Thermography Inspection Report Furnace no. F-101 …ITC Level 2 cert. no. 2007ID28N003 Checked by:...

16
Thermography Inspection Report Furnace no. F-101 (Part 2) XYZ Refinery Inspected on Jan.xx, 20yy by: Weerawut Leelawetchabutr ITC Level 2 cert. no. 2007ID28N003 Checked by: Mikael Cronholm ITC Level 3 cert. no. 13973

Transcript of Thermography Inspection Report Furnace no. F-101 …ITC Level 2 cert. no. 2007ID28N003 Checked by:...

Thermography Inspection Report

Furnace no. F-101 (Part 2)

XYZ Refinery

Inspected on Jan.xx, 20yy

by:

Weerawut Leelawetchabutr ITC Level 2 cert. no. 2007ID28N003

Checked by:

Mikael Cronholm

ITC Level 3 cert. no. 13973

F-101 20110120 part 2 Anomalies 2 (16)

Thermography Inspection report For F-101

XYZ Refinery

Date: Jan.20, 2011

INFORMATION

Inspection site information

Customer XYZ

Address Somehwre

Contact person Someone

Phone number ################

E-mail address [email protected]

Thermographer Weerawut Leelawetchabutr

General comment

1. Oxidation staining/ Peeling of paint area/ or different layer of painting can change thermal pattern to look hotter than actual

2. Insulation surrounding peep holes/man doors is generally in poor condition. 3. Temperature limits must be individual for each furnace and each section. And they must be

determined by XYZ or from furnace manufacturers recommendation. 4. Recommend to maintain peep hole to be available to open for inspection.

Overview of Fault Rating:

A: Severe grade fault Attention immediately

B: Medium grade fault Repair at scheduled shut down C: Minor grade fault To monitor – Plan new inspection

F-101 20110120 part 2 Anomalies 3 (16)

Thermography Inspection report For F-101

XYZ Refinery

Date: Jan.20, 2011

< Intentionally blank page >

F-101 20110120 part 2 Anomalies 4 (16)

Thermography Inspection report For F-101

XYZ Refinery

Date: Jan.20, 2011

Summary of Inspection

Page Number

Section Direction or side

Elevation Fault rating Symptom Recommendation

5 Convection North side, view from D-4001

4th walkway floor

- Normal For reference

6 Convection North side 4th walkway floor

- Normal For reference

7 Convection North side 4th walkway floor

C (Minor fault) Suspected hot spot Monitor next time

8 Convection North side B (Medium fault)

Hot spot, temp.>200 degC

Plan to repair in schedule shutdown

9 Convection North side 4th walkway floor

B (Medium fault)

Hot spot over 200 degC Repair in schedule shutdown

10 Convection North side, near West

4th walkway floor

- Normal For reference

11 Convection East side, view from D-4001

4th walkway floor

- Normal For reference

12 Convection South side, near West

4th walkway floor

- Normal For reference

13 Convection South side 4th walkway floor

C (Minor fault) Suspected hot spot Monitor next time

14 Convection South side 4th walkway floor

B (Medium fault)

Hot spot over 200 degC Repair in schedule shutdown

15 Convection East roof 5th walkway floor

- Normal For reference

16 Convection East roof 5th walkway floor

- Normal For reference

17 Convection West roof Ladder on 4th walkway floor

- Normal For reference

18 Convection West roof Ladder on 4th walkway floor

- Normal For reference

19 Air pre-heater unit

North-East side 4th walkway floor

- Normal For reference

20 Air pre-heater unit

East side 5th walkway floor

- Normal For reference

21 Air pre-heater unit

East side 2nd walkway floor

C (Minor fault) Suspected hot spot Monitor next time

22 Air pre-heater unit

North-East side 2nd walkway floor

- Normal For reference

23 Air pre-heater unit

East side 2nd walkway floor

B (Medium fault)

Hot spot over 200 deg C Repair in schedule shutdown

24 Air pre-heater unit

South-East side 2nd walkway floor

B (Medium fault)

Hot spot over 200 degC Plan to repair in schedule shutdown

25 Air pre-heater unit

East side 1st walkway floor

- Normal For reference

26 Air pre-heater unit

North-East side 1st walkway floor

C (Minor fault) Suspected hot spot Monitor next time

27 Air pre-heater unit

East side 1st walkway floor

C (Minor fault) Suspected hot spot Monitor next time

28 Air pre-heater unit

North-East side 4th walkway floor

- Normal For reference

29 Air pre-heater unit

North-East side 5th walkway floor

- Normal For reference

30 Air pre-heater unit

West side 1st walkway floor

B (Medium fault)

Hot spot over 200 degC Plan to repair in schedule shutdown

31 Air pre-hearter unit

West side Ground B (Medium fault)

Hot spot over 200 degC Plan to repair in schedule shutdown

32 Pre-heat air South side 1st walkway floor

C (Minor fault) Suspected hot spot Monitor next time

33 Stack North-East side 6th walkway floor

- Normal For reference

34 Stack East side 6th walkway floor

- Normal For reference

35 Stack South-East side 6th walkway floor

- Normal For reference

F-101 20110120 part 2 Anomalies 5 (16)

Thermography Inspection report For F-101

XYZ Refinery

Date: Jan.20, 2011

Furnace position Identification

Photo and Identification

Tag no. F-101

Equipment Name APS-1 Furnace

Section Convection

Direction or side North side

Elevation 4th walkway floor

Weather Moderate wind

Fault rating C (Minor fault)

Symptom Suspected hot spot

Recommendation Monitor next time

Thermogram and Inspection result

Sp1

44.4

109.4 °C

60

80

100

IR camera : ThermaCAM T-400 Image : IR_11405.jpg , taken on 2011-01-18 Lens : FOL18

Emissivity 0.90

Object Distance 3.0 m

Reflected Temperature 3.5 °C

Atmospheric Temperature 28.0 °C

Sp1 Temperature 119.8 °C

Case 0022

Analysis & Recommendation:

Found hot spot near peep door. Recommend to monitor trend of temperature follow case no.0022.

ELEVATION

N

PLAN

E W

S

F-101 20110120 part 2 Anomalies 6 (16)

Thermography Inspection report For F-101

XYZ Refinery

Date: Jan.20, 2011

Furnace position Identification

Photo and Identification

Tag no. F-101

Equipment Name APS-1 Furnace

Section Convection

Direction or side North side

Elevation 4th walkway floor

Weather Moderate wind

Fault rating B (Medium fault)

Symptom Hot spot over 200 degC

Recommendation Repair in schedule shutdown

Thermogram and Inspection result

Sp1

40.0

200.0 °C

50

100

150

IR camera : ThermaCAM T-400 Image : IR_11409.jpg , taken on 2011-01-18 Lens : FOL18

Emissivity 0.90

Object Distance 4.0 m

Reflected Temperature 3.5 °C

Atmospheric Temperature 28.0 °C

Sp1 Temperature 202.8 °C

Case 0001

Analysis & Recommendation:

Found hot spot at the wall, temperature is higher than 200°C. It is same trouble as previous page, but took from another side of beam. Recommend monitoring trend of temperature follow case no.0001 and plan to repair in schedule shutdown.

ELEVATION

N

PLAN

E W

S

F-101 20110120 part 2 Anomalies 7 (16)

Thermography Inspection report For F-101

XYZ Refinery

Date: Jan.20, 2011

Furnace position Identification

Photo and Identification

Tag no. F-101

Equipment Name APS-1 Furnace

Section Convection

Direction or side South side

Elevation 4th walkway floor

Weather Moderate wind

Fault rating C (Minor fault)

Symptom Suspected hot spot

Recommendation Monitor next time

Thermogram and Inspection result

Sp1

53.1

199.8 °C

100

150

IR camera : ThermaCAM T-400 Image : IR_11417.jpg , taken on 2011-01-18 Lens : FOL18

Emissivity 0.95

Object Distance 3.0 m

Reflected Temperature 3.5 °C

Atmospheric Temperature 28.0 °C

Sp1 Temperature 191.3 °C

Case 0023

Analysis & Recommendation:

Found hot spot on the wall at South side. Recommend to monitor trend of temperature follow case no.0023.

ELEVATION

N

PLAN

E W

S

F-101 20110120 part 2 Anomalies 8 (16)

Thermography Inspection report For F-101

XYZ Refinery

Date: Jan.20, 2011

Furnace position Identification

Photo and Identification

Tag no. F-101

Equipment Name APS-1 Furnace

Section Convection

Direction or side South side

Elevation 4th walkway floor

Weather Moderate wind

Fault rating B (Medium fault)

Symptom Hot spot over 200 degC

Recommendation Repair in schedule shutdown

Thermogram and Inspection result

Sp1

60.0

200.6 °C

100

150

200

IR camera : ThermaCAM T-400 Image : IR_11419.jpg , taken on 2011-01-18 Lens : FOL18

Emissivity 0.79

Object Distance 4.0 m

Reflected Temperature 3.5 °C

Atmospheric Temperature 28.0 °C

Sp1 Temperature 200.9 °C

Case 0024

Analysis & Recommendation:

Found hot spot at the wall, temperature is higher than 200°C. Recommend monitoring trend of temperature follow case no.0024 and plan to repair in schedule shutdown.

ELEVATION

N

PLAN

E W

S

F-101 20110120 part 2 Anomalies 9 (16)

Thermography Inspection report For F-101

XYZ Refinery

Date: Jan.20, 2011

Furnace position Identification

Photo and Identification

Tag no. F-101

Equipment Name APS-1 Furnace

Section Air pre-heater unit

Direction or side East side

Elevation 2nd walkway floor

Weather Moderate wind

Fault rating C (Minor fault)

Symptom Suspected hot spot

Recommendation Monitor next time

Thermogram and Inspection result

Sp1

Sp2

34.2

100.4 °C

40

60

80

100

IR camera : ThermaCAM T-400 Image : IR_11333.jpg , taken on 2011-01-18 Lens : FOL18

Emissivity 0.79

Object Distance 15.0 m

Reflected Temperature 3.5 °C

Atmospheric Temperature 28.0 °C

Sp1 Temperature 104.3 °C

Sp2 Temperature 83.3 °C

Case 0025

Analysis & Recommendation:

Found hot spot on the hot gas side duct beside man door. Recommend to monitor trend of temperature follow case no.0025.

ELEVATION

N

PLAN

E W

S

F-101 20110120 part 2 Anomalies 10 (16)

Thermography Inspection report For F-101

XYZ Refinery

Date: Jan.20, 2011

Furnace position Identification

Photo and Identification

Tag no. F-101

Equipment Name APS-1 Furnace

Section Air pre-heater unit

Direction or side South-East side

Elevation 2nd walkway floor

Weather Moderate wind

Fault rating B (Medium fault)

Symptom Hot spot over 200 degC

Recommendation Plan to repair in schedule shutdown

Thermogram and Inspection result

Sp1

Sp3

Sp2

41.3

201.6 °C

50

100

150

200

IR camera : ThermaCAM T-400 Image : IR_11431.jpg , taken on 2011-01-18 Lens : FOL18

Emissivity 0.95

Object Distance 15.0 m

Reflected Temperature 3.5 °C

Atmospheric Temperature 28.0 °C

Sp1 Temperature 272.3 °C

Sp2 Temperature 227.9 °C

Sp3 Temperature 224.7 °C

Case 0002

Analysis & Recommendation:

Found hot spot at West side flange of heat exchanger, temperature is higher than 200°C. Recommend monitoring trend of temperature follow case no.0002 and plan to repair in schedule shutdown.

ELEVATION

N

PLAN

E W

S

F-101 20110120 part 2 Anomalies 11 (16)

Thermography Inspection report For F-101

XYZ Refinery

Date: Jan.20, 2011

Furnace position Identification

Photo and Identification

Tag no. F-101

Equipment Name APS-1 Furnace

Section Air pre-heater unit

Direction or side North-East side

Elevation 1st walkway floor

Weather Moderate wind

Fault rating C (Minor fault)

Symptom Suspected hot spot

Recommendation Monitor next time

Thermogram and Inspection result

Sp1:emiss 0 .90

Sp3

Sp2

30.6

80.6 °C

40

60

80

IR camera : ThermaCAM T-400 Image : IR_11327.jpg , taken on 2011-01-18 Lens : FOL18

Emissivity 0.79

Object Distance 15.0 m

Reflected Temperature 3.5 °C

Atmospheric Temperature 28.0 °C

Sp1 Temperature 81.9 °C

Sp2 Temperature 85.3 °C

Sp3 Temperature 56.5 °C

Case 0026

Analysis & Recommendation:

Found hot spot on the flue gas side duct below man door. Recommend to monitor trend of temperature follow case no.0026.

ELEVATION

N

PLAN

E W

S

F-101 20110120 part 2 Anomalies 12 (16)

Thermography Inspection report For F-101

XYZ Refinery

Date: Jan.20, 2011

Furnace position Identification

Photo and Identification

Tag no. F-101

Equipment Name APS-1 Furnace

Section Air pre-heater unit

Direction or side East side

Elevation 1st walkway floor

Weather Moderate wind

Fault rating C (Minor fault)

Symptom Suspected hot spot

Recommendation Monitor next time

Thermogram and Inspection result

Sp1

Sp3

Sp2

30.0

80.0 °C

40

60

IR camera : ThermaCAM T-400 Image : IR_11329.jpg , taken on 2011-01-18 Lens : FOL18

Emissivity 0.79

Object Distance 20.0 m

Reflected Temperature 3.5 °C

Atmospheric Temperature 28.0 °C

Sp1 Temperature 81.9 °C

Sp2 Temperature 88.1 °C

Sp3 Temperature 56.1 °C

Case 0027 and Case 0028

Analysis & Recommendation:

Found hot spot on the top portion of duct and discharge duct from blower. Recommend to monitor trend of temperature follow case no.0027 and 0028.

ELEVATION

N

PLAN

E W

S

F-101 20110120 part 2 Anomalies 13 (16)

Thermography Inspection report For F-101

XYZ Refinery

Date: Jan.20, 2011

Furnace position Identification

Photo and Identification

Tag no. F-101

Equipment Name APS-1 Furnace

Section Air pre-heater unit

Direction or side West side

Elevation 1st walkway floor

Weather No wind (0-2 m/s)

Fault rating B (Medium fault)

Symptom Hot spot over 200 degC

Recommendation Plan to repair in schedule shutdown

Thermogram and Inspection result

Sp1

Sp2

40.0

200.0 °C

50

100

150

IR camera : ThermaCAM T-400 Image : IR_11381.jpg , taken on 2011-01-18 Lens : FOL18

Emissivity 0.90

Object Distance 4.0 m

Reflected Temperature 3.5 °C

Atmospheric Temperature 28.0 °C

Sp1 Temperature 217.6 °C

Sp2 Temperature 74.9 °C

Case 0003

Analysis & Recommendation:

Found hot spot at West side flange of heated air duct, temperature is higher than 200°C. Recommend monitoring trend of temperature follow case no.0003 and plan to repair in schedule shutdown.

ELEVATION

N

PLAN

E W

S

F-101 20110120 part 2 Anomalies 14 (16)

Thermography Inspection report For F-101

XYZ Refinery

Date: Jan.20, 2011

Furnace position Identification

Photo and Identification

Tag no. F-101

Equipment Name APS-1 Furnace

Section Air pre-hearter unit

Direction or side West side

Elevation Ground

Weather No wind (0-2 m/s)

Fault rating B (Medium fault)

Symptom Hot spot over 200 degC

Recommendation Plan to repair in schedule shutdown

Thermogram and Inspection result

Sp1

Sp2

40.0

220.0 °C

50

100

150

200

IR camera : ThermaCAM T-400 Image : IR_11383.jpg , taken on 2011-01-18 Lens : FOL18

Emissivity 0.90

Object Distance 4.0 m

Reflected Temperature 3.5 °C

Atmospheric Temperature 28.0 °C

Sp1 Temperature 231.3 °C

Sp2 Temperature 81.8 °C

Case 0004

Analysis & Recommendation:

Found hot spot at West side flange of heated air duct, temperature is higher than 200°C. Recommend monitoring trend of temperature follow case no.0004 and plan to repair in schedule shutdown.

ELEVATION

N

PLAN

E W

S

F-101 20110120 part 2 Anomalies 15 (16)

Thermography Inspection report For F-101

XYZ Refinery

Date: Jan.20, 2011

Furnace position Identification

Photo and Identification

Tag no. F-101

Equipment Name APS-1 Furnace

Section Pre-heat air

Direction or side South side

Elevation 1st walkway floor

Weather No wind (0-2 m/s)

Fault rating C (Minor fault)

Symptom Suspected hot spot

Recommendation Monitor next time

Thermogram and Inspection result

Sp1

Sp2

39.3

141.0 °C

60

80

100

120

140

IR camera : ThermaCAM T-400 Image : IR_11395.jpg , taken on 2011-01-18 Lens : FOL18

Emissivity 0.90

Object Distance 1.0 m

Reflected Temperature 50.0 °C

Atmospheric Temperature 28.0 °C

Sp1 Temperature 141.6 °C

Sp2 Temperature 104.5 °C

Case 0029

Analysis & Recommendation:

Found hot spot on the top portion of damper at South side. Recommend to monitor trend of temperature follow case no.0029.

ELEVATION

N

PLAN

E W

S

F-101 20110120 part 2 Anomalies 16 (16)

Thermography Inspection report For F-101

XYZ Refinery

Date: Jan.20, 2011

REFERENCE

1. Infrared Camera

2. Thermographer

Specification: IR resolution : 320 x 240 pixels

Thermal sensitivity : 60 mK @ +30C Detector type : FPA, microbolometer Spectral range : 7.5 to 13 µm

Object temperature range : -20 to +1,200C

Accuracy : ±2C or ±2% of reading