TOSHIBAA
IR CONDITIONING
Putting you in control…
Interactive IntelligencePutting you in Control…
Controls V 1.08
Sebastien Desmottes - Controls Development Engineer @ Plymouth (UK)
TOSHIBAA
IR CONDITIONING
Putting you in control…
Controls ProductContents
• RBC-RDx-PE: Refrigerant Detection• RBC-FDP1-PE: Fault Display Panel• RBC-CRx-PE: Central Remote Controller• RBC-WG1-PE: Windows Gateway• RBC-WP1-PE:Windows Software• RBC-EM1-PE: Energy Monitoring• RBC-IK1-PE: Internet Kit
TOSHIBAA
IR CONDITIONING
Putting you in control…
Refrigerant Detection
Refrigerant DetectionIndoor / Outdoor
RBC-RD1-PE / RBC-RD2-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Refrigerant DetectionContents
• Why Refrigerant Detection• Options available• Indoor Unit: RBC-RD1-PE• Outdoor Unit: RBC-RD2-PE• System Layout• Electrical Installation• System Operation• Installation Indoor / Outdoor
Note: RBC-RD1-PE, RBC-RD2-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Refrigerant DetectionWhy Refrigerant Detection?• To protect personnel (EN 378)
•To prevent environmental damage
•To maintain system efficiency
•Government Tax Incentives
Note: RBC-RD1-PE, RBC-RD2-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Refrigerant DetectionOptions Available
• Indoor Unit: RBC-RD1-PE – Interface box with remote refrigerant
sensor & audible alarm
• Outdoor Unit: RBC-RD2-PE– Interface box with internal sensor
Note: RBC-RD1-PE, RBC-RD2-PERBC-RDx-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Refrigerant DetectionIndoor Unit: RBC-RD1-PE• Control box and screw caps• Remote sensor/audible alarm
assembly• Front plate• FCU interface cable• Installation instructions• Owners manual
RBC-RD1-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Refrigerant DetectionOutdoor Unit: RBC-RD2-PE• Control box with integral sensor and
screw caps• CDU interface cable• Mounting bracket and screw• Installation Instructions• Owners Manual
RBC-RD2-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Refrigerant DetectionRBC-RD1-PE System Layout
FCU Electrical Box
Hotel Room
Metal oxide refrigerant detector. Low level position with audible alarm and 3 alarm set-points
Standard XY communication protocol
Front end PC running Windows control package (RBC-WP1-PE). Displays alarm message and unit location.
Isolating solenoid valves positioned in the gas and liquid lines (supplied by installer).
Interconnecting cable: control and Sensor.
Gateway: RBC-WG1-PE
XY PQ
RBC-RD1-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Refrigerant DetectionRBC-RD1-PE System Layout
RD1 box near unit sends signal to solenoid valves and indoor unit.
Sensor located close to the floor monitors room air.Emits audible alarm when 1000ppm refrigerant (R407C) detected.
Liquid Line
Communication cable
Suction Line To Indoor Network
TOSHIBAA
IR CONDITIONING
Putting you in control…
Refrigerant DetectionElectrical Installation RBC-RD1-PE• Mount the control box near to the
indoor unit in a visible location• Mount the remote sensor assembly
low down in the room. Maximum height from the floor surface should be 300mm. Ensure 500mm clearance around the sensor
• Connect the remote sensor assembly to the control box using a 6 core cable
• Connect the control box to a fused 240V AC 1amp supply
• For RAV units connect the FCU interface cable to CN17 on the indoor PCB
• For MM units connect the FCU interface cable to CN21 on the indoor PCB
RBC-RD1-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Refrigerant DetectionElectrical Installation RBC-RD2-PE• Mount the control box inside the
compressor housing of the outdoor unit• Connect a 3-core supply cable from the
control unit to the electrical box on the outdoor unit. Ensure a 1A fuse is fitted
• If one outdoor unit is used connect the CDU interface cable from the control unit to the electrical box on the outdoor unit.
• Locate the 3 ceramic fuses at the top of the electrical box
• From the top fuse remove the small red cable from the right side of the fuse. In its place fit the CDU interface cable
• From the small red cable removed from the ceramic fuse place into the crimp butt joint and crimp firmly
TOSHIBAA
IR CONDITIONING
Putting you in control…
Refrigerant DetectionElectrical Installation RBC-RD2-PE• For multiple outdoor units, each
refrigerant detector must be connected in series to the unit in the inverter outdoor unit. The CDU interface cable is only used in the inverter unit
• Connect each refrigerant detector using 3-core cable to the L1, N and earth terminals in each CDU. Each detector must be protected by a 1amp 240VAC fuse
• Connect the AI terminals in the control units as shown in the diagram
• To complete the series circuit connect the CDU interface cable to the inverter electrical box as described in the previous slide
RBC-RD1-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Refrigerant DetectionSystem Operation
• Low Level Alarm – 250ppm (RBC-RD1-PE Only):When the low level alarm limit is reached:
– The Detector Active LED will be “ON”
– The amber Low Level Alarm LED will start flashing
– After 10 minutes, the Low Level Alarm LED will stop flashing and remain “ON”
– B5 fault code will be generated by the indoor unit
– The indoor unit will not shut downNote: If the refrigerant concentration drops below 250ppm the control box will self reset
RBC-RD1-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Refrigerant DetectionSystem Operation
• High Level Alarm – 1000ppm (RBC-RD1/RD2-PE):When the high level alarm limit is reached:
– The Detector Active and the Low Level Alarm LED’s will be “ON”
– The red High Level Alarm LED will start flashing
– After 10 minutes, the High Level Alarm LED will stop flashing and remain “ON”. The red Shutdown LED will also come “ON”
– B5 & B6 fault codes will be generated by the indoor unit, 04 fault code will be generated by the outdoor unit
– The indoor unit will shut down and the audible alarm will sound if an RD1 was activated
– The outdoor unit will shut down if an RD2 was activated
– The alarm volt free contacts will operate to control any suitable external device
Note: The system must be manually reset using the reset buttons on the control box
RBC-RDx-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Refrigerant DetectionSystem Operation
• Spill Alarm – 2200ppm (RBC-RD1/RD2-PE)
When the spill alarm limit is reached:
– The Detector Active LED will be “ON”
– After 10 seconds at the Spill Alarm limit, the Shutdown LED will come “ON” The Low Level Alarm & the High Level Alarm LED’s will start flashing
– B6 fault code will be generated by the indoor unit if the refrigerant is detected in the room by RBC-RD1-PE
– 04 fault code will be generated by the outdoor unit if the refrigerant is detected in the compressor housing by RBC-RD2-PE
– The indoor unit will shut down and the audible alarm will sound if an RD1 was activated
– The outdoor unit will shut down if an RD2 was activated
– The “alarm” volt free contacts will operate to control any suitable external device connected to the control box
Note: The system must be manually reset using the reset buttons on the control box
RBC-RDx-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Refrigerant DetectionSystem Operation
• Sensor Failure (RBC-RD1/RD2-PE)When the refrigerant sensor fails:
– After 1 minute the Detector Active LED will go “OFF”, and the Low Level Alarm LED will come “ON”
– B5 fault code will be generated by the indoor unit. No fault code will be generated by the outdoor unit. The indoor or outdoor unit will not shut down
– After 4 hours the Low Level Alarm LED will go “OFF” and the Shutdown LED will come “ON”
– B6 fault code will be generated by the indoor unit if the refrigerant leak is detected in the room by RBC-RD1-PE
– A 04 fault code will be generated by the outdoor unit if the refrigerant is detected in the compressor housing by RBC-RD2-PE
– The indoor or outdoor unit will shutdown
– The “alarm” volt free contacts will operate to control any suitable external device connected to the control box
Note: The system must be manually reset using the reset buttons on the control box after replacing the sensor
RBC-RDx-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Refrigerant DetectionRefrigerant Mass Required• RBC-RD1-PE : High Level Alarm
Calculation based on a hotel room 5m x 8m x 2.5m.Density of R407C vapour at ambient pressure = 3.518kg/m3.
For high level alarm (unit shutdown) at 1000ppm: Ppm concentration = 1000/1000000 = 0.001
Grams of R407C = 5m x 8m x 2.5m x 3.518kg/m3 x 0.001 ppm/conc = 0.3518 kg = 352 g
• RBC-RD1-PE : Low Level AlarmGrams of R407C = 5m x 8m x 2.5m x 3.518kg/m3 x 0.00025 ppm/conc
= 0.0880 kg
= 88 g
RBC-RD1-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Refrigerant DetectionRefrigerant Mass Required• RBC-RD2-PE : High Level Alarm
Calculation based on the volume of the compressor housing = 0.8m3
Density of R407C vapour at ambient pressure = 3.518kg/m3.
For high level alarm (unit shutdown) at 1000ppm:Ppm concentration = 1000/1000000
= 0.001Grams of R407C = 0.8m3 x 3.518kg/m3 x 0.001 ppm/conc
= 0.0028 kg = 2.8 g
RBC-RD2-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Refrigerant DetectionInstallation Indoor / Outdoor• Indoor Installation
– Standard Grid Plate (BS 57533:1995)– Standard Front Plate– Integral audible alarm mute button and refrigerant sensor
RBC-RD1-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Refrigerant DetectionInstallation Indoor / Outdoor• Outdoor Installation• RBC-RD2-PE only available with MMS
RBC-RD2-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Fault Display Panel
Fault Display Panel
RBC-FDP1-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Fault Display PanelContents
• Features• Installation
TOSHIBAA
IR CONDITIONING
Putting you in control…
Fault Display Panel Features
• Detect all Indoor Units faults• Attached in parallel with the Remote Controller
(ABC)• LED to indicate activity (flashing at 1s rate)• LED to indicate fault / no fault• Volt-free contact allows external signalling of the fault• Relay closed under fault free conditions• 09 Fault can be optionally filteredRBC-FDP1-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Fault Display Panel Installation
• No external power supply needed as it is attached in parallel with the Remote Controller (ABC).
• Fault filter – OFF: 09 faults are treated like any other fault
code– ON: 09 faults are only reported after 3 hours
RBC-FDP1-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Central Remote Controller
Central Remote Controller
RBC-CR1-PE, RBC-CR64-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Central Remote Controller Contents• Models• Features / Options• Installation
TOSHIBAA
IR CONDITIONING
Putting you in control…
Central Remote Controller Models Available• RBC-CR1-PE
– Control up to 16 Indoor Units
• RBC-CR64-PE– Control up to 64 Indoor Units
RBC-CRx-PE Note: RBC-CRx-PE cannot be used in conjunction with the Windows Gateway (WG1)
TOSHIBAA
IR CONDITIONING
Putting you in control…
Central Remote Controller Options Available• RBC-CR1-PE / RBC-CR64-PE
– Compatible with Toshiba MMS and 4 Series Heat Pump– Compatible with 7 Day Timer (RBC-WT1-PE)
• RBC-CR64-PE– External switch (Input Shutdown)– External timer– Units can be grouped in Zones– Two central Controllers can be used on the same XY
Network
RBC-CRx-PE Note: RBC-CRx-PE cannot be used in conjunction with the Windows Gateway (WG1)
TOSHIBAA
IR CONDITIONING
Putting you in control…
Central Remote Controller Installation (RBC-CR64-PE)• All types of systems (MMS, SMi, Single
split) can be connected to the same Central Remote Controller
RBC-CR64-PE Note: RBC-CR64-PE cannot be used in conjunction with the Windows Gateway (WG1)
TOSHIBAA
IR CONDITIONING
Putting you in control…
Interactive Intelligence
Building Management System
RBC-WG1-PE, RBC-WP1-PE, RBC-EM1-PE, RBC-IK1-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Interactive IntelligenceBMS - Contents
• Link Between Products• Windows Gateway• Windows Software• Energy Monitoring• Internet Kit
Note: RBC-WG1-PE, RBC-WP1-PE, RBC-EM1-PE, RBC-IK1-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Interactive IntelligenceLink Between Product ?
Internet / Intranet
TOSHIBAA
IR CONDITIONING
Putting you in control…
Link Between Controls ProductWindows Gateway 1:64• To control up to 64 Toshiba I./D (MMS
or RAV AI) units– Consists of:
• One Gateway• One IEC Plug• Installation Instruction with functional profile
RBC-WG1-PE Note: RBC-WG1-PE cannot be used in conjunction with any other Central Controller
TOSHIBAA
IR CONDITIONING
Putting you in control…
Link Between Controls ProductWindows Software 1:1024• To manage on one PC up to 1024 I/D
i.e. 16 Gateways– Consists of:
• One CD “Interactive Intelligence”• One hardware key • One owner's manual• PCI Card (Extension)
RBC-WG1-PE Note: RBC-WG1-PE cannot be used in conjunction with any other Central Controller
TOSHIBAA
IR CONDITIONING
Putting you in control…
Link Between Controls ProductEnergy Monitoring• RBC-EM1-PE is an add-on to RBC-WP1-
PE– Consists of:
• One power meter• Current Transformers x3• Installation Instructions
RBC-EM1-PE Note: RBC-EM1-PE must be used in conjunction with RBC-WG1-PE, RBC-WP1-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Link Between Controls ProductInternet Kit 1:5• RBC-IK1-PE is an add-on to RBC-WP1-PE
– Consists of:• One key file CD “Interactive Intelligence”• License for 5 concurrent users
RBC-WP1-PE Note: RBC-IK1-PE must be used in conjunction with RBC-WG1-PE, RBC-WP1-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Interactive Intelligence
Windows Gateway
RBC-WG1-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Interactive IntelligenceWindows Gateway 1:64• Gateway using LonWorks Technology • Control up to to 64 I/D• Auto Detect number of I/D
automatically• Functions of Central Remote Controller• Ambient & Coil Temperatures available
RBC-WG1-PE Note: RBC-WG1-PE is not compliant with Echelon.
TOSHIBAA
IR CONDITIONING
Putting you in control…
Interactive Intelligence
Windows SoftwareInteractive Intelligence
RBC-WP1-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Interactive IntelligenceWindows Software 1:1024 Contents• Features• Installation• Navigation (Schematics)• Alarms• Remote Connection• Timed Operation and Optimised Start• Frost Protection Module• Data Logging• Graphical view• Backup / Restore of the complete System• Customisation of Schematics• Website
TOSHIBAA
IR CONDITIONING
Putting you in control…
Interactive IntelligenceFeatures
• Automated Configuration • Display and retransmission of Intelligent fault
code • Unit location can be displayed on PC• Data and alarms logging• Timed operation under several schedule• Navigator (schematics) fully customisable• Hardware key protection and 100 access level
configurableRBC-WP1-PE Note: Compatible with Win 98 SE, Win NT 4.0,
Win 2000 and Win XP.
TOSHIBAA
IR CONDITIONING
Putting you in control…
Interactive IntelligenceAutomatic Installation
BEFORE:
• LonMaker / Front End Software
• PC & PCLTA20
• Systems Integrator
RBC-WP1-PE
AFTER:
•Interactive Intelligence
•PC
TOSHIBAA
IR CONDITIONING
Putting you in control…
Interactive IntelligenceAutomatic Installation
• Auto-detect of the number of units on each Windows Gateway
• Auto-detect how many Gateways on the network
• Auto-detect how many Power Meters if any are present
• Generates a Network database• Generates standard schematics for each units
RBC-WP1-PE Note: The XY network connection must be checked.
TOSHIBAA
IR CONDITIONING
Putting you in control…
Interactive IntelligenceAutomatic Installation
• Opening system
• Create schematics ?
RBC-WP1-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Interactive IntelligenceAutomatic Installation
• Commissioned Devices ? (Windows Gateway / Power Meter)
• Software looking fordevices (Commissioned / Decommissioned)
RBC-WP1-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Interactive IntelligenceAutomatic Installation
• Database generated•Able to rename Gateways•Able to rename Indoor Units•Able to decommission Gateways (right click on the Gateway)
RBC-WP1-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Interactive IntelligenceNavigation / Schematics• Level 1 Schematic• Number of Gateways
Click here to go to Level 2 (I/D attached to this Gateway)
RBC-WP1-PE Note: LEVEL 1 Schematic
TOSHIBAA
IR CONDITIONING
Putting you in control…
Interactive IntelligenceNavigation / Schematics• Level 2 Schematic• Number of Indoor Units
Click here to go to Level 3 (details of the settings)
RBC-WP1-PE Note: LEVEL 2 Schematic
TOSHIBAA
IR CONDITIONING
Putting you in control…
Interactive IntelligenceNavigation / Schematics• Level 3 Schematic• Settings of theIndoor Unit
Able to change thepicture of the IndoorUnit
RBC-WP1-PE Note: LEVEL 3 Schematic
TOSHIBAA
IR CONDITIONING
Putting you in control…
Interactive IntelligenceNavigation / Schematics• All models
RBC-WP1-PE Note: LEVEL 3 Schematic
TOSHIBAA
IR CONDITIONING
Putting you in control…
Interactive IntelligenceAlarms
• Indication:– Intelligent FaultCode– Gateway/Indoor Unit
RBC-WP1-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Interactive IntelligenceAlarms
• Transmission– Print– Audio– Popup Window
• Retransmission:– Fax– Email– Remote Site– GSM / Pager
RBC-WP1-PE Note: Modem Internal / External Required on Supervisor.
TOSHIBAA
IR CONDITIONING
Putting you in control…
Interactive IntelligenceRemote Connection
• Internet Kit– Site: RBC-WP1-PE + RBC-IK1-PE – Office: Internet Explorer
• Remote Connection:– Site: RBC-WP1-PE – Office: RBC-WP1-PE
RBC-WP1-PE Note: Modem Internal / External Required on Supervisor.
WP1 / IK1IE
RBC-WP1-PERBC-WP1-PE
Site Office
TOSHIBAA
IR CONDITIONING
Putting you in control…
Interactive IntelligenceRemote Connection
• Remote Connection – Able to:
• Access system set-up• Edit / Modify schematics
– Not able to access:• Driver set-up• Any plug-in (Optimised Start, Frost Protection Module, Energy Monitoring)
RBC-WP1-PE Note: Modem Internal / External Required on Supervisor.
TOSHIBAA
IR CONDITIONING
Putting you in control…
Interactive IntelligenceTimer – Option 1: Local Calendar• Weekly Schedule
– 300 Items– 24 Events in a day
• Special Day
RBC-WP1-PE Note: Local Calendar Option.
TOSHIBAA
IR CONDITIONING
Putting you in control…
Interactive IntelligenceTimer – Option 2: Optimised Start• Weekly Schedule
RBC-WP1-PE Note: Optimised Start Option.
TOSHIBAA
IR CONDITIONING
Putting you in control…
Interactive IntelligenceTimer – Option 2: Optimised Start• Weekly Schedule• Optimised Start Option • User Friendly set-up
RBC-WP1-PE Note: Optimised Start Option.
TOSHIBAA
IR CONDITIONING
Putting you in control…
Interactive IntelligenceTimer – Option 2: Optimised Start• Enable a specificTemperature to be achieved at a specific time
• Learning the room inertia todetermine when to start theAir Conditioning system
RBC-WP1-PE
23 °C
20 °C
Setpoint
23 °C
20 °C
08:50 09:00 09:10 time
Setpoint
23 °C
20 °C
Setpoint
DAY 1
DAY 2
DAY 3
08:50 09:00 09:10 time
08:50 09:00 09:10 time
Note: Optimised Start Option.
TOSHIBAA
IR CONDITIONING
Putting you in control…
Interactive IntelligenceFrost Protection Module• Can enable the A/C and maintain in constant
temperature in the event of low temperature being detected
• Can stop the A/C when a temperature is achieved• Able to:
– Turn On / Off– Change the Set Point– Change the Mode
• Conditions can be entered which includes samples times, the trigger and reset points.
RBC-WP1-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Interactive IntelligenceData Logging
• Record any data– SetPoint– Mode– Fan Speed– On / Off– Fault Codes– Demand Data– TA, TC
RBC-WP1-PE Note: Max Log Time Base = 1 Day.
TOSHIBAA
IR CONDITIONING
Putting you in control…
Interactive IntelligenceGraphical View
• Graphics from– Data logging– Colours and type of Graphic customisable- Zoom In / Out- Print
RBC-WP1-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Interactive IntelligenceBackup the complete system• Backup system
– Notes– Basic Configuration– Schematics– Data logging– Local Calendars– Script
RBC-WP1-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Interactive IntelligenceRestore the complete system• Restore system
– Notes– Basic Configuration– Schematics– Data logging– Local Calendars– Script
RBC-WP1-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Interactive IntelligenceCustomisation
• Site fully customisable• Examples:
– United Kingdom Plymouth - Life Test– United Kingdom Leatherhead – UTC House
Life Test– United Kingdom Glasgow – Airbels Road– France Nantes - System U– Austria – Office
• Diagnostics (16 I/D and 32 I/D)RBC-WP1-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Interactive IntelligenceCustomisation – UK - Plymouth• Level 1 Schematic
– 4 Gateways– 8 Different Systems
RBC-WP1-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Interactive IntelligenceCustomisation – UK - Plymouth• Level 2 Schematic
– MMS14HP – Energy Consumptionavailable
RBC-WP1-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Interactive IntelligenceCustomisation – UK - Plymouth• Level 2 Schematic
– SMI10HP– Top view importedfrom AutoCAD
RBC-WP1-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Interactive IntelligenceCustomisation – UK - Leatherhead• Level 1 Schematic
– UTC House
RBC-WP1-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Interactive IntelligenceCustomisation – UK - Leatherhead• Level 2 Schematic
– Top view importedfrom AutoCAD- Blue and Red buttonto specify if the I./Dis cooling or heating
RBC-WP1-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Interactive IntelligenceCustomisation – UK - Leatherhead• Level 2 Schematic
– Only available forService Engineers
RBC-WP1-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Interactive IntelligenceCustomisation – UK - Leatherhead• Level 2 Schematic
– Outdoor view imported from AutoCAD
RBC-WP1-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Interactive IntelligenceCustomisation – UK – AirbelsRoad• Level 1 Schematic
– 2 Gateways– Trend System (Ventilation, hot waterair handling plant,water levels, metering)
RBC-WP1-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Interactive IntelligenceCustomisation – UK – AirbelsRoad• Level 2 Schematic
– Gateway Ground &First floor– I/D Fault Codes
RBC-WP1-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Interactive IntelligenceCustomisation – UK – AirbelsRoad• Level 2 Schematic
– Gateway First &Second floor– I/D Fault Codes
RBC-WP1-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Interactive IntelligenceCustomisation – UK – AirbelsRoad• Trend Control
– Fan– Heaters– Water Tank– Metering
RBC-WP1-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Interactive IntelligenceCustomisation – UK – AirbelsRoad• Air Handling Unit
– Global view
RBC-WP1-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Interactive IntelligenceCustomisation – UK – AirbelsRoad• Extract Fan
– Global view
RBC-WP1-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Interactive IntelligenceCustomisation – UK – AirbelsRoad• Heaters
– Global view
RBC-WP1-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Interactive IntelligenceCustomisation – UK – AirbelsRoad• Metering
RBC-WP1-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Interactive IntelligenceCustomisation – FR - Nantes• Level 1
Schematic– Building view- 3 Gateways- 150 I/D
RBC-WP1-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Interactive IntelligenceCustomisation – FR - Nantes• Level 2 Schematic
– Top view imported from AutoCAD- TS, TA reading- Heat / Cool reading
RBC-WP1-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Interactive IntelligenceCustomisation – FR - Nantes• Special Schematic
– Top view imported from AutoCAD- Outdoor view- Display outdoor faults
RBC-WP1-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Interactive IntelligenceCustomisation – AT - Adelsberger• Level 2 Schematic
– Complete view of thesystem- Temperatures reading from LonWorks sensors- Ventilation controlledwith Interactive IntelligenceI/D will stop if ventilationoff
RBC-WP1-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Interactive IntelligenceCustomisation – Diagnostics 16• Special Schematic
– Able to seeI/D data:
• 01 to 16 • 17 to 38• 39 to 48• 49 to 64
RBC-WP1-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Interactive IntelligenceCustomisation – Diagnostics 32• Special Schematic
– Able to seeall the data fromthe Gateway
RBC-WP1-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Interactive IntelligenceWebsite - Home
•Home (basic feature of Interactive Intelligence)
RBC-WP1-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Interactive IntelligenceWebsite -Updates
•Updates•Interactive•LNS Driver•RGM •NDS•OZM•FPM•Node Utility•Checklist
RBC-WP1-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Interactive IntelligenceWebsite - FAQ
•FAQ•Commissioning…
RBC-WP1-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Interactive Intelligence
Energy Monitoring
RBC-EM1-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Energy MonitoringContents
• Features• Installation of Power Meter• Set-up the system• View data• Set-up the report
RBC-EM1-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Energy MonitoringFeatures
• Automatic Power Meter configuration• Calculation of Unit Running costs per indoor
unit and system• Running costs based on a multiple tariffs • Running report based with different clients• Option for data export to CSV file(Compatible with Excel)• One Power Meter for one Outdoor Unit
RBC-EM1-PE Note: Possibility to connect one Power Meter to 2 MMS Outdoor Units.
TOSHIBAA
IR CONDITIONING
Putting you in control…
Energy MonitoringInstallation of Power Meter• Installation 1: MMS14HP
– Inverter Power Meter– Fix Power Meter– Current Transformer x 3
RBC-EM1-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Energy MonitoringInstallation of Power Meter• Installation 2: MMS26HP
– Inverter Power Meter– Fix Power Meter (1 Power Meter for 2 Fix Speed)– Current Transformer x 3
RBC-EM1-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Energy MonitoringInstallation of Power Meter• Installation 3: SMI10HP
– Inverter Power Meter– Current Transformer x 3
RBC-EM1-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Energy MonitoringSet-up the system
• Set-up the database• Data Tree
– System– Power Meter– Indoor Units
RBC-EM1-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Energy MonitoringSet-up the system
• Set-up Power Metersand Indoor Units
– Link with LonWorksdatabase- Model names
RBC-EM1-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Energy MonitoringView Data
• System data:– Indoor Unit 1– Indoor Unit 2– Indoor Unit 3– Indoor Unit 4…
RBC-EM1-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Energy MonitoringSet-up the report
• Select:– Client– Tariff– Layout– Destination (Email or Printer)- Link (System)- Select Indoor Unit
RBC-EM1-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Energy MonitoringSet-up the report
• View the report:– Toshiba StandardReport with:
- Client- Date- System reference
RBC-EM1-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Energy MonitoringSet-up the report
• Modify the report:– Able to change thecomplete layout- Able to import pictures
RBC-EM1-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Interactive Intelligence
Internet Kit
RBC-IK1-PE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Internet Kit
• Internet Kit is a license which enables a plug-in• Get connected to server using Internet Explorer• No software need to be installed on the client PC
RBC-IK1-PE Note: The license is for 5 concurrent users.
Click HERE
TOSHIBAA
IR CONDITIONING
Putting you in control…
Internet Kit
• 2 Levels of Access:– Remote A/C system monitoring- Full remote A/C system control and monitoring
RBC-IK1-PE Note: The license is for 5 concurrent users.
TOSHIBAA
IR CONDITIONING
Putting you in control…
Internet Kit
• Internet Kit does not allow to modify the system set-up of Interactive Intelligence
• 5 concurrent users can be connected in the same time
• Each user can be allocated their own unique schematic
• Alarms can be viewed remotely
RBC-IK1-PE Note: The license is for 5 concurrent users.
TOSHIBAA
IR CONDITIONING
Putting you in control…
Interactive Intelligence
Internet / Intranet
Any questions ?
TOSHIBAA
IR CONDITIONING
Putting you in control…
Interactive IntelligencePutting you in Control…
Thanks for your time…
Controls Sebastien Desmottes - Controls Development Engineer @ Plymouth (UK)