6
3M Fire Protection Products Fire Barrier Protective Wraps “Outside the box” thinking is often ahead of its time; and the continued growth of the 3M Fire Rated Duct Wrap line which was introduced over ten years ago is proof. We know space and time are at a premium on the job site. With 3M’s range of products and approved applications, these products provide a smart alternative to the time, labor, weight, and bulk of gypsum wallboard shafts; and the bulk and stiffness of other wrap systems. The result: • Architects get expanded design options • Building owners and inspectors get the confidence of using tested systems to meet code • Contractors can help increase productivity on the job site And because 3M is the fire protection industry leader, you can trust our innovative technologies will help protect people and property for decades to come. Box Thinking Outside The

Transcript of Thinking Outside TheBox - 3Mmultimedia.3m.com/mws/media/229181O/3mtm-fire-barrier...3MU/FRD 120-05...

3M Fire Protection ProductsFire Barrier Protective Wraps

Surface Burning Characteristics (ASTM E 84 for 15A, 20A, 5A) Product Flame Spread Smoke DevelopedFoil Encapsulated Blanket 0 0Blanket 0 0

“Outside the box” thinking is often ahead of its time; and the continued growth of

the 3M™ Fire Rated Duct Wrap line which was introduced over ten years ago is

proof. We know space and time are at a premium on the job site. With 3M’s range

of products and approved applications, these products provide a smart alternative

to the time, labor, weight, and bulk of gypsum wallboard shafts; and the bulk and

stiffness of other wrap systems. The result:

• Architects get expanded design options

• Building owners and inspectors get the confidence of using

tested systems to meet code

• Contractors can help increase productivity on the job site

And because 3M is the fire protection industry leader, you can trust our innovative

technologies will help protect people and property for decades to come.

Box

ThinkingOutside

The

3M™ Fire Barrier Duct Wrap 615 & Accessories 3M recognizes the need to fire protect the integrity of stair pressurization ducts, life safety

ducts and smoke exhaust systems. Fire compartmentation and the continued operation of life

safety duct systems are essential for building occupants to allow fire service personnel to

do their job safely when they arrive on the scene. But our drive to protect doesn’t stop there.

We want to help make sure the people who install these life saving systems are safer during

installation. That’s why we created the new 3M™ Fire Barrier Duct Wrap 615 series. Unlike

traditional refractory ceramic fibers used in most common fire barrier wraps, these unique

wraps are created with man-made vitreous spun fibers. This gives them lower biopersistence1

and allows them to perform up to 2192˚F (1200˚C), which means you can help protect both

the people who build the structures as well as those who

inhabit and protect them later.

1 Has been demonstrated to be soluble in the lungs according to EU guidelines 97/69/EC. Note Q for biopersistance.

Life Safety and Smoke Management Air Duct Applications

Advantages• Lighter weight for easier installation

• Stitched for maximum application ease

• Low thermal conductivity

• Supports maximum temperatures of up

to 2192°F (1200°C)

• Thermal shock resistant

• Monolithic blanket

• Tested to ISO 6944 Fire Resistance Tests –

Ventilation Ducts

• Safe fiber construction1 for contractor piece of mind

3M™ Fire Barrier Duct Wrap 615

Protecting MorePeople and Places

Partnership in Practice

3M™ Fire Barrier Wraps 15A & 20A Series These mold resistant2, non-asbestos fire resistance wraps are a stitched, patented inorganic

blanket encapsulated with scrim-reinforced foil. The result is an extremely flexible wrap with

high strength which can help increase productivity. Insulation properties protect combustible

construction at zero clearance throughout the entire closure system, providing an alternative,

“outside the box” solution to a 2-hour rated fire-resistance gypsum shaft enclosure.

Advantages

• Passes the rigors of internal grease fire

tests UL 19783 and ASTM E 23364 (AC101)5

• Zero clearance to combustibles throughout

the entire closure system for congested spaces

• Foil encapsulated with unique center overlap seam

for blanket strength, protection, and less dust

• Safe fiber construction1 for contractor peace of mind

Grease Duct Applications

3M™ Fire Barrier Wrap 20A

3M™ Fire Barrier Plenum Wrap 5A Patented inorganic blanket encapsulated with a scrim-reinforced foil. This wrap provides

a flexible, non-combustable enclosure for cables and pipes in return air plenums.

Advantages

• Tested to UL 910 and UL 1887 flammability tests

• Strong, lightweight and flexible material for

easy installation

• Foil encapsulated scrim

Air Plenum Applications

3M™ Fire Barrier Plenum Wrap 5A

1 Has been demonstrated to be soluble in the lungs according to EU guidelines 97/69/EC. Note Q for biopersistance. 2 Tested to ASTM C 1338 standard test method for determining fungi resistance of insulation materials and facings.3 1 – layer 15A 4 2 – layer 15A 5 2 – layer 20A

Think OutsideTheBox

3M's space saving fire barrier wrap.

Traditional bulky protection with gypsum wall shaft.

Note: Consult individual project plans for which codes and standards apply.

Call your 3M customer service representative at 1-800-328-1687, or visit the www.3M.com/firestop to learn how you can start thinking “outside the box” and start protecting more people and places with 3M firestopping products.

3M Fire Barrier Duct Wrap Performance CharacteristicsProduct

Test 615 15A 20A 5A

ASTM C 411 • • •ASTM C 518 • • • •ASTM C 1338 • • • •ASTM E 84 • • •ASTM E 119 • •ASTM E 136 • • •ASTM E 814 • • •ASTM E 2336 • • •ICC ES AC 101 Internal •UL 910 •UL 1887 •UL 1978 (secs. 12 and 13) •ISO 6944 • •

3M Fire Barrier Duct Wrap ApplicationsProduct

615 15A 20A 5A

Grease Duct • •Chemical Duct • •Ventilation Air Duct • •Life Safety Duct (Stair Pressurization, Smoke, Exhaust, etc.)

• •

Plenum Applications •

Surface Burning Characteristics (ASTM E 84) Product Flame Spread Smoke Developed

Fire Barrier Duct Wrap 615 <25 <50

InnovationCode

Approved

Ventilation Air Duct Listings for 615 (tested to ISO 6944)Fire Resistive Rating

Enclosure System

Duct System

Through- Penetration System

Listing Agency

1 or 2 hours

1 layer of 3M™ Fire

Barrier Duct Wrap 615, 3" (76mm)

perimeter and longitudinal

overlaps

V-27 W-L-7180, W-J-7104 UL

3MU/FRD-120-15

3MU/ PH 60-03, 3MU/PV 120-23, 3MU/PV 120-25

Intertek (OPL)

This is only a partial list of systems that use Duct Wrap 615. For complete information visit www.3M.com/firestop.

Code Compliance for 615 NFPA 92A Standard for Smoke-Control System Utilizing Barriers and Pressure Differences, 2006 Edition — Section 6.6.2

NFPA 92B Standard for Smoke Management Systems in Malls, Atria, and Large Spaces, 2005 Edition — Section 7.5.2

NFPA 101® Life Safety Code®, 2006 Edition— Section(s) 8.6.7, 18.7.7

International Mechanical Code®, 2006 Edition — Section 513.10.2

International Building Code®, 2006 Edition — Section 909.10.2 This is only a partial list of code compliance. Go to 3M.com/firestop or speak to your authorized 3M distributor or sales representative at 1-800-328-1687.

Building and Commercial Services Division3M Center, Building 223-2N-21St. Paul, MN 55144-1000Ph. 800-328-16873M.com/firestop

Please recycle. Printed in U.S.A.© 3M 2008. All rights reserved.98-0213-4369-8

Warranty and Limited Remedy. This product will be free from defects in material and manufacture for a period of ninety (90) days from date of purchase. 3M MAKES NO OTHER WARRANTIES INCLUDING, BUT NOT LIMITED TO, ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. User is responsible for determining whether the 3M product is fit for a particular purpose and suitable for user’s application. If the 3M product is proved to be defective within the warranty period stated above, your exclusive remedy and 3M’s obligation, at 3M’s option, to replace or repair the 3M product or refund the purchase price of the 3M product. Limitation of Liability. Except where prohibited by law, 3M will not be liable for any loss or damage arising from a 3M product, whether direct, indirect, special, incidental, or consequential, regardless of the legal theory asserted, including warranty, contract, negligence or strict liability.

3M is a trademark of 3M company. NFPA 101 and Life Safety Code are trademarks of the National Fire Protection Association. International Mechanical Code and International Building Code are trademarks of the International Code Council. All other trademarks are the property of their respective owners.

Grease Duct Listings for 15A and 20AFire Resistive Rating Enclosure System

Duct System, Intertek (OPL) Testing

15A

1 or 2 hours

1 layer of 3M™ Fire Barrier Duct Wrap 15A,

3" (76mm) perimeter and longitudinal overlaps

3MU/FRD 120-06 (GD 532 F)

UL 1978 / ASTM E 119

3MU/FRD 120-07 (GD 538 F)

3MU/FRD 120-08 1(GD 548 F)

3MU/FRD 120-09 (GD 549 F)

2 layers of 3M™ Fire Barrier Duct Wrap 15A, 4" (102mm) perimeter

and 4 in. (102mm) longitudinal overlaps

3MU/FRD 120-13 (GD 556 F) ASTM E 2336 /

ICC ES AC1013MU/FRD 120-14 (GD 557 F)

20A

1 or 2 hours

2 layers of 3M™ Fire Barrier Duct Wrap 20A, 3" (76mm) perimeter

and 3" (76mm) longitudinal overlaps

3MU/FRD 120-05 (GD 531 F) ASTM E 2336 /

ICC ES AC1013MU/FRD 120-12 (GD 547 F)

Chemical Fume Duct Listings for 15A and 20AFire Resistive Rating Enclosure System

Duct System, Intertek (OPL) Testing

15A

1 or 2 hours

1 layer of 3M™ Fire Barrier Duct Wrap 15A,

3" (76mm) perimeter and longitudinal overlaps

3MU/FRD 120-10 (CFD 500 F) UL 1978 /

ASTM E 1193MU/FRD 120-11 (CFD 501 F)

Grease Duct Code ApprovalsFire Resistive Rating Enclosure System

Duct System, Intertek (OPL)

Report Number

1 or 2 hours

1 layer of 3M™ Fire Barrier Duct Wrap 15A, 3" (76mm) perimeter

and longitudinal overlaps

BOCA SBCCI

21-61 2132

2 layers of 3M™ Fire Barrier Duct Wrap 20A, 3" (76mm) perimeter

and longitudinal overlapsICC 1255

Ventilation Air Duct Listings for 15A (tested to ISO 6944)Fire Resistive Rating Enclosure System Duct System, Intertek (OPL)

15A

1 hour

1 layer of 3M™ Fire Barrier Duct Wrap 15A,

3" (76mm) perimeter and longitudinal overlaps

3MU/FRD 120-01 (VAD 529)3MU/FRD 120-02 (VAD 530)3MU/FRD 120-03 (VAD 531)3MU/FRD 120-04 (VAD 542)

2 hours

2 layers of 3M™ Fire Barrier Duct Wrap 15A,

3" (76mm) perimeter and longitudinal overlaps

3MU/FRD 120-01 (VAD 529)3MU/FRD 120-02 (VAD 530)3MU/FRD 120-03 (VAD 531)3MU/FRD 120-04 (VAD 542)

Plenum Wrap Listings for 5A

Enclosure SystemDesign Listing Number, (OPL) Protected Item Testing

1 layer of 3M™ Fire Barrier Plenum Wrap 5A, 1" (25mm) perimeter and

longitudinal overlaps

(PP 100 P)Plastic Pipe: PVC,

CPVC, ABS, PB, PE, PP and PVDF

UL 1887

(PP 101 P)

Cabling with PVC, CPVC, ABS, PB,

PE, PP and PVDF jacketing

UL 910

Availability

Product Roll SizeRoll/ctn.

Wt./ ctn.

3M™ Fire Barrier Duct Wrap 615-24

1.5" x 24" x 25' (38mm x 60.9cm x 762cm) 1 39 lbs.

18 kg.

3M™ Fire Barrier Duct Wrap 615-48

1.5" x 48" x 25' (38mm x 121.9cm x 762cm) 1 79 lbs.

36 kg.

3M™ Fire Barrier Duct Wrap 15A

1.5" x 24" x 20' (38mm x 60.9cm x 609.6cm) 1 53 lbs.

24 kg.

3M™ Fire Barrier Duct Wrap 15A

1.5" x 48" x 20' (38mm x 121.9cm x 609.6cm) 1 106 lbs.

48 kg.

3M™ Fire Barrier Duct Wrap 20A

1.5" x 24" x 20' (38mm x 60.9cm x 609.6cm) 1 70 lbs.

31 kg.

3M™ Fire Barrier Duct Wrap 20A Collar

1.5" x 6" x 20' (38mm x 15.2cm x 609.6cm) 4 140 lbs.

63 kg.

3M™ Fire Barrier Plenum Wrap 5A Collar

.5" x 24" x 50' (38mm x 121.9cm x 1524cm) 1 45 lbs.

20 kg.

3M™ Fire Barrier Plenum Wrap 5A Collar

.5" x 48" x 25' (12.7mm x 121.9cm x 762cm) 2 90 lbs.

40 kg.

Code Compliance for 15A and 20ANFPA 96, 2008 Edition

NFPA 96, 2004 Edition

NFPA 90A, 2002 Edition

Uniform Mechanical Code, 2006 Edition, Section 507.2.4

International Mechanical Code®, 2003 Edition, Section 506.3.10

International Mechanical Code®, 2006 Edition, Section 506.3.10

This is only a partial list of code compliance. Go to 3M.com/firestop or speak to your authorized 3M distributor or sales representative at 1-800-328-1687.

Complies withInternational

Mechanical Code 2006 Edition

Warnock Hersey

INTERTEK

CM

C US

O

MEGA POIN

T

LABORATORIE

SC US

BATTS AND BLANKETSFOR USE IN FIRE RESISTIVE DUCT ASSEMBLIES SEE UL DIRECTORY OF PRODUCTS

CERTIFIED FOR CANADA AND SEE UL FIRE RESISTANCE

DIRECTORY 90G9

DUCT WRAP MATERIALSFOR USE IN THROUGH-

PENETRATION FIRESTOP SYSTEMS SEE UL DIRECTORY

OF PRODUCTS CERTIFIED FOR CANADA AND UL FIRE

RESISTANCE DIRECTORY 90G9

Surface Burning Characteristics (ASTM E 84 for 15A, 20A, 5A) Product Flame Spread Smoke Developed

Foil Encapsulated Blanket 0 0Blanket 0 0

3M’s Grease, Chemical Fume and Ventilation Air Duct listings all have affiliated Through-Penetration design listings that comply with ASTM E 814. Go to 3M.com/firestop or speak to your authorized 3M distributor or sales representative at 1-800-328-1687 for more information.