The use of multiple sensors, of electrical and non-electrical type, for online PD measurement of cables , transformers, switchgears and motors BY LEE WAI MENG ELECTRICAL PE/LEW (230KV GRADE)

Transcript of The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the...

Page 1: The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the sensor location. For instance; UHF sensor is used to detect PD at cable termination.

The use of multiple sensors, of electrical and

non-electrical type, for online PD measurement of cables , transformers, switchgears and motors

BY

LEE WAI MENG

ELECTRICAL PE/LEW (230KV GRADE)

Page 2: The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the sensor location. For instance; UHF sensor is used to detect PD at cable termination.

• J.M. Pang & Seah (Pte) Ltd (JMPS) was established on 21st January 1976 as a Electrical &

Mechanical Engineering Consultancy company.

• In August 2012, JMPS became a part of Pon group of Companies, a Dutch international

trading and service organization with a workforce of 13,000 people spread over 450 locations

in 32 countries.

• In May 2019, JMPS and QPM were merged to form On Engineers Pte Ltd

• Our services:

About Us

Condition Monitoring Business

LEW (Licensed Electrical Worker) services

Electrical Site testing and maintenances

Electrical System Study using ETAP and SKM software

M & E Consultancy

Page 3: The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the sensor location. For instance; UHF sensor is used to detect PD at cable termination.

Types Of Electrical Assets

Type of Electrical Assets

Switchgear

• Air Insulated

• Gas Insulated

Transformer

• Dry Type

• Oil Type

Cable

• XLPE Insulation

• EPR Insulation

Rotating Machine

• Motor

• Generator

Page 4: The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the sensor location. For instance; UHF sensor is used to detect PD at cable termination.

Non – Electrical Method of PD detection

Page 5: The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the sensor location. For instance; UHF sensor is used to detect PD at cable termination.

Electrical Method Of PD detection

Partial Discharge

Offline

• AC 0.1Hz Test Source • AC 50 Hz Test Source • AC 30 ~ 300 Hz Test Source

Online

• Transient Earth Voltage • High Frequency current transformer • Ultra-High Frequency • Resistance Temperature as PD sensor • Voltage Detection System as PD sensor

Page 6: The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the sensor location. For instance; UHF sensor is used to detect PD at cable termination.

Non – Electrical Method of PD Detection

Page 7: The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the sensor location. For instance; UHF sensor is used to detect PD at cable termination.

Ultrasound

Sound waves beyond the hearing range of the human ear.

Audio Sound Waves

In the range of human hearing (20Hz to 5000Hz).

Airborne Ultrasound Waves

Frequency above the audible range(20kHz to 40kHz).

Page 8: The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the sensor location. For instance; UHF sensor is used to detect PD at cable termination.

Online Airborne Ultrasound Measurement

Oil type Transformer

Air Insulated Switchgear

Page 9: The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the sensor location. For instance; UHF sensor is used to detect PD at cable termination.

Online Contact Ultrasound Measurement 66kV Gas Insulated Switchgear

Page 10: The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the sensor location. For instance; UHF sensor is used to detect PD at cable termination.

Infrared Thermography

• To find hot spots caused by defects in connections and components.

• To inspect electrical equipment because excess heat is usually the first sign of trouble.

Page 11: The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the sensor location. For instance; UHF sensor is used to detect PD at cable termination.

Infrared Thermography

Page 12: The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the sensor location. For instance; UHF sensor is used to detect PD at cable termination.

• Diagnostic tools for detecting of transformer oil faults in transformers.

• Reliable results from the removal of an oil sample from the transformer

• Able to be done without de-energization of the transformer.

• Analysis using gas chromatography technique

Dissolved Gas Analysis (DGA)

Page 13: The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the sensor location. For instance; UHF sensor is used to detect PD at cable termination.

The numbers shown in table in parts per million.

TDCG – Total Dissolved Combustible Gases

C57-104-2008 : IEEE Guide for the Interpretation of Gases Generated in Oil-Immersed

Transformers

Dissolved Gas Analysis (DGA)

Page 14: The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the sensor location. For instance; UHF sensor is used to detect PD at cable termination.

C57-104-2008 : Actions Based on TDCG (Table-3)

Dissolved Gas Analysis (DGA)

Page 15: The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the sensor location. For instance; UHF sensor is used to detect PD at cable termination.

SF6 Gas Measurement – IEC 60480

This multi-functional device allows the determination of three quality parameters with only

one measurement. The SF6 gas is pumped back to the GIS after measurement.

• SF6 concentration (%)

• Moisture concentration (oC or ppmv or ppmw )

• SO2 concentration (ppmv)

Page 16: The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the sensor location. For instance; UHF sensor is used to detect PD at cable termination.

Suitable for AIS, Transformer Cable box , LV switchboard

(Portable Smoke detector)

Smoke Particles Measurement

Page 17: The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the sensor location. For instance; UHF sensor is used to detect PD at cable termination.

Video Borescope Inspection

Page 18: The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the sensor location. For instance; UHF sensor is used to detect PD at cable termination.

Electrical Method of PD Detection

Page 19: The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the sensor location. For instance; UHF sensor is used to detect PD at cable termination.

Transient Earth Voltage (TEV) Sensor

• TEV = Transient Earth Voltage

• Capacitive couplers placed at external metal surface of

electrical equipment using a magnet

• Pulse Width – A few tens of nanoseconds

• Bandwidth =

10 nanoseconds

_____________

= 100 MHz

1

Page 20: The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the sensor location. For instance; UHF sensor is used to detect PD at cable termination.

Principal of Transient Earth Voltage Detection

HV BUSBAR

PARTIAL DISCHARGE JOINT/GASKET

HV BUSBAR

HIGH FREQUENCY

PULSE TO METALWORK VIA

CAPACITANCE OF INSULATOR

TEV Detector

PULSE TRAVELS

VIA SKIN EFFECT

Page 21: The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the sensor location. For instance; UHF sensor is used to detect PD at cable termination.

HFCT = High Frequency Current Transformer

Does not respond to 50Hz current

Frequency range of 100kHz to 25MHz

Soft ferrite range

Split core construction

High Frequency Current Transformer (HFCT) Sensor

Split core type HFCT sensor

Page 22: The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the sensor location. For instance; UHF sensor is used to detect PD at cable termination.

Connection Diagram: Inductive HFCT sensor

PD Test set

PD Current Pulse

Defect in insulation

HFCT-1 HFCT-2

Page 23: The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the sensor location. For instance; UHF sensor is used to detect PD at cable termination.

UHF = Ultra High Frequency

Response frequency range - 300 MHz to 3,000 MHz

To detect PD fault that are closer to the sensor location. For

instance; UHF sensor is used to detect PD at cable termination.

Ultra High Frequency (UHF) Sensor

Inductive type UHF Sensor

100 MHz – 450MHz

10MHz – 200MHz

Capacitive type UHF Sensor

100MHz-1,000MHz

Page 24: The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the sensor location. For instance; UHF sensor is used to detect PD at cable termination.

Connection Diagram: UHF Capacitive and UHF Inductive Sensor

UHF Inductive

Cable Metallic Screen

Conductor

UHF Capacitive

Bandwidth Converter

PD set

Page 25: The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the sensor location. For instance; UHF sensor is used to detect PD at cable termination.

Online PD Measurement using UHF sensor

To detect PD fault that are closer to the sensor

location

Page 26: The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the sensor location. For instance; UHF sensor is used to detect PD at cable termination.

Embedded Non PD Sensors

Page 27: The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the sensor location. For instance; UHF sensor is used to detect PD at cable termination.

• RTD = Resistance Temperature Detector

• Temperature sensor that contain resistor that change resistance value as

temperature changes

• Act as antenna type PD Sensor to detect defects in stator winding

Resistance Temperature Detector (RTD) as Embedded PD Sensor

Terminal Box Resistant Temperature Detector

Page 28: The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the sensor location. For instance; UHF sensor is used to detect PD at cable termination.

Physical Construction of RTD element and the lead wires

• Two wire Configuration • Three wire Configuration

• Four wire Configuration

Page 29: The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the sensor location. For instance; UHF sensor is used to detect PD at cable termination.

Connection Diagram: Existing RTD as Embedded PD Sensor

RTD Reader

HFCT

MPD

Set 1 MCU

MPD

Set 2

MPD

Set 3

HFCT

HFCT

RTD T1

RTD T2

RTD T3

Page 30: The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the sensor location. For instance; UHF sensor is used to detect PD at cable termination.

Voltage Detection System (VDS) as Embedded PD Sensor

• VDS = Voltage Detection System

• Devices used to detect the presence or absence of operating voltage.

• Act as antenna type PD Sensor to detect defects at the cable termination

Page 31: The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the sensor location. For instance; UHF sensor is used to detect PD at cable termination.

PD set 3

L2

L3

Coupling

electrode

L1

Coupling

electrode

L1 L2 L3

Coupling

electrode

PD set 1

PD set 2

VDS of type LRM

Connection Diagram: VDS as Embedded PD Sensor

Page 32: The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the sensor location. For instance; UHF sensor is used to detect PD at cable termination.

LRM

PD test set

Quadripole

ABB GIS

Online PD Measurement Using VDS as Embedded PD Sensor

Page 33: The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the sensor location. For instance; UHF sensor is used to detect PD at cable termination.

Case Studies

Page 34: The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the sensor location. For instance; UHF sensor is used to detect PD at cable termination.

Case Studies 1:

• Device Under Test (DUT):

2.5MVA 22kV/420V Oil type Transformer at a Chemical Plant in Jurong

Island

• Type of Partial Discharge Sensor Used:

Airborne Ultrasonic sensor

TEV sensor

• Date:

29th January 2016

Page 35: The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the sensor location. For instance; UHF sensor is used to detect PD at cable termination.

PD detection using TEV Sensor

Phase Resolved TEV Transformer 001

Phase Resolved TEV Transformer 002

PD data for Channel 3

Phase (Degrees)

350300250200150100500

PD M

agni

tude

(mV)

7

6

5

4

3

2

1

0

Page 36: The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the sensor location. For instance; UHF sensor is used to detect PD at cable termination.

Audio Analysis => High level abnormal ultrasound was detected Audio Analysis => No Abnormal ultrasound was detected.

Transformer 001 Transformer 002 Frequency Domain Analysis Frequency Domain Analysis

Time Domain Analysis

PD detection using Airborne Ultrasonic Sensor

Page 37: The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the sensor location. For instance; UHF sensor is used to detect PD at cable termination.

Photos of PD during SDM

Page 38: The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the sensor location. For instance; UHF sensor is used to detect PD at cable termination.

Case Studies 2:

• Device Under Test (DUT):

22kV Areva, GIS Switchgear @ Wafer Fab in Pasir Ris

• Type of Partial Discharge Sensor Used:

Contact Ultrasonic sensor

Capacitive UHF sensor

TEV sensor

HFCT sensor

• Date:

14th November 2016

Page 39: The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the sensor location. For instance; UHF sensor is used to detect PD at cable termination.

PD detection using TEV Sensor

Phase Resolved TEV (After replacement of terminations on 10 Jan 2017)

Phase Resolved TEV (Before replacement of terminations on 02nd Nov 2016)

Page 40: The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the sensor location. For instance; UHF sensor is used to detect PD at cable termination.

Phase Resolved Ultrasound (Before replacement of terminations on 02nd Nov 2016)

PD detection using Contact Ultrasonic Sensor

Phase Resolved Ultrasound (After replacement of terminations on 10 Jan 2017)

Page 41: The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the sensor location. For instance; UHF sensor is used to detect PD at cable termination.

Phase Resolved UHF (Before replacement of terminations on 02nd Nov 2016)

PD detection using Capacitive UHF Sensor

Phase Resolved UHF (After replacement of terminations on 10 Jan 2017)

Page 42: The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the sensor location. For instance; UHF sensor is used to detect PD at cable termination.

Phase Resolved HFCT (Before replacement of terminations on 02nd Nov 2016)

PD detection using HFCT Sensor

Phase Resolved HFCT (After replacement of terminations on 10 Jan 2017)

Page 43: The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the sensor location. For instance; UHF sensor is used to detect PD at cable termination.

Phase Resolved HFCT (Before replacement of terminations on 02nd Nov 2016)

PD detection using HFCT Sensor

Phase Resolved HFCT (After replacement of terminations on 10 Jan 2017)

Page 44: The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the sensor location. For instance; UHF sensor is used to detect PD at cable termination.

Photos of PD during SDM

Observation : Partial Discharge at the Cable Termination of the Blue Phase.

Page 45: The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the sensor location. For instance; UHF sensor is used to detect PD at cable termination.

Case Studies 3:

• Device Under Test (DUT):

2MVA, 22kV/420V Oil Type Transformer @ a Biofuel plant

• Type of Partial Discharge Sensor Used:

TEV sensor

Capacitive UHF sensor

HFCT sensor

• Date:

18th May 2017

Page 46: The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the sensor location. For instance; UHF sensor is used to detect PD at cable termination.

Phase Resolved TEV (After replacement of terminations on 07th Sept 2017)

Phase Resolved TEV (Before replacement of terminations on 18th May 2017)

PD detection using TEV Sensor

Page 47: The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the sensor location. For instance; UHF sensor is used to detect PD at cable termination.

Phase Resolved UHF (Before replacement of terminations on 18th May 2017)

PD detection using Capacitive UHF Sensor

Phase Resolved UHF (After replacement of terminations on 07th Sept 2017)

Page 48: The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the sensor location. For instance; UHF sensor is used to detect PD at cable termination.

Phase Resolved HFCT (Before replacement of terminations on 18th May 2017)

PD detection using HFCT Sensor

Phase Resolved HFCT (After replacement of terminations on 07th Sept 2017)

Page 49: The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the sensor location. For instance; UHF sensor is used to detect PD at cable termination.

Photos of PD during SDM

Observation : During Shutdown, Rust was found at the 22kV cable termination.

Page 50: The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the sensor location. For instance; UHF sensor is used to detect PD at cable termination.

Case Studies 4:

• Device Under Test (DUT):

VT of 22kV Yorkshire, AIS Switchgear

• Type of Partial Discharge Sensor Used:

TEV sensor

Capacitive UHF sensor

HFCT sensor

• Date:

07th May 2018

Page 51: The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the sensor location. For instance; UHF sensor is used to detect PD at cable termination.

PD detection using TEV Sensor

DFA300

Phase Resolved TEV (AFTER ISOLATING VT2 on August 2018)

PD data for multi Channels

Phase (Degrees)

350300250200150100500

PD M

agnit

ude (

mV)

280

260

240

220

200

180

160

140

120

100

80

60

40

20

0

PD data for multi Channels

Phase (Degrees)

350300250200150100500

PD M

agnitu

de (m

V)

35

30

25

20

15

10

5

0

Phase Resolved TEV (BEFORE ISOLATING VT2 on May 2018)

OSM-ST1

Page 52: The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the sensor location. For instance; UHF sensor is used to detect PD at cable termination.

Phase Resolved UHF (BEFORE ISOLATING VT2 on May 2018)

Phase Resolved UHF (AFTER ISOLATING VT2 on August 2018)

PD detection using Capacitive UHF Sensor

Page 53: The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the sensor location. For instance; UHF sensor is used to detect PD at cable termination.

Phase Resolved HFCT (BEFORE ISOLATING VT2 on May 2018)

Phase Resolved HFCT (AFTER ISOLATING VT2 on August 2018)

PD detection using HFCT Sensor

Page 54: The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the sensor location. For instance; UHF sensor is used to detect PD at cable termination.

Observation : Visible crack at 22kV VT.

Photos of PD during SDM

Page 55: The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the sensor location. For instance; UHF sensor is used to detect PD at cable termination.

Case Studies 5:

• Device Under Test (DUT):

22kV Alstom GMA, GIS Switchgear

• Type of Partial Discharge Sensor Used:

Airborne Ultrasonic sensor

TEV sensor

Capacitive UHF sensor

HFCT sensor

Infra-Red scanning

• Date:

19th May 2018

Page 56: The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the sensor location. For instance; UHF sensor is used to detect PD at cable termination.

Phase Resolved Ultrasound (Partial Discharge in cable termination on 19th May 2018)

PD detection using Airborne Ultrasonic Sensor

Phase Resolved Ultrasound (AFTER Rectifiction on 26th May 2018)

Page 57: The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the sensor location. For instance; UHF sensor is used to detect PD at cable termination.

Phase Resolved UHF (Partial Discharge in cable termination on 19th May 2018)

Phase Resolved UHF (AFTER Rectification on 26th May 2018)

PD detection using Capacitive UHF Sensor

Page 58: The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the sensor location. For instance; UHF sensor is used to detect PD at cable termination.

Phase Resolved HFCT (Partial Discharge in cable termination on 19th May 2018)

Phase Resolved HFCT (AFTER Rectification on 26th May 2018)

PD detection using HFCT Sensor

Page 59: The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the sensor location. For instance; UHF sensor is used to detect PD at cable termination.

PD detection using TEV Sensor

Phase Resolved TEV (AFTER rectification on 26th May 2018)

Phase Resolved TEV (Partial Discharge in cable termination on 19th May 2018)

Page 60: The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the sensor location. For instance; UHF sensor is used to detect PD at cable termination.

PD detection using Infra-Red

Phase Resolved HFCT (Partial Discharge in cable termination on 19th May 2018)

Phase Resolved HFCT (AFTER Rectification on 26th May 2018)

Page 61: The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the sensor location. For instance; UHF sensor is used to detect PD at cable termination.

Observation : Partial discharge was found at the cable lug of L3 with green discoloration.

Photos of PD during SDM

Page 62: The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the sensor location. For instance; UHF sensor is used to detect PD at cable termination.

Q & A

Page 63: The use of multiple sensors, of electrical and non ... · To detect PD fault that are closer to the sensor location. For instance; UHF sensor is used to detect PD at cable termination.

Thank you.