OFF ENDING FLEX LOCATION 2 CONTACT POINT 4 PASS/FAIL 7 VOLTAGE CHANGE ANODE VOLTAGE VOLTAGE 5 EARTH VOLTAGE ATTACHED? VOLTAGE 6 (if necessary)" Font "Arial,Bold" changed to "Arial-BoldMT".
Text Inserted�
Text
"X"
Text Replaced�
Text
[Old]: "X A PIPING" [New]: "PIPING A M #3 REGULAR" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "M #3 REGULAR 10,000 CONT. -980 mV -845" [New]: "VALVE CONT. -980 mV 845" Font "Arial" changed to "ArialMT".
Text Inserted�
Text
"- 10,000"
Text Deleted�
Text
"VALVE"
Text Replaced�
Text
[Old]: "E PREM. FLEX IN" [New]: "PREM. STP FLEX E" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "10,000" [New]: "IN" Font "Arial" changed to "ArialMT".
Text Inserted�
Text
"10,000"
Text Deleted�
Text
"______________________________________________________________________________________________________________________________________________________________"
Text Inserted�
Text
"2"
Text Inserted�
Text
"3"
Text Inserted�
Text
"in the Continuity Survey section (XIV)"
Text Inserted�
Text
"voltage"
Text Replaced�
Text
[Old]: "polarization." [New]: "shift." Font "Arial,Bold" changed to "ArialMT".Font-size "6.96001" changed to "7.98".
Text Replaced�
Text
[Old]: "(XIV.)" [New]: "(XIV)" Font "Arial,Bold" changed to "ArialMT".Font-size "6.96001" changed to "7.98".
Text Inserted�
Text
"4"
Text Replaced�
Text
[Old]: "one.)" [New]: "one). 5" Font "Arial,Bold" changed to "ArialMT".Font-size "6.96001" changed to "7.98".
Text Replaced�
Text
[Old]: "measured with the reference electrode placed “local”" [New]: "measurement for “Local Voltage”" Font "Arial,Bold" changed to "ArialMT".Font-size "6.96001" changed to "7.98".
Text Inserted�
Text
"6"
Text Replaced�
Text
[Old]: "measured with the reference electrode placed “remote” (or use the voltage measurements obtained during continuity survey if remote reference cell placement was used)." [New]: "measurement for “True Remote Earth Voltage” in millivolts. 7" Font "Arial,Bold" changed to "ArialMT".Font-size "6.96001" changed to "7.98".
Text Deleted�
Text
"2 3 4 5 6 7 39"
Page 54: Total Changes Content 821 - tn.gov

DRAFT

51

APPENDIX 7: GALVANIC CATHODIC PROTECTION TESTING SURVEY

(Modifications are made to these forms from time to time. Please check the Division’s website for the most current version of the State’s official form)

Text Replaced�
Text
[Old]: "7" [New]: "7:" Font "Open Sans,Bold" changed to "OpenSans-Bold".
Text Inserted�
Text
"DRAFT"
Text Deleted�
Text
"40"
Page 55: Total Changes Content 821 - tn.gov

DRAFT

DRAFT

STATE OF TENNESSEE DEPARTMENT OF ENVIRONMENT AND CONSERVATION

DIVISION OF UNDERGROUND STORAGE TANKS William R Snodgrass Tennessee Tower 312 Rosa L. Parks Avenue, 12th Floor

Nashville, TN 37243 GALVANIC CATHODIC PROTECTION TESTING SURVEY

Utilize this form to evaluate underground storage tank (UST) galvanic cathodic protection systems in the State of Tennessee. Access to the soil directly over the cathodically protected structure that is being evaluated is required.

I. UST FACILITY II. UST OWNERNAME: NAME:

FACILITY ID NUMBER: COMPANY:

ADDRESS: ADDRESS:

CITY: COUNTY: CITY: STATE:

III. CP TESTERTESTER’S NAME: COMPANY:

ADDRESS: LIST CERTIFICATION, IF ANY:

CITY: STATE: PHONE NUMBER:

IV. REASON SURVEY WAS CONDUCTED (mark only one)□ Routine – 3 year □ Routine – within 6 months of installation □ Re-survey after fail/repair/modification

Date next cathodic protection survey must be conducted by: __________________________ (required every 3 years).

V. CATHODIC PROTECTION TESTER’S EVALUATION (mark only one)

□ PASS All protected structures at this facility pass the cathodic protection survey and it is judged that adequate cathodic protection has been provided to the UST system (indicate all applicable criteria by completion of Section VII).

□ INCOMPLETE One or more protected structures at this facility fail the cathodic protection survey and it is judged that adequate cathodic protection has not been provided to the UST system (complete Section VIII).

□ FAIL All tanks or piping did not pass the cathodic protection survey (complete Section VIII).

□ INCONCLUSIVE If the remote and local do not both indicate the same result on all protected structures (both pass or fail), inconclusive isindicated and the resurvey must be evaluated and/or conducted by a corrosion expert.(Complete section VI.)

CP TESTER’S SIGNATURE: ________________________________________________ DATE CP SURVEY PERFORMED: ________________________________

VI. CORROSION EXPERT’S EVALUATION (mark only one)The survey must be conducted and/or evaluated by a corrosion expert when: a) an inconclusive is indicated for any protected structure since both the local and the remote structure-to-soil potentials do not result in the same outcome (both pass or both fail); b) repairs to galvanized or uncoated steel piping are conducted; or c) replacement or addition of anodes for tanks and/or piping (except flexible connectors and/or short sections of metal piping).

□ PASS (based on above criteria) □ FAIL (based on above criteria)

CORROSION EXPERT’S NAME: COMPANY NAME:

NACE INTERNATIONAL CERTIFICATION NUMBER:

CORROSION EXPERT’S SIGNATURE: _________________________________________________________ DATE: _____________________________________ VII. CRITERIA APPLICABLE TO EVALUATION (mark all that apply)

□ 850 ON Structure-to-soil potentials –850 mV or more negative with respect to a Cu/CuSO4 reference electrode with the protective current applied (applicable to any galvanically protected structure).

□ 850 OFF Structure-to-soil potentials –850 mV or more negative with respect to a Cu/CuSO4 reference electrode with protective current temporarily interrupted (applicable only to galvanic systems where the anodes can be disconnected).

□ 100 mV Shift Structure tested exhibits at least 100 mV shift (applicable to galvanic systems where the anodes can be temporarily disconnected).

VIII. ACTION REQUIRED AS A RESULT OF THIS EVALUATION (mark only one)

□ NONE Cathodic protection is adequate. No further action is necessary at this time. Test again by no later than the date specified in Section IV.

□ REPAIR & RETEST Cathodic protection is not adequate. Repair/modification is necessary as soon as practical.

CN-1140 1 RDA-2304

Text Inserted�
Text
"STATE OF TENNESSEE"
Text Replaced�
Text
[Old]: "This form must be utilized" [New]: "Utilize this form" Font "Arial" changed to "ArialMT".
Text Inserted�
Text
"galvanic"
Text Replaced�
Text
[Old]: "must be provided." [New]: "is required." Font "Arial" changed to "ArialMT".
Text Inserted�
Text
"DRAFT DRAFT"
Text Replaced�
Text
[Old]: "-3" [New]: "– 3" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "fail □ Re-survey after repair/modification" [New]: "fail/repair/modification" Font "Arial" changed to "ArialMT".
Text Deleted�
Text
"within 6 months of installation/repair, or"
Text Replaced�
Text
[Old]: "All protected structures at this facility pass the cathodic protection survey and it is judged that adequate cathodic protection has been provided to the UST system (indicate all applicable criteria by completion of Section VII)." [New]: "A has ll pr been pr otected s ovi tr de uc d to the US tures at this T fac sys il tem ity pas (indi s the c cate al ath l appl odic ic pr abl otec e c ti r on s iteria ur by vey com and i pleti t is on of S judged that ad ection VII) equ . ate cathodic protection" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "One or more protected structures at this facility fail the cathodic protection survey and it is judged that adequate cathodic protection has not been provided to the UST system (complete Section VIII)." [New]: "O pr ne o otec r tion has more pr no otec t been pr ted struc ov tur ided t es at thi o the US s fac T ili s ty ys fai tem l the c (com athodi plete S c pr ec ot ti ec on V tion s III) ur . vey and it is judged that adequate cathodic" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "If the remote and local do not both indicate the same result on all protected structures (both pass or fail), inconclusive is indicated and the resurvey must be evaluated and/or conducted by a corrosion expert.(Complete section VI.) □ INCONCLUSIVE CP TESTER’S SIGNATURE:" [New]: "□ INCONCLUSIVE If the r indicated and the emote and l r oc es al urv do not both ey must be ev indi al cate the s uated and/ am or e r c es onduc ult on al ted by l pr a c otec or ted s rosion ex tructur pe es rt.( (both pas Complete s s or ec fai tion V l), inc I.) onclusive is CP TESTER’S SIGNATURE: ________________________________________________" Font "Arial" changed to "ArialMT".Font-size "8.03999" changed to "19.98".
Text Replaced�
Text
[Old]: "conducted" [New]: "conducted;" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "supplemental anodes are added to the tanks and/or piping." [New]: "replacement or addition of anodes for tanks and/or piping (except flexible connectors and/or short sections of metal piping)." Font "Arial" changed to "ArialMT".
Text Inserted�
Text
"□"
Text Replaced�
Text
[Old]: "potential more negative than –850 mV" [New]: "potentials –850 mV or more negative" Font "Arial" changed to "ArialMT".
Text Deleted�
Text
"□"
Text Replaced�
Text
[Old]: "potential more negative than –850 mV" [New]: "potentials –850 mV or more negative" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "Polarization" [New]: "Shift" Font "Arial,Bold" changed to "Arial-BoldMT".
Text Replaced�
Text
[Old]: "of cathodic polarization" [New]: "shift" Font "Arial" changed to "ArialMT".
Text Deleted�
Text
"41"
Page 56: Total Changes Content 821 - tn.gov

DRAFT

DRAFT

IX. DESCRIPTION OF UST SYSTEMFACILITY NAME: FACILITY ID NUMBER:

TANK # PRODUCT CAPACITY TANK MATERIAL PIPING MATERIAL FLEX CONNECTORS (Y / N). IF YES, INDICATE LOCATION (STP / DISP / STP AND DISP)

1 2 3 4 5 6 7

If metal flex connectors are present, are they corrosion protected?

□ YES Method:□ Isolation (booted) □Isolation (not in contact with the ground)□ Attached Anode1 (provide details in comments)

□ NO Action taken: __________________________________________________________________________

Comments (e.g., piping brand, specific flex/anode location, etc.):

1If the flex connectors are protected by sacrificial anodes, test accordingly and include in Section XIV. on this form.X. DESCRIPTION OF CATHODIC PROTECTION SYSTEM REPAIRS AND/OR MODIFICATION

Complete if repairs or modifications to the cathodic protection system are made or are necessary. Certain repairs/modifications as explained in Technical Chapter 4.1Corrosion Protection, are required to be designed and/or evaluated by a corrosion expert (completion of Section VI. required).

□ Adding or replacing existing anodes for a sti-P3® tank (attach corrosion expert’s design).

□ Adding or replacing existing anodes for metallic pipe (attach corrosion expert’s design).

□ Resolving continuity issues when problems identified and system does not pass (attach explanation).

Remarks/Other

CN-1140 2 RDA-2304

Text Replaced�
Text
[Old]: "ID NUMBER: FACILITY NAME:" [New]: "NAME: FACILITY ID NUMBER:" Font "Arial,Bold" changed to "Arial-BoldMT".
Text Replaced�
Text
[Old]: "/ LOCATION 1 2 3 4 5 6 7 8 9 10" [New]: "(Y / N). IF YES, INDICATE LOCATION (STP / DISP / STP AND DISP) 1 2 3 4 5 6 7" Font "Arial,Bold" changed to "ArialMT".
Text Inserted�
Text
"If metal flex connectors"
Text Replaced�
Text
[Old]: "□ Isolation (booted) □Isolation (contained in sump or no soil contact)" [New]: "□Isolation (booted)" Font "Arial,Bold" changed to "Arial-BoldMT".
Text Inserted�
Text
"DRAFT DRAFT"
Text Inserted�
Text
"(provide details in comments) □Isolation (not in contact with the ground)"
Text Deleted�
Text
"If metal flex connectors"
Text Inserted�
Text
"Comments (e.g., piping brand, specific flex/anode location, etc.):"
Text Replaced�
Text
[Old]: "the text of the Standardized Compliance inspection Manual, Technical Chapter 4.1 Corrosion Protection" [New]: "Technical Chapter 4.1 Corrosion Protection," Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "supplemental" [New]: "or replacing existing" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "supplemental" [New]: "or replacing existing" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "Remarks/Other:" [New]: "Remarks/Other"
Text Deleted�
Text
"__________________________________________________________________________________________________________________________"
Text Deleted�
Text
"42"
Page 57: Total Changes Content 821 - tn.gov

DRAFT

DRAFT

XI. UST FACILITY SITE DRAWINGAttach detailed legible drawing or use the space provided to draw a sketch of the UST and cathodic protection systems. Sufficient detail must be given to clearly indicate where the reference electrode/cell was placed for each structure-to-soil potential that is recorded on the survey forms. Include details such as the location of all tanks, piping, and dispensers; buildings and streets; and additional anodes (if applicable)and wires. Each CP test (reference electrode placement) location must be indicated by a code (1,2, T-1, D-1, etc.) corresponding with the appropriate line number in Section XIII. of this form. Also, include the two (2) locations used to determine true remote earth (e.g., R1 and R2).

AN EVALUATION OF THE CATHODIC PROTECTION SYSTEM IS NOT COMPLETE WITHOUT AN ACCEPTABLE SITE DRAWING.

CN-1140 3 RDA-2304

Text Deleted�
Text
"in order"
Text Replaced�
Text
[Old]: "electrode" [New]: "electrode/cell" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "as:" [New]: "as the location of" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "anodes and wires; and location of rectifier." [New]: "and additional anodes (if applicable)and wires." Font "Arial" changed to "ArialMT".
Text Inserted�
Text
"Also, include the two (2) locations used to determine true remote earth (e.g., R1 and R2)."
Text Inserted�
Text
"DRAFT DRAFT"
Text Deleted�
Text
"43"
Page 58: Total Changes Content 821 - tn.gov

DRAFT

DRAFT

XII. GALVANIC (SACRIFICIAL ANODE) CATHODIC PROTECTION SYSTEM CONTINUITY SURVEY

This section will be utilized to record measurements of continuity on UST systems that are protected by galvanic cathodic protection systems. When conducting a fixed cell-moving ground survey, the reference electrode/cell must be placed in soil at a true remote earth location and left undisturbed. Either fixed cell-moving ground or point-to-point methods may be used to test continuity between any two structures. For galvanic systems, the structure that is to be protected must be isolated from any other metallic structure to pass the continuity survey except for conditions specified in

Section XIV

FACILITY NAME: FACILITY ID NUMBER:

DESCRIBE LOCATION OF TRUE REMOTE EARTH REFERENCE ELECTRODE/CELL PLACEMENT (e.g. In grass 50 feet NE of Premium Tank, etc.):

Provide the two (2) remote measurements used to determine the location of “True Remote Earth” (measurements must be less than 10 mV difference) (e.g., Premium Tank Remote 1 = -890 mV & Premium Tank Remote 2 = -884 mV, etc.):

STRUCTURE “A” 1 STRUCTURE “B” 2 STRUCTURE “A” 3

TRUE REMOTE EARTH VOLTAGE

STRUCTURE “B” 4 TRUE REMOTE

EARTH VOLTAGE

POINT-TO-POINT 5

VOLTAGE DIFFERENCE

ISOLATED/ 6

CONTINUOUS/ INCONCLUSIVE

(example)

PREMIUM TANK BOTTOM (example)

PREMIUM TANK FILL RISER (example) -921 mV

(example) -915 mV

(example) INCONCLUSIVE

(example)

PREMIUM TANK BOTTOM (example)

PREMIUM TANK FILL RISER (example) 17 mV

(example) ISOLATED

(example)

PREMIUM STP FLEX (example)

PREMIUM STP (example) 25 mV

(example) ISOLATED

COMMENTS: _______________________________________________________________________________ ________________________________________________________________________________________________________________________________________________________________________________1 Describe the cathodically protected structure that you are attempting to demonstrate is isolated from unprotected structures (e.g. prem. tank). 2 Describe the unprotected structure that you are attempting to demonstrate is isolated from the protected structure (e.g. premium tank fill riser). 3 Record the measured structure-to-soil potential at true remote earth of the cathodically protected structure “A” in millivolts (e.g. –921 mV). 4 Record the measured structure-to-soil potential at true remote earth of the unprotected structure “B” in millivolts (e.g. –915 mV). 5 Record the voltage observed between the protected and the unprotected structures when conducting point-to-point testing (e.g. 17 mV). 6 Document whether the test indicated the protected structure was continuous (1 - 5 mV), inconclusive (6 - 9 mV), or isolated ( > 10 mV).

CN-1140 4 RDA-2304

Text Deleted�
Text
"XII. GALVANIC (SACRIFICIAL ANODE) CATHODIC PROTECTION SYSTEM CONTINUITY SURVEY"
Text Replaced�
Text
[Old]: "conduct" [New]: "record" Font "Arial" changed to "ArialMT".
Text Inserted�
Text
"galvanic"
Text Replaced�
Text
[Old]: "electrode" [New]: "electrode/cell" Font "Arial" changed to "ArialMT".
Text Deleted�
Text
"the"
Text Inserted�
Text
"true"
Text Deleted�
Text
"in order"
Text Replaced�
Text
[Old]: "survey. FACILITY NAME: FACILITY ID NUMBER: DESCRIBE LOCATION OF “FIXED REMOTE” REFERENCE ELECTRODE PLACEMENT:" [New]: "survey except for conditions specified in Section XIV FACILITY NAME: FACILITY ID NUMBER: DESCRIBE LOCATION OF TRUE REMOTE EARTH REFERENCE ELECTRODE/CELL PLACEMENT (e.g. In grass 50 feet NE of Premium Tank, etc.): Provide the two (2) remote measurements used to determine the location of “True Remote Earth” (measurements must be less than 10 mV difference) (e.g., Premium Tank Remote 1 = -890 mV & Premium Tank Remote 2 = -884 mV, etc.):" Font "Arial" changed to "ArialMT".
Text Inserted�
Text
"ISOLATED/"
Text Deleted�
Text
"ISOLATED/"
Text Replaced�
Text
[Old]: "FIXED REMOTE FIXED" [New]: "TRUE REMOTE TRUE" Font "Arial,Bold" changed to "Arial-BoldMT".
Text Inserted�
Text
"EARTH VOLTAGE EARTH"
Text Deleted�
Text
"INCONCLUSIVE"
Text Inserted�
Text
"INCONCLUSIVE"
Text Inserted�
Text
"(example)"
Text Inserted�
Text
"DRAFT DRAFT"
Text Inserted�
Text
"(example) (example) (example) ISOLATED PREMIUM STP FLEX PREMIUM STP 25 mV"
Text Deleted�
Text
"________________________________________________________________________________________"
Text Deleted�
Text
"2 3 4"
Text Inserted�
Text
"2"
Text Inserted�
Text
"3"
Text Inserted�
Text
"at true remote earth"
Text Replaced�
Text
[Old]: "{“A”}" [New]: "“A”" Font "Arial" changed to "ArialMT".
Text Inserted�
Text
"4"
Text Replaced�
Text
[Old]: "of the unprotected structure {“B”}" [New]: "at true remote earth of the unprotected structure “B”" Font "Arial" changed to "ArialMT".
Text Inserted�
Text
"5"
Text Inserted�
Text
"6"
Text Replaced�
Text
[Old]: "( 6" [New]: "(6" Font "Arial" changed to "ArialMT".
Text Deleted�
Text
"5 6"
Text Deleted�
Text
"44"
Page 59: Total Changes Content 821 - tn.gov

DRAFT

DRAFT

XIII. GALVANIC (SACRIFICIAL ANODE) CATHODIC PROTECTION SYSTEM SURVEY This section will be utilized to record structure-to-soil potential measurements obtained from a galvanic cathodic protection system. The reference electrode must be placed in soil directly over the tested structure (local) and at true remote earth (typically 25-100 feet away from the structure). A minimum of one local measurement must be obtained over the middle of the tank and two at remote earth. Additional measurements may be obtained over both ends

of each tank, if desired. All local and remote earth voltage measurements must be –850 mV or more negative for the structure to pass. Inconclusive is indicated when both the local and remote earth structure-to-soil potentials do not result in the same outcome (i.e., both pass or both fail).

FACILITY NAME: FACILITY ID NUMBER:

If not provided in Section XII, provide the two (2) remote measurements used to determine the location of “True Remote Earth” (measurements must be less than 10 mV difference) (e.g., Regular Tank Remote 1 = -890 mV & Regular Tank Remote 2 = -884 mV, etc.):

LOCATION1 CODE

STRUCTURE 2 CONTACT POINT 3 LOCAL REFERENCE CELL PLACEMENT 4 LOCAL VOLTAGE5

TRUE REMOTE EARTH

VOLTAGE6

PASS / FAIL /INCONCLUSIVE7

(example) 1

(example) PLUS TANK

(example) TANK BOTTOM

(example) PLUS TANK STP MANWAY

(example) -928 mV

(example) -810 mV

(example) INCONCLUSIVE

(example) 2

(example) PLUS PIPING

(example) PLUS PIPING @DISP 5/6

(example) SOIL UNDER DISP 5/6

(example) -890 mV

(example) -885 mV

(example) PASS

COMMENTS: _______________________________________________________________________________ ________________________________________________________________________________________________________________________________________________________________________________ ________________________________________________________________________________________ 1 Designate numerically or by code on the site drawing each “local” reference electrode placement (e.g. 1, 2, 3… T-1, T-2, P-1, P-2…etc.). 2 Describe the structure that is being tested (e.g. plus tank; premium piping; diesel submersible pump flex connector; etc.). 3 Describe where contact with the structure being tested is made (e.g. diesel piping @ dispenser 5/6; etc.). 4 Describe exact location where reference electrode is placed for each “local” reading (e.g. soil @ plus tank STP; soil @ dispenser 5/6; etc.)5 Record the structure-to-soil potential measured with the reference electrode placed “local” in millivolts (e.g. –865 mV, -920 mV, etc.). 6 Record the structure-to-soil potential measured with the reference electrode placed “remote” (copy voltage obtained during continuity survey). 7 Indicate whether the tested structure passed or failed the –850 mV “on” criterion based on your interpretation of the test data.

CN-1140 5 RDA-2304

Text Replaced�
Text
[Old]: "conduct a survey of a galvanic cathodic protection system by obtaining structure-to-soil potential measurements." [New]: "record structure-to-soil potential measurements obtained from a galvanic cathodic protection system." Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "a" [New]: "true" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "location, at least" [New]: "(typically" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "structure." [New]: "structure)." Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "made" [New]: "obtained" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "tank. Additional readings may be made over both ends of each tank" [New]: "tank and two at remote earth. Additional measurements may be obtained over both ends of each tank," Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "readings" [New]: "measurements" Font "Arial" changed to "ArialMT".
Text Deleted�
Text
"in order"
Text Replaced�
Text
[Old]: "DESCRIBE LOCATION OF REMOTE REFERENCE ELECTRODE PLACEMENT:" [New]: "If not provided in Section XII, provide the two (2) remote measurements used to determine the location of “True Remote Earth” (measurements must be less than 10 mV difference) (e.g., Regular Tank Remote 1 = -890 mV & Regular Tank Remote 2 = -884 mV, etc.):" Font "Arial,Bold" changed to "Arial-BoldMT".Font-size "6" changed to "7.02".
Text Inserted�
Text
"LOCAL TRUE"
Text Deleted�
Text
"LOCAL REMOTE"
Text Inserted�
Text
"REMOTE"
Text Inserted�
Text
"CODE"
Text Inserted�
Text
"EARTH"
Text Deleted�
Text
"CODE"
Text Inserted�
Text
"mV -810 mV"
Text Replaced�
Text
[Old]: "PLUS PIPING DISPENSER 5/6 UNDER DISPENSER 5/6 -890 -885 PASS" [New]: "PLUS PIPING PLUS PIPING SOIL UNDER DISP 5/6 -890 mV -885 mV PASS @DISP 5/6" Font "Comic Sans MS,Bold" changed to "ComicSansMS-BoldItalic".
Text Inserted�
Text
"DRAFT DRAFT"
Text Inserted�
Text
"________________________________________________________________________________________"
Text Replaced�
Text
[Old]: "plus tank @ test lead; diesel piping @ dispenser 5/6; etc)." [New]: "diesel piping @ dispenser 5/6; etc.)." Font "Arial" changed to "ArialMT".
Text Deleted�
Text
"6"
Text Inserted�
Text
"6"
Text Inserted�
Text
"7"
Text Deleted�
Text
"7"
Text Replaced�
Text
[Old]: "45" [New]: "5 RDA-2304 CN-1140" Font "Times New Roman" changed to "Arial".Font-size "12" changed to "9".
Page 60: Total Changes Content 821 - tn.gov

DRAFT

DRAFT

XIV. FLEXIBLE CONNECTORS (OR OTHER SHORT SECTION OF METAL PIPING) CATHODIC PROTECTION SYSTEM SURVEY This form will be utilized to record structure-to-soil potential measurements for galvanically protected flexible connectors (or other metal piping sections). A total of three (3) potential measurements (one local and two at remote earth to determine True Remote Earth) is required for each flex connector when using the “On” / “Local Voltage” (-850 mV) criteria. Record the True Remote Earth

Voltage on the form below. If either the local or the remote potential measurements fail (more positive than -850 mV), use the instant off or 100 mV shift criteria to determine protective status (i.e. Pass / Fail). The instant off or 100 mV shift measurements are

obtained after disconnecting the anode from the flex connector. See also Appendix 4 of Technical Chapter 4.1, Corrosion Protection. Potential measurements must be obtained for each flex connector.

FACILITY NAME: FACILITY ID NUMBER: Location of Remote Reference Cell Placement, if Applicable (also designate on site drawing):

TANK #, PRODUCT, CAPACITY1 FLEX LOCATION2

WHERE IS ANODE

ATTACHED?

CONTINUOUS OR ISOLATED? 3 (must

also complete Section XII)

CONTACT POINT4 LOCAL VOLTAGE5

TRUE REMOTE EARTH

VOLTAGE6

INSTANT OFF VOLTAGE

(if necessary)

100 mV SHIFT

PASS/FAIL7 ENDING

VOLTAGE (if

necessary)

VOLTAGE CHANGE

E X A M P L E S

#2 DIESEL 8,000 DIESEL FLEX AT

STP ON FLEX ISO. ON FLEX -875 mV -760 mV -860 mV PASS

#3 Regular 10,000 REG. FLEX AT DISPENSER 3/4

PIPING ABOVE SHEAR VALVE CONT. PIPING ABOVE

SHEAR VALVE -980 mV -845 mV -790 mV 55 mV FAIL

#4 PREMIUM 10,000 PREM. STP FLEX IN CONTAINED

SUMP STP HEAD CONT. STP HEAD -910 mV PASS

COMMENTS:__________________________________________________________________________________________________________________________________________________

______________________________________________________________________________________________________________________________________________________________

1 Designate the number, product, and capacity of the tank with which the flex connector is associated. 2 Indicate location of flex being tested (e.g. REGULAR FLEX AT DISPENSER 3/4, DIESEL FLEX AT STP, etc.) 3 Continuity or isolation of flex connectors must be documented in the Continuity Survey section (XII) before completion of this section to determine whether to use remote or instant off/100 mV shift. If testing

flex connectors only, include Continuity Survey section (XII.) of this form with this section. 4 Designate exact point of contact when testing flex (i.e., if isolated, must contact only the flex itself. If continuous with another component, can contact either one.). 5 Record the structure-to-soil potential measurement for “Local Voltage” in millivolts (e.g. –875 mV, -980 mV, etc.). 6 Record the structure-to-soil potential measurement for “True Remote Earth Voltage” in millivolts. 7 Indicate whether the tested structure passed or failed based on your interpretation of the test data.

CN-1140 6 RDA-2304

Text Replaced�
Text
[Old]: "CONNECTOR CATHODIC PROTECTION SYSTEM" [New]: "CONNECTORS (OR OTHER SHORT SECTION OF METAL PIPING) CATHODIC PROTECTION SYSTEM SURVEY" Font "Arial,Bold" changed to "Arial-BoldMT".
Text Replaced�
Text
[Old]: "conduct a survey of galvanic protected flexible connectors by obtaining structure-to-soil potential measurements. • A minimum of one measurement must be made with the reference electrode placed in soil directly over the tested structure (local) and one measurement at a remote earth location, at least 25-100 feet away from the structure. • Flex connectors in contained sumps or continuous with dispenser cabinets or STPs must use instant off or voltage change (100 mV shift) to determine protected status. • If either local or remote reading is more positive than -850 mV, obtain instant off by disconnecting anode. If instant off is more positive than -850 mV, then conduct" [New]: "record structure-to-soil potential measurements for galvanically protected flexible connectors (or other metal piping sections). • A total of three (3) potential measurements (one local and two at remote earth to determine True Remote Earth) is required for each flex connector when using the “On” / “Local Voltage” (-850 mV) criteria. Record the True Remote Earth Voltage on the form below. • If either the local or the remote potential measurements fail (more positive than -850 mV), use the instant off or 100 mV shift criteria to determine protective status (i.e. Pass / Fail). The instant off or 100 mV shift measurements are obtained after disconnecting the anode from the flex connector. • See also Appendix 4 of Technical Chapter 4.1, Corrosion Protection. • Potential measurements must be obtained for each flex connector. FACILITY NAME: FACILITY ID NUMBER: Location of Remote Reference Cell Placement, if Applicable (also designate on site drawing):" Font "Arial" changed to "ArialMT".
Text Inserted�
Text
"DRAFT DRAFT"
Text Replaced�
Text
[Old]: "polarization" [New]: "SHIFT TRUE CONTINUOUS OR ISOLATED? 3 (must also complete Section XII) INSTANT OFF WHERE IS ENDING TANK #, PRODUCT, CAPACITY 1 LOCAL REMOTE FLEX LOCATION 2 CONTACT POINT 4 PASS/FAIL 7 VOLTAGE ANODE VOLTAGE VOLTAGE VOLTAGE 5 EARTH (if necessary) ATTACHED? (if CHANGE VOLTAGE 6 necessary) DIESEL FLEX AT E X ON FLEX ISO. ON FLEX -875 mV -760 mV -860 mV PASS #2 DIESEL 8,000 STP A REG. FLEX AT PIPING ABOVE PIPING ABOVE SHEAR VALVE M #3 Regular 10,000 CONT. -980 mV -845 mV -790 mV 55 mV FAIL DISPENSER 3/4 SHEAR VALVE P L PREM. STP FLEX E S #4 PREMIUM 10,000 IN CONTAINED STP HEAD CONT. STP HEAD -910 mV PASS SUMP COMMENTS:__________________________________________________________________________________________________________________________________________________" Font "Arial" changed to "Arial-BoldMT".Font-size "6.48" changed to "7.02".
Text Inserted�
Text
"______________________________________________________________________________________________________________________________________________________________"
Text Inserted�
Text
"1 Designate the number, product, and capacity of the tank with which the flex connector is associated. 2 Indicate location of flex being tested (e.g. REGULAR FLEX AT DISPENSER 3/4, DIESEL FLEX AT STP, etc.) 3 Continuity or isolation of flex connectors must be documented in the Continuity Survey section (XII) before completion of this section to determine whether to use remote or instant off/100 mV shift. If testing flex connectors only, include Continuity Survey section (XII.) of this form with this section. 4 Designate exact point of contact when testing flex (i.e., if isolated, must contact only the flex itself. If continuous with another component, can contact either one.). 5 Record the structure-to-soil potential measurement for “Local Voltage” in millivolts (e.g. –875 mV, -980 mV, etc.). 6 Record the structure-to-soil potential measurement for “True Remote Earth Voltage” in millivolts. 7"
Text Inserted�
Text
"Indicate whether the tested structure passed or failed based on your interpretation of the test data."
Text Inserted�
Text
"6 RDA-2304 CN-1140"
Page 61: Total Changes Content 821 - tn.gov

DRAFT

DRAFT

XIV. FLEXIBLE CONNECTORS (OR OTHER SHORT SECTION OF METAL PIPING) CATHODIC PROTECTION SYSTEM SURVEY (CONTINUED) This form will be utilized to record structure-to-soil potential measurements for galvanically protected flexible connectors (or other metal piping sections). A total of three (3) potential measurements (one local and two at remote earth to determine True Remote Earth) is required for each flex connector when using the “On” / “Local Voltage” (-850 mV) criteria. Record the True Remote Earth

Voltage on the form below. If either the local or the remote potential measurements fail (more positive than -850 mV), use the instant off or 100 mV shift criteria to determine protective status (i.e. Pass / Fail). The instant off or 100 mV shift measurements are

obtained after disconnecting the anode from the flex connector. See also Appendix 4 of Technical Chapter 4.1, Corrosion Protection. Potential measurements must be obtained for each flex connector.

FACILITY NAME: FACILITY ID NUMBER: Location of Remote Reference Cell Placement, if Applicable (also designate on site drawing):

TANK #, PRODUCT, CAPACITY1 FLEX LOCATION2

WHERE IS ANODE

ATTACHED?

CONTINUOUS OR ISOLATED? 3 (must

also complete Section XII)

CONTACT POINT4 LOCAL VOLTAGE5

TRUE REMOTE EARTH

VOLTAGE6

INSTANT OFF VOLTAGE

(if necessary)

100 mV SHIFT

PASS/FAIL7 ENDING

VOLTAGE (if

necessary)

VOLTAGE CHANGE

E X A M P L E S

#2 DIESEL 8,000 DIESEL FLEX AT

STP ON FLEX ISO. ON FLEX -875 mV -760 mV -860 mV PASS

#3 Regular 10,000 REG. FLEX AT DISPENSER 3/4

PIPING ABOVE SHEAR VALVE CONT. PIPING ABOVE

SHEAR VALVE -980 mV -845 mV -790 mV 55 mV FAIL

#4 PREMIUM 10,000 PREM. STP FLEX IN CONTAINED

SUMP STP HEAD CONT. STP HEAD -910 mV PASS

COMMENTS:__________________________________________________________________________________________________________________________________________________

______________________________________________________________________________________________________________________________________________________________

1 Designate the number, product, and capacity of the tank with which the flex connector is associated. 2 Indicate location of flex being tested (e.g. REGULAR FLEX AT DISPENSER 3/4, DIESEL FLEX AT STP, etc.) 3 Continuity or isolation of flex connectors must be documented in the Continuity Survey section (XII) before completion of this section to determine whether to use remote or instant off/100 mV shift. If testing

flex connectors only, include Continuity Survey section (XII.) of this form with this section. 4 Designate exact point of contact when testing flex (i.e., if isolated, must contact only the flex itself. If continuous with another component, can contact either one.). 5 Record the structure-to-soil potential measurement for “Local Voltage” in millivolts (e.g. –875 mV, -980 mV, etc.). 6 Record the structure-to-soil potential measurement for “True Remote Earth Voltage” in millivolts. 7 Indicate whether the tested structure passed or failed based on your interpretation of the test data.

CN-1140 7 RDA-2304

Text Replaced�
Text
[Old]: "record ending voltage. If difference between instant off and ending voltage is more than 100 mV, the result is PASS. If difference is less than 100 mV, or either local or remote reading is more positive than -850 mV, then structure is not protected and the result is FAIL." [New]: "XIV. FLEXIBLE CONNECTORS (OR OTHER SHORT SECTION OF METAL PIPING) CATHODIC PROTECTION SYSTEM SURVEY (CONTINUED) • This form will be utilized to record structure-to-soil potential measurements for galvanically protected flexible connectors (or other metal piping sections). • A total of three (3) potential measurements (one local and two at remote earth to determine True Remote Earth) is required for each flex connector when using the “On” / “Local Voltage” (-850 mV) criteria. Record the True Remote Earth Voltage on the form below. • If either the local or the remote potential measurements fail (more positive than -850 mV), use the instant off or 100 mV shift criteria to determine protective status (i.e. Pass / Fail). The instant off or 100 mV shift measurements are obtained after disconnecting the anode from the flex connector. • See also Appendix 4 of Technical Chapter 4.1, Corrosion Protection. • Potential measurements must be obtained for each flex connector." Font "Arial" changed to "Arial-BoldMT".Font-size "6.48" changed to "10.02".
Text Inserted�
Text
"______________________________________________________________________________________________________________________________________________________________ DRAFT DRAFT"
Text Deleted�
Text
"INSTANT"
Text Replaced�
Text
[Old]: "POLARIZATION OFF WHERE CONTINUOUS ENDING LOCAL REMOTE VOLTAGE TANK #, PRODUCT, CAPACITY 1 FLEX LOCATION 2 CONTACT POINT 4 PASS/FAIL 7 ANODE OR" [New]: "SHIFT TRUE CONTINUOUS OR ISOLATED? 3 (must also complete Section XII) INSTANT OFF WHERE IS ENDING TANK #, PRODUCT, CAPACITY 1 LOCAL REMOTE FLEX LOCATION 2 CONTACT POINT 4 PASS/FAIL 7 VOLTAGE ANODE" Font "Arial,Bold" changed to "Arial-BoldMT".
Text Replaced�
Text
[Old]: "VOLTAGE 6 (if ISOLATED? 3 ATTACHED? (if CHANGE necessary)" [New]: "EARTH (if necessary) ATTACHED? (if CHANGE VOLTAGE 6" Font "Arial,Bold" changed to "Arial-BoldMT".
Text Inserted�
Text
"E X"
Text Deleted�
Text
"E"
Text Deleted�
Text
"X A PIPING"
Text Inserted�
Text
"PIPING"
Text Inserted�
Text
"SHEAR VALVE"
Text Deleted�
Text
"SHEAR"
Text Replaced�
Text
[Old]: "VALVE L E PREM. FLEX IN" [New]: "L PREM. STP FLEX E S" Font "Arial" changed to "ArialMT".
Text Inserted�
Text
"IN"
Text Deleted�
Text
"S"
Text Deleted�
Text
"______________________________________________________________________________________________________________________________________________________________"
Text Inserted�
Text
"2"
Text Inserted�
Text
"3"
Text Inserted�
Text
"in the Continuity Survey section (XII)"
Text Replaced�
Text
[Old]: "polarization." [New]: "shift." Font "Arial,Bold" changed to "Arial-BoldMT".
Text Inserted�
Text
"4"
Text Replaced�
Text
[Old]: "one.)" [New]: "one.). 5" Font "Arial,Bold" changed to "Arial-BoldMT".
Text Replaced�
Text
[Old]: "measured with the reference electrode placed “local”" [New]: "measurement for “Local Voltage”" Font "Arial,Bold" changed to "Arial-BoldMT".
Text Inserted�
Text
"6"
Text Replaced�
Text
[Old]: "measured with the reference electrode placed “remote” (or use the voltage measurements obtained during continuity survey if remote reference cell placement was used)." [New]: "measurement for “True Remote Earth Voltage” in millivolts. 7 Indicate whether the tested structure passed or failed based on your interpretation of the test data." Font "Arial,Bold" changed to "Arial-BoldMT".
Text Deleted�
Text
"Indicate whether the tested structure passed or failed based on your interpretation of the test data."
Text Deleted�
Text
"2 3 4 5 6 7 46"
Page 62: Total Changes Content 821 - tn.gov

DRAFT

60

APPENDIX 8: IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM 60-DAY RECORD OF RECTIFER OPERATION FORM

(Modifications are made to these forms from time to time. Please check the Division’s website for the most current version of the State’s official form)

Text Replaced�
Text
[Old]: "8" [New]: "8:" Font "Open Sans,Bold" changed to "OpenSans-Bold".
Text Inserted�
Text
"DRAFT"
Text Deleted�
Text
"47"
Page 63: Total Changes Content 821 - tn.gov

DRAFT

DRAFT

STATE OF TENNESSEE DEPARTMENT OF ENVIRONMENT AND CONSERVATION

DIVISION OF UNDERGROUND STORAGE TANKS William R Snodgrass Tennessee Tower 312 Rosa L. Parks Avenue, 12th Floor

Nashville, TN 37243

IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM 60-DAY RECORD OF RECTIFER OPERATION

This form may be utilized to document that the cathodic protection system rectifier is checked for operation at least once every 60 days, isturned on, and is continuously receiving power (rules 0400-18-01-.02(4)(c)1 and .02(4)(c)4).

Record the output voltage, amperage, and/or the number of hours indicated on the hour meter (if equipped). Any variance greater than 20% in the DC output of the rectifier (as indicated on the last cathodic protection test) should be reported

to your corrosion professional so that the system can be retested and, if necessary, repairs and/or adjustments can be made.

UST OWNER UST FACILITY NAME: NAME: ID #

ADDRESS: ADDRESS:

CITY: STATE: CITY: COUNTY:

IMPRESSED CURRENT RECTIFIER DATA

Rectifier Manufacturer: Rated DC Output: ____________ VOLTS ____________ AMPS

Rectifier Model: Rectifier Serial Number:

What is the ‘as designed’ or lastly recommended rectifier output? ____________ VOLTS ___________AMPS

60-DAY LOG OF RECTIFIER OPERATION

DATE INSPECTED

RECTIFIER POWER

ON?

TAP SETTINGS DC OUTPUT HOUR METER

CHECKED BY

INITIALS COMMENTS

COARSE FINE VOLTS AMPS

CN-1282 1 RDA-2304

Text Inserted�
Text
"STATE OF TENNESSEE"
Text Replaced�
Text
[Old]: "days. • Checked for operation is taken to mean that it was confirmed the rectifier was receiving power and is “turned-on”. Rectifier power must be on continuously according to rule 0400-18-1-.02(4)(c )1. • If your rectifier is so equipped, you should also record the output voltage, amperage and the number of hours indicated on the meter. • Any significant variance greater than 20% in the DC output from the ‘as designed’ or recommended volts or amps output should be reported to your corrosion professional so that any necessary" [New]: "days, is turned on, and is continuously receiving power (rules 0400-18-01-.02(4)(c)1 and .02(4)(c)4). • Record the output voltage, amperage, and/or the number of hours indicated on the hour meter (if equipped). • Any variance greater than 20% in the DC output of the rectifier (as indicated on the last cathodic protection test) should be reported to your corrosion professional so that the system can be retested and, if necessary," Font "Arial" changed to "ArialMT".
Text Inserted�
Text
"DRAFT DRAFT"
Text Replaced�
Text
[Old]: "___________AMPS" [New]: "____________ AMPS" Font "Arial" changed to "ArialMT".
Text Deleted�
Text
"DATE"
Text Inserted�
Text
"CHECKED"
Text Inserted�
Text
"DATE POWER"
Text Inserted�
Text
"METER"
Text Replaced�
Text
[Old]: "CHECKED" [New]: "BY" Font "Arial" changed to "ArialMT".
Text Deleted�
Text
"POWER"
Text Deleted�
Text
"METER"
Text Deleted�
Text
"BY ON?"
Text Inserted�
Text
"ON?"
Text Deleted�
Text
"CN 1282 RDA 2304"
Text Deleted�
Text
"48"
Page 64: Total Changes Content 821 - tn.gov

file://NoURLProvided[1/28/2021 5:10:01 PM]

Summary

Shows Replacements

Shows Insertions

Shows Deletions

821Total Changes

Page 65: Total Changes Content 821 - tn.gov
Text Inserted�
Text
"Corrosion Protection"
Text Inserted�
Text
"DRAFT"
Text Inserted�
Text
"Standardized Inspection Manual Technical Chapter 4.1 Tennessee Department of Environment & Conservation Division of Underground Storage Tanks Rules Effective October 13, 2018 Document Last Edited: 1/28/2021"
Page 66: Total Changes Content 821 - tn.gov

1

This page intentionally left blank

Text Inserted�
Text
"DRAFT"
Text Deleted�
Text
"1"
Page 67: Total Changes Content 821 - tn.gov

2

STATE OF TENNESSEE

DEPARTMENT OF ENVIRONMENT AND CONSERVATION

DIVISION OF UNDERGROUND STORAGE TANKS

TECHNICAL CHAPTER 4.1

CORROSION PROTECTION

EFFECTIVE DATE – October 1, 2015

PURPOSE

The purpose of this technical chapter is to assist Division of Underground Storage Tanks (Division) staff in

understanding the requirements for Underground Storage Tank (UST) system corrosion protection design,

construction, operation/maintenance, repair, testing, and recordkeeping. Evaluating the performance of these

systems, whether during operational inspections by the State or during the periodically required testing by

vendors, has resulted in some inconsistencies in understanding and application of testing practices. State

policies and regulations have historically deferred to industry standards without specifics in regard to

inspection and testing practices. A primary goal of this technical chapter is to standardize the performance

evaluation of these systems by detailing specific policies and guidelines that will create a uniformity of

understanding and consistency of practice among Division inspectors, testers, and service providers.

This technical chapter contains the current policy of the Division based on the statute and regulations

governing the Tennessee Petroleum Underground Storage Tank program. This document supersedes all

previously published versions. The most current version of this technical chapter will be posted and always

available on the Division’s website.

AUTHORITY

All rules referred to in this technical chapter are contained in Chapter 0400-18-01 and are available on the

Division of Underground Storage Tanks website at http://www.state.tn.us/sos/rules/0400/0400-18/0400-18-

01.20130121.pdf

Text Inserted�
Text
"Table of Contents 1. DISCLAIMER 1 PURPOSE 1 AUTHORITY 1 PLICABILITY 2 REQUIREMENTS 3 2. 3. 4. AP 5. a. General Design and Construction of Tanks .......................................................................................... 3 b. General Design and Construction of Piping ......................................................................................... 4 1. Non-Metallic (Rigid or Flexible) ........................................................................................................ 4 2 . Metallic"
Text Inserted�
Text
"DRAFT"
Text Inserted�
Text
"................................................................................................................................................ 4 6. Corrosion System Design and Construction 4 a. Corrosion Expert ...................................................................................................................................... 4 b. Cathodic Protection Tester ..................................................................................................................... 5 7. Methods of Corrosion Protection 5 a. Galvanic Systems ...................................................................................................................................... 6 1. Design and Construction .................................................................................................................. 6 2. Operation and Maintenance/Inspection ........................................................................................ 6 3 . Repairs ................................................................................................................................................ 6 4 . Testing ................................................................................................................................................. 7 5. Rec ordkeeping ................................................................................................................................... 9 b. I mpressed Current Systems ................................................................................................................. 10 1. Design and Construction ................................................................................................................ 10 2. Operation and Maintenance/Inspection ...................................................................................... 10 3 . Repairs .............................................................................................................................................. 12 4 . Testing ............................................................................................................................................... 13 5. Rec ordkeeping ................................................................................................................................. 14 8. Corrosion Protection for Flexible (flex) Connectors and Short Sections of Metal Piping 15 a. I solation ................................................................................................................................................... 15 b. Cathodic Protection & Testing Flex Connectors and Short Sections of Metal Piping* ................. 18 1. Electrically Isolated Flex Connectors ............................................................................................. 19 2. Electrically Shorted (Continuous) Flex Connectors ..................................................................... 20 3. Flex Connectors in Contact with Water Inside Containment Sump(s) ..................................... 20 4. Flex Connectors Not In Contact with Water Inside Containment Sump (or the Sump is Dry) and an Anode Is Attached .............................................................................................................. 21 5. Flex Connector(S)/Piping in a “Partially Contained Sump” ......................................................... 21 6. Short STP Piping Sections: .............................................................................................................. 22"
Text Inserted�
Text
"i"
Text Inserted�
Text
"9. Internally Lined Tanks 22 a. For internally lined tanks with a CP system (tanks with a properly operating CP system do not require periodic inspections of the internal lining) ........................................................................... 22 b. Internal Lining of Tanks as a Tank Repair ........................................................................................... 22 c. Lining And Relining Tanks to Assure Compatibility with Alternative Fuels .................................... 24 REFERENCES 25 APPENDICES 26 APPENDIX 1 : STRUCTURE-TO-SOIL TEST PROCEDURE FOR GALVANIC CATHODIC PROTECTION SYSTEMS 27 APPENDIX 2 : CONTINUITY TESTING PROCEDURE FOR CATHODIC PROTECTION SYSTEMS 30 APPENDIX 3 : STRUCTURE-TO-SOIL TEST PROCEDURE FOR IMPRESSED CURRENT CATHODIC PROTECTION SYSTEMS 32 APPENDIX 4 : TEST PROCEDURE FOR FLEX CONNECTORS (INCLUDING SHORT SECTIONS OF METAL PIPING)"
Text Inserted�
Text
"DRAFT"
Text Inserted�
Text
"35 APPENDIX 5 : COMMONLY USED DEFINITIONS 38 APPENDIX 6 : IMPRESSED CURRENT CATHODIC PROTECTION TESTING SURVEY 41 APPENDIX 7 : GALVANIC CATHODIC PROTECTION TESTING SURVEY 51 APPENDIX 8 : IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM 60-DAY RECORD OF RECTIFER OPERATION FORM 60 ii"
Text Replaced�
Text
[Old]: "EFFECTIVE DATE – October 1, 2015" [New]: "1. DISCLAIMER This document is guidance only and does not affect legal rights or obligations. Agency decisions in any particular case will be made applying applicable laws and regulations to the specific facts. Mention of trade names or commercial products does not constitute an endorsement or recommendation for use. 2." Font "Open Sans,Bold" changed to "OpenSans-Bold".Font-size "11.04" changed to "12".
Text Inserted�
Text
"DRAFT"
Text Replaced�
Text
[Old]: "and always available on the Division’s website." [New]: "on the Division’s website https://www.tn.gov/environment/program-areas/ust-underground-storage-tanks.html. 3." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "http://www.state.tn.us/sos/rules/0400/0400-18/0400-1801.20130121.pdf" [New]: "https://publications.tnsosfiles.com/rules/0400/0400-18/0400-18.htm" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "2" [New]: "1" Font "Times New Roman" changed to "OpenSans".Font-size "12" changed to "10.98".
Page 68: Total Changes Content 821 - tn.gov

3

APPLICABILITY

Rule .02(4)(c)1. requires that all corrosion protection systems must be designed, constructed, operated, and

maintained to continuously provide corrosion protection to the metal components of that portion of the tank

and piping that “routinely contains petroleum” and is in contact with the ground and/or any liquid. These

components include:

1. Any bare steel (no dielectric coating) tanks or piping*

2. STI-P3® tank systems which original anodes have become depleted

3. All below-grade piping (including piping that is partially above-grade if continuous with below grade

piping) including remote fill piping

4. Metal flexible connectors including any sections of piping between dispensers or STP heads and the

respective flexible connectors regardless of length.

5. Any tank or piping with a coating that is determined not to be acceptable by the Division as a “suitable

dielectric coating” (Note: dielectric coatings alone are not adequate corrosion protection)*

6. Tank systems constructed with suitable dielectric coatings (such as fiberglass or urethane, ACT-100®

tanks) that a corrosion expert requires to be bonded into the same cathodic protection system of

other tanks within or near the same tankhold.

7. Or, any other system component that could potentially cause a release of petroleum into the

environment as a result of corrosion failure unless a corrosion expert determines CP is not required.

* This only applies to tank systems that were required to be upgraded by the Federal deadline of December

1998 (Tennessee, December 1999). Existing tank systems and piping currently in operation that did not

meet the upgrading requirements by these dates cannot be upgraded and are considered substandard

and shall be immediately and permanently closed by removal or closure-in-place as required by rule

.07(2).

The Division does not require corrosion protection on the following components of an underground tank

system:

1. Automatic Tank Gauge (ATG) risers and

2. Vapor recovery risers

3. Fill risers, but only if the fill riser is fitted with a drop tube. See rule .02(4)(b)5. If there is no drop

tube, the fill riser must be corrosion protected

4. Vent lines

5. The STP riser including the STP head

6. Interstitial Monitoring risers or any other riser not routinely containing petroleum

REQUIREMENTS

CORROSION SYSTEM DESIGN AND CONSTRUCTION

A Corrosion Expert must design all “field installed” corrosion protection systems as required by rules

.02(4)(a)2.(ii) and .02(4)(b)2.(ii). (Field Installed systems include the original or subsequent installation of anodes

or modification to a galvanic corrosion protection system or an Impressed Current System.) This does not

include anodes installed on isolated flexible connectors that may be in STP sumps or under dispensers.

Documentation that the cathodic protection system is designed by a corrosion expert as required by rules

.02(4)(a)2.(ii) and .02(4)(b)2.(ii) must be maintained by the owner and/or operator for inspection by the

Division.

Text Inserted�
Text
"4."
Text Replaced�
Text
[Old]: "Rule .02(4)(c)1. requires that all corrosion protection systems must" [New]: "Rules .02(4)(a), .02(4)(b) and 02(4)(c)1. require that all corrosion protection systems" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "operated," [New]: "operated" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "and" [New]: "and/or" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "the ground and/or any liquid. These components include: 1." [New]: "the ground. The United States Environmental Protection Agency, for the purpose of corrosion protection, interprets the term “ground” to be any naturally occurring substance (e.g., soil, sand, water, gravel, etc.) that can serve as an electrolyte and thereby result in corrosion to a metallic object. These components include, but are not limited to" Font "Open Sans,Bold" changed to "OpenSans".
Text Inserted�
Text
"DRAFT"
Text Inserted�
Text
"1 : a."
Text Replaced�
Text
[Old]: "piping* 2. STI-P3® tank systems which original anodes have become depleted 3." [New]: "piping*; b. STI-P3 ® tank systems with depleted anodes; c." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "piping) including remote fill piping 4. Metal flexible connectors including any sections" [New]: "piping, remote fill piping, and connecting piping for manifolded tanks); d. Metal flexible connectors (including any section" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "STP" [New]: "submersible turbine pump (STP)" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "length. 5." [New]: "length); e." Font "Open Sans,Bold" changed to "OpenSans-Bold".
Text Replaced�
Text
[Old]: "protection)* 6." [New]: "protection)*; f." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "(such as" [New]: "(i.e.," Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "tanks)" [New]: "tanks, etc.)" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "tankhold. 7. Or, any" [New]: "tankhold; or g. Any" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "CP is not required. * This only applies to" [New]: "corrosion protection (CP) is not required. 1 Required by Rule 0400-18-01-.02(4)(c)1" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "tank systems that were required to be" [New]: "*Any tank or piping system meeting this criterion that was not" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "1999). Existing tank systems and piping currently in operation that did not meet the upgrading requirements by these dates cannot be upgraded and are" [New]: "1999) is" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "1." [New]: "a." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "risers and 2. Vapor recovery risers 3. Fill risers, but only" [New]: "risers; b. Vapor recovery risers; c. Fill risers (only" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "tube. See rule .02(4)(b)5. If there is no drop tube, the fill riser must be corrosion protected 4. Vent lines 5. The STP riser including the STP head 6. Interstitial Monitoring risers or any other riser not routinely containing petroleum" [New]: "tube -see rule .02(4)(b)5); d. Vent lines; e. The STP riser including the STP head; f. Interstitial Monitoring risers or any other riser not routinely containing petroleum; g. Manifold" Font "Open Sans" changed to "OpenSans".
Text Deleted�
Text
"REQUIREMENTS"
Text Deleted�
Text
"CORROSION SYSTEM DESIGN AND CONSTRUCTION A Corrosion Expert must design all “field installed” corrosion protection systems as required by rules .02(4)(a)2.(ii) and .02(4)(b)2.(ii). (Field Installed systems include the original or subsequent installation of anodes or modification to a galvanic corrosion protection system or an Impressed Current System.) This does not include anodes installed on isolated flexible connectors that may be in STP sumps or under dispensers. Documentation that the cathodic protection system is designed by a corrosion expert as required by rules .02(4)(a)2.(ii) and .02(4)(b)2.(ii) must be maintained by the owner and/or operator for inspection by the Division."
Text Replaced�
Text
[Old]: "3" [New]: "2" Font "Times New Roman" changed to "OpenSans".Font-size "12" changed to "10.98".
Page 69: Total Changes Content 821 - tn.gov

4

CORROSION EXPERT

Corrosion Expert is defined in rule .01(4) and means a person who, by reason of thorough knowledge of the

physical sciences and the principles of engineering and mathematics acquired by a professional education and

related practical experience, is qualified to engage in the practice of corrosion control on buried or submerged

metal piping systems and metal tanks. Such a person must submit documentation for review by the Division

that they have accreditation or certification as a Corrosion Specialist or Cathodic Protection Specialist by the

National Association of Corrosion Engineers (NACE). If it is determined by the Division that a person has

sufficient experience and education to be qualified to take responsible charge in corrosion control of buried or

submerged metal piping systems and metal tanks, then that person shall be classified by the Division as a

corrosion expert. The Division currently maintains a list of known corrosion experts that may be provided to

owner/operators.

To date, the Division has not made any determinations other than those made by NACE regarding who is

qualified to be a corrosion expert.

Some examples of situations requiring corrosion expert review:

1. Design of Field-Installed Cathodic Protection Systems.

2. Any modification (including repairs) of the Cathodic Protection System, such as addition of

supplemental anodes or other changes in the design or construction of the Cathodic Protection

System.

3. Review of Cathodic Protection System test results indicating anomalies, such as: if stray currents are

affecting metallic structures, inconclusive CP test results, and any other system test results that the

Division determines to require additional expert review.

CATHODIC PROTECTION TESTER

A Cathodic Protection Tester is defined in rule .01(4) and means a person who can demonstrate an

understanding of the principles and measurements of all common types of cathodic protection systems as

applied to buried or submerged metal piping systems and metal tanks. At a minimum, such persons must

have education and experience in soil resistivity, stray current, structure-to-soil potential, and component

electrical isolation measurements of buried metal piping and tank systems.

Testing cathodic protection systems is not required to be performed by a corrosion expert to comply with rule

.02(4)(c)2. The Division requires that all cathodic protection testing performed by a person meeting the

qualifications of a Cathodic Protection Tester. All testing must be conducted in accordance with the

guidelines as detailed in this technical chapter and all results shall be recorded on the official Tennessee

Cathodic Protection Testing Survey Forms (CN-1140 and CN-1309) as required by rule .02(4)(c)2.(iii) and

.03(2)(b)2 .

GENERAL DESIGN AND CONSTRUCTION OF TANKS

Tanks must be properly designed and constructed as required by rule .02(4)(a), so that any portion

underground that routinely contains petroleum and is in contact with the ground and/or liquid is protected

from corrosion by one of the following:

1) Fiberglass-Tank is constructed of fiberglass-reinforced plastic-rule .02(4)(a)1.

Text Replaced�
Text
[Old]: "CORROSION EXPERT Corrosion Expert is defined in rule .01(4) and means a person who, by reason of thorough knowledge of the physical sciences and the principles of engineering and mathematics acquired by a professional education and related practical experience, is qualified to engage in the practice of corrosion control on buried or submerged metal piping systems and metal tanks. Such a person must submit documentation for review by the Division that they have accreditation or certification as a Corrosion Specialist or Cathodic Protection Specialist by the National Association of Corrosion Engineers (NACE)." [New]: "piping siphon assist lines; or h. Vapor recovery assist lines." Font "Open Sans,Bold" changed to "OpenSans".Font-size "11.04" changed to "10.02".
Text Deleted�
Text
"If it is determined by the Division that a person has sufficient experience and education to be qualified to take responsible charge in corrosion control of buried or submerged metal piping systems and metal tanks, then that person shall be classified by the Division as a corrosion expert."
Text Deleted�
Text
"The Division currently maintains a list of known corrosion experts that may be provided to owner/operators. To date, the Division has not made any determinations other than those made by NACE regarding who is qualified to be a corrosion expert."
Text Deleted�
Text
"Some examples of situations requiring corrosion expert review:"
Text Replaced�
Text
[Old]: "Design of Field-Installed Cathodic Protection Systems. 2. Any modification (including repairs) of the Cathodic Protection System, such as addition of supplemental anodes or other changes in the design or construction of the Cathodic Protection System. 3." [New]: "REQUIREMENTS a. General Design" Font "Open Sans" changed to "OpenSans-Bold".Font-size "9.96001" changed to "12".
Text Deleted�
Text
"Review of Cathodic Protection System test results indicating anomalies, such as: if stray currents are affecting metallic structures, inconclusive CP test results, and any other system test results that the Division determines to require additional expert review."
Text Replaced�
Text
[Old]: "CATHODIC PROTECTION TESTER A Cathodic Protection Tester is defined in rule .01(4) and means a person who can demonstrate an understanding of the principles and measurements of all common types of cathodic protection systems as applied to buried or submerged metal piping systems and metal tanks." [New]: "and Construction of Tanks" Font "Open Sans,Bold" changed to "OpenSans-Bold".Font-size "11.04" changed to "12".
Text Deleted�
Text
"At a minimum, such persons must have education and experience in soil resistivity, stray current, structure-to-soil potential, and component electrical isolation measurements of buried metal piping and tank systems."
Text Deleted�
Text
"Testing cathodic protection systems is not required to be performed by a corrosion expert to comply with rule .02(4)(c)2."
Text Deleted�
Text
"The Division requires that all cathodic protection testing performed by a person meeting the qualifications of a Cathodic Protection Tester."
Text Replaced�
Text
[Old]: "All testing must be conducted in accordance with the guidelines as detailed in this technical chapter and all results shall be recorded on the official Tennessee Cathodic Protection Testing Survey Forms (CN-1140 and CN-1309) as required by rule .02(4)(c)2.(iii) and .03(2)(b)2 . GENERAL DESIGN AND CONSTRUCTION OF TANKS Tanks must be properly designed and constructed as required by rule .02(4)(a), so that any portion underground that routinely contains petroleum and is in contact with the ground and/or liquid is protected from corrosion by one of the following: 1) Fiberglass-Tank is constructed of fiberglass-reinforced plastic-rule .02(4)(a)1." [New]: "Tanks must be properly designed and constructed as required by rule .02(4)(a), so that any portion underground that routinely contains petroleum and is in contact with the ground is protected from corrosion by one of the following: 1. Fiberglass-Tank is constructed of fiberglass-reinforced plastic -rule .02(4)(a)1;" Font "Open Sans" changed to "OpenSans".
Text Deleted�
Text
"4"
Page 70: Total Changes Content 821 - tn.gov

5

2) Steel tank with Cathodic Protection-Tank is constructed of steel and is protected from corrosion by

a cathodic protection system (either galvanic cathodic protection or impressed current cathodic

protection)-rule .02(4)(a)2.

3) Composite (Clad)-Tank is constructed of a steel-fiberglass-reinforced-plastic composite-rule .02(4)(a)4.

4) Jacketed-Tank is constructed with a fiberglass-reinforced plastic jacket, which has an interstitial space

between the inner tank and the outer jacket-rule .02(4)(a)4.

5) The tank is constructed of metal without additional corrosion protection measures provided that the

tank is installed at a site that is determined by a corrosion expert not to be corrosive enough to cause

it to have a release due to corrosion during its operational life.-rule .02(4)(a)5.

6) The tank construction and corrosion protection are determined by the Division to be designed to

prevent the release of any petroleum in a manner that is no less protective than any of the previously

mentioned methods of corrosion protection.-rule .02(4)(a)6.

GENERAL DESIGN AND CONSTRUCTION OF PIPING

Piping must be properly designed and constructed, as required by rule .02(4)(b), so that any portion that

routinely contains petroleum and is in contact with the ground and/or liquid is protected from corrosion by

one of the following methods:

1) Non-metallic (rigid or flexible)

a. If installed on or after November 1, 2005, shall meet or exceed the Standard for Safety

established by Underwriters Laboratory in UL 971 - “Non-Metallic Underground Piping for

Flammable Liquids”, July 1, 2005. This requirement shall apply to all new and/or replacement

piping.-rule .02(4)(b)1.(i)

b. Pipe marking or labeling shall comply with the Underwriters Laboratory standard as outlined in

Division rules.-rule .02(4)(b)1.(ii)

2) Metallic

a. Dielectrically coated piping: Piping coated with a suitable dielectric material and has

cathodic protection.-rule .02(4)(b)2.(i)

b. Bare steel with cathodic protection system: Bare steel piping to which a galvanic or impressed

current system has been added.-rule .02(4)(b)2.(ii)

c. Isolation: Metallic piping that is never in contact with the ground and/or liquid (such as

rubber boots acceptable to the Division, excavation of all soil or earthen material that exposes

the entire length of the piping, or installation of any containment device that isolates the piping

from the ground and/or liquids).-rule .02(4)(b)4.

d. The piping is constructed of metal without additional corrosion protection measures provided

that the piping is installed at a site that is determined by a corrosion expert not to be corrosive

enough to cause it to have a release due to corrosion during its operational life.-rule

.02(4)(b)3.(i)

e. The piping construction and corrosion protection are determined by the Division to be

designed to prevent the release of any petroleum in a manner that is no less protective than

any of the previously mentioned methods of corrosion protection. -rule .02(4)(b)4.

METHODS OF CORROSION PROTECTION

Text Replaced�
Text
[Old]: "(either" [New]: "by either" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "protection)-rule .02(4)(a)2." [New]: "protection -rule .02(4)(a)2;" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "composite-rule .02(4)(a)4." [New]: "composite rule .02(4)(a)4;" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "jacket-rule .02(4)(a)4." [New]: "jacket -rule .02(4)(a)4;" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"DRAFT"
Text Replaced�
Text
[Old]: "life.-rule .02(4)(a)5." [New]: "life -rule .02(4)(a)5; or" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "protection.-rule" [New]: "protection -rule" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"3"
Text Replaced�
Text
[Old]: "GENERAL DESIGN AND CONSTRUCTION OF PIPING" [New]: "b. General Design and Construction of Piping" Font "Open Sans,Bold" changed to "OpenSans-Bold".Font-size "11.04" changed to "12".
Text Replaced�
Text
[Old]: "Non-metallic (rigid or flexible) a." [New]: "Non-Metallic (Rigid or Flexible)" Font "Open Sans,Bold" changed to "OpenSans-Bold".Font-size "9.96001" changed to "10.98".
Text Replaced�
Text
[Old]: "piping.-rule .02(4)(b)1.(i) b. Pipe marking or labeling shall comply with the Underwriters Laboratory standard as outlined in Division rules.-rule .02(4)(b)1.(ii)" [New]: "piping. -rule .02(4)(b)1." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "a." [New]: "i." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "protection.-rule .02(4)(b)2.(i) b. Bare steel" [New]: "protection." Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"DRAFT"
Text Inserted�
Text
"-rule .02(4)(b)2.(i). ii. Piping with field-installed"
Text Inserted�
Text
"or other metal"
Text Replaced�
Text
[Old]: "added.-rule .02(4)(b)2.(ii) c." [New]: "added. -rule .02(4)(b)2.(ii). iii." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "(such as rubber boots acceptable to the Division," [New]: "(e.g., metallic piping that is contained inside of a rubber boot that is sealed on each end," Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "any" [New]: "a" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "liquids).-rule .02(4)(b)4. d." [New]: "liquid, etc.). -rule .02(4)(b)4. iv." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "life.-rule .02(4)(b)3.(i) e." [New]: "life. -rule .02(4)(b)3.(i). v." Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"release or threatened release of any stored"
Text Replaced�
Text
[Old]: "METHODS OF CORROSION PROTECTION" [New]: "6. Corrosion System Design and Construction A Corrosion Expert must design all “field installed” corrosion protection systems as required by rules .02(4)(a)2.(ii) and .02(4)(b)2.(ii). Field Installed systems include the original or subsequent installation of anodes or modification to a galvanic corrosion protection system or an Impressed Current System and does not include the installation of anodes on flexible connectors in STP sumps, transition sumps or under dispensers. Documentation that the cathodic protection system was designed by a corrosion expert as required by rules .02(4)(a)2.(ii) and .02(4)(b)2.(ii) must be maintained by the owner and/or operator and be available for inspection by the Division. a. Corrosion Expert Corrosion Expert is defined in rule .01(4) and means a person who, by reason of thorough knowledge of the physical sciences and the principles of engineering and mathematics acquired by a professional education and related practical experience, is qualified to engage in the practice of corrosion control on buried or submerged metal piping systems and metal tanks. Such a person must submit documentation for review by the Division that the person has accreditation or certification as a Corrosion Specialist or Cathodic Protection Specialist by" Font "Open Sans,Bold" changed to "OpenSans-Bold".Font-size "11.04" changed to "12".
Text Replaced�
Text
[Old]: "5" [New]: "4" Font "Times New Roman" changed to "OpenSans".Font-size "12" changed to "10.98".
Page 71: Total Changes Content 821 - tn.gov

6

There are two acceptable methods available to meet corrosion protection requirements: Galvanic CP Systems

and Impressed Current CP Systems. Metals corrode naturally by the loss of electrons from the surface of the

metallic components out into the surrounding soil. Corrosion protection systems reverse this flow of electrons

inhibiting the natural process. Galvanic Systems are “passive” corrosion protection systems that utilize anodes

made of metals such as magnesium and zinc that corrode instead of the tank or piping. Due to the difference

of the innate electric potentials, a naturally occurring electric current flows from the anodes through moisture

in the ground to the tank and/or piping resulting in the protection of the metal components. Impressed

Current Systems utilize the same principle but with the addition of an external direct current of electricity

applied to the system which supplies the flow of electrons necessary to reverse the corrosion process.

1) Galvanic Systems are comprised of sacrificial anodes that were installed on the ends of the tank by

the tank manufacturer such as sti-P3® tanks. These systems may include anodes which were added

subsequent to installation such as supplemental anodes bonded to sti-P3® tanks when the original

anodes have become depleted. Not only can these systems be installed to protect the tanks, but also

steel piping which includes flexible connectors.

2) Impressed Current Systems are always “Field Installed” systems that are added subsequent to the

original installation of the tank system. These systems are designed to protect previously unprotected

steel tanks, tanks that the attached anodes (sti-P3® tanks) have become depleted, or tanks which were

previously lined internally. These systems can be installed to protect the tanks as well as electrically

continuous steel piping.

GALVANIC SYSTEMS

1) Design and Construction

Galvanic systems are also known as sacrificial anode systems because an anode (usually zinc or

magnesium) corrodes instead of the metal structure. Because the anode corrodes instead of the metal

it is protecting, the anode sacrifices itself. Sacrificial anodes are connected directly to the structure to

be protected by either welding or mechanical connection of lead wires. Galvanic systems are generally

limited to those tank components that are well coated with a dielectric material (sti-P3® tanks or

fusion bonded epoxy coated steel piping) because the available current output of these systems is low.

Attempts to protect large areas of uncoated tanks or long runs of piping is generally not practical

because the useful life of the anodes is too short or the number of anodes needed is too great.

2) Operation and maintenance/inspection

All galvanic systems must be operated and maintained to continuously provide corrosion protection to

the metal components of that portion of the tank, piping and underground ancillary equipment that

routinely contains petroleum and is in contact with the ground and/or liquid. See rules .02(4)(a)2. and

.02(4)(b)2. Since galvanic systems are “passive” corrosion protection systems, rule .02(4)(c)2.(i) requires

only periodic testing every three years to determine if the system is operating properly and the anodes

are supplying sufficient protection. There are usually no maintenance requirements for galvanic

systems and are limited to repairs to such things as bonding wires for anodes that have been added

subsequently to the original installation of the tanks. Due to the nature of construction of the original

system or subsequently added anodes, there are no components of galvanic systems usually requiring

periodic inspection unless the anode bonding wiring is visible and/or accessible as described above.

3) Repairs

a. Repairs include but are not limited to the following: replacement of anode(s) if depleted, repair

or replacement of damaged bonding wires, and repair/replacement of system components to

Text Inserted�
Text
"the National Association of Corrosion Engineers (NACE). If it is determined by the Division that a person has sufficient experience and education to be qualified to take responsible charge in corrosion control of buried or submerged metal piping systems and metal tanks, then that person shall be classified by the Division as a corrosion expert. The Division maintains a list of corrosion experts that routinely perform work in the State of Tennessee. This list is available on the Division’s website. Some examples of situations requiring corrosion expert review: Design of Field-Installed Cathodic Protection Systems 2 . Any modification (including repairs) of the Cathodic Protection System, such as adding or replacing anodes, or other changes in the design or construction of the Cathodic Protection System. 3 Review of Cathodic Protection System test results indicating anomalies, such as: if stray currents are affecting metallic structures, inconclusive CP test results, and any other system test results that the Division determines to require additional expert review."
Text Inserted�
Text
"DRAFT"
Text Replaced�
Text
[Old]: "There are two acceptable methods available to meet corrosion protection requirements: Galvanic CP Systems and Impressed Current CP Systems. Metals corrode naturally by the loss of electrons from the surface of the metallic components out into the surrounding soil." [New]: "4 b. Cathodic Protection Tester A Cathodic Protection Tester is defined in rule .01(4) and means a person who can demonstrate an understanding of the principles and measurements of all common types of cathodic protection systems as applied to buried or submerged metal piping systems and metal tanks. At a minimum, such persons must have education and experience in soil resistivity, stray current, structure-to-soil potential, and component electrical isolation measurements of buried metal piping and tank systems. Testing cathodic protection systems is not required to be performed by a corrosion expert to comply with rule .02(4)(c)2. The Division requires that all cathodic protection testing performed by a person meeting the qualifications of a Cathodic Protection Tester. All testing must be conducted in accordance with the guidelines detailed in this technical chapter and all results shall be recorded on the official Tennessee Cathodic Protection Testing Survey Forms (CN-1140 and CN-1309) as required by rule .02(4)(c)2.(iii) and the records be maintained in accordance with rule .03(2)(b)5 . 7. Methods of Corrosion Protection There are two acceptable methods available to meet corrosion protection requirements: Galvanic CP Systems and Impressed Current CP Systems. 5 Metals corrode naturally by the loss of electrons from the surface of the metallic components out into the ground." Font "Open Sans" changed to "OpenSans".Font-size "9.96001" changed to "6.48".
Text Inserted�
Text
"2 Required by Rule 0400-18-01-.02(4)(a)2(ii) 3 Required by Rule 0400-18-01-.02(4)(c)1 4 Required by Rule 0400-18-01-.03(2) 5 Required by Rule 0400-18-01-.02(4)(a)2"
Text Inserted�
Text
"5"
Text Replaced�
Text
[Old]: "1)" [New]: "a." Font "Open Sans,Bold" changed to "OpenSans".
Text Replaced�
Text
[Old]: "anodes that were installed on the ends of the tank by the tank manufacturer such as sti-P3® tanks. These systems may include anodes which were added subsequent to installation such as supplemental anodes bonded to sti-P3® tanks when the original anodes have become depleted. Not only can these systems be installed to protect the tanks, but also steel piping which includes flexible connectors. 2)" [New]: "anodes installed to cathodically protect metallic components (tanks, piping, ancillary equipment and/or flex connectors) in contact with soil or liquid. Tanks with anodes that were factory installed on the ends of the tank by the tank manufacturer are referred to as a sti-P3 ® tank(s). Depending on the situation, supplemental anodes can be bonded to a sti-P3 ® tank(s) when the original anodes have become depleted. b." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "that the" [New]: "with" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"that"
Text Replaced�
Text
[Old]: "steel piping. GALVANIC SYSTEMS" [New]: "metallic piping. a. Galvanic Systems" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "structure. Because the anode corrodes instead of the metal it is protecting, the anode sacrifices itself." [New]: "structure (i.e., the anode sacrifices itself (corrodes) to protect the metal to which it is connected)." Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"DRAFT"
Text Inserted�
Text
"6"
Text Deleted�
Text
"the"
Text Replaced�
Text
[Old]: "maintenance/inspection All galvanic systems must be operated and maintained" [New]: "Maintenance/Inspection Operate and maintain all galvanic systems" Font "Open Sans,Bold" changed to "OpenSans-Bold".Font-size "9.96001" changed to "10.98".
Text Replaced�
Text
[Old]: "Since galvanic systems are “passive” corrosion protection systems, rule .02(4)(c)2.(i) requires only periodic testing every three years" [New]: "Periodic testing of galvanic systems is required every three years, rule .02(4)(c)2.(i)," Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "There are usually no maintenance requirements for galvanic systems and are limited to repairs to such things as" [New]: "Maintenance/repair of galvanic systems is minimal and, if required, is typically limited to such things as repairs to" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "tanks. Due to the nature of construction of the original system or subsequently added anodes, there are no components of galvanic systems usually requiring periodic inspection unless the anode bonding wiring is visible and/or accessible as described above. 3) Repairs a. Repairs include but are not limited to the following: replacement of anode(s) if depleted," [New]: "tanks or reburying of visibly exposed wiring. 3. Repairs i. Repairs include, but are not limited to, the following: replacement of depleted anode(s)," Font "Open Sans" changed to "OpenSans".
Page 72: Total Changes Content 821 - tn.gov

7

achieve isolation. If anodes are added to a sti-P3® tank with depleted anodes, that constitutes

a “Field Installation” and requires that the CP system be designed by a corrosion expert,

according to rules .02(4)(a)2.(ii) and .02(4)(b)2.(ii). All documents related to the repair and

design approval by a corrosion expert must be maintained for the life of the system and

transferred to any new owner of the system. See rules .02(4)(c)5.(iii) and .03(2)(d). For replacing

depleted anodes on STIP-3 or steel product tanks, all design and construction requirements

shall comply with Steel Tank Institute’s “Recommended Practice for the Addition of

Supplemental Anodes to sti-P3® USTs” (R972) revised January 2006 (or later), or have written

repair design calculations signed by a corrosion expert.

b. The Division will allow the addition of an impressed current system, that is designed by a

corrosion expert as required by rules .02(4)(a)2.(ii) and .02(4)(b)2.(ii), to a STI-P3 tank as a repair

of the cathodic protection system when the anodes on a cathodically protected tank are

depleted. A bare steel tank which never met the 1999 upgrade deadlines may not be upgraded

by addition of an impressed current system. Records of this repair must be maintained for the

operational life of the UST system as required by rules .02(7)(f) and transferred to any new

owner as required by rule .03(2)(d).

c. Within six (6) months following a repair of a cathodically protected system, the system shall be

tested in accordance with rule .02(7)(e) to ensure that it is operating properly and all results

shall be recorded on the official Tennessee Cathodic Protection Testing Survey Forms (CN-1140

and CN-1309) as required by rule .02(4)(c)2.(iii) and .03(2)(b)2 .

4) Testing

a. A Cathodic Protection Tester must inspect all galvanic systems for proper operation within six

(6) months of installation and at least every three (3) years thereafter and as stated above

tested within six (6) months after a repair. The system must be functioning as designed and is

effectively preventing corrosion. See rule .02(4)(c)2. Testing shall be performed in accordance

with Appendix 1 and as directed according to instructions in state form CN-1140.

b. All UST systems to which sacrificial anodes have been added for the purpose of replacing or

enhancing an existing galvanic system shall be tightness tested. The tightness test shall be

conducted no later than six (6) months, but no sooner than three (3) months, following the

addition of the anodes. See rules .02(4)(c)3. and .02(4)(c)5.(iii). The Division may not require

tightness testing of flex connectors to which anodes have been added. Records must be

transferred to any new owner as required by rule .03(2)(d).

c. Structures utilizing galvanic cathodic protection will be considered adequately protected

according to the criterion in Section 8 of NACE TM0101 when “A negative (cathodic) potential of

at least 850 mV with the protective current applied. This potential is measured with respect to

a saturated copper/copper sulfate reference electrode contacting the electrolyte. Voltage

drops other than those across the structure to electrolyte boundary must be considered for

valid interpretation of this measurement.” This criterion is also known as “850 on” and is not

applicable to impressed current systems.

Text Inserted�
Text
"supplemental"
Text Replaced�
Text
[Old]: "to a sti-P3® tank with depleted anodes, that constitutes a “Field Installation” and requires that the CP system be designed by" [New]: "or new anodes are installed on a sti-P3® tank, all design and construction requirements must comply with Steel Tank Institute’s “Recommended Practice for the Addition of Supplemental Anodes to sti-P3® USTs” (R972) revised December 2010 (or current version). If, based on the design calculations, greater than 30 milliamperes of current 6 Required by Rule 0400-18-01-.02(4)(c)1" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "a corrosion expert, according to rules" [New]: "is needed to achieve protection as specified in document R972, a corrosion expert will need to design the corrosion system. This will constitute a “Field Installation” – rules ii." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "system. See rules .02(4)(c)5.(iii) and .03(2)(d). For replacing depleted anodes on STIP-3 or steel product tanks, all design and construction requirements shall comply with Steel Tank Institute’s “Recommended Practice for the Addition of Supplemental Anodes to sti-P3® USTs” (R972) revised January 2006 (or later), or have written repair design calculations signed by a corrosion expert. b. The Division will allow the addition of an impressed current system, that is designed by a corrosion expert as required by rules .02(4)(a)2.(ii) and .02(4)(b)2.(ii), to a STI-P3 tank as a repair of the cathodic protection system when the anodes on a cathodically protected" [New]: "system -rules .02(4)(c)5(ii), .02(4)(c)5.(iii), .03(2)(b)5 and .03(2)(d). The Division will allow the addition of an impressed current system, that is designed by a corrosion expert as required by rules .02(4)(a)2.(ii) and .02(4)(b)2.(ii), to a STI-P3® tank as a repair of the cathodic protection system when the anodes on a" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: ".02(7)(f)" [New]: ".02(7)(h)" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "c." [New]: "iii." Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"DRAFT"
Text Replaced�
Text
[Old]: ".02(7)(e)" [New]: ".02(7)(f)" Font "Open Sans" changed to "OpenSans".
Text Deleted�
Text
"shall be"
Text Replaced�
Text
[Old]: ".03(2)(b)2 . 4) Testing a." [New]: ".03(2)(b)5. 4. Testing i." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "corrosion. See rule .02(4)(c)2. Testing shall be performed in accordance with Appendix 1 and as directed according to instructions in state form CN-1140. b. All UST systems to which sacrificial" [New]: "corrosion per rule .02(4)(c)2. Perform all testing in accordance with the instructions in Appendix 1 and 2 of this Technical Chapter, and the Galvanic Cathodic Protection Testing Survey Form (CN1140).7 ii. All UST systems to which" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "may" [New]: "generally does" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "c." [New]: "iii." Font "Times New Roman" changed to "OpenSans".Font-size "12" changed to "10.02".
Text Deleted�
Text
"according to the criterion in Section 8 of NACE TM0101"
Text Inserted�
Text
"8"
Text Inserted�
Text
"For a more detailed discussion, see “Measurement Techniques Related to Criteria for Cathodic Protection of Underground Storage Tank Systems” (NACE Standard TM0101, Section 8). 7 Required by Rule 0400-18-01-.03(2)(b)5 8 Required by Rule 0400-18-01-.02(4)(c)2"
Page 73: Total Changes Content 821 - tn.gov

8

NOTE: A Cathodic Protection Tester may not use a cathodic protection test station (PP4®

) that was

permanently installed during the original installation of tank system to obtain potential

measurements during a cathodic protection test. Also, a cathodic protection test wire (PP2®

) may not

be used unless it has been demonstrated that the wire is continuous with the tank bottom. This is

because of continuity issues, unknown location of wire contact point and/or deterioration of the

originally installed reference cell resulting in incorrect potential readings.

5) Recordkeeping

Records must be maintained in accordance with the following:

a. The CP system is to be tested every three (3) years and the results of the last two (2) tests must

be maintained and made available upon request by the Division. See rules .02(4)(c)5.(i) and

.02(4)(c)2.

b. A record of the addition of sacrificial anodes to an existing Galvanic System must be retained for

the remaining operational life of the underground storage tank system and such records must be

Text Replaced�
Text
[Old]: "(PP4" [New]: "(such as PP4" Font "Open Sans,Bold" changed to "OpenSans".
Text Inserted�
Text
"DRAFT"
Text Inserted�
Text
"8"
Text Replaced�
Text
[Old]: "(PP2" [New]: "(such as PP2" Font "Open Sans,Bold" changed to "OpenSans".
Text Replaced�
Text
[Old]: "This is because of continuity issues, unknown location of wire contact point" [New]: "8 The reason for not using a test station and/or test wire is because of possible continuity issues, unknown location of wire contact point," Font "Open Sans,Bold" changed to "OpenSans-Bold".Font-size "9.96001" changed to "6.48".
Text Replaced�
Text
[Old]: "cell resulting" [New]: "cell. Any of which can result" Font "Open Sans,Bold" changed to "OpenSans".
Text Replaced�
Text
[Old]: "5)" [New]: "5." Font "Open Sans,Bold" changed to "OpenSans-Bold".Font-size "9.96001" changed to "10.98".
Text Replaced�
Text
[Old]: "a." [New]: "i." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "b." [New]: "ii." Font "Open Sans" changed to "OpenSans".
Page 74: Total Changes Content 821 - tn.gov

9

transferred in accordance with Division rules at the time of ownership transfer. See rules

.02(4)(c)5.(ii) and .03(2)(d).

c. The results of tightness testing required when sacrificial anodes have been added for the

purpose of replacing or enhancing an existing Galvanic System must be retained for the

remaining operational life of the underground storage tank system. Such records must be

transferred in accordance with Division rules at the time of ownership transfer. See rules

.02(4)(c)3., .02(4)(c)5.(iii) and .03(2)(d).

d. The results of any cathodic protection system repairs must be maintained for the operational life

of the system. See rule .02(7)(f).

e. Records Transfer. Upon transfer of ownership, including, but not limited to, sale of the tank

system, originals and/or copies of all documents required for recordkeeping of corrosion

protection systems shall be transferred to the new owner of the tank system at the time of the

ownership transfer. See rule .03(2)(d).

IMPRESSED CURRENT SYSTEMS

1) Design and construction

All Impressed Current Systems are “Field Installed” systems and thus required to be designed by a

corrosion expert as required by rules .02(4)(a)2.(ii) and .02(4)(b)2.(ii). All design and construction

requirements shall comply with NACE Standards RP 0285 (latest revision) for tanks, and RP 0169 (latest

revision) for piping.

2) Operation and maintenance/inspection

a. All Impressed Current Systems must be operated and maintained to continuously provide

corrosion protection to the metal components of that portion of the tank, piping and

underground ancillary equipment that routinely contains petroleum and is in contact with the

ground and/or liquid. See rule .02(4)(c)1.

b. All Impressed Current Cathodic Protection Systems must be designed to allow

determination of current operating status.

The rectifier must be visually inspected every sixty days, noting that it is turned on and

operating properly. See rule .02(4)(c)4.

The results of these inspections must be recorded on the Impressed Current Cathodic

Protection System 60-day Record of Rectifier Operation Form CN-1282. See rule

.02(4)(c)4.

The 60-day Rectifier Log entries shall include the date of inspection, Rectifier On/Off

status, voltage output if available, amperage output, hour meter reading if available,

name of person inspecting, and any applicable comments. See rule .02(4)(c)4.

The last three visual inspection results (i.e., the last six (6) months) must be maintained

by the owner and/or operator. See rule .02(4)(c)4 and .02(4)(c)5.(iv).

Text Replaced�
Text
[Old]: "in accordance with Division rules" [New]: "to the new owner" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "c." [New]: "iii." Font "Open Sans" changed to "OpenSans".
Text Deleted�
Text
"sacrificial"
Text Inserted�
Text
"DRAFT"
Text Replaced�
Text
[Old]: "in accordance with Division rules at the time of ownership transfer." [New]: "to the new owner." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "d." [New]: "iv." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: ".02(7)(f). e." [New]: ".02(7)(h). v." Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"9"
Text Replaced�
Text
[Old]: "IMPRESSED CURRENT SYSTEMS 1) Design and construction" [New]: "b. Impressed Current Systems 1. Design and Construction" Font "Open Sans,Bold" changed to "OpenSans-Bold".Font-size "11.04" changed to "12".
Text Replaced�
Text
[Old]: "thus" [New]: "are" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "All design and construction requirements shall comply with NACE Standards RP 0285 (latest revision) for tanks, and RP 0169 (latest revision) for piping. 2) Operation and maintenance/inspection a." [New]: "Rule .02(4)(c)1 requires cathodic protections systems to be operated and maintained in accordance with a corrosion expert whose design and construction requirements must comply with NACE Standards SP0285 for tanks, and SP0169 for piping. 2. Operation and Maintenance/Inspection i." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "ground and/or liquid." [New]: "ground." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "b." [New]: "ii." Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"DRAFT"
Text Replaced�
Text
[Old]: "inspecting," [New]: "inspecting the equipment," Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"rectifier"
Text Replaced�
Text
[Old]: "rule .02(4)(c)4" [New]: "rules .02(4)(c)4." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "9" [New]: "10" Font "Times New Roman" changed to "OpenSans".Font-size "12" changed to "10.98".
Page 75: Total Changes Content 821 - tn.gov

10

The following conditions may not be providing continuous corrosion protection as required by rule

.02(4)(c)1.:

A properly operating rectifier but the gauges show either no voltage or current at all,

a malfunctioning rectifier,

the rectifier gauges showing voltage or current flow with the switch in the 'off' position,

the rectifier gauge is spiked indicating the maximum voltage or current flow, or

rectifier logs show an amperage and/ or voltage variance of more than 20% from initial

reading to subsequent readings.

If the Impressed Current System has no electrical power, then it is not providing continuous corrosion protection

as required by rule .02(4)(c)1.

(Unless otherwise directed by the Division, in accordance with rule .02(4)(c)6.(i), UST systems with

impressed current systems which have been turned off or inoperable for a period of less than twelve

months, the tanks and lines shall be tightness tested with additional testing thereafter. In accordance

with rule .02(4)(c)6.(ii), UST systems with impressed current systems which have been turned off or

inoperable for a period of twelve months or more, the tanks shall be permanently closed.)

A CP tester or corrosion expert must determine the cause of the problem and restore the system to a

satisfactory operating condition, and unless directed otherwise by the Division, conduct a test of the CP system

to document that the system is protecting the tanks as required in rule .02(4)(c)6. This test will suffice for the

post repair test required in the rule. The CP tester must engage the services of a corrosion expert when

restoration of the CP system to proper operating condition requires any changes to its design or adjustment to

rectifier output as required by rules .02(4)(a)2.(ii) and .02(4)(b)2.(ii).

This rectifier shown on the following page contains both an ammeter and voltmeter. To verify that the rectifier is

on, these gauges should have values above zero. The readings do not indicate that the system is protecting the

tanks and piping, it only indicates that the unit is operating.

Text Replaced�
Text
[Old]: "not be" [New]: "indicate that the cathodic protection system is not" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: ".02(4)(c)1.: A properly operating rectifier but the gauges show either no voltage or current at all, a malfunctioning rectifier, the rectifier gauges showing voltage or current flow" [New]: ".02(4)(c)1and may require investigation and/or repair: The rectifier meter(s) show either no voltage or current (amperage) at all, The rectifier meter(s) show voltage or current (amperage)" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "the rectifier gauge is spiked indicating the maximum voltage or current flow, or rectifier logs show an amperage and/ or voltage variance of more than 20% from initial reading to subsequent readings." [New]: "No electrical power is being supplied to the impressed current system, The rectifier meter(s) is “spiked” indicating the maximum voltage or current (amperage) rating of the rectifier has been exceeded, Rectifier logs show a current (amperage) and/or voltage variance of more than 20% from initial reading (as indicated on the most recent cathodic protection survey) to any subsequent readings, or An otherwise malfunctioning rectifier." Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"i."
Text Replaced�
Text
[Old]: "Impressed Current System has no electrical power, then it is not providing continuous corrosion protection as required by rule .02(4)(c)1. (Unless otherwise directed by the Division, in accordance with rule .02(4)(c)6.(i), UST systems with impressed current systems which have been turned off or inoperable for a period of less than twelve months, the tanks and lines shall be tightness tested with additional testing thereafter. In accordance with rule .02(4)(c)6.(ii), UST systems with" [New]: "impressed current system(s) has been off or inoperable for less than twelve (12) months, tightness test the tank(s) and line(s) in accordance with rules .04(3)(b) and .04(4)(b). 1. If the results of the tightness test(s) indicate the UST system(s) is in compliance (i.e., both the tank(s) and line(s) pass a tightness test), then: a. Repair the impressed current system (if necessary); 9 b. Place the impressed current system back into operation; c. Tightness test the tank(s) and line(s) between three (3) and six (6) months of placing the system back into operation. 10 2. If the results of the tightness test(s) indicate the UST system(s) is not in compliance (i.e., either the tank(s) or line(s) fail a tightness test), then:" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"DRAFT"
Text Replaced�
Text
[Old]: "impressed current systems which have been turned off or inoperable for a period of twelve months or more, the tanks shall be permanently closed.) A CP tester or corrosion expert must determine the cause of the problem and restore the system to a satisfactory operating condition, and unless directed otherwise by the Division, conduct a test of the CP system to document that the system is protecting the tanks as required in rule .02(4)(c)6. This test will suffice for the post repair test required in the rule." [New]: "a. A release shall be reported to the Division within 72-hours of discovery, and b. Investigated per rules .05(1) through .05(4) and .06 if a release is confirmed. ii. If the impressed current system has been off or inoperable for greater than twelve (12) months: 1. Permanently close the UST system(s) in accordance with rule .07(2), or 2. The tank owners and/or operators shall submit a written request to the Division justifying why the UST system(s) should not be permanently closed. If the Division determines that circumstances warrant further investigation, the Division will send a written response requiring additional action. 11 All repairs (see Section 3 below) to the impressed current system must be designed and approved by a corrosion expert. 12 After repairs, test the impressed current system following the procedures described in Section 4 below. Perform this test within six months of completing the repairs. 13 9 Required by Rule 0400-18-01-.02(4)(c)1 10 Required by Rule 0400-18-01-.02(4)(c)3 11 Required by Rule 0400-18-01-.02(4)(c)(6)(ii)(II) 12 Required by Rule 0400-18-01-.02(4)(c)1 13 Required by Rule 0400-18-01-.02(4)(c)2(i)" Font "Open Sans,Bold" changed to "OpenSans".
Text Replaced�
Text
[Old]: "CP tester must engage the services of a corrosion expert when restoration of the CP system to proper operating condition requires any changes to its design or adjustment to rectifier output as required by rules .02(4)(a)2.(ii) and .02(4)(b)2.(ii). This rectifier shown on the following page contains both an ammeter and voltmeter. To verify that the rectifier is on, these gauges should have values above zero. The readings do not indicate that the system is protecting the tanks and piping, it only indicates" [New]: "following images of a rectifier includes both an ammeter and voltmeter. To verify that the rectifier is on, these meters should have values greater than zero. The readings do not indicate that the system is protecting the tanks and piping, only" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "10" [New]: "11" Font "Times New Roman" changed to "OpenSans".Font-size "12" changed to "10.98".
Page 76: Total Changes Content 821 - tn.gov

11

3) Repairs

Rule .02(7) requires that owners and/or operators of UST systems shall ensure that repairs will prevent

releases due to structural failure or corrosion as long as the UST system is used to store petroleum.

Rules .02(4)(a)2.(ii) and .02(4)(b)2.(ii) require that field installed cathodic protection systems for tanks and

piping be designed by a corrosion expert.

The Division has determined that to comply with rules .02(4)(a)2.(ii), .02(4)(b)2.(ii) and .02(7)(a) a corrosion

expert must be either involved in the design and installation, approve, oversee, or sign off on all repairs

made to cathodic protection systems that affect the operation of the system.

Repairs include, but are not limited to, the following list of activities:

1. Replacing rectifier

2. Adding anodes

3. Replacing broken rectifier components

4. Replacing broken ground wires or anode wires

5. Resolving continuity issues when problems identified and system still does not pass

6. Adding additional structures to an existing CP system.

7. Increasing tap settings on rectifier to achieve passing results

Text Inserted�
Text
"DRAFT"
Text Inserted�
Text
"The"
Text Deleted�
Text
"The"
Text Replaced�
Text
[Old]: "1. Replacing rectifier 2. Adding anodes 3. Replacing broken rectifier components 4. Replacing broken ground wires or anode wires 5. Resolving continuity issues when problems identified and system still does not pass 6. Adding additional structures to an existing CP system. 7. Increasing tap settings on rectifier to achieve passing results" [New]: "14 i. Replacing rectifier; ii. Adding or replacing anodes (except as specified as maintenance – see below); iii. Replacing broken rectifier components; iv. Replacing broken ground wires or anode wires; v. Resolving continuity issues; vi. Adding additional structures to an existing CP system; vii. Increasing tap settings on rectifier to achieve passing results; or viii. Any other system modifications that change the current (amperage) output of the system. Any of these" Font "Open Sans" changed to "OpenSans".Font-size "9.96001" changed to "6.48".
Text Replaced�
Text
[Old]: "11" [New]: "12" Font "Times New Roman" changed to "OpenSans".Font-size "12" changed to "10.98".
Page 77: Total Changes Content 821 - tn.gov

12

These activities require a retest of the CP system within 6 months following the repair to comply with

rules .02(7)(e).

Activities listed below may be considered maintenance and do not require the approval of a corrosion

expert under .02(4)(a)2.(ii), .02(4)(b)2.(ii) and .02(7)(a).:

Maintenance includes, but is not limited to, the following list of activities:

1. Routine CP testing

2. Turning rectifier on and off for testing.

3. Replacing blown fuse in rectifier

4. Reburying anode wires that have surfaced

5. Adding a drive-in rod anode to a single, isolated flex connector.

6. Replacing anodes (limited to same size and location as anode being replaced)

4) Testing

a. A Cathodic Protection Tester must inspect all impressed current systems for proper operation

within six (6) months of installation and at least every three (3) years thereafter. The system must

be functioning as designed and is effectively preventing corrosion. See rule .02(4)(c)2.

b. All UST systems to which sacrificial anodes have been added for the purpose of replacing or

enhancing an existing impressed current system shall be tightness tested. The tightness test shall

be conducted no later than six (6) months, but no sooner than three (3) months, following the

addition of the anodes. See rules .02(4)(c)3. and .02(4)(c)5.(iii). The Division may not require

tightness testing of flex connectors to which anodes have been added. Records must be

transferred to any new owner as required by rule .03(2)(d).

c. Testing shall be performed in accordance with Appendix 3 and as directed according to

instructions in state form CN-1309. Structures utilizing impressed current cathodic protection will

be considered adequately protected, as required by rules .02(4)(c)1. and 2. and .02(7), if they

meet either:

i. The criterion in Section 9 of NACE TM0101: a negative (cathodic) potential of at least 850

mV when the voltage drop from the applied protective current has been eliminated. This

second meter reading is known as the “instant off” and is measured with the protective

current interrupted when the power to the rectifier is cut off, or by using the min/max

function on a meter to capture the instant off reading, or

ii. The criterion in Section 10 of NACE TM0101: when a minimum of 100 mV of cathodic

polarization (either formation or decay) can be measured on the protected structures.

When the current is interrupted, an “instant off” potential is recorded and the structure

under cathodic protection is then allowed to depolarize until a change of at least 100 mV

in potential is observed. Depolarization may take as long as 24 hours in some cases, but

should not exceed 72 hours.

Text Deleted�
Text
"These"
Text Inserted�
Text
"14 Required by Rule 0400-18-01-.01(1)(4)"
Text Inserted�
Text
"of the system"
Text Replaced�
Text
[Old]: ".02(7)(e)." [New]: ".02(7)(f)." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: ".02(7)(a).:" [New]: ".02(7)(a):" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "1." [New]: "i." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "testing 2." [New]: "Testing; ii." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "testing. 3. Replacing blown fuse in rectifier 4. Reburying anode wires that have surfaced 5. Adding a drive-in rod anode to a single, isolated flex connector. 6. Replacing anodes (limited to same size and location as anode being replaced)" [New]: "testing; iii. Replacing blown fuse(s) or voltage/amperage meter in rectifier; iv. Reburying anode wires that have surfaced; or v. Adding or replacing a bag or drive-in rod anode to a flex connector(s)." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "a." [New]: "i." Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"DRAFT"
Text Replaced�
Text
[Old]: "b." [New]: "ii." Font "Open Sans" changed to "OpenSans".
Text Deleted�
Text
"sacrificial"
Text Replaced�
Text
[Old]: "anodes. See" [New]: "anodes per" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "may" [New]: "generally does" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "c. Testing shall be performed in accordance with Appendix 3 and as directed according to instructions in state form CN-1309." [New]: "iii. Perform corrosion testing in accordance with the instructions in Appendix 2 and 3, and the Impressed Current Cathodic Protection Testing Survey Form (CN-1309).15" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "2." [New]: "2.," Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "i." [New]: "16 1." Font "Open Sans" changed to "OpenSans".Font-size "9.96001" changed to "6.48".
Text Replaced�
Text
[Old]: "ii." [New]: "2." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "decay)" [New]: "decay, i.e. shift)" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"15 Required by Rule 0400-18-01-.02(4)(c)2(iii) 16 Required by Rule 0400-18-01-.02(4)(c)2"
Text Replaced�
Text
[Old]: "12" [New]: "13" Font "Times New Roman" changed to "OpenSans".Font-size "12" changed to "10.98".
Page 78: Total Changes Content 821 - tn.gov

13

5) Recordkeeping

Records must be maintained in accordance with the following:

a. The CP system is to be tested every three (3) years and the results of the last two (2) tests must

be maintained and made available upon request by the Division. See rule .02(4)(c)2.(i). and

.02(4)(c)5.(i).

b. The results of the sixty (60) day rectifier inspection shall be recorded on the Impressed Current

CP System 60 Day Record of Rectifier Operation Form CN-1282 and in accordance with rule

.02(4)(c)2.(iii). The results of the last three sixty (60) day rectifier inspections must be retained for

inspection by the Division. As required by rule .02(4)(c)5.(iv) and .03(2)(b)2.

c. The results of any cathodic protection system repairs must be retained for the remaining

operational life of the underground storage tank system and such records must be transferred at

the time of ownership transfer. See rule .02(7)(f) and .03(2)(d).

d. Documentation that the cathodic protection system is designed by a corrosion expert and that a

corrosion expert was involved with repairs made to the system must be maintained by the owner

and/or operator for inspection by the Division. See rules .02(4)(a)2.(ii), .02(4)(b)2.(ii), .02(7)(f), and

.03(2)(b).

e. The results of tightness testing required when sacrificial anodes have been added for the

purpose of replacing or enhancing an existing Impressed Current System must be retained for

the remaining operational life of the underground storage tank system. See rule .02(4)(c)5.(ii) and

.02(7)(f). Such records must be transferred in accordance with Division rules at the time of

ownership transfer. See rule .02(4)(c)5.(ii) and .03(2)(d).

Rectifiers used on USTs are manually controlled for the most part. A corrosion expert will determine the

amount of current necessary in the design to protect the structures and set the rectifier output

accordingly at installation or during modification of the CP system as required by rules .02(4)(a)2.(ii) and

.02(4)(b)2.(ii), and as outlined in the definition of corrosion expert in rule .01(4).

If the rectifier is equipped with a voltmeter, 60 day voltage readings made by tank owners should be

fairly constant unless the rectifier is a constant current rectifier. The tank owner should record current

(amps or milliamps) from an ammeter. The recorded current readings could vary if the anodes are

buried shallow or there are wide seasonal variations in soil moisture content. If the anodes are buried at

least 8 feet deep, then measured current output should remain fairly constant. Any variation in

current and/or voltage of more than 20% from initial reading to subsequent readings, must be

investigated and repaired if necessary.

CORROSION PROTECTION FOR FLEXIBLE (FLEX) CONNECTORS

Flex connectors are braided stainless steel fittings used to make connections from a product line to a dispenser

or submersible pump. A braided steel mesh protects an interior plastic or non-metallic hose that carries

petroleum. There are two different ways to protect flex connectors from corrosion: isolation and cathodic

protection.

Text Replaced�
Text
[Old]: "a." [New]: "i." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "Division. See rule" [New]: "Division per rules" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "b." [New]: "ii." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "CN-1282" [New]: "(CN-1282)" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "Division. As required by rule" [New]: "Division as required by rules" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: ".03(2)(b)2. c." [New]: ".03(2)(b)5. iii." Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"DRAFT"
Text Replaced�
Text
[Old]: "transfer. See rule .02(7)(f) and .03(2)(d). d." [New]: "transfer per rules .02(7)(h) and .03(2)(d). iv." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "Division. See" [New]: "Division per" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: ".02(7)(f)," [New]: ".02(7)(h)," Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "e." [New]: "v." Font "Open Sans" changed to "OpenSans".
Text Deleted�
Text
"sacrificial"
Text Replaced�
Text
[Old]: "system. See rule .02(4)(c)5.(ii) and .02(7)(f)." [New]: "system per rules .02(4)(c)5.(ii) and .02(7)(h)." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "transfer. See rule .02(4)(c)5.(ii) and .03(2)(d). Rectifiers used on USTs" [New]: "transfer per rules.03(2)(d). Rectifiers used on UST systems" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"metallic"
Text Inserted�
Text
"the"
Text Replaced�
Text
[Old]: "to subsequent readings, must be investigated and repaired if necessary. CORROSION PROTECTION FOR FLEXIBLE (FLEX) CONNECTORS" [New]: "(as determined by the most recent 3-year cathodic protection test) to a subsequent reading must be investigated and repaired, if necessary. 17 17 Required by Rule 0400-18-01-.02(4)(c)1" Font "Open Sans,Bold" changed to "OpenSans-Bold".
Text Inserted�
Text
"8. Corrosion Protection for Flexible (flex) Connectors and Short Sections of Metal Piping This section does not apply to UST system(s) that utilize Interstitial Monitoring as a method of release detection for product piping because the referenced piping components are required to be in containment sumps that remain dry per rules .02(2)(b)1(ii) and .04(4)(c)1."
Text Replaced�
Text
[Old]: "There are two different ways to protect flex connectors" [New]: "Short sections of metal piping can include swing joints, elbows, valves, STP piping stubs, unions for suction piping, dispenser piping, etc. There are two primary methods to protect flex connectors and short sections of metal piping" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "13" [New]: "14" Font "Times New Roman" changed to "OpenSans".Font-size "12" changed to "10.98".
Page 79: Total Changes Content 821 - tn.gov

14

1) Isolation

Isolation means keeping a flex connector free from all contact with ground and/or water. If a sump can

be kept free of water so that the flex connector is never exposed to soil and/ or water, then no further

action is necessary under rule .02(4)(b). If the flex connector can come in contact with ground and/or

water, then another means of achieving isolation, such as isolation boots, will be necessary to comply

with rule .02(4)(b). When used in the context of isolation, water in this Technical Chapter is understood to

be a synonymous term for electrolyte as used by NACE.

Isolation boots are plastic materials made for isolating flex connectors and are placed around the entire

flex connector and secured. Isolation boots may be either one piece “sleeves” which slip over a flex

connector and are secured at both ends with nylon zip ties, or stainless steel band clamps, also known as

radiator clamps. Another design is a boot that is heat shrunk directly to a flex connector.

A third kind of isolation boot is a boot that is applied around the pipe and “zipped” or secured with nylon

ties, or possibly Velcro fasteners. When boots show signs of degradation they must be replaced. Isolation

boots must be secured at both ends in a manner that prevents the flex connector from coming in contact

with soil or water to comply with rule .02(4)(b) and .02(4)(c)1. Flex connectors which cannot be isolated

from contact with soil or water are not corrosion protected, and cathodic protection is required if

isolation cannot be achieved in accordance with rules .02(4)(b)2. and .02(4)(c)1.

Following a limited study in 2001 by the Division, a decision was made not to approve the use of tape wraps

alone to provide adequate corrosion protection to flex connectors and metallic piping components. See rule

.02(4)(b)4. The study showed that exposure to hydrocarbons compromised the integrity of the rubberized

tape material. Adhesive tapes provide some protection to metallic surfaces, but under direct burial

conditions or exposure to water or other electrolyte, any exposed metal would be subject to corrosion even

in the absence of petroleum. Another concern was a reduced likelihood of achieving proper installation

under field application conditions, and no assurance that proper application techniques would be used by

adequately trained individuals. Tape-wrapped flex connectors must also have a form of galvanic or

impressed current cathodic protection, or the flex connector must be situated so that it is never exposed to

soil and/or water in order to meet the requirements of rule .02(4)(b)2. and .02(4)(b)4.

One- piece Isolation boot

Zip boot

Text Replaced�
Text
[Old]: "1) Isolation Isolation means keeping a flex connector free from all contact with" [New]: "a. Isolation The piping components are considered isolated if they are not in contact with the" Font "Open Sans,Bold" changed to "OpenSans-Bold".Font-size "9.96001" changed to "12".
Text Inserted�
Text
"DRAFT"
Text Replaced�
Text
[Old]: "sump can be kept free of water so that the flex connector is never exposed to soil and/ or water, then no further action is necessary under rule .02(4)(b). If the flex connector can come in contact with ground and/or water, then another means of achieving isolation, such as isolation boots, will be necessary to comply with rule .02(4)(b). When used in the context of isolation, water in this Technical Chapter is understood to be a synonymous term for electrolyte as used by NACE. Isolation boots are plastic materials made for isolating flex connectors and are placed around the entire flex connector and secured. Isolation boots may be either one piece “sleeves” which slip over a flex connector and are secured at both ends with nylon zip ties, or stainless steel band clamps, also known as radiator clamps. Another design is a boot that is heat shrunk directly to a flex connector. A third kind of isolation boot is a boot that is applied around the pipe and “zipped” or secured with nylon ties, or possibly Velcro fasteners. When boots show signs of degradation they must be replaced. Isolation boots must be secured at both ends in a manner that prevents the flex connector from coming in contact with soil or water to comply with rule .02(4)(b) and .02(4)(c)1. Flex connectors which cannot be isolated from contact with soil or water are not corrosion protected, and cathodic protection is required if isolation cannot be achieved" [New]: "dry sump serves that purpose, then no further action is necessary. If all or part of the piping components are in contact with the ground and/or water at any time (whether in a containment sump or not), then another means of achieving isolation will be necessary to comply with rule .02(4)(b). Isolation boots that prevent the piping component from being in contact with soil and/or water, or removing the soil that is in contact with the piping components can be used to achieve this goal. If the piping components cannot be completely isolated, the addition of cathodic protection is required (see Item #2 below) in accordance with rule .02(4)(b)2 and .02(4)(c)1. Isolation boots are typically constructed of either a plastic or rubber material that wraps around the entire piping component and secured. Isolation boots may be either one piece “sleeves” which slip over a flex connector and are secured at both ends with nylon zip ties, or stainless-steel band clamps, also known as radiator (hose) clamps. Other designs are boots that are heat shrunk directly to a flex connector. Also, some boots are wrapped around the flex connector/pipe and are secured with zippers, nylon ties, or Velcro fasteners. If isolation boots show signs of degradation they must be replaced. Isolation boots must be secured at both ends in a manner that prevents the flex connector from coming in contact with soil or water. Flex connectors which cannot be isolated from contact with soil or water are not corrosion protected; therefore, cathodic protection is required" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"DRAFT"
Text Replaced�
Text
[Old]: "Zip boot One-piece Isolation boot Following a limited study in 2001 by the Division, a decision was made not to approve the use of tape wraps alone to provide adequate corrosion protection to flex connectors and metallic piping components." [New]: "One Piece Isolation Boot Zip Boot The use of tape wraps as a standalone method of isolating flex connectors and/or other piping components is not an acceptable method" Font "Open Sans" changed to "OpenSans".
Text Deleted�
Text
"See rule .02(4)(b)4."
Text Replaced�
Text
[Old]: "The study showed that exposure to hydrocarbons compromised the integrity of the rubberized tape material. Adhesive tapes provide some protection to metallic surfaces, but under direct burial conditions or exposure to water or other electrolyte, any exposed metal would be subject to corrosion even in the absence of petroleum. Another concern was a reduced likelihood of achieving proper installation under field application conditions, and no assurance that proper application techniques would be used by adequately trained individuals. Tape-wrapped flex connectors must also have a form of galvanic or impressed current cathodic protection, or the flex connector must be situated so that it is never exposed to soil and/or water in order to meet the requirements of rule .02(4)(b)2. and .02(4)(b)4." [New]: "of corrosion protection; therefore, tape-wrapped flex connectors (or other piping components) must also have a form of galvanic or impressed current cathodic protection." Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"See rule .02(4)(b)4."
Text Replaced�
Text
[Old]: "14" [New]: "15" Font "Times New Roman" changed to "OpenSans".Font-size "12" changed to "10.98".
Page 80: Total Changes Content 821 - tn.gov

15

2) Cathodic Protection

Sacrificial anodes may be attached to isolated flex connectors to achieve cathodic protection. A sacrificial

anode is a less noble metal like zinc or magnesium alloys intentionally connected to form a galvanic cell with

a more noble metal for the purpose of protecting the more noble metal from corrosion. Some flex

connectors have a circular piece of anode material attached during manufacturing. If a factory designed

anode is not present, cathodic protection can be added in the field. A spike anode (drive-in rod anode) is

attached with a clamp, and then driven into the soil/backfill next to the piping. Sacrificial anodes can be

connected to the flex connector at the submersible pump or under the dispenser. Also bracelet anodes can

be attached with a U-bolt around the flex connector. In all cases the anodes must be in contact with backfill

for the anode to work properly. Cathodic protection systems must be tested every three years as required

by rule .02(4)(c)2.(i).

Drive-in rod anodes

Bracelet anode

Text Deleted�
Text
"2)"
Text Replaced�
Text
[Old]: "isolated flex connectors to achieve cathodic protection. A sacrificial anode is a less noble metal like zinc or magnesium alloys intentionally connected to form a galvanic cell with a more noble metal for the purpose of protecting the more noble metal from corrosion. Some flex connectors have a circular piece of anode material attached during manufacturing. If a factory designed anode is not present, cathodic protection can be added in the field. A spike anode (drive-in rod anode) is attached with a clamp, and then driven into the soil/backfill next to the piping. Sacrificial anodes can be connected to the flex connector at the submersible pump or under the dispenser. Also bracelet anodes can be attached with a U-bolt around the flex connector. In all cases the anodes must be in contact with backfill for the anode to work properly." [New]: "piping components under the dispenser or at the submersible pump, for example, to achieve cathodic protection. Typically, sacrificial anodes like a spike anode (drive-in rod anode) or bag anode are added in the field by burying them in the ground adjacent to the piping and connecting a bond wire between the anode and the component that requires cathodic protection. If the piping component that requires protection is only in contact with water, it is recommended that a “bare” anode (not a bag anode) be placed in the water adjacent to the piping and connected as described above. Less common types of anodes are bracelet anodes that are attached with a U-bolt around the piping component or anodes that are factory fitted to the flex connector (donut anodes). Regardless of the type, the anode must be in contact with the ground or water for it to work properly. 18" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"18 Required by Rule 0400-18-01-.02(4)(c)1"
Text Inserted�
Text
"16"
Text Inserted�
Text
"Drive in rod anode Bracelet Anode"
Text Inserted�
Text
"DRAFT"
Text Deleted�
Text
"anodes Bracelet"
Text Replaced�
Text
[Old]: "15" [New]: "17" Font "Times New Roman" changed to "OpenSans".Font-size "12" changed to "10.98".
Page 81: Total Changes Content 821 - tn.gov

16

Drive-in rod, bracelet or bag anodes are designed to provide protection to a single, isolated flex

connector. They are not designed to provide adequate protection for flex connectors which are electrically

continuous with other structures such as the STP, impact valve, dispenser cabinet or other piping

components. If a drive-in rod, bracelet or bag anode is used to provide cathodic protection to a flex

connector the CP test must determine that the flex connector is isolated as required by rule .02(4)(c)2. The

Division issued a memo in October 2009 which said that adding a drive-in rod anode to a single, isolated

flex connector does not require approval by a corrosion expert. If the flex connector is electrically

continuous with other flex connectors or other components, then follow the testing procedures

described below:

TESTING CATHODIC PROTECTION ON FLEX CONNECTORS

Described below are various conditions which may be encountered when testing flex connectors. These

methods may also be used to test short sections of isolated metallic piping. Use the applicable method. The

Steel Tank Institute’s step by step procedures for testing flex connectors are described in Appendix 4.

Isolated flex connectors: Test continuity between flex connector and connecting component (i.e., either

the STP piping or dispenser piping) by using either the point-to-point or fixed-cell/moving ground (remote

reference cell placement) method. If isolated, then both local “on” measurements and “remote”

measurements must be taken and pass (-850 mV). NOTE: When measuring the remote potential, the

reference cell must be placed at true “remote earth” (see procedure below). If local “on” and/or remote

measurements do not pass, then a local “Instant Off” measurement must be taken by disconnecting the

bond wire of the anode. If multiple isolated flexes are present, then all other flexes not being tested must be

disconnected from their respective anodes during the testing in order to obtain valid Instant Off

measurements. If Instant Off measurements fail, then continue to observe the depolarization to obtain a

passing 100 mV shift measurement. For local Instant Off readings, each flex must be tested individually by

placing the reference cell immediately adjacent to each flex (not the anode) and making contact directly with

the flex while disconnecting the bond wire to the anode.

NOTE: Permanently attached anodes, such as “bracelet” anodes, may not allow proper testing of flex

connectors if remote readings cannot be obtained or fail. As a result, the instant off/100 mV polarization

method must be used. Since disconnecting bracelet anodes is difficult, one solution is to replace bracelet

Note that although

this flex connector

has a bracelet anode

attached, it is

ineffective in

preventing

corrosion. In order

to work properly,

the anode must be

buried in soil.

Text Replaced�
Text
[Old]: "Note that" [New]: "Note:" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "In order to" [New]: "To" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "soil. Drive-in rod, bracelet or bag anodes are" [New]: "the ground. A single drive-in rod, bracelet or bag anode is only" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "connector. They are not designed to provide adequate protection for flex connectors which are electrically continuous with other structures such as" [New]: "connector or short piece of metallic piping; 19 therefore, additional anodes may be required to achieve cathodic protection if the component to be protected is continuous with other metallic components (e.g., STP pump head, dispenser cabinet, electrical conduit, etc.). Flex connectors are also occasionally bonded to the impressed current system to achieve protection. For this design, each flex connector must be continuous with the disconnected rectifier negative cable; otherwise, some other method (isolation, sacrificial anodes, etc.) 19 Required by Rule 0400-18-01-.02(4)(b)2" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"will be required to achieve corrosion protection. 20 b. Cathodic Protection & Testing Flex Connectors and Short Sections of Metal Piping*"
Text Inserted�
Text
"*"
Text Replaced�
Text
[Old]: "the STP, impact valve, dispenser cabinet or other piping components. If a drive-in rod, bracelet or bag anode is used to provide cathodic protection to a flex connector the CP test must determine that the flex connector" [New]: "The terms flex connector, short section of metal piping and piping component are used interchangeably in the sections below. The most common piping component that requires cathodic protection is a “Flex Connector”; therefore, it is term most commonly used below. ** Document continuity test results for ALL flex connectors and short sections of metal piping on the continuity survey page of either the Impressed Current Cathodic Protection Testing Survey form (CN-1309) or the Galvanic Cathodic Protection Testing Survey form (CN-1140), as appropriate. 21 Flex connectors or short sections of metal piping connected to an impressed current system This scenario could exist at a site that has metal tanks protected by impressed current system, non-metallic piping, and flex connectors or short sections of metal piping (i.e., piping components) that have been connected to the impressed current system. To test these piping components: Test continuity using the point-to-point continuity test procedure (see applicable section in Appendix 2) to confirm that each piping component is continuous with the disconnected rectifier negative cable (impressed current system must be off when performing this procedure). Document the continuity test results in Section XIV of form CN-1309." Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"DRAFT"
Text Replaced�
Text
[Old]: "is isolated as required by rule .02(4)(c)2. The Division issued a memo in October 2009 which said that adding a drive-in rod anode to a single, isolated flex connector does not require approval by a corrosion expert. If the flex connector is electrically continuous with other flex connectors or other components, then follow the testing procedures described below: TESTING CATHODIC PROTECTION ON FLEX CONNECTORS Described below are various conditions which may be encountered" [New]: "22 If a piping component(s) is not continuous with the disconnected rectifier negative cable, the referenced piping component will either need to be bonded to the impressed current system or another method of corrosion protection will be required (i.e., isolation, sacrificial anode, etc.). 23 NOTE: if any piping component is being bonded to the impressed current system, the involvement of a CP Expert is required (including signing off on the CP Test report). 24 If the referenced piping component is continuous with the disconnected rectifier negative cable, measure the “On” and “Instant Off” voltage in accordance with Appendix 3 (reference electrode/cell must be placed in soil adjacent to the piping component). Document the test results in Section XV on form CN-1309. If multiple piping components (e.g., flex connectors) under a dispenser (for example) are all continuous with the disconnected rectifier negative cable, all flex connectors under that particular dispenser can be tested as “one” piece of metal. Follow the testing procedure in Appendix 3. NOTE: To avoid depolarizing the piping components, it may be necessary to perform continuity testing after obtaining “On” and “Instant Off” voltages. 20 Required by Rule 0400-18-01-.02(4)(b)2 21 Required by Rule 0400-18-01-.02(4)(b)2(iii) 22 Required by Rule 0400-18-01-.02(4)(c)2(iii) 23 Required by Rule 0400-18-01-.02(4)(b)2 24 Required by Rule 0400-18-01-.02(4)(b)2(ii)" Font "Open Sans" changed to "OpenSans".Font-size "9.96001" changed to "6.48".
Text Inserted�
Text
"18"
Text Replaced�
Text
[Old]: "when testing flex connectors. These methods may also be used to test short sections of isolated metallic piping. Use the applicable method. The Steel Tank Institute’s step by step procedures for testing flex connectors are described in Appendix 4. Isolated flex connectors: Test continuity between flex connector and connecting component (i.e., either the STP piping or dispenser piping) by using either the point-to-point or fixed-cell/moving ground (remote reference cell placement) method. If isolated, then both local “on” measurements and “remote” measurements must be taken and pass (-850 mV)." [New]: "Flex connectors or short sections of metal piping with attached sacrificial anode(s) Utilize the following methods when testing flex connectors with attached sacrificial anodes. 25 These methods may also be used to test short sections of metallic piping. Step by step procedures for testing flex connectors are described in Appendix 4. NOTE: To test flex connectors or short sections of metal piping with attached sacrificial anodes, the impressed current system (if applicable) must be turned off. 1. Electrically Isolated Flex connectors Test continuity between the flex connector and connecting component (i.e., either the STP piping or dispenser piping) by using either the point-to-point or fixed-cell/moving ground (remote reference cell placement) method. If the flex connector is isolated from the connecting component, then both local “on” measurements and “remote” measurements must be taken for each flex connector. Both measurements must pass (–850 mV or more negative) for the flex connector to be cathodically protected." Font "Open Sans" changed to "OpenSans-Bold".
Text Inserted�
Text
"DRAFT"
Text Inserted�
Text
"25"
Text Replaced�
Text
[Old]: "measuring the remote potential, the" [New]: "collecting “remote” measurements, the" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"either"
Text Replaced�
Text
[Old]: "and/or remote" [New]: "or “remote”" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "flexes" [New]: "flex connectors" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "flexes" [New]: "flex connectors" Font "Open Sans" changed to "OpenSans".
Text Deleted�
Text
"in order"
Text Replaced�
Text
[Old]: "Instant Off measurements. If Instant Off measurements fail, then continue to observe the depolarization to obtain a passing 100 mV shift measurement. For local Instant Off readings, each flex" [New]: "“Instant Off” measurements for the flex connector being tested. If “Instant Off” measurements fail, then continue to observe the depolarization to determine whether the 100 mV shift criteria is met. For local “Instant Off” readings, each flex connector" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"connector"
Text Inserted�
Text
"connector"
Text Replaced�
Text
[Old]: "NOTE: Permanently" [New]: "25 NOTE: The use of permanently" Font "Open Sans" changed to "OpenSans".Font-size "9.96001" changed to "6.48".
Text Inserted�
Text
"or “donut”"
Text Replaced�
Text
[Old]: "remote readings" [New]: "“remote” measurements" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "polarization" [New]: "shift" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "Since disconnecting bracelet anodes is difficult, one solution is to replace bracelet" [New]: "25 Disconnecting bracelet or donut anodes is usually not practical; therefore, one solution is to add a" Font "Open Sans" changed to "OpenSans".Font-size "9.96001" changed to "6.48".
Text Replaced�
Text
[Old]: "16" [New]: "19" Font "Times New Roman" changed to "OpenSans".Font-size "12" changed to "10.98".
Page 82: Total Changes Content 821 - tn.gov

17

anodes with spike or bag anodes with bonding wires which can be disconnected in order to conduct the

instant off/100 mV polarization.

Shorted (continuous) flex connectors: Test continuity between flex connector and connecting component

(i.e., either the STP piping or dispenser piping) by using either the point-to-point or fixed-cell/moving ground

(remote reference cell placement) method. If shorted to connecting component, then local Instant Off

potentials only must be measured (no remotes required). If multiple flexes are shorted together in a

sump with multiple anodes attached, then the ability to disconnect all anode bonding wires at the

same time is recommended. This may require the anode bond wires to be bonded to one common point

to disconnect during testing. To test, disconnect the common bond wire each time and contact each flex

separately and conduct separate Instant Off tests for the individual flexes. This method of bonding all wires

together will also make future testing more convenient.

Bonding all anode wires to a common point is the recommended practice. Alternatively, bond wires that

are attached to each flex separately may be tested in the following manner: Contact the first flex, while all

other bond wires are detached, and disconnect its anode bond wire and conduct Instant Off test. Repeat

this procedure for each flex. Again, if Instant Off fails, then continue to observe depolarization to obtain

passing 100mV shift.

NOTE: For local Instant Off readings, each flex must be tested individually by placing the reference cell

immediately adjacent to each flex (not the anode) and making contact directly with the flex being tested

while disconnecting the bond wire.

Flexes within contained sumps: If an anode has been attached to a flex within a contained sump

containing water, then only a local Instant Off (or 100 mV shift) potential must be measured. If multiple

flexes/anodes are present, then the same procedures previously described for isolated or shorted flexes

also apply.

Obtaining true “remote earth”: True remote earth is not just placing the reference cell a few feet away

from the protected structure. True remote earth must be determined in order to overcome any IR (voltage)

drop between the anode and the protected structure. IR drop is the additional voltage produced by the

anode in order to overcome resistance in the soil. As a result, the measured voltage for an “on” reading may

not be the actual amount of voltage reaching the protected structure. The measurement is actually more

negative (the measurement appears more negative than -850 mV). For example: you measure -890 mV

when the actual amount reaching the protected structure may only be -820 mV.

Procedure: Place reference cell at least 25 feet away from structure being tested. Measure the remote

potential. Move the reference cell another 10 feet away and measure potential again. If the difference in the

two measurements is less than 10 mV, then this location represents true remote earth for any structures

being tested at the site. If the two measurements are not within 10 mV, then continue to move 10 feet away

and measure again until two consecutive measurements are within 10 mV.

Testing of Flex Connectors in “Partially Contained Sump” areas: A partially contained sump is the area

surrounding the STP head and associated piping that has a barrier or retaining wall made of plastic, wood,

metal, or other material designed to prevent soil/gravel from coming in contact with the pump head/piping.

These barriers/walls are not sealed and allow access to the surrounding soil/gravel to a varying degree at

the bottom or sides. Part of the STP head and associated flex/piping may be in contact with soil inside as

well as outside of these barriers/walls. As a result, flex/piping in contact with soil requires corrosion

protection and testing. The configuration of these walls presents some challenges in obtaining proper

testing results. The following scenarios may be encountered:

Text Deleted�
Text
"anodes with"
Text Replaced�
Text
[Old]: "anodes with bonding wires which" [New]: "anode with a bonding wire that" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "in order to conduct" [New]: "to measure" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "polarization." [New]: "shift. True “remote earth”: True “remote earth” is a location away from the protected structure where the potential measurements do not significantly change regardless of how much further away the reference electrode/cell is located from the protected structure. The purpose of obtaining this potential measurement is to overcome the effects of any IR (voltage) drop between the anode and the protected structure. IR drop refers to the voltage produced by an anode to overcome resistance in the soil. 25 Required by Rule 0400-18-01-.02(4)(c)2" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"Procedure to obtain true “remote earth”: Place reference cell at least 25 feet away from structure being tested."
Text Inserted�
Text
"Measure the remote potential. Move the reference cell another 10 feet away and measure potential again."
Text Inserted�
Text
"If the difference in the two measurements is less than 10 mV, then this location represents true “remote earth” for any structures being tested at the site."
Text Inserted�
Text
"If the two measurements are not within 10 mV, then continue to move 10 feet away and measure again until two consecutive measurements are within 10 mV."
Text Replaced�
Text
[Old]: "Shorted (continuous) flex connectors: Test continuity between" [New]: "26 2. Electrically Shorted (Continuous) Flex Connectors Test continuity between the" Font "Open Sans,Bold" changed to "OpenSans".Font-size "9.96001" changed to "6.48".
Text Replaced�
Text
[Old]: "shorted to connecting component, then local Instant Off potentials only must be measured (no remotes required). If multiple flexes are shorted together in a sump with multiple anodes attached, then" [New]: "the flex connector is shorted to the connecting component, then only measure local “Instant Off” potentials for each flex connector. 26 If multiple flex connectors are shorted together," Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"connector"
Text Replaced�
Text
[Old]: "Instant Off" [New]: "“Instant Off”" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "flexes." [New]: "flex connectors." Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"DRAFT"
Text Inserted�
Text
"connector"
Text Replaced�
Text
[Old]: "Contact" [New]: "contact" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "flex," [New]: "flex connector," Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "conduct Instant Off test. Repeat this procedure for each flex. Again, if Instant Off" [New]: "measure the “Instant Off” potential. Repeat this procedure for each flex connector. Again, if the “Instant Off” potential" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "obtain passing 100mV shift. NOTE: For local Instant Off readings, each flex must be tested individually by" [New]: "determine whether the 100mV shift criteria is met. NOTE: For local “Instant Off” readings, each flex connector must be tested individually. This is accomplished by (1)" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"connector"
Text Replaced�
Text
[Old]: "anode) and" [New]: "anode), (2)" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "being tested while disconnecting the bond wire. Flexes within contained sumps: If an anode has been attached to a flex within a contained sump containing water, then only a local Instant Off" [New]: "connector being tested, and (3) disconnecting the bond wire to the anode. 3. Flex Connectors in Contact with Water Inside Containment Sump(s) If an anode has been attached to a single flex connector in a sump containing water, then only a local “Instant Off”" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "flexes/anodes" [New]: "flex connectors/anodes" Font "Open Sans" changed to "OpenSans".
Text Deleted�
Text
"same"
Text Replaced�
Text
[Old]: "isolated or shorted flexes also apply. Obtaining true “remote earth”: True remote earth is not just placing the reference cell a few feet away from the protected structure. True remote earth must be determined in order to overcome any IR (voltage) drop between the anode and the protected structure. IR drop is the additional voltage produced by the anode in order to overcome resistance in the soil. As a result, the measured voltage for an “on” reading may not be the actual amount of voltage reaching the protected structure." [New]: "testing isolated (“instant off” or “100 mV shift” portion only) or shorted flex connectors apply. NOTE: In sumps with high water levels, the anode bond wire that is attached directly to a flex connector/piping that is completely submerged may not be accessible in order to disconnect to obtain “Instant Off” measurements. In this scenario, it is best to have the bond wire from the anode and the bond wire from the flex connector/piping terminate at a point above the water surface and then connect these two bond wires together. When testing, connect the positive lead from the voltmeter to the bond wire going to the flex connector and the negative lead to the reference electrode/cell (only submerge tip of reference electrode/cell in water) and then disconnect the two bond wires to collect an 26 Required by Rule 0400-18-01-.02(4)(c)2" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "The measurement is actually more negative (the measurement appears more negative than -850 mV). For example: you measure -890 mV when the actual amount reaching the protected structure may only be -820 mV. Procedure: Place reference cell at least 25 feet away from structure being tested." [New]: "“Instant Off” measurement. 26 4. Flex Connectors Not In Contact with Water Inside Containment Sump (Or The Sump is Dry) and an Anode is Attached If the flex connector cannot be tested because it is not" Font "Open Sans" changed to "OpenSans".
Text Deleted�
Text
"Measure the remote potential. Move the reference cell another 10 feet away and measure potential again."
Text Replaced�
Text
[Old]: "If the difference in the two measurements is less than 10 mV, then this location represents true remote earth for any structures being tested at the site." [New]: "in contact with water, then document accordingly in the flex connector portion" Font "Open Sans" changed to "OpenSans".
Text Deleted�
Text
"If the two measurements are not within 10 mV, then continue to move 10 feet away and measure again until two consecutive measurements are within 10 mV."
Text Replaced�
Text
[Old]: "Testing of Flex Connectors in “Partially Contained Sump” areas: A partially contained sump is the area surrounding the STP head and associated piping that has a barrier or retaining wall made of plastic, wood, metal, or other material designed to prevent soil/gravel from coming in contact with the pump head/piping. These barriers/walls are not sealed and allow access to the surrounding soil/gravel to a varying degree at the bottom or sides. Part of the STP head and associated flex/piping may be in contact with soil inside as well as outside of these barriers/walls. As a result, flex/piping in contact with soil requires corrosion protection and testing. The configuration of these walls presents some challenges in obtaining proper testing results." [New]: "of the cathodic protection test form (e.g., unable to test Plus STP flex – not in contact with water, etc.). 27 5. Flex connector(s)/piping in a “partially contained sump” A containment sump is considered partially contained if it is constructed in such a way that it does not fully prevent soil/gravel from being in contact with flex connector(s) and/or metal piping (typically under a dispenser or at a submersible turbine pump). These “sumps” are typically constructed of plastic, wood, or metal. The piping at these sump locations may be in contact with soil/gravel inside the sump as well as soil/gravel outside of the sump walls. The configuration of the sump walls can present challenges in obtaining proper potential measurements on the structure being tested." Font "Open Sans,Bold" changed to "OpenSans".
Text Replaced�
Text
[Old]: "17" [New]: "20" Font "Times New Roman" changed to "OpenSans".Font-size "12" changed to "10.98".
Page 83: Total Changes Content 821 - tn.gov

18

1. Flex/piping in contact with soil and is totally inside the retaining wall area with the STP head. All

previously described testing procedures also apply to this scenario. The retaining wall will sometimes

cause “shielding” which inhibits obtaining a remote measurement. As a result, in many cases, only local

Instant Off/100mV shift measurements can be taken as described previously. The flex/piping is

contacted directly and the reference cell placed immediately adjacent to the flex in the soil inside of the

retaining wall.

2. Flex/piping in contact with soil inside of the retaining wall area with the STP head and also extends into

soil outside of the wall (by going through, around, or under it). All previously described testing

procedures also apply to this scenario. A problem occurs when attempting to obtain a remote

measurement for the portion of the flex/piping inside the retaining wall area. The retaining wall will

sometimes “shield” the ability to obtain this measurement. As a result, only Instant Off/100mV shift

measurements can be taken on the portion inside of the retaining wall. The portion of the same

flex/piping outside the wall will require separate testing. A remote measurement may be able to be

taken here since it is not shielded by the wall. Contact can be made with the flex inside the wall and a

separate local “on” measurement obtained with the reference cell placed outside of the wall (by drilling

a hole if needed). But, if a remote cannot be obtained in this situation, then an Instant Off/100mV shift

measurement is required on the portion outside the wall.

In either scenario, consideration must be given to where the anodes are located. This will affect where the

reference cell is placed during testing as well as determining if the anode’s location is adequate to protect

the flex/piping regardless of whether it is all inside the wall or also extends outside the wall. Consideration

must be given to the material of construction of these walls, i.e., if made of galvanized steel. This may

influence the measurements as well as where the reference cell is placed.

Installing anodes: It is important that anodes be attached to the flex connectors properly not only to ensure

that the anode is actually bonded to metal continuous with the flex, but to also make future testing more

practical. This is especially needed in sumps with high water levels. If the anode bond wire is attached

directly to the flex itself and submerged well below the water surface, it may not be accessible in order to

conduct Instant Off tests. New anode bond wires, as well as previously installed anodes, may need to have

the wire attached to a continuous component (piping or STP head) above the water surface in order to be

accessible each successive testing. If the flex is isolated and the wire can only be attached directly to it, then

an additional length of bond wire may need to brought above the surface of the water with a connection

which can be detached in order to conduct an Instant Off test.

Short STP piping sections: Piping sections between STP heads and flex connectors that are in contact with

the soil and/or water are at risk of failure from corrosion. This short “stub” of piping between the STP head

and flex connectors is often overlooked. Although the STP head does not require CP and an isolated flex

connector may be adequately booted or have CP added, the stub may be unprotected. If the flex connector

is continuous with this stub and if the flex has adequate CP, then it may be sufficient to protect the stub

also. Another recommended solution would be to eliminate the soil and/or water contact with this stub.

INTERNALLY LINED TANKS

As of December 22, 2012, all internally lined tanks shall have a cathodic protection system added or be permanently

closed as required by rule .02(4)(a)3.(v). All lined tanks must be compatible with the product stored as required by

.02(4) (a)3.(i)(II). Records of the lining installation must be maintained for the operational life of the tank as required

by rule .02(4)(a)3.(i)(VI) and transferred to any new owners as required by rule .03(2)(d).

Text Replaced�
Text
[Old]: "1. Flex/piping" [New]: "a." Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"DRAFT"
Text Replaced�
Text
[Old]: "in contact with soil" [New]: "Flex connector/piping is in contact with soil/gravel" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"contained"
Text Replaced�
Text
[Old]: "retaining wall area with the STP head. All previously described testing procedures also" [New]: "walls of the partially contained sump. All previously described testing procedures" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "The retaining wall will sometimes cause “shielding” which inhibits obtaining a remote measurement. As a result, in many cases," [New]: "If collecting remote measurements, the sump wall can sometimes cause “shielding” which may inhibit obtaining passing remote measurements. As a result, collecting" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "can be taken as described previously. The flex/piping is contacted directly and the reference cell placed immediately adjacent to the flex in the soil inside of the retaining wall. 2. Flex/piping in contact with soil inside of the retaining wall area with the STP head and also extends into soil outside of the wall (by going through, around, or under it). All previously described testing procedures also apply to this scenario. A problem occurs when attempting to obtain a remote measurement for the portion of the flex/piping inside the retaining wall area. The retaining wall will sometimes “shield” the ability to obtain this measurement. As a result, only Instant Off/100mV shift measurements can be taken on the portion inside of the retaining wall. The portion of the same flex/piping outside the wall will require separate testing. A remote measurement may be able to be taken here since it is not shielded by the wall. Contact can be made with the flex inside the wall and a separate local “on” measurement obtained with" [New]: "may be necessary. Regardless, the applicable data must be obtained individually for each flex connector. If “instant off” measurements are being collected, the reference cell must be placed in the soil inside the sump wall immediately adjacent to each flex connector (not the anode) while obtaining instant off/100 mV shift data using the previously described procedures. b. Flex connector/piping is in contact with soil inside the walls of the partially contained sump and extends into the soil outside of the sump wall (by going through, around, or under the sump wall). For this scenario, the testing procedure varies depending on whether the flex connector/piping is isolated or shorted (described in earlier sections), and whether the remote measurements, if applicable, pass (–850 mV or more negative) or fail (more positive than –850 mV). i. If the flex connector/piping is isolated, obtain local “on” and remote measurements while making contact with each flex connector/pipe inside the sump walls. If the local (reference cell inside sump and away from anodes) and remote measurements (reference cell at true remote earth) pass for a given flex connector/piping section, no additional testing is required for that particular flex connector/pipe. ii. If either the remote measurements fail (which is likely due to “shielding”) or the flex connector/piping is shorted (see earlier section), additional testing will be needed. Specifically, Instant Off/100mV shift measurements will be required for each flex connector/pipe section inside and outside the sump wall. To test the piping section outside the sump, make contact with the piping inside the sump wall and a place 27 Required by Rule 0400-18-01-.02(4)(c)2(iii)" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"21"
Text Replaced�
Text
[Old]: "placed outside of the wall (by drilling a hole if needed). But, if a remote cannot be obtained in this situation, then an Instant Off/100mV shift measurement is required on the portion outside the wall." [New]: "outside the sump wall in soil above the piping (if necessary a hole may be drilled in the groundcover to obtain soil access). 28" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "cell" [New]: "electrode/cell" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "if" [New]: "whether" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "flex/piping regardless of whether it is all inside the wall or also extends outside the wall. Consideration must be given to the material of construction of these walls, i.e., if made of galvanized steel. This may influence the measurements as well as where the reference cell is placed. Installing anodes: It is important that anodes be attached to the flex connectors properly not only to ensure that the anode is actually bonded to metal continuous with the flex, but to also make future testing more practical. This is especially needed in sumps with high water levels. If the anode bond wire is attached directly to the flex itself and submerged well below the water surface, it may not be accessible in order to conduct Instant Off tests. New anode bond wires, as well as previously installed anodes, may need to have the wire attached to a continuous component (piping or STP head) above the water surface in order to be accessible each successive testing. If the flex is isolated and the wire can only be attached directly to it, then an additional length of bond wire may need to brought above the surface of the water with a connection which can be detached in order to conduct an Instant Off test. Short STP piping sections: Piping sections between STP heads and flex connectors that are in contact with the soil and/or water" [New]: "piping. Also, consideration must be given to the material of construction of the sump walls when placing the reference cell, because sump wall construction material (e.g., galvanized steel, etc.) may influence the potential measurements. To reduce this influence, the reference cell should be placed as far away from the metal retaining wall (if possible) and anode. 6. Short STP Piping Sections: Piping sections between STP heads and flex connectors that are in contact with the ground" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "require CP and an isolated flex connector may be adequately booted" [New]: "require corrosion protection, the referenced piping stub does require cathodic protection if it is in contact with the ground." Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"DRAFT"
Text Replaced�
Text
[Old]: "or have CP added, the stub may be unprotected. If the flex connector is continuous with this stub and if the flex has adequate CP, then it may be sufficient to protect the stub also. Another recommended solution would be to eliminate the soil and/or water contact with this stub. INTERNALLY LINED TANKS As of December 22, 2012, all internally lined tanks shall have a cathodic protection system added or be permanently closed as required by rule .02(4)(a)3.(v). All lined tanks must be compatible with the product stored as required by .02(4) (a)3.(i)(II)." [New]: "29 To achieve protection, the soil or water in contact with the piping stub can be removed, or an anode can be added to protect the stub. If the flex connector is protected with an anode, the piping stub may already be protected if it is electrically continuous with the flex connector. Regardless, if an anode is being used to protect the referenced piping, the piping must be tested to confirm that it is cathodically protected. 28 9. Internally Lined Tanks As of December 22, 2012, all internally lined tanks shall have a cathodic protection system added or be permanently closed as required by rule .02(4)(a)3.(v). The lining material must be compatible with the product stored as required by .02(4)(a)3.(i)(II)." Font "Open Sans" changed to "OpenSans".Font-size "9.96001" changed to "6.48".
Text Replaced�
Text
[Old]: "18" [New]: "22" Font "Times New Roman" changed to "OpenSans".Font-size "12" changed to "10.98".
Page 84: Total Changes Content 821 - tn.gov

19

1) For internally lined tanks with a CP system (tanks with a properly operating CP system do not

require periodic inspections of the internal lining)

a. The tank owner and/or operator must have CP test records required by rule .02(4)(c)2.(ii), .02(4)(c)5.(i),

and .03(2)(b)2. indicating the corrosion protection status. If the tank owner and/or operator does not

have the CP records, then they must conduct a CP test as required by rule .02(4)(c)2.

b. An Impressed Current CP system must remain operational for the remaining life of the tank, as

required by rule .02(4)(c)1. and records maintained as required by rule .02(4)(c)5. and .03(2).

For testing and recordkeeping of cathodic protection systems, refer to sections 4 Testing and 5

Recordkeeping above.

2) Internal lining of tanks as a tank repair

If a tank meets any one of the construction standards in rule .02(4)(a)1. through 5., it may be repaired by

lining. The Division will consider the lining or relining to be “in a manner that is no less protective”, as

allowed in rule .02(4)(a)6., as long as the tank is lined following the requirements of rule .02(4)(a)3. and

.02(7)(a) and the record of the lining is maintained for the operational life of the UST system as required by

rule .02(7)(f) and records of the lining are transferred to any new tank owner as required by rule .03(2)(d).

Tank owners may also submit the lining records to the Division for retention in its files, and the Division will

maintain the records following the requirements of rule .14(1).

Exception: If the tank is constructed of fiberglass, rule .02(7)(b) has the additional requirement mandating:

“Repairs to fiberglass-reinforced plastic tanks shall be made by the manufacturers authorized

representatives or in accordance with the manufacturer’s specifications.”

Consequently, if the manufacturer of a fiberglass reinforced tank does not allow its tanks to be repaired by

lining, rule .02(7)(b) would prevent lining as a repair.

The following conditions must be met for tank owners and/or operators using tank lining as a repair:

a. Prior to adding the internal lining, the tank integrity must first be assessed and determined to be

structurally sound in accordance with NLPA Standard 631 and determined to be suitable for internal

lining as required by rule .02(4)(a)3.(i)(III).

b. Rule .02(4)(a)3.(i)(IV) requires linings to be installed in accordance with manufacturer’s instructions. The

following standards are allowed by federal rule 40 CFR Part 280.33(a) and (b), and they may be used to

comply with rule .02(4)(a)3.(i)(IV) and .02(4)(a)6.:

National Leak Prevention Association Standard 631, Chapter 631, Chapter A-Entry, Cleaning, Interior

Inspection, Repair, and Lining of Underground Storage Tanks

National Leak Prevention Association Standard 631, Chapter D-Lining of Fiberglass Tanks for

Compatibility & Repairs That Are Allowed

The NLPA standards are available at http://www.nlpa-online.org/standards.html and they include

requirements like the ones listed below:

i. Internal tank linings must be installed in accordance with NLPA Standard 631 which requires an

assessment of the tank shell after cleaning the tank and abrasive blasting of the tank interior. NLPA

Text Replaced�
Text
[Old]: "1)" [New]: "a." Font "Open Sans,Bold" changed to "OpenSans-Bold".Font-size "9.96001" changed to "12".
Text Replaced�
Text
[Old]: "a." [New]: "1." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: ".02(4)(c)2.(ii)," [New]: ".02(4)(c)2.(iii)," Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: ".03(2)(b)2." [New]: ".03(2)(b)5." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "b." [New]: "2." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "sections 4 Testing" [New]: "Sections 4 “Testing”" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "Recordkeeping above. 2) Internal lining of tanks as a tank repair" [New]: "“Recordkeeping” in the “Galvanic Systems” and “Impressed Current Systems” portions of this document. b. Internal Lining of Tanks as a Tank Repair 28 Required by Rule 0400-18-01-.02(4)(c)2 29 Required by Rule 0400-18-01-.02(4)(b)2" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: ".02(7)(f)" [New]: ".02(7)(h)" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "Tank owners may also submit the lining records to the Division for retention in its files, and the Division will maintain the records following the requirements of rule .14(1). Exception: If the tank is constructed of fiberglass, rule .02(7)(b) has the additional requirement mandating: “Repairs to fiberglass-reinforced plastic tanks shall be made by the manufacturers" [New]: "Exception: If the tank is constructed of fiberglass, rule .02(7)(b) has the additional requirement mandating: “Repairs to fiberglass-reinforced plastic tanks shall be made by the manufacturer’s" Font "Open Sans" changed to "OpenSans-BoldItalic".
Text Replaced�
Text
[Old]: "a." [New]: "1." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "631" [New]: "63130" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "b." [New]: "2." Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"DRAFT"
Text Deleted�
Text
"631, Chapter"
Text Replaced�
Text
[Old]: "19" [New]: "23" Font "Times New Roman" changed to "OpenSans".Font-size "12" changed to "10.98".
Page 85: Total Changes Content 821 - tn.gov

20

631 contains specifications for testing for and repairing tank wall perforations. The procedures for

assessing the tank shell in NPLA 631 must be followed and if it is determined the tank does not pass

the assessment, the tank is not suitable for lining.

ii. The tank assessment must be done by a company trained and qualified to do this work, and tank

lining must be installed in accordance with NLPA 631 and lining manufacturer’s instructions, by a

company trained and qualified to do tank lining.

c. Rule .02(7)(a) requires that repairs to UST systems be made to prevent releases due to structural

failures or corrosion as long as the UST system is used to store petroleum. In accordance with rule

.02(4)3., any tank lining must be installed to effectively prevent a release due to corrosion for the

operational life of the system.

d. The Division asks to be given sufficient advance notice of the tank entry, cleaning, assessment, repair,

and lining installation to have staff on site during every phase of the process. Complete documentation

of the repair process is considered a tank repair record and must be maintained for the life of the

system as required by rule .02(7)(f) and transferred to any new owner as required by rule .03(2)(d).

3) Lining and relining tanks to assure compatibility with alternative fuels

If a tank meets any one of the construction standards in rule .02(4)(a)1. through 5., it may be lined or relined

to meet the compatibility requirements of rule .02(5). The Division will consider the lining or relining to be

“in a manner that is no less protective”, as allowed in rule .02(4)(a)6., as long as the tank is lined following the

requirements of rule .02(4)(a)3. and .02(7)(a) and the record of the lining is maintained for the operational

life of the UST system as required by rule .02(7)(f) and records of the lining are transferred to any new tank

owner as required by rule .03(2)(d). If records are not maintained, the tank would be considered

incompatible with alternative fuels. Tank owners may also submit the lining records to the Division for

retention in its files, and the Division will maintain the records following the requirements of rule .14(1).

REFERENCES

1. Guidelines for the Evaluation of Underground Storage Tank Cathodic Protection Systems. Mississippi

Department of Environmental Quality, July 1, 2002

2. NACE Standard TM0101-2012, NACE International

3. NACE Recommended Practice RP 0285- “Corrosion Control of Underground Storage Tank Systems by Cathodic

Protection” NACE International

4. NACE Recommended Practice RP 0169- “Control of External Corrosion on Underground or Submerged Metallic

Piping Systems” NACE International

5. Steel Tank Institute (STI) Recommended Practice R892 “Recommended Practice for Corrosion Protection of

Underground Piping Networks Associated with Liquid Storage and Dispensing Systems” Steel Tank Institute

6. Steel Tank Institute (STI) Recommended Practice R972 “Recommended Practice for the Installation of

Supplemental Anodes for sti-P3® UST's” Steel Tank Institute

Text Replaced�
Text
[Old]: "done" [New]: "performed" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "do" [New]: "perform" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"the"
Text Replaced�
Text
[Old]: "instructions," [New]: "instructions" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "c." [New]: "3." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: ".02(4)3.," [New]: ".02(4)(a)3.(i)(I)," Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"30 Required by Rule 0400-18-01-.02(7)(a)"
Text Replaced�
Text
[Old]: "d." [New]: "4." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: ".02(7)(f)" [New]: ".02(7)(h)" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "3) Lining and relining tanks to assure compatibility with alternative fuels" [New]: "c. Lining And Relining Tanks to Assure Compatibility with Alternative Fuels" Font "Open Sans,Bold" changed to "OpenSans-Bold".Font-size "9.96001" changed to "12".
Text Replaced�
Text
[Old]: ".02(7)(f)" [New]: ".02(7)(h)" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"DRAFT"
Text Deleted�
Text
"Tank owners may also submit the lining records to the Division for retention in its files, and the Division will maintain the records following the requirements of rule .14(1)."
Text Replaced�
Text
[Old]: "July 1, 2002" [New]: "Revised February 1, 2019" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "TM0101-2012, NACE International 3. NACE Recommended Practice RP 0285-“Corrosion" [New]: "TM0101-2012-“Measurement Techniques Related to Criteria for Cathodic Protection of Underground Storage Tank Systems” NACE International 3. NACE Standard Practice SP0285-“External Corrosion" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "Recommended Practice RP 0169-“Control" [New]: "Standard Practice SP0169-“Control" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "R892 “Recommended" [New]: "R892-“Recommended" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "R972 “Recommended" [New]: "R972-“Recommended" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "Installation" [New]: "Addition" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "for" [New]: "to" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "20" [New]: "24" Font "Times New Roman" changed to "OpenSans".Font-size "12" changed to "10.98".
Page 86: Total Changes Content 821 - tn.gov

21

7. Steel Tank Institute (STI) Recommended Practice R051 “Cathodic Protection Testing Procedures for sti-P3®

UST's” Steel Tank Institute

8. Technical Interpretation and Guidance Regarding the Combination of Cathodic Protection and Internal Lining,

December 4, 1995 Environmental Protection Agency

APPENDICES

1. Structure-to-Soil Test Procedure for Galvanic CP Systems

2. Continuity Testing Procedure for CP Systems

3. Structure-to-Soil Test Procedure for Impressed Current CP Systems

4. Test Procedure for Flex Connectors

5. Commonly Used Definitions

6. Impressed Current CP Testing Survey

7. Galvanic CP Testing Survey

8. Impressed Current CP System 60 Day Record of Rectifier Operation Form

Text Replaced�
Text
[Old]: "R051 “Cathodic" [New]: "R051-“Cathodic" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "sti-P3®" [New]: "sti-P3" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"DRAFT"
Text Inserted�
Text
"®"
Text Inserted�
Text
"DRAFT"
Text Replaced�
Text
[Old]: "21" [New]: "25" Font "Times New Roman" changed to "OpenSans".Font-size "12" changed to "10.98".
Page 87: Total Changes Content 821 - tn.gov

22

APPENDIX 1

STRUCTURE-TO-SOIL TEST PROCEDURE FOR GALVANIC CATHODIC PROTECTION SYSTEMS

For tanks with galvanic cathodic protection systems in which the anodes cannot be disconnected, a minimum of one

local potential measurement near the UST center and away from the anodes and one remote potential

measurement must be taken.1,2

Alternatively, three potential measurements, one at each of the UST ends and one

near the center of the UST, and one remote potential measurement may be taken.1,2

It is vital that proper equipment and proper techniques be used when testing cathodic protection on UST systems.

Proper Copper/Copper Sulfate Reference Electrode Usage3

Reference electrode may not be placed on concrete or other paving materials to make potential readings.

Drill holes in concrete to obtain access to soil over tank and piping if necessary.

Ensure that the reference electrode is placed in a vertical position (tip down).

Ensure that soil where the reference electrode is placed is moist – add tap water if necessary.

Ensure that soil where the reference electrode is placed is not contaminated with hydrocarbons.

Ensure that the reference electrode window is not exposed to direct sunlight.

Proper Cathodic Protection Measurement Techniques3

Ensure that good metal-to-metal contact is made between the test lead clip/probe and the structure.

Ensure that no corrosion exists where the test lead makes contact with the structure.

Ensure that your body does not come into contact with the electrical connections.

Ensure that test leads are not submerged in any standing water.

Ensure that test lead insulation is in good condition.

Ensure that any drop tube that is installed in the tank does not prohibit contact with the tank bottom.

If a metallic probe is used to contact the tank bottom, ensure that the probe does not contact the fill riser or

any other metallic component of the UST system.

Mandatory Test Procedure:

STI-P3® tanks3

1. Place voltmeter on 2 volt DC scale.

2. Connect voltmeter negative lead to reference electrode.

3. Place reference electrode in clean soil at a true remote earth* from the protected structure.

4. Positive voltmeter lead will be used to contact tank bottom, external tank shell or structure being tested.

This may be accomplished by connecting the voltmeter lead wire to a copper test prod mounted to the

bottom of a wooden gauging stick and lowering the stick into the tank fill riser.

5. Obtain voltage and record in the remote voltage column on Tennessee Galvanic Cathodic Protection Survey

Form CN-1140. More than one remote potential reading may be made if desired.

6. Move reference electrode to a point near the center of the tank along the midline directly over the structure

that is being tested to obtain local potential reading(s). More than one local potential reading may be made

if desired.

7. Obtain voltage and record in the local voltage column on CN-1140.

Note: If a sti-P3® tank is equipped with a PP4 test station, the PP4 test station is disregarded and potentials must

be obtained with a portable reference electrode placed in the soil at both local and remote earth locations.3

If a test lead wire or PP2 test station is utilized to make contact with the tested structure you must ensure that

continuity exists between the test lead wire and the structure. This may be accomplished by conducting a point-to-

point continuity test.3

Text Deleted�
Text
"APPENDIX 1 STRUCTURE-TO-SOIL TEST PROCEDURE FOR GALVANIC CATHODIC PROTECTION SYSTEMS"
Text Replaced�
Text
[Old]: "For tanks with galvanic cathodic protection systems in which" [New]: "APPENDIX 1: STRUCTURE-TO-SOIL TEST PROCEDURE FOR GALVANIC CATHODIC PROTECTION SYSTEMS For tank(s) with galvanic cathodic protection systems where" Font "Open Sans" changed to "OpenSans-Bold".Font-size "9.96001" changed to "12".
Text Replaced�
Text
[Old]: "one local potential measurement near the UST center and away from the anodes and one remote potential measurement must be taken. 1,2 Alternatively, three potential measurements, one at each of the UST ends and one near the center of the UST, and one remote potential measurement may be taken. 1,2 It is vital that proper equipment and proper techniques be used when testing cathodic protection on UST systems. Proper Copper/Copper Sulfate Reference Electrode Usage 3 Reference electrode may not be placed on concrete or other paving materials to make potential readings." [New]: "three potential measurement must be taken (one local potential measurement at the center of the tank and away from the anodes, and two remote earth potential measurements). 1,2 These two remote earth readings can be used to determine the “true” remote earth measurements. Additional local measurements may be collected at the ends of the UST. It is vital that proper equipment and proper techniques be used when testing cathodic protection on UST systems. Proper Copper/Copper Sulfate Reference Electrode/Cell Usage 3 Reference electrode/cell may not be placed on concrete or other paving materials to collect potential measurements." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "electrode" [New]: "electrode/cell" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "electrode" [New]: "electrode/cell" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "electrode" [New]: "electrode/cell" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "electrode window" [New]: "electrode/cell window (if applicable)" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"DRAFT"
Text Replaced�
Text
[Old]: "STI-P3®" [New]: "STI-P3 ®" Font "Open Sans,Bold" changed to "OpenSans-Bold".
Text Replaced�
Text
[Old]: "electrode." [New]: "electrode/cell." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "electrode" [New]: "electrode/cell" Font "Open Sans" changed to "OpenSans".
Text Deleted�
Text
"a"
Text Replaced�
Text
[Old]: "Positive voltmeter lead will be used to contact tank bottom, external tank shell or structure being tested." [New]: "Contact tank bottom, external shell or structure being tested with positive voltmeter lead wire." Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"or brass test prod (do not used galvanized metal)"
Text Replaced�
Text
[Old]: "into the tank fill riser." [New]: "to make contact with the structure." Font "Open Sans" changed to "OpenSans".
Text Deleted�
Text
"Tennessee"
Text Replaced�
Text
[Old]: "More than one remote potential reading may be made if desired. 6. Move reference electrode" [New]: "6. Move reference electrode/cell" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"form"
Text Replaced�
Text
[Old]: "sti-P3®" [New]: "sti-P3 ®" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"®"
Text Replaced�
Text
[Old]: "the PP4 test station is disregarded and potentials must be obtained with a portable reference electrode placed in the soil at both local and remote earth locations. 3 If a test lead wire or PP2" [New]: "do not use the test station to collect either local or remote potential measurements. 3 If a test lead wire or PP2 ®" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"3 Cathodically protected steel or other metallic piping with galvanic anodes"
Text Replaced�
Text
[Old]: "22" [New]: "27" Font "Times New Roman" changed to "OpenSans".Font-size "12" changed to "10.98".
Page 88: Total Changes Content 821 - tn.gov

23

Cathodically protected steel piping with galvanic anodes3

Steel piping is tested by following Steps 1-7 above and making the contact from the positive voltmeter lead to a

point on the piping. Piping requires measurement at each end of the pipe. If more than 100 feet of piping exist

between any two anodes, the reference electrode must also be placed at the midpoint between the two anodes that

are separated by more than 100 feet. If it is not known where the piping anodes are located, there can be no more

than 100 feet of piping between any two test points.

* True Remote Earth is determined by placing the reference cell at least 25 feet away from any structure that is to

be tested, taking a reading then moving the reference cell at least 10 feet farther from the first remote cell test

location. If the two readings are within 10 mV of each other, then true remote earth has been established. If the

difference between the two readings is greater than 10 mV, then move another 10 feet away from the structure and

take another reading. Once 2 consecutive locations that are within 10 mV of each other are obtained, that will be

true remote earth and the remote structure readings are made with the reference cell in this location.

Data Interpretation for Cathodic Protection Testers1,2,3

Pass- If both the local and the remote potential are –850 mV or more negative, the -850 mV on criterion is met and

adequate cathodic protection has been demonstrated.

Fail - If both the local and the remote potential are more positive than –850 mV, the- 850 mV on criterion is not met

and adequate cathodic protection has not been demonstrated.

Inconclusive- If either the local or the remote potential is more positive than –850 mV for all structures tested, the

test result is inconclusive and further testing and/or repairs are necessary.

Incomplete- If one or more of the structures tested pass the above criteria and other structures fail the above

criteria, the tester may issue an incomplete result on CN-1140. Structures which do not pass the above criteria are

not considered corrosion protected, and further testing and/or repairs are necessary.

NOTE: Any NACE certified corrosion expert may evaluate results of the survey or conduct the survey and declare a

pass or fail based on their interpretation of the data and professional judgment.

Continuity Testing

If test results are Fail or Inconclusive, a tester may perform continuity testing to determine if the protected

structure is shorted. This can help determine why the minimum -850 mV was not achieved. See Appendix 2 for

Continuity Testing Procedure.

References

1. NACE Standard TM0101-2012, NACE International

2. Cathodic Protection Testing Procedures for STI-P3 USTs, R051, Steel Tank Institute, January 2006

3. Guidelines for the Evaluation of Underground Storage Tank Cathodic Protection Systems. Mississippi DEQ, July 1,

2002.

Text Deleted�
Text
"3 Cathodically protected steel piping with galvanic anodes"
Text Inserted�
Text
"or other metallic"
Text Inserted�
Text
"wire"
Text Replaced�
Text
[Old]: "measurement" [New]: "potential measurements" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "electrode" [New]: "electrode/cell" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "cell" [New]: "electrode/cell" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "reading" [New]: "potential measurement" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "cell" [New]: "electrode/cell" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "cell" [New]: "reference electrode/cell" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "readings" [New]: "measurements" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "readings" [New]: "measurements" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "reading. Once 2 consecutive locations that" [New]: "measurement. Once two (2) consecutive locations" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "other are obtained, that will be true remote earth and the remote structure readings are made with the reference cell in this location." [New]: "other, either of those locations will be true remote earth." Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"DRAFT"
Text Replaced�
Text
[Old]: "Pass-If" [New]: "Pass -If" Font "Open Sans" changed to "OpenSans-Bold".
Text Inserted�
Text
"measurements"
Text Replaced�
Text
[Old]: "-850" [New]: "– 850" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"measurements"
Text Replaced�
Text
[Old]: "the-850" [New]: "the – 850" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "Inconclusive-If" [New]: "Inconclusive -If" Font "Open Sans" changed to "OpenSans-Bold".
Text Inserted�
Text
"measurement"
Text Replaced�
Text
[Old]: "Incomplete-If" [New]: "Incomplete -If" Font "Open Sans,Bold" changed to "OpenSans-Bold".
Text Inserted�
Text
"form"
Text Replaced�
Text
[Old]: "-850" [New]: "–850" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "1." [New]: "a." Font "Times New Roman" changed to "OpenSans-Bold".
Text Replaced�
Text
[Old]: "2." [New]: "b." Font "Times New Roman" changed to "OpenSans-Bold".
Text Inserted�
Text
"®"
Text Replaced�
Text
[Old]: "January 2006 3." [New]: "April 2017 c." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "July 1, 2002." [New]: "Revised February 1, 2019." Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"DRAFT"
Text Replaced�
Text
[Old]: "23" [New]: "28" Font "Times New Roman" changed to "OpenSans".Font-size "12" changed to "10.98".
Page 89: Total Changes Content 821 - tn.gov

24

APPENDIX 2

CONTINUITY TESTING PROCEDURE FOR CATHODIC PROTECTION SYSTEMS

(GALVANIC & IMPRESSED CURRENT)

Adapted from Mississippi Department of Environmental Quality, July 1, 2002

Fixed Cell – Moving Ground Continuity Test Procedure (must not be used for impressed current systems)

1. Place reference electrode in contact with the soil at a location remote (25 – 100 feet) from all cathodically

protected structures. You must ensure that the remote reference electrode placement is not in proximity to

any other cathodic protection systems (e.g. natural gas pipelines) or directly over any buried metallic

structure in order to minimize the chances of unwanted interference.

2. Be sure that reference electrode is firmly placed in moist soil and is not in contact with any vegetation.

3. Connect reference electrode to the negative terminal of voltmeter using a long spool of suitable wire.

4. Connect positive lead wire to voltmeter. This lead wire should have a sharp test prod (scratch awl or similar)

in order to assure good contact with the metallic structures under test.

5. Place voltmeter on 2 volt DC scale.

6. Contact each buried metallic structure with the positive test lead without moving the reference electrode.

Typical items that would be tested during a continuity survey include: all tanks, tank risers, submersible

pump heads, piping, flex connectors/swing joints, vent lines, electrical conduits, dispensers, utilities, etc.

7. Obtain voltage for each component and record on Tennessee cathodic protection survey form.

8. Voltages for each component that is tested must be obtained as quickly as possible since the observed

potential can change over time. This is because the conditions in the soil where the reference electrode is

placed can change over a relatively short period of time.

Fixed Cell – Moving Ground Data Interpretation

If two or more structures exhibit potentials that vary by 5 mV or less, the structures are considered to be

electrically continuous.

If two or more structures exhibit potentials that vary by 10 mV or greater, the structures are considered to

be electrically isolated.

If two or more structures exhibit potentials that vary by more than 5 mV but less than 10 mV, the result is

inconclusive and further testing (point-to-point) is necessary.

Point-to-Point Continuity Test Procedure must be used with impressed current systems; may be used with

galvanic systems)

1. Turn off power to rectifier if testing an impressed current system and disconnect the negative cable at the

rectifier. This is necessary to obtain accurate results.

2. Connect test leads to voltmeter. Both test leads should have a sharp test prod or suitable clip lead in order

to make good contact with tested structures.

3. Place voltmeter on millivolt DC scale.

Text Deleted�
Text
"APPENDIX 2"
Text Inserted�
Text
"APPENDIX 2:"
Text Replaced�
Text
[Old]: "July 1, 2002" [New]: "Revised February 1, 2019" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "(must not" [New]: "(not to" Font "Open Sans,Bold" changed to "OpenSans-Bold".
Text Replaced�
Text
[Old]: "systems)" [New]: "systems):" Font "Open Sans,Bold" changed to "OpenSans-Bold".
Text Replaced�
Text
[Old]: "electrode" [New]: "electrode/cell" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "a location remote (25 – 100 feet) from all cathodically protected structures." [New]: "true remote earth (see Appendix 1)." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "Be sure that reference electrode is firmly placed in moist soil and" [New]: "Place reference electrode/cell firmly in moist soil and ensure that it" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "electrode" [New]: "electrode/cell" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "in order to assure" [New]: "to ensure" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "electrode. Typical items" [New]: "electrode/cell. Typical structures" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"turbine"
Text Replaced�
Text
[Old]: "Voltages" [New]: "Obtain voltages" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "that is tested must be obtained as quickly as possible since the observed potential can change over time. This is because the conditions in the soil where the reference electrode is placed can change over a relatively short period of time. Fixed Cell – Moving Ground Data Interpretation" [New]: "quickly because observed potential measurements can change in a relatively short period of time due to conditions in the soil where the reference electrode/cell is placed. Fixed Cell – Moving Ground Data Interpretation (not to be used for impressed current systems)" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"DRAFT"
Text Replaced�
Text
[Old]: "potentials" [New]: "potential measurements" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "potentials" [New]: "potential measurements" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "potentials" [New]: "potential measurements" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "Procedure must be used with impressed current systems;" [New]: "Procedure* (required for impressed current systems; however," Font "Open Sans,Bold" changed to "OpenSans-Bold".
Text Replaced�
Text
[Old]: "Turn off power to rectifier if testing an impressed current system and disconnect the negative cable at the rectifier. This is necessary to obtain accurate results." [New]: "If testing an impressed current system, turn off power to rectifier and disconnect the negative cable at the rectifier to obtain accurate continuity measurements." Font "Open Sans" changed to "OpenSans".
Text Deleted�
Text
"in order"
Text Replaced�
Text
[Old]: "24" [New]: "30" Font "Times New Roman" changed to "OpenSans".Font-size "12" changed to "10.98".
Page 90: Total Changes Content 821 - tn.gov

25

4. Connect one voltmeter test lead to one of the structures for which continuity is being tested; connect the

other voltmeter test lead to the other structure being tested or preferably, the negative rectifier lead wire.

5. Record voltages observed (millivolt difference) on each of the two structures that are being compared and

record on Tennessee cathodic protection survey form. Reconnect the negative lead wire to the rectifier

when testing is completed.

Testing with this method does not require a reference electrode. The two structures of interest are simply

connected in parallel with the voltmeter and a determination made as to whether or not any potential difference

exists between them.

Point-to-Point Data Interpretation

If the voltage difference observed between the two structures is 5 mV or less, this indicates that the two

structures are considered to be electrically continuous with each other.

If the voltage difference observed between the two structures is 10 mV or greater, this indicates that the two

structures are considered to be electrically isolated from each other.

If the voltage difference observed between the two structures is greater than 5mV but less than 10 mV, the

result is inconclusive and further testing is necessary.

Text Replaced�
Text
[Old]: "one of the structures for which continuity is" [New]: "the structure" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "or preferably, the negative rectifier lead wire. 5. Record voltages observed (millivolt difference) on each of the two structures that are being compared and record on Tennessee cathodic protection survey form. Reconnect the negative lead wire to the rectifier" [New]: "(galvanic systems) or to the disconnected negative rectifier wire (impressed current systems). Typical structures that would be tested during a continuity survey include: all tanks, tank risers, submersible turbine pump heads, piping, flex connectors/swing joints, vent lines, electrical conduits, dispensers, utilities, etc. 5. Record voltages observed (millivolt difference) on each of the two structures that are being compared and record measurements on the Tennessee cathodic protection survey form. Reconnect the negative wire to the rectifier (impressed current systems)" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "electrode." [New]: "electrode/cell." Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"* For impressed current systems, perform the point-to-point continuity testing AFTER collecting Instant Off and/or 100 mV shift measurements to ensure the system does not depolarize prior to collecting instant off and/or 100 mV shift data."
Text Deleted�
Text
"this indicates that"
Text Deleted�
Text
"this indicates that"
Text Inserted�
Text
"test"
Text Inserted�
Text
"DRAFT"
Text Replaced�
Text
[Old]: "25" [New]: "31" Font "Times New Roman" changed to "OpenSans".Font-size "12" changed to "10.98".
Page 91: Total Changes Content 821 - tn.gov

26

APPENDIX 3

STRUCTURE-TO-SOIL TEST PROCEDURE FOR IMPRESSED CURRENT CATHODIC PROTECTION SYSTEMS

Adapted from Mississippi Department of Environmental Quality, July 1, 2002

For a tank with impressed current CP systems, a minimum of three local potential measurements, one at each of

the UST ends and one near the center of each UST must be taken. 1 For metal piping, one reading shall be collected

at each dispenser, midpoints of steel piping greater than 100 feet in length, and metal piping at STP sumps. Record

all necessary information on the Tennessee Impressed Current Cathodic Protection Survey Form (CN-1309). It is

vital that proper equipment and proper techniques be used when testing cathodic protection on UST systems.

Proper Copper/Copper Sulfate Reference Electrode Usage2

Reference electrode may not be placed on concrete or other paving materials to make potential readings.

Drill holes in concrete to obtain access to soil over tank or piping if necessary.

Ensure that the reference electrode is placed in a vertical position (tip down).

Ensure that soil where the reference electrode is placed is moist – add tap water if necessary.

Ensure that soil where the reference electrode is placed is not contaminated with hydrocarbons.

Ensure that the reference electrode window is not exposed to direct sunlight.

Proper Cathodic Protection Measurement Techniques2

Ensure that good metal-to-metal contact is made between the test lead clip/probe and the structure.

Ensure that no corrosion exists where the test lead makes contact with the structure.

Ensure that your body does not come into contact with the electrical connections.

Ensure that test leads are not submerged in any standing water.

Ensure that test lead insulation is in good condition.

Ensure that any drop tube that is installed in the tank does not prohibit contact with the tank bottom.

If a metallic probe is used to contact the tank bottom, ensure that the probe does not contact the fill riser or

any other metallic component of the UST system.

Mandatory Test Procedure:

1. Inspect rectifier for proper operation and document information on Division Form CN-1309.

2. Measure rectifier output (voltage/ amperage) with a multimeter (do not rely on rectifier gauge readings).

Measurement of individual anode circuits may also be made if there is a junction box present.

3. Place voltmeter on 2 volt DC scale.

4. Connect voltmeter positive lead to structure to be tested and connect voltmeter negative lead to reference

electrode.

5. Place reference electrode in clean soil directly over the structure that is being tested. Take at least three (3)

measurements for each tank, preferably at the approximate midpoint and at each end of the tank along the

centerline if tank length can be verified, or for small capacity tanks, one (1) local measurement over the tank top

for every 10 feet of tank length. Piping requires measurement at each end of the pipe and at midpoints of piping

over 100 feet in length.

6. Obtain voltage potential with the protective current applied and record in the On Voltage column on Form CN-

1309.

7. Without moving reference electrode from the position it was in during step 6 above, obtain voltage potential with

the protective current temporarily interrupted (instant off*) and record in the Instant Off Voltage column on CN-

1309. If any instant off potential reading is more positive than -850 mV, the tank may or may not be adequately

protected and a 100 mV shift must be performed. See below.

8. Disconnect and make contact with the negative cable of the rectifier and determine continuity for all structures

that are required to be protected by impressed current using point-to-point method. See Appendix 2 for

Continuity Testing Procedure.

Text Deleted�
Text
"APPENDIX 3"
Text Inserted�
Text
"APPENDIX 3:"
Text Replaced�
Text
[Old]: "July 1, 2002 For a tank" [New]: "Revised February 1, 2019 For tank(s)" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"collect"
Text Replaced�
Text
[Old]: "UST must be taken." [New]: "UST." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "one reading shall be collected" [New]: "collect one potential measurement" Font "Open Sans" changed to "OpenSans".
Text Deleted�
Text
"Tennessee"
Text Replaced�
Text
[Old]: "Electrode" [New]: "Electrode/Cell" Font "Open Sans,Bold" changed to "OpenSans-Bold".
Text Replaced�
Text
[Old]: "electrode" [New]: "electrode/cell" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "make potential readings." [New]: "collect potential measurements." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "electrode" [New]: "electrode/cell" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "electrode" [New]: "electrode/cell" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "electrode" [New]: "electrode/cell" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "electrode window" [New]: "electrode/cell window (if applicable)" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"DRAFT"
Text Replaced�
Text
[Old]: "(voltage/ amperage)" [New]: "(voltage/amperage)" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "gauge readings). Measurement of" [New]: "meter readings). Measure" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "may also be made if there is a junction box" [New]: "if a junction box is" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "2 volt" [New]: "2-volt" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "electrode. 5. Place reference electrode in clean soil directly over the structure that is being tested. Take at least three (3) measurements for each tank, preferably" [New]: "electrode/cell. If the structure being tested has been internally lined, then the positive lead of the voltmeter shall make contact with the exterior of the structure or to any tank system component that is continuous with that structure. 5. Place reference electrode/cell in clean soil directly over the structure that is being tested. Collect at least three (3) potential measurements for each tank. The preferred locations for the potential measurements are" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "if" [New]: "(assuming" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "verified, or for small capacity tanks, one (1) local measurement over the tank top for every 10 feet of tank length. Piping requires measurement at each end of the pipe and at midpoints of piping over 100 feet in length. 6. Obtain voltage potential with the protective current applied and record in the On Voltage column on Form CN1309. 7. Without moving reference electrode from the position it was in during step 6 above, obtain voltage potential with the protective current temporarily interrupted (instant off*) and record in the Instant Off Voltage column on" [New]: "verified). Piping requires collection of potential measurement at each end of the pipe and at midpoints of piping over 100 feet in length. 6. At each location (step 5 above) obtain voltage potential measurements with the protective current applied and record in the “On Voltage” column on form CN-1309. 7. Also, at each location (step 5 above), without moving reference electrode/cell, obtain voltage potential measurements with the protective current temporarily interrupted (instant off*) and record in the “Instant Off Voltage” column on form" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "-850" [New]: "–850" Font "Open Sans,Italic" changed to "OpenSans-Italic".
Text Inserted�
Text
"and/or piping"
Text Replaced�
Text
[Old]: "protected and" [New]: "protected; therefore," Font "Open Sans,Italic" changed to "OpenSans-Italic".
Text Replaced�
Text
[Old]: "performed. See below. 8. Disconnect and make contact with the negative cable of the rectifier and determine continuity for all structures that are required to be protected by impressed current using point-to-point method. See Appendix 2 for Continuity Testing Procedure." [New]: "performed (see below). 8. Upon completion of this test procedure, disconnect the rectifier negative cable and perform a point-to-point continuity test (see Appendix 2)." Font "Open Sans,Italic" changed to "OpenSans-Italic".
Text Replaced�
Text
[Old]: "26" [New]: "32" Font "Times New Roman" changed to "OpenSans".Font-size "12" changed to "10.98".
Page 92: Total Changes Content 821 - tn.gov

27

100 mV depolarization (shift)

Must be performed whenever instant off potential of -850 mV or more positive for any reading in step 7 is not

observed.

100 mV of polarization is determined by interrupting the polarized potential on the structure until a change of at

least 100 mV in the structure-to-soil potential is observed. In calculating the 100 mV decay, the instant off potential

obtained in step 7 above is utilized as the starting point (e.g. if instant off = -800 mV, power must be left off until

decayed to at least -700 mV for the 100 mV polarization to be demonstrated). Depolarization may take as long as 24

hours in some cases, but cathodic protection power to the structure should not be interrupted for more than 72

hours.

Calculate voltage change by subtracting final (or ending) voltage from the instant off voltage and record these

values in the appropriate columns on CN-13099.

Data Interpretation for Cathodic Protection Testers

Pass- one of the following two criteria must be met in order for the structure to be protected:

1. If all instant off potentials are -850 mV or more negative, the -850 off criterion is met and adequate cathodic

protection has been demonstrated and further testing is not necessary. If the instant off potentials are more positive

than -850 mV, the tank may or may not be adequately protected and a 100 mV polarization test may be performed.

2. If the structure exhibits more than 100 mV polarization, the 100 mV polarization criterion is met and adequate

cathodic protection has been demonstrated

For impressed current systems, the instant off potential should never exceed -1.6 volts (-1600 millivolts). Such high readings

can cause coatings to disbond and result in metal embrittlement.

Fail - If neither the - 850 instant off nor the 100 mV polarization criteria are met, adequate cathodic protection has

not been demonstrated and repairs/modification will be necessary to achieve cathodic protection.

Inconclusive - The cathodic protection survey of an impressed current system must be evaluated by a corrosion

expert because it cannot be determined that the protected structures are continuous or other factors may result in

high readings

NOTE: A NACE certified corrosion expert may evaluate results of the survey or conduct the survey and determine

that cathodic protection is adequate based on their interpretation.

*The instant off potential is the second value that is observed on a digital voltmeter the instant the power is

interrupted. The first number that appears immediately after power interruption must be disregarded. After the

second number appears, a rapid decay (depolarization) of the structure will normally occur. Alternately, the instant

off reading may be captured by using the min/max function on the meter if the meter is so equipped.

In order to obtain instant off potentials, a current interrupter or a second person may be necessary. If a current

interrupter is not available, have a second person throw the power switch at the rectifier off for 2 seconds and then

back on for 15 seconds. Repeat this procedure until you are sure an accurate instant off reading has been obtained.

References

1. NACE Standard TM0101-2012, NACE International

2. Guidelines for the Evaluation of Underground Storage Tank Cathodic Protection Systems. Mississippi DEQ, July 1,

2002.

Text Replaced�
Text
[Old]: "Must be performed whenever instant off potential of -850 mV or more positive for any reading in step 7 is not observed. 100 mV of polarization is determined by interrupting the polarized potential on the structure until a change of at least 100 mV in the structure-to-soil potential is observed. In calculating the 100 mV decay, the instant off potential obtained in step 7 above is utilized as the starting point (e.g. if instant off = -800 mV, power must be left off until decayed to at least -700 mV for the 100 mV polarization to be demonstrated). Depolarization may take as long as 24 hours in some cases, but cathodic protection power to the structure should not be interrupted for more than 72 hours. Calculate voltage change by subtracting final (or ending) voltage from the instant off voltage and record these values in the appropriate columns on CN-13099." [New]: "Perform when the instant off potential measurement is more positive than –850 mV at any test location (see Step 7 above). 100 mV of depolarization is determined by measuring the difference in polarization between the instant off potential (see step 7 above) and the depolarized potential. If this change is 100 mV or greater, the 100 mV shift criteria has been met. Depolarization typically takes minutes but may take 24 hour or longer. Regardless do not interrupt the current to the cathodic protection system for more than 72 hours. Calculate voltage change by subtracting final (or ending) voltage from the instant off voltage and record these values in the appropriate columns on form CN-1309." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "Pass-one" [New]: "Pass -one" Font "Open Sans,Bold" changed to "OpenSans-Bold".
Text Replaced�
Text
[Old]: "-850" [New]: "–850" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "-850" [New]: "–850" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "demonstrated and further" [New]: "demonstrated." Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"DRAFT"
Text Inserted�
Text
"Further"
Text Replaced�
Text
[Old]: "-850" [New]: "–850" Font "Open Sans,Italic" changed to "OpenSans-Italic".
Text Replaced�
Text
[Old]: "tank" [New]: "tank(s) and/or piping" Font "Open Sans,Italic" changed to "OpenSans-Italic".
Text Replaced�
Text
[Old]: "protected and" [New]: "protected; therefore," Font "Open Sans,Italic" changed to "OpenSans-Italic".
Text Replaced�
Text
[Old]: "polarization test may" [New]: "depolarization test must" Font "Open Sans,Italic" changed to "OpenSans-Italic".
Text Replaced�
Text
[Old]: "polarization," [New]: "shift," Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "polarization" [New]: "shift" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "exceed -1.6 volts (-1600 millivolts). Such high readings" [New]: "be more negative than –1.6 volts (– 1600 millivolts) because such high potential measurements" Font "Open Sans,Italic" changed to "OpenSans-Italic".
Text Replaced�
Text
[Old]: "-If neither the -850" [New]: "– If neither the –850" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "polarization" [New]: "shift" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "-The cathodic protection survey of an impressed current system must be evaluated by a corrosion expert because it cannot be determined that the protected structures are continuous or other factors may result in high readings" [New]: "– All test locations meet the instant off or 100 mV shift criteria; however, other unusual factors are discovered that may warrant review by a corrosion expert before a passing or failing result can be determined (such as instant off potential measurements are more negative than –1,600 mV, structures do not appear to be continuous, etc.)" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"the"
Text Replaced�
Text
[Old]: "survey or conduct the" [New]: "cathodic protection" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"measurement"
Text Deleted�
Text
"that is"
Text Replaced�
Text
[Old]: "the instant the power" [New]: "immediately after the current" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "reading" [New]: "potential measurement" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "meter" [New]: "voltmeter" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "In order to obtain instant off potentials," [New]: "To obtain instant off potential measurements," Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "necessary. If a current interrupter is not available, have a second person throw the power switch at the rectifier off for 2 seconds and then back on for 15 seconds. Repeat this procedure until you are sure" [New]: "necessary to briefly interrupt the power. If a second person option is utilized, have that person turn the rectifier off for approximately 2 seconds and then back on for approximately 15 seconds. If necessary, repeat this procedure until" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "1." [New]: "a." Font "Open Sans" changed to "OpenSans-Bold".
Text Replaced�
Text
[Old]: "2." [New]: "b." Font "Open Sans" changed to "OpenSans-Bold".
Text Replaced�
Text
[Old]: "July 1, 2002." [New]: "Revised February 1, 2019." Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"DRAFT"
Text Replaced�
Text
[Old]: "27" [New]: "33" Font "Times New Roman" changed to "OpenSans".Font-size "12" changed to "10.98".
Page 93: Total Changes Content 821 - tn.gov

28

APPENDIX 4

TEST PROCEDURE FOR FLEX CONNECTORS

(adapted from Steel Tank Institute procedure)

The following procedures will describe how to determine potential readings for a flex connector relative to a

copper/copper sulfate reference electrode. The flex connector may be considered protected if the potential

readings meet one or more of the criteria described below for cathodic protection. Results of these tests must be

recorded on the applicable Division’s official cathodic protection survey form.

The procedure for testing a flex connector will depend on where and how a flex connector is installed. Flex

connectors may be either directly buried in soil or submerged in water within a containment sump.

All flex connectors must be tested by either:

1. Obtaining passing local and remote measurements, (PROCEDURE A) or

2. Obtaining passing Instant Off and/or 100 mV shift measurements. (PROCEDURE B)

PROCEDURE A. -850 mV “current on” Criterion

This procedure is applicable to flex connectors directly buried in soil.

A total of 3 test measurements (one local and two at remote earth) are required for each directly buried flex

connector when using the -850 mV current on criterion.

1. Set the voltmeter to the 2 volt DC scale.

2. Make contact to the flex connector with the positive lead of the voltmeter.

3. Connect the negative lead of the voltmeter to the reference electrode.

4. Place the reference electrode in the soil immediately adjacent to the flex connector.

5. Record the voltage observed on the voltmeter as the "local" potential.

6. Place the reference electrode in the soil approximately 25 feet away from the flex connector and any

other cathodically protected structure at the facility and note voltage observed on the voltmeter.

7. Move the reference electrode 10 feet further away, place in the soil and observe the voltage.

8. If the voltage observed in step 6 is within 10 mV of the voltage observed in step 7, then it may be

assumed that the reference electrode is at “remote earth”.

9. If the voltages observed in steps 6 and 7 are not within 10 mV of each other, continue moving the

reference electrode until the voltages obtained at two different locations are within 10 mV of each other.

Determination of PASS/FAIL

Pass = All three potential measurements must be -850 mV or more negative.

Fail = One or more of the three potential measurements are less than -850 mV.

NOTE: There may be situations when a remote earth reading cannot be obtained. This may occur when the flex

connector is in contact with water within a sealed containment sump at a STP or dispenser. Also, certain conditions,

such as shielding by metallic or non-metallic skirts or retaining walls at sumps or inaccessibility of soil remotely, may

prevent obtaining good remote measurements. As a result, if remote measurements cannot be obtained for

whatever reason, then Procedure B - Instant Off and/or 100mV shift must be used.

Text Deleted�
Text
"APPENDIX 4"
Text Inserted�
Text
"APPENDIX 4:"
Text Replaced�
Text
[Old]: "(adapted from Steel Tank Institute procedure) The following procedures will describe how to determine potential readings for a flex connector relative to a copper/copper sulfate reference electrode. The flex connector may be considered protected if the potential readings meet one or more of the criteria described below for cathodic protection. Results of these tests must be recorded on the applicable Division’s official cathodic protection survey form." [New]: "(INCLUDING SHORT SECTIONS OF METAL PIPING) (adapted from Steel Tank Institute procedure) If the flex connectors are protected by an impressed current system, then test the referenced piping components in accordance with Appendix 2 and 3; otherwise follow the test procedures below for testing flex connectors protected with galvanic anodes. The following procedures will describe how to obtain potential measurements for a flex connector relative to a copper/copper sulfate reference electrode/cell. The flex connector is considered protected if the potential measurements meet one or more of the criteria described below. Results of these tests must be recorded on the Division’s applicable cathodic protection survey form (CN1140 or CN-1309)." Font "Open Sans" changed to "OpenSans-Bold".Font-size "9.96001" changed to "12".
Text Deleted�
Text
"either"
Text Replaced�
Text
[Old]: "soil or submerged in water within a containment sump. All flex connectors must be tested by either: 1. Obtaining passing local and remote measurements, (PROCEDURE A) or 2. Obtaining passing Instant Off and/or 100 mV shift measurements. (PROCEDURE B)" [New]: "soil, in contact with water, extend outside the walls of the sump, etc. Regardless of the flex connector configuration, follow either Procedure A or B below (as applicable): Prior to testing flex connectors, determine whether each flex connector is electrically isolated or continuous (shorted) with other pieces of metal (dispenser piping, STP piping stub, etc.) using either the point-to-point or fixed-cell/moving ground (remote reference cell placement) method. A more detailed description on how to determine electrical continuity or isolation is provided in the “Corrosion Protection for Flexible (Flex) Connectors and Short Sections of Metal Piping” section of this Technical Chapter and Appendix 2. Document the continuity test results on the applicable continuity survey page of form CN-1140 or CN-1309 (as applicable). After determining whether each flex connector is electrically continuous or isolated, test each flex connector using the following method (as applicable): 1. Obtaining local and remote potential measurements, (PROCEDURE A)* or 2. Obtaining Instant Off potential measurements and/or 100 mV shift measurements. (PROCEDURE B)* *If flex connectors are protected with galvanic anodes and other structures at the facility are protected by an impressed current system, the impressed current system must be turned off prior to testing the flex connectors." Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"DRAFT"
Text Replaced�
Text
[Old]: "-850" [New]: "–850" Font "Open Sans" changed to "OpenSans".Font-size "9.75673" changed to "10.02".
Text Replaced�
Text
[Old]: "to flex connectors directly buried in" [New]: "for testing isolated flex connectors in contact with" Font "Open Sans" changed to "OpenSans".
Text Deleted�
Text
"directly buried"
Text Replaced�
Text
[Old]: "-850" [New]: "–850" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "connector" [New]: "connector**" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "electrode." [New]: "electrode/cell." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "electrode" [New]: "electrode/cell" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "connector." [New]: "connector and away from any anodes." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "electrode" [New]: "electrode/cell" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "step" [New]: "Step" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "step" [New]: "Step" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "electrode is at “remote" [New]: "electrode/cell location in Step 7 is at “true remote" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "steps" [New]: "Steps" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "electrode" [New]: "electrode/cell" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"**Test each flex connector individually."
Text Replaced�
Text
[Old]: "must be -850" [New]: "(one local and two remotes) must be –850" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "-850 mV. NOTE: There may be situations when a remote earth reading cannot be obtained. This may occur when the flex connector is in contact with water within a sealed containment sump at a STP or dispenser. Also, certain conditions, such as shielding by metallic or non-metallic skirts or retaining walls at sumps or inaccessibility of soil remotely, may prevent obtaining good remote measurements. As a result, if remote measurements cannot be obtained for whatever reason, then Procedure B -Instant Off and/or 100mV shift must be used." [New]: "–850 mV. PROCEDURE B." Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"DRAFT"
Text Replaced�
Text
[Old]: "28" [New]: "35" Font "Times New Roman" changed to "OpenSans".Font-size "12" changed to "10.98".
Page 94: Total Changes Content 821 - tn.gov

29

PROCEDURE B. -850 mV instant off or 100 mV Shift Criterion

This procedure is applicable to flex connectors directly buried in soil, or to flex connectors submerged or partially

submerged underwater within a containment sump, or in situations as described above where remote

measurements cannot be taken.

1. Set the voltmeter to the 2 volt DC scale.

2. Make contact to the flex connector with the positive lead of the voltmeter.

3. Connect the negative lead of the voltmeter to the reference electrode.

4. Place the reference electrode in the soil immediately adjacent to the flex connector.

5. Record the voltage observed on the voltmeter as the on potential.

6. Without moving the reference electrode, disconnect the anode lead wire(s) and record the instant off

potential (Note: All anodes on all flex connectors at the same sump must be disconnected in order to

utilize the -850 mV instant off or 100 mV Shift criteria.)

7. If the instant off potential is not -850 mV or more negative, then the anode may remain temporarily

disconnected and the flex connector allowed to depolarize in an effort to demonstrate a shift in the

potential of 100 mV or greater.

Determination of PASS/FAIL:

Pass = The instant off potential is -850mV or more, OR the shift in the potential is 100 mV or greater.

Fail = The instant off potential is less than -850 mV, OR the shift in the potential is less than 100 mV.

Note: When attempting to demonstrate the 100 mV shift criterion has been met, the ending voltage is subtracted

from the instant off voltage.

For example: If the instant off voltage is recorded as -730 mV and the ending voltage is recorded at -550 mV then

the potential shift would be 180 mV and the flex connector would pass the test. If the instant off voltage is -735

mV and the ending voltage is -680 mV, then the shift would only be 55 mV and the flex connector would fail the

test.

Text Deleted�
Text
"PROCEDURE B."
Text Replaced�
Text
[Old]: "-850" [New]: "–850" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "to" [New]: "for" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "directly buried in soil, or to flex connectors submerged or partially submerged underwater within" [New]: "in contact with soil, submerged or partially submerged in water in" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "above where remote measurements cannot be taken." [New]: "in Procedure A where passing remote potential measurements cannot be obtained." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "the flex connector" [New]: "each flex connector**" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "electrode." [New]: "electrode/cell." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "electrode" [New]: "electrode/cell" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"or water (only submerge the ceramic tip)"
Text Replaced�
Text
[Old]: "electrode," [New]: "electrode/cell," Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"measurement"
Text Inserted�
Text
"other"
Text Replaced�
Text
[Old]: "all flex connectors at" [New]: "any other flex connectors in" Font "Open Sans" changed to "OpenSans-Bold".
Text Replaced�
Text
[Old]: "in order to utilize the -850 mV instant off or 100 mV Shift criteria.) 7. If the instant off potential" [New]: "when obtaining instant off potential measurements or 100 mV shift data.) 7. If the instant off potential measurement" Font "Open Sans" changed to "OpenSans-Bold".
Text Replaced�
Text
[Old]: "-850" [New]: "–850" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"**Test each flex connector individually."
Text Replaced�
Text
[Old]: "more," [New]: "more negative," Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "-850 mV," [New]: "–850 mV (i.e., more positive than –850 mV)," Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "-730" [New]: "–730" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "at -550 mV" [New]: "as –550 mV," Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "and the flex connector would pass the test." [New]: "thus indicating that the flex connector is cathodically protected (i.e., Pass)." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "-735" [New]: "–735" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"potential"
Text Replaced�
Text
[Old]: "and the flex connector would fail the test." [New]: "thus indicating that the flex connector is not cathodically protected (i.e., Fail)." Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"DRAFT"
Text Replaced�
Text
[Old]: "29" [New]: "36" Font "Times New Roman" changed to "OpenSans".Font-size "12" changed to "10.98".
Page 95: Total Changes Content 821 - tn.gov

30

APPENDIX 5

COMMONLY USED DEFINITIONS

Anode—the part of a corrosion cell where oxidation (corrosion) occurs. Electrons flow away from the anode and

carry metal ions.

Cathode—the part of a corrosion cell at which is protected by the anode. Reduction is the principal reaction

occurring at the cathode. Electrons flow toward the cathode in the corrosion cell.

Cathodic protection—a process that reduces the corrosion rate of a metal surface by making that surface the

cathode of a corrosion cell.

Conductivity— the measure of the ability of a material to conduct an electric charge. (Conductivity is the reciprocal

of resistivity.)

Continuity bond—a metallic connection that provides electrical continuity between structures.

Corrosion—deterioration of a material, usually a metal, that results from a chemical or electrochemical reaction

with its environment.

Current— a flow of electric charge or the amount of electric charge flowing past a specified point per unit of time.

Delamination— separation of layers in a material or separation between one or more coats from another coat

within a coating system.

Disbondment—the loss of adhesion between a coating and the substrate.

Discontinuity—a condition in which the electrical path through a structure is interrupted by something that acts as

a dielectric or insulating fitting.

Corrosion cell — an electrochemical system consisting of an anode and a cathode in metallic contact and

immersed in an electrolyte. This process produces an electrochemical reaction involving oxidation of the anode and

reduction of the cathode. The anode and cathode may be different metals or dissimilar areas on the same metal

surface.

Electrode—a material that conducts electrons, is used to establish contact with an electrolyte, and through which

current is transferred to or from an electrolyte.

Electrode potential—the potential of an electrode in an electrolyte as measured against a reference electrode.

Electromotive series—a list of elements arranged according to their standard electrode potentials.

Galvanic anode—a metal that provides sacrificial protection to another metal that is more noble when electrically

coupled in an electrolyte. This type of anode is the electron source in one type of cathodic protection.

Galvanic corrosion—accelerated corrosion of a metal because of an electrical contact with a more noble metal or

nonmetallic conductor in a corrosive electrolyte.

General corrosion - corrosion that is distributed more-or-less uniformly over the surface of a material.

Half cell—commonly used in the field to refer to a reference electrode, It may be comprised of a copper rod and a

copper sulfate solution commonly used for measuring corrosion of steel with respect to copper. It may also be

made of a silver and silver chloride solution for measuring in marine environments.

Text Deleted�
Text
"APPENDIX 5"
Text Inserted�
Text
"APPENDIX 5:"
Text Deleted�
Text
"at"
Text Replaced�
Text
[Old]: "Conductivity— the" [New]: "Conductivity—the" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "Current— a" [New]: "Current—a" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "Delamination— separation" [New]: "Delamination—separation" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "cell — an" [New]: "cell—an" Font "Open Sans,Bold" changed to "OpenSans".
Text Inserted�
Text
"DRAFT"
Text Replaced�
Text
[Old]: "corrosion -corrosion" [New]: "corrosion—corrosion" Font "Open Sans,Bold" changed to "OpenSans".
Text Replaced�
Text
[Old]: "electrode," [New]: "electrode." Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "30" [New]: "38" Font "Times New Roman" changed to "OpenSans".Font-size "12" changed to "10.98".
Page 96: Total Changes Content 821 - tn.gov

31

Holiday—a discontinuity in a protective coating that exposes unprotected surface to the environment.

Hydrogen embrittlement—metal degradation caused by the presence of hydrogen within a metal or alloy

resulting from the application of too much protective current on the structure being protected.

Impressed current—an electric current supplied by a power source that is external to the electrode system. An

example is direct current for cathodic protection.

Impressed current anode— a suitable electrode used in an impressed current system.

Instant-off potential—the polarized half-cell potential of an electrode taken immediately after the cathodic

protection current is interrupted, which closely approximates the potential without IR drop (i.e., the polarized

potential) when the current was on.

Ion—an electrically charged atom or group of atoms.

IR drop—the voltage across a resistance when current is applied in accordance with Ohm’s law.

Lining—a coating or layer of sheet material adhered to the interior surface of a container used to protect the

container against corrosion by its contents and/or to protect the contents of the container from contamination by

the container material.

Localized corrosion—corrosion at discrete sites also known as pitting or crevice corrosion.

Negative return—a point of connection between the cathodic protection negative cable and the protected

structure.

Ohm's Law - the current through a conductor between two points is directly proportional to the potential

difference across the two points. Voltage = current x resistance.

Passivation—the process in metal corrosion by which metals become passive generally by having a coating form

on the surface that isolates the metal from the electrolyte.

Pinhole—a minute hole through a coat or coats that exposes an underlying coat or the substrate.

Pit—a surface cavity with depth equal to or greater than the minimum dimension at the opening.

Pitting—localized corrosion of a metal surface that is confined to a small area and takes the form of cavities called

pits.

Polarization—the change from the corrosion potential as a result of current flow across the electrode/electrolyte

interface.

Polarized potential— the potential across the structure/electrolyte interface that is the sum of the corrosion

potential and the cathodic polarization.

Protective coating—a coating applied to a surface to protect the substrate from corrosion.

Reference electrode—an electrode having a stable and reproducible potential, used in the measurement of other

electrode potentials.

Remote earth—a location on the earth far enough from the affected structure that the soil potential gradients

associated with currents entering the earth from the affected structure are insignificant.

Text Replaced�
Text
[Old]: "anode— a" [New]: "anode—a" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "Law -the" [New]: "Law—the" Font "Open Sans,Bold" changed to "OpenSans".
Text Inserted�
Text
"DRAFT"
Text Replaced�
Text
[Old]: "potential— the" [New]: "potential—the" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "electrode—an electrode" [New]: "electrode/cell—an electrode/cell" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "31" [New]: "39" Font "Times New Roman" changed to "OpenSans".Font-size "12" changed to "10.98".
Page 97: Total Changes Content 821 - tn.gov

32

Sacrificial (galvanic) protection—reduction of corrosion of a metal by electrically connecting the metal to a

galvanic anode. (a form of cathodic protection).

Shielding— preventing the cathodic protection current from reaching its destination or diverting it from its natural

path.

Stray current—current flowing through paths other than the intended circuit.

Stray-current corrosion—corrosion resulting from stray current.

Structure-to-electrolyte potential—the potential difference between the surface of a buried or submerged

metallic structure and the electrolyte that is measured with reference to an electrode in contact with the electrolyte.

Structure-to-soil potential—see structure-to-electrolyte potential.

Structure-to-structure potential—the potential difference between metallic structures, or sections of the same

structure, in a common electrolyte.

Uniform corrosion—corrosion that proceeds at exactly the same rate over the surface of a material.

Text Replaced�
Text
[Old]: "anode." [New]: "anode" Font "Open Sans" changed to "OpenSans".
Text Replaced�
Text
[Old]: "Shielding— preventing" [New]: "Shielding—preventing" Font "Open Sans" changed to "OpenSans".
Text Inserted�
Text
"DRAFT"
Text Deleted�
Text
"32"
Page 98: Total Changes Content 821 - tn.gov

33

APPENDIX 6

IMPRESSED CURRENT CATHODIC PROTECTION TESTING SURVEY

(Modifications are made to these forms from time to time. Please check the Division’s website for the

most current version of the State’s official form)

Text Replaced�
Text
[Old]: "6" [New]: "6:" Font "Open Sans,Bold" changed to "OpenSans-Bold".
Text Inserted�
Text
"DRAFT"
Page 99: Total Changes Content 821 - tn.gov

34

DEPARTMENT OF ENVIRONMENT AND CONSERVATION

DIVISION OF UNDERGROUND STORAGE TANKS

William R Snodgrass Tennessee Tower

312 Rosa L. Parks Avenue, 12th

Floor

Nashville, TN 37243

IMPRESSED CURRENT CATHODIC PROTECTION TESTING SURVEY

This form must be utilized to evaluate underground storage tank (UST) cathodic protection systems in the State of Tennessee.

Access to the soil directly over the cathodically protected structure that is being evaluated must be provided.

I. UST FACILITY II. UST OWNER

NAME: NAME:

FACILITY ID NUMBER: COMPANY:

ADDRESS: ADDRESS:

CITY: COUNTY: CITY: STATE:

III. CP TESTER

TESTER’S NAME: COMPANY:

ADDRESS: LIST CERTIFICATION, IF ANY:

CITY: STATE: PHONE NUMBER:

IV. REASON SURVEY WAS CONDUCTED (mark only one)

□ Routine - 3 year □ Routine – within 6 months of installation □ Re-survey after fail □ Re-survey after repair/modification

Date next cathodic protection survey must be conducted by: __________________________ (required within 6 months of installation/repair, or every 3 years).

V. CATHODIC PROTECTION TESTER’S EVALUATION (mark only one)

□ PASS All protected structures at this facility pass the cathodic protection survey and it is judged that adequate cathodic protection has been provided to the UST system (indicate all applicable criteria by completion of Section VII).

□ FAIL One or more components did not pass the cathodic protection survey.

□ INCONCLUSIVE The cathodic protection survey must be evaluated by a corrosion expert for such reasons as it cannot be determined that the protected structures are continuous, or other factors may result in high readings, etc. (complete Section VI).

CP TESTER’S SIGNATURE: ________________________________________________ DATE CP SURVEY PERFORMED: ________________________________

VI. CORROSION EXPERT’S EVALUATION (mark only one)

The survey must be conducted and/or evaluated by a corrosion expert when: a) supplemental anodes or other changes in the construction of the impressed current system are made; b) stray current may be affecting buried metallic structures; or c) an inconclusive result was indicated in Section V.

□ PASS (based on above criteria) □ FAIL (based on above criteria) CORROSION EXPERT’S NAME: COMPANY NAME:

NACE INTERNATIONAL CERTIFICATION NUMBER:

CORROSION EXPERT’S SIGNATURE: _________________________________________________________ DATE: _____________________________________

VII. CRITERIA APPLICABLE TO EVALUATION (mark all that apply)

□ 850 OFF Structure-to-soil potential more negative than –850 mV with respect to a Cu/CuSO4 reference electrode with protective current temporarily interrupted (instant-off).

□ 100 mV Polarization Structure(s) tested exhibit at least 100 mV of cathodic polarization.

VIII. ACTION REQUIRED AS A RESULT OF THIS EVALUATION (mark only one)

□ NONE Cathodic protection is adequate. No further action is necessary at this time. Test again by no later than the date specified in Section IV.

□ RETEST Cathodic protection may not be adequate. Retest to determine if passing results can be achieved.

□ REPAIR & RETEST Cathodic protection is not adequate. Repair/modification is necessary as soon as practical.

CN 1309 RDA 2304

Text Replaced�
Text
[Old]: "This form must be utilized" [New]: "Utilize this form" Font "Times New Roman,Bold" changed to "TimesNewRomanPS-BoldMT".Font-size "8.03999" changed to "8.52".
Text Inserted�
Text
"impressed current"
Text Replaced�
Text
[Old]: "must be provided." [New]: "is required." Font "Times New Roman,Bold" changed to "TimesNewRomanPS-BoldMT".Font-size "8.03999" changed to "8.52".
Text Inserted�
Text
"DRAFT"
Text Inserted�
Text
"3 year □Routine –"
Text Replaced�
Text
[Old]: "□ Re-survey after fail □ Re-survey after repair/modification □ Routine -3 year Date next cathodic protection survey must be conducted by: __________________________ (required within 6 months of installation/repair, or" [New]: "□Re-survey after fail/repair/modification Date next cathodic protection survey must be conducted by: _______________________ (required" Font "Arial,Bold" changed to "Arial-BoldMT".
Text Replaced�
Text
[Old]: "All protected structures at this facility pass the cathodic protection survey and it is judged that adequate cathodic protection has been provided to the UST system (indicate all applicable criteria by completion of Section VII)." [New]: "A pr ll otec protec tion has ted str be uc en pr tures ov at thi ided to th s facil e US ity pas T s sy the c stem ath (indi odi c c ate al protec l appl tion s ica ur bl v e c ey r and i iteria by t is ju com dged that ad pletion of S equ ec ate c tion V athodi II). c" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "The cathodic protection survey must be evaluated by a corrosion expert for such reasons as it cannot be determined that the protected structures are continuous, or other factors may result in high readings, etc. (complete Section VI)." [New]: "T str he c uctur athodi es ar c e c pro o tec ntinuous tion sur , or vey othe mus r fac t be ev tors al m uated ay res by ult i a c n hi or gh r ros eadi ion ex ngs per , etc t if . ( it c com annot b plete S e deter ection V mined th I). at the protected" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "supplemental anodes" [New]: "replacement or addition of anodes," Font "Arial" changed to "ArialMT".
Text Inserted�
Text
"or design"
Text Replaced�
Text
[Old]: "made;" [New]: "made (see also the Repairs section of the Impressed Current portion of Technical Chapter 4.1 “Corrosion Protection – Standardized Inspection Manual”);" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "_________________________________________________________" [New]: "_________________________________________________" Font "Arial,Bold" changed to "Arial-BoldMT".
Text Inserted�
Text
"□ □ □"
Text Replaced�
Text
[Old]: "more negative than –850 mV" [New]: "measurements are–850 mV or more negative" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "□ 100 mV Polarization Structure(s) tested exhibit" [New]: "Continuity Structure(s) listed in Section XIV that are to be protected by the impressed current system are continuous with the rectifier negative. 100 mV Shift Structure(s) tested exhibit a shift of" Font "Arial" changed to "Arial-BoldMT".Font-size "20.04" changed to "9".
Text Deleted�
Text
"by"
Text Deleted�
Text
"CN 1309 RDA 2304"
Text Deleted�
Text
"34"
Page 100: Total Changes Content 821 - tn.gov

35

IX. DESCRIPTION OF UST SYSTEM

FACILITY NAME: FACILITY ID NUMBER:

TANK # PRODUCT CAPACITY TANK MATERIAL PIPING MATERIAL FLEX CONNECTORS /

LOCATION

1

2

3

4

5

6

7

8

9

10

If metal flex connectors are present, are they corrosion protected?

□ YES Method: □ Isolation (booted) □ Isolation (contained in sump or no soil contact)

□ Attached Anode1

□ NO Action taken: ___________________________________________________________________________

1If the flex connectors are protected by sacrificial anodes, test accordingly and include in Section XVI on this form.

X. IMPRESSED CURRENT RECTIFIER DATA (complete all applicable)

In order to conduct an effective evaluation of the cathodic protection system, a complete evaluation of rectifier operation is necessary.

RECTIFIER MANUFACTURER:

RATED DC OUTPUT: ______________ VOLTS _______________ AMPS

RECTIFIER MODEL:

RECTIFIER SERIAL NUMBER:

RECTIFIER OUTPUT AS INITIALLY DESIGNED OR LAST MEASURED (if available):

_____________ VOLTS ________________ AMPS

EVENT DATE TAP SETTINGS

MEASURED

DC OUTPUT HOUR

METER

COMMENTS

COARSE FINE VOLTS AMPS

“AS FOUND”

“AS LEFT”

Check all that apply: □ single amp/voltmeter □ dual amp/voltmeter □ red/green indicator light

XI. IMPRESSED CURRENT POSITIVE CIRCUIT MEASUREMENTS (output amperage)

Complete if system design allows such measurements (i.e. individual lead wires for each anode are installed and measurement shunts are present).

CIRCUIT 1 2 3 4 5 6 7 8 8 10 TOTAL

ANODE (+)

XII. DESCRIPTION OF CATHODIC PROTECTION SYSTEM REPAIRS AND/OR MODIFICATION Complete if repairs or modifications to the cathodic protection system are made or are necessary. Certain repairs/modifications as explained in the text of the

Standardized Compliance inspection Manual, Technical Chapter 4.1 Corrosion Protection, are required to be designed and/or evaluated by a corrosion expert (completion of Section VI required). Attach corrosion expert’s calculations and diagram and have corrosion expert sign Section VI.

□ Additional anodes for an impressed current system (attach corrosion expert’s design).

□ Repairs or replacement of rectifer (explain in Remarks/Other below).

□ Anode header cables repaired and/or replaced (explain in Remarks/Other below).

□ Impressed current protected tanks/ piping not electrically continuous (explain in Remarks/Other below).

Remarks/ Other________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________

Text Deleted�
Text
"MATERIAL PIPING MATERIAL"
Text Inserted�
Text
"(Y / N). IF YES, INDICATE LOCATION (STP / DISP / STP AND DISP) MATERIAL MATERIAL"
Text Inserted�
Text
"DRAFT"
Text Replaced�
Text
[Old]: "8 9 10 □ YES Method: □ Isolation (booted) □ Attached Anode 1 □ Isolation (contained in sump or no soil contact) If metal flex connectors are present, are they corrosion protected? □ NO Action taken: ___________________________________________________________________________" [New]: "□Isolation (booted) □Attached Anode 1 (provided details in comments) □Isolation (not in contact with the ground) □ YES Method: If metal flex connectors are present, are they corrosion □ NO Action taken: ____________________________________________________________________ protected?" Font "Arial,Bold" changed to "Arial-BoldMT".Font-size "12" changed to "19.98".
Text Inserted�
Text
"__________________________________________________________________________________________"
Text Inserted�
Text
"Comments (e.g., piping brand, specific flex/anode locations, etc.):"
Text Replaced�
Text
[Old]: "In order to" [New]: "To" Font "Arial" changed to "ArialMT".
Text Deleted�
Text
"RECTIFIER MANUFACTURER:"
Text Inserted�
Text
"RECTIFIER MANUFACTURER:"
Text Replaced�
Text
[Old]: "MEASURED" [New]: "DC OUTPUT" Font "Arial,Bold" changed to "Arial-BoldMT".Font-size "6.96001" changed to "7.5".
Text Deleted�
Text
"EVENT DATE TAP SETTINGS"
Text Inserted�
Text
"(as indicated on (MEASURED using"
Text Inserted�
Text
"TAP SETTINGS"
Text Inserted�
Text
"EVENT DATE"
Text Inserted�
Text
"the rectifier meter) a voltmeter)"
Text Inserted�
Text
"VOLTS AMPS"
Text Inserted�
Text
"(AMPS)"
Text Deleted�
Text
"the text of the Standardized Compliance inspection Manual,"
Text Deleted�
Text
"diagram and"
Text Replaced�
Text
[Old]: "Additional" [New]: "Replacement or addition of" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "tanks/ piping" [New]: "tanks/piping" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "Other________________________________________________________________________________________________________________________" [New]: "Other______________________________________________________________________________________________________________________" Font "Arial" changed to "ArialMT".
Text Deleted�
Text
"_____________________________________________________________________________________________________________________________ ___"
Text Replaced�
Text
[Old]: "35" [New]: "2 RDA-2304 CN-1304" Font "Times New Roman" changed to "Arial".Font-size "12" changed to "9".
Page 101: Total Changes Content 821 - tn.gov

36

XIII. UST FACILITY SITE DRAWING Attach detailed legible drawing or use the space provided to draw a sketch of the UST and cathodic protection systems. Sufficient detail must be given in order to clearly indicate where the reference electrode was placed for each structure-to-soil potential that is recorded on the survey forms. Include details such as: all tanks, piping, and dispensers; buildings and streets; anodes and wires; and location of rectifier. Each CP test (reference electrode placement) location must be indicated by a code (1,2, T-1, D-1, etc.) corresponding with the appropriate line number in Section XV. of this form.

AN EVALUATION OF THE CATHODIC PROTECTION SYSTEM IS NOT COMPLETE WITHOUT AN ACCEPTABLE SITE DRAWING.

Text Deleted�
Text
"in order"
Text Replaced�
Text
[Old]: "as:" [New]: "as the location of" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "location of" [New]: "the" Font "Arial" changed to "ArialMT".
Text Inserted�
Text
"DRAFT"
Text Deleted�
Text
"36"
Page 102: Total Changes Content 821 - tn.gov

37

XIV. IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM CONTINUITY SURVEY

This section will be utilized to conduct measurements of continuity on UST systems that are protected by cathodic protection systems. Conduct point-to-point test between the disconnected rectifier negative cable and all other structures. For impressed current systems, the protected structure must be continuous with all other protected structures in order to pass the continuity survey.

FACILITY NAME:

FACILITY ID NUMBER:

STRUCTURE “A”1 STRUCTURE “B”2

POINT-TO-POINT3

VOLTAGE

DIFFERENCE

ISOLATED/

CONTINUOUS/ INCONCLUSIVE4

(example)

RECTIFIER NEGATIVE CABLE (example)

PLUS STEEL PROD LINE @ STP (example)

11 mV

(example)

ISOLATED

(example)

RECTIFIER NEGATIVE CABLE (example)

PLUS STEEL TANK BOTTOM (example)

0 mV

(example)

CONTINUOUS

(example)

RECTIFIER NEGATIVE CABLE (example)

PLUS TANK STP (example)

6 mV

(example)

INCONCLUSIVE

COMMENTS:

____________________________________________________________________________________________________________________________________________________________________________________

1 Structure “A” should always be the Rectifier negative cable after disconnecting from the rectifier.

2 Describe the “other” protected structure “B” that you are attempting to demonstrate is continuous (e.g. plus steel product line @ STP, plus tank

bottom, plus tank STP, etc). 3 Record the voltage difference observed between structure “A” and structure “B” when conducting “point-to-point” testing (e.g. 1 mV).

4 Document whether the test indicated the protected structure was continuous (1 -5 mV), inconclusive ( 6 - 9 mV), or isolated ( > 10 mV).

Text Deleted�
Text
"XIV. IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM CONTINUITY SURVEY"
Text Replaced�
Text
[Old]: "• This section will be utilized to conduct measurements of continuity on UST systems that are protected by" [New]: "XIV. IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM CONTINUITY SURVEY (Perform Tasks in Section XV before completing tasks in this section) • This section will be utilized to record measurements of continuity on UST systems that are protected by impressed current" Font "Wingdings" changed to "Arial-BoldMT".Font-size "7.56" changed to "10.02".
Text Replaced�
Text
[Old]: "the" [New]: "each" Font "Arial" changed to "ArialMT".Font-size "7.56" changed to "7.98".
Text Replaced�
Text
[Old]: "all other protected structures in order" [New]: "the disconnected rectifier negative cable" Font "Arial" changed to "ArialMT".Font-size "7.56" changed to "7.98".
Text Replaced�
Text
[Old]: "POINT-TO-POINT 3 ISOLATED/ CONTINUOUS/" [New]: "POINT-TO- POINT 3 VOLTAGE ISOLATED / CONTINUOUS /" Font "Arial,Bold" changed to "Arial-BoldMT".
Text Deleted�
Text
"VOLTAGE"
Text Deleted�
Text
"ISOLATED"
Text Inserted�
Text
"ISOLATED"
Text Inserted�
Text
"DRAFT"
Text Inserted�
Text
"(example) (example) (example) (example) CONTINUOUS RECTIFIER NEGATIVE CABLE REGULAR TANK TOP 4 mV"
Text Inserted�
Text
"__________________________________________________________________________________________"
Text Deleted�
Text
"2 3 4"
Text Replaced�
Text
[Old]: "Rectifier" [New]: "rectifier" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "rectifier." [New]: "rectifier (unless you are documenting continuity of flex connectors protected by galvanic anodes). 2" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "etc)." [New]: "etc.). 3" Font "Arial" changed to "ArialMT".
Text Inserted�
Text
"4"
Text Replaced�
Text
[Old]: "37" [New]: "4 RDA-2304 CN-1304" Font "Times New Roman" changed to "Arial".Font-size "12" changed to "9".
Page 103: Total Changes Content 821 - tn.gov

38

XV. IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM SURVEY

This section will be utilized to conduct a survey of an impressed current cathodic protection system by obtaining structure-to-soil potential measurements.

The reference electrode must be placed in soil directly over the tested structure and as far away from active anodes as practical to obtain a valid structure-to-soil potential.

Both on and instant off potentials must be measured for each structure that is intended to be under cathodic protection.

All instant off potentials must be -850 mV or more negative or the 100 mV polarization criterion must be satisfied in order to pass.

At least three readings shall be recorded over each tank, one reading at each dispenser, and mid points of steel product lines more than 100 feet in length.

FACILITY NAME:

FACILITY ID NUMBER:

LOCATION

CODE1 STRUCTURE

2 CONTACT POINT

3 REFERENCE CELL PLACEMENT

4 ON

VOLTAGE5

INSTANT

OFF

VOLTAGE6

100 mV POLARIZATION PASS /

FAIL9

ENDING

VOLTAGE7

VOLTAGE

CHANGE8

(example)

1 (example)

PLUS TANK (example)

TANK BOTTOM (example)

SOIL @ REG. TANK STP MANWAY

(example)

-1070 mV (example)

-875 mV

(example)

PASS

(example)

2 (example)

PLUS PIPING

(example)

DISPENSER 5/6 (example)

UNDER DISPENSER 5/6 (example)

-810 mV (example)

-680 mV (example)

-575 mV

(example)

105 mV (example)

PASS

COMMENTS: ________________________________________________________________________________ _________________________________________________________________________________________

1 Designate numerically or by code on the site drawing each “local” reference electrode placement (e.g. 1, 2, 3… T-1, T-2, P-1, P-2…etc.).

2 Describe the structure that is being tested (e.g. plus tank; diesel piping; flex connector; etc.).

3 Describe where the structure being tested is contacted by the test lead (e.g. plus tank bottom, diesel piping @ dispenser 7/8, etc).

4 Describe exact location where reference electrode is placed for each measurement (e.g., soil @ regular tank STP, soil @ dispenser 5/6, etc.)

5 Record the structure-to-soil potential observed with the current applied (e.g. –1070 mV).

6 Record the structure-to-soil potential observed with the current is interrupted (e.g., -875 mV).

7 (Applies to 100 mV polarization only) Record the voltage observed at the end of the test period (e.g., -575 mV)

8 (Applies to 100 mV polarization only) Subtract the instant off voltage from the ending voltage (e.g., -575 mV – [-680 mV] = 105 mV change)

9 Indicate if the tested structure passed or failed one of the two acceptable criteria (<-850 mV instant off or >100 mV polarization).

Text Deleted�
Text
"XV. IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM SURVEY"
Text Replaced�
Text
[Old]: "• This section will be utilized to conduct a survey of an impressed current cathodic protection system by obtaining structure-to-soil potential measurements." [New]: "XV. IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM SURVEY • This section will be utilized to record structure-to-soil potential measurements obtained from a survey of the impressed current cathodic protection system." Font "Wingdings" changed to "Arial-BoldMT".Font-size "6.96001" changed to "10.02".
Text Replaced�
Text
[Old]: "intended" [New]: "required" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "under cathodic protection." [New]: "cathodically protected." Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "polarization" [New]: "shift" Font "Arial" changed to "ArialMT".
Text Deleted�
Text
"in order"
Text Replaced�
Text
[Old]: "At least three readings shall be recorded" [New]: "Collect at least three potential readings" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "dispenser, and mid points of steel product lines more than" [New]: "end of every piping run, and one reading at the midpoint of product lines over" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "POLARIZATION" [New]: "SHIFT CONTACT POINT 3" Font "Arial,Bold" changed to "Arial-BoldMT".
Text Inserted�
Text
"REFERENCE CELL PLACEMENT"
Text Replaced�
Text
[Old]: "ON PASS / LOCATION CODE 1 STRUCTURE 2 CONTACT POINT 3" [New]: "4 STRUCTURE 2 ON VOLTAGE 5 PASS / FAIL 9 LOCATION CODE 1" Font "Arial,Bold" changed to "Arial-BoldMT".Font-size "6.48" changed to "6".
Text Deleted�
Text
"REFERENCE CELL PLACEMENT"
Text Replaced�
Text
[Old]: "4 OFF 5 ENDING FAIL 9 7 VOLTAGE 8 VOLTAGE 6 VOLTAGE VOLTAGE CHANGE" [New]: "OFF ENDING VOLTAGE VOLTAGE 6 VOLTAGE 7 CHANGE 8" Font "Arial,Bold" changed to "Arial-BoldMT".Font-size "6" changed to "6.48".
Text Deleted�
Text
"1 PLUS TANK TANK"
Text Replaced�
Text
[Old]: "REG." [New]: "PLUS" Font "Comic Sans MS,Bold" changed to "ComicSansMS".
Text Inserted�
Text
"1 PLUS TANK"
Text Replaced�
Text
[Old]: "2 PLUS DISPENSER 5/6 UNDER DISPENSER" [New]: "PLUS PIPING PASS 2 PLUS PIPING SOIL UNDER DISP" Font "Comic Sans MS,Bold" changed to "ComicSansMS".
Text Replaced�
Text
[Old]: "PASS" [New]: "@ DISP 5/6" Font "Comic Sans MS,Bold" changed to "ComicSansMS".Font-size "8.03999" changed to "8.52".
Text Inserted�
Text
"DRAFT"
Text Replaced�
Text
[Old]: "etc)." [New]: "etc.)." Font "Arial" changed to "ArialMT".
Text Deleted�
Text
"6 7 8"
Text Inserted�
Text
"6"
Text Replaced�
Text
[Old]: "with" [New]: "when" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "-875 mV)." [New]: "–875 mV). 7" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "polarization" [New]: "shift" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "-575 mV)" [New]: "–575 mV) 8" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "polarization" [New]: "shift" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "-575" [New]: "–575" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "[-680" [New]: "[–680" Font "Arial" changed to "ArialMT".
Text Inserted�
Text
"9"
Text Replaced�
Text
[Old]: "(<-850 mV instant off or >100 mV polarization). 9" [New]: "(more negative than –850 mV instant-off or greater than 100 mV shift criteria)." Font "Arial" changed to "ArialMT".
Text Deleted�
Text
"38"
Page 104: Total Changes Content 821 - tn.gov

39

XVI. FLEXIBLE CONNECTOR CATHODIC PROTECTION SYSTEM

This form will be utilized to conduct a survey of galvanic protected flexible connectors by obtaining structure-to-soil potential measurements.

A minimum of one measurement must be made with the reference electrode placed in soil directly over the tested structure (local) and one measurement at a remote earth location, at least 25-100 feet away from the structure.

Flex connectors in contained sumps or continuous with dispenser cabinets or STPs must use instant off or voltage change (100 mV shift) to determine protected status. If either local or remote reading is more positive than -850 mV, obtain instant off by disconnecting anode. If instant off is more positive than -850 mV, then conduct 100 mV polarization and record ending voltage. If difference between

instant off and ending voltage is more than 100 mV, the result is PASS. If difference is less than 100 mV, or either local or remote reading is more positive than -850 mV, then structure is not protected and the result is FAIL.

FACILITY NAME: FACILITY ID NUMBER:

Location of Remote Reference Cell Placement, if Applicable (also designate on site drawing):

TANK #, PRODUCT, CAPACITY

1

FLEX LOCATION

2

WHERE ANODE

ATTACHED?

CONTINUOUS OR

ISOLATED? 3

CONTACT POINT4

LOCAL VOLTAGE

5

REMOTE VOLTAGE

6

INSTANT OFF

VOLTAGE (if necessary)

100 mV POLARIZATION

PASS/FAIL7

ENDING VOLTAGE

(if necessary)

VOLTAGE CHANGE

E X A M P L E S

#2 DIESEL 8,000 DIESEL FLEX AT

STP ON FLEX ISO. ON FLEX -875 mV -760 mV -860 mV

PASS

#3 REGULAR 10,000 REG. FLEX AT

DISPENSER 3/4

PIPING ABOVE SHEAR VALVE

CONT. PIPING ABOVE SHEAR

VALVE -980 mV -845 mV -790 mV 55 mV FAIL

#4 PREMIUM 10,000 PREM. FLEX IN

CONTAINED SUMP

STP HEAD CONT. STP HEAD

-910 mV

PASS

COMMENTS:__________________________________________________________________________________________________________________________________________________

______________________________________________________________________________________________________________________________________________________________

1 Designate the number, product, and capacity of the tank with which the flex connector is associated.

2 Indicate location of flex being tested (e.g. REGULAR FLEX AT DISPENSER 3/4, DIESEL FLEX AT STP, etc.)

3 Continuity or isolation of flex connectors must be documented before completion of this section to determine whether to use remote or instant off/100 mV polarization. If testing flex connectors only, include Continuity Survey section (XIV.) of this form with this section.

4 Designate exact point of contact when testing flex (i.e., if isolated, must contact only the flex itself. If continuous with another component, can contact either one.)

5 Record the structure-to-soil potential measured with the reference electrode placed “local” in millivolts (e.g. –875 mV, -980 mV, etc.).

6 Record the structure-to-soil potential measured with the reference electrode placed “remote” (or use the voltage measurements obtained during continuity survey if remote reference cell placement was used).

7 Indicate whether the tested structure passed or failed based on your interpretation of the test data.

Text Replaced�
Text
[Old]: "CONNECTOR CATHODIC PROTECTION SYSTEM" [New]: "CONNECTORS (OR OTHER SHORT SECTIONS OF METAL PIPING) CATHODIC PROTECTION SYSTEM SURVEY" Font "Arial,Bold" changed to "Arial-BoldMT".
Text Replaced�
Text
[Old]: "conduct a survey of galvanic protected flexible connectors by obtaining structure-to-soil potential measurements. • A minimum of one measurement must be made with the reference electrode placed in soil directly over the tested structure (local) and one measurement at a remote earth location, at least 25-100 feet away from the structure. • Flex connectors in contained sumps or continuous with dispenser cabinets or STPs must use instant off or voltage change (100 mV shift) to determine protected status. • If either local or remote reading is more positive than -850 mV, obtain instant off by disconnecting anode. If instant off is more positive than -850 mV, then conduct" [New]: "record structure-to-soil potential measurements for galvanically protected flex connectors (or short piping sections). • A total of three (3) potential measurements (one local and two at remote earth to determine True Remote Earth) is required for each flex connector when using the “On” / ”Local Voltage” (-850 mV) criteria. Record the True Remote Earth Voltage on the form below. • If either the local or the remote potential measurements fail (more positive than -850 mV), use the instant off or 100 mV shift criteria to determine protective status (i.e. Pass / Fail). The instant off or 100 mV shift measurements are obtained after disconnecting the anode from the flex connector. • See also Appendix 4 of Technical Chapter 4.1, Corrosion Protection. • Potential measurements must be obtained for each flex connector. FACILITY NAME: FACILITY ID NUMBER: Location of Remote Reference Cell Placement, if Applicable (also designate on site drawing):" Font "Arial" changed to "ArialMT".Font-size "6.48" changed to "7.98".
Text Inserted�
Text
"______________________________________________________________________________________________________________________________________________________________ DRAFT"
Text Replaced�
Text
[Old]: "polarization and" [New]: "SHIFT TRUE INSTANT WHERE IS CONTINUOUS OR ISOLATED? 3 (must also complete Section XIV) TANK #, PRODUCT, CAPACITY 1 LOCAL REMOTE OFF ENDING FLEX LOCATION 2 CONTACT POINT 4 PASS/FAIL 7 VOLTAGE CHANGE ANODE VOLTAGE VOLTAGE 5 EARTH VOLTAGE ATTACHED? VOLTAGE 6 (if necessary) (if necessary) DIESEL FLEX AT ON FLEX ISO. ON FLEX -875 mV -760 mV -860 mV PASS E X #2 DIESEL 8,000 STP PIPING A M #3 REGULAR REG. FLEX AT ABOVE PIPING ABOVE SHEAR VALVE CONT. -980 mV 845 mV -790 mV 55 mV FAIL - 10,000 DISPENSER 3/4 SHEAR P VALVE L PREM. STP FLEX E #4 PREMIUM IN CONTAINED STP HEAD CONT. STP HEAD -910 mV PASS S 10,000 SUMP COMMENTS:__________________________________________________________________________________________________________________________________________________ 1 Designate the number, product, and capacity of the tank with which the flex connector is associated. 2 Indicate location of flex being tested (e.g. REGULAR FLEX AT DISPENSER 3/4, DIESEL FLEX AT STP, etc.) 3 Continuity or isolation of flex connectors must be documented in the Continuity Survey section (XIV) before completion of this section to determine whether to use remote voltage or instant off/100 mV shift. If testing flex connectors only, include Continuity Survey section (XIV) of this form with this section. 4 Designate exact point of contact when testing flex (i.e., if isolated, must contact only the flex itself. If continuous with another component, can contact either one). 5 Record the structure-to-soil potential measurement for “Local Voltage” in millivolts (e.g. –875 mV, -980 mV, etc.). 6 Record the structure-to-soil potential measurement for “True Remote Earth Voltage” in millivolts. 7 Indicate whether the tested structure passed or failed based on your interpretation of the test data." Font "Arial" changed to "Arial-BoldMT".Font-size "6.48" changed to "7.02".
Text Inserted�
Text
"6 RDA-2304 CN-1304"
Text Replaced�
Text
[Old]: "record ending voltage. If difference between instant off and ending voltage is more than 100 mV, the result is PASS. If difference is less than 100 mV, or either local or remote reading is more positive than -850 mV, then structure is not protected and the result is FAIL." [New]: "XVI. FLEXIBLE CONNECTORS (OR OTHER SHORT SECTIONS OF METAL PIPING) CATHODIC PROTECTION SYSTEM SURVEY (CONTINUTED) • This form will be utilized to record structure-to-soil potential measurements for galvanically protected flex connectors (or short piping sections). • A total of three (3) potential measurements (one local and two at remote earth to determine True Remote Earth) is required for each flex connector when using the “On” / “Local Voltage” (-850 mV) criteria. Record the True Remote Earth Voltage on the form below. • If either the local or the remote potential measurements fail (more positive than -850 mV), use the instant off or 100 mV shift criteria to determine protective status (i.e. Pass / Fail). The instant off or 100 mV shift measurements are obtained after disconnecting the anode from the flex connector. • See also Appendix 4 of Technical Chapter 4.1, Corrosion Protection. • Potential measurements must be obtained for each flex connector." Font "Arial" changed to "Arial-BoldMT".Font-size "6.48" changed to "10.02".
Text Inserted�
Text
"______________________________________________________________________________________________________________________________________________________________ DRAFT"
Text Deleted�
Text
"INSTANT"
Text Replaced�
Text
[Old]: "POLARIZATION WHERE CONTINUOUS OFF TANK #, PRODUCT, CAPACITY 1 FLEX LOCAL REMOTE ENDING CONTACT POINT 4 PASS/FAIL 7 ANODE OR VOLTAGE VOLTAGE LOCATION 2 VOLTAGE 5 VOLTAGE 6 VOLTAGE ISOLATED? 3 ATTACHED? (if necessary) CHANGE" [New]: "SHIFT TRUE INSTANT WHERE IS CONTINUOUS OR ISOLATED? 3 (must also complete Section XIV) TANK #, PRODUCT, CAPACITY 1 LOCAL REMOTE OFF ENDING FLEX LOCATION 2 CONTACT POINT 4 PASS/FAIL 7 VOLTAGE CHANGE ANODE VOLTAGE VOLTAGE 5 EARTH VOLTAGE ATTACHED? VOLTAGE 6 (if necessary)" Font "Arial,Bold" changed to "Arial-BoldMT".
Text Inserted�
Text
"X"
Text Replaced�
Text
[Old]: "X A PIPING" [New]: "PIPING A M #3 REGULAR" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "M #3 REGULAR 10,000 CONT. -980 mV -845" [New]: "VALVE CONT. -980 mV 845" Font "Arial" changed to "ArialMT".
Text Inserted�
Text
"- 10,000"
Text Deleted�
Text
"VALVE"
Text Replaced�
Text
[Old]: "E PREM. FLEX IN" [New]: "PREM. STP FLEX E" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "10,000" [New]: "IN" Font "Arial" changed to "ArialMT".
Text Inserted�
Text
"10,000"
Text Deleted�
Text
"______________________________________________________________________________________________________________________________________________________________"
Text Inserted�
Text
"2"
Text Inserted�
Text
"3"
Text Inserted�
Text
"in the Continuity Survey section (XIV)"
Text Inserted�
Text
"voltage"
Text Replaced�
Text
[Old]: "polarization." [New]: "shift." Font "Arial,Bold" changed to "ArialMT".Font-size "6.96001" changed to "7.98".
Text Replaced�
Text
[Old]: "(XIV.)" [New]: "(XIV)" Font "Arial,Bold" changed to "ArialMT".Font-size "6.96001" changed to "7.98".
Text Inserted�
Text
"4"
Text Replaced�
Text
[Old]: "one.)" [New]: "one). 5" Font "Arial,Bold" changed to "ArialMT".Font-size "6.96001" changed to "7.98".
Text Replaced�
Text
[Old]: "measured with the reference electrode placed “local”" [New]: "measurement for “Local Voltage”" Font "Arial,Bold" changed to "ArialMT".Font-size "6.96001" changed to "7.98".
Text Inserted�
Text
"6"
Text Replaced�
Text
[Old]: "measured with the reference electrode placed “remote” (or use the voltage measurements obtained during continuity survey if remote reference cell placement was used)." [New]: "measurement for “True Remote Earth Voltage” in millivolts. 7" Font "Arial,Bold" changed to "ArialMT".Font-size "6.96001" changed to "7.98".
Text Deleted�
Text
"2 3 4 5 6 7 39"
Page 105: Total Changes Content 821 - tn.gov

40

APPENDIX 7

GALVANIC CATHODIC PROTECTION TESTING SURVEY

(Modifications are made to these forms from time to time. Please check the Division’s website for

the most current version of the State’s official form)

Text Replaced�
Text
[Old]: "7" [New]: "7:" Font "Open Sans,Bold" changed to "OpenSans-Bold".
Text Inserted�
Text
"DRAFT"
Text Deleted�
Text
"40"
Page 106: Total Changes Content 821 - tn.gov

41

DEPARTMENT OF ENVIRONMENT AND CONSERVATION

DIVISION OF UNDERGROUND STORAGE TANKS

William R Snodgrass Tennessee Tower

312 Rosa L. Parks Avenue, 12th

Floor

Nashville, TN 37243

GALVANIC CATHODIC PROTECTION TESTING SURVEY

This form must be utilized to evaluate underground storage tank (UST) cathodic protection systems in the State of Tennessee.

Access to the soil directly over the cathodically protected structure that is being evaluated must be provided.

I. UST FACILITY II. UST OWNER

NAME: NAME:

FACILITY ID NUMBER: COMPANY:

ADDRESS: ADDRESS:

CITY: COUNTY: CITY: STATE:

III. CP TESTER

TESTER’S NAME: COMPANY:

ADDRESS: LIST CERTIFICATION, IF ANY:

CITY: STATE: PHONE NUMBER:

IV. REASON SURVEY WAS CONDUCTED (mark only one)

□ Routine - 3 year □ Routine – within 6 months of installation □ Re-survey after fail □ Re-survey after repair/modification

Date next cathodic protection survey must be conducted by: __________________________ (required within 6 months of installation/repair, or every 3 years).

V. CATHODIC PROTECTION TESTER’S EVALUATION (mark only one)

□ PASS All protected structures at this facility pass the cathodic protection survey and it is judged that adequate cathodic protection has been provided to the UST system (indicate all applicable criteria by completion of Section VII).

□ INCOMPLETE One or more protected structures at this facility fail the cathodic protection survey and it is judged that adequate cathodic protection has not been provided to the UST system (complete Section VIII).

□ FAIL All tanks or piping did not pass the cathodic protection survey (complete Section VIII).

□ INCONCLUSIVE If the remote and local do not both indicate the same result on all protected structures (both pass or fail), inconclusive is indicated and the resurvey must be evaluated and/or conducted by a corrosion expert.(Complete section VI.)

CP TESTER’S SIGNATURE: ________________________________________________

DATE CP SURVEY PERFORMED: ________________________________

VI. CORROSION EXPERT’S EVALUATION (mark only one) The survey must be conducted and/or evaluated by a corrosion expert when: a) an inconclusive is indicated for any protected structure since both the local and the remote structure-to-soil potentials do not result in the same outcome (both pass or both fail); b) repairs to galvanized or uncoated steel piping are conducted or c) supplemental anodes are added to the tanks and/or piping.

□ PASS (based on

above criteria) □ FAIL (based on above criteria)

CORROSION EXPERT’S NAME: COMPANY NAME:

NACE INTERNATIONAL CERTIFICATION NUMBER:

CORROSION EXPERT’S SIGNATURE: _________________________________________________________ DATE: _____________________________________

VII. CRITERIA APPLICABLE TO EVALUATION (mark all that apply)

□ 850 ON Structure-to-soil potential more negative than –850 mV with respect to a Cu/CuSO4 reference electrode with the protective current applied (applicable to any galvanically protected structure).

□ 850 OFF Structure-to-soil potential more negative than –850 mV with respect to a Cu/CuSO4 reference electrode with protective current temporarily interrupted (applicable only to galvanic systems where the anodes can be disconnected).

□ 100 mV Polarization Structure tested exhibits at least 100 mV of cathodic polarization (applicable to galvanic systems where the anodes can be temporarily disconnected).

VIII. ACTION REQUIRED AS A RESULT OF THIS EVALUATION (mark only one)

□ NONE Cathodic protection is adequate. No further action is necessary at this time. Test again by no later than the date specified in Section IV.

□ REPAIR & RETEST Cathodic protection is not adequate. Repair/modification is necessary as soon as practical.

Text Inserted�
Text
"STATE OF TENNESSEE"
Text Replaced�
Text
[Old]: "This form must be utilized" [New]: "Utilize this form" Font "Arial" changed to "ArialMT".
Text Inserted�
Text
"galvanic"
Text Replaced�
Text
[Old]: "must be provided." [New]: "is required." Font "Arial" changed to "ArialMT".
Text Inserted�
Text
"DRAFT DRAFT"
Text Replaced�
Text
[Old]: "-3" [New]: "– 3" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "fail □ Re-survey after repair/modification" [New]: "fail/repair/modification" Font "Arial" changed to "ArialMT".
Text Deleted�
Text
"within 6 months of installation/repair, or"
Text Replaced�
Text
[Old]: "All protected structures at this facility pass the cathodic protection survey and it is judged that adequate cathodic protection has been provided to the UST system (indicate all applicable criteria by completion of Section VII)." [New]: "A has ll pr been pr otected s ovi tr de uc d to the US tures at this T fac sys il tem ity pas (indi s the c cate al ath l appl odic ic pr abl otec e c ti r on s iteria ur by vey com and i pleti t is on of S judged that ad ection VII) equ . ate cathodic protection" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "One or more protected structures at this facility fail the cathodic protection survey and it is judged that adequate cathodic protection has not been provided to the UST system (complete Section VIII)." [New]: "O pr ne o otec r tion has more pr no otec t been pr ted struc ov tur ided t es at thi o the US s fac T ili s ty ys fai tem l the c (com athodi plete S c pr ec ot ti ec on V tion s III) ur . vey and it is judged that adequate cathodic" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "If the remote and local do not both indicate the same result on all protected structures (both pass or fail), inconclusive is indicated and the resurvey must be evaluated and/or conducted by a corrosion expert.(Complete section VI.) □ INCONCLUSIVE CP TESTER’S SIGNATURE:" [New]: "□ INCONCLUSIVE If the r indicated and the emote and l r oc es al urv do not both ey must be ev indi al cate the s uated and/ am or e r c es onduc ult on al ted by l pr a c otec or ted s rosion ex tructur pe es rt.( (both pas Complete s s or ec fai tion V l), inc I.) onclusive is CP TESTER’S SIGNATURE: ________________________________________________" Font "Arial" changed to "ArialMT".Font-size "8.03999" changed to "19.98".
Text Replaced�
Text
[Old]: "conducted" [New]: "conducted;" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "supplemental anodes are added to the tanks and/or piping." [New]: "replacement or addition of anodes for tanks and/or piping (except flexible connectors and/or short sections of metal piping)." Font "Arial" changed to "ArialMT".
Text Inserted�
Text
"□"
Text Replaced�
Text
[Old]: "potential more negative than –850 mV" [New]: "potentials –850 mV or more negative" Font "Arial" changed to "ArialMT".
Text Deleted�
Text
"□"
Text Replaced�
Text
[Old]: "potential more negative than –850 mV" [New]: "potentials –850 mV or more negative" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "Polarization" [New]: "Shift" Font "Arial,Bold" changed to "Arial-BoldMT".
Text Replaced�
Text
[Old]: "of cathodic polarization" [New]: "shift" Font "Arial" changed to "ArialMT".
Text Deleted�
Text
"41"
Page 107: Total Changes Content 821 - tn.gov

42

IX. DESCRIPTION OF UST SYSTEM

FACILITY NAME: FACILITY ID NUMBER:

TANK # PRODUCT CAPACITY TANK MATERIAL PIPING MATERIAL FLEX CONNECTORS / LOCATION

1

2

3

4

5

6

7

8

9

10

If metal flex connectors are present, are they corrosion protected?

□ YES Method: □ Isolation (booted) □Isolation (contained in sump or no soil contact)

□ Attached Anode1

□ NO Action taken: __________________________________________________________________________

1If the flex connectors are protected by sacrificial anodes, test accordingly and include in Section XIV. on this form.

X. DESCRIPTION OF CATHODIC PROTECTION SYSTEM REPAIRS AND/OR MODIFICATION Complete if repairs or modifications to the cathodic protection system are made or are necessary. Certain repairs/modifications as explained in the text of the

Standardized Compliance inspection Manual, Technical Chapter 4.1 Corrosion Protection are required to be designed and/or evaluated by a corrosion expert (completion of Section VI. required).

□ Adding supplemental anodes for a sti-P3® tank (attach corrosion expert’s design).

□ Adding supplemental anodes for metallic pipe (attach corrosion expert’s design).

□ Resolving continuity issues when problems identified and system does not pass (attach explanation).

Remarks/Other: __________________________________________________________________________________________________________________________

Text Replaced�
Text
[Old]: "ID NUMBER: FACILITY NAME:" [New]: "NAME: FACILITY ID NUMBER:" Font "Arial,Bold" changed to "Arial-BoldMT".
Text Replaced�
Text
[Old]: "/ LOCATION 1 2 3 4 5 6 7 8 9 10" [New]: "(Y / N). IF YES, INDICATE LOCATION (STP / DISP / STP AND DISP) 1 2 3 4 5 6 7" Font "Arial,Bold" changed to "ArialMT".
Text Inserted�
Text
"If metal flex connectors"
Text Replaced�
Text
[Old]: "□ Isolation (booted) □Isolation (contained in sump or no soil contact)" [New]: "□Isolation (booted)" Font "Arial,Bold" changed to "Arial-BoldMT".
Text Inserted�
Text
"DRAFT DRAFT"
Text Inserted�
Text
"(provide details in comments) □Isolation (not in contact with the ground)"
Text Deleted�
Text
"If metal flex connectors"
Text Inserted�
Text
"Comments (e.g., piping brand, specific flex/anode location, etc.):"
Text Replaced�
Text
[Old]: "the text of the Standardized Compliance inspection Manual, Technical Chapter 4.1 Corrosion Protection" [New]: "Technical Chapter 4.1 Corrosion Protection," Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "supplemental" [New]: "or replacing existing" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "supplemental" [New]: "or replacing existing" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "Remarks/Other:" [New]: "Remarks/Other"
Text Deleted�
Text
"__________________________________________________________________________________________________________________________"
Text Deleted�
Text
"42"
Page 108: Total Changes Content 821 - tn.gov

43

XI. UST FACILITY SITE DRAWING

Attach detailed legible drawing or use the space provided to draw a sketch of the UST and cathodic protection systems. Sufficient detail must be given in order to clearly indicate where the reference electrode was placed for each structure-to-soil potential that is recorded on the survey forms. Include details such as: all tanks, piping, and dispensers; buildings and streets; anodes and wires; and location of rectifier. Each CP test (reference electrode placement) location must be indicated by a code (1,2, T-1, D-1, etc.) corresponding with the appropriate line number in Section XIII. of this form.

AN EVALUATION OF THE CATHODIC PROTECTION SYSTEM IS NOT COMPLETE WITHOUT AN ACCEPTABLE SITE DRAWING.

Text Deleted�
Text
"in order"
Text Replaced�
Text
[Old]: "electrode" [New]: "electrode/cell" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "as:" [New]: "as the location of" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "anodes and wires; and location of rectifier." [New]: "and additional anodes (if applicable)and wires." Font "Arial" changed to "ArialMT".
Text Inserted�
Text
"Also, include the two (2) locations used to determine true remote earth (e.g., R1 and R2)."
Text Inserted�
Text
"DRAFT DRAFT"
Text Deleted�
Text
"43"
Page 109: Total Changes Content 821 - tn.gov

44

XII. GALVANIC (SACRIFICIAL ANODE) CATHODIC PROTECTION SYSTEM CONTINUITY SURVEY

This section will be utilized to conduct measurements of continuity on UST systems that are protected by cathodic protection systems. When conducting a fixed cell-moving ground survey, the reference electrode must be placed in the soil at a remote earth location and left undisturbed. Either fixed cell-moving ground or point-to-point methods may be used to test continuity between any two structures. For galvanic systems, the structure that is to be protected must be isolated from any other metallic structure in order to pass the continuity survey.

FACILITY NAME:

FACILITY ID NUMBER:

DESCRIBE LOCATION OF “FIXED REMOTE” REFERENCE ELECTRODE PLACEMENT:

STRUCTURE “A” 1 STRUCTURE “B” 2

STRUCTURE “A” 3

FIXED REMOTE VOLTAGE

STRUCTURE “B” 4

FIXED REMOTE VOLTAGE

POINT-TO-POINT 5

VOLTAGE DIFFERENCE

ISOLATED/ 6

CONTINUOUS/ INCONCLUSIVE

(example)

PREMIUM TANK BOTTOM (example)

PREMIUM TANK FILL RISER (example)

-921 mV (example)

-915 mV (example)

INCONCLUSIVE

(example)

PREMIUM TANK BOTTOM (example)

PREMIUM TANK FILL RISER (example)

17 mV (example)

ISOLATED

COMMENTS: _______________________________________________________________________________ ________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________________

1 Describe the cathodically protected structure that you are attempting to demonstrate is isolated from unprotected structures (e.g. prem. tank).

2 Describe the unprotected structure that you are attempting to demonstrate is isolated from the protected structure (e.g. premium tank fill riser).

3 Record the measured structure-to-soil potential of the cathodically protected structure {“A”} in millivolts (e.g. –921 mV).

4 Record the measured structure-to-soil potential of the unprotected structure {“B”} in millivolts (e.g. –915 mV).

5 Record the voltage observed between the protected and the unprotected structures when conducting point-to-point testing (e.g. 17 mV).

6 Document whether the test indicated the protected structure was continuous (1 -5 mV), inconclusive ( 6 - 9 mV), or isolated ( > 10 mV).

Text Deleted�
Text
"XII. GALVANIC (SACRIFICIAL ANODE) CATHODIC PROTECTION SYSTEM CONTINUITY SURVEY"
Text Replaced�
Text
[Old]: "conduct" [New]: "record" Font "Arial" changed to "ArialMT".
Text Inserted�
Text
"galvanic"
Text Replaced�
Text
[Old]: "electrode" [New]: "electrode/cell" Font "Arial" changed to "ArialMT".
Text Deleted�
Text
"the"
Text Inserted�
Text
"true"
Text Deleted�
Text
"in order"
Text Replaced�
Text
[Old]: "survey. FACILITY NAME: FACILITY ID NUMBER: DESCRIBE LOCATION OF “FIXED REMOTE” REFERENCE ELECTRODE PLACEMENT:" [New]: "survey except for conditions specified in Section XIV FACILITY NAME: FACILITY ID NUMBER: DESCRIBE LOCATION OF TRUE REMOTE EARTH REFERENCE ELECTRODE/CELL PLACEMENT (e.g. In grass 50 feet NE of Premium Tank, etc.): Provide the two (2) remote measurements used to determine the location of “True Remote Earth” (measurements must be less than 10 mV difference) (e.g., Premium Tank Remote 1 = -890 mV & Premium Tank Remote 2 = -884 mV, etc.):" Font "Arial" changed to "ArialMT".
Text Inserted�
Text
"ISOLATED/"
Text Deleted�
Text
"ISOLATED/"
Text Replaced�
Text
[Old]: "FIXED REMOTE FIXED" [New]: "TRUE REMOTE TRUE" Font "Arial,Bold" changed to "Arial-BoldMT".
Text Inserted�
Text
"EARTH VOLTAGE EARTH"
Text Deleted�
Text
"INCONCLUSIVE"
Text Inserted�
Text
"INCONCLUSIVE"
Text Inserted�
Text
"(example)"
Text Inserted�
Text
"DRAFT DRAFT"
Text Inserted�
Text
"(example) (example) (example) ISOLATED PREMIUM STP FLEX PREMIUM STP 25 mV"
Text Deleted�
Text
"________________________________________________________________________________________"
Text Deleted�
Text
"2 3 4"
Text Inserted�
Text
"2"
Text Inserted�
Text
"3"
Text Inserted�
Text
"at true remote earth"
Text Replaced�
Text
[Old]: "{“A”}" [New]: "“A”" Font "Arial" changed to "ArialMT".
Text Inserted�
Text
"4"
Text Replaced�
Text
[Old]: "of the unprotected structure {“B”}" [New]: "at true remote earth of the unprotected structure “B”" Font "Arial" changed to "ArialMT".
Text Inserted�
Text
"5"
Text Inserted�
Text
"6"
Text Replaced�
Text
[Old]: "( 6" [New]: "(6" Font "Arial" changed to "ArialMT".
Text Deleted�
Text
"5 6"
Text Deleted�
Text
"44"
Page 110: Total Changes Content 821 - tn.gov

45

XIII. GALVANIC (SACRIFICIAL ANODE) CATHODIC PROTECTION SYSTEM SURVEY

This section will be utilized to conduct a survey of a galvanic cathodic protection system by obtaining structure-to-soil potential measurements.

The reference electrode must be placed in soil directly over the tested structure (local) and at a remote earth location, at least 25-100 feet away from the structure.

A minimum of one local measurement must be made over the middle of the tank. Additional readings may be made over both ends of each tank if desired.

All local and remote earth voltage readings must be –850 mV or more negative in order for the structure to pass.

Inconclusive is indicated when both the local and remote earth structure-to-soil potentials do not result in the same outcome (i.e., both pass or both fail).

FACILITY NAME:

FACILITY ID NUMBER:

DESCRIBE LOCATION OF REMOTE REFERENCE ELECTRODE PLACEMENT:

LOCATION1

CODE STRUCTURE

2 CONTACT POINT

3 LOCAL REFERENCE CELL PLACEMENT

4 LOCAL

VOLTAGE5

REMOTE

VOLTAGE6

PASS / FAIL /

INCONCLUSIVE7

(example)

1 (example)

PLUS TANK (example)

TANK BOTTOM (example)

PLUS TANK STP MANWAY (example)

-928 (example)

-810 (example)

INCONCLUSIVE

(example)

2 (example)

PLUS PIPING (example)

DISPENSER 5/6 (example)

UNDER DISPENSER 5/6 (example)

-890 (example)

-885 (example)

PASS

COMMENTS: _______________________________________________________________________________ ________________________________________________________________________________________________________________________________________________________________________________

1 Designate numerically or by code on the site drawing each “local” reference electrode placement (e.g. 1, 2, 3… T-1, T-2, P-1, P-2…etc.). 2 Describe the structure that is being tested (e.g. plus tank; premium piping; diesel submersible pump flex connector; etc.). 3 Describe where contact with the structure being tested is made (e.g. plus tank @ test lead; diesel piping @ dispenser 5/6; etc).

4 Describe exact location where reference electrode is placed for each “local” reading (e.g. soil @ plus tank STP; soil @ dispenser 5/6; etc.) 5 Record the structure-to-soil potential measured with the reference electrode placed “local” in millivolts (e.g. –865 mV, -920 mV, etc.). 6 Record the structure-to-soil potential measured with the reference electrode placed “remote” (copy voltage obtained during continuity survey). 7 Indicate whether the tested structure passed or failed the –850 mV “on” criterion based on your interpretation of the test data.

Text Replaced�
Text
[Old]: "conduct a survey of a galvanic cathodic protection system by obtaining structure-to-soil potential measurements." [New]: "record structure-to-soil potential measurements obtained from a galvanic cathodic protection system." Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "a" [New]: "true" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "location, at least" [New]: "(typically" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "structure." [New]: "structure)." Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "made" [New]: "obtained" Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "tank. Additional readings may be made over both ends of each tank" [New]: "tank and two at remote earth. Additional measurements may be obtained over both ends of each tank," Font "Arial" changed to "ArialMT".
Text Replaced�
Text
[Old]: "readings" [New]: "measurements" Font "Arial" changed to "ArialMT".
Text Deleted�
Text
"in order"
Text Replaced�
Text
[Old]: "DESCRIBE LOCATION OF REMOTE REFERENCE ELECTRODE PLACEMENT:" [New]: "If not provided in Section XII, provide the two (2) remote measurements used to determine the location of “True Remote Earth” (measurements must be less than 10 mV difference) (e.g., Regular Tank Remote 1 = -890 mV & Regular Tank Remote 2 = -884 mV, etc.):" Font "Arial,Bold" changed to "Arial-BoldMT".Font-size "6" changed to "7.02".
Text Inserted�
Text
"LOCAL TRUE"
Text Deleted�
Text
"LOCAL REMOTE"
Text Inserted�
Text
"REMOTE"
Text Inserted�
Text
"CODE"
Text Inserted�
Text
"EARTH"
Text Deleted�
Text
"CODE"
Text Inserted�
Text
"mV -810 mV"
Text Replaced�
Text
[Old]: "PLUS PIPING DISPENSER 5/6 UNDER DISPENSER 5/6 -890 -885 PASS" [New]: "PLUS PIPING PLUS PIPING SOIL UNDER DISP 5/6 -890 mV -885 mV PASS @DISP 5/6" Font "Comic Sans MS,Bold" changed to "ComicSansMS-BoldItalic".
Text Inserted�
Text
"DRAFT DRAFT"
Text Inserted�
Text
"________________________________________________________________________________________"
Text Replaced�
Text
[Old]: "plus tank @ test lead; diesel piping @ dispenser 5/6; etc)." [New]: "diesel piping @ dispenser 5/6; etc.)." Font "Arial" changed to "ArialMT".
Text Deleted�
Text
"6"
Text Inserted�
Text
"6"
Text Inserted�
Text
"7"
Text Deleted�
Text
"7"
Text Replaced�
Text
[Old]: "45" [New]: "5 RDA-2304 CN-1140" Font "Times New Roman" changed to "Arial".Font-size "12" changed to "9".
Page 111: Total Changes Content 821 - tn.gov

46

XIV. FLEXIBLE CONNECTOR CATHODIC PROTECTION SYSTEM

This form will be utilized to conduct a survey of galvanic protected flexible connectors by obtaining structure-to-soil potential measurements.

A minimum of one measurement must be made with the reference electrode placed in soil directly over the tested structure (local) and one measurement at a remote earth location, at least 25-100 feet away from the structure.

Flex connectors in contained sumps or continuous with dispenser cabinets or STPs must use instant off or voltage change (100 mV shift) to determine protected status. If either local or remote reading is more positive than -850 mV, obtain instant off by disconnecting anode. If instant off is more positive than -850 mV, then conduct 100 mV polarization and record ending voltage. If difference between

instant off and ending voltage is more than 100 mV, the result is PASS. If difference is less than 100 mV, or either local or remote reading is more positive than -850 mV, then structure is not protected and the result is FAIL.

FACILITY NAME: FACILITY ID NUMBER:

Location of Remote Reference Cell Placement, if Applicable (also designate on site drawing):

TANK #, PRODUCT, CAPACITY1 FLEX LOCATION

2

WHERE ANODE

ATTACHED?

CONTINUOUS OR

ISOLATED? 3

CONTACT POINT4

LOCAL VOLTAGE

5

REMOTE VOLTAGE

6

INSTANT OFF

VOLTAGE (if

necessary)

100 mV POLARIZATION

PASS/FAIL7

ENDING VOLTAGE

(if necessary)

VOLTAGE CHANGE

E X A M P L E S

#2 DIESEL 8,000 DIESEL FLEX AT

STP ON FLEX ISO. ON FLEX -875 mV -760 mV -860 mV

PASS

#3 Regular 10,000 REG. FLEX AT

DISPENSER 3/4

PIPING ABOVE SHEAR VALVE

CONT. PIPING ABOVE SHEAR VALVE

-980 mV -845 mV -790 mV 55 mV FAIL

#4 PREMIUM 10,000 PREM. FLEX IN

CONTAINED SUMP

STP HEAD CONT. STP HEAD

-910 mV

PASS

COMMENTS:__________________________________________________________________________________________________________________________________________________

______________________________________________________________________________________________________________________________________________________________

1 Designate the number, product, and capacity of the tank with which the flex connector is associated.

2 Indicate location of flex being tested (e.g. REGULAR FLEX AT DISPENSER 3/4, DIESEL FLEX AT STP, etc.)

3 Continuity or isolation of flex connectors must be documented before completion of this section to determine whether to use remote or instant off/100 mV polarization. If testing flex connectors only, include Continuity Survey section (XII.) of this form with this section.

4 Designate exact point of contact when testing flex (i.e., if isolated, must contact only the flex itself. If continuous with another component, can contact either one.)

5 Record the structure-to-soil potential measured with the reference electrode placed “local” in millivolts (e.g. –875 mV, -980 mV, etc.).

6 Record the structure-to-soil potential measured with the reference electrode placed “remote” (or use the voltage measurements obtained during continuity survey if remote reference cell placement was used).

7 Indicate whether the tested structure passed or failed based on your interpretation of the test data.

Text Replaced�
Text
[Old]: "CONNECTOR CATHODIC PROTECTION SYSTEM" [New]: "CONNECTORS (OR OTHER SHORT SECTION OF METAL PIPING) CATHODIC PROTECTION SYSTEM SURVEY" Font "Arial,Bold" changed to "Arial-BoldMT".
Text Replaced�
Text
[Old]: "conduct a survey of galvanic protected flexible connectors by obtaining structure-to-soil potential measurements. • A minimum of one measurement must be made with the reference electrode placed in soil directly over the tested structure (local) and one measurement at a remote earth location, at least 25-100 feet away from the structure. • Flex connectors in contained sumps or continuous with dispenser cabinets or STPs must use instant off or voltage change (100 mV shift) to determine protected status. • If either local or remote reading is more positive than -850 mV, obtain instant off by disconnecting anode. If instant off is more positive than -850 mV, then conduct" [New]: "record structure-to-soil potential measurements for galvanically protected flexible connectors (or other metal piping sections). • A total of three (3) potential measurements (one local and two at remote earth to determine True Remote Earth) is required for each flex connector when using the “On” / “Local Voltage” (-850 mV) criteria. Record the True Remote Earth Voltage on the form below. • If either the local or the remote potential measurements fail (more positive than -850 mV), use the instant off or 100 mV shift criteria to determine protective status (i.e. Pass / Fail). The instant off or 100 mV shift measurements are obtained after disconnecting the anode from the flex connector. • See also Appendix 4 of Technical Chapter 4.1, Corrosion Protection. • Potential measurements must be obtained for each flex connector. FACILITY NAME: FACILITY ID NUMBER: Location of Remote Reference Cell Placement, if Applicable (also designate on site drawing):" Font "Arial" changed to "ArialMT".
Text Inserted�
Text
"DRAFT DRAFT"
Text Replaced�
Text
[Old]: "polarization" [New]: "SHIFT TRUE CONTINUOUS OR ISOLATED? 3 (must also complete Section XII) INSTANT OFF WHERE IS ENDING TANK #, PRODUCT, CAPACITY 1 LOCAL REMOTE FLEX LOCATION 2 CONTACT POINT 4 PASS/FAIL 7 VOLTAGE ANODE VOLTAGE VOLTAGE VOLTAGE 5 EARTH (if necessary) ATTACHED? (if CHANGE VOLTAGE 6 necessary) DIESEL FLEX AT E X ON FLEX ISO. ON FLEX -875 mV -760 mV -860 mV PASS #2 DIESEL 8,000 STP A REG. FLEX AT PIPING ABOVE PIPING ABOVE SHEAR VALVE M #3 Regular 10,000 CONT. -980 mV -845 mV -790 mV 55 mV FAIL DISPENSER 3/4 SHEAR VALVE P L PREM. STP FLEX E S #4 PREMIUM 10,000 IN CONTAINED STP HEAD CONT. STP HEAD -910 mV PASS SUMP COMMENTS:__________________________________________________________________________________________________________________________________________________" Font "Arial" changed to "Arial-BoldMT".Font-size "6.48" changed to "7.02".
Text Inserted�
Text
"______________________________________________________________________________________________________________________________________________________________"
Text Inserted�
Text
"1 Designate the number, product, and capacity of the tank with which the flex connector is associated. 2 Indicate location of flex being tested (e.g. REGULAR FLEX AT DISPENSER 3/4, DIESEL FLEX AT STP, etc.) 3 Continuity or isolation of flex connectors must be documented in the Continuity Survey section (XII) before completion of this section to determine whether to use remote or instant off/100 mV shift. If testing flex connectors only, include Continuity Survey section (XII.) of this form with this section. 4 Designate exact point of contact when testing flex (i.e., if isolated, must contact only the flex itself. If continuous with another component, can contact either one.). 5 Record the structure-to-soil potential measurement for “Local Voltage” in millivolts (e.g. –875 mV, -980 mV, etc.). 6 Record the structure-to-soil potential measurement for “True Remote Earth Voltage” in millivolts. 7"
Text Inserted�
Text
"Indicate whether the tested structure passed or failed based on your interpretation of the test data."
Text Inserted�
Text
"6 RDA-2304 CN-1140"
Text Replaced�
Text
[Old]: "record ending voltage. If difference between instant off and ending voltage is more than 100 mV, the result is PASS. If difference is less than 100 mV, or either local or remote reading is more positive than -850 mV, then structure is not protected and the result is FAIL." [New]: "XIV. FLEXIBLE CONNECTORS (OR OTHER SHORT SECTION OF METAL PIPING) CATHODIC PROTECTION SYSTEM SURVEY (CONTINUED) • This form will be utilized to record structure-to-soil potential measurements for galvanically protected flexible connectors (or other metal piping sections). • A total of three (3) potential measurements (one local and two at remote earth to determine True Remote Earth) is required for each flex connector when using the “On” / “Local Voltage” (-850 mV) criteria. Record the True Remote Earth Voltage on the form below. • If either the local or the remote potential measurements fail (more positive than -850 mV), use the instant off or 100 mV shift criteria to determine protective status (i.e. Pass / Fail). The instant off or 100 mV shift measurements are obtained after disconnecting the anode from the flex connector. • See also Appendix 4 of Technical Chapter 4.1, Corrosion Protection. • Potential measurements must be obtained for each flex connector." Font "Arial" changed to "Arial-BoldMT".Font-size "6.48" changed to "10.02".
Text Inserted�
Text
"______________________________________________________________________________________________________________________________________________________________ DRAFT DRAFT"
Text Deleted�
Text
"INSTANT"
Text Replaced�
Text
[Old]: "POLARIZATION OFF WHERE CONTINUOUS ENDING LOCAL REMOTE VOLTAGE TANK #, PRODUCT, CAPACITY 1 FLEX LOCATION 2 CONTACT POINT 4 PASS/FAIL 7 ANODE OR" [New]: "SHIFT TRUE CONTINUOUS OR ISOLATED? 3 (must also complete Section XII) INSTANT OFF WHERE IS ENDING TANK #, PRODUCT, CAPACITY 1 LOCAL REMOTE FLEX LOCATION 2 CONTACT POINT 4 PASS/FAIL 7 VOLTAGE ANODE" Font "Arial,Bold" changed to "Arial-BoldMT".
Text Replaced�
Text
[Old]: "VOLTAGE 6 (if ISOLATED? 3 ATTACHED? (if CHANGE necessary)" [New]: "EARTH (if necessary) ATTACHED? (if CHANGE VOLTAGE 6" Font "Arial,Bold" changed to "Arial-BoldMT".
Text Inserted�
Text
"E X"
Text Deleted�
Text
"E"
Text Deleted�
Text
"X A PIPING"
Text Inserted�
Text
"PIPING"
Text Inserted�
Text
"SHEAR VALVE"
Text Deleted�
Text
"SHEAR"
Text Replaced�
Text
[Old]: "VALVE L E PREM. FLEX IN" [New]: "L PREM. STP FLEX E S" Font "Arial" changed to "ArialMT".
Text Inserted�
Text
"IN"
Text Deleted�
Text
"S"
Text Deleted�
Text
"______________________________________________________________________________________________________________________________________________________________"
Text Inserted�
Text
"2"
Text Inserted�
Text
"3"
Text Inserted�
Text
"in the Continuity Survey section (XII)"
Text Replaced�
Text
[Old]: "polarization." [New]: "shift." Font "Arial,Bold" changed to "Arial-BoldMT".
Text Inserted�
Text
"4"
Text Replaced�
Text
[Old]: "one.)" [New]: "one.). 5" Font "Arial,Bold" changed to "Arial-BoldMT".
Text Replaced�
Text
[Old]: "measured with the reference electrode placed “local”" [New]: "measurement for “Local Voltage”" Font "Arial,Bold" changed to "Arial-BoldMT".
Text Inserted�
Text
"6"
Text Replaced�
Text
[Old]: "measured with the reference electrode placed “remote” (or use the voltage measurements obtained during continuity survey if remote reference cell placement was used)." [New]: "measurement for “True Remote Earth Voltage” in millivolts. 7 Indicate whether the tested structure passed or failed based on your interpretation of the test data." Font "Arial,Bold" changed to "Arial-BoldMT".
Text Deleted�
Text
"Indicate whether the tested structure passed or failed based on your interpretation of the test data."
Text Deleted�
Text
"2 3 4 5 6 7 46"
Page 112: Total Changes Content 821 - tn.gov

47

APPENDIX 8

IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM

60-DAY RECORD OF RECTIFER OPERATION FORM

(Modifications are made to these forms from time to time. Please check the Division’s website for the

most current version of the State’s official form)

Text Replaced�
Text
[Old]: "8" [New]: "8:" Font "Open Sans,Bold" changed to "OpenSans-Bold".
Text Inserted�
Text
"DRAFT"
Text Deleted�
Text
"47"
Page 113: Total Changes Content 821 - tn.gov

48

DEPARTMENT OF ENVIRONMENT AND CONSERVATION

DIVISION OF UNDERGROUND STORAGE TANKS

William R Snodgrass Tennessee Tower

312 Rosa L. Parks Avenue, 12th

Floor

Nashville, TN 37243

IMPRESSED CURRENT CATHODIC PROTECTION SYSTEM

60-DAY RECORD OF RECTIFER OPERATION

This form may be utilized to document that the cathodic protection system rectifier is checked for operation at least once every 60 days. Checked for operation is taken to mean that it was confirmed the rectifier was receiving power and is “turned-on”. Rectifier power must be on

continuously according to rule 0400-18-1-.02(4)(c )1. If your rectifier is so equipped, you should also record the output voltage, amperage and the number of hours indicated on the meter. Any significant variance greater than 20% in the DC output from the ‘as designed’ or recommended volts or amps output should be reported

to your corrosion professional so that any necessary repairs and/or adjustments can be made.

UST OWNER UST FACILITY

NAME: NAME: ID #

ADDRESS: ADDRESS:

CITY: STATE: CITY: COUNTY:

IMPRESSED CURRENT RECTIFIER DATA

Rectifier Manufacturer: Rated DC Output: ____________ VOLTS ___________AMPS

Rectifier Model: Rectifier Serial Number:

What is the ‘as designed’ or lastly recommended rectifier output? ____________ VOLTS ___________AMPS

60-DAY LOG OF RECTIFIER OPERATION DATE

INSPECTED

RECTIFIER POWER

ON?

TAP SETTINGS DC OUTPUT HOUR METER

CHECKED BY

INITIALS

COMMENTS

COARSE FINE VOLTS AMPS

CN 1282 RDA 2304

Text Inserted�
Text
"STATE OF TENNESSEE"
Text Replaced�
Text
[Old]: "days. • Checked for operation is taken to mean that it was confirmed the rectifier was receiving power and is “turned-on”. Rectifier power must be on continuously according to rule 0400-18-1-.02(4)(c )1. • If your rectifier is so equipped, you should also record the output voltage, amperage and the number of hours indicated on the meter. • Any significant variance greater than 20% in the DC output from the ‘as designed’ or recommended volts or amps output should be reported to your corrosion professional so that any necessary" [New]: "days, is turned on, and is continuously receiving power (rules 0400-18-01-.02(4)(c)1 and .02(4)(c)4). • Record the output voltage, amperage, and/or the number of hours indicated on the hour meter (if equipped). • Any variance greater than 20% in the DC output of the rectifier (as indicated on the last cathodic protection test) should be reported to your corrosion professional so that the system can be retested and, if necessary," Font "Arial" changed to "ArialMT".
Text Inserted�
Text
"DRAFT DRAFT"
Text Replaced�
Text
[Old]: "___________AMPS" [New]: "____________ AMPS" Font "Arial" changed to "ArialMT".
Text Deleted�
Text
"DATE"
Text Inserted�
Text
"CHECKED"
Text Inserted�
Text
"DATE POWER"
Text Inserted�
Text
"METER"
Text Replaced�
Text
[Old]: "CHECKED" [New]: "BY" Font "Arial" changed to "ArialMT".
Text Deleted�
Text
"POWER"
Text Deleted�
Text
"METER"
Text Deleted�
Text
"BY ON?"
Text Inserted�
Text
"ON?"
Text Deleted�
Text
"CN 1282 RDA 2304"
Text Deleted�
Text
"48"