Time Current Curves TD012027EN Series G J-Framepub/@electrical/documents/cont… · Time Current...
Transcript of Time Current Curves TD012027EN Series G J-Framepub/@electrical/documents/cont… · Time Current...
Time Current Curves TD012027EN Effective April 2014
ContentsDescription Page
Catalog Number Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Digitrip 310+ Electronic Trip Unit Types JGE, JGS, JGH, JGC, JGU, JGXLong delay response and short delay with flat response curve . . . . . . . . . . . . . . . . . . . . . TC01201001E . . . . . . . .5Long delay response and short delay with I2T response curve . . . . . . . . . . . . . . . . . . . . . TC01201002E . . . . . . . .6Ground fault delay response curve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . TC01203004E . . . . . . . .7
Thermal/Magnetic Trip UnitJGE, JGS, JGH, JGC, JGU, and JGX 2, 3, and 4 pole circuit breakers . . . . . . . . . . . . . . . . . . JGTCC2 . . . . . . . . . . .8
Peak Let-Through CurvesLGX, JGX, EGC, and EGC CL (with Current Limiter) — 240V . . . . . . . . . . . . . . . . . . . . . . . TC01200001E . . . . . . . .9LGC, JGH CL (with Current Limiter), JGX, EG, and EGC CL — 480V . . . . . . . . . . . . . . . . TC01200001E . . . . . . .10LGX, JGH CL (with Current Limiter), JGX, EG, and EGC CL — 600V . . . . . . . . . . . . . . . . . TC01200001E . . . . . . .11JGH CL—690V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . TC01200001E . . . . . . .12Peak Let-Through Currents (Ip) and Clearing (I2T) Summary Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Earth Leakage Module CurvesUL JG250 Circuit Breaker Earth Leakage Module, 3 and 4 poles, 110-480V . . . . . . . . . . . TC01204004E . . . . . . .14IEC JG250 Circuit Breaker Earth Leakage Module, 3 and 4 poles, 110-480V . . . . . . . . . . . TC01205001E . . . . . . .15
Note:The following curves meet the requirements of UL, CSA, IEC, CCC and CE .The following circuit breakers are derived from Eaton, Westinghouse, or Cutler-Hammer history .
Time Current Curves are engineering reference documents for application and coordination purposes only.For field testing molded case circuit breakers, refer to NEMA AB 4 guidelines.
Series G J-Frame 20-250A, 240-600V
2
Time Current Curves AD012020ENEffective October 2013
Series G L-Frame
eaton www.eaton.com
otee:N Unless noted below, all curves remain unchanged from their prior revision .
Revision Curve Number Page Date
2
Time Current Curves TD012027ENEffective April 2014
Series GJ-Frame
eaton www.eaton.com
3
Time Current Curves TD012027ENEffective April 2014
Series GJ-Frame
eaton www.eaton.com
J G S 3 250 FA G C
Frame
J
Terminations/Hardware
Amperes
050070080090100125150160175200225250
MEGW
= Metric end caps= Imperial end caps= Line/load standard= Without terminals
Number of Poles
23489
= Two= Three= Four - Neutral 0% Protected= Four - Neutral 0-60% Protected= Four - Neutral 100% Protected
Standard/Application
G = IEC/CE/UL/CSA
Perfomance
E
S
H
C
U
X
18
18
25
35
50
50
600 480 415 240
Trip Unit
AAFAKS33323536NN
= Adj. adj.= Fixed adj.= Molded case switch= 310+ electronic LS= 310+ electronic LSI= 310+ electronic LSG= 310+ electronic LSIG= Frame only (no trip)
MetricImperialMetric
25
35
65
100
150
200
25
40
70
100
150
200
65
85
100
200
200
200
Rating
BlankCQ01Q02
= 80% rated= 100% rated= CL module, Line Side= CL Module, Load Side
Table 1. Series G JG–Frame (63-250 Amperes)
Catalog number Selection
This information is presented only as an aid to understanding catalog numbers .It is not to be used to build catalog numbers for circuit breakers or trip units .
JT 4 100 FA
Trip
JT
Amperes
T/M080090100110125150160175200225250
Number of Poles
23489
= Two= Three= Four - Neutral 0% Protected= Four - Neutral 0-60% Protected= Four - Neutral 100% Protected
Trip Unit
AAFAKS33323536NN
= Adj. adj.= Fixed adj.= Molded case switch= 310+ electronic LS= 310+ electronic LSI= 310+ electronic LSG= 310+ electronic LSIG= Frame only (no trip)
ETU050100160250
Table 2. Trip Unit
Frame
ELJBAmperes
150 (UL) / 160 (IEC)250
Number of Poles
34
= Three= Four
Rating
NE
= UL rated= IEC rated
Terminations/Hardware
W = Without terminals
ELJB N 3 250 W
G = Line/load standard (metric)
Table 3. Earth Leakage Modules
4
Time Current Curves TD012027ENEffective April 2014
Series GJ-Frame
eaton www.eaton.com
20 30
0.01
1
2
3
4
5
6789
10
20
30
40
50
60
708090
100
1000900800700
600
500
400
300
200
2000
3000
4000
5000
6000
700080009000
10000
0.02
0.03
0.04
0.05
0.06
0.070.080.090.1
0.2
0.3
0.4
0.5
0.60.70.80.9
1
3
4
5
6789
10
20
30
40
50
60
708090
100
1000900800700
600
500
400
300
200
2000
3000
4000
5000
6000
700080009000
10000
1M
INU
TE
SR
UO
H2
SD
NO
CE
SNI
EMI
T1
HO
UR
0.01
0.02
0.03
0.04
0.05
0.060.070.080.090.1
0.2
0.3
0.4
0.5
0.6
0.70.80.91
2
Maximum TotalClearing Time
Available Long Delay Time:2, 4, 7, 10, 12, 15, 20, 24 sec.
Shown at 6 x Ir2, 4, 7, 15, 24 seconds
+0/–30%
SD
NO
CE
SNI
EMI
T
Available Short DelayPickup Settings
2–8, 10, 12 x Ir ±5% (See Note 7)
2
Current in Multiples of (Ir)
1 2 3 4 5 7 10 20 30 40 50 70 100 2 3 4 5 7 10 20 30 40 50 70 1000.5 0.7
1 2 3 4 5 7 100.5 0.7
8
12
10
4
.
.24
63
1.15
Application DeterminesEnd of Curve
InstantaneousOverride (Ii)
7
.
5
.
300 ms(P, Q, R)
120 ms(M, N, O)
Inst.(J, K, L)
15
7
.4
2
Minimum TotalClearing Time
Current in Multiples of (Ir) Current in Multiples of (In)
±5%
Figure 1. Digitrip 310+ Faceplates
AdjustmentButtons
H02
6
7
10
8 Im
9
5 x In∂ ∑
Figure 2. JG Thermal/Magnetic Faceplate
Figure 3. JG Earth Leakage Module Faceplate
5
Time Current Curves TD012027ENEffective April 2014
Series GJ-Frame
eaton www.eaton.com
20 30
0.01
1
2
3
4
5
6789
10
20
30
40
50
60
708090
100
1000900800700
600
500
400
300
200
2000
3000
4000
5000
6000
700080009000
10000
0.02
0.03
0.04
0.05
0.06
0.070.080.090.1
0.2
0.3
0.4
0.5
0.60.70.80.9
1
3
4
5
6789
10
20
30
40
50
60
708090
100
1000900800700
600
500
400
300
200
2000
3000
4000
5000
6000
700080009000
10000
1M
INU
TE
SR
UO
H2
SD
NO
CE
SNI
EMI
T1
HO
UR
0.01
0.02
0.03
0.04
0.05
0.060.070.080.090.1
0.2
0.3
0.4
0.5
0.6
0.70.80.91
2
Maximum TotalClearing Time
Available Long Delay Time:2, 4, 7, 10, 12, 15, 20, 24 sec.
Shown at 6 x Ir2, 4, 7, 15, 24 seconds
+0/–30%
SD
NO
CE
SNI
EMI
TAvailable Short Delay
Pickup Settings2–8, 10, 12 x Ir ±5%
(See Note 7)
2
Current in Multiples of (Ir)
1 2 3 4 5 7 10 20 30 40 50 70 100 2 3 4 5 7 10 20 30 40 50 70 1000.5 0.7
1 2 3 4 5 7 100.5 0.7
8
12
10
4
.
.24
63
1.15
Application DeterminesEnd of Curve
InstantaneousOverride (Ii)
7
.
5
.
300 ms(P, Q, R)
120 ms(M, N, O)
Inst.(J, K, L)
15
7
.4
2
Minimum TotalClearing Time
Current in Multiples of (Ir) Current in Multiples of (In)
±5%
Figure 4. Digitrip 310+ Long Delay Response and Short Delay with Flat Response Curve (LSI, LSIG)—Curve Number TC01201001E, March 2012
Digitrip 310+ Circuit Breaker time/Current Curves (Phase Current)
Series G J-Frame Circuit Breakers
Catalog types: JGE, JGS, and JGH circuit breakers, two, three- and four-pole .
Trip Unit Types: 32 (LSI), and 36 (LSIG)
Available Sensors (In): 50A 100A 160A 250A
Long Delay and Short Delay with Flat Response
A 20A 40A 63A 100AB 20A 45A 80A 125AC 25A 50A 90A 150AD 30A 63A 100A 160AE 32A 70A 110A 175AF 40A 80A 125A 200AG 45A 90A 150A 225AH 50A 100A 160A 250A
Ir/In 50A 100A 160A 250A
notes:
1 . Curve accuracy applies from –20°C to +55°C ambient . For possible continuous ampere derating for ambient above 40°C, refer to Eaton . Temperatures above +85°C cause an over-temperature protection trip .
2 . Application frequency is 50/60 Hertz .
3 . There is a memory effect that can act to shorten the long delay . The memory effect comes into play if a current above the long delay pickup value exists for a time and then is cleared by the tripping of a downstream device or the circuit breaker itself . A subsequent overload will cause the circuit breaker to trip in shorter time than normal . The amount of time reduction is inverse to the amount of time that has elapsed since the previous overload . Approximately five minutes is required between overloads to completely reset the memory .
4 . The right portion of the curve is determined by the interrupting rating of the circuit breaker .
5 . The left portion of the curve is shown as a multiple of the Long Delay Setting . (Long Delay Pickup = 115% of Ir) . Range is 110%–120% .
6 . Total clearing times shown include the response times of the trip unit, the breaker opening, and the interruption of the current .
7 . The Short Delay Pick Up has 9 settings/positions, 2–8 and 10, 12 .
8 . For high fault current levels, an additional fixed instantaneous hardware override (Ii) is provided at 14x . Instantaneous tolerance is ±20% .
Ir = Continuous Current Setting or Rating Plug Value, Is = Current Sensor Frame Rating, In = Rating Plug Value, Ig = Ground Current Pickup Multiplier, Ii = Instantaneous Override Pickup .
6
Time Current Curves TD012027ENEffective April 2014
Series GJ-Frame
eaton www.eaton.com
0.01
1
2
3
4
5
6
789
10
20
30
40
50
60
708090
100
1000900800700
600
500
400
300
200
2000
3000
4000
5000
6000
700080009000
10000
0.02
0.03
0.04
0.05
0.06
0.070.080.090.1
0.2
0.3
0.4
0.5
0.60.70.80.9
3
4
5
6
789
10
20
30
40
50
60
708090
100
1000900800700
600
500
400
300
200
2000
3000
4000
5000
6000
700080009000
10000
1MIN
UT
ES
RU
OH
2S
DN
OC
ES
NIE
MIT
1HO
UR
0.01
0.02
0.03
0.04
0.05
0.060.070.080.090.1
0.2
0.3
0.4
0.5
0.6
0.70.80.91
SD
NO
CE
SNI
EMI
T2
1 2 5 7 10 20 2 5 7 10 20 30 40 50 70 1000.5 0.7
1 234 5 7 10 20300.5 0.7
8
12
10
7
5
4
.
.4
.
.
.24
6
.
3
1.15
67 ms
15
7
2
Current in Multiples of (Ir)
Maximum TotalClearing Time
Available Long Delay Time:2, 4, 7, 10, 12, 15, 20, 24 sec.
Shown at 6 x Ir2, 4, 7, 15, 24 seconds
+0/–30%
Minimum TotalClearing Time
Available Short DelayPickup Settings
2–8, 10, 12 x Ir ±5% (See Note 7)
I2T Short Delay (See Note 8)
See Note 9
Current in Multiples of (Ir) Current in Multiples of (In)
Application DeterminesEnd of Curve
InstantaneousOverride (Ii)
3 43 4 10070504030
0.01
2
3
4
5
6
8
10
20
30
40
50
60708090
100
1000900800700
600
500
400
300
200
0.02
0.03
0.04
0.05
0.06
0.070.080.09
0.1
0.2
0.3
0.4
0.5
0.6
0.70.80.9
1
7
9
2000
3000
4000
5000
6000
700080009000
10000
1M
INU
TE
SD
NO
CE
SNI
EMI
T
0.1 0.2 0.5 0.7 1.0 2.0
0.1 0.2 0.5 0.7 1.0 2.0
Ground Fault Pickup Settings(Tolerance ±10%)
0.4X
0.3X
0.2X 1X0.6X
0.8X
0.3 0.4
0.3 0.4
Ground Current in Multiples of (In)
300 ms(L, O, R)
120 ms(K, N, Q)
Inst.(J, M, P)
Figure 5. Digitrip 310+ Long Delay Response and Short Delay with I2T Response Curve (LS, LSG)—Curve Number TC01201002E, March 2012
Digitrip 310+ Circuit Breaker time/Current Curves (Phase Current)
Series G J-Frame Circuit Breakers
Catalog types: JGE, JGS, and JGH circuit breakers, two- three- and four-pole .
Trip Unit Types: 33 (LS) and 35 (LSG)
Available Sensors (In): 50A 100A 160A 250A
Long Delay and Short Delay with I2T Response
A 20A 40A 63A 100AB 20A 45A 80A 125AC 25A 50A 90A 150AD 30A 63A 100A 160AE 32A 70A 110A 175AF 40A 80A 125A 200AG 45A 90A 150A 225AH 50A 100A 160A 250A
Ir/In 50A 100A 160A 250A
notes:
1 . Curve accuracy applies from –20°C to +55°C ambient . For possible continuous ampere derating for ambient above 40°C, refer to Eaton . Temperatures above +85°C cause an over-temperature protection trip .
2 . Application frequency is 50/60 Hertz .
3 . There is a memory effect that can act to shorten the long delay . The memory effect comes into play if a current above the long delay pickup value exists for a time and then is cleared by the tripping of a downstream device or the circuit breaker itself . A subsequent overload will cause the circuit breaker to trip in shorter time than normal . The amount of time reduction is inverse to the amount of time that has elapsed since the previous overload . Approximately five minutes is required between overloads to completely reset the memory .
4 . The right portion of the curve is determined by the interrupting rating of the circuit breaker .
5 . The left portion of the curve is shown as a multiple of the Long Delay Setting . (Long Delay Pickup = 115% of Ir) . Range is 110%–120% .
6 . Total clearing times shown include the response times of the trip unit, the breaker opening, and the interruption of the current .
7 . The Short Delay Pick Up has 9 settings/positions, 2–8 and 10, 12 .
8 . Short Delay I2T band has a tolerance of ±15% .
9 . Breakpoint back to FLAT response occurs at 8x Ir for upper line of the I2T curve .
10 . For high fault current levels, an additional fixed instantaneous hardware override (Ii) is provided (corresponding to SDPU position 9) at 14x (In) . Instantaneous tolerance is ±20% .
Ir = Continuous Current Setting or Rating Plug Value, Is = Current Sensor Frame Rating, In = Rating Plug Value, Ig = Ground Current Pickup Multiplier, Ii = Instantaneous Override Pickup .
7
Time Current Curves TD012027ENEffective April 2014
Series GJ-Frame
eaton www.eaton.com
0.01
2
3
4
5
6
8
10
20
30
40
50
60708090
100
1000900800700
600
500
400
300
200
0.02
0.03
0.04
0.05
0.06
0.070.080.09
0.1
0.2
0.3
0.4
0.5
0.6
0.70.80.9
1
7
9
2000
3000
4000
5000
6000
700080009000
10000
1M
INU
TE
SD
NO
CE
SNI
EMI
T
0.1 0.2 0.5 0.7 1.0 2.0
0.1 0.2 0.5 0.7 1.0 2.0
Ground Fault Pickup Settings(Tolerance ±10%)
0.4X
0.3X
0.2X 1X0.6X
0.8X
0.3 0.4
0.3 0.4
Ground Current in Multiples of (In)
300 ms(L, O, R)
120 ms(K, N, Q)
Inst.(J, M, P)
Figure 6. Ground Fault Delay Response Curve (LSG, LSIG)—Curve Number TC01203004E, March 2012
Digitrip 310+ Circuit Breaker time/Current Curves (Ground Current)
Series G J-Frame Circuit Breakers
Catalog types: JGE, JGS, and JGH circuit breakers, two- three- and four-pole .
Trip Unit Types: 35 (LSG), 36 (LSIG)
note: Refer to table below for variations .
available Sensors (In): 50A 100A 160A 250A
SD/GF Delay Settings table
Ground Fault Delay Response notes:
1 . Curve accuracy applies from –20°C to +55°C ambient . For possible continuous ampere derating for ambient above 40°C, refer to Eaton . Temperatures above +85°C cause an over-temperature protection trip .
2 . Application frequency is 50/60 Hertz .
3 . Trip units are suitable for functional eld testing with test kit CAT # MTST230V .
4 . For testing information, please contact Eaton .
t
t
g
sd
(ms)
(ms)
120KNQ
300LOR
* Inst.JMP
120300
Settings
Inst.
8
Time Current Curves TD012027ENEffective April 2014
Series GJ-Frame
eaton www.eaton.com
0.001
0.01
0.1
1
10
100
1000
10000
000010001001011
Tim
e in
Sec
on
ds
Current in Multiples of Rated Current
Maximum
Minimum
10x +30% -20%
Interrupting Rating Determines End of Curve
Maximum Interrupting Time
5x+30%-20%
Peak Let-Through Current (Ip), kA
100
kA
50 k
A
10 k
A
5 kA
1 kA
1 kA
100
kA50
kA
10 k
A5
kA
1000
kA
200
kA
Ava
ilab
le S
ho
rt-C
ircu
it C
urr
ent,
kA
rm
s
Ava
ilab
le Ip
fo
r 1s
t sy
mm
. 1/2
cyc
le
LGX
3600
JGX
3250
EG
C31
25
EG
C C
L100
A
LGX
3600
JGX
3250
EG
C31
25
EG
C C
L 10
0A
Peak Let-Through I2t, A2 sec
10,0
00,0
00
5,00
0,00
0
1,00
0,00
0
500,
000
100,
000
10,0
00
1 kA
100
kA50
kA
10 k
A5
kA
1000
kA
200
kA
Ava
ilab
le S
ho
rt-C
ircu
it C
urr
ent,
kA
rm
s
Figure 7. Thermal/Magnetic JGE, JGS, JGH, JGC, JGU, and JGX 2, 3, and 4 pole circuit breakers
thermal-Magnetic Circuit Breaker time/Current Curves (Phase Current)
Series G J-Frame Circuit Breakers
Catalog types: JGE, JGS, JGH, JGC, JGU, and JGX, two- three- and four-pole circuit breakers .
For application and coordination purposes only . Based on cold start at rated ambient temperature . Connected with four (4) feet of rated wire (60/75°C) per terminal with all poles wired in series . Tested in open air .
Maximum Voltage: 690V, AC (50/60 Hz) 250V, DC
JGE 65 25 18 10JGS 85 35 18 22JGH 100 65 25 42JGC 200 100 35 42JGU 200 150 50 50JGX 200 200 50 50
Breaker Rating
RatedAmperes (In)
Instantaneous TripAmperes
63-250 500 to 1000% of trip unit rating (DC values are approximately 40% higher)
Interrupting Rating
UL/CSA rms Sym. kA, 50/60 Hz kA, DCBreaker Type 240V 480V 600V 250V
IEC 60947-2 rms Sym. kA, 50/60 Hz kA, DCBreaker Type 240V, (Ue) 415V, (Ue) 690V (Ue) 250V, (Ue)
Icu Ics Icu Ics Icu Ics Icu IcsJGE 65 65 25 25 12 6 10 10JGS 85 85 40 40 12 6 22 22JGH 100 100 70 53 14 7 22 22JGC 200 200 100 100 16 12 42 42JGU 200 200 150 150 18 14 50 50JGX 300 200 200 200 18 14 50 50
9
Time Current Curves TD012027ENEffective April 2014
Series GJ-Frame
eaton www.eaton.com
Peak Let-Through Current (Ip), kA
100
kA
50 k
A
10 k
A
5 kA
1 kA
1 kA
100
kA50
kA
10 k
A5
kA
1000
kA
200
kA
Ava
ilab
le S
ho
rt-C
ircu
it C
urr
ent,
kA
rm
s
Ava
ilab
le Ip
fo
r 1s
t sy
mm
. 1/2
cyc
le
LGX
3600
JGX
3250
EG
C31
25
EG
C C
L100
A
LGX
3600
JGX
3250
EG
C31
25
EG
C C
L 10
0A
Peak Let-Through I2t, A2 sec
10,0
00,0
00
5,00
0,00
0
1,00
0,00
0
500,
000
100,
000
10,0
00
1 kA
100
kA50
kA
10 k
A5
kA
1000
kA
200
kA
Ava
ilab
le S
ho
rt-C
ircu
it C
urr
ent,
kA
rm
s
Figure 9. Peak Let-Through I2t Series G Types LGX, JGX, EGC, and EGC CL (with Current Limiter), Molded-Case Circuit Breakers—240V—Curve Number TC01200001E-A, April 2012
Figure 8. Peak Let-Through Current Series G Types LGX, JGX, EGC, and EGC CL (with Current Limiter), Molded-Case Circuit Breakers—240V—Curve Number TC01200001E-A, April 2012
notes: All values are typical .
JGH
CL
250A
LG
X36
00
JGX
3250
10 k
A
100
kA
50 k
A
5 kA
1
kA
500
kA
1000
kA
10 k
A
100
kA
50 k
A
5 kA
1 kA
Ava
ilab
le Ip
fo
r 1s
tsy
mm
. 1/2
cyc
le
Ava
ilab
le S
ho
rt-C
ircu
it C
urr
ent,
kA
rm
s
Peak Let-Through Current (Ip), kA
EG
C31
25
EG
C C
L 10
0A
10,0
00,0
00
5,00
0,00
0
1,00
0,00
0
500,
000
100,
000
1 kA
5
kA
10 k
A
1000
kA
50
0 kA
10
0 kA
50
kA
Ava
ilab
le S
ho
rt-C
ircu
it C
urr
ent,
kA
rm
s
Peak Let-Through I2t, A2 sec
JGH
CL
250A
LGX
3600
JGX
3250
EG
C31
25 E
GC
CL
100A
10
Time Current Curves TD012027ENEffective April 2014
Series GJ-Frame
eaton www.eaton.com
Peak Let-Through Current (Ip), kA
Ava
ilab
le S
ho
rt-C
ircu
it C
urr
ent,
kA
rm
s
LGC
3600
JGH
CL
250A
JGX
3250
EG
C31
25
EG
C C
L 10
0A
10 k
A
100
kA
50 k
A
5 kA
1 kA
10 k
A
100
kA
50 k
A
5 kA
1
kA
500
kA
1000
kA
Ava
ilab
le lp
fo
r 1s
tsy
mm
. 1/2
cyc
le
Ava
ilab
le S
ho
rt-C
ircu
it C
urr
ent,
kA
rm
s
JGH
CL
250A
LGC
3600
JGX
3250
EG
C31
25
EG
C C
L 10
0A
10 k
A
100
kA
50 k
A
5 kA
1
kA
500
kA
1000
kA
10,0
00,0
00
100,
000
500,
000
1,00
0,00
0
500,
000
Peak Let-Through I2t, A2 sec
notes: All values are typical .
Figure 11. Peak Let-Through I2t Series G Types LG, JG, JG CL, EG, and EG CL (with Current Limiter), Molded-Case Circuit Breakers—480V—Curve Number TC01200001E-B, April 2012
Figure 10. Peak Let-Through Current Series G Types LG, JG CL, JG, EG, and EG CL (with Current Limiter), Molded-Case CircuitBreakers—480V—Curve Number TC01200001E-B, April 2012
JGH
CL
250A
LG
X36
00
JGX
3250
10 k
A
100
kA
50 k
A
5 kA
1
kA
500
kA
1000
kA
10 k
A
100
kA
50 k
A
5 kA
1 kA
Ava
ilab
le Ip
fo
r 1s
tsy
mm
. 1/2
cyc
le
Ava
ilab
le S
ho
rt-C
ircu
it C
urr
ent,
kA
rm
s
Peak Let-Through Current (Ip), kA
EG
C31
25
EG
C C
L 10
0A
10,0
00,0
00
5,00
0,00
0
1,00
0,00
0
500,
000
100,
000
1 kA
5
kA
10 k
A
1000
kA
50
0 kA
10
0 kA
50
kA
Ava
ilab
le S
ho
rt-C
ircu
it C
urr
ent,
kA
rm
s
Peak Let-Through I2t, A2 sec
JGH
CL
250A
LGX
3600
JGX
3250
EG
C31
25 E
GC
CL
100A
11
Time Current Curves TD012027ENEffective April 2014
Series GJ-Frame
eaton www.eaton.com
Figure 13. Peak Let-Through I2t Series G Types LG, JG, JG CL, EG, and EG CL (with Current Limiter), Molded-Case Circuit Breakers—600V—Curve Number TC01200001E-C, April 2012
Figure 12. Peak Let-Through Current Series G Types LG, JG CL, JG, EG, and EG CL (with Current Limiter), Molded-Case CircuitBreakers—600V—Curve Number TC01200001E-C, April 2012
notes: All values are typical .
1 kA
5 kA
10 k
A
100
kA
50 k
A 1
kA
5 kA
10
kA
10
0 kA
50
kA
50
0 kA
1000
kA
Ava
ilab
le S
ho
rt-C
ircu
it C
urr
ent,
kA
rm
s
Ava
ilab
le Ip
fo
r 1s
tsy
mm
. 1/2
cyc
le
Peak Let-Through Current, kA
JG C
L 25
0A
1 kA
5
kA
10 k
A
1000
kA
500
kA
100
kA
50 k
A
1,00
0,00
0
10,0
00,0
00
5,00
0,00
0
500,
000
100,
000
Peak Let-Through I2t, A2 sec
JG C
L 25
0A
Ava
ilab
le S
ho
rt-C
ircu
it C
urr
ent,
kA
rm
s
12
Time Current Curves TD012027ENEffective April 2014
Series GJ-Frame
eaton www.eaton.com
Figure 14. Series G Types JG CL Molded-Case Circuit Breakers—690V
Figure 15. Series G Types JG CL Molded-Case Circuit Breakers—690V
notes: All values are typical .
13
Time Current Curves TD012027ENEffective April 2014
Series GJ-Frame
eaton www.eaton.com
Maximum Available Fault Current
JGC/250A 18 510,000 20 560,000 24 610,000 27 700,000 N/A N/A N/A N/AJGU/250A 18 510,000 20 560,000 24 610,000 27 700,000 29 750,000 N/A N/AJGX/250A 18 510,000 20 560,000 24 610,000 27 700,000 29 750,000 32 800,000
Ip (kA) I2T (A2 sec) Ip (kA) I2T (A2 sec) Ip (kA) I2T (A2 sec) Ip (kA) I2T (A2 sec) Ip (kA) I2T (A2 sec) Ip (kA) I2T (A2 sec)
Frame/Max.Amperes (UL)
35 kA 42 kA 65 kA 100 kA 150 kA 200 kA
Figure 26. 240V Peak Let-Through (Ip) and Clearing (I2t) Values for Series G High-Performance Breakers
Maximum Available Fault Current
JGC/250A 24 1,300,000 28 1,500,000 32 1,700,000 36 1,800,000 N/A N/A N/A N/AJGU/250A 24 1,300,000 28 1,500,000 32 1,700,000 36 1,800,000 40 2,100,000 N/A N/AJGX/250A 24 1,300,000 28 1,500,000 32 1,700,000 36 1,800,000 40 2,100,000 44 2,300,000JGH CL/250A 26 1,300,000 31 1,400,000 34 1,500,000 40 1,700,000 45 1,900,000 48 2,000,000
Ip (kA) I2T (A2 sec) Ip (kA) I2T (A2 sec) Ip (kA) I2T (A2 sec) Ip (kA) I2T (A2 sec) Ip (kA) I2T (A2 sec) Ip (kA) I2T (A2 sec)
Frame/Max.Amperes (UL)
35 kA 50 kA 65 kA 100 kA 150 kA 200 kA
Figure 27. 480V Peak Let-Through (Ip) and Clearing (I2t) Values for Series G High-Performance Breakers
Maximum Available Fault Current
JGC/250A 25 1,900,000 N/A N/A N/A N/AJGU/250A 25 1,900,000 30 2,300,000 N/A N/AJGX/250A 25 1,900,000 30 2,300,000 N/A N/AJGH CL/250A 29 1,600,000 34 1,800,000 37 1,900,000
Ip (kA) I2T (A2 sec) Ip (kA) I2T (A2 sec) Ip (kA) I2T (A2 sec)
Frame/Max.Amperes (UL)
35 kA 50 kA 65 kA
Figure 28. 600V Peak Let-Through (Ip) and Clearing (I2t) Values for Series G High-Performance Breakers
notes: All values are typical .
Maximum Available Fault Current
JGH CL/250A 23 1,600,000 38 2,500,000 43 3,200,000
Ip (kA) I2T (A2 sec) Ip (kA) I2T (A2 sec) Ip (kA) I2T (A2 sec)
Frame/Max.Amperes (IEC)
18 kA 50 kA 70 kA
Figure 29. 690V Peak Let-Through (Ip) and Clearing (I2t) Values for Series G High-Performance Breakers
1000
.001
.002
.003
.004
.005
.006
.007
.008
.009
.01
.02
.03
.04
.05
.06
.07
.08
.09
.1
.2
.3
.4
.5
.6
.7
.8
.91.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.010.0
100.090.0
80.0
70.0
60.0
50.0
40.0
30.0
20.0
200.0
300.0
400.0
500.0
600.0
700.0
800.0
900.0
TIM
E IN
SE
CO
ND
S
1000
.001
.002
.003
.004
.005
.006
.007
.008
.009
.01
.02
.03
.04
.05
.06
.07
.08
.09
.1
.2
.3
.4
.5
.6
.7
.8
.91.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.010.0
100.090.0
80.0
70.0
60.0
50.0
40.0
30.0
20.0
200.0
300.0
400.0
500.0
600.0
700.0
800.0
900.0
IT
ME
NIS
DN
OC
ES
Ig(A)
1031.3.1Available Ig(A) Settings.
1S
500ms
300ms
150ms
60ms
Inst
.03
.01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1.0 2 3 4 5 7 10
.01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1.0 2 3 4 5 7 10
14
Time Current Curves TD012027ENEffective April 2014
Series GJ-Frame
eaton www.eaton.com
Figure 16. UL JG Circuit Breaker Earth Leakage Module, Three- and Four-Pole, 110-480V - Curve Number TC01204004E, March 2003
Circuit Breaker time/Current Curves (Phase Current)
earth Leakage JG Circuit Breakers—UL
Catalog types: ELJBN circuit breakers, three- and four-pole .
notes:
1 . JG250 Circuit Breaker Earth Leakage Module, 3and 4 Poles, 110 - 480V 50/60Hz .
2 . For application and coordination purposes only . -20C to 55C ambient .
3 . Total clearing times include the response time of the Earth Leakage module, opening time of the circuit breaker, and interruption of current .
4 . For additional curve tolerances, contact Eaton .
15
Time Current Curves TD012027ENEffective April 2014
Series GJ-Frame
eaton www.eaton.com
1000
.001
.002
.003
.004
.005
.006
.007
.008
.009
.01
.02
.03
.04
.05
.06
.07
.08
.09
.1
.2
.3
.4
.5
.6
.7
.8
.91.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.010.0
100.090.0
80.0
70.0
60.0
50.0
40.0
30.0
20.0
200.0
300.0
400.0
500.0
600.0
700.0
800.0
900.0
TIM
E IN
SE
CO
ND
S
1000
.001
.002
.003
.004
.005
.006
.007
.008
.009
.01
.02
.03
.04
.05
.06
.07
.08
.09
.1
.2
.3
.4
.5
.6
.7
.8
.91.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.010.0
100.090.0
80.0
70.0
60.0
50.0
40.0
30.0
20.0
200.0
300.0
400.0
500.0
600.0
700.0
800.0
900.0
IT
ME
NIS
DN
OC
ES
1031.3.1
1S
500ms
300ms
150ms
60ms
Inst
.01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1.0 2 3 4 5 7 10
.01 .02 .03 .04 .05 .07 .1 .2 .3 .4 .5 .7 1.0 2 3 4 5 7 10
Available I n settings
I n
.03
(Amperes)
Figure 17. IEC JG Circuit Breaker Earth Leakage Module, Three- and Four-Pole, 110-480V - Curve Number TC01205001E, March 2003
Circuit Breaker time/Current Curves (Phase Current)
earth Leakage JG Circuit Breakers—UL
Catalog types: ELJBE circuit breakers, three- and four-pole .
notes:
1 . JG250 Circuit Breaker Earth Leakage Module, 3 and 4 Poles, 110 - 480V 50/60Hz .
2 . For application and coordination purposes only . -20C to 55C ambient .
3 . Total clearing times include the response time of the Earth Leakage module, opening time of the circuit breaker, and interruption of current .
4 . For additional curve tolerances, contact Eaton .
Eaton1000 Eaton BoulevardCleveland, OH 44122United StatesEaton .com
© 2014 EatonAll Rights ReservedPrinted in USAPublication No . TD012027EN / KDCApril 2014
Eaton is a registered trademark .
All other trademarks are property of their respective owners .
Series GJ-Frame
Time Current Curves TD012027ENEffective April 2014