The Smart Electricity Grid - Engineers Australia · Radial energy flows “Blind” Operation...

50
The Smart Electricity Grid Engineers Australia Sydney Division Southern Highlands and Tablelands Regional Group Thursday 24 th June Robin Eckermann Principal, Eckermann & Associates Adjunct Professor, University of Canberra representing the CURRENT Group

Transcript of The Smart Electricity Grid - Engineers Australia · Radial energy flows “Blind” Operation...

Page 1: The Smart Electricity Grid - Engineers Australia · Radial energy flows “Blind” Operation Largely manual fault finding & service restoration Inefficiencies & losses . DANGER!

The Smart Electricity GridEngineers Australia – Sydney Division

Southern Highlands and Tablelands Regional Group

Thursday 24th June

Robin EckermannPrincipal, Eckermann & Associates

Adjunct Professor, University of Canberrarepresenting the CURRENT Group

Page 2: The Smart Electricity Grid - Engineers Australia · Radial energy flows “Blind” Operation Largely manual fault finding & service restoration Inefficiencies & losses . DANGER!

Think …

… about how

broadband has

changed the

world over the

last 15 years

Page 3: The Smart Electricity Grid - Engineers Australia · Radial energy flows “Blind” Operation Largely manual fault finding & service restoration Inefficiencies & losses . DANGER!

Voice-over-IP (VOIP) Telephony

ATA (Analog Telephony Adapter) interfaces a conventional phone

to the broadband connection

Portable phone number

Voice messages forwarded by email

Local numbers interstate & overseas

Page 4: The Smart Electricity Grid - Engineers Australia · Radial energy flows “Blind” Operation Largely manual fault finding & service restoration Inefficiencies & losses . DANGER!
Page 5: The Smart Electricity Grid - Engineers Australia · Radial energy flows “Blind” Operation Largely manual fault finding & service restoration Inefficiencies & losses . DANGER!

MP3 Music

Page 6: The Smart Electricity Grid - Engineers Australia · Radial energy flows “Blind” Operation Largely manual fault finding & service restoration Inefficiencies & losses . DANGER!

New &better

approachesto old

problems

Page 7: The Smart Electricity Grid - Engineers Australia · Radial energy flows “Blind” Operation Largely manual fault finding & service restoration Inefficiencies & losses . DANGER!

Check thepremises

fromanywhere

in theworldvia theInternet

Page 8: The Smart Electricity Grid - Engineers Australia · Radial energy flows “Blind” Operation Largely manual fault finding & service restoration Inefficiencies & losses . DANGER!

Multi-camera view

Page 9: The Smart Electricity Grid - Engineers Australia · Radial energy flows “Blind” Operation Largely manual fault finding & service restoration Inefficiencies & losses . DANGER!

Mobile Phone Access

Record on any camera

Alert others

by SMS

Feed the dog

Open garage &

record

Page 10: The Smart Electricity Grid - Engineers Australia · Radial energy flows “Blind” Operation Largely manual fault finding & service restoration Inefficiencies & losses . DANGER!

SimpleInternet

DogFeeder

Receives wireless signal

Activates solenoid& buzzer

Pulls this end of arm up

This end of arm goes

down

Catch releases & bucket tips & dumps dry food

Page 11: The Smart Electricity Grid - Engineers Australia · Radial energy flows “Blind” Operation Largely manual fault finding & service restoration Inefficiencies & losses . DANGER!

Dog feeder

under video

surveillance

Page 12: The Smart Electricity Grid - Engineers Australia · Radial energy flows “Blind” Operation Largely manual fault finding & service restoration Inefficiencies & losses . DANGER!

The World’s most Globally-fed Dog?

Page 13: The Smart Electricity Grid - Engineers Australia · Radial energy flows “Blind” Operation Largely manual fault finding & service restoration Inefficiencies & losses . DANGER!

Sprung!

Caught in the act of trying to guess the password for

the dog feeder

(nobody knows you’re a dog on the Internet!)

Page 14: The Smart Electricity Grid - Engineers Australia · Radial energy flows “Blind” Operation Largely manual fault finding & service restoration Inefficiencies & losses . DANGER!

Think aboutthe possibilities

in areas likeaged care!

(helping olderpeople to live

safely at homefor longer)

Page 15: The Smart Electricity Grid - Engineers Australia · Radial energy flows “Blind” Operation Largely manual fault finding & service restoration Inefficiencies & losses . DANGER!

VideoConferencing

An enhancedcommunicationsexperience, butit needs:

• speed

• symmetricbandwidth

Page 16: The Smart Electricity Grid - Engineers Australia · Radial energy flows “Blind” Operation Largely manual fault finding & service restoration Inefficiencies & losses . DANGER!

High-end “Tele-Presence”

Dare to imagine that the “high end” business technology of today might filter its way down to consumer use tomorrow!

Photo courtesy of

Page 17: The Smart Electricity Grid - Engineers Australia · Radial energy flows “Blind” Operation Largely manual fault finding & service restoration Inefficiencies & losses . DANGER!

ThomasEdison1847-1931

AlexanderGraham

Bell1847-1922

?

Page 18: The Smart Electricity Grid - Engineers Australia · Radial energy flows “Blind” Operation Largely manual fault finding & service restoration Inefficiencies & losses . DANGER!

Utilities haven’t changed muchfor decades, but there are new

challenges on the horizon!

• Ageing workforce• Environmental concerns• Increasing demand & rising costs

Page 19: The Smart Electricity Grid - Engineers Australia · Radial energy flows “Blind” Operation Largely manual fault finding & service restoration Inefficiencies & losses . DANGER!

Radial energyflows

“Blind” Operation

Largely manual faultfinding & service

restoration

Inefficiencies& losses

Page 20: The Smart Electricity Grid - Engineers Australia · Radial energy flows “Blind” Operation Largely manual fault finding & service restoration Inefficiencies & losses . DANGER!

DANGER!

2005(actual):380 PPM

2050(predicted):480-580 PPM

1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000

600

550

500

450

400

350

300

250

Atmospheric CO2 Concentrations(parts-per-million, 1010-1978 AD, from carbon-dated ice cores)

For the last 400,000 yrs CO2 levels

have varied between 180 & 300 PPM

2010

392

Page 21: The Smart Electricity Grid - Engineers Australia · Radial energy flows “Blind” Operation Largely manual fault finding & service restoration Inefficiencies & losses . DANGER!

Electricity is under the spotlight!

Australia 2005:559m tonnes

CO2 emissions

About the world’sworst on a per capita basis!

Electricity usagerepresents ~35%

EPRI: 13-25%GHG reduction

from Smart Grids

Page 22: The Smart Electricity Grid - Engineers Australia · Radial energy flows “Blind” Operation Largely manual fault finding & service restoration Inefficiencies & losses . DANGER!

1989 BMW 535i

3.4 litres155 kW

0-100 km/h in 8.6s 12.3 l/100km

2007 BMW 525i

2.5 litres160 kW

0-100 km/h in 7.9s9.4 l/100km

Smart engine technology (embeddedmicro-computers & communications)

accounts for most of the improvement

Page 23: The Smart Electricity Grid - Engineers Australia · Radial energy flows “Blind” Operation Largely manual fault finding & service restoration Inefficiencies & losses . DANGER!

How can a Gridbe made Smart?

By infusing it with:

1. Sensing

2. Communications

3. Analytics

4. Control

Page 24: The Smart Electricity Grid - Engineers Australia · Radial energy flows “Blind” Operation Largely manual fault finding & service restoration Inefficiencies & losses . DANGER!

The Starting Point for Smart Grids(gaining visibility into and control over

the network – from end to end)

SCADA already exists down tozone substations

Distribution transformers are the next most populous element in the network

Page 25: The Smart Electricity Grid - Engineers Australia · Radial energy flows “Blind” Operation Largely manual fault finding & service restoration Inefficiencies & losses . DANGER!

Sensing Energy Flows

Rogowski Coil – accurate to 1%

Clamp-on (no outage)

Automatic calibration

Page 26: The Smart Electricity Grid - Engineers Australia · Radial energy flows “Blind” Operation Largely manual fault finding & service restoration Inefficiencies & losses . DANGER!

Bolt-on devicewith:

• Processor• Low & mediumvoltage Sensing

• Upstream comms• Downstream comms• Other inputs & outputs

. Transformer Monitoring

Page 27: The Smart Electricity Grid - Engineers Australia · Radial energy flows “Blind” Operation Largely manual fault finding & service restoration Inefficiencies & losses . DANGER!

Horses for courses(no silver-bullet solution)

Options include• Optical Fibre (NBN?)

• Wireless (WiMAX, 3G)

• Ethernet (xDSL)

• MV BPL

Upstream Communications(from the transformer)

Page 28: The Smart Electricity Grid - Engineers Australia · Radial energy flows “Blind” Operation Largely manual fault finding & service restoration Inefficiencies & losses . DANGER!

. Central Systems

Page 29: The Smart Electricity Grid - Engineers Australia · Radial energy flows “Blind” Operation Largely manual fault finding & service restoration Inefficiencies & losses . DANGER!

PortableMonitoring

Page 30: The Smart Electricity Grid - Engineers Australia · Radial energy flows “Blind” Operation Largely manual fault finding & service restoration Inefficiencies & losses . DANGER!

Communication requirements areinfluenced by the approach

Dumb sensingand a flood

of rawinformation

Limited sensingand a drip-feed

of scantyinformation

Smart sensingand a timely

feed of qualityinformation

Page 31: The Smart Electricity Grid - Engineers Australia · Radial energy flows “Blind” Operation Largely manual fault finding & service restoration Inefficiencies & losses . DANGER!

Critical Requirementsfor SG Communications Fabric

Reliabilityand Security

LowLatency

Load-handlingCapacity

Page 32: The Smart Electricity Grid - Engineers Australia · Radial energy flows “Blind” Operation Largely manual fault finding & service restoration Inefficiencies & losses . DANGER!

The Benefits(from the upgrades discussed thus far)

Grid Optimisation

• Conserve voltages, balance phases, reduce losses• 3-5% saving in power & associated carbon• no change in user behaviour required

Distribution Monitoring & Control

• Immediate fault recognition & root cause analysis• Location pin-pointed, crews sent with right equipment• Repairs verified before leaving the site• Equipment operated within tolerances, extending life• Looming failures predicted and avoided

Page 33: The Smart Electricity Grid - Engineers Australia · Radial energy flows “Blind” Operation Largely manual fault finding & service restoration Inefficiencies & losses . DANGER!

Next comesthe meter!

(in extending visibility & control)

Critically located at the point of interfacebetween the grid andthe consumer’s world

Most expensiveelement to replace

Central role inDemand-Response

Page 34: The Smart Electricity Grid - Engineers Australia · Radial energy flows “Blind” Operation Largely manual fault finding & service restoration Inefficiencies & losses . DANGER!

Designing & Building for Peaks

0

100

200

300

400

500

600

7000

0:0

0

01

:00

02

:00

03

:00

04

:00

05

:00

06

:00

07

:00

08

:00

09

:00

10

:00

11

:00

12

:00

13

:00

14

:00

15

:00

16

:00

17

:00

18

:00

19

:00

20

:00

21

:00

22

:00

23

:00

00

:00

MW

Page 35: The Smart Electricity Grid - Engineers Australia · Radial energy flows “Blind” Operation Largely manual fault finding & service restoration Inefficiencies & losses . DANGER!

“Smart Meters”(Advanced Metering Infrastructure)

Time-of-day

pricing to

change human

behaviour &

discourage

discretionary

use during

peak periods

Page 36: The Smart Electricity Grid - Engineers Australia · Radial energy flows “Blind” Operation Largely manual fault finding & service restoration Inefficiencies & losses . DANGER!

That’s >100 million foldincrease in computingpower over the period!

In 1965 Gordon Moore predicted a doubling of silicon densities (and computing power) every 24 months

Moore’s Law is now 45 years old and power has been doubling every 18-24 months

Page 37: The Smart Electricity Grid - Engineers Australia · Radial energy flows “Blind” Operation Largely manual fault finding & service restoration Inefficiencies & losses . DANGER!

Human

EquivalentBrainPower

Bacterium

NematodeWorm

Spider

Lizard

Mouse

Monkey

1900 1920 1940 1960 1980 2000 2020

1

1000

Million

1Billion

1Million

11000

UNIVAC1

IBM 650IBM 1620

IBM704

IBM7090

IBM 360/50

IBM 7040

DEC PDP10 VAX 11/750

CDC7600DG NOVA

Apple2

VAX 11/780

Sun3

IBM PC

MAC II

IBM PS2/90

PowerMac 8100/80Gateway G6-200

MIPS (millionsof instructionsper second)

per $US1,000

Year

ColossusENIAC

Zuse-1

MonroeCalculator

BurroughsClass 16

IBM Tabulator

Source: Hans Moravec (1997)

ProfoundConsequences!

Page 38: The Smart Electricity Grid - Engineers Australia · Radial energy flows “Blind” Operation Largely manual fault finding & service restoration Inefficiencies & losses . DANGER!

In 15 yrs a 1000-foldincrease inICT power

Smartdigital

appliances

Focuson energy

management

Over theHorizon

Page 39: The Smart Electricity Grid - Engineers Australia · Radial energy flows “Blind” Operation Largely manual fault finding & service restoration Inefficiencies & losses . DANGER!

Renewables

From traditionalradial energy

flows to a mesh

Volatile – eitherunderwrite capacity

or dynamicallybalance supply

& demand

Highlights theneed for end-to-end

visibility & control

Page 40: The Smart Electricity Grid - Engineers Australia · Radial energy flows “Blind” Operation Largely manual fault finding & service restoration Inefficiencies & losses . DANGER!

Think about the challenges ofhigh photo-voltaic uptake

Page 41: The Smart Electricity Grid - Engineers Australia · Radial energy flows “Blind” Operation Largely manual fault finding & service restoration Inefficiencies & losses . DANGER!

0:0

0

1:0

0

2:0

0

3:0

0

4:0

0

5:0

0

6:0

0

7:0

0

8:0

0

9:0

0

10

:00

11

:00

12

:00

13

:00

14

:00

15

:00

16

:00

17

:00

18

:00

19

:00

20

:00

21

:00

22

:00

23

:00

24

:00

10

9

8

7

6

5

4

3

2

1

Demand

“Hotspots” where supply>demand!k

W (

kil

ow

att

s)

Solar Supply

Page 42: The Smart Electricity Grid - Engineers Australia · Radial energy flows “Blind” Operation Largely manual fault finding & service restoration Inefficiencies & losses . DANGER!

Huge opportunities withemerging appliances likeplug-in electric vehicles

Latitude in the timing ofovernight recharging

Huge, distributed energystore for the grid

Needs communications!

Page 43: The Smart Electricity Grid - Engineers Australia · Radial energy flows “Blind” Operation Largely manual fault finding & service restoration Inefficiencies & losses . DANGER!

OK … it’s Tuesday, so you can have 10 kWh and that will still leave me enough energy to get home after work

I’m desperate. How about $1.00/kWh?

No deal!

The Grid Plug-inElectricVehicle

Things are starting to run hot here! Can you pause recharging?

Sure! I’ve got nothing on for the next 8 hours

Its just gone from bad to worse. I’ll offer $0.50 per kWh for anything you can give me …

Page 44: The Smart Electricity Grid - Engineers Australia · Radial energy flows “Blind” Operation Largely manual fault finding & service restoration Inefficiencies & losses . DANGER!

The communication requirementsof a Smart Grid start to look very

different from those of Smart Meters!

“Smart Meters” using comms solutions lacking real-time performance and the capacity to handle flurries of high-volume traffic will either:

• limit progress or • need upgrading!

Page 45: The Smart Electricity Grid - Engineers Australia · Radial energy flows “Blind” Operation Largely manual fault finding & service restoration Inefficiencies & losses . DANGER!

Smart MetersEnabler or blocker?

Questionable effectiveness of pricing signals

Limited commsrequirements

Risky to startreplacing meters

ahead of SG plan!

Page 46: The Smart Electricity Grid - Engineers Australia · Radial energy flows “Blind” Operation Largely manual fault finding & service restoration Inefficiencies & losses . DANGER!

Potential to use theNational Broadband Network?

No questions abouttechnical capability

Pragmatic issues:

• Location of Optical NetworkTermination (ONT)

• ONT powering• ONT connection• Customers with no otherNBN services

In-grid alternatives mayprove easier (eg: PRIME)

Page 47: The Smart Electricity Grid - Engineers Australia · Radial energy flows “Blind” Operation Largely manual fault finding & service restoration Inefficiencies & losses . DANGER!

Greenfields Opportunity

Brownfields issuesresolved by design

Will utilities want to support separategreenfield/brownfieldapproaches?

Slow attainment ofcritical mass!

Page 48: The Smart Electricity Grid - Engineers Australia · Radial energy flows “Blind” Operation Largely manual fault finding & service restoration Inefficiencies & losses . DANGER!

Optical Fibre?

NBN aerial deployment will pass many transformers,and meter and ONT may be as little as 1 metre apart

Page 49: The Smart Electricity Grid - Engineers Australia · Radial energy flows “Blind” Operation Largely manual fault finding & service restoration Inefficiencies & losses . DANGER!

Summary: Smart Grids are Coming!

They represent a wave of innovation that will transform the way we generate, distribute, store and use energy

They lay the foundations for mitigating the impact on the environment of our unrelenting appetite for energy

There will be lots ofchallenges … and lots of new business opportunities

Page 50: The Smart Electricity Grid - Engineers Australia · Radial energy flows “Blind” Operation Largely manual fault finding & service restoration Inefficiencies & losses . DANGER!

Thank You

Robin Eckermann

Principal, Eckermann & AssociatesAdjunct Professor, University of Canberra

Representing CURRENT GroupEmail: .

Phone: +61-2-61-61-61-61

for allowing me to share these thoughts with you!