One-Line Diagram - OLV1 (Short-Circuit Analysis) page 1 19:42:55 Feb 11, 2015 Project File: NMC speciality hospital THREE PHASE FAULT RESULT Bus2 0.415 kV 0 kV 0 33.27 kA -67.1 Bus4 0.415 kV 0 kV 0 33.27 k A -67.1 ± ± ± ± ± ± ± NMC hospital SWS bus B 11 kV 0 kV 0 8.32 kA -62.7 SE44PRY1 11 kV 0 kV 0 16.4 kA -84.3 NMC hospital sws BUS A 11 kV 0 kV 0 8.32 kA -62.7 Cable3 I> R Cable5 I> R R T1 1.5 MVA R T3 1.5 MVA R 33.27 U1 312 MVAsc 16.4 33.27 Open Bus2 0.415 kV 0 kV 0 33.27 kA -67.1 NMC hospital sws BUS A 11 kV 0 kV 0 8.32 kA -62.7 SE44PRY1 11 kV 0 kV 0 16.4 kA -84.3 NMC hospital SWS bus B 11 kV 0 kV 0 8.32 kA -62.7 8.32 Cable3 8.32 8.32 Cable5 8.32 Open Bus4 0.415 kV 0 kV 0 33.27 k A -67.1 T1 1.5 MVA 33.27 T3 1.5 MVA U1 312 MVAsc 16.4 33.27
description
OK
Transcript of Three Phase Short Circuit Result
One-Line Diagram - OLV1 (Short-Circuit Analysis)
page 1 19:42:55 Feb 11, 2015 Project File: NMC speciality hospital
THREE PHASE
FAULT RESULT
Bus2
0.415 kV 0 kV 0
33.27 kA -67.1
Bus4
0.415 kV 0 kV 0
33.27 kA -67.1
±
± ±
±
±
±
±
NMC hospital SWS bus B
11 kV 0 kV 0
8.32 kA -62.7
SE44PRY1
11 kV 0 kV 0
16.4 kA -84.3
NMC hospital sws BUS A
11 kV 0 kV 0
8.32 kA -62.7
Cable3
I>
R
Cable5
I>
R
R
T1
1.5 MVA
R
T3
1.5 MVA
R
33.27
U1
312 MVAsc
16.4
33.27
Open
Bus2
0.415 kV 0 kV 0
33.27 kA -67.1
NMC hospital sws BUS A
11 kV 0 kV 0
8.32 kA -62.7
SE44PRY1
11 kV 0 kV 0
16.4 kA -84.3
NMC hospital SWS bus B
11 kV 0 kV 0
8.32 kA -62.7
8.32
Cable3
8.32 8.32
Cable5
8.32
Open
Bus4
0.415 kV 0 kV 0
33.27 kA -67.1
T1
1.5 MVA
33.27
T3
1.5 MVA
U1
312 MVAsc
16.4
33.27