Power RPC Quick Reference - RPC Technologies --- Netbula RPC ONC
THREE PHASE GRID CONNECTED PV SYSTEM WITH LVRT …€¦ · the inverter. Based on this theory, the...
Transcript of THREE PHASE GRID CONNECTED PV SYSTEM WITH LVRT …€¦ · the inverter. Based on this theory, the...
http://www.iaeme.com/IJMET/index.asp 579 [email protected]
International Journal of Mechanical Engineering and Technology (IJMET) Volume 9, Issue 7, July 2018, pp. 579–585, Article ID: IJMET_09_07_061
Available online at http://www.iaeme.com/ijmet/issues.asp?JType=IJMET&VType=9&IType=7
ISSN Print: 0976-6340 and ISSN Online: 0976-6359
© IAEME Publication Scopus Indexed
THREE PHASE GRID CONNECTED PV SYSTEM
WITH LVRT CONTROL STRATEGY
T. MURALI KRISHNA
Assistant Professor, Dept. of EEE, CBIT, Gandipet, Hyderabad
DEEPAK GEHLOT
Manager, BHEL R&D, Hyderabad
N. ANUSHA
P.G. Student, Dept. of EEE, CBIT, Gandipet, Hyderabad
G. SURESH BABU
Professor, Dept. of EEE, CBIT, Gandipet, Hyderabad
ABSTRACT
In power system the transient short circuit faults result in low voltages in the lines.
Due to this, performance of the loads connected to the grid will be affected. In order
to maintain constant grid voltage during transient faults, reactive power must be
controlled accordingly.
In order to supply the required reactive power during dynamic fault condition,
conventionally Distribution Static Synchronous Compensator (D-STATCOM), Unified
power flow controller (UPFC), Unified Power Quality Conditioner (UPQC) etc. were
proposed. In order to reduce the installation and operating cost, Low Voltage Ride
through (LVRT) is one of the upcoming technique to supply the necessary reactive
power during low voltage condition. In this technique a Photo Voltaic (PV) system
should stay connected to the grid and injects reactive power in order to maintain
constant grid voltage during fault conditions. After the grid voltage recovers to its
nominal value, the PV system needs to provide real power as fast as possible, so as to
maintain real power balance which therefore helps the whole system recovery.
Keywords: PV system, LVRT, GRID, Short circuit faults.
Cite this Article: T. Murali Krishna, Deepak Gehlot, N. Anusha and G. Suresh Babu,
Three Phase Grid Connected PV System with LVRT Control Strategy, International
Journal of Mechanical Engineering and Technology, 9(7), 2018, pp. 579–585
http://www.iaeme.com/IJMET/issues.asp?JType=IJMET&VType=9&IType=7
Three Phase Grid Connected PV System with LVRT Control Strategy
http://www.iaeme.com/IJMET/index.asp 580 [email protected]
1. INTRODUCTION
In recent years, more efforts have been made on the integration of PV systems into the grid in
order to meet the imperative demand of a clean and reliable electricity generation. Electric
power generation through solar energy process is one of the more methods available at the
moment, during the operation of solar energy systems do not generate any greenhouse gas
pollution of the environment. The high penetration of PV energy into the power system has
resulted in power system operators revising the grid codes requirements for interconnection of
this type of generation [1].
With this increased penetration of Distributed Generation (DG) systems into grid, fault
tolerance of these DG systems became one of major concerns as the sudden tripping of DG
from grid during faults results in serious problems such as voltage flickers, power outages and
may even cause blackout. Hence high power DG systems must be considered as conventional
systems and they need to support grid even during fault conditions. [2].
A special focus in these requirements is drawn to the PV fault ride-through capability
(LVRT), which addressed primarily the design of the PV controller in such that PV is able to
remain connected to the network during abnormal operation condition as well as can
contribute to voltage support during and after the abnormal operation conditions[3-5].
According to the theory of instantaneous reactive power, the active and reactive currents
of inverter can be regulated by changing the amplitude and the phase of the output voltage of
the inverter. Based on this theory, the active power output and the reactive power
compensation (RPC) of the system are realized simultaneously at daylight. When the
insolation is weak or the PV modules are inoperative at night, the RPC feature of PV system
can still be used to improve the utilization factor of the system [6].
In grid-connected systems, with an electrolytic capacitor in the dc-link, the oscillations of
the dc-link voltage with Distributed generator facility (DGF) can deteriorate the capacitor
lifetime, and thus the entire system. The proposed Low-Voltage Ride- through (LVRT)
control strategy benefits from a reference current generation method, which can eliminate the
oscillations at the dc-link and in the active power during unbalanced voltage dips [7-8].
2. STRUCTURE OF GRID CONNECTED VOLTAGE SOURCE
CONVERTER
Grid connected converters find application in a wide variety of fields such as distributed
generation, Active power filters, UPF rectifiers, HVDC systems etc. These converters works
as inverters when the power flow is from the dc side to ac side and vice versa when they
operate as rectifiers. The control capabilities and the structure of these converters are very
much generic irrespective of the mode of operation, except the direction of power flow. The
general structure of grid connected voltage source converter (VSC) is shown in Figure 1.
Figure 1 General structure of control of grid connected converter
Decision Support Systems- An overview
http://www.iaeme.com/IJMET/index.asp 581 [email protected]
A very important feature of grid side converter control is the grid synchronization. The
synchronization algorithm is able to detect the phase angle of grid voltage in order to
synchronize the delivered power. The purpose of this method is to synchronize the inverter
output current with the grid voltage, in order to obtain a unity power factor. The PLL is
shown in below Figure 2.
Figure 2 Basic structure for the SRF PLL system
Input is the three phase voltages measured on the grid side and the output is the tracked
phase angle. The PLL model is implemented in synchronous dq reference frame, where a Park
transformation is used. The phase-locking of the system is realized by adjusting the q-axis
voltage to zero or d–axis to zero. A PI controller is used for this purpose. By integrating the
sum between the PI output and the reference frequency the phase angle is obtained.
The phase angle θ is tracked by synchronizing the voltage space vector along q or d axis
in the Synchronous rotating reference frame. Here the voltage space vector is synchronized
with the q-axis.
3. LVRT CONTROL STRATEGY
The SEG system comprises photovoltaic (PV) arrays, a power conversion system, grid-side
inverter, a filter, and a three-phase grid. If the grid voltage drops in the solar energy
generation (SEG) system, reactive power is injected in the grid-side inverter by PV system. In
the SEG system, the LVRT control strategy with maximum power generation is widely used.
Using the LVRT control strategy, the q-axis current (Iq) required for injecting the reactive
power into the grid having a low voltage is determined based on the LVRT requirement
depending on the level of low voltage.
The rotating reference frame method, also called d-q control, is widely used in three-phase
systems. Rotating reference frame regulators have become industry standard in the field of
high-performance current-control methods. Vector control is performed entirely in the
rotating d-q coordinate system to make the controller side elegant for a wide range of
applications. The method for determining the injection quantity of the active and reactive
currents depends on the voltage drop ratio of the three-phase grid. The voltage-level (VLEVEL)
of the three-phase grid is calculated by the voltage-level calculation process using the three-
phase grid voltages Va, Vb and Vc. VLEVEL is classified into three parts depending on the
LVRT requirement of the grid-code regulations, and the method for determining the injection
quantity of the active and reactive currents is selected by each part as shown in Figure 3.
Figure 3 Method for determining the injection quantity of the active and reactive currents depending
on the voltage drop ratio of the 3-phase grid
Three Phase Grid Connected PV System with LVRT Control Strategy
http://www.iaeme.com/IJMET/index.asp 582 [email protected]
If VLEVEL is greater than 90% of the three-phase grid voltage under normal conditions, the
reactive current injected into the three-phase grid is zero, and the active current becomes the
reference current. If VLEVEL is greater than 50% but less than 90% of the three-phase grid
voltage, then reactive current to be injected into the three-phase grid is determined based on
the voltage drop ratio of the three-phase grid. In addition, the active current is calculated using
the reactive current and the rating current of the grid-connected ESS. If VLEVEL is less than
50% of the three-phase grid voltage, the reactive current injected into the three-phase grid is
the rating current of the grid-connected ESS, and the active current is zero.
4. RESULTS
The system consists of a 3-phase grid, battery and a LCL filter. An LCL filter is used to
interconnect an inverter to the utility grid in order to filter the harmonics produced by the
inverter. A PLL is used to synchronise the phase angle of the inverter with grid voltage. A
Closed loop vector current control is used to generate reference signals to the inverter.
Decoupling is used to independent control of active and reactive power. From the voltage
level Vd, the reference active current and the reference reactive current is controlled according
to the depth of voltage sags. The block diagram of 3-phase grid connected PV system with
LVRT is shown in Figure 4.
Figure 4 3-phase grid connected VSC with LVRT
Figure 5 Inverter voltages & currents at grid voltage 320V
Decision Support Systems- An overview
http://www.iaeme.com/IJMET/index.asp 583 [email protected]
Figure 6 Inverter Active & Reactive power waveforms at grid voltage 320V
The Figure 5 & Figure 6 shows the Closed Loop Grid Connected PV System, inverter
voltage and current waveforms for a Grid voltage of 320V and DC voltage of 650V, Active
power of 500kW. Consider Base voltage as 320V, and Base power 500kVA. In normal
operating condition the Active power delivered is 500kW, and Reactive power is 0 kVAr.
Figure 7 Inverter voltages & currents at grid voltage 240V
Figure 8 Inverter Active & Reactive power waveforms at grid voltage 240V
The waveforms Figure 7 & Figure 8 shows, the Active power is 320kW, Reactive power
is 180kVAr during fault condition, for grid voltage 240V,
Figure 9 Inverter voltages with & without LVRT during normal operating condition.
Three Phase Grid Connected PV System with LVRT Control Strategy
http://www.iaeme.com/IJMET/index.asp 584 [email protected]
The inverter voltages with & without LVRT during normal operating condition is shown
in Figure 9. During normal operating condition, the inverter voltages are same in both the
circuits, with and without LVRT. The voltages are taken in per unit. The base value is 320V.
Figure 10 Inverter currents with & without LVRT during normal operating condition.
The inverter currents with & without LVRT during normal operating condition is shown
in Figure 10. During normal operating condition, the inverter currents are more without
LVRT and within the limit during LVRT. The excessive over currents through inverter are
controlled with LVRT.
Figure 11 Active power with & without LVRT during normal operating condition
The Active power with & without LVRT during normal operating condition is shown in
Figure 11. During normal operating condition, the active power delivered is 1.2 pu without
LVRT, and with LVRT the active power delivered is 1.6 pu. The active power delivered to
the load is more with LVRT.
Figure 12 Reactive power with & without LVRT during normal operating condition.
The Reactive power with & without LVRT during normal operating condition is shown in
Figure 12. During normal operating condition, the reactive power delivered is 1.8 pu, without
LVRT, and with LVRT the reactive power delivered is 0 pu. The Reactive power delivered to
the load is less with LVRT during healty condition.
5. CONCLUSION
The proposed control enables the PV system to generate a reactive power during fault to
support the grid. This helps the grid to maintain voltage stability during fault. Reactive power
is provided to support voltage recovery according to the depth of grid voltage sags. After the
grid voltage recovers to its nominal value, the PV system provides real power as fast as
possible, so as to maintain real power balance which therefore helps the whole system
recovery.
Decision Support Systems- An overview
http://www.iaeme.com/IJMET/index.asp 585 [email protected]
REFERENCES
[1] Yanan Liu and Lijun Tian, “Research on Low Voltage Ride Through Technology of Grid-
Connected Photovoltaic System” International Conference on Smart Grid and Clean
Energy Technologies, IEEE 2016.
[2] B.V.V.N. Manikanta, G. Kesavarao and Shefali Talati, "LVRT of Grid Connected PV
System with Energy Storage", International Journal of Control Theory and Applications
2017.
[3] Gazi M.S. Islam, and Ahmed Al Durra, “LVRT Capability Improvement of a Grid-
connected PV Park by Robust Sliding Mode Control” American Control Conference
(ACC), pp 1002-1009,2015.
[4] Yeongsu Bak , June-Seok Lee and Kyo-Beum Lee, "Low-Voltage Ride-Through Control
Strategy for a Grid-Connected Energy Storage System", Applied Sciences 2018.
[5] Huajun Yu, Junmin Pan, An Xiang, "A multi-function grid-connected PV system with
reactive power compensation for the grid", ELSEVIER, Vol. 79, pp. 101-106.
[6] Ehsan Afshari, Babak Farhangi, Yongheng Yang, Shahrokh Farhangi, "A Low-Voltage
Ride-Through Control Strategy for Three-Phase Grid-Connected PV Systems", IEEE
2017.
[7] MG Molina, PE Mercado, "Modeling and control of grid-connected photovoltaic energy
conversion system used as a dispersed generator", Transmission and Distribution
Conference 2008.
[8] Gaurav Tembhurnikar, Ajit Chaudhari, Nilesh Wani, Atul Gajare, Pankaj Gajare, "A
Review on Reactive Power Compensation Techniques using FACTS Devices",
International Journal of Engineering and Management Research, Vol. 4, pp.76-80, 2014.
[9] Sheeraz Kirmani and Mohammad Kalimullah, Estimation of Energy Pay-Back Time and
Air Pollution Mitigation Potential of A 25-KWP Grid Connected Rooftop Solar
Photovoltaic System. International Journal of Electrical Engineering & Technology, 8(4),
2017, pp. 1–8.
[10] Dr. Y. L. ChandraShekar and Dr. P.S. Puttaswamy, Design and Simulation of Improved
Dc-Dc Converters Using Simulink For Grid Connected Pv Systems. International Journal
of Electronics and Communication Engineering and Technology, 8(6), 2017, pp. 62–71.
[11] Mihail Hristov Antchev, Hristo Mihailov Antchev, Mariya Petkova Petkova and Angelina
Mihaylova Tomova, Computer Investigation Of Three Phase Clarke-Maximum
(Maximum P, Q) Trigonometrical Pll For Grid Connected Power Converters, International
Journal of Electronics and Communication Engineering & Technology (IJECET), Volume
5, Issue 1, January (2014), pp. 119-129.
[12] Reshmi Krishnan S and Soniya Raju, Simulation Analysis on Grid Connected Inverter.
International Journal of Advanced Research in Engineering and Technology, 9(2), 2018,
pp 77–86.
[13] T. Narasimha Prasad and G. Viswanath, Fault Analysis on Three Phase Three Level
Svpwm Based Grid Connected Photovoltaic System, International Journal of Electrical
Engineering and Technology (IJEET), Volume 5, Issue 1, January (2014), pp. 54-65.