Theory of Arc Interruption

download Theory of Arc Interruption

of 128

description

arc quenching processes and theory on arc interruption.

Transcript of Theory of Arc Interruption

  • Theory of Arc Interruption

    1

    Dr. Bhavesh Bhalja, Dr. Bhavesh Bhalja, Dr. Bhavesh Bhalja, Dr. Bhavesh Bhalja, Senior Member IEEESenior Member IEEESenior Member IEEESenior Member IEEE

    [email protected]@[email protected]@ieee.org

  • What is Electrical Switchgear?

    All electrical devices used for

    making and breaking the electrical

    2

    making and breaking the electrical

    circuits are grouped under the

    term Electrical Switchgear

  • What comes under ES?

    Relays

    OFF/ON-load switches and Fuses

    Isolators

    3

    Isolators

    Circuit Breakers (CBs)

    Control Panels

  • Circuit Breaker (CB)

    CB is a device that can open or close a

    4

    high voltage circuit in a fraction of a

    second.

  • Functions of CB?

    1. Capable to carry IFL at rated PF

    continuously.

    2. Capable to interrupt heavy s/ckt current

    5

    at very low power factor.

    3. Capable to perform making duty (closing

    on to a circuit in which a fault exits and

    immediately reopening to clear the fault.

  • Functions of CB?

    4. Capable to carry currents of short-circuit

    6

    magnitudes until the fault is cleared by

    another CB or fuse (near to fault point).

  • Functions of CB?

    5. During open condition of CB, the gap

    must withstand the steady state power

    7

    must withstand the steady state power

    frequency system voltage continuously

    and transient high frequency voltage for

    a short duration of time.

  • Functions of CB?

    7. Capable to withstand the effects of arcing

    of the contacts and electromagnetic

    8

    of the contacts and electromagnetic

    forces produced due to high currents.

  • Fundamentals of Circuit Breaking

    When the movable contacts begin to separate, the

    CB begins interrupting the current.

    9

    CB begins interrupting the current.

    As a result, the contact area decreases.

    This results in a high current density, which finally

    vaporizes the metal, and an arc is generated

    between the switching contacts.

  • Fundamentals of Circuit Breaking

    In spite of the physical separation of switching

    contacts, current flows continuously because of

    10

    contacts, current flows continuously because of

    the sustained arc.

  • Fundamentals of Circuit Breaking

    This arc plasma must be cooled and extinguished

    in a systematic way so that the gap between the

    11

    in a systematic way so that the gap between the

    contacts can again withstand the voltage in the

    circuit.

  • Fundamentals of Circuit Breaking

    The separation of switching contacts of any CB

    leads to the formation of gas and metal vapour

    12

    leads to the formation of gas and metal vapour

    between them in its current carrying condition.

    Any kind of gas or vapour always contains

    positive and negative charge carriers.

  • Fundamentals of Circuit Breaking

    Even when no potential is applied across the

    electrode, the gas conducts and sets up a small

    13

    electrode, the gas conducts and sets up a small

    current due to natural ionization.

    This current is known as leakage current.

  • Fundamentals of Circuit Breaking

    When an electrical potential is applied across

    the two electrodes, the charge carriers gain

    14

    the two electrodes, the charge carriers gain

    mobility, and their motion depends on the

    applied electrical field intensity.

  • Fundamentals of Circuit Breaking

    When the moving charges collide with the

    electrode (ions move towards the cathode and

    15

    electrode (ions move towards the cathode and

    electrons move towards the anode), they

    disperse their charges, and a current flows

    between the electrodes.

  • Fundamentals of Circuit Breaking

    This process of current conduction in a gaseous

    medium is due to an ionization process such as

    16

    medium is due to an ionization process such as

    photoelectric or thermionic emission and

    remains continuous till a potential is applied.

  • V-I relationship during electric discharge for different values of applied voltage

    17

  • 1. Linear current limit:- OP

    Linear relationship between I and V for a small

    V-I relationship during electric discharge for different values of applied voltage

    18

    Linear relationship between I and V for a small

    value of applied voltage.

  • 2. Saturation current limit:- PQ

    When an equilibrium is reached (the production

    V-I relationship during electric discharge for different values of applied voltage

    19

    When an equilibrium is reached (the production

    of charge carriers is equal to the charge

    carriers received by the electrodes), there is no

    increase in significant current.

  • 2. Saturation current limit:- PQ

    This phenomenon depends on

    V-I relationship during electric discharge for different values of applied voltage

    20

    This phenomenon depends on

    (a) the intensity of ionization

    (b) the quantity of gas between the electrodes

    (c) the gas pressure

  • 3. High current :- QR

    If the electrical potential across the electrode

    V-I relationship during electric discharge for different values of applied voltage

    21

    If the electrical potential across the electrode

    increases to a high level, ionization occurs

    freely and free positive charges gain a high

    velocity.

  • 3. High current :- QR

    In this situation, they strike the cathodes with

    V-I relationship during electric discharge for different values of applied voltage

    22

    In this situation, they strike the cathodes with

    enough force to knock out a number of free

    electrons that maintain the discharge.

  • 3. High current :- QR

    Such discharge remains self-sustained because

    it does not require any external excitation.

    V-I relationship during electric discharge for different values of applied voltage

    23

    it does not require any external excitation.

    This process rises exponentially, and the

    current continues to increase between two

    electrodes even when the applied voltage

    remains constant.

  • 3. High current :- QR

    The voltage that forces such a high current

    V-I relationship during electric discharge for different values of applied voltage

    24

    The voltage that forces such a high current

    density (million charges) through a gas medium

    is known as breakdown voltage.

  • The gases between electrodes no more remain

    insulators but provide a current conducting path.

    V-I relationship during electric discharge for different values of applied voltage

    25

    insulators but provide a current conducting path.

    Hence, a continuous arc is formed between

    electrodes, which are surrounded by hot ionized

    gases.

  • The quenching or extinction of high current is

    done externally.

    V-I relationship during electric discharge for different values of applied voltage

    26

    done externally.

    Thus, it is very important to decide the

    breakdown voltage and insulating medium to

    quench the arc while designing the CB.

  • 1. Decay Discharge: (exp: tube light and lamps)

    When potential is applied in a gas having small

    Types of Gaseous Discharges

    27

    pressure (less than atmospheric), number of

    atoms or molecules/unit volume are less.

    Hence, discharge current is less at the time of

    break down.

  • 2. Spark Discharge: (exp: switches)

    When potential is applied to the gap intermittently

    in a gas having high pressure (more than

    atmospheric), spark discharge occurs.

    Types of Gaseous Discharges

    28

    atmospheric), spark discharge occurs.

    Such discharge will occur between two contacts of

    a simple switch or in a CB when it interrupts a

    rated load current at higher PF.

  • 3. Arc Discharge: (exp: switches)

    When high potential is applied to the gap in a gas

    having high pressure (more than atmospheric),

    Types of Gaseous Discharges

    29

    having high pressure (more than atmospheric),

    number of charges are quite large and collision

    ionisations do occur.

    Temp is of the order of 20000 to 90000 C.

  • 3. Arc Discharge: (exp: opening of CB)

    The arc is self-sustaining unless quenched by

    external means.

    Types of Gaseous Discharges

    30

    external means.

  • 4. Corona Discharge: (exp: opening of CB)

    This discharge occurs across the two contacts

    when an electric field is not uniform but dense

    Types of Gaseous Discharges

    31

    when an electric field is not uniform but dense

    near one electrode and scarce near another

    electrode.

    Breakdown is limited to a small area (around one

    of the electrode).

  • 4. Corona Discharge: (exp: opening of CB)

    This discharge mechanism is useful to decide

    (a) the material of the electrode

    Types of Gaseous Discharges

    32

    (a) the material of the electrode

    (b) the smoothness of the electrode

    (c) the profile of the electrode

  • Ionization is the process of removing an electron

    from the neutral molecule by externally applying

    Ionization Process in a Gaseous Insulating Medium

    33

    from the neutral molecule by externally applying

    finite amount of energy.

  • 1. Ionization by Collision

    If a particle of mass m and velocity v collides with

    a neutral atom, kinetic energy of the moving

    Ionization Process in a Gaseous Insulating Medium

    34

    a neutral atom, kinetic energy of the moving

    particle can create ionization state if

    . m.v2 > wi

    wi is energy of ionization

  • 2. Photo Ionization

    When energy is imparted to a neutral atom, an

    electron may jump from lower orbit to a higher

    Ionization Process in a Gaseous Insulating Medium

    35

    electron may jump from lower orbit to a higher

    orbit.

    The atom can remain in such a meta-stable state

    for a small period (micro/nano-second).

  • 2. Photo Ionization

    When it returns to its original stable state, it

    releases energy in the form of a quantum of light

    Ionization Process in a Gaseous Insulating Medium

    36

    releases energy in the form of a quantum of light

    or in the form of a wave of different frequencies.

    Such energy is termed as photon.

    hf > wi

  • 3. Thermal Ionization

    Molecules of gases move with all possible

    velocities.

    Ionization Process in a Gaseous Insulating Medium

    37

    velocities.

    At higher temperature, velocity increases and

    probability of ionization is more.

  • 4. Ionization on the surface of electrodes

    Liberation of electron needs a certain amount of

    energy called energy of liberation.

    Ionization Process in a Gaseous Insulating Medium

    38

    energy called energy of liberation.

    This energy is different for different electrode

    materials.

  • 4. Ionization on the surface of electrodes

    The energy can be imparted by

    (a) heating the cathode (called thermionic

    Ionization Process in a Gaseous Insulating Medium

    39

    (a) heating the cathode (called thermionic

    emission)

    (b) bombardment on the surface of the metal by

    particles

  • 4. Ionization on the surface of electrodes

    The energy can be imparted by

    (c) irradiating the cathode surface by short wave

    Ionization Process in a Gaseous Insulating Medium

    40

    (c) irradiating the cathode surface by short wave

    radiation

    (d) superposition of strong electric field

  • 1. Reduction of Velocity of Charged Particles

    Gas pressure , the mean free path (distance of

    Decay Process (Deionization)

    41

    Gas pressure , the mean free path (distance of

    travel of a charged particle before collision) of a

    charge particle gets reduced.

  • 1. Reduction of Velocity of Charged Particles

    Hence, collision takes place before the charged

    Decay Process (Deionization)

    42

    Hence, collision takes place before the charged

    particle can acquire a velocity enough to gather

    kinetic energy more than the ionization energy.

    Hence, collision can not result in ionization.

  • 1. Reduction of Velocity of Charged Particles

    Chances of recombination are greatly reduced and

    Decay Process (Deionization)

    43

    Chances of recombination are greatly reduced and

    the gas gets de-ionized.

  • 1. Reduction of Velocity of Charged Particles

    Chances of recombination are greatly reduced and

    Decay Process (Deionization)

    44

    Chances of recombination are greatly reduced and

    the gas gets de-ionized.

  • 1. Voltage across the electrode and its variation with

    time

    Factors responsible for the formation of an arc

    45

    2. The nature, shape and separation of electrodes

    3. The nature and pressure of the medium

    4. Presence of external ionizing and de-ionizing

    agents

  • 1. Arc characteristic is the curve between the

    instantaneous voltage across the electrode and

    Characteristic of Arc

    46

    the corresponding current through the arc.

  • Voltage distribution across an arc column

    Arc column

    Anode Cathode

    +VA

    Arc length

    47

    VC

    Varc

  • Theory of Arc Quenching

    )]sin([ += wteEiRt

    m

    When a sudden short circuit occurs in a power system,the fault current is given by,

    48

    )]sin([ += wtewLE

    i Lm

  • Theory of Arc Quenching

    LRt

    m ewLE

    is known as transient component or dc offset.

    If fault occurs at an instantaneous voltage

    49

    If fault occurs at an instantaneous voltageequal to Vmax , there would be no dc offset.

    The steady state value of fault current is given by

    )sin( = wtwLE

    i m

  • Theory of Arc Quenching

    When such a fault current is interrupted, high voltageis developed across the contacts of CB when the arcdue to this fault current is quenched.

    50

  • Theory of Arc Quenching

    functionarycomplementtakingBywtSinEv

    idtCdt

    diLiRv

    m=

    ++= )(

    1

    51

    LCjD

    iC

    LD

    iCdt

    idL

    functionarycomplementtakingBy

    =

    +=

    ++=

    ]1[0

    100

    2

    2

    2

  • Theory of Arc Quenching

    LCjt

    LCjt

    BeAei

    bewillsolutiontheHence

    +=

    ,

    52

  • Theory of Arc Quenching

    BABA

    iextinctionarcoftinstheattAt

    =

    +=

    ==

    00,)tan(0

    53

    LCk

    dtdi

    tAt

    LCt

    LCk

    dtdi

    LCtkeeAi LC

    jtLCjt

    ==

    =

    ==

    ,0

    )(cos

    )(sin][

  • Theory of Arc Quenching

    breaacrossvoltageVWhere

    dtiC

    VtBut

    dtiCdt

    diLv

    itAt

    C

    =

    ===

    +=

    ==

    ker,

    01,0

    10,0

    54

    LC

    vk

    Lv

    LCk

    Lv

    dtdi

    vdtdiL

    breaacrossvoltageVWhere C

    =

    =

    ==

    = ker,

  • Theory of Arc Quenching

    breaacrossvoltageVWhere

    dtiC

    VtBut

    dtiCdt

    diLv

    itAt

    C

    =

    ===

    +=

    ==

    ker,

    01,0

    10,0

    55

    LC

    vk

    Lv

    LCk

    Lv

    dtdi

    vdtdiL

    breaacrossvoltageVWhere C

    =

    =

    ==

    = ker,

  • Theory of Arc Quenching

    (sin11

    )(sin

    dttLC

    vC

    dtiC

    V

    LCt

    LC

    vi

    c ==

    =

    56

    ')(cos

    ')](cos[1

    (sin

    kLCt

    vV

    kLCtLC

    LC

    vC

    V

    dtLCL

    vC

    dtiC

    V

    c

    c

    c

    +=

    +=

    ==

  • Theory of Arc Quenching

    '

    '00,0,)tan(0

    vkkv

    VhenceandiextinctionarcoftinstheattAt c

    =

    +=

    ===

    57

    )cos1(LCt

    vVc =

    Hence, a transient voltage (Vc) is superimposed on steady-state phase to neutral Voltage. The frequency of this transient voltage is known as natural frequency (fn) and given by,

  • Theory of Arc Quenching

    LCf n

    pi21

    =

    The maximum value of this transient voltage (Vcmax) is given by,

    58

    cmax

    is given by,

    LCtatvVc pi== 2max

    Hence, the insulation of CB should be able to withstandtwo times the peak of phase to neutral voltage whichwill appear across the contacts of CB.

  • 1. Re-striking Voltage:-

    The peak of voltage at the time of re-striking of

    Definitions related to quenching of an Arc

    59

    an arc when the dielectric strength of the

    insulating medium between contacts of CB has

    not bulid up and breaks down.

  • 2. Arc Voltage:-

    The voltage across the contacts of CB

    Definitions related to quenching of an Arc

    60

    immediately after the instant of separation of

    contacts of CB.

    It is in phase with arc current.

  • 3. Transient Re-striking Voltage (TRV):-

    The high frequency voltage appear across the

    Definitions related to quenching of an Arc

    61

    contacts of CB immediately after the instant of arc

    extinction is known as TRV.

  • 4. Recovery Voltage:-

    The power frequency steady-state voltage appear

    Definitions related to quenching of an Arc

    62

    across the contacts of CB after arc extinction is

    known as recovery voltage.

  • 5. Active Recovery Voltage:-

    The instantaneous value of recovery voltage at

    Definitions related to quenching of an Arc

    63

    the instant of arc extinction is known as active

    recovery voltage.

  • 6. Rate of Rise of Restriking Voltage:-

    The slope of the steepest tangent to the restriking

    Definitions related to quenching of an Arc

    64

    voltage curve is defined as the rate of rise of

    restriking voltage (RRRV).

    It is expressed in kV/ s.

  • 6. Rate of Rise of Restriking Voltage:-

    Definitions related to quenching of an Arc

    LCt

    dtd

    vdt

    dVRRRV C ))cos(1( ==

    65

    LCvRRRV

    LCtAt

    LCt

    LCvRRRV

    LCdtdt

    12

    )sin(1

    =

    =

    =

    pi

  • 1. High Resistance Interruption:-

    The arc is restricted by increasing its effective

    Arc Interruption Theories

    66

    resistance with respect to time.

    With the increase of arc resistance, the current is

    reduced to a value inadequate to sustain the arc

    across the contacts of CB.

  • 1. High Resistance Interruption:-

    How to increases arc resistance?

    Arc Interruption Theories

    67

    (i) lengthening the arc column

    (ii) Cooling

    (iii) Splitting the arc in many sub-segments.

  • Such a high resistance interruption method is not

    appropriate for a high power AC CB because of

    Arc Interruption Theories

    68

    high energy losses at the time of arc interruption.

    Thus, the use of this method is limited to low

    power AC and DC CBs.

  • 2. Low Resistance Interruption:-

    Mainly used for the interruption of an arc in an AC

    Arc Interruption Theories

    69

    circuit as the arc current passes through zero

    twice in a cycle (100 times per second for a 50 Hz

    system).

  • 2. Low Resistance Interruption:-

    The arc tries to either die out at every current

    Arc Interruption Theories

    70

    zero or reignite with rising current.

    (a) Slepians Theory

    (b) Cassies Theory

  • 2. Slepians Theory:- Background

    1. During the separation of contacts of the CB,

    Arc Interruption Theories

    71

    the medium is ionized because of high field

    intensity, and it sets up a very hot gaseous path.

  • 2. Slepians Theory:- Background

    2.To stop this ionization process, it is necessary

    Arc Interruption Theories

    72

    to remove the ionized gases by

    (a) prohibiting electron generation

    (b) advancing the recombination process.

  • 2. Slepians Theory:- Background

    3.The rate of ionization is very low in the zero

    Arc Interruption Theories

    73

    current region.

    Hence, it is easier to increase the resistance of

    the arc in this region and build up high dielectric

    strength across the contacts of CB.

  • 2. Slepians Theory:- Actual Theory

    At each current zero, there is a race between the

    Arc Interruption Theories

    74

    RRRV and the rate at which the insulating

    medium recovers its dielectric strength.

  • 2. Slepians Theory:- Actual Theory

    If the rate at which the dielectric strength

    Arc Interruption Theories

    75

    progress is faster than the rate at which the

    voltage rises (RRRV), the arc will be quenched;

    otherwise, the arc restrikes and is not interrupted.

  • 2. Slepians Theory:-

    Arc Interruption Theories

    76

    Representation of Slepians theory (a) Arc interruption (b) Dielectric failure

  • 2. Slepians Theory:- Assumptions

    1.Build-up of the restriking voltage and dielectric

    Arc Interruption Theories

    77

    strength during the interruption are totally

    different processes.

  • 2. Slepians Theory:- Assumptions

    This assumption is not valid as it does not

    Arc Interruption Theories

    78

    calculate the rate at which the dielectric strength

    recovers.

    Moreover, it does not consider the energy relation

    at the time of the interruption.

  • 2. Cassies Theory:-

    The interruption of arc is a process of energy

    balance.

    At current zero, if the rate at which the energy

    Arc Interruption Theories

    79

    input to the arc column is higher than the rate at

    which maximum energy is lost from the arc

    column, the arc restrikes; if not, the arc can be

    interrupted.

  • 2. Cassies Theory:- Assumptions:-

    1. The temperature of the arc is assumed to be

    constant during this high current period.

    Arc Interruption Theories

    80

    However, the change in current creates the

    necessary change in the diameter of the arc,

    maintaining almost constant temperature at the

    centre of the arc column.

  • 2. Cassies Theory:- Assumptions:-

    2. When current decays towards the zero current

    regions, the cross section of the arc is a small

    Arc Interruption Theories

    81

    fraction of a millimetre, still maintaining high

    temperature.

  • 2. Cassies Theory:- Assumptions:-

    3. This high temperature can reignite the arc with a

    bigger cross-section if the electric field intensity

    Arc Interruption Theories

    82

    reappears across the contacts of CB.

  • It means interruption of small inductive currents.

    During interruption of small inductive currents

    (such as no-load current of transformer or shunt

    Current Chopping

    83

    reactors), the arc path which is ionized by the low

    current may reach a zero value before natural

    zero.

    This phenomena is known as current chopping.

  • The electromagnetic energy of inductance of the

    circuit is converted into electrostatic energy of the

    capacitance of the system.

    Current Chopping

    CVLI = 2221

    21

    84

    This voltage is impressed on a power frequency

    voltage and can damage insulation of transformer or

    other equipments.

    ICLV =

  • Current Chopping

    33/110 kV

    85

    33/110 kV20 MVA

    C=5000 pF

    No-load current is 2% of the full load current of transformer.What will be the voltage appear on the transformer insulationon HV side?

  • Current Chopping

    86

  • Arc is de-ionized before natural current zero

    comes.

    The prospective value of this voltage may reach a

    dangerous level, even higher than the dielectric

    Current Chopping

    87

    dangerous level, even higher than the dielectric

    strength, and leads to the next current conduction

    by restriking.

  • If de-ionizing force is still sufficient, second re-

    strike occurs. This time chopped current and

    RRRV are lower than previous re-strike.

    Current Chopping

    88

    Finally, when enough dielectric strength

    recovers after selective current chop, the

    current is concealed without restrike.

  • Self Blast Breaker:- gas pressure current to

    interrupted.

    Current Chopping

    89

    Forced Blast CB/SF6 CB:- gas pressure is

    independent of current to interrupted.

  • Improve power factor.

    The application of shunt capacitor banks hasbecome a special tool for improving the power

    Interruption of Capacitive Current

    90

    become a special tool for improving the powerfactor.

  • It is common practice for utilities to

    switch on /off the shunt capacitors as per daily loadvariations.

    Interruption of Capacitive Current

    91

    variations.

    Switching on /off of unloaded transmission line.

    This creates a challenge since the voltage acrossthe capacitor cannot change instantaneously.

  • This switching causes unwanted high frequencyvoltage and current transients across the contactsof CB, which may damage the equipment.

    Interruption of Capacitive Current

    92

    of CB, which may damage the equipment.

  • This switching causes unwanted high frequencyvoltage and current transients across the contactsof CB, which may damage the equipment.

    Interruption of Capacitive Current

    93

    of CB, which may damage the equipment.

  • Interruption of Capacitive Current

    94

  • After point P, VCB = VU- VC =

    At point Q (after half a cycle), VU reverses. Hence,

    Interruption of Capacitive Current

    95

    U

    VCB = -Vm- Vm =-2Vm

    This high voltage across CB contact leads torestriking of an arc. Hence, the circuit will reclose inan oscillating manner by developing the voltage

    -2Vm-Vm=-3Vm

  • Thus, the line is charged at a voltage of 3 Vmafter the interruption of a restriking current.

    Interruption of Capacitive Current

    96

    Afterwards, the voltage across the contacts of CBcontinues to increase, and at point S, the valuebecomes 4 Vm. If the breaker restrikes at thisinstant, high frequency oscillation of VC will occur ata voltage of 5 Vm.

  • Intentional insertion of resistance across thecontacts of CB after its separation is known asresistance switching.

    Resistance Switching

    97

    resistance switching.

    Utilization of shunt resistance across the contactsof CB leads to reduction of

  • 1. transient restriking voltage (TRV)

    2. RRRV

    Resistance Switching

    98

    3. Arc intensity (due to diversion of part of arc

    current)

    4. Breaking capacity (MVA) of CB also increases.

  • In case of ABCB and SF6 CB, the pressure of thearc quenching medium is independent of normalcurrent or fault current.

    Resistance Switching

    99

    Hence, low current interruption is achieved withhigh pressure of insulating medium.

    In this situation, it chops the current before naturalzeros.

  • This creates a very severe TRV across the contactgap of CB.

    Consequently, these TRV can cause flashover on

    Resistance Switching

    100

    Consequently, these TRV can cause flashover onthe insulation.

    Therefore, resistance switching is used to damp outsuch extreme high voltages.

  • If the value of the added resistance is higher thantwice the surge impedance of the line, the naturalfrequency oscillation of the circuit can be easily

    Resistance Switching

    101

    frequency oscillation of the circuit can be easilysuppressed.

    2

    2

    41

    21

    LR

    LCf n =

    pi

  • Resistance Switching

    102

  • RRRV is directly proportional to the naturalfrequency of the circuit, and it mainly depends on

    Resistance Switching

    103

    frequency of the circuit, and it mainly depends onthe value of the inserted shunt resistance.

    Thus, insertion of deliberate shunt resistanceacross the contact of CB increases the rupturingcapacity of the breaker.

  • Resistance Switching

    104

  • Find out the natural frequency of TRV when CB isopened on fault assuming L=0.5 H and C=5000pF.

    Examples on Resistance Switching

    105

    opened on fault assuming L=0.5 H and C=5000pF.What will be the natural frequency if a deliberateresistance of 10 k is added across CB contacts?

  • Quenching of DC Arc

    106

  • For points between A & B, the available supplyvoltage is greater than the arc voltage and hence,arc is maintained.

    Quenching of DC Arc

    107

    arc is maintained.

    A is a stable point.

    B is an unstable point.

  • When the available voltage is not sufficient tomaintain the arc current then it is quenched.

    Quenching of DC Arc

    108

    This can be obtained by

    (i) Increasing the arc length so that arccharacteristic can be shifted upward and thereis no intersection of arc characteristic and V-iRline.

  • This can be obtained by

    (ii) By increasing the external resistance in thecircuit so that V-iR characteristic can be shifted

    Quenching of DC Arc

    109

    circuit so that V-iR characteristic can be shifteddownward (V-i1R) and there is no intersectionof arc characteristic and V-iR line.

  • A 50 Hz, 13.8 kV, three-phase generator withgrounded neutral has an inductance of 15mH/phase and is connected to a busbar through aCB. The capacitance to earth between the

    Examples

    110

    CB. The capacitance to earth between thegenerator and the CB is 0.05 F/phase. Neglectingthe resistance of generator winding, determine :

    1. Maximum restriking voltage

    2. Time for maximum RRRV

    3. Average RRRV up to the first peak

    4. Frequency of oscillations

  • 1. Rated current :

    It is defined as the highest RMS current-carryingcapability of a CB without exceeding the limit oftemperature rise.

    Terms related to Circuit Breaker

    111

    temperature rise.

    2. Rated Voltage:

    It is defined as the maximum RMS voltage of a CBabove the nominal system voltage for which the CBis designed.

  • 3.Rated Breaking Capacity :

    It is defined as the highest RMS current-carryingcapability of a CB without exceeding the limit oftemperature rise.

    Terms related to Circuit Breaker

    112

  • 3.Rated Breaking Capacity :

    The CB starts to open its switching contacts aftersome time (t), starting from the inception of fault.

    Terms related to Circuit Breaker

    113

    The real value of fault current to be interrupted bya CB is quite less than the initial value at the timeof fault inception.

  • 3.Rated Breaking Capacity :

    Therefore, the highest value of fault current thatflows through the switching contacts at the instantof contact separation is known as the breaking

    Terms related to Circuit Breaker

    114

    of contact separation is known as the breakingcurrent of the CB.

  • 3.Rated Breaking Capacity :

    1. Symmetrical breaking current :

    It is the RMS value of the AC component of currentflowing through the CB at the instant of contact

    Terms related to Circuit Breaker

    115

    flowing through the CB at the instant of contactseparation.

    symmetrical = 2xyI

  • 3.Rated Breaking Capacity :

    2. Asymmetrical breaking current:

    It is the RMS value of current (including both ACand DC components of the current) flowing through

    Terms related to Circuit Breaker

    116

    and DC components of the current) flowing throughthe CB at the instant of contact separation..

    22

    asymmetrical = + ( )2xyI yz

  • 3.Rated Breaking Capacity :

    Breaking capacity is expressed in MVA by takinginto account the rated breaking current and therated system voltage.

    Terms related to Circuit Breaker

    117

    rated system voltage.

    Thus, if I is the rated breaking current in kA and Vis the rated system voltage in kV, then for a three-phase circuit,

    the breaking capacity = MVA3 V I

  • 4.Rated Making Capacity :

    The rated making capacity of a CB is related to itsability to withstand maximum current, closed underthe fault condition.

    Terms related to Circuit Breaker

    118

    the fault condition.

    The electromagnetic forces produced during thistime are proportional to the square of peakinstantaneous current.

  • 4.Rated Making Capacity :

    The peak RMS value of short circuit currentmeasured for the first cycle of current wave afterthe closure of CB under fault condition is known as

    Terms related to Circuit Breaker

    119

    the closure of CB under fault condition is known asthe making capacity.

    The peak of making capacity is given by ,

    Where, is the maximum asymmetry.

    2 symmetrical breaking capacity

  • 5. Short time rating :

    It is the duration for which the CB can carrymaximum fault current under its fully closedcondition without any damage.

    Terms related to Circuit Breaker

    120

    condition without any damage.

    Short time rating depends on the electromagneticforce withstanding capacity of the CBs and thermallimitations.

  • 6. Rated Standard Duty Cycle

    The standard duty cycle is estimated as thefrequent operation of CB for its particularapplication.

    Terms related to Circuit Breaker

    121

    application.

    The CBs are usually able to follow an open-close-open cycle with an energized spring chargemechanism without any new manual or electricalcharging.

  • 6. Rated Standard Duty Cycle

    The standard operating duty of a CB is as follows:

    O t CO t' CO where,

    Terms related to Circuit Breaker

    122

    where,

    O = Open

    CO = Close-open

    t = 3 min

    t = 15 s for CBs not rated for rapid reclosing

    t = 0.3 s for CBs rated for rapid reclosing

  • Used for low voltage to medium voltage distribution

    Systems.

    In order to increase the effective resistance of an arc

    Air Break Circuit Breaker

    123

    In order to increase the effective resistance of an arc

    in an ACB, the following methods are used.

    Arc lengthening

    Arc cooling

    Arc splitting

    Arc constraining

  • Contact separation and arc extinction take place at

    atmospheric pressure.

    Construction of Air Break Circuit Breaker

    124

    When the contacts are opened, an arc is drawn

    between them.

    The arc resistance is increased to such an extent that

    the system cannot maintain the arc, and thus, the arc

    is finally extinguished.

  • It consists of two contacts, namely, main contact and arcing contact.

    1. Main contact:

    Construction of Air Break Circuit Breaker

    125

    1. Main contact:

    It conducts current in the closed position.

    It has low contact resistance and is silver plated.

    The main contact consists of a moving contact anda fixed contact assembly.

  • Construction of Air Break Circuit Breaker

    126

  • 2. Arcing contact

    The arcing contact is hard, heat resistant, andmade of copper alloy.

    Construction of Air Break Circuit Breaker

    127

    While opening, the main contact is dislodged firstand the current is shifted to arcing contacts, andthen they are dislodged.

    Thus, the arc is drawn between the arcingcontacts.

  • The arc is now forced by electromagnetic forcesand thermal action.

    The ends of the arc move along the arc runners,and they are divided by the arc splitter plates in thearc chute.

    Construction of Air Break Circuit Breaker

    128

    The dimension of the arc chute depends on thenumber of arcing contacts.

    Hence, the arc is extinguished by lengthening,cooling, and splitting.