TK13301
Transcript of TK13301
8/2/2019 TK13301
http://slidepdf.com/reader/full/tk13301 1/24
February 2007
CA08101001E For more information visit: www.eaton.com
Contents
Switchboards1
S w
i t c h b o a r d
s
Description Page
Group-Mounted Feeder Sections
Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-2
Application Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-2
Features, Benefits and Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-2
Standards and Certifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-2
Product Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-4
Integrated Facility Switchboards
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-5
Compartmentalized Feeder Sections
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-6
Instant Service Switchboards
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-7
Roll-up Generator Termination Box
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-10
Pow-R-Line C Group-Mounted Distribution Switchboard
8/2/2019 TK13301
http://slidepdf.com/reader/full/tk13301 2/24
February 2007
15-2
For more information visit: www.eaton.com
CA08101001E
Switchboards
5
Pow-R-Line C Switchboards
Group-Mounted Feeder Sections
Product Description
Eaton’s Cutler-Hammer
Pow-R-LineC
Distribution Switchboardscombine a space-saving design withmodular construction and increased
systems rating to provide economicaland dependable electrical systemdistribution and protection.
Pow-R-Line C Group-Mounted Distribution Switchboard
Application Description
■
Refer to the Cutler-Hammer Consult- ing Application Guide, 13th Edition.
Features, Benefitsand Functions
■
6000 amperes maximum mainbus rating.
■
600 Vac and below.
■
Front or rear accessible.
■
Type 1 or Type 3R enclosures.
■
ANSI-61 gray powder coatpaint finish.
■
The IQ family of microprocessor-based metering and monitoringdevices.
■
Utility metering provisions.
■
Transient Voltage SurgeSuppression (TVSS).
■
Ground Fault protection on mainsand distribution devices.
■
Busway and transformer connections.
■
Complete protective device accessory
capability.
■
65 kAIC standard bus bracing;optional 100 or 200 kAIC.
■
Standard tin-plated aluminum bus;optional copper- or silver-platedcopper bus.
■
Standard bus ampacities basedon UL
heat test ratings. Optionaldensity rated bus systems arealso available.
Main Devices
■
DS/DSL air power circuit breakers,800 – 4000 amperes, fixed ordrawout.
■
Magnum DS power circuit breakers,800 – 5000 amperes, fixed ordrawout.
■
Molded case circuit breakers,400 – 2500 amperes, fixed mounted.
■
Bolted pressure switches,800 – 5000 amperes.
■
FDPW fusible switches, 400 – 1200amperes.
Group-Mounted Distribution Devices
■
Molded case circuit breakers,15 – 1200 amperes.
■
FDPW fusible switches, 30 – 1200amperes.
Standards and Certifications
■
Meets NEMA
Standard PB-2and UL 891.
■
Seismically qualified.
For complete application and pricing information,contact your local Eaton sales office.
8/2/2019 TK13301
http://slidepdf.com/reader/full/tk13301 3/24
February 2007
CA08101001E For more information visit: www.eaton.com
1Switchboards
Pow-R-Line C Switchboards
Group-Mounted Feeder Sections
Product Description
Eaton’s Cutler-Hammer commercialmetering switchboards provide electri-cal system distribution and meteringfor shopping centers, office buildings
and other commercial multimeteringapplications.
Using standard Pow-R-Line Cconstruction and features, theseswitchboards incorporate meteringsections with tenant feeder circuitsusing meter sockets to meet localutility or customer requirements.
All meter sockets and associatedfeeder devices are completely factoryprewired and shipped ready for theinstallation of the meters.
WWCMS
WCMS
Service
■
120/240 volt, 1-phase, 3-wire.
■
240/120, 208Y/120 or 480Y/277 volt,3-phase, 4-wire.
Main Bus Rating
■
400 – 4000 amperes.
Service Section
■
Main circuit breaker, 400 – 4000amperes.
■
Main fusible switch, 400 – 4000amperes.
■
Main lugs only, 400 – 4000 amperes.
Metering Sections
■
Tenant Main Disconnects and MeterSockets (200 amperes maximumself-contained metered circuits).
■
Hot sequence metering circuits.
■
Cold sequence metering circuits(WCMS only).
■
Optional rear barriered wirewaysor load side pull sections for cableexit requirements.
■
Sections for metered circuits largerthan 200 amperes available with 400amperes continuous rated self-con-tained sockets or with CT compart-ment and transformer rated socketin combination with disconnect.
Application Description
■
Type WWCMS
For EUSERC serviced areas. The self-contained meter sockets include a testbypass/disconnect block per EUSERC
requirements, and are arranged,typically, for hot sequence metering.
Socket and Test Block Assembly
■
Type WCMS
For other than EUSERC serviced areas.Self-contained meter sockets areprovided with manual lever bypassand can be arranged for either hotor cold sequence metering.
Socket with Manual Lever Bypass
■
Refer to the Cutler-Hammer Consult- ing Application Guide, 13th Edition.
Standards and Certifications
■
UL 891.
■
NEMA PB-2.
■
Seismically qualified.
8/2/2019 TK13301
http://slidepdf.com/reader/full/tk13301 4/24
February 2007
15-4
For more information visit: www.eaton.com
CA08101001E
Switchboards
5
Pow-R-Line C Switchboards
Group-Mounted Feeder Sections
Product Specifications
Pow-R-Line designates a family ofdistribution switchboards incorporat-ing new design concepts that fit theever-increasing need for applications
on high short-circuit systems, whileretaining maximum standardization,safety and convenience throughoutthe line.
Front Accessibility
Front accessibility switchboards alignat the rear, enabling them to be placedagainst a wall (Cutler-Hammer TypePow-R-Line C front accessible). If themain section is deeper than others,due to physical size of the main device,the necessary off-set in line-up willoccur in front, and the main sectionwill be accessible from the side aswell as from the front. Standard front
accessible switchboards will alignat the front and rear.
Rear AccessibilityRear accessible switchboards alignat the front and the rear. Bus mainte-nance and cable entry and exit requirerear access. There are two types ofrear accessible switchboards. Bothtypes utilize the same incoming utilityand/or main structures. The first typeutilizes group mounted feeder deviceswith panel construction (Cutler-Hammer Type Pow-R-Line C rearaccessible). The second type utilizesindividually compartmentalized feederdevices with load side insulated busbar extensions (Cutler-Hammer TypePow-R-Line i
).
Standard Switchboard Height
Standard Pow-R-Line switchboardheight is 90 inches (2286 mm).
Group Mounting
Group mounted circuit protectivedevices are an assembly of unitsmounted on a panelboard type base(panelboard construction). Units maybe molded case breakers, or FDPWfusible switches. Circuit protective
devices are accessible from the front.
A main molded case breaker or mainFDPW fusible switch, within the sizeslisted for panelboard design, can beincluded in the panel-mounted assem-bly in lieu of a separate, individuallymounted unit.
Space Only for Future DevicesGroup Mounted Construction
Where space only for future circuitprotective devices is required, theproper space and a blank filler platewill be supplied. Connections andmounting hardware are not included.
Provision for Future Devices
Where provisions for future circuit pro-tective devices are required, space forthe device, corresponding vertical bus,device connectors and the necessarymounting hardware will be supplied.
Bus Bar System
Standard bus in the switchboardsis tin-plated aluminum. Copper andsilver-plated copper are also available.
Main bus and sub-main buses
meet UL and NEMA standards fortemperature rise on all Pow-R-Lineswitchboards. Special bus densitiesare available.
Overcurrent Devices
To properly select and size overcurrentdevices for use in a switchboard, theallowable temperature rise must betaken into account as to its effect onthe tripping characteristics of thedevices in question.
Accordingly, Article 220-4(a) of theNEC
requires overcurrent devices tobe rated not less than 125% of the
continuous load they are protecting.To comply with this, an 80% deratingfactor must be used with all overcur-rent devices such as molded casebreakers and FDPW fusible switchesunless they are tested and approvedfor application at 100% of the rating.
Short Circuit Rating
Standard bus and connectors on allswitchboards are rated for use onsystems capable of producing upto 65,000 amperes rms symmetricalshort circuit current at the incomingterminals.
Increased bus short circuit ratingsequal to that of connected switchboarddevices, up to 200,000 amperes rmssymmetrical, are available in mostPow-R-Line switchboards whenapproved main devices are installed.Contact Eaton for more information.UL labeled switchboard sections aremarked with their applicable short-cir-cuit rating.
Provision for Busway Entranceand Exit
Busway connections to switchboardsections include cutout and drilling inthe top of the switchboard with riserconnections from the switchboarddevice or bus, up to the point wherethe bus duct enters the switchboard.No connections are furnished externalto the switchboard.
In all transactions involving buswayattached to switchboards, it is essen-tial that information regarding orienta-tion of the busway with respect to thefront of the switchboard be suppliedto the coordinating assembly plant.
On Pow-R-Line switchboards, solidbus bar is used to connect the busduct to the individually mounted maindevice, main or sub-main switchboard
bus, or vertical main bus of panelmounted circuit protective devicepanels. Busway fed by group mountedbranch devices are cable connected.
Aluminum riser connections arestandard. Copper- or silver-platedcopper is available as a modification.
Transitions
Transition structures are required forconnecting switchboards to the sec-ondary of power center transformer(dry or fluid filled), motor control cen-ters, and for other special switchboardconfigurations such as “L” or “U”
shaped lineups. In some application,an extra structure complete with con-nections is required; in others, whereswitchboard depth and space permit,only the connection conductors arerequired. (Refer to factory for theseapplications.)
For complete application and pricing information,contact your local Eaton sales office.
8/2/2019 TK13301
http://slidepdf.com/reader/full/tk13301 5/24
February 2007
CA08101001E For more information visit: www.eaton.com
1Switchboards
Integrated Facility Switchboards
Product Description
Product Description
Cutler-Hammer Integrated FacilitySwitchboards™ by Eaton Corporationutilize the modular Pow-R-Line Cgroup mounted switchboard design to
integrate traditionally separate electri-cal distribution and control equipmentinto a single space-saving factoryassembled and connected package.
The service entrance equipment canbe integrated with multiple lightingand appliance branch panelboardsinto a compact front accessible groupmounted switchboard. Where multi-ple panelboards are utilized in thesame electrical room as a conventionaldistribution switchboard or powerpanelboards, the integrated designwill significantly reduce equipmentspace requirements, as well as,reducing installation time and costs.
Other associated equipment canalso be integrated into the assembly,including dry type distribution trans-formers, time clock space, lightingcontrol, electronic controls, surgesuppression, metering and energymonitoring devices. Depending uponthe application, other user-definedequipment such as a subsystem con-trol package may also be incorporated.
Application Description
Cutler-Hammer Integrated Switch-boards are designed to meet specific
needs for:
■
Retail chain stores.
■
Commercial offices.
■
High rise offices.
■
Correctional facilities.
■
Agricultural facilities.
■
Industrial facilities.
■
Hospitals/healthcare facilities.
■
Others.
Whether the application is a multi-site prototype or single application,integrated switchboards offer timeand space saving features.
For complete application description,refer to the Cutler-Hammer Consulting Application Guide, 13th Edition.
Standards and Certifications
■
Meets NEMA Standard PB-2and UL 891.
■
Panelboards mounted inside thesections meet NEMA PB-1 and UL 67.
■
Other equipment is UL listed asapplicable and appropriate.
Integrated Facility Switchboard
Features, Benefitsand Functions
Front Accessibility
Integrated Switchboards are front
accessible and align at the rear,enabling them to be placed against awall. Most switchboards align at thefront and the rear. If the main sectionis deeper than others, due to physicalsize of the main device, the necessaryoff-set in line up will occur in front,and the main section will be accessiblefrom the side as well as from the front.
Standard Switchboard Height
Switchboard height is 90 inches(2286 mm).
A limited offering of 78 inch (1981.2 mm)high equipment is available. Consult the
factory for specific applications.
Switchboard Shipping Splits
The sections can be shipped as speci-fied by the customer to meet specificrequirements.
For retrofit applications, single-pieceswitchboard structures can be shippedto facilitate movement through limitedaccess doorways, etc.
Traditionally Mounted Equipment
Factory InterconnectionsMost sub-panels are fed from the maindistribution panel feeder circuit break-ers utilizing copper cable sized perthe NEC and UL.
Space SavingsThe space-saving switchboard installa-tion provides additional usable floorspace. For example:
Retail Stores. . . . . . Floor space for salesOffices. . . . . . Additional storage, cubicleHealth Care. . . . . . . Additional work areaRetrofits . . . .Ability to fit existing rooms
Site Construction Savings
Timely installation of the electricalsystem is typically a key element onthe critical path for any project.
Along with the time to install the
equipment, other expenses include thetime to handle all of the loose piecesof equipment arriving on a job site andensuring it reaches the proper tradesperson. With Eaton’s Cutler-HammerIntegrated Switchboards, one piece ofequipment is typically shipped to a jobsite virtually eliminating these issues.
The equipment may also be usedfor temporary power on job sitesfurther reducing constructionexpenses and times.
Figure 15-1. Construction Savings
For complete application and pricing information,contact your local Eaton sales office.
8/2/2019 TK13301
http://slidepdf.com/reader/full/tk13301 6/24
February 2007
15-6
For more information visit: www.eaton.com CA08101001E
Switchboards
5
Compartmentalized Feeder Sections
Pow-R-Line i
Product Description
Eaton’s Cutler-Hammer Pow-R-Line i Switchboards are engineered in a newcompartmentalized design for applica-tions where a greater degree of safety
is required. A wide variety of configu-rations is possible including utilitymetering, customer metering, maindevices, branch devices, accessoriesand enclosures.
Significant safety features include:
■ Individual compartments forbranch devices — glass polyesterfor circuit breakers and steel for fus-ible switches. These compartmentshelp eliminate possible contact withthe main bus and reduce faultpropagation.
■ Three-section construction with eachsection barriered from the other.
❑ Device Section. Each device ismounted in its own compartment.
❑ Bus Bar Section. Contains bothhorizontal and vertical buses.
❑ Rear Cable Compartment. Com-pletely isolated from the bus bars.
■ Insulated copper runback. Poweris taken from the protective deviceby the insulated copper runbackthrough a standard full height glasspolyester barrier to the rear cablecompartment. This design virtuallyeliminates the possibility of acciden-tal contact with the main busesduring installation or maintenance.
Front View — Circuit Breakers
Application Description
■ Refer to the Cutler-Hammer Consult- ing Application Guide, 13th Edition.
For complete application and pricing information,contact your local Eaton sales office.
Front View — Fusible Units
Features, Benefitsand Functions
Main devices are available from 400 to4000 amperes and can include MoldedCase Circuit Breakers, SPB Systems
Pow-R-Breakers, DS or DSL Low Volt-age Air Circuit Breakers, Magnum DSCircuit Breakers, FDPW fusible switchesor bolted pressure switches. Mainbuses are rated up to 6000 amperes.
Branch circuit breakers range from 150to 1200 ampere frames. When Series CCircuit Breakers are used, higher rat-ings and increased series ratings will beachieved. Branch fusible switches areavailable from 100 to 1200 amperes.
Interrupting capacities up to 200,000amperes are UL listed and the bus barsystem may be braced from a stan-dard 65,000 amperes up to a maxi-
mum 200,000 amperes.Pow-R-Line i Switchboards are ULlisted and meet all applicable require-ments of NEMA and NEC. They arerear accessible and front and rearaligned. Both Type 1 and Type 3Renclosures are available.
Integrated Monitoring Protectionand Control CommunicationsSystems
The capabilities of distribution andcontrol assemblies can be expandedby tying together multiple devices in
electrical distribution systems. Froma central location (on-site or off-site),an operator uses a personal computer(master control unit) to monitor, con-trol and communicate with compatibledevices on a distribution system.These microprocessor-based devices,designed and built by Eaton, performmonitoring, protection and controlfunctions.
Space-Saving Ground FaultTest Panels
Pow-R-Line i Switchboards canaccommodate either integral or zerosequence types of ground fault protec-tion. Depending on the specific appli-cation, a test panel can be mountedin the circuit breaker compartmentwhich may eliminate the need foran auxiliary structure.
Fusible Switches
Pow-R-Line i Switchboards have beendesigned to accommodate fusibleswitches. Safety is provided by steelcompartments that insulate eachhorizontally mounted switch fromthe vertical and main buses. As withswitchboards utilizing circuit breakers,insulated copper runbacks carry powerinto the spacious, glass polyester
barriered rear cable compartment.
UL Listed Shunt Trip andFusible Switches
Shunt trip attachments for use withground fault protection devices canbe installed on 400 to 1200 ampereType FDPW fusible switches. Bothare UL listed when the shunt trip isfactory installed.
High Durability Finish
A baked-on polyester powder coatingsystem protects all structural steelparts. It provides excellent mechanical
strength and resistance to chalkingnormally caused by the sun’s ultravioletrays and meets the salt spray require-ments of ASTM B-117.
Pow-R-Line i Quality Assurance
Final testing helps ensure that eachPow-R-Line i Switchboard performsin accordance with UL standards andcustomer specifications. Each assem-bly is shipped with a “SwitchboardVerification Report” that documentscompletion of every inspection and test.
Provisions for the Future
Future expansion provisions includeline side connectors, load side runbacks,terminals, and glass polyester com-partments and covers (for circuitbreakers). Space only for both circuitbreakers and fusible switches is alsoavailable.
Standards and Certifications
■ Meets NEMA Standard PB-2 andUL 891.
■ Seismically qualified.
8/2/2019 TK13301
http://slidepdf.com/reader/full/tk13301 7/24
CA08101001E For more information visit: www.eaton.com
1Switchboards
February 2007
Instant Service Switchboards
Product Description
Product Description
Eaton’s Cutler-Hammer Instant® Ser-vice Switchboards are designed asstocked units to provide fast delivery to match the needs of the construction
market.Suitable for use as service entranceequipment, they combine utilitymetering provisions with a fused mainswitch in a single compact section thatcan also include a distribution panelfor feeder and branch circuit breakers.
Typical applications for these versatileswitchboards include small officebuildings and factories, stores, super-markets and shopping centers.
Type 1 Indoor
Type 3R Outdoor
Application Description
■ 120/240 Vac, 1-phase 3-wire.
■ 208Y/120 volt or 240/120 Vac,3-phase 4-wire.
■ 480Y/277 Vac, 3-phase 4-wire.
Interrupting Ratings (Series Rating)
■ 65,000 rms symmetrical amperes at240 Vac, using Types BAB and EDbranch circuit breakers.
■ 65,000 rms symmetrical amperes at480Y/277 Vac, using Types GHB andFD branch circuit breakers.
Features, Benefitsand Functions
These switchboards are available ineither indoor or outdoor enclosuresmanufactured of code-gauge steelwith a durable light gray finish. Allunits are completely enclosed withfront, rear and side covers. Outdoorunits include a front hinged door.
The service section includes:
■ Main lugs mounted at the top(two #4 – 600 kcmil per phase) foroverhead feed or for use with anunderground pull section.
■ A sealable metering and CT com-partment with bussing for utility bartype CTs and two 15-inch (381.0 mm)high meter compartment doors —one with provisions for meter socket
and test block, one blank. (Metersocket is ordered separately.)
■ A 400 or 600 ampere T-Typefused main switch with either loadlugs (same as main lugs) or withconnections to a factory installeddistribution panel.
Underground pull sections are avail-able with lug landing kits providingstuds for incoming cables per EUSERCstandards and two #4 – 600 kcmil lugsper phase for cable connection to theservice section.
Distribution panels can be included for240 Vac maximum (1-phase 3-wire or3-phase 4-wire) or for 480Y/277 Vac(3-phase 4-wire). The 240 volt panelshave provisions for four Type ED 225ampere frame circuit breakers and 24
poles of Type BAB 100 ampere framecircuit breakers. The 480Y/277 voltpanel has provisions for four Type FD225 ampere frame circuit breakersand 24 poles of Type GHB 100 ampereframe circuit breakers. The bolt-on typecircuit breakers are ordered separately.
For applications that require the loadcircuit conductors to exit at the top, aloadside wireway compartment is avail-able that bolts to the service section.
Standard switchboards include two15-inch (381.0 mm) high meter com-partment doors, one with meter socketprovisions and one blank. For other
arrangements, accessory units areavailable. Check utility requirements.
Standards and Certifications
Eaton’s Cutler-Hammer Instant ServiceSwitchboards are listed by Under-writers Laboratories and comply withall applicable industry standards.
These switchboards meet EUSERC stan-dards as well as other local utility codes.
Seismic Qualified
Cutler-Hammer Instant Service Switch-boards are seismically tested, seismi-
cally qualified, and exceed requirementsof both the Uniform Building Code (UBC) and the California Building Code(CBC) for all seismic zones.
Table 15-1. Dimensions in Inches (mm)
Height Width Depth
Indoor
90 (2286.0) 32 (812.8) 14 (355.6)
Outdoor
90 (2286.0) 38 (965.2) 26 (660.4)
8/2/2019 TK13301
http://slidepdf.com/reader/full/tk13301 8/24
February 2007
15-8
For more information visit: www.eaton.com CA08101001E
Switchboards
5
Instant Service Switchboards
Product Selection
Product Selection
Table 15-2. Main Fused Switch Only
Table 15-3. Main Fused Switch with Distribution Panel
240 volt distribution panels have double branch provisions for: four Type ED 225 ampere framecircuit breakers and 24 poles of Type BAB 100 ampere frame circuit breakers.
480Y/277 volt distribution panels have double branch provisions for: four Type FD 225 ampereframe circuit breakers and 24 poles of Type GHB 100 ampere frame circuit breakers.
Note: Circuit breakers for distribution panels are ordered separately.
Table 15-4. Underground Pull Sections —Same Depth as Switchboard with Provisions for Lug Landing Kit
Check utility requirements — most EUSERC utilities require 30-inch (762.0 mm) width.
Service MainAmpereRating
Type 1 — Indoor Type 3R — Outdoor
CatalogNumber
PriceU.S. $
CatalogNumber
PriceU.S. $
240 Vac Maximum1-Phase 3-Wire 400
600MSB423MSB623
RMSB423RMSB623
3-Phase 4-Wire 400600
MSB424MSB624
RMSB424RMSB624
480Y/277 Vac
3-Phase 4-Wire 400600
MSB444MSB644
RMSB444RMSB644
Service MainAmpereRating
Type 1 — Indoor Type 3R — Outdoor
CatalogNumber
PriceU.S. $
CatalogNumber
PriceU.S. $
240 Vac Maximum
1-Phase 3-Wire 400
600
MSBP423
MSBP623
RMSBP423
RMSBP6233-Phase 4-Wire 400
600MSBP424MSBP624
RMSBP424RMSBP624
480Y/277 Vac
3-Phase 4-Wire 400600
MSBP444MSBP644
RMSBP444RMSBP644
Section Width Type 1 — Indoor Type 3R — Outdoor
Inches mm Catalog
Number
Price
U.S. $
Catalog
Number
Price
U.S. $
24
30609.6
762.0UG24WUG30W
RUG24WRUG30W
NEMA Type 1 pull section can be installed separate from service section. Add Side Closer Plate,Catalog Number UGCP, Price U.S. dollars $94.00.
Table 15-5. Lug Landing Kits for UndergroundPull Sections
Mounts in 30-inch (762.0 mm) widesection only.
Table 15-6. Load Side Wireway —12 Inches (304.8 mm) WideSame Depth as Switchboard
MaximumAmpereRating
Service CatalogNumber
PriceU.S. $
400 1-Phase3-Wire
LL4003
3-Phase4-Wire
LL4004
800 1-Phase3-Wire
LL8003
3-Phase4-Wire
LL8004
Type Catalog
Number
Price
U.S. $
Type 1 — IndoorType 3R — Outdoor
LSS12WRLSS12W
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . . DE1
8/2/2019 TK13301
http://slidepdf.com/reader/full/tk13301 9/24
February 2007
CA08101001E For more information visit: www.eaton.com
1SwitchboardsInstant Service Switchboards
Accessories and Circuit Breakers
AccessoriesTable 15-7. Meter Compartment Doors — (Meter Sockets Not Included) Table 15-8. Meter Sockets — For Field Installation
Fifth jaw at 9 o’clock position. Basic four jaw socket with fifth and sixth jaws at 3 and
9 o’clock positions. Required for all SDG&E services rated at 3-phase 4-wire.
Circuit BreakersTable 15-9. Circuit Breakers for Distribution Panels — 240 Vac Maximum (1-Phase 3-Wire or 3-Phase 4-Wire)
Table 15-10. Circuit Breakers for Distribution Panels —480Y/277 Vac (3-Phase 4-Wire)
Door Size Dimensions Drilling CatalogNumber
PriceU.S. $Inches mm
15 H x 32 W 381.0 H x 812.8 W Blank MD150
One socket MD151
30 H x 32 W 762.0 H x 812.8 W Blank MD300
Two sockets MD302
Numberof Jaws
CatalogNumber
PriceU.S. $
Numberof Jaws
CatalogNumber
PriceU.S. $
4
5
6
M4
M5M6
8
1315
M8
M13M15
AmpereRating
1-Pole — 120/240 Vac 2-Pole — 120/240 Vac 2-Pole — 240 Vac 3-Pole — 240 Vac
CatalogNumber
PriceU.S. $
CatalogNumber
PriceU.S. $
CatalogNumber
PriceU.S. $
CatalogNumber
PriceU.S. $
15203040
5060
BAB1015IBAB1020IBAB1030IBAB1040I
BAB1050IBAB1060I
BAB2015IBAB2020IBAB2030IBAB2040I
BAB2050IBAB2060I
BAB2015HIBAB2020HIBAB2030HIBAB2040HI
BAB2050HIBAB2060HI
BAB3015HIBAB3020HIBAB3030HIBAB3040HI
BAB3050HIBAB3060HI
70 — BAB2070I BAB2070HI BAB3070HI
90100
——
BAB2090IBAB2100I
BAB2090HIBAB2100HI
BAB3090HIBAB3100HI
100125150175200225
——————
——————
ED2100IED2125IED2150IED2175IED2200IED2225I
ED3100IED3125IED3150IED3175IED3200IED3225I
AmpereRating
1-Pole 2-Pole 3-Pole
CatalogNumber
PriceU.S. $
CatalogNumber
PriceU.S. $
CatalogNumber
PriceU.S. $
152030405060
GHB1015IGHB1020IGHB1030IGHB1040IGHB1050IGHB1060I
GHB2015IGHB2020IGHB2030IGHB2040IGHB2050IGHB2060I
GHB3015IGHB3020IGHB3030IGHB3040IGHB3050IGHB3060I
708090
100
————
GHB2070IGHB2080IGHB2090IGHB2100I
GHB3070IGHB3080IGHB3090IGHB3100I
100 — FD2100I FD3100I
125150175200225
—————
FD2125IFD2150IFD2175IFD2200IFD2225I
FD3125IFD3150IFD3175IFD3200IFD3225I
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . . DE1
8/2/2019 TK13301
http://slidepdf.com/reader/full/tk13301 10/24
February 2007
5-10
For more information visit: www.eaton.com CA08101001E
Switchboards
5
Roll-up Generator Termination Box
Product Description
Roll-up GeneratorTermination Box
Roll-up Generator Termination Box
Product Description
Eaton's Cutler-Hammer Roll-upGenerator Termination Boxes (RUGTB)are designed as an intermediate termi-nation cabinet between a temporary,portable roll-up generator and thefacility being served. The RUGTB isdesigned for permanent installation
and is secured to a concrete padwith bolts.
The RUGTB includes line terminationsfor the temporary connection of theportable generator and permanentconnections on the load side to thesecondary disconnect in the facilitywhich is interlocked with the mainovercurrent device in a mannerthat ensures that only one (either theservice main or the generator main)can be energized at any one time.The conductors and conduits mustbe sized and suitable for carrying theload ratings marked on the equipmentper the National Electrical Code.
Standards and Ratings
■ UL 1773 listed — Termination Boxes.
■ 600 Vac maximum.
■ Amperage ratings: 800, 1200, 1600,2000 and 2500.
■ Assembly short circuit rating: 25,000amperes rms symmetrical.
■ Marked “Suitable for use on theline side of service equipment” perUL 1773.
Features
EnclosureThe enclosure is free-standing withfeet on the bottom providing accessto the cable connections for temporaryroll-up generator terminations. Theenclosure is made from code gauge
steel and is suitable for either outdooror indoor installation (Type 3R con-struction). The enclosure is powdercoat painted ANSI 61 gray. Eachenclosure houses line and load phase,neutral and ground connections.Access is provided at the bottom ofthe enclosure for both the temporaryconnections to the roll-up generatorand permanent connections tothe facility's generator overcurrentdisconnecting means. The permanentconnection section at the bottom ofthe enclosure contains a fixed mount-ing plate. The temporary generatorconnection to the RUGTB contains ahinged cover that allows access to theenclosure for generator conductors.
The enclosure utilizes feet that raisethe termination compartment off fin-ished grade by 18-inches (457.2 mm).Enclosure feet have provisions foranchoring the RUGTB. Anchor boltsare to secure the RUGTB and shallbe encased in a concrete pad by theinstaller in a manner that is suitableas a permanent base for the unit.A template for anchor bolt installationis available from the manufacturer.
The enclosure contains a sturdy,lockable, hinged door for access tothe termination compartment by quali-fied personnel as described in NFPA70E and the National Electrical Code.Feeder conductor entry is provided
in the bottom of the enclosure for theline side (generator). A hinged bottomplate is provided on the line sidefor access to line terminations. Thepermanent load connections (feedingto the facility overcurrent device)exit the enclosure from the bottom.
Terminations
All Roll-up Generator TerminationBoxes contain a termination/luglanding for three phases and neutralplus ground. Line termination optionsinclude mechanical lugs, one-holeand two-hole compression lugs,one-hole and two-hole compression
lug provisions and quick disconnect.
Lug provisions are provided withbolt configurations as described in thecatalog data on the following pages.Where lug provisions are ordered,lugs are supplied by others.
8/2/2019 TK13301
http://slidepdf.com/reader/full/tk13301 11/24
February 2007
CA08101001E For more information visit: www.eaton.com
15SwitchboardsRoll-up Generator Termination Box
Dimensions
Dimensions
Figure 15-2. Enclosure Dimensions
Figure 15-3. Termination/Lug Landing
8/2/2019 TK13301
http://slidepdf.com/reader/full/tk13301 12/24
February 2007
5-12
For more information visit: www.eaton.com CA08101001E
Switchboards
5
Roll-up Generator Termination Box
Technical Data
Technical Data
Table 15-11. Roll-up Generator Termination Box with Line and Load Mechanical Box Lugs
Note: Line and load mechanical lugs are factory selected and installed.
Table 15-12. Roll-up Generator Termination Box with Line Mechanical Box Lugs; Load 1-Hole Compression Lugs
Note: Line side mechanical lugs are factory selected and installed.
Note: Load side Anderson, 1-hole compression lugs are factory selected and installed.
AmpereRating
Dimensions in Inches (mm)H x W x D
Mechanical Box Lugs LineTermination Number,Range and Type
Mechanical Box Lugs LoadTermination Number,Range and Type
CatalogNumber
PriceU.S. $
800 78.00 x 36.00 x 24.00(1981.2 x 914.4 x 609.6)
(3) 4/0 – 500 kcmil Al/Cu (3) 4/0 – 500 kcmil Al/Cu GTB08MAMA
(3) 4/0 – 500 kcmil Al/Cu (2) 3/0 – 750 kcmil Al/Cu GTB08MAMB
(2) 3/0 – 750 kcmil Al/Cu (3) 4/0 – 500 kcmil Al/Cu GTB08MBMA
(2) 3/0 – 750 kcmil Al/Cu (2) 3/0 – 750 kcmil Al/Cu GTB08MBMB
1200 78.00 x 36.00 x 24.00(1981.2 x 914.4 x 609.6)
(4) 4/0 – 500 kcmil Al/Cu (4) 4/0 – 500 kcmil Al/Cu GTB12MCMC
(4) 4/0 – 500 kcmil Al/Cu (3) 3/0 – 750 kcmil Al/Cu GTB12MCMD
(3) 3/0 – 750 kcmil Al/Cu (4) 4/0 – 500 kcmil Al/Cu GTB12MDMC
(3) 3/0 – 750 kcmil Al/Cu (3) 3/0 – 750 kcmil Al/Cu GTB12MDMD
1600 78.00 x 36.00 x 24.00(1981.2 x 914.4 x 609.6)
(5) 4/0 – 500 kcmil Al/Cu (5) 4/0 – 500 kcmil Al/Cu GTB16MEME
(5) 4/0 – 500 kcmil Al/Cu (4) 3/0 – 750 kcmil Al/Cu GTB16MEMF
(4) 3/0 – 750 kcmil Al/Cu (5) 4/0 – 500 kcmil Al/Cu GTB16MFME
(4) 3/0 – 750 kcmil Al/Cu (4) 3/0 – 750 kcmil Al/Cu GTB16MFMF
2000 78.00 x 36.00 x 24.00(1981.2 x 914.4 x 609.6)
(6) 4/0 – 500 kcmil Al/Cu (6) 4/0 – 500 kcmil Al/Cu GTB20MGMG
(6) 4/0 – 500 kcmil Al/Cu (5) 3/0 – 750 kcmil Al/Cu GTB20MGMH
(5) 3/0 – 750 kcmil Al/Cu (6) 4/0 – 500 kcmil Al/Cu GTB20MHMG
(5) 3/0 – 750 kcmil Al/Cu (5) 3/0 – 750 kcmil Al/Cu GTB20MHMH
2500 78.00 x 36.00 x 24.00(1981.2 x 914.4 x 609.6)
(8) 4/0 – 500 kcmil Al/Cu (8) 4/0 – 500 kcmil Al/Cu GTB25MJMJ
(8) 4/0 – 500 kcmil Al/Cu (7) 3/0 – 750 kcmil Al/Cu GTB25MJMK
(7) 3/0 – 750 kcmil Al/Cu (8) 4/0 – 500 kcmil Al/Cu GTB25MKMJ
(7) 3/0 – 750 kcmil Al/Cu (7) 3/0 – 750 kcmil Al/Cu GTB25MJMJ
AmpereRating
Dimensions in Inches (mm)H x W x D
Mechanical Box Lugs LineTermination Number,Range and Type
1-Hole Compression LoadTermination Number,Range and Type
CatalogNumber
PriceU.S. $
800 78.00 x 36.00 x 24.00(1981.2 x 914.4 x 609.6)
(3) 4/0 – 500 kcmil Al/Cu (3) 4/0 – 500 kcmil Al/Cu GTB08MACA
(3) 4/0 – 500 kcmil Al/Cu (2) 3/0 – 750 kcmil Al/Cu GTB08MACB
(2) 3/0 – 750 kcmil Al/Cu (3) 4/0 – 500 kcmil Al/Cu GTB08MBCA
(2) 3/0 – 750 kcmil Al/Cu (2) 3/0 – 750 kcmil Al/Cu GTB08MBCB
1200 78.00 x 36.00 x 24.00(1981.2 x 914.4 x 609.6)
(4) 4/0 – 500 kcmil Al/Cu (4) 4/0 – 500 kcmil Al/Cu GTB12MCCC
(4) 4/0 – 500 kcmil Al/Cu (3) 3/0 – 750 kcmil Al/Cu GTB12MCCD
(3) 3/0 – 750 kcmil Al/Cu (4) 4/0 – 500 kcmil Al/Cu GTB12MDCC
(3) 3/0 – 750 kcmil Al/Cu (3) 3/0 – 750 kcmil Al/Cu GTB12MDCD
1600 78.00 x 36.00 x 24.00(1981.2 x 914.4 x 609.6)
(5) 4/0 – 500 kcmil Al/Cu (5) 4/0 – 500 kcmil Al/Cu GTB16MECE
(5) 4/0 – 500 kcmil Al/Cu (4) 3/0 – 750 kcmil Al/Cu GTB16MECF
(4) 3/0 – 750 kcmil Al/Cu (5) 4/0 – 500 kcmil Al/Cu GTB16MFCE
(4) 3/0 – 750 kcmil Al/Cu (4) 3/0 – 750 kcmil Al/Cu GTB16MFCF
2000 78.00 x 36.00 x 24.00(1981.2 x 914.4 x 609.6)
(6) 4/0 – 500 kcmil Al/Cu (6) 4/0 – 500 kcmil Al/Cu GTB20MGCG
(6) 4/0 – 500 kcmil Al/Cu (5) 3/0 – 750 kcmil Al/Cu GTB20MGCH
(5) 3/0 – 750 kcmil Al/Cu (6) 4/0 – 500 kcmil Al/Cu GTB20MHCG
(5) 3/0 – 750 kcmil Al/Cu (5) 3/0 – 750 kcmil Al/Cu GTB20MHCH2500 78.00 x 36.00 x 24.00
(1981.2 x 914.4 x 609.6)(8) 4/0 – 500 kcmil Al/Cu (8) 4/0 – 500 kcmil Al/Cu GTB25MJCJ
(8) 4/0 – 500 kcmil Al/Cu (7) 3/0 – 750 kcmil Al/Cu GTB25MJCK
(7) 3/0 – 750 kcmil Al/Cu (8) 4/0 – 500 kcmil Al/Cu GTB25MKCJ
(7) 3/0 – 750 kcmil Al/Cu (7) 3/0 – 750 kcmil Al/Cu GTB25MJCJ
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . CE9
8/2/2019 TK13301
http://slidepdf.com/reader/full/tk13301 13/24
February 2007
CA08101001E For more information visit: www.eaton.com
15SwitchboardsRoll-up Generator Termination Box
Technical Data
Table 15-13. Roll-up Generator Termination Box with Line Mechanical Box Lugs; Load 2-Hole Compression Lugs
Note: Line side mechanical lugs are factory selected and installed.
Note: Load side factory installed Burndy, 2-hole, short barrel compression lugs suitable for COPPER WIRE ONLY requires 45-inches(1143.0 mm) wide enclosure.
AmpereRating
Dimensions in Inches (mm)H x W x D
Mechanical Box Lugs LineTermination Number,Range and Type
2-Hole Compression LoadTermination Cu ONLYWire Size
CatalogNumber
PriceU.S. $
800 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(3) 4/0 – 500 kcmil Al/Cu (3) 350 kcmil Cu ONLY GTB08MACL
(3) 4/0 – 500 kcmil Al/Cu (3) 400 kcmil Cu ONLY GTB08MBCM
(2) 3/0 – 750 kcmil Al/Cu (3) 350 kcmil Cu ONLY GTB08MBCL
(2) 3/0 – 750 kcmil Al/Cu (3) 400 kcmil Cu ONLY GTB08MACL
1200 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(4) 4/0 – 500 kcmil Al/Cu (4) 500 kcmil Cu ONLY GTB12MCCN
(4) 4/0 – 500 kcmil Al/Cu (3) 600 kcmil Cu ONLY GTB12MCCP
(4) 4/0 – 500 kcmil Al/Cu (3) 750 kcmil Cu ONLY GTB12MCCQ
(3) 3/0 – 750 kcmil Al/Cu (4) 500 kcmil Cu ONLY GTB12MDCN
(3) 3/0 – 750 kcmil Al/Cu (3) 600 kcmil Cu ONLY GTB12MDCP
(3) 3/0 – 750 kcmil Al/Cu (3) 750 kcmil Cu ONLY GTB12MDCQ
1600 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(5) 4/0 – 500 kcmil Al/Cu (5) 500 kcmil Cu ONLY GTB16MECR
(5) 4/0 – 500 kcmil Al/Cu (4) 600 kcmil Cu ONLY GTB16MECS
(5) 4/0 – 500 kcmil Al/Cu (4) 750 kcmil Cu ONLY GTB16MECT
(4) 3/0 – 750 kcmil Al/Cu (5) 500 kcmil Cu ONLY GTB16MFCR
(4) 3/0 – 750 kcmil Al/Cu (4) 600 kcmil Cu ONLY GTB16MFCS
(4) 3/0 – 750 kcmil Al/Cu (4) 750 kcmil Cu ONLY GTB16MFCT
2000 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(6) 4/0 – 500 kcmil Al/Cu (6) 500 kcmil Cu ONLY GTB20MGCu
(6) 4/0 – 500 kcmil Al/Cu (5) 600 kcmil Cu ONLY GTB20MGCV
(6) 4/0 – 500 kcmil Al/Cu (5) 750 kcmil Cu ONLY GTB20MGCW
(5) 3/0 – 750 kcmil Al/Cu (6) 500 kcmil Cu ONLY GTB20MHCu
(5) 3/0 – 750 kcmil Al/Cu (5) 600 kcmil Cu ONLY GTB20MHCV
(5) 3/0 – 750 kcmil Al/Cu (5) 750 kcmil Cu ONLY GTB20MHCW
2500 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(8) 4/0 – 500 kcmil Al/Cu (7) 500 kcmil Cu ONLY GTB25MJCX
(8) 4/0 – 500 kcmil Al/Cu (6) 600 kcmil Cu ONLY GTB25MJCY
(8) 4/0 – 500 kcmil Al/Cu (6) 750 kcmil Cu ONLY GTB25MJCZ
(7) 3/0 – 750 kcmil Al/Cu (7) 500 kcmil Cu ONLY GTB25MKCX
(7) 3/0 – 750 kcmil Al/Cu (6) 600 kcmil Cu ONLY GTB25MKCY
(7) 3/0 – 750 kcmil Al/Cu (6) 750 kcmil Cu ONLY GTB25MKCZ
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . CE9
8/2/2019 TK13301
http://slidepdf.com/reader/full/tk13301 14/24
February 2007
5-14
For more information visit: www.eaton.com CA08101001E
Switchboards
5
Roll-up Generator Termination Box
Technical Data
Table 15-14. Roll-up Generator Termination Box with Line Mechanical Box Lugs; Load PROVISIONS ONLY 1-Hole Compression Lugs
Note: Line side mechanical lugs are factory selected and installed.
Note: Load side factory installed 3/8" bolt provisions for 1-hole compression lugs (lugs furnished by others).
Table 15-15. Roll-up Generator Termination Box with Line Mechanical Box Lugs; Load PROVISIONS ONLY 2-Hole Compression Lugs
Note: Line side mechanical lugs are factory selected and installed.
Note: Load side factory installed 1/2" bolt provisions on 1 3/4" hole centers for 2-hole compression lugs (lugs furnished by others).
Note: Requires 45-inch (1143.0 mm) wide enclosure.
AmpereRating
Dimensions in Inches (mm)H x W x D
Mechanical Box Lugs LineTermination Number,Range and Type
1-Hole Compression LoadProvisions ONLY Numberand Range
CatalogNumber
PriceU.S. $
800 78.00 x 36.00 x 24.00(1981.2 x 914.4 x 609.6)
(3) 4/0 – 500 kcmil Al/Cu (3) Provisions Per Phase GTB08MAP1
(2) 3/0 – 750 kcmil Al/Cu (3) Provisions Per Phase GTB08MBP1
1200 78.00 x 36.00 x 24.00(1981.2 x 914.4 x 609.6)
(4) 4/0 – 500 kcmil Al/Cu (4) Provisions Per Phase GTB12MCP2
(3) 3/0 – 750 kcmil Al/Cu (4) Provisions Per Phase GTB12MDP2
1600 78.00 x 36.00 x 24.00(1981.2 x 914.4 x 609.6)
(5) 4/0 – 500 kcmil Al/Cu (5) Provisions Per Phase GTB16MEP3
(4) 3/0 – 750 kcmil Al/Cu (5) Provisions Per Phase GTB16MFP3
2000 78.00 x 36.00 x 24.00(1981.2 x 914.4 x 609.6)
(6) 4/0 – 500 kcmil Al/Cu (6) Provisions Per Phase GTB20MGP4
(5) 3/0 – 750 kcmil Al/Cu (6) Provisions Per Phase GTB20MHP4
2500 78.00 x 36.00 x 24.00(1981.2 x 914.4 x 609.6)
(8) 4/0 – 500 kcmil Al/Cu (8) Provisions Per Phase GTB25MJP5
(7) 3/0 – 750 kcmil Al/Cu (8) Provisions Per Phase GTB25MKP5
AmpereRating
Dimensions in Inches (mm)H x W x D
Mechanical Box Lugs LineTermination Number,Range and Type
2-Hole Compression LoadProvisions ONLY Numberand Range
CatalogNumber
PriceU.S. $
800 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(3) 4/0 – 500 kcmil Al/Cu (3) Provisions Per Phase GTB08MAPA
(2) 3/0 – 750 kcmil Al/Cu (3) Provisions Per Phase GTB08MBPA
1200 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(4) 4/0 – 500 kcmil Al/Cu (4) Provisions Per Phase GTB12MCPB
(3) 3/0 – 750 kcmil Al/Cu (4) Provisions Per Phase GTB12MDPB
1600 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(5) 4/0 – 500 kcmil Al/Cu (5) Provisions Per Phase GTB16MEPC
(4) 3/0 – 750 kcmil Al/Cu (5) Provisions Per Phase GTB16MFPC
2000 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(6) 4/0 – 500 kcmil Al/Cu (6) Provisions Per Phase GTB20MGPD
(5) 3/0 – 750 kcmil Al/Cu (6) Provisions Per Phase GTB20MHPD
2500 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(8) 4/0 – 500 kcmil Al/Cu (8) Provisions Per Phase GTB25MJPE
(7) 3/0 – 750 kcmil Al/Cu (8) Provisions Per Phase GTB25MKPE
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . CE9
8/2/2019 TK13301
http://slidepdf.com/reader/full/tk13301 15/24
February 2007
CA08101001E For more information visit: www.eaton.com
15SwitchboardsRoll-up Generator Termination Box
Technical Data
Table 15-16. Roll-up Generator Termination Box with Line 1-Hole Compression Lugs and Load Mechanical Box Lugs
Note: Line side Anderson, 1-hole compression lugs are factory selected and installed.
Note: Load side mechanical lugs are factory selected and installed.
Table 15-17. Roll-up Generator Termination Box with Line and Load 1-Hole Compression Lugs
Note: Line side and load Anderson, 1-hole compression lugs are factory selected and installed.
AmpereRating
Dimensions in Inches (mm)H x W x D
1-Hole Compression LineTermination Number,Range and Type
Mechanical Box Lugs LoadTermination Number,Range and Type
CatalogNumber
PriceU.S. $
800 78.00 x 36.00 x 24.00(1981.2 x 914.4 x 609.6)
(3) 4/0 – 500 kcmil Al/Cu (3) 4/0 – 500 kcmil Al/Cu GTB08CAMA
(3) 4/0 – 500 kcmil Al/Cu (2) 3/0 – 750 kcmil Al/Cu GTB08CAMB
(2) 3/0 – 750 kcmil Al/Cu (3) 4/0 – 500 kcmil Al/Cu GTB08CBMA
(2) 3/0 – 750 kcmil Al/Cu (2) 3/0 – 750 kcmil Al/Cu GTB08CBMB
1200 78.00 x 36.00 x 24.00(1981.2 x 914.4 x 609.6)
(4) 4/0 – 500 kcmil Al/Cu (4) 4/0 – 500 kcmil Al/Cu GTB12CCMC
(4) 4/0 – 500 kcmil Al/Cu (3) 3/0 – 750 kcmil Al/Cu GTB12CCMD
(3) 3/0 – 750 kcmil Al/Cu (4) 4/0 – 500 kcmil Al/Cu GTB12CDMC
(3) 3/0 – 750 kcmil Al/Cu (3) 3/0 – 750 kcmil Al/Cu GTB12CDMD
1600 78.00 x 36.00 x 24.00(1981.2 x 914.4 x 609.6)
(5) 4/0 – 500 kcmil Al/Cu (5) 4/0 – 500 kcmil Al/Cu GTB16CEME
(5) 4/0 – 500 kcmil Al/Cu (4) 3/0 – 750 kcmil Al/Cu GTB16CEMF
(4) 3/0 – 750 kcmil Al/Cu (5) 4/0 – 500 kcmil Al/Cu GTB16CFME
(4) 3/0 – 750 kcmil Al/Cu (4) 3/0 – 750 kcmil Al/Cu GTB16CFMF
2000 78.00 x 36.00 x 24.00(1981.2 x 914.4 x 609.6)
(6) 4/0 – 500 kcmil Al/Cu (6) 4/0 – 500 kcmil Al/Cu GTB20CGMG
(6) 4/0 – 500 kcmil Al/Cu (5) 3/0 – 750 kcmil Al/Cu GTB20CGMH
(5) 3/0 – 750 kcmil Al/Cu (6) 4/0 – 500 kcmil Al/Cu GTB20CHMG
(5) 3/0 – 750 kcmil Al/Cu (5) 3/0 – 750 kcmil Al/Cu GTB20CHMH
2500 78.00 x 36.00 x 24.00(1981.2 x 914.4 x 609.6)
(8) 4/0 – 500 kcmil Al/Cu (8) 4/0 – 500 kcmil Al/Cu GTB25CJMJ
(8) 4/0 – 500 kcmil Al/Cu (7) 3/0 – 750 kcmil Al/Cu GTB25CJMK
(7) 3/0 – 750 kcmil Al/Cu (8) 4/0 – 500 kcmil Al/Cu GTB25CKMJ
(7) 3/0 – 750 kcmil Al/Cu (7) 3/0 – 750 kcmil Al/Cu GTB25CJMK
AmpereRating
Dimensions in Inches (mm)H x W x D
1-Hole Compression LineTermination Number,Range and Type
1-Hole Compression LoadTermination Number,Range and Type
CatalogNumber
PriceU.S. $
800 78.00 x 36.00 x 24.00(1981.2 x 914.4 x 609.6)
(3) 4/0 – 500 kcmil Al/Cu (3) 4/0 – 500 kcmil Al/Cu GTB08CACA
(3) 4/0 – 500 kcmil Al/Cu (2) 3/0 – 750 kcmil Al/Cu GTB08CACB
(2) 3/0 – 750 kcmil Al/Cu (3) 4/0 – 500 kcmil Al/Cu GTB08CBCA(2) 3/0 – 750 kcmil Al/Cu (2) 3/0 – 750 kcmil Al/Cu GTB08CBCB
1200 78.00 x 36.00 x 24.00(1981.2 x 914.4 x 609.6)
(4) 4/0 – 500 kcmil Al/Cu (4) 4/0 – 500 kcmil Al/Cu GTB12CCCC
(4) 4/0 – 500 kcmil Al/Cu (3) 3/0 – 750 kcmil Al/Cu GTB12CCCD
(3) 3/0 – 750 kcmil Al/Cu (4) 4/0 – 500 kcmil Al/Cu GTB12CDCC
(3) 3/0 – 750 kcmil Al/Cu (3) 3/0 – 750 kcmil Al/Cu GTB12CDCD
1600 78.00 x 36.00 x 24.00(1981.2 x 914.4 x 609.6)
(5) 4/0 – 500 kcmil Al/Cu (5) 4/0 – 500 kcmil Al/Cu GTB16CECE
(5) 4/0 – 500 kcmil Al/Cu (4) 3/0 – 750 kcmil Al/Cu GTB16CECF
(4) 3/0 – 750 kcmil Al/Cu (5) 4/0 – 500 kcmil Al/Cu GTB16CFCE
(4) 3/0 – 750 kcmil Al/Cu (4) 3/0 – 750 kcmil Al/Cu GTB16CFCF
2000 78.00 x 36.00 x 24.00(1981.2 x 914.4 x 609.6)
(6) 4/0 – 500 kcmil Al/Cu (6) 4/0 – 500 kcmil Al/Cu GTB20CGCG
(6) 4/0 – 500 kcmil Al/Cu (5) 3/0 – 750 kcmil Al/Cu GTB20CGCH
(5) 3/0 – 750 kcmil Al/Cu (6) 4/0 – 500 kcmil Al/Cu GTB20CHCG
(5) 3/0 – 750 kcmil Al/Cu (5) 3/0 – 750 kcmil Al/Cu GTB20CHCH
2500 78.00 x 36.00 x 24.00(1981.2 x 914.4 x 609.6) (8) 4/0 – 500 kcmil Al/Cu (8) 4/0 – 500 kcmil Al/Cu GTB25CJCJ(8) 4/0 – 500 kcmil Al/Cu (7) 3/0 – 750 kcmil Al/Cu GTB25CJCK
(7) 3/0 – 750 kcmil Al/Cu (8) 4/0 – 500 kcmil Al/Cu GTB25CKCJ
(7) 3/0 – 750 kcmil Al/Cu (7) 3/0 – 750 kcmil Al/Cu GTB25CJCK
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . CE9
8/2/2019 TK13301
http://slidepdf.com/reader/full/tk13301 16/24
February 2007
5-16
For more information visit: www.eaton.com CA08101001E
Switchboards
5
Roll-up Generator Termination Box
Technical Data
Table 15-18. Roll-up Generator Termination Box with Line 1-Hole Compression Lugs; Load 2-Hole Compression Lugs
Note: Line side Anderson, 1-hole compression lugs are factory selected and installed.
Note: Load side factory installed Burndy, 2-hole, short barrel compression lugs suitable for COPPER WIRE ONLY.Note: Requires 45-inch (1143.0 mm) wide enclosure.
Table 15-19. Roll-up Generator Termination Box with Line 1-Hole Compression Lugs; Load PROVISIONS ONLY 1-Hole Compression Lugs
Note: Line side Anderson, 1-hole compression lugs are factory selected and installed.
Note: Load side factory installed 3/8" bolt provisions for 1-hole compression lugs (lugs furnished by others).
AmpereRating
Dimensions in Inches (mm)H x W x D
1-Hole Compression LineTermination Number,Range and Type
2-Hole Compression LoadTermination Cu ONLYWire Size
CatalogNumber
PriceU.S. $
800 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(3) 4/0 – 500 kcmil Al/Cu (3) 350 kcmil Cu ONLY GTB08CACL
(3) 4/0 – 500 kcmil Al/Cu (3) 400 kcmil Cu ONLY GTB08CACM
(2) 3/0 – 750 kcmil Al/Cu (3) 350 kcmil Cu ONLY GTB08CBCL
(2) 3/0 – 750 kcmil Al/Cu (3) 400 kcmil Cu ONLY GTB08CBCM
1200 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(4) 4/0 – 500 kcmil Al/Cu (4) 500 kcmil Cu ONLY GTB12CCCN
(4) 4/0 – 500 kcmil Al/Cu (3) 600 kcmil Cu ONLY GTB12CCCP
(4) 4/0 – 500 kcmil Al/Cu (3) 750 kcmil Cu ONLY GTB12CCCQ
(3) 3/0 – 750 kcmil Al/Cu (4) 500 kcmil Cu ONLY GTB12CDCN
(3) 3/0 – 750 kcmil Al/Cu (3) 600 kcmil Cu ONLY GTB12CDCP
(3) 3/0 – 750 kcmil Al/Cu (3) 750 kcmil Cu ONLY GTB12CDCQ
1600 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(5) 4/0 – 500 kcmil Al/Cu (5) 500 kcmil Cu ONLY GTB16CECR
(5) 4/0 – 500 kcmil Al/Cu (4) 600 kcmil Cu ONLY GTB16CECS
(5) 4/0 – 500 kcmil Al/Cu (4) 750 kcmil Cu ONLY GTB16CECT
(4) 3/0 – 750 kcmil Al/Cu (5) 500 kcmil Cu ONLY GTB16CFCR
(4) 3/0 – 750 kcmil Al/Cu (4) 600 kcmil Cu ONLY GTB16CFCS
(4) 3/0 – 750 kcmil Al/Cu (4) 750 kcmil Cu ONLY GTB16CFCT
2000 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(6) 4/0 – 500 kcmil Al/Cu (6) 500 kcmil Cu ONLY GTB20CGCu
(6) 4/0 – 500 kcmil Al/Cu (5) 600 kcmil Cu ONLY GTB20CGCV
(6) 4/0 – 500 kcmil Al/Cu (5) 750 kcmil Cu ONLY GTB20CGCW
(5) 3/0 – 750 kcmil Al/Cu (6) 500 kcmil Cu ONLY GTB20CHCu
(5) 3/0 – 750 kcmil Al/Cu (5) 600 kcmil Cu ONLY GTB20CHCV
(5) 3/0 – 750 kcmil Al/Cu (5) 750 kcmil Cu ONLY GTB20CHCW
2500 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(8) 4/0 – 500 kcmil Al/Cu (7) 500 kcmil Cu ONLY GTB25CJCX
(8) 4/0 – 500 kcmil Al/Cu (6) 600 kcmil Cu ONLY GTB25CJCY
(8) 4/0 – 500 kcmil Al/Cu (6) 750 kcmil Cu ONLY GTB25CJCZ
(7) 3/0 – 750 kcmil Al/Cu (7) 500 kcmil Cu ONLY GTB25CKCX
(7) 3/0 – 750 kcmil Al/Cu (6) 600 kcmil Cu ONLY GTB25CKCY
(7) 3/0 – 750 kcmil Al/Cu (6) 750 kcmil Cu ONLY GTB25CKCZ
AmpereRating
Dimensions in Inches (mm)H x W x D
1-Hole Compression LineTermination Number,Range and Type
1-Hole Compression LoadProvisions ONLY Numberand Range
CatalogNumber
PriceU.S. $
800 78.00 x 36.00 x 24.00(1981.2 x 914.4 x 609.6)
(3) 4/0 – 500 kcmil Al/Cu (3) Provisions Per Phase GTB08CAP1
(2) 3/0 – 750 kcmil Al/Cu (3) Provisions Per Phase GTB08CBP1
1200 78.00 x 36.00 x 24.00(1981.2 x 914.4 x 609.6)
(4) 4/0 – 500 kcmil Al/Cu (4) Provisions Per Phase GTB12CCP2
(3) 3/0 – 750 kcmil Al/Cu (4) Provisions Per Phase GTB12CDP2
1600 78.00 x 36.00 x 24.00(1981.2 x 914.4 x 609.6)
(5) 4/0 – 500 kcmil Al/Cu (5) Provisions Per Phase GTB16CEP3
(4) 3/0 – 750 kcmil Al/Cu (5) Provisions Per Phase GTB16CFP3
2000 78.00 x 36.00 x 24.00(1981.2 x 914.4 x 609.6)
(6) 4/0 – 500 kcmil Al/Cu (6) Provisions Per Phase GTB20CGP4
(5) 3/0 – 750 kcmil Al/Cu (6) Provisions Per Phase GTB20CHP42500 78.00 x 36.00 x 24.00
(1981.2 x 914.4 x 609.6)(8) 4/0 – 500 kcmil Al/Cu (8) Provisions Per Phase GTB25CJP5
(7) 3/0 – 750 kcmil Al/Cu (8) Provisions Per Phase GTB25CKP5
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . CE9
8/2/2019 TK13301
http://slidepdf.com/reader/full/tk13301 17/24
February 2007
CA08101001E For more information visit: www.eaton.com
15SwitchboardsRoll-up Generator Termination Box
Technical Data
Table 15-20. Roll-up Generator Termination Box with 1-Hole Compression Lugs; Load PROVISIONS ONLY 2-Hole Compression Lugs
Note: Line side Anderson, 1-hole compression lugs are factory selected and installed.
Note: Load side factory installed 1/2" bolt provisions on 1 3/4" hole centers for 2-hole compression lugs (lugs furnished by others).
Note: Requires 45-inch (1143.0 mm) wide enclosure.
Table 15-21. Roll-up Generator Termination Box with Line 2-Hole Compression Lugs and Load Mechanical Box Lugs
Note: Line side factory installed Burndy, 2-hole, short barrel compression lugs suitable for COPPER WIRE ONLY.
Note: Load side mechanical lugs are factory selected and installed.
Note: Requires 45-inch (1143.0 mm) wide enclosure.
AmpereRating
Dimensions in Inches (mm)H x W x D
1-Hole Compression LineTermination Number,Range and Type
2-Hole Compression LoadProvisions ONLY Numberand Range
CatalogNumber
PriceU.S. $
800 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(3) 4/0 – 500 kcmil Al/Cu (3) Provisions Per Phase GTB08CAPA
(2) 3/0 – 750 kcmil Al/Cu (3) Provisions Per Phase GTB08CBPA
1200 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(4) 4/0 – 500 kcmil Al/Cu (4) Provisions Per Phase GTB12CCPB
(3) 3/0 – 750 kcmil Al/Cu (4) Provisions Per Phase GTB12CDPB
1600 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(5) 4/0 – 500 kcmil Al/Cu (5) Provisions Per Phase GTB16CEPC
(4) 3/0 – 750 kcmil Al/Cu (5) Provisions Per Phase GTB16CGPC
2000 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(6) 4/0 – 500 kcmil Al/Cu (6) Provisions Per Phase GTB20CGPD
(5) 3/0 – 750 kcmil Al/Cu (6) Provisions Per Phase GTB20CHPD
2500 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(8) 4/0 – 500 kcmil Al/Cu (8) Provisions Per Phase GTB25CJPE
(7) 3/0 – 750 kcmil Al/Cu (8) Provisions Per Phase GTB25CKPE
AmpereRating Dimensions in Inches (mm)H x W x D 2-Hole Compression LineTermination Cu ONLYWire Size
Mechanical Box Lugs LoadTermination Number,Range and Type
CatalogNumber PriceU.S. $
800 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(3) 350 kcmil Cu ONLY (3) 4/0 – 500 kcmil Al/Cu GTB08CLMA
(3) 350 kcmil Cu ONLY (2) 3/0 – 750 kcmil Al/Cu GTB08CLMB
(3) 400 kcmil Cu ONLY (3) 4/0 – 500 kcmil Al/Cu GTB08CMMA
(3) 400 kcmil Cu ONLY (2) 3/0 – 750 kcmil Al/Cu GTB08CMMB
1200 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(4) 500 kcmil Cu ONLY (4) 4/0 – 500 kcmil Al/Cu GTB12CNMC
(4) 500 kcmil Cu ONLY (3) 3/0 – 750 kcmil Al/Cu GTB12CNMD
(3) 600 kcmil Cu ONLY (4) 4/0 – 500 kcmil Al/Cu GTB12CPMC
(3) 600 kcmil Cu ONLY (3) 3/0 – 750 kcmil Al/Cu GTB12CPMD
(3) 750 kcmil Cu ONLY (4) 4/0 – 500 kcmil Al/Cu GTB12CQMC
(3) 750 kcmil Cu ONLY (3) 3/0 – 750 kcmil Al/Cu GTB12CQMD
1600 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(5) 500 kcmil Cu ONLY (5) 4/0 – 500 kcmil Al/Cu GTB16CRME
(5) 500 kcmil Cu ONLY (4) 3/0 – 750 kcmil Al/Cu GTB16CRMF(4) 600 kcmil Cu ONLY (5) 4/0 – 500 kcmil Al/Cu GTB16CSME
(4) 600 kcmil Cu ONLY (4) 3/0 – 750 kcmil Al/Cu GTB16CSMF
(4) 750 kcmil Cu ONLY (5) 4/0 – 500 kcmil Al/Cu GTB16CTME
(4) 750 kcmil Cu ONLY (4) 3/0 – 750 kcmil Al/Cu GTB16CTMF
2000 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(6) 500 kcmil Cu ONLY (6) 4/0 – 500 kcmil Al/Cu GTB20CuMG
(6) 500 kcmil Cu ONLY (5) 3/0 – 750 kcmil Al/Cu GTB20CuMH
(5) 600 kcmil Cu ONLY (6) 4/0 – 500 kcmil Al/Cu GTB20CVMG
(5) 600 kcmil Cu ONLY (5) 3/0 – 750 kcmil Al/Cu GTB20CVMH
(5) 750 kcmil Cu ONLY (6) 4/0 – 500 kcmil Al/Cu GTB20CWMG
(5) 750 kcmil Cu ONLY (5) 3/0 – 750 kcmil Al/Cu GTB20CWMH
2500 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(7) 500 kcmil Cu ONLY (8) 4/0 – 500 kcmil Al/Cu GTB25CXMJ
(7) 500 kcmil Cu ONLY (7) 3/0 – 750 kcmil Al/Cu GTB25CXMK
(6) 600 kcmil Cu ONLY (8) 4/0 – 500 kcmil Al/Cu GTB25CYMJ
(6) 600 kcmil Cu ONLY (7) 3/0 – 750 kcmil Al/Cu GTB25CYMK(6) 750 kcmil Cu ONLY (8) 4/0 – 500 kcmil Al/Cu GTB25CZMJ
(6) 750 kcmil Cu ONLY (7) 3/0 – 750 kcmil Al/Cu GTB25CZMK
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . . CE9
8/2/2019 TK13301
http://slidepdf.com/reader/full/tk13301 18/24
February 2007
5-18
For more information visit: www.eaton.com CA08101001E
Switchboards
5
Roll-up Generator Termination Box
Technical Data
Table 15-22. Roll-up Generator Termination Box with Line 2-Hole Compression Lugs and Load 1-Hole Compression Lugs
Note: Line side factory installed Burndy, 2-hole, short barrel compression lugs suitable for COPPER WIRE ONLY.
Note: Load side Anderson, 1-hole compression lugs are factory selected and installed.Note: Requires 45-inch (1143.0 mm) wide enclosure.
AmpereRating
Dimensions in Inches (mm)H x W x D
2-Hole Compression LineTermination Cu ONLYWire Size
1-Hole Compression LoadTermination Number,Range and Type
CatalogNumber
PriceU.S. $
800 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(3) 350 kcmil Cu ONLY (3) 4/0 – 500 kcmil Al/Cu GTB08CLCA
(3) 350 kcmil Cu ONLY (2) 3/0 – 750 kcmil Al/Cu GTB08CLCB
(3) 400 kcmil Cu ONLY (3) 4/0 – 500 kcmil Al/Cu GTB08CMCA
(3) 400 kcmil Cu ONLY (2) 3/0 – 750 kcmil Al/Cu GTB08CMCB
1200 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(4) 500 kcmil Cu ONLY (4) 4/0 – 500 kcmil Al/Cu GTB12CNCC
(4) 500 kcmil Cu ONLY (3) 3/0 – 750 kcmil Al/Cu GTB12CNCD
(3) 600 kcmil Cu ONLY (4) 4/0 – 500 kcmil Al/Cu GTB12CPCC
(3) 600 kcmil Cu ONLY (3) 3/0 – 750 kcmil Al/Cu GTB12CPCD
(3) 750 kcmil Cu ONLY (4) 4/0 – 500 kcmil Al/Cu GTB12CQCC
(3) 750 kcmil Cu ONLY (3) 3/0 – 750 kcmil Al/Cu GTB12CQCD
1600 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(5) 500 kcmil Cu ONLY (5) 4/0 – 500 kcmil Al/Cu GTB16CRCE
(5) 500 kcmil Cu ONLY (4) 3/0 – 750 kcmil Al/Cu GTB16CRCF
(4) 600 kcmil Cu ONLY (5) 4/0 – 500 kcmil Al/Cu GTB16CSCE
(4) 600 kcmil Cu ONLY (4) 3/0 – 750 kcmil Al/Cu GTB16CSCF
(4) 750 kcmil Cu ONLY (5) 4/0 – 500 kcmil Al/Cu GTB16CTCE
(4) 750 kcmil Cu ONLY (4) 3/0 – 750 kcmil Al/Cu GTB16CTCF
2000 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(6) 500 kcmil Cu ONLY (6) 4/0 – 500 kcmil Al/Cu GTB20CuCG
(6) 500 kcmil Cu ONLY (5) 3/0 – 750 kcmil Al/Cu GTB20CuCH
(5) 600 kcmil Cu ONLY (6) 4/0 – 500 kcmil Al/Cu GTB20CVCG
(5) 600 kcmil Cu ONLY (5) 3/0 – 750 kcmil Al/Cu GTB20CVCH
(5) 750 kcmil Cu ONLY (6) 4/0 – 500 kcmil Al/Cu GTB20CWCG
(5) 750 kcmil Cu ONLY (5) 3/0 – 750 kcmil Al/Cu GTB20CWCH
2500 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(7) 500 kcmil Cu ONLY (8) 4/0 – 500 kcmil Al/Cu GTB25CXCJ
(7) 500 kcmil Cu ONLY (7) 3/0 – 750 kcmil Al/Cu GTB25CXCK
(6) 600 kcmil Cu ONLY (8) 4/0 – 500 kcmil Al/Cu GTB25CYCJ
(6) 600 kcmil Cu ONLY (7) 3/0 – 750 kcmil Al/Cu GTB25CYCK
(6) 750 kcmil Cu ONLY (8) 4/0 – 500 kcmil Al/Cu GTB25CZCJ
(6) 750 kcmil Cu ONLY (7) 3/0 – 750 kcmil Al/Cu GTB25CZCK
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . CE9
8/2/2019 TK13301
http://slidepdf.com/reader/full/tk13301 19/24
February 2007
CA08101001E For more information visit: www.eaton.com
15SwitchboardsRoll-up Generator Termination Box
Technical Data
Table 15-23. Roll-up Generator Termination Box with Line 2-Hole Compression Lugs; Load 2-Hole Compression Lugs
Note: Line and load side factory installed Burndy, 2-hole, short barrel compression lugs suitable for COPPER WIRE ONLY.
Note: Requires 45-inch (1143.0 mm) wide enclosure.
AmpereRating
Dimensions in Inches (mm)H x W x D
2-Hole Compression LineTermination Cu ONLYWire Size
2-Hole Compression LoadTermination Cu ONLYWire Size
CatalogNumber
PriceU.S. $
800 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(3) 350 kcmil Cu ONLY (3) 350 kcmil Cu ONLY GTB08CLCL
(3) 350 kcmil Cu ONLY (3) 400 kcmil Cu ONLY GTB08CLCM
(3) 400 kcmil Cu ONLY (3) 350 kcmil Cu ONLY GTB08CMCL
(3) 400 kcmil Cu ONLY (3) 400 kcmil Cu ONLY GTB08CMCM
1200 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(4) 500 kcmil Cu ONLY (4) 500 kcmil Cu ONLY GTB12CNCN
(4) 500 kcmil Cu ONLY (3) 600 kcmil Cu ONLY GTB12CNCP
(4) 500 kcmil Cu ONLY (3) 750 kcmil Cu ONLY GTB12CNCQ
(3) 600 kcmil Cu ONLY (4) 500 kcmil Cu ONLY GTB12CPCN
(3) 600 kcmil Cu ONLY (3) 600 kcmil Cu ONLY GTB12CPCP
(3) 600 kcmil Cu ONLY (3) 750 kcmil Cu ONLY GTB12CPCQ
(3) 750 kcmil Cu ONLY (4) 500 kcmil Cu ONLY GTB12CQCN
(3) 750 kcmil Cu ONLY (3) 600 kcmil Cu ONLY GTB12CQCP
(3) 750 kcmil Cu ONLY (3) 750 kcmil Cu ONLY GTB12CQCQ
1600 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(5) 500 kcmil Cu ONLY (5) 500 kcmil Cu ONLY GTB16CRCR
(5) 500 kcmil Cu ONLY (4) 600 kcmil Cu ONLY GTB16CRCS
(5) 500 kcmil Cu ONLY (4) 750 kcmil Cu ONLY GTB16CRCT
(4) 600 kcmil Cu ONLY (5) 500 kcmil Cu ONLY GTB16CSCR
(4) 600 kcmil Cu ONLY (4) 600 kcmil Cu ONLY GTB16CSCS
(4) 600 kcmil Cu ONLY (4) 750 kcmil Cu ONLY GTB16CSCT
(4) 750 kcmil Cu ONLY (5) 500 kcmil Cu ONLY GTB16CTCR
(4) 750 kcmil Cu ONLY (4) 600 kcmil Cu ONLY GTB16CTCS
(4) 750 kcmil Cu ONLY (4) 750 kcmil Cu ONLY GTB16CTCT
2000 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(6) 500 kcmil Cu ONLY (6) 500 kcmil Cu ONLY GTB20CuCu
(6) 500 kcmil Cu ONLY (5) 600 kcmil Cu ONLY GTB20CuCV
(6) 500 kcmil Cu ONLY (5) 750 kcmil Cu ONLY GTB20CuCW
(5) 600 kcmil Cu ONLY (6) 500 kcmil Cu ONLY GTB20CVCu
(5) 600 kcmil Cu ONLY (5) 600 kcmil Cu ONLY GTB20CVCu
(5) 600 kcmil Cu ONLY (5) 750 kcmil Cu ONLY GTB20CVCW
(5) 750 kcmil Cu ONLY (6) 500 kcmil Cu ONLY GTB20CWCu
(5) 750 kcmil Cu ONLY (5) 600 kcmil Cu ONLY GTB20CWCV
(5) 750 kcmil Cu ONLY (5) 750 kcmil Cu ONLY GTB20CWCW
2500 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(7) 500 kcmil Cu ONLY (7) 500 kcmil Cu ONLY GTB25CXCX
(7) 500 kcmil Cu ONLY (6) 600 kcmil Cu ONLY GTB25CXCY
(7) 500 kcmil Cu ONLY (6) 750 kcmil Cu ONLY GTB25CXCZ
(6) 600 kcmil Cu ONLY (7) 500 kcmil Cu ONLY GTB25CYCX
(6) 600 kcmil Cu ONLY (6) 600 kcmil Cu ONLY GTB25CYCY
(6) 600 kcmil Cu ONLY (6) 750 kcmil Cu ONLY GTB25CYCZ
(6) 750 kcmil Cu ONLY (7) 500 kcmil Cu ONLY GTB25CZCX
(6) 750 kcmil Cu ONLY (6) 600 kcmil Cu ONLY GTB25CZCY
(6) 750 kcmil Cu ONLY (6) 750 kcmil Cu ONLY GTB25CZCZ
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . CE9
8/2/2019 TK13301
http://slidepdf.com/reader/full/tk13301 20/24
February 2007
5-20
For more information visit: www.eaton.com CA08101001E
Switchboards
5
Roll-up Generator Termination Box
Technical Data
Table 15-24. Roll-up Generator Termination Box with Line 2-Hole Compression Lugs; Load PROVISIONS ONLY 1-Hole Compression Lugs
Note: Line side factory installed Burndy, 2-hole, short barrel compression lugs suitable for COPPER WIRE ONLY.
Note: Load side factory installed 3/8" bolt provisions for 1-hole compression lugs (lugs furnished by others).
Note: Requires 45-inch (1143.0 mm) wide enclosure.
Table 15-25. Roll-up Generator Termination Box with 2-Hole Compression Lugs; Load PROVISIONS ONLY 2-Hole Compression Lugs
Note: Line side factory installed Burndy, 2-hole, short barrel compression lugs suitable for COPPER WIRE ONLY.
Note: Load side factory installed 1/2" bolt provisions on 1 3/4" hole centers for 2-hole compression lugs (lugs furnished by others).
Note: Requires 45-inch (1143.0 mm) wide enclosure.
Table 15-26. Roll-up Generator Termination Box with Line 1-Hole Compression Lug PROVISIONS; Load Mechanical Box Lugs
Note: Line side factory installed 3/8" bolt provisions for 1-hole compression lugs (lugs furnished by others).
Note: Load side mechanical lugs are factory selected and installed.
AmpereRating
Dimensions in Inches (mm)H x W x D
2-Hole Compression LineTermination Cu ONLY Wire Size
1-Hole Compression Load ProvisionsONLY Number and Range
CatalogNumber
PriceU.S. $
800 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(3) 350 kcmil Cu ONLY (3) Provisions Per Phase GTB08CLP1
(3) 400 kcmil Cu ONLY (3) Provisions Per Phase GTB08CMP1
1200 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(4) 500 kcmil Cu ONLY (4) Provisions Per Phase GTB12CNP2
(3) 600 kcmil Cu ONLY (4) Provisions Per Phase GTB12CPP2
(3) 750 kcmil Cu ONLY (4) Provisions Per Phase GTB12CQP2
2000 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(6) 500 kcmil Cu ONLY (6) Provisions Per Phase GTB20CuP4
(5) 600 kcmil Cu ONLY (6) Provisions Per Phase GTB20CVP4
(5) 750 kcmil Cu ONLY (6) Provisions Per Phase GTB20CWP4
2500 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(7) 500 kcmil Cu ONLY (8) Provisions Per Phase GTB25CXP5
(6) 600 kcmil Cu ONLY (8) Provisions Per Phase GTB25CYP6
(6) 750 kcmil Cu ONLY (8) Provisions Per Phase GTB25CZP6
AmpereRating
Dimensions in Inches (mm)H x W x D
2-Hole Compression LineTermination Cu ONLY Wire Size
2-Hole Compression Load ProvisionsONLY Number and Range
CatalogNumber
PriceU.S. $
800 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(3) 350 kcmil Cu ONLY (3) Provisions Per Phase GTB08CLPA
(3) 400 kcmil Cu ONLY (3) Provisions Per Phase GTB08CMPA
1200 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(4) 500 kcmil Cu ONLY (4) Provisions Per Phase GTB12CNPB
(3) 600 kcmil Cu ONLY (4) Provisions Per Phase GTB12CPPB
(3) 750 kcmil Cu ONLY (4) Provisions Per Phase GTB12CQPB
1600 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(5) 500 kcmil Cu ONLY (5) Provisions Per Phase GTB16CRPC
(4) 600 kcmil Cu ONLY (5) Provisions Per Phase GTB16CSPC
(4) 750 kcmil Cu ONLY (5) Provisions Per Phase GTB16CTPC
2000 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(6) 500 kcmil Cu ONLY (6) Provisions Per Phase GTB20CuPD
(5) 600 kcmil Cu ONLY (6) Provisions Per Phase GTB20CVPD
(5) 750 kcmil Cu ONLY (6) Provisions Per Phase GTB20CWPD
2500 78.00 x 45.00 x 24.00
(1981.2 x 1143.0 x 609.6)
(7) 500 kcmil Cu ONLY (8) Provisions Per Phase GTB25CXPE
(6) 600 kcmil Cu ONLY (8) Provisions Per Phase GTB25CYPE
(6) 750 kcmil Cu ONLY (8) Provisions Per Phase GTB25CZPE
AmpereRating
Dimensions in Inches (mm)H x W x D
1-Hole Compression Line ProvisionsONLY Number and Range
Mechanical Box Lugs LoadTermination Number, Range and Type
CatalogNumber
PriceU.S. $
800 78.00 x 36.00 x 24.00(1981.2 x 914.4 x 609.6)
(3) Provisions Per Phase (3) 4/0 – 500 kcmil Al/Cu GTB08P1MA
(3) Provisions Per Phase (2) 3/0 – 750 kcmil Al/Cu GTB08P1MB
1200 78.00 x 36.00 x 24.00(1981.2 x 914.4 x 609.6)
(4) Provisions Per Phase (4) 4/0 – 500 kcmil Al/Cu GTB12P2MC
(4) Provisions Per Phase (3) 3/0 – 750 kcmil Al/Cu GTB12P2MD
1600 78.00 x 36.00 x 24.00(1981.2 x 914.4 x 609.6) (5) Provisions Per Phase (5) 4/0 – 500 kcmil Al/Cu GTB16P3ME(5) Provisions Per Phase (4) 3/0 – 750 kcmil Al/Cu GTB16P3MF
2000 78.00 x 36.00 x 24.00(1981.2 x 914.4 x 609.6)
(6) Provisions Per Phase (6) 4/0 – 500 kcmil Al/Cu GTB20P4MG
(6) Provisions Per Phase (5) 3/0 – 750 kcmil Al/Cu GTB20P4MH
2500 78.00 x 36.00 x 24.00(1981.2 x 914.4 x 609.6)
(8) Provisions Per Phase (8) 4/0 – 500 kcmil Al/Cu GTB25P5MJ
(8) Provisions Per Phase (7) 3/0 – 750 kcmil Al/Cu GTB25P5MK
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . CE9
8/2/2019 TK13301
http://slidepdf.com/reader/full/tk13301 21/24
February 2007
CA08101001E For more information visit: www.eaton.com
15SwitchboardsRoll-up Generator Termination Box
Technical Data
Table 15-27. Roll-up Generator Termination Box with Line 1-Hole Compression Lug PROVISIONS; Load 1-Hole Compression Lugs
Note: Line side factory installed 3/8" bolt provisions for 1-hole compression lugs (lugs furnished by others).
Note: Load side Anderson, 1-hole compression lugs are factory selected and installed.
Table 15-28. Roll-up Generator Termination Box with Line 1-Hole Compression Lug PROVISIONS; Load 2-Hole Compression Lugs
Note: Line side factory installed 3/8" bolt provisions for 1-hole compression lugs (lugs furnished by others).
Note: Load side factory installed Burndy, 2-hole, short barrel compression lugs suitable for COPPER WIRE ONLY.
Note: Requires 45-inch (1143.0 mm) wide enclosure.
Table 15-29. Roll-up Generator Termination Box with Line 1-Hole Compression Lug PROVISIONS; Load 1-Hole Compression Lugs
Note: Line and load side factory installed 3/8" bolt provisions for 1-hole compression lugs (lugs furnished by others).
AmpereRating
Dimensions in Inches (mm)H x W x D
1-Hole Compression Line ProvisionsOnly Number and Range
1-Hole Compression Load TerminationNumber, Range and Type
CatalogNumber
PriceU.S. $
800 78.00 x 36.00 x 24.00(1981.2 x 914.4 x 609.6)
(3) Provisions Per Phase (3) 4/0 – 500 kcmil Al/Cu GTB08P1CA
(3) Provisions Per Phase (2) 3/0 – 750 kcmil Al/Cu GTB08P1CB
1200 78.00 x 36.00 x 24.00(1981.2 x 914.4 x 609.6)
(4) Provisions Per Phase (4) 4/0 – 500 kcmil Al/Cu GTB12P2CC
(4) Provisions Per Phase (3) 3/0 – 750 kcmil Al/Cu GTB12P2CD
1600 78.00 x 36.00 x 24.00(1981.2 x 914.4 x 609.6)
(5) Provisions Per Phase (5) 4/0 – 500 kcmil Al/Cu GTB16P3CE
(5) Provisions Per Phase (4) 3/0 – 750 kcmil Al/Cu GTB16P3CF
2000 78.00 x 36.00 x 24.00(1981.2 x 914.4 x 609.6)
(6) Provisions Per Phase (6) 4/0 – 500 kcmil Al/Cu GTB20P4CG
(6) Provisions Per Phase (5) 3/0 – 750 kcmil Al/Cu GTB20P4CH
2500 78.00 x 36.00 x 24.00(1981.2 x 914.4 x 609.6)
(8) Provisions Per Phase (8) 4/0 – 500 kcmil Al/Cu GTB25P5CJ
(8) Provisions Per Phase (7) 3/0 – 750 kcmil Al/Cu GTB25P5CK
AmpereRating
Dimensions in Inches (mm)H x W x D
1-Hole Compression Line ProvisionsONLY Number and Range
2-Hole Compression Load TerminationCu ONLY Wire Size
CatalogNumber
PriceU.S. $
800 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(3) 4/0 – 500 kcmil (3) 350 kcmil Cu ONLY GTB08P1CL
(3) 4/0 – 500 kcmil (3) 400 kcmil Cu ONLY GTB08P1CM
1200 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(4) 4/0 – 500 kcmil (4) 500 kcmil Cu ONLY GTB12P2CN
(4) 4/0 – 500 kcmil (3) 600 kcmil Cu ONLY GTB12P2CP
(4) 4/0 – 500 kcmil (3) 750 kcmil Cu ONLY GTB12P2CQ
1600 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(5) 4/0 – 500 kcmil (5) 500 kcmil Cu ONLY GTB16P3CR
(5) 4/0 – 500 kcmil (4) 600 kcmil Cu ONLY GTB16P3CS
(5) 4/0 – 500 kcmil (4) 750 kcmil Cu ONLY GTB16P3CT
2000 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(6) 4/0 – 500 kcmil (6) 500 kcmil Cu ONLY GTB20P4Cu
(6) 4/0 – 500 kcmil (5) 600 kcmil Cu ONLY GTB20P4Cu
(6) 4/0 – 500 kcmil (5) 750 kcmil Cu ONLY GTB20P4CW
2500 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(8) 4/0 – 500 kcmil (7) 500 kcmil Cu ONLY GTB25P5CX
(8) 4/0 – 500 kcmil (6) 600 kcmil Cu ONLY GTB25P5CY
(8) 4/0 – 500 kcmil (6) 750 kcmil Cu ONLY GTB25P5CZ
AmpereRating
Dimensions in Inches (mm)H x W x D
1-Hole Compression Line ProvisionsOnly Number and Range
1-Hole Compression Load ProvisionsOnly Number and Range
CatalogNumber
PriceU.S. $
800 78.00 x 36.00 x 24.00(1981.2 x 914.4 x 609.6)
(3) Provisions Per Phase (3) Provisions Per Phase GTB08P1P1
1200 78.00 x 36.00 x 24.00(1981.2 x 914.4 x 609.6)
(4) Provisions Per Phase (4) Provisions Per Phase GTB12P2P2
1600 78.00 x 36.00 x 24.00.(1981.2 x 914.4 x 609.6)
(5) Provisions Per Phase (5) Provisions Per Phase GTB16P3P3
2000 78.00 x 36.00 x 24.00(1981.2 x 914.4 x 609.6)
(6) Provisions Per Phase (6) Provisions Per Phase GTB20P4P4
2500 78.00 x 36.00 x 24.00(1981.2 x 914.4 x 609.6)
(8) Provisions Per Phase (8) Provisions Per Phase GTB25P5P5
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . . CE9
8/2/2019 TK13301
http://slidepdf.com/reader/full/tk13301 22/24
February 2007
5-22
For more information visit: www.eaton.com CA08101001E
Switchboards
5
Roll-up Generator Termination Box
Technical Data
Table 15-30. Roll-up Generator Termination Box with Line 1-Hole Compression Lug PROVISIONS; Load PROVISIONS ONLY 2-Hole Compression Lugs
Note: Line side factory installed 3/8" bolt provisions for 1-hole compression lugs (lugs furnished by others).
Note: Load side factory installed 1/2" bolt provisions on 1 3/4" hole centers for 2-hole compression lugs (lugs furnished by others).
Note: Requires 45-inch (1143.0 mm) wide enclosure.
Table 15-31. Roll-up Generator Termination Box with Line 1-Hole Compression Lug PROVISIONS; Load Mechanical Box Lugs
Note: Line side factory installed 1/2" bolt provisions on 1 3/4" hole centers for 2-hole compression lugs (lugs furnished by others).
Note: Load side mechanical lugs are factory selected and installed.
Note: Requires 45-inch (1143.0 mm) wide enclosure.
Table 15-32. Roll-up Generator Termination Box with Line 2-Hole Compression Lug PROVISIONS; Load 1-Hole Compression Lugs
Note: Line side factory installed 1/2" bolt provisions on 1 3/4" hole centers for 2-hole compression lugs (lugs furnished by others).Note: Load side Anderson, 1-hole compression lugs are factory selected and installed.
Note: Requires 45-inch (1143.0 mm) wide enclosure.
AmpereRating
Dimensions in Inches (mm)H x W x D
1-Hole Compression Line ProvisionsONLY Number and Range
2-Hole Compression Load ProvisionsONLY Number and Range
CatalogNumber
PriceU.S. $
800 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(3) Provisions Per Phase (3) Provisions Per Phase GTB08P1PA
1200 78.00 x 45.00 x 24.00
(1981.2 x 1143.0 x 609.6)
(4) Provisions Per Phase (4) Provisions Per Phase GTB12P2PB
1600 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(5) Provisions Per Phase (5) Provisions Per Phase GTB16P3PC
2000 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(6) Provisions Per Phase (6) Provisions Per Phase GTB20P4PD
2500 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(8) Provisions Per Phase (8) Provisions Per Phase GTB25P5PE
AmpereRating
Dimensions in Inches (mm)H x W x D
2-Hole Compression Line ProvisionsONLY Number and Range
Mechanical Box Lugs LoadTermination Number, Range and Type
CatalogNumber
PriceU.S. $
800 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6) (3) Provisions Per Phase (3) 4/0 – 500 kcmil GTB08PAMA(3) Provisions Per Phase (2) 3/0 – 750 kcmil GTB08PAMB
1200 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(4) Provisions Per Phase (4) 4/0 – 500 kcmil GTB12PBMC
(4) Provisions Per Phase (3) 3/0 – 750 kcmil GTB12PBMD
1600 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(5) Provisions Per Phase (5) 4/0 – 500 kcmil GTB16PCME
(5) Provisions Per Phase (4) 3/0 – 750 kcmil GTB16PCMF
2000 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(6) Provisions Per Phase (6) 4/0 – 500 kcmil GTB20PDMG
(6) Provisions Per Phase (5) 3/0 – 750 kcmil GTB20PDMH
2500 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(8) Provisions Per Phase (8) 4/0 – 500 kcmil GTB25PEMJ
(8) Provisions Per Phase (7) 3/0 – 750 kcmil GTB25PEMK
AmpereRating
Dimensions in Inches (mm)H x W x D
2-Hole Compression Line ProvisionsONLY Number and Range
1-Hole Compression LoadTermination Number, Range and Type
CatalogNumber
PriceU.S. $
800 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(3) Provisions Per Phase (3) 4/0 – 500 kcmil Al/Cu GTB08PACA
(3) Provisions Per Phase (2) 3/0 – 750 kcmil Al/Cu GTB08PACB
1200 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(4) Provisions Per Phase (4) 4/0 – 500 kcmil Al/Cu GTB12PBCC
(4) Provisions Per Phase (3) 3/0 – 750 kcmil Al/Cu GTB12PBCD
1600 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(5) Provisions Per Phase (5) 4/0 – 500 kcmil Al/Cu GTB16PCCE
(5) Provisions Per Phase (4) 3/0 – 750 kcmil Al/Cu GTB16PCCF
2000 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(6) Provisions Per Phase (6) 4/0 – 500 kcmil Al/Cu GTB20PDCG
(6) Provisions Per Phase (5) 3/0 – 750 kcmil Al/Cu GTB20PDCH
2500 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(8) Provisions Per Phase (8) 4/0 – 500 kcmil Al/Cu GTB25PECJ
(8) Provisions Per Phase (7) 3/0 – 750 kcmil Al/Cu GTB25PECK
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . CE9
8/2/2019 TK13301
http://slidepdf.com/reader/full/tk13301 23/24
February 2007
CA08101001E For more information visit: www.eaton.com
15SwitchboardsRoll-up Generator Termination Box
Technical Data
Table 15-33. Roll-up Generator Termination Box with Line 2-Hole Compression Lug PROVISIONS; Load 2-Hole Compression Lugs
Note: Line side factory installed 1/2" bolt provisions on 1 3/4" hole centers for 2-hole compression lugs (lugs furnished by others).
Note: Load side factory installed Burndy, 2-hole, short barrel compression lugs suitable for COPPER WIRE ONLY.
Note: Requires 45-inch (1143.0 mm) wide enclosure.
Table 15-34. Roll-up Generator Termination Box with Line 2-Hole Compression Lug PROVISIONS; Load 1-Hole Compression Lugs
Note: Line side factory installed 1/2" bolt provisions on 1 3/4" hole centers for 2-hole compression lugs (lugs furnished by others).
Note: Load side factory installed 3/8" bolt provisions for 1-hole compression lugs (lugs furnished by others).
Note: Requires 45-inch (1143.0 mm) wide enclosure.
Table 15-35. Roll-up Generator Termination Box with Line 2-Hole Compression Lug PROVISIONS; Load 2-Hole Compression Lugs PROVISIONS
Note: Line and load side factory installed 1/2" bolt provisions on 1 3/4" hole centers for 2-hole compression lugs (lugs furnished by others).
Note: Requires 45-inch (1143.0 mm) wide enclosure.
UL is a federally registered trademark of UnderwritersLaboratories Inc. NEMA is the registered trademarkand service mark of the National Electrical Manufactur-ers Association. National Electrical Code and NEC areregistered trademarks of the National Fire ProtectionAssociation, Quincy, Mass. Uniform Building Code(UBC) is a trademark of the International Conference ofBuilding Officials (ICBO). Cutler-Hammer is a federallyregistered trademark of Eaton Corporation.
AmpereRating
Dimensions in Inches (mm)H x W x D
2-Hole Compression Line ProvisionsONLY Number and Range
2-Hole Compression LoadTermination Cu ONLY Wire Size
CatalogNumber
PriceU.S. $
800 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(3) Provisions Per Phase (3) 350 kcmil Cu ONLY GTB08PACL
(3) Provisions Per Phase (3) 400 kcmil Cu ONLY GTB08PACM
1200 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(4) Provisions Per Phase (4) 500 kcmil Cu ONLY GTB12PBCN
(4) Provisions Per Phase (3) 600 kcmil Cu ONLY GTB12PBCP
(4) Provisions Per Phase (3) 750 kcmil Cu ONLY GTB12PBCQ
1600 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(5) Provisions Per Phase (5) 500 kcmil Cu ONLY GTB16PCCR
(5) Provisions Per Phase (4) 600 kcmil Cu ONLY GTB16PCCS
(5) Provisions Per Phase (4) 750 kcmil Cu ONLY GTB16PCCT
2000 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(6) Provisions Per Phase (6) 500 kcmil Cu ONLY GTB20PDCu
(6) Provisions Per Phase (5) 600 kcmil Cu ONLY GTB20PDCu
(6) Provisions Per Phase (5) 750 kcmil Cu ONLY GTB20PDCW
2500 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(8) Provisions Per Phase (7) 500 kcmil Cu ONLY GTB25PECX
(8) Provisions Per Phase (6) 600 kcmil Cu ONLY GTB25PECY
(8) Provisions Per Phase (6) 750 kcmil Cu ONLY GTB25PECZ
AmpereRating
Dimensions in Inches (mm)H x W x D
2-Hole Compression Line ProvisionsONLY Number and Range
1-Hole Compression Load ProvisionsOnly Number and Range
CatalogNumber
PriceU.S. $
800 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(3) Provisions Per Phase (3) Provisions Per Phase GTB08PAP1
1200 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(4) Provisions Per Phase (4) Provisions Per Phase GTB12PBP2
1600 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(5) Provisions Per Phase (5) Provisions Per Phase GTB16PCP3
2000 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(6) Provisions Per Phase (6) Provisions Per Phase GTB20PDP4
2500 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(8) Provisions Per Phase (8) Provisions Per Phase GTB25PEP5
AmpereRating
Dimensions in Inches (mm)H x W x D
2-Hole Compression Line ProvisionsONLY Number and Range
2-Hole Compression Load ProvisionsONLY Number and Range
CatalogNumber
PriceU.S. $
800 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(3) Provisions Per Phase (3) Provisions Per Phase GTB08PAPA
1200 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(4) Provisions Per Phase (4) Provisions Per Phase GTB12PBPB
1600 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(5) Provisions Per Phase (5) Provisions Per Phase GTB16PCPC
2000 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(6) Provisions Per Phase (6) Provisions Per Phase GTB20PDPD
2500 78.00 x 45.00 x 24.00(1981.2 x 1143.0 x 609.6)
(8) Provisions Per Phase (8) Provisions Per Phase GTB25PEPE
Discount Symbol . . . . . . . . . . . . . . . . . . . . . . . . . . CE9