IM 05P03D21-11EN page 1/8
Contents1. Safety Precautions2. ModelandSuffixCodes3. How to Install4. HardwareSpecifications5. HowtoConnectWires6. TerminalWiringDiagrams
IntroductionThankyouforpurchasingtheUM33ADigitalIndicatorwithAlarms.ThisoperationguidedescribesthebasicoperationsoftheUM33A.Theguideshouldbeprovidedtotheenduserofthisproduct.Besure to read thisoperationguidebeforeusing theproduct inorder toensurecorrect operation. For details of each function, refer to the electronic manual. Before usingtheproduct,refertothetableofModelandSuffixCodestomakesurethatthedeliveredproduct isconsistentwith themodelandsuffixcodesyouordered.Alsomakesurethatthefollowingitemsareincludedinthepackage.
•DigitalIndicatorwithAlarms(themodelyouordered) ............................x1• Set of Brackets ........................................................................................x1•UnitLabel(L4502VZ) ..............................................................................x1•TagLabel(L4502VE)(Onlywhenordered.) ...........................................x1•OperationGuide(thisdocument) ............................................................x4(A3size)(InstallationandWiring,InitialSettings,Operations,andParameters)
lTargetReadersThisguideisintendedforthefollowingpersonnel;• Engineersresponsibleforinstallation,wiring,andmaintenanceoftheequipment.• Personnelresponsiblefornormaldailyoperationoftheequipment.
1. Safety PrecautionsThefollowingsymbol isusedonthe instrument. It indicatesthepossibilityof injuryto theuserordamageto the instrument,andsignifies that theusermustrefer totheuser’smanual forspecial instructions.Thesamesymbol isused in theuser’smanualonpagesthattheuserneedstoreferto,togetherwiththeterm“WARNING”or“CAUTION.”
WARNING
Calls attention to actions or conditions that could cause serious or fatal injury to the user, and indicates precautions that should be taken to prevent such occurrences.
CAUTION
Calls attention to actions or conditions that could cause injury to the user or damage to the instrument or property and indicates pre-cautions that should be taken to prevent such occurrences.
AC
AC/DC
Theequipmentwhollyprotectedbydoubleinsulationorreinforcedinsulation.
Functionalgroundingterminals (Donotusethisterminalasaprotectivegroundingterminal).
NoteIdentifiesimportantinformationrequiredtooperatetheinstrument.
Warning and Disclaimer(1)YOKOGAWAmakesnowarrantiesregardingtheproductexceptthosestatedin
theWARRANTYthatisprovidedseparately.(2)Theproductisprovidedonan"asis"basis.YOKOGAWAassumesnoliabilityto
anypersonorentity forany lossordamage,director indirect,arisingfromtheuseoftheproductorfromanyunpredictabledefectoftheproduct.
Safety,Protection,andModificationoftheProduct(1) Inordertoprotectthesystemcontrolledbythisproductandtheproductitself,andto
ensuresafeoperation,observethesafetyprecautionsdescribedintheuser’smanual.Useoftheinstrumentinamannernotprescribedhereinmaycompromisetheproduct'sfunctionsandtheprotectionfeaturesinherentinthedevice.Weassumenoliabilityforsafety,or responsibility for theproduct'squality,performanceor functionalityshouldusersfailtoobservetheseinstructionswhenoperatingtheproduct.
(2) Installationofprotectionand/orsafetycircuitswith respect toa lightningprotector;protectiveequipment for thesystemcontrolledbytheproductandtheproduct itself;foolproofor failsafedesignofaprocessor lineusing thesystemcontrolledby theproductortheproductitself;and/orthedesignandinstallationofotherprotectiveandsafetycircuitsaretobeappropriatelyimplementedasthecustomerdeemsnecessary.
(3)BesuretousethesparepartsapprovedbyYOKOGAWAwhenreplacingpartsorconsumables.
(4)Thisproduct isnotdesignedormanufacturedtobeusedincriticalapplicationsthatdirectlyaffector threatenhuman lives.Suchapplications includenuclearpower equipment, devices using radioactivity, railway facilities, aviationequipment,airnavigation facilities,aviation facilities,andmedicalequipment.If soused, it is theuser’s responsibility to include in thesystemadditionalequipmentanddevicesthatensurepersonnelsafety.
(5)Modificationoftheproductisstrictlyprohibited.(6)Thisproductisintendedtobehandledbyskilled/trainedpersonnelforelectricdevices.(7)This product isULRecognizedComponent. In order to complywithUL
standards,end-productsarenecessary tobedesignedby thosewhohaveknowledgeoftherequirements.
WARNING
lPower Supply Ensure that the instrument’s supply voltage matches the voltage
of the power supply before turning ON the power.l Do Not Use in an Explosive Atmosphere Do not operate the instrument in locations with combustible
or explosive gases or steam. Operation in such environments constitutes an extreme safety hazard. Use of the instrument in environments with high concentrations of corrosive gas (H2S, SOX, etc.) for extended periods of time may cause a failure.
l Do Not Remove Internal Unit The internal unit should not be removed by anyone other than
YOKOGAWA's service personnel. There are dangerous high voltage parts inside. Additionally, do not replace the fuse by yourself.
l Damage to the Protective Construction Operation of the instrument in a manner not specified in the
user’s manual may damage its protective construction.
CAUTION
This instrument is an EMC class A product. In a domestic environ-ment this product may cause radio interference in which case the user needs to take adequate measures.
2. ModelandSuffixCodes UM33A
Model SuffixcodeOptional suffixcode
Description
UM33ADigitalIndicatorwithAlarms(Powersupply:100-240VAC)(providedwithretransmissionoutputor15VDClooppowersupply,2DIs,and3DOs)
Type1:Basic
-0 Standard type
-SUM33ADigitalIndicatorwithAlarms(SENCOMHMIType)(pleaseseetheOperationGuideIM05P09D21-11EN.)
Type2:Functions
0 None
1 1additionalDO(c-contactrelay),RS-485communication(Max.38.4kbps,2-wire/4-wire)(*1)
2 1additionalDO(c-contactrelay)
3 6additionalDOs(c-contactrelay:1point,opencollector:5points)
Type3:Opennetworks
0 None3 CC-Linkcommunication(withModbusmasterfunction)(*2)
Displaylanguage(*3)
-1 English(Default.Canbeswitchedtootherlanguagebythesetting.)-2 German(Default.Canbeswitchedtootherlanguagebythesetting.)-3 French(Default.Canbeswitchedtootherlanguagebythesetting.)-4 Spanish(Default.Canbeswitchedtootherlanguagebythesetting.)
Casecolor0 White(Lightgray)1 Black(Lightcharcoalgray)
Optionalsuffixcodes
/LP 24VDClooppowersupply(*4)/DC Powersupply24VAC/DC/CT Coating(*5)/CV Terminalcover
*1: When/LPoptionisspecified,theRS-485communicationoftheType2code“1”is2-wiresystem.*2: Type3code“3”canbespecifiedonlywhentheType2codeis“0”or“2”.*3: English,German,French,andSpanishareavailablefortheguidedisplay.*4: The/LPoptioncanbespecifiedonlywhenthecodeforType2codeisanyof“0”,“1”or“2”,
andtheType3codeis“0”.*5: Whenthe/CToptionisspecified,theUM33Adoesnotconformtothesafetystandards(UL
andCSA)andCEmarking(Productswith/CToptionarenotintendedforcountrieswhichrequireCEmarking.).
Accessories (sold separately)Thefollowingisanaccessorysoldseparately.• LL50AParameterSettingSoftware
Model Suffixcode DescriptionLL50A -00 ParameterSettingSoftware
• ExternalPrecisionResistorModel Suffixcode Description
X010 SeetheGeneralSpecifications(GSX010-01EN)(*)
ResistanceModule
*:Necessarytoinputthecurrentsignaltothevoltageinputterminal.• TerminalCover ForUM33A:ModelUTAP002• User’sManual(A4size) Note:User’sManualcanbedownloadedfromawebsite.• Brackets Partnumber:L4502TP(2pcsforupperandlowersides)
• Areasclosetoflammablearticles Absolutelydonotplacetheinstrumentdirectlyonflam-mablesurfaces. Ifsuchacircumstance isunavoidableandtheinstrumentmustbeplacedclosetoaflammableitem,provideashieldforitmadeof1.43mmthickplatedsteel or 1.6 mm thick unplated steel with a space of at least150mmbetweenitandtheinstrumentonthetop,bottom,andsides.
• Areas subject to being splashed with water
WARNING
Be sure to turn OFF the power supply to the indicator before install-ing it on the panel to avoid an electric shock.
Mounting the Instrument Main UnitProvideaninstrumentedpanelsteelsheetof1to10mmthickness.Afteropeningthemountingholeonthepanel,followtheproceduresbelowtoinstalltheindicator:1) Insert the indicator into theopening from the frontof thepanelso that the
terminalboardontherearisatthefarside.2) Set thebrackets inplaceontherightand leftof the indicatorasshownin the
figurebelow,thentightenthescrewsofthebrackets.Takecarenottoovertightenthem.
Direction to insert theindicatorInsert the indicatorinto the opening atthe front of the panel.
Panel
Bracket(side mounting hardware)
Bracket(side mounting hardware)
Terminal boardInsert a screwdriver into thebrackets to tighten the screws.
Appropriatetightening torque:0.25 N•m
CAUTION
• Tighten the screws with appropriate tightening torque within 0.25 N•m. Otherwise it may cause the case deformation or the bracket damage.
• Make sure that foreign materials do not enter the inside of the instrument through the case’s slit holes.
External Dimensions and Panel Cutout DimensionsUM33A Unit: mm (approx. inch)
Normal tolerance: ±(value of JIS B 0401-1998 tolerance class IT18)/2
96 (3.78)
48 (1
.89)
Bracket
20 (
0.79
)65
(2.5
6)11
(0.4
3)
Terminal cover
Bracket
94.6 (3.72)91.6 (3.61)
105.2 (4.14)
1 to 10 (0.04 to 0.39)
(panel thickness)(25) (0.98)
(53)
(2.09)
• General mounting145 (5.71)min.
+0.030(3.62 )
+0.6045
+0.020(1.77 ) +0.8
092
70 (2.76) min.
150 mm150 mm
150 mm
150 mm
OperationGuideIM 05P03D21-11EN
UM33ADigital Indicator with AlarmsOperation Guide
This operation guide describes installation, wiring, and other tasks required to make the indicator ready for operation.
7th Edition : Dec. 2018
Installation and Wiring
For details of the each function, refer to the electronic manual. User's manuals can be downloaded or viewed at the following URL.
Functional
Enhancement
http://www.yokogawa.com/ns/ut/im/
www.yokogawa.com/ns
YOKOGAWA ELECTRIC CORPORATIONNetwork Solutions Business Division
2-9-32, Naka-cho Musashino-shi, Tokyo 180-8750 JAPANYOKOGAWA CORPORATION OF AMERICA
Head office and for product sales2 Dart Road, Newnan, Georgia 30265, USA
YOKOGAWA EUROPE B.V.Headquarters
Euroweg 2, 3825 HD Amersfoort, THE NETHERLANDS
All Rights Reserved, Copyright © 2010 Yokogawa Electric Corporation
Protection of Environment Waste Electrical and Electronic Equipment (WEEE), Directive
ThisisanexplanationofhowtodisposeofthisproductbasedonWasteElectricalandElectronicEquipment(WEEE),Directive.ThisdirectiveisonlyvalidintheEU.
MarkingThis product complieswith theWEEEDirectivemarkingrequirement.Thismarkingindicatesthatyoumustnotdiscardthis electrical/electronic product in domestic household waste.
ProductCategoryWithreferencetotheequipmenttypesintheWEEEdirective,thisproductisclassifiedasa“Smallequipment”product.Donotdispose indomestichouseholdwaste.Whendisposingproducts in theEU, contact your localYokogawaEuropeB.V.office.
3. How to Install Installation LocationThe instrument shouldbe installed in indoor locationsmeeting the followingconditions:• Instrumented panel This instrument isdesignedtobemounted inan instrumentedpanel.Mount theinstrumentinalocationwhereitsterminalswillnotinadvertentlybetouched.
• Well ventilated locations Mounttheinstrumentinwellventilatedlocationstopreventtheinstrument’sinter-naltemperaturefromrising.
However,makesurethattheterminalportionsarenotexposedtowind.Exposureto wind may cause the temperature sensor accuracy to deteriorate. To mount mul-tipleindicators,seetheexternaldimensions/panelcutoutdimensionswhichfollow.Ifmountingotherinstrumentsadjacenttotheinstrument,complywiththesepanelcut-outdimensionstoprovidesufficientclearancebetweentheinstruments.
• Locations with little mechanical vibration Installtheinstrumentinalocationsubjecttolittlemechanicalvibration.• Horizontal location Mounttheinstrumenthorizontallyandensurethatitislevel,withnoinclinationtotherightorleft.
Front panelof the indicator
30°
Keep this anglewithin 30°
NoteIf the instrument ismovedfroma locationwith lowtemperatureand lowhumiditytoaplacewithhightemperatureandhighhumidity,or if thetemperaturechangesrapidly,condensationwill result.Moreover, in thecaseof thermocouple inputs,measurementerrorswillresult.Toavoidsuchasituation,leavetheinstrumentinthenewenvironmentunderambientconditionsformorethan1hourpriortousingit.
Donotmounttheinstrumentinthefollowinglocations:• Outdoors• Locations subject to direct sunlight or close to a heater Installtheinstrumentinalocationwithstabletemperaturesthatremainclosetoanaveragetemperatureof23°C.Donotmountitinlocationssubjecttodirectsunlightorclosetoaheater.Doingsoadverselyaffectstheinstrument.
• Locations with substantial amounts of oily fumes, steam, moisture, dust, or corrosive gases
Thepresenceofoily fumes,steam,moisture,dust,orcorrosivegasesadverselyaffectstheinstrument.Donotmounttheinstrumentinlocationssubjecttoanyofthesesubstances.
• Areasnearelectromagneticfieldgeneratingsources Donotplacemagnetsortoolsthatgeneratemagnetismneartheinstrument.Iftheinstrument isusedin locationsclosetoastrongelectromagneticfieldgeneratingsource,themagneticfieldmaycausemeasurementerrors.
• Locationswherethedisplayisdifficulttosee The instrumentusesanLCDfor thedisplayunit,andthiscanbedifficult toseefromextremelyobliqueangles.Mounttheinstrumentinalocationwhereitcanbeseenasmuchaspossiblefromthefront.
CustomizedProduct Forcustomizedproduct,theproductisidentifiedbytheoptioncodeof/S#(where‘#’isanumber).
Contactyoursupplier incaseyour instrumenthasoption /S#,andyouarenotin thepossessionofFX1-[Modelcode]-S#or IM[Modelcode]-S#(where[Modelcode]means,forexample,UT55A).
![Page 2: ting the Instrument Main Unit Moun Contents · 3 CC-Linkcommunication(withModbusmasterfunction)(*2) Display language (*3)-1 English (Default. Can be switched to other language by](https://reader035.fdocuments.in/reader035/viewer/2022062415/5fbc320a628cf40c643da491/html5/thumbnails/2.jpg)
IM 05P03D21-11EN page 2/8
4. HardwareSpecifications
WARNING
This instrument is for Measurement Category No.1.Do not use it for measurements in locations falling under Measure-ment Categories No.2, No.3, and No.4.
Internal Wiring
Outlet
Entrance IVCable
III TO( I )
II
Category IEC/EN/CSA/UL 61010-1 EN 61010-2-030 Remarks
No.1 Measurement CategoryI O(Other) For measurements performed on circuits not direct-
lyconnectedtoMAINS.
No.2 Measurement CategoryII
Measurement CategoryII
For measurements performed on circuits directly connectedtothelow-voltageinstallation.
No.3 Measurement CategoryIII
Measurement CategoryIII
Formeasurementsperformedinthebuildinginstal-lation.
No.4 Measurement CategoryIV
Measurement CategoryIV
For measurements performed at the source of the low-voltageinstallation.
InputSpecifications
UniversalInput(Equippedasstandard)• Numberofinputs:1• Inputtype,instrumentrange,andmeasurementaccuracy:Seethetablebelow,
Input Type Instrument Range
AccuracyºC ºF
Thermo-couple
K-270.0to1370.0ºC -450.0to2500.0ºF ±0.1%ofinstrumentrange±1digitfor
0°Cormore ±0.2%ofinstrumentrange±1digitforlessthan0°C ±2%ofinstrumentrange±1digitforlessthan-200.0°CofthermocoupleK±1%ofinstrumentrange±1digitforlessthan-200.0°CofthermocoupleT
-270.0to1000.0ºC -450.0to2300.0ºF-200.0to500.0ºC -200.0to1000.0ºF
J -200.0to1200.0ºC -300.0to2300.0ºF
T-270.0to400.0ºC -450.0to750.0ºF
0.0to400.0ºC -200.0to750.0ºF
B 0.0to1800.0ºC 32to3300ºF
±0.15%ofinstrumentrange±1digitfor400°Cormore ±5%ofinstrumentrange±1digitforlessthan400°C
S 0.0to1700.0ºC 32to3100ºF±0.15%ofinstrumentrange±1digit
R 0.0to1700.0ºC 32to3100ºF
N -200.0to1300.0ºC -300.0to2400.0ºF±0.1%ofinstrumentrange±1digit±0.25%ofinstrumentrange±1digitforlessthan0°C
E -270.0to1000.0ºC -450.0to1800.0ºF ±0.1%ofinstrumentrange±1digitfor0°Cormore ±0.2%ofinstrumentrange±1digitforlessthan0°C ±1.5%ofinstrumentrange±1digitforlessthan-200.0°CofthermocoupleE.
L -200.0to900.0ºC -300.0to1600.0ºF
U-200.0to400.0ºC -300.0to750.0ºF
0.0to400.0ºC -200.0to1000.0ºF
W 0.0to2300.0ºC 32to4200ºF ±0.2%ofinstrumentrange±1digit(Note2)
Platinel 2 0.0to1390.0ºC 32.0to2500.0ºF ±0.1%ofinstrumentrange±1digit
PR20-40 0.0to1900.0ºC 32to3400ºF
±0.5%ofinstrumentrange±1digitfor800°Cormore Accuracyisnotguaranteedforlessthan800°C.
W97Re3-W75Re25 0.0to2000.0ºC 32to3600ºF ±0.2%ofinstrumentrange±1digit
RTD
JPt100-200.0to500.0ºC -300.0to1000.0ºF ±0.1%ofinstrumentrange±1digit
(Note1)-150.00to150.00ºC -200.0to300.0ºF ±0.1%ofinstrumentrange±1digit
Pt100-200.0to850.0ºC -300.0to1560.0ºF ±0.1%ofinstrumentrange±1digit
(Note1)-200.0to500.0ºC -300.0to1000.0ºF-150.00to150.00ºC -200.0to300.0ºF ±0.1%ofinstrumentrange±1digit
Standardsignal0.400to2.000V
±0.1%ofinstrumentrange±1digit
1.000to5.000V4.00to20.00mA
DCvoltage/current
0.000to2.000V0.00to10.00V0.00to20.00mA-10.00to20.00mV0.0to100.0mV
Theaccuracyisthatinthestandardoperatingconditions:23±2°C,55±10%RH,andpowerfrequencyat50/60Hz.
Note1: ±0.3°C±1digitintherangebetween0and100°C,±0.5°C±1digitintherange between-100and200°C.
Note2: W:W-5%Re/W-26%Re(HoskinsMfg.Co.).ASTME988
•Inputsamplingperiod:50,100,200ms•Burnoutdetection: FunctionsatTC,RTD,andstandardsignal. Upscale,downscale,andoffcanbespecified. Forstandardsignal,burnoutisdeterminedtohaveoccurredifitis0.1Vor0.4 mAorless.
•Inputbiascurrent:0.05µA(forTCorRTD)•Measuredcurrent(RTD):About0.16mA•Inputresistance: TCormVinput:1MΩormore Vinput:About1MΩ mAinput:About250Ω
•Allowablesignalsourceresistance: TCormVinput:250Ωorless Effectsofsignalsourceresistance:0.1µV/Ωorless DCvoltageinput:2kΩorless Effectsofsignalsourceresistance:About0.01%/100Ω• Allowablewiringresistance: RTDinput:Max.150Ω/wire(Theconductorresistancebetweenthethreewires shallbeequal.)
Wiringresistanceeffect:±0.1ºC/10Ω• Allowableinputvoltage/current: TC,mV,mAandRTDinput:±10VDC Vinput:±20VDC mAinput:±40mA• Noiserejectionratio: Normalmode:40dBormore(at50/60Hz) Commonmode:120dBormore(at50/60Hz) For100-240VAC, thepower frequencycanbesetmanually.Automatic detectionisalsoavailable.
For24VAC/DC,thepowerfrequencycanbesetmanually.• Referencejunctioncompensationerror: ±1.0ºC(15to35ºC) ±1.5ºC(-10to15ºCand35to50ºC)• Applicablestandards:JIS/IEC/DIN(ITS-90)forTCandRTD
ContactInputSpecifications• Numberofinputs:2points• Inputtype:No-voltagecontactinputortransistorcontactinput• Inputcontactrating:12VDC,10mAormore Useacontactwithaminimumon-currentof1mAormore.• ON/OFFdetection: No-voltagecontactinput: Contactresistanceof1kΩorlessisdeterminedas“ON”andcontact resistanceof50kΩormoreas“OFF.” Transistorcontactinput: Inputvoltageof2Vorlessisdeterminedas“ON”andleakagecurrentmust notexceed100µAwhen“OFF.”• Minimumstatusdetectionholdtime:Inputsamplingperiod+50ms• Use:Eventinput
RelayContactOutputSpecifications• Contacttypeandnumberofoutputs: Alarm-1to-3output:contactpoint1a;3points(commonisindependent) Alarm-4output:contactpoint1c;1point• Contactrating: Contactpoint1a(Alarm-1to-3output):240VAC,1Aor30VDC,1A(resistanceload) Contactpoint1c(Alarm-4output):250VAC,3Aor30VDC,3A(resistanceload)• Use:Alarmoutput,FAILoutput,etc.Note:Thealarmoutputshouldalwaysbeusedwithaloadof1mAormore.
TransistorContactOutputSpecifications• Numberofoutputs:SeethetableofModelandSuffixCodes.• Outputtype:Opencollector(SINKcurrent)• Outputcontactrating:Max.24VDC,50mA• Outputtimeresolution:Min.50ms• Use:Alarmoutput,FAILoutput,etc.
RetransmissionOutputSpecifications• Numberofoutputs:Retransmissionoutput;1,sharedwith15VDC looppower
supply• Currentoutput:4to20mADCor0to20mADC/loadresistanceof600Ωorless• Currentoutputaccuracy(conversionaccuracyfromPVdisplayonthesetscale):±0.1%ofspan(±5%ofspanfor1mAorless)
Theaccuracyisthatinthestandardoperatingconditions:23±2°C,55±10%RH, andpowerfrequencyat50/60Hz. This isnotconversionaccuracythroughinputandoutputbut theperformanceof
transmission output itself.
15VDCLoopPowerSupplySpecifications(Sharedwithretransmissionoutput.)• Powersupply:14.5to18.0VDC• Maximumsupplycurrent:About21mA(withshort-circuitcurrentlimitingcircuit)
StepResponseTimeSpecificationsWithin500ms(whentheinputsamplingperiodis50msor100ms)Within1s(whentheinputsamplingperiodis200ms)(63%ofanalogoutputresponsetimewhenastepchangeof10to90%ofinputspanisapplied)
24VDCLoopPowerSupplySpecifications• Use:Powerissuppliedtoa2-wiretransmitter.• Powersupply:21.6to28.0VDC• Ratedcurrent:4to20mADC• Maximumsupplycurrent:About30mA(withshort-circuitcurrentlimitingcircuit.)
SafetyandEMCStandards• Safety: CompliantwithIEC/EN61010-1(CE),IEC/EN61010-2-201(CE),IEC/EN61010-2-030(CE),approvedbyCAN/CSAC22.2No.61010-1(CSA),approvedbyUL61010-1.
Installationcategory:II Pollutiondegree:2 Measurementcategory:I(CATI)(UL,CSA) O(Other)(CE) Ratedmeasurementinputvoltage:Max.10VDC Ratedtransientovervoltage:1500V(*) *ThisisareferencesafetystandardvalueformeasurementcategoryIofCSA/UL61010-
1,andformeasurementcategoryOofIEC/EN61010-2-030.Thisvalueisnotnecessarilyaguaranteeofinstrumentperformance.
• EMCstandards: CompliantwithCEmarking EN61326-1ClassA,Table2, EN61326-2-3 *Theinstrumentcontinuestooperateatameasurementaccuracyofwithin±20%ofthe
rangeduringtesting. EN55011ClassA,Group1 EN61000-3-2ClassA EN61000-3-3 EMCRegulatoryArrangementinAustraliaandNewZealand(forallmodelinclud-
ingLL50A) EN55011ClassA,Group1• KCmarking: Electromagneticwave interferencepreventionstandard,electromagneticwave
protection standard compliance
Construction,Installation,andWiring• Dust-proofanddrip-proof:IP66(forfrontpanel)• Material:Polycarbonate(Flameretardancy:UL94V-0)• Casecolor:White(Lightgray)orBlack(Lightcharcoalgray)• Weight:0.5kgorless• Externaldimensions(mm):96(W)×48(H)×65(depthfromthepanelface) (Depthexcepttheprojectionontherearpanel)• Installation:Directpanelmounting;mountingbracket,oneeachforrightand leftmounting
• Panelcutoutdimensions(mm):92+0.8/0(W)×45+0.6/0(H)• Mountingattitude:Upto30degreesabovethehorizontal.Nodownwardtitlingallowed.• Wiring:M3screwterminalwithsquarewasher(forsignalwiringandpowerwiring)
PowerSupplySpecificationsandIsolation• Powersupply: Ratedvoltage:100-240VAC(+10%/-15%),50/60Hz 24VAC/DC(+10%/-15%)(for/DCoption)• Powerconsumption:15VA(DC:7VA,AC:11VAif/DCoptionisspecified)• Databackup:Nonvolatilememory• Powerholduptime:20ms(for100VACdrive)• Withstandingvoltage Betweenprimaryterminalsandsecondaryterminals:2300VACfor1minute(UL,CSA) Betweenprimaryterminalsandsecondaryterminals:3000VACfor1minute(CE) Betweenprimaryterminals:1500VACfor1minute Betweensecondaryterminals:500VACfor1minute (Primaryterminals:Power*andrelayoutputterminals;Secondaryterminals: AnalogI/Osignalterminals,contactinputterminals,communicationterminals andfunctionalgroundingterminals.)
*:Powerterminalsfor24VAC/DCmodelsarethesecondaryterminals.• Insulationresistance:Betweenpowersupplyterminalsandagroundingterminal20MΩormoreat500VDC
• Isolationspecifications
PV (universal ) input terminals
Alarm-1 relay (contact point a) output terminals
Alarm-2 relay (contact point a) output terminals
Alarm-3 relay (contact point a) output terminals
Contact input terminals (all)RS-485 communication terminals
24 V DC loop power supply terminals
Contact output (transistor) terminals
Retransmission (analog) output terminals(not isolated between the analog output terminals)
Internal
circuits
Power
supply
CC-Link communication terminals
The circuits divided by lines are insulated mutually.
Alarm-4 relay (contact point c) output terminals
EnvironmentalConditions
Normal Operating Conditions• Ambienttemperature:-10to50ºC IftheCC-Linkoptionisspecified,0to40°CforUM33A.• Ambienthumidity:20to90%RH(nocondensationallowed)• Magneticfield:400A/morless• Continuousvibrationat5to9Hz:Halfamplitudeof1.5mmorless,1oct/minfor90minuteseachinthethreeaxisdirections
Continuousvibrationat9to150Hz:4.9m/s2orless,1oct/minfor90minuteseachinthethreeaxisdirections
• Short-periodvibration:14.7m/s2, 15 seconds or less• Shock:98m/s2 or less, 11 ms• Altitude:2000morlessabovesealevel• Warm-uptime:30minutesormoreafterthepoweristurnedon• Startuptime:Within10seconds *: TheLCD(aliquidcrystaldisplay)isusedforadisplayportionofthisproduct.
TheLCDhasacharacteristicthatthedisplayactionbecomeslateatthelow temperature.
Transportation and Storage Conditions• Temperature:-25to70ºC• Temperaturechangerate:20ºC/horless• Humidity:5to95%RH(nocondensationallowed)
EffectsofOperatingConditions• Effectofambienttemperature: VoltageorTCinput:±1µV/ºCor±0.01%ofF.S./ºC,whicheverislarger Currentinput:±0.01%ofF.S./ºC RTDinput:±0.05ºC/ºC(ambienttemperature)orless Analogoutput:±0.02%ofF.S./ºCorless• Effectofpowersupplyvoltagefluctuation Analoginput:±0.05%ofF.S.orless Analogoutput:±0.05%ofF.S.orless (Eachwithinratedvoltagerange)
![Page 3: ting the Instrument Main Unit Moun Contents · 3 CC-Linkcommunication(withModbusmasterfunction)(*2) Display language (*3)-1 English (Default. Can be switched to other language by](https://reader035.fdocuments.in/reader035/viewer/2022062415/5fbc320a628cf40c643da491/html5/thumbnails/3.jpg)
IM 05P03D21-11EN page 3/8
5. How to Connect Wires
WARNING
• Wiring work must be carried out by a person with basic electrical knowledge and practical experience.
• Be sure to turn OFF the power supply to the indicator before wiring to avoid an electric shock. Use a tester or similar device to ensure that no power is being supplied to a cable to be connected.
• For the wiring cable, the temperature rating is 75 °C or more.• As a safety measure, always install a circuit breaker (an IEC
60947-compatible product, 5 A, 100 V or 220 V AC) in an easily accessible location near the instrument. Moreover, provide indication that the switch is a device for turning off the power to the instrument.
• Install the power cable keeping a distance of more than 1 cm from other signal wires.
• The power cable is required to meet the IEC standards concerned or the requirements of the area in which the instrument is being installed.
• Wiring should be installed to conform to NEC (National Electrical Code: ANSI/NFPA-70) or the wiring construction standards in countries or regions where wiring will be installed.
• Since the insulation provided to each relay output terminal is Functional insulation, provide Reinforced insulation to the external of the device as necessary. (Refer to the drawing below.)
This product
Functional insulation
A safety voltage circuit
A safety voltage circuit
This product
Reinforced insulation
Reinforced insulation
Functional insulation
A hazardous voltage circuit
A hazardous voltage circuit
A safety voltage circuit
A safety voltage circuit
This product
Reinforced insulation
Reinforced insulation
Functional insulation
A hazardous voltage circuit
A hazardous voltage circuit
A hazardous voltage circuit
A hazardous voltage circuit
CAUTION
• When connecting two or more crimp-on terminal lugs to the single terminal block, bend the crimp-on terminal lugs before tightening the screw.
• Note that the wiring of two or more crimp-on terminal lugs to the single high-voltage terminal of the power supply and relay, etc. does not comply with the safety standard.
CAUTION
• Provide electricity from a single-phase power supply. If the power is noisy, install an isolation transformer on the primary side, and use a line filter on the secondary side. When measures against noise are taken, do not install the primary and secondary power cables close to each other.
• If there is a risk of external lightning surges, use a lightning arrester etc.
• For TC input, use shielded compensating lead wires for wiring. For RTD input, use shielded wires that have low conductor resistance and cause no significant differences in resistance between the three wires.
• Since the alarm output relay has a life span (resistance load of 100,000 times), use the auxiliary relay to perform ON/OFF control.
• The use of inductance (L) loads such as auxiliary relays, motors and solenoid valves causes malfunction or relay failure; always insert a CR filter for use with alternating current or a diode for use with direct current, as a spark-removal surge suppression circuit, into the line in parallel with the load.
• After completing the wiring, the terminal cover is recommended to use for the instrument.
RecommendedCrimp-onTerminalLugs
(A)
(F)
(ød)
5.5 3.3
Recommendedtighteningtorque:0.6N·m Applicablewiresize:Powersupplywiring1.25mm2 or moreApplicable terminal lug Applicable wire size mm2 (AWG#) (φd) (A) (F)M3 0.25to1.65(22to16) 3.3 5.5 4.2
CableSpecificationsandRecommendedCablesPurpose Name and Manufacturer
Power supply, relay contact outputs 600VGradeheat-resistantPVCinsulatedwires,JISC3317(HIV),0.9to2.0mm2
Thermocouple Shieldedcompensatingleadwires,JISC1610Forthermocoupleinput(PVinputandremoteinputwithdirectinput),shieldedcompensatingleadwireofcross-sectionalarealessthanorequalto0.75mm2 is recommended. If the cross-sectionalareaiswide,thereferencejunctioncompensationerrormaybelarge.
RTD Shieldedwires(three/fourconductors),UL2482(HitachiCable)Othersignals(otherthancontactinput/output) Shielded wiresOthersignals(contactinput/output) UnshieldedwiresRS-485communication Shielded wiresCC-Linkcommunication DedicatedcableforCC-Link(Shieldedthree-wires)
Recommendedtighteningtorque:0.5to0.6N·m
DC Relay Wiring
R
External DC power supplyRelayUM33A
UM’s contact
Diode(Mount it directlyto the relay coilterminal (socket).)
Relay(Use one with a relay coil rating
less than the UM’s contact rating.)
AC Relay Wiring
UM33A
R
UM’s contact CR filter(Mount it directlyto the relay coilterminal (socket).)
External AC power supply
Relay(Use one with a relay coilrating less than the UM’s
contact rating.)
Transistor Output Wiring
power+ –
UMDO
LoadCOM
6. Terminal Wiring Diagrams
CAUTION
• Do not use an unassigned terminal as the relay terminal.• Do not use a 100-240 V AC power supply for the 24 V AC/DC
model; otherwise, the instrument will malfunction.
UM33A
301-312
201-212
101-112
212 211 210 208 207 204 203
112 111 110 109 106 105 104108 107 103
202 201
102 101
306 305 304 303 302 301312 311 310 309 308 307
E1-terminal area
PVPV input (Equippedas standard)
TC input
+
-
202
203
RTD input
A
B
b
201
202
203
Voltage (mV, V) input
+
-
202
203
Current (mA) input
+
- 203
204
Factory default: PV input type is undefined.
RETRetransmission output (Equipped as standard)Retransmission output
4-20 mA DC or0-20 mA DC
+
-
Default: 4-20 mA DC
Default: PV retransmission
Load resistance 600 Ω or less
207
208
15 V DC loop power supply
14.5-18.0 V DC(Max. 21 mA DC)
+
-
207
208
Can be used for 15 V DC loop power supply when not used for retransmission output.
ALM (Equipped as standard)Contact output
External contact output (relay)
AL3
AL2
AL1
Relay contact rating: 240 V AC, 1 A 30 V DC, 1 A (resistance load)
Alarm-3 output(PV high limit)
Alarm-2 output( PV low limit)
Alarm-1 outputPV high limit
Common
Common
Common
UM104
105
106
107
108
109
ALM4Contact output
Contact rating: 250 V AC, 3 A 30 V DC, 3 A (resistance load)
AL4
(24 V AC/DC power supply: Optional suffix code /DC)
Power supply
Allowable range: 100-240 V AC (+10%/-15%) (free voltage) 50/60 Hz shared
100-240 V AC power supply
N
L
110
111
112
24 V AC/DC power supply
-
+
110
111
112
N
L
+
24 V DC loop power supply
21.6-28.0 V DC(Max. 30 mA DC)
-
24 V DC loop power supply
(Suffix code: Type 2=0 or 2 and with optional suffix code /LP)
305
306
LPS24RS-485
SDB(+)
SDA(-)
RDB(+)
RDA(-)
SG
RS-485 communication
301
302
303
304
305
RS485(Suffix code: Type 2=1 and without optional suffix code /LP)
(Suffix code: Type 2=3)Contact outputExternal contact output
DO14
DO15
DO13
DO12
DO11
COMCommon
UM301
302
303
304
305
306
DO
Transistor contact rating: 24 V DC, 50 mA
The function of each contact output can be changed.
Alarm-6 output( PV low limit)
Alarm-5 output(PV high limit)
Alarm-8 output( PV low limit)
FAIL
Alarm-7 output(PV high limit)
DI (Equipped as standard)Contact input
Contact rating: 12 V DC, 10 mA or more
External contact input
DI2
DI1
COMCommon
DI2
DI1
COM
+5V
+5V
No-voltagecontact
Transistor contactUM UM
210
211
212
210
211
212
The function of each contact input can be changed.
DI1=ON: PV peak and bottom values reset
OFF → ON: Latch release
101
102
Relay contact output
103
NC
NO
COM
Alarm-4 output
( PV low limit)
AL4
CC-Link communication (with Modbus master)
(Suffix code: Type 3=3)FG: Flame ground
SLD: Shield
DG: TX/RX signal ground
DB: RX/TX signal - signal
DA: RX/TX signal + signal
CHK(red)(Lit: User profile error/Adress error, Unlit: Normal)
L ERR(red)(Lit: Communication failure(CRC error), Unlit: Normal)
L RUN(green)(Lit: Normal, Unlit: No carrier detected/Communication timeout)
Not used
301
302
303
304
305
306
307
308
309
RS-485
RSB(+)
RSA(-)
SG
310
311
312
DB
DA
110Ω
CC-LIf the UM is located at the end of a segment for the CC-Link communication wiring,terminating resistors are separately needed.These are to be prepared by users. (110 Ω: 1 pc.)
RS-485
RSB(+)
RSA(-)
SG
RS-485 communication/24 V DC loop power supply
+
24 V DC loop power supply
21.6-28.0 V DC(Max. 30 mA DC)
-
301
302
303
305
306
RS485/LPS24(Suffix code: Type 2=1 and with optional suffix code /LP)
(Suffix code: Type 2=1, 2 or 3)
![Page 4: ting the Instrument Main Unit Moun Contents · 3 CC-Linkcommunication(withModbusmasterfunction)(*2) Display language (*3)-1 English (Default. Can be switched to other language by](https://reader035.fdocuments.in/reader035/viewer/2022062415/5fbc320a628cf40c643da491/html5/thumbnails/4.jpg)
IM 05P03D21-11EN page 4/8
Intentionallyblank Intentionallyblank
![Page 5: ting the Instrument Main Unit Moun Contents · 3 CC-Linkcommunication(withModbusmasterfunction)(*2) Display language (*3)-1 English (Default. Can be switched to other language by](https://reader035.fdocuments.in/reader035/viewer/2022062415/5fbc320a628cf40c643da491/html5/thumbnails/5.jpg)
IM 05P03D21-11EN page 5/8
Contents1. NamesandFunctionsofDisplayParts2. QuickSettingFunction(SettingofInputandOutput)3. SettingAlarmType
1. Names and Functions of Display Parts
(1)
(2)
(3)(4)
(5)
(11)
(8)(6)(7)
(13)
(12)
(10)
(9)
No.infigure Name Description
(1) PVdisplay (whiteorred)
DisplaysPV.Displaysanerrorcodeifanerroroccurs.DisplaysthescrollingguideintheMenuDisplayandParameterSettingDisplaywhentheguidedisplayON/OFFissettoON.
(2) Groupdisplay(green) Displaysagroupnumber.(3) Symboldisplay(orange) Displaysaparametersymbol.(4) Datadisplay(orange) Displaysaparametersetpointandmenusymbol.
(5) Eventindicator (orange)
Litwhenthealarms1to8occur.Eventdisplaysotherthanalarmscanbesetbytheparameter.
(6) Keynavigationindica-tor(green)
LitorblinkswhentheUp/DownorLeft/Rightarrowkeyoperationispossible.
(7) Parameterdisplaylevelindicator(green)
Displaysthesettingconditionsoftheparameterdisplaylevelfunction.
Parameter display level EASY PROEasysettingmode Lit UnlitStandardsettingmode Unlit UnlitProfessionalsettingmode Unlit Lit
(8) Securityindicator(red) Litifapasswordisset.Thesetupparametersettingsarelocked.
No.infigure Name Description
(9) DISPkey
UsedtoswitchtheOperationDisplays.PressthekeyintheOperationDisplaytoswitchtheprovidedSELECTDisplays.PressthekeyintheMenuDisplayorParameterSettingDisplaytoreturntotheOperationDisplay.
(10) PARAkey
Holddownthekeyfor3secondstomovetotheOperationParameterSettingDisplay.HolddownthekeyandtheLeftarrowkeysimultaneouslyfor3secondstomovetotheSetupParameterSettingDisplay.PressthekeyintheParameterSettingDisplaytoreturntotheMenuDisplay.Pressthekeyoncetocanceltheparameterset-ting(setpointisblinking).
(11)SET/ENTERkeyUp/Down/Left/Rightarrow keys
SET/ENTERkeyPressthekeyintheMenuDisplaytomovetotheParameterSettingDisplayoftheMenu.PressthekeyintheParameterSettingDisplaytotransfertotheparametersettingmode(setpointisblinking),andtheparametercanbechanged.Pressthekeyduringparametersettingmodetoregisterthe setpoint.Up/Down/Left/RightarrowkeysPresstheLeft/RightarrowkeysintheMenuDisplaytoswitchtheDisplays.PresstheUp/DownarrowkeysintheParameterSettingDisplaytoswitchtheDisplays.PresstheUp/Downarrowkeysduringparametersettingmode(setpointisblinking)tochangeasetpoint.PresstheLeft/Rightarrowkeysduringparametersettingmode (setpointisblinking)tomovebetweendigitsaccordingtotheparameter.
(12) Light-loaderinterfaceItisthecommunicationinterfacefortheadaptercableusedwhensettingandstoringparametersfromaPC.TheLL50AParameterSettingSoftware(soldseparately)isrequired.
(13) Userfunctionkeys Fnkey.Theusercanassignafunctiontothekey.Thefunctionissetbytheparameter.
Note: Thecommunicationconnector(maintenanceport)forLL50AParameterSettingSoftwareison the side of the unit.
2. Quick Setting Function (Setting of Input and Output)TheQuicksettingfunctionisafunctiontoeasilysetthebasicfunctionoftheindicator.TurnontheindicatortostarttheQuicksettingfunction.Thisfunctionallowsyoutoeasilysettheinput,andquicklystartthealarmaction.Theitems(parameters)tobesetbyQuicksettingfunctionareasfollows.(1)Inputfunction(PVinputtype,range,scale(atvoltageinput),etc.)
Afterturningontheindicator,firstdecidewhetherornottousetheQuicksettingfunction.
Operation in Initial Display· PresstheSET/ENTERkeywhileYESisdisplayedtostarttheQuicksettingfunction.· IfyouchangeYEStoNOandpresstheSET/ENTERkey,OperationDisplaywillappearwithoutstartingtheQuicksettingfunction.
Operation for Setting· Toselecttheparametersettingdisplayedastheinitialvalue,presstheDownarrowkeytomovetothenextparameter.
· Tochangeandset theparametersetting,presstheSET/ENTERkeytostart thesetpointblinking.Theblinkingstateallowsyoutomakechanges(settingmode).UsetheUp/Down/Left/Rightarrowkeystochangethesetpoint.PresstheSET/EN-TERkeytoregisterthesetting.
MakingSettingsUsingQuickSettingFunctionExample: Setting to thermocouple type K (range of 0.0 to 500.00C).Forthedetailedprocedureandswitchingofdisplays,see"FlowofQuickSettingFunction"below.Fortheparameterstoset,seethenextpage.
(1)PresstheSET/ENTERkeywhileYESforQSM(Quicksettingmode)isdisplayed.(2)SetthePVinputtypeparameter(IN)toK1(-270.0to1370.00C).(3)SetthePVinputunitparameter(UNIT)toC(DegreeCelsius).(4)SetthemaximumvalueofPVinputrangeparameter(RH)to500.0.(5)SettheminimumvalueofPVinputrangeparameter(RL)to0.0.(6)Finally,EXITisdisplayed.ChangeNOtoYESandpresstheSET/ENTERkeyto
completethesetup.OperationDisplayappears.
FlowofQuickSettingFunctionInQuicksettingmode,theparameterguideappearsonPVdisplay.Thisguidecanbeturnedon/offwiththeFnkey.
8
1.
2.
3.
4.
5.
6.
8.
9.
10.
11.
7.
8
8
8
8
Power-on
Quick setting starts
The PV input type parameter (IN) is displayed.Initial value: OFF
OFF blinks.Blinking allows you to change the setting.
K1 is displayed.
K1 has been registered.
The last digit of the upper limit value blinks.
The parameter RH (maximum value of PV input range) has been changed to 500.0.
The setpoint for the parameter RH has been registered.
The PV input unit parameter (UNIT) is displayed.Initial value: C (Degree Celsius)
Select NO with the Down arrow key and press the SET/ENTER key.
Press the SET/ENTER key while YES is displayed to start the Quick setting.
[YES][NO]
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the Up arrow key.
Select NO to return to the Operation Display.
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key.
The upper limit value of the setting range is displayed for the parameter RH (maximum value of PV input range).
Change the setpoint using the Up/Down arrow keys to increase and decrease the value and the Left/Right arrow keys to move between digits.
Finally, EXIT is displayed.Press the SET/ENTER key to swtich to the setting mode.Change NO to YES and press the SET/ENTER key to complete the setup of the basic function.Operation Display appears.The Quick setting function continues in the NO state.
Operation Display
Displays the measured input value (PV).
Follow the same procedure to set RL.
OperationGuide
Initial Settings
UM33ADigital Indicator with AlarmsOperation Guide
This operation guide describes basic settings and operations of the UM33A.For details of each function, see User’s manual.The scrolling guide is displayed on PV display in the Parameter Setting Display.This guide can be turned on/off with the Fn key. For details of the each function, refer to the electronic manual. User's manuals can be downloaded or viewed at the following URL.
Functional
Enhancement
http://www.yokogawa.com/ns/ut/im/
3. Setting Alarm TypeThefollowingoperatingprocedureshowsanexampleofchangingthealarm-1type(factorydefault:PVhighlimitalarm)toPVlowlimitalarm(setpoint:02).
1.
2.
3.
4.
5.
6.
8
AL menu is displayed.
ALRM menu is displayed.
Show the Operation Display.
Hold down the key for 3 seconds.
Press the Right arrow key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
The parameter AL1 (alarm-1 type) is displayed.
The last digit of the setpoint blinks.
Change the setpoint using the Up/Down arrow keys to increase and decrease the value and the Left/Right arrow keys to move between digits.
The alarm-1 type setpoint 02 (PV low limit) is registered. After the setup is completed, press the DISP key once to return to the Operation Display.
To change the alarm type, change the last 2 digits of the 5-digit value.
Stand-by action and excitation are turned on or off by selecting 1 or 0. (See “ Setting Display of Alarm Type.”)
For the latch action, see User ’s Manual.
Symbol Stand-by actionEnergized/De-energizedLatch action
- -No alarm (00)
Alarm Action (De-energized)
PV high limit (01)
PV low limit (02)
PV velocity (29)
Fault diagnosis alarm (30)
FAIL (31)
Alarm Type (Alarm Setpoint) Alarm Action (Energized)
Hysteresis
Alarm setpoint PV
Closed (lit)
Open (unlit)
Alarm setpoint
Hysteresis
PV
Closed (lit)
Open (unlit)
Hysteresis
Alarm setpoint PV
Open (lit)
Closed (unlit)
Alarm setpoint
Hysteresis
PV
Open (lit)
Closed (unlit)
Burnout of PV input, ADC failure, RJC error.
For the factory default, the contact output is turned ON in normal operation, OFF at the time of FAIL. Alarm output: OFF
Note 1: “Open/closed” shows status of relay contact, and “lit/unlit” shows status of EV (event) lamp.
Setting Display of Alarm Type Stand-by Action
Energized (0) / De-energized (1)
Alarm typeWithout (0) or With (1) Stand-by action
Latch action (0/1/2/3/4)See User’s Manual.
PV low limit alarm setpoint
Treatedas normal
ºC
Power-on Time
The alarm output does not turn onin this region even if the PV valuleis below PV low limit alarm setpoint.
Normal Abnormal
The alarm outputturns on.
8
1.
2.
3.
4.
5.
6.
8.
9.
10.
11.
7.
8
8
8
8
Power-on
Quick setting starts
The PV input type parameter (IN) is displayed.Initial value: OFF
OFF blinks.Blinking allows you to change the setting.
K1 is displayed.
K1 has been registered.
The last digit of the upper limit value blinks.
The parameter RH (maximum value of PV input range) has been changed to 500.0.
The setpoint for the parameter RH has been registered.
The PV input unit parameter (UNIT) is displayed.Initial value: C (Degree Celsius)
Select NO with the Down arrow key and press the SET/ENTER key.
Press the SET/ENTER key while YES is displayed to start the Quick setting.
[YES][NO]
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the Up arrow key.
Select NO to return to the Operation Display.
Press the Down arrow key.
Press the Down arrow key.
Press the Down arrow key.
The upper limit value of the setting range is displayed for the parameter RH (maximum value of PV input range).
Change the setpoint using the Up/Down arrow keys to increase and decrease the value and the Left/Right arrow keys to move between digits.
Finally, EXIT is displayed.Press the SET/ENTER key to swtich to the setting mode.Change NO to YES and press the SET/ENTER key to complete the setup of the basic function.Operation Display appears.The Quick setting function continues in the NO state.
Operation Display
Displays the measured input value (PV).
Follow the same procedure to set RL.
ParameterstobesetInput Function
Parameter Symbol Name of Parameter Setting Range
IN PVinputtype
OFF:DisableK1:-270.0to1370.00C/-450.0to2500.0 0FK2:-270.0to1000.00C/-450.0to2300.0 0FK3:-200.0to500.00C/-200.0to1000.0 0FJ:-200.0to1200.00C/-300.0to2300.0 0FT1:-270.0to400.00C/-450.0to750.0 0FT2:0.0to400.00C/-200.0to750.0 0FB:0.0to1800.00C/32to3300 0FS:0.0to1700.00C/32to3100 0FR:0.0to1700.00C/32to3100 0FN:-200.0to1300.00C/-300.0to2400.0 0FE:-270.0to1000.00C/-450.0to1800.0 0FL:-200.0to900.00C/-300.0to1600.0 0FU1:-200.0to400.00C/-300.0to750.0 0FU2:0.0to400.00C/-200.0to1000.0 0FW:0.0to2300.00C/32to4200 0FPL2:0.0to1390.00C/32.0to2500.0 0FP2040:0.0to1900.00C/32to3400 0FWRE:0.0to2000.00C/32to3600 0FJPT1:-200.0to500.00C/-300.0to1000.0 0FJPT2:-150.00to150.000C/-200.0to300.0 0FPT1:-200.0to850.00C/-300.0to1560.0 0FPT2:-200.0to500.00C/-300.0to1000.0 0FPT3:-150.00to150.000C/-200.0to300.0 0F0.4-2V:0.400to2.000V1-5V:1.000to5.000V4-20:4.00to20.00mA0-2V:0.000to2.000V0-10V:0.00to10.00V0-20:0.00to20.00mA-1020:-10.00to20.00mV0-100:0.0to100.0mV
UNIT PVinputunit -:Nounit,C:DegreeCelsius-:Nounit,--:Nounit,---:Nounit,F:DegreeFahrenheit
RH MaximumvalueofPVinputrange
Dependsontheinputtype.- For temperature input -Setthetemperaturerangethatisactuallydisplayed.(RL<RH)-Forvoltage/currentinput-Settherangeofavoltage/currentsignalthatisapplied.Thescaleacrosswhichthevoltage/currentsignalisactuallydisplayedshouldbesetusingthemaximumvalueofinputscale(SH)andminimumvalueofinputscale(SL).(Inputisalways0%whenRL=RH.)
RL MinimumvalueofPVinputrange
SDPPVinputscaledecimal point position
0:Nodecimalplace1:Onedecimalplace2:Twodecimalplaces
3:Threedecimalplaces4:Fourdecimalplaces
SH MaximumvalueofPVinputscale
-19999to30000,(SL<SH),|SH-SL|≤30000SL Minimumvalueof
PVinputscale
Note1:SDP,SH,andSLaredisplayedonlyforvoltage/currentinput.Note2:W:W-5%Re/W-26%Re(HoskinsMfg.Co.),ASTME988
![Page 6: ting the Instrument Main Unit Moun Contents · 3 CC-Linkcommunication(withModbusmasterfunction)(*2) Display language (*3)-1 English (Default. Can be switched to other language by](https://reader035.fdocuments.in/reader035/viewer/2022062415/5fbc320a628cf40c643da491/html5/thumbnails/6.jpg)
IM 05P03D21-11EN page 6/8
Contents1. Monitoring-purposeOperationDisplaysAvailableduringOperation2. SettingAlarmSetpoint3. Troubleshooting
1. Monitoring-purpose Operation Displays Available during Operation
OperationDisplaySwitchingDiagram
8 8
PV Display SELECT Displays (1 to 5)
PresstheDISPkeytoshowSELECTDisplay-1to-5conditionally.FortheregistrationoftheSELECTDisplays,seeUser’sManual.
2. Setting Alarm SetpointThefollowingoperatingprocedureshowsanexampleofsettingthealarm-1setpointto180.0.Beforesettingthealarmsetpoint,checkthealarmtype.Tochange thealarm type,see“3.SettingAlarmType” in “Initialsettings”of thismanual.
1.
2.
3.
4.
5.
6.
8
8
AL menu is displayed.
Display the parameter that need to be changed.
Blinks during the change.
Show the Operation Display.
Hold down the PARA key for 3 seconds.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
The parameter A1 is displayed.A1 to A8 represent the alarm-1 to -8 setpoints.
Each parameter can be changed in the Parameter Setting Displays of alarms using Up/Down arrow keys .
Change the setpoint using the Up/Down arrow keys to increase and decrease the value and the Left/Right arrow keys to move between digits.
The setpoint has been registered.After the setup is completed, press the DISP key once to return to the Operation Display.
OperationGuide
UM33ADigital Indicator with AlarmsOperation Guide
This operation guide describes key entries for operating the UM33A.For operations using external contact inputs, see “DI” of “6. Terminal Wiring Diagrams” in “Installation and Wiring.” If you cannot remember how to carry out an operation during setting, press the DISP key once. This brings you to the display (Operation Display) that appears at power-on. The scrolling guide is displayed on PV display in the Parameter Setting Display. This guide can be turned on/off with the Fn key.
Operations
For details of the each function, refer to the electronic manual. User's manuals can be downloaded or viewed at the following URL.
Functional
Enhancement
http://www.yokogawa.com/ns/ut/im/
1.
2.
3.
4.
5.
6.
8
8
AL menu is displayed.
Display the parameter that need to be changed.
Blinks during the change.
Show the Operation Display.
Hold down the PARA key for 3 seconds.
Press the SET/ENTER key.
Press the SET/ENTER key.
Press the SET/ENTER key.
The parameter A1 is displayed.A1 to A8 represent the alarm-1 to -8 setpoints.
Each parameter can be changed in the Parameter Setting Displays of alarms using Up/Down arrow keys .
Change the setpoint using the Up/Down arrow keys to increase and decrease the value and the Left/Right arrow keys to move between digits.
The setpoint has been registered.After the setup is completed, press the DISP key once to return to the Operation Display.
3. Troubleshooting
TroubleshootingFlowIftheOperationDisplaydoesnotappearafterturningontheindicator’spower,checktheproceduresinthefollowingflowchart.Ifaproblemappearstobecomplicated,contactoursalesrepresentatives.
RemediesifPowerFailureOccursduringOperations• Instantaneous power failure within 20 ms. Apowerfailureisnotdetected.Normaloperationcontinues.• Power failure for less than about 5 seconds, or for about 5 seconds or more. Affectsthe"settings"and"operationstatus." Fordetails,seeUser'sManual.
NOTEWritedownthesettingsofparametersforarepairrequest.
Is the indicatordefective?
Contact us for repair. Problem solved.
No communicationcapability
Completelyinactive?
Yes
Yes
Yes
No
No
No
Keyoperationfailure?
Yes
No
Yes
Check wiring of thepower terminals.
Check the key locksetting.
Displayfailure?
*Yes
No
Turn off power, andthen turn it on again.
I/O signalfailure?
Yes
No
Check the supply voltage.
Check the specifications and polarity
of connected devices .
Check the communication-related parameters.
Check the specificationsof communication
devices.
Check thecommunication wiring.
Communicationfailure?
No Withcommuni-
cation?
Yes
Yes
Normal?Is the
key locked?
Check the specificationsof the indicator.
Yes
NoCorrect?
Correct the error(s).
Cancel the setting.
Check the I/O specificationsof the indicator.
* The LCD (a liquid crystal display) is used for a display portion of this product.
The LCD has a characteristic that the display action becomes late at the low temperature.
Additionally, the luminance and contrast degradation are caused due to aged deterioration.
However, the function is not affected.
Errors at Power OnTheerrorsshownbelowmayoccurinthefaultdiagnosiswhenthepoweristurnedon.(FordetailsofSetpointdisplayandinput/outputactionwheneacherroroccurs,seeUser’sManual.)
PV display (Operation
Display)Setpoint display
(Operation Display)Status indicator
(Operation Display)Parameter that displays error
details Error description Cause and diagnosis Remedy
Indicationoff Indicationoff — — FaultyMCURAM/MCUROM MCURAM/MCUROMarefailed. Faulty. Contactusforrepair.
ERR
SYS-----
—
— System data error System data is corrupted. Faulty. Contactusforrepair.
PAR0004 (foruserdefaultvalueerroronly)
Setupparameter(PA.ER)
User(parameter)defaultvalueerror
Userparameteriscorrupted.Initializedtofactorydefaultvalue. Checkandreconfiguretheinitialized
settingparameters.Errorindicationiserased when the power is turned on again.
PAR0010(forsetupparametererroronly) Setup parameter error Setup parameter data is corrupted.
Initializedtouserdefaultvalue.
PAR0020(foroperationparametererroronly) Operationparametererror Operationparameterdataiscorrupted.
Initializedtouserdefaultvalue.
SLOT0001 Setupparameter(OP.ER)Nonrespondinghardwareofextendedfunction(E1-terminalarea)
Inconsistence of system data and hardware of extendedfunction.Nonrespondingcommunicationbetweenhardwareofextendedfunction(E1-terminalarea).
Faulty.Contactusforrepair.
Normalindication Normalindication
RightmostdecimalpointonPVdisplayblinks.
Setupparameter(PA.ER)Calibrationvalueerror Initializedtocalibrateddefaultvaluebecause
ofcorruptedfactorydefaultvalue. Faulty.Contactusforrepair.Rightmostdecimalpoint
onSymboldisplayblinks. FaultyFRAM Datawriting(storing)toFRAMisimpossible.
Normalindication
0.00000000(DecimalpointontheleftoftheSymboldisplayblinks)
— Setupparameter(OP.ER) Userprofileerror Userprofileiscorrupted. Downloadtheuserprofileagain.
Errors during OperationTheerrorsshownbelowmayoccurduringoperation.(Forinput/outputactionwheneacherroroccurs,seeUser’sManual.)
PV display (Operation
Display)Setpoint display
(Operation Display)Status indicator
(Operation Display)Parameter that displays
error details Error description Cause and diagnosis Remedy
AD.ERR Normalindication — Setupparameter(AD1.E) AnaloginputterminalADCerror•PVinput AnaloginputterminalADvalueerror Faulty.
Contactusforrepair.
RJC.E(DisplaysRJC.EandPValternately.)
Normalindication — Setupparameter(AD1.E) UniversalinputterminalRJCerror•PVinput UniversalinputterminalRJCerror
Faulty.Contactusforrepair.SettheparameterRJCtoOFFtoeraseerror indication.
B.OUT Normalindication —
Setupparameter(AD1.E) Analoginputterminalburnouterror•PVinput Analoginputterminalsensorburnout
Checkwiringandsensor.Errorindicationiserasedinnormaloperation.
Setupparameter(PV1.E) PVinputburnouterror BurnoutofanaloginputconnectedtoPV
Checkwiringandsensorofconnectedanaloginputterminals.Errorindicationiserasedinnormaloperation.
OVER-OVER Normalindication — Setupparameter(PV1.E)
PVinputover-scalePVinputunder-scale(PVvaluesoutof-5to105%)
PVinputisoutof-5to105%.Alsooccurswhenthedataoutofrangewhichistheladder calculation result is input.
Checkanaloginputvalueorladderprogram.
Normalindication
0.00000000(DecimalpointontheleftoftheSymboldisplayblinks)
— Setupparameter(OP.ER) Communicationerror(RS-485communication)
FramingparityerrorBufferoverflowInter-character time-out Checksumerror(PClinkcommunicationwithchecksum)CRCcheckerror(Modbus/RTU)LRCcheckerror(Modbus/ASCII)
Checkthecommunicationparameters.Recoveryatnormalreceipt.Holddownanykeytostopblinking.
Normalindication
0.00000000(DecimalpointontheleftoftheSymboldisplayblinks)
— Setupparameter(OP.ER) Userprofileerror Userprofileiscorrupted. Downloadtheuserprofileagain.
Normalindication Normalindication Rightmostdecimalpointon
Symboldisplayblinks. Setupparameter(PA.ER) FaultyFRAM Writing(storing)datatoFRAMisimpossible. Faulty.Contactusforrepair.
Undefined Undefined — — FaultyMCU/DCU(ROM/RAMerror,corrupted) MCU/DCUiscorrupted. Faulty.Contactusforrepair.
![Page 7: ting the Instrument Main Unit Moun Contents · 3 CC-Linkcommunication(withModbusmasterfunction)(*2) Display language (*3)-1 English (Default. Can be switched to other language by](https://reader035.fdocuments.in/reader035/viewer/2022062415/5fbc320a628cf40c643da491/html5/thumbnails/7.jpg)
IM 05P03D21-11EN page 7/8
Operation ParametersHolddownthePARAkeyfor3secondstomovefromtheOperationDisplaytotheOp-erationParameterSettingDisplay.PresstheDISPkeyoncetoreturntotheOperationDisplay.
Menu
Hold down PARA keyfor 3 sec.
DISP key
SET/ENTER key PARA key
key key key
key key
Operation Dsipaly
Parameter
Parameter
Parameter
Parameter
Parameter
ParameterEND
Menu
END
Menu END
END
Menu Display and Parameter Setting Display are changed in a circular pattern.
Move to the Setup Parameter Setting Display: Hold down the PARA key and the Left arrow key simultaneously for 3 sec.
Operation for Setting· Toselecttheparametersettingdisplayedastheinitialvalue,presstheDownarrowkeytomovetothenextparameter.
· Tochangeandsettheparametersetting,presstheSET/ENTERkeytostarttheset-pointblinking.Theblinkingstateallowsyoutomakechanges(settingmode).UsetheUp/Down/Left/Rightarrowkeystochangethesetpoint.PresstheSET/ENTERkeytoregisterthesetting.
Notethattherearesomeparameterswhicharenotdisplayeddependingonthemodelandsuffixcodes.Theparametersforprofessionalsettingmode(LEVL:PRO)arenotdescribedinthismanual.SeeUser’sManual.
Alarm Setpoint Setting ParameterMenusymbol: (AL)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
to
(A1toA8)
Alarm-1to-8setpoint
SetadisplayvalueofsetpointofPValarmorvelocityalarm. -19999to30000(Setavaluewithintheinputrange.) Decimalpointpositiondependsonthe input type
0 Tablebelow EASY
For thealarmsetpointparameter,alarm-1to-8aredisplayedfor thefactorydefault.ThenumberofalarmscanbechangedusingthesetupparameterALNO.(numberofalarms).Tochangethenumberofalarms,seeUser'sManual.Usethefollowingtabletorecordalarmsetpoints.
Parameter Setpoint Parameter Setpoint
A1 A5
A2 A6
A3 A7
A4 A8
Alarm Function Setting ParameterMenusymbol: (ALRM)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
to
(AL1toAL8)
Alarm-1to8typeExample:Alarm-1
Stand-by action
Latch actionEnergized/De-energize
Alarm type
Seta5-digitvalueinthefollowingorder.[Latchaction(0/1/2/3/4)]+[Ener-gized(0)orDe-energized(1)]+[Without(0)orWith(1)Stand-byaction]+[Alarmtype:2digits(seebelow)]Forlatchaction,seeUser'sManual.
AL1,AL3,AL5,AL7:Latch
action(0) Energized
(0) WithoutStand-byaction(0) PVhighlimit(01)
AL2,AL4,AL6,AL8:Latch
action(0) Ener-
gized(0) WithoutStand-byaction(0) PVlowlimit(02)
Tablebelow
EASY
Alarmtype:2digits 00:Disable 01:PVhighlimit 02:PVlowlimit 29:PVvelocity30:Faultdiagnosis31:FAIL
to
(VT1toVT8)
PVvelocityalarmtimesetpoint1to8 0.01to99.59(minute.second) 1.00
to
(HY1toHY8)
Alarm-1to-8hysteresis
Setadisplayvalueofsetpointofhysteresis. -19999to30000(Setavaluewithintheinputrange.) Decimalpointpositiondependsonthe input type.Whenthedecimalpointpositionfortheinputtypeissetto"1",theinitialvalueofthehysteresisis"1.0".
10
to
(DYN1toDYN8)
Alarm-1to-8On-delaytimer
AnalarmoutputisONwhenthedelaytimerexpiresafterthealarmsetpoint is reached. 0.00to99.59(minute.second)
0.00 STD
Forthealarmfunctionsettingparameter,8alarmsaredisplayedforthefactorydefault.Thenumberofalarmscanbechangedby thesetupparameterALNO. (numberofalarms).Tochangethenumberofalarms,seeUser'sManual.Parameter n=1 n=2 n=3 n=4 n=5 n=6 n=7 n=8
ALn
VTn
HYn
DYNn
n:alarmnumber
PV-related Setting ParameterMenusymbol: (PVS)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(BS)PVinputbias -100.0to100.0%ofPVinputrange
span(EUS)
0.0%ofPVinput rangespan
EASY(FL)PVinputfilter OFF,1to120s OFF
(PEAK)PVpeakvalue
Displayonly (-5.0to105.0%ofPVinputrange(EU))
None
(BOTM)PVbottomvalue None
Setup ParametersHolddownthePARAkeyandLeftarrowkeysimultaneously for3secondstomovefromtheOperationDisplayorOperationParameterSettingDisplayto theSetupPa-rameterSettingDisplay.PresstheDISPkeyoncetoreturntotheOperationDisplay.
Menu
DISP key
SET/ENTER key PARA key
key key key
key key
Operation Dsipaly
Parameter
Parameter
Parameter
Parameter
Parameter
ParameterEND
Menu
END
Menu END
END
Menu Display and Parameter Setting Display are changed in a circular pattern.
Move to the Operation Parameter Setting Display: Hold down the PARA key for 3 sec.
Hold down PARA key and Left arrow key simultaneously for 3 sec.
Operation for Setting· Toselecttheparametersettingdisplayedastheinitialvalue,presstheDownarrowkeytomovetothenextparameter.
· Tochangeandsettheparametersetting,presstheSET/ENTERkeytostarttheset-pointblinking.Theblinkingstateallowsyoutomakechanges(settingmode).UsetheUp/Down/Left/Rightarrowkeystochangethesetpoint.PresstheSET/ENTERkeytoregisterthesetting.
NotethattherearesomeparameterswhicharenotdisplayeddependingontheModelandSuffixcodes.Theparametersforprofessionalsettingmode(LEVL:PRO)arenotdescribedinthismanual.SeeUser’sManual.
Function Setting ParameterMenusymbol: (CTL)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(SMP)Inputsamplingperiod 50:50ms,100:100ms,200:200ms 50 STD
PV Input Setting ParameterMenusymbol: (PV)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(IN)PVinputtype
OFF:DisableK1:-270.0to1370.00C/-450.0to2500.0 0FK2:-270.0to1000.00C/-450.0to2300.0 0FK3:-200.0to500.00C/-200.0to1000.0 0FJ:-200.0to1200.00C/-300.0to2300.0 0FT1:-270.0to400.00C/-450.0to750.0 0FT2:0.0to400.00C/-200.0to750.0 0FB:0.0to1800.00C/32to3300 0FS:0.0to1700.00C/32to3100 0FR:0.0to1700.00C/32to3100 0FN:-200.0to1300.00C/-300.0to2400.0 0FE:-270.0to1000.00C/-450.0to1800.0 0FL:-200.0to900.00C/-300.0to1600.0 0FU1:-200.0to400.00C/-300.0to750.0 0FU2:0.0to400.00C/-200.0to1000.0 0FW:0.0to2300.00C/32to4200 0FPL2:0.0to1390.00C/32.0to2500.0 0FP2040:0.0to1900.00C/32to3400 0FWRE:0.0to2000.00C/32to3600 0FJPT1:-200.0to500.00C/-300.0to1000.0 0FJPT2:-150.0to150.00C/-200.0to300.0 0FPT1:-200.0to850.00C/-300.0to1560.0 0FPT2:-200.0to500.00C/-300.0to1000.0 0FPT3:-150.00to150.000C/-200.0to300.0 0F0.4-2V:0.400to2.000V1-5V:1.000to5.000V4-20:4.00to20.00mA0-2V:0.000to2.000V0-10V:0.00to10.00V0-20:0.00to20.00mA-1020:-10.00to20.00mV0-100:0.0to100.0mV
OFF EASY
(UNIT)PVinputunit
-:Nounit,C:DegreeCelsius -:Nounit,--:Nounit,---:Nounit,F:DegreeFahrenheit
C EASY
(RH)MaximumvalueofPVinputrange
Dependsontheinputtype. - For temperature input - Setthetemperaturerangethatisactuallydisplayed.(RL<RH) -Forvoltage/currentinput- Settherangeofavoltage/currentsignalthatisapplied. Thescaleacrosswhichthevoltage/currentsignalisactuallydisplayedshouldbesetusingthemaximumvalueofinputscale(SH)andminimumvalueofinputscale(SL).(Inputisalways0%whenRL=RH.)
Dependson the
input typeEASY
(RL)MinimumvalueofPVinputrange
(SDP)PVinputscaledecimalpoint position
0:Nodecimalplace 1:Onedecimalplace 2:Twodecimalplaces 3:Threedecimalplaces 4:Fourdecimalplaces
Dependson the
input typeEASY
(SH)MaximumvalueofPVinput scale
-19999to30000,(SL<SH),|SH-SL|≤30000
Dependson the
input typeEASY
(SL)MinimumvalueofPVinput scale
(BSL)PVinputburnoutaction
OFF:Disable UP:Upscale DOWN:Downscale
Dependson the
input type
STD(A.BS)
PVanaloginputbias -100.0to100.0%ofPVinputrangespan(EUS)
0.0%ofPVinputrangespan
(A.FL)PVanaloginputfilter OFF,1to120s OFF
W:W-5%Re/W-26%Re(HoskinsMfg.Co.).ASTME988WRE:W97Re3-W75Re25
Input Range Setting ParameterMenusymbol: (MPV)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(P.UNI)DisplayPVinputunit
-:NounitC:DegreeCelsius-:Nounit--:Nounit---:NounitF:DegreeFahrenheit
Same asPVinput unit
STD
(P.DP)DisplayPVinputdecimalpoint position
0:Nodecimalplace1:Onedecimalplace2:Twodecimalplaces3:Threedecimalplaces4:Fourdecimalplaces
1
(P.RH)MaximumvalueofdisplayPVinputrange
-19999to30000,(P.RL<P.RH),|P.RH-P.RL|≤30000
Dependson the
input type
(P.RL)MinimumvalueofdisplayPVinputrange
Output Setting ParameterMenusymbol: (OUT)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(RTS)RetransmissionoutputtypeofRET
OFF:Disable PV1:PV LPS:15VDClooppowersupply
PV1 EASY
(RTH)
Maximumvalueofretransmission output scaleofRET
WhenRTS=PV1RTL+1digitto30000-19999toRTH-1digitDecimalpointposition:When
RTS=PV1,decimalpointpositionissameasthatofPVinput.
WhenRTS=PV,decimalpointpositionissameasthatofPVinputscale.
100%ofPVinput range
STD(RTL)
Minimumvalueofretransmission output scaleofRET
0%ofPVinput range
(RET.A)RETcurrentoutputrange
4-20:4to20mA 0-20:0to20mA 20-4:20to4mA 20-0:20to0mA
4-20
OperationGuide
UM33ADigital Indicator with AlarmsOperation Guide
Yokogawa Electric Corporation
Parameters
For details of the each function, refer to the electronic manual. User's manuals can be downloaded or viewed at the following URL.
Functional
Enhancement
http://www.yokogawa.com/ns/ut/im/
This operation guide describes the functions of parameters briefly. The parameter symbols listed are in the order shown on the display in each group of menu symbols. In addition, each parameter table has a “User Setting” column, where you can record your setpoints when setting them in the indicator. The scrolling guide is displayed on PV display in the Parameter Setting Display. This guide can be turned on/off with the Fn key.
![Page 8: ting the Instrument Main Unit Moun Contents · 3 CC-Linkcommunication(withModbusmasterfunction)(*2) Display language (*3)-1 English (Default. Can be switched to other language by](https://reader035.fdocuments.in/reader035/viewer/2022062415/5fbc320a628cf40c643da491/html5/thumbnails/8.jpg)
IM 05P03D21-11EN page 8/8
RS-485 Communication Setting Parameter (E1-terminal Area)Menusymbol: (R485)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(PSL)Protocol selection
PCL:PClinkcommunication PCLSM:PClinkcommunication(withchecksum) LADR:Laddercommunication MBASC:Modbus(ASCII) MBRTU:Modbus(RTU)
MBRTU
EASY
(BPS)Baud rate
600:600bps1200:1200bps2400:2400bps4800:4800bps9600:9600bps19200:19.2kbps38400:38.4kbps
19200
(PRI)Parity
NONE:None EVEN:Even ODD:Odd
EVEN
(STP)Stopbit 1:1bit,2:2bits 1
(DLN)Datalength 7:7bits,8:8bits 8
(ADR)Address 1to99 1
CC-Link Communication Setting Parameter (E1-terminal Area)Menusymbol: (CC-L)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(BR)Baud rate
156K:156kbps625K:625kbps2.5K:2.5kbps5M:5Mbps10M:10Mbps
10M
EASY(ADR)Address 1 to 64 1
(BPS)Baud rate
9600:9600bps19200:19.2kbps38400:38.4kbps
38400
(FILE)Profilenumber 0,31to34(0,31:Ver1.10,32to34:
Ver2.00) 0
KeyActionSettingParameterMenusymbol: (KEY)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(Fn)Userfunctionkey-n actionsetting
OFF:DisableLTUP:LCDbrightnessUPLTDN:LCDbrightnessDOWNBRI:AdjustLCDbrightnessLCD:LCDbacklightON/OFFswitchLAT:Latchrelease(ACK)AL:AlarmsetpointsettingRST:PVpeakandbottomvalues
reset
RST EASY
DisplayFunctionSettingParameterMenusymbol: (DISP)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(PCMD)ActivecolorPVdisplayswitch
0:Fixedinwhite1:Fixedinred2:Linktoalarm1(AlarmOFF:white,
AlarmON:red)3:Linktoalarm1(AlarmOFF:red,
AlarmON:white)4:Linktoalarm1or2(AlarmOFF:
white,AlarmON:red)5:Linktoalarm1or2(AlarmOFF:
red,AlarmON:white)6:PVlimit(Withinrange:white,Out
ofrange:red)7:PVlimit(Withinrange:red,Outof
range:white)10:LinktoDI(ON:red,OFF:white)
0
EASY
(PCH)PVcolorchangehighlimit
SetadisplayvaluewheninPVlimitorSPdeviation. -19999to30000(Setavaluewithintheinputrange.) Decimalpointpositiondependsonthe input type.
0
(PCL)PVcolorchangelowlimit 0
(GUID)GuidedisplayON/OFF OFF:Non-display,ON:Display ON
STD
(ECO)Economymode
OFF:Disable1:EconomymodeON(AllindicationsexceptPVdisplayOFF)2:EconomymodeON(AllindicationsOFF)3:Brightness10%(wholeindication)
OFF
(BRI)Brightness (Dark)1to5(Bright) 3 EASY
(MLSD)LeastsignificantdigitalmaskofPVdisplay
OFF:Withleastsignificantdigit ON:Withoutleastsignificantdigit OFF STD
(MKTP)
Methodforleastsignifi-cantdigitalmaskofPVdisplay
0:Rounding,1:Rounding-off 0 STD
SELECTDisplaySettingParameterMenusymbol: (CSEL)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
to
(CS1toCS5)
SELECTDisplay-1to-5registration
Registertheoperationparameter(excepttheOperaitonMode)thatisfrequentlymodifiedtodisplayitintheOperationDisplay. OFF,2301to5000 Forthesettingrange,seeCommuni-cationUser'sManual.
OFF STD
UsethefollowingtabletorecordSELECTDsipalysettingvalue.
Parameter n=1 n=2 n=3 n=4 n=5
CSn
KeyLockSettingParameterMenusymbol: (KLOC)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(COM.W)Communicationwriteenable/disable OFF:Enable,ON:Disable OFF
STD
(DATA)Front panel parameter data(,)keylock
OFF:Unlock,ON:Lock (AvailableforOperationDisplayonly.) OFF
DIFunctionResistrationParameterMenusymbol: (DI.SL)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(RST)PVpeakandbottomvaluesreset
SetanIrelaynumberofcontactinput.Set“OFF”todisablethefunction.
Standard terminalsDI1:5025,DI2:5026
5025
STD(LAT)
Latchrelease(ACK) 5026
(LCD)LCDbacklightON/OFFswitch OFF
(PVRW)PVred/whiteswitch OFF
AL1-AL4FunctionRegistrationParameterMenusymbol: (ALM)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(AL1.S)AL1functionselection
SetanIrelaynumber.Fortheitemsotherthanbelow,seeUser'sManual.Ex.)Setthenumber4353forAL1.Sto use the alarm 1.Set“OFF”todisablethefunction.
Nofunction:OFFAlarm1:4353Alarm2:4354Alarm3:4355Alarm4:4357Alarm5:4358Alarm6:4359Alarm7:4361Alarm8:4362
FAIL(NormallyON)output:4256
4353
STD
(AL2.S)AL2functionselection 4354
(AL3.S)AL3functionselection 4355
(AL4.S)AL4functionselection 4357
DOSettingParameter(E1-terminalArea)Menusymbol: (DO)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(DO1.S)DO11functionselection
SameasAL1.SSet“OFF”todisablethefunction
4358
STD
(DO2.S)DO12functionselection 4359
(DO3.S)DO13functionselection 4361
(DO4.S)DO14functionselection 4362
(DO5.S)DO15functionselection 4256
SystemSettingParameterMenusymbol: (SYS)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(R.TM)Restarttimer 0to10s. 0 STD
(FREQ)Powerfrequency AUTO,60:60Hz,50:50Hz AUTO
EASY
(QSM)Quicksettingmode OFF:Disable
ON:Enable ON
(LANG)Guidedisplaylanguage
ENG:EnglishFRA:FrenchGER:GermanSPA:Spanish
Depe-nds on the model and suffixcodes
(PASS)Passwordsetting
0(Nopassword)to65535 Setting“0”means“withoutpasswordprotection.”
0
ErrorandVersionConfirmationParameter(fordisplayonly)Menusymbol: (VER)
Parameter symbol Name of Parameter Status record Display
level
(PA.ER)Parameter error status
EASY
(OP.ER)Optionerrorstatus
(AD1.E)A/Dconvertererrorstatus1
(PV1.E)PVinputerrorstatus
(MCU)MCUversion
(DCU)DCUversion
(ECU1)ECU-1version(E1-terminalarea)
(PARA)Parameterversion
(H.VER)Productversion
(SER1)Serialnumber1
(SER2)Serialnumber2
ParameterDisplayLevelParameterMenusymbol: (LVL)
Parameter symbol Name of Parameter Setting Range Initial
valueUser
settingDisplay
level
(LEVL)Parameterdisplaylevel
EASY:Easysettingmode STD:Standardsettingmode PRO:Professionalsettingmode
STD EASY
*ForProfessionalsettingmode,seeUser’sManual.
Trademarks Our product names or brand names mentioned in this manual are the trademarks or registered trademarks of Yokogawa Electric Corporation. Adobe, Acrobat, and Postscript are either registered trademarks or trademarks of Adobe Systems Incorporated. We do not use the TM or ® mark to indicate these trademarks or registered trademarks in this manual. CC-Link is a registered trademark of CC-Link Partner Association. All other product names mentioned in this manual are trademarks or registered trademarks of their respective companies.
• AuthorisedRepresentativeintheEEA YokogawaEuropeBV.(Address:Euroweg2,3825HDAmersfoort,TheNether-lands) istheAuthorisedRepresentativeofYokogawaElectricCorporationforthisProductintheEEA.
• Printed ManualsModel Description
UM33ADigitalIndicatorwithAlarmsOperationGuide IM05P03D21-11ENUM33A-SDigitalIndicatorwithAlarmsOperationGuide IM05P09D21-11ENX010ExternalPrecisionResistor IMX010-01ENPrecautionsontheUseoftheUTAdvancedSeries IM05P01A01-11EN
• ElectronicManuals Youcandownloadthelatestmanualsfromthefollowingwebsite: URL:http://www.yokogawa.com/ns/ut/im/
Model DescriptionUM33ADigitalIndicatorwithAlarmsOperationGuide IM05P03D21-11ENUM33ADigitalIndicatorwithAlarmsUser’sManual IM05P03D21-01ENUM33A-SDigitalIndicatorwithAlarmsOperationGuide IM05P09D21-11ENUTAdvancedSeriesCommunicationInterface(RS-485,Ethernet)User’sManual IM05P07A01-01ENUTAdvancedSeriesCommunicationInterface(OpenNetwork)User’sManual IM05P07A01-02ENLL50AParameterSettingSoftwareInstallationManual IM05P05A01-01ENLL50AParameterSettingSoftwareUser’sManual IM05P05A01-02ENX010ExternalPrecisionResistor IMX010-01ENPrecautionsontheUseoftheUTAdvancedSeries IM05P01A01-11EN
• GeneralSpecificationModel Description
UM33ADigitalIndicatorwithAlarms GS05P03D21-01ENUM33A-SDigitalIndicatorwithAlarms GS05P09D21-01ENLL50AParameterSettingSoftware GS05P05A01-01ENX010ExternalPrecisionResistor GSX010-01EN
* Thelasttwocharactersofthemanualnumberandgeneralspecificationnumberindicatethelanguageinwhichthemanualiswritten.