Paul Denholm Erik Ela Brendan Kirby Michael Milligan March 2010 NREL/PR-6A2-49396 The Role of Energy Storage with Renewable Electricity Generation (Report Summary)

Transcript of The Role of Energy Storage with Renewable Electricity ... · The Role of Energy Storage with...

Page 1: The Role of Energy Storage with Renewable Electricity ... · The Role of Energy Storage with Renewable Electricity Generation (Report Summary) Outline • Operation of the Electric

Paul DenholmErik ElaBrendan KirbyMichael Milligan

March 2010

NREL/PR-6A2-49396

The Role of Energy Storage with Renewable Electricity Generation (Report Summary)

Page 2: The Role of Energy Storage with Renewable Electricity ... · The Role of Energy Storage with Renewable Electricity Generation (Report Summary) Outline • Operation of the Electric

Outline

• Operation of the Electric Grid

• Electricity Storage in the Existing Grid

• Impacts of Renewables on the Grid and the Role of Enabling Technologies

• Storage and Flexibility Options for Renewable-Driven Grid Applications

• Conclusions

National Renewable Energy Laboratory Innovation for Our Energy Future2

Page 3: The Role of Energy Storage with Renewable Electricity ... · The Role of Energy Storage with Renewable Electricity Generation (Report Summary) Outline • Operation of the Electric

Operation of the Electric Grid

• Supply must always meet demand

• Large hourly and season variations in electricity demand

• Operating reserve requirements to maintain system stability and reliability

National Renewable Energy Laboratory Innovation for Our Energy Future3

Page 4: The Role of Energy Storage with Renewable Electricity ... · The Role of Energy Storage with Renewable Electricity Generation (Report Summary) Outline • Operation of the Electric

Large Demand Variability

0.0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

0

10000

20000

30000

40000

50000

60000

0 24 48 72 96 120 144 168

Load

(Fra

ctio

n of

Ann

ual P

eak)

Load

(MW

)

Hour

Summer Maximum Winter Spring Minimum

Hourly electricity demand for three weeks in the ERCOT (Texas) Grid in 2005

Requires multiple generator types: baseload, load-following (intermediate load and peaking)

4National Renewable Energy Laboratory Innovation for Our Energy Future

Page 5: The Role of Energy Storage with Renewable Electricity ... · The Role of Energy Storage with Renewable Electricity Generation (Report Summary) Outline • Operation of the Electric

Reserve Requirements

• Provides stable and reliable operation

• Not uniformly defined

• Frequency Regulation– Serves the random, rapid variation around the normal load

– Highest value

• Contingency Reserve (often referred to as spinning reserves)

– Quickly replaces a lost generator or transmission line

– Infrequently called ~ 1x/week for about 10 minutes

National Renewable Energy Laboratory Innovation for Our Energy Future5

Page 6: The Role of Energy Storage with Renewable Electricity ... · The Role of Energy Storage with Renewable Electricity Generation (Report Summary) Outline • Operation of the Electric

Frequency Regulation Requirements

National Renewable Energy Laboratory Innovation for Our Energy Future6

System load following and regulation. Regulation (red) is the fast fluctuating component of total load (green)

while load following (blue) is the slower trend

Page 7: The Role of Energy Storage with Renewable Electricity ... · The Role of Energy Storage with Renewable Electricity Generation (Report Summary) Outline • Operation of the Electric

Reserve Requirements Add Costs

• Non-economic dispatch• Part-load inefficiencies• Additional units online

National Renewable Energy Laboratory Innovation for Our Energy Future7

0

500

1000

1500

2000

2500

3000

0 4 8 12 16 20 24Hour

Load

(MW

) Peak 2Peak 1IntBase2Base 1

0

500

1000

1500

2000

2500

3000

0 4 8 12 16 20 24Hour

Load

(MW

)

Insufficient Flexibility to Provide Reserves

Lower Cost Unit Backed Off To Accommodate Higher Cost Flexible

Generator

Insufficient Reserve Capacity

“Ideal” Dispatch

Higher Cost Unit Started Early To Provide Reserve

Capacity

Reserve Constrained Dispatch

Page 8: The Role of Energy Storage with Renewable Electricity ... · The Role of Energy Storage with Renewable Electricity Generation (Report Summary) Outline • Operation of the Electric

Energy Storage in the Existing Grid

• Historical motivations

• Renewed interest due to emergence of restructured markets

• Applications of energy storage

National Renewable Energy Laboratory Innovation for Our Energy Future8

Page 9: The Role of Energy Storage with Renewable Electricity ... · The Role of Energy Storage with Renewable Electricity Generation (Report Summary) Outline • Operation of the Electric

9

Electricity Storage in the Existing Grid

Historical motivations (pre-1980)

• Storage provides load following and reserves, while increasing use of low-cost baseload plants

• Limited options for peaking and intermediate load generation – Increasing cost of natural gas and oil

– Restrictions on use of oil and natural gas (Power Plant and Industrial Fuel Use Act)

– Low-efficiency oil and steam gas plants as opposed to today’s efficient gas turbines

• Anticipated construction of many nuclear plants providing low cost (but inflexible) baseload energy

National Renewable Energy Laboratory Innovation for Our Energy Future9

Page 10: The Role of Energy Storage with Renewable Electricity ... · The Role of Energy Storage with Renewable Electricity Generation (Report Summary) Outline • Operation of the Electric

10

Pumped Hydro

National Renewable Energy Laboratory Innovation for Our Energy Future10

0.0

2.0

4.0

6.0

8.0

10.0

12.0

14.0

1976

1977

1978

1979

1980

1981

1982

1983

1984

1985

1986

1987

1988

1989

1990

1991

1992

1993

1994

1995

1996

1997

1998

1999

2000

2001

2002

2003

2004

2005

2006

2007

2008

Year

Fuel

Cos

t (2

008

Cent

s/kW

h)

Gas SteamOil SteamGas CCGTStorage (Coal Charging)

Variable costs of storage are less than from oil or gas

Pumped hydro costs during this period (before 1980) are comparable to combined-cycle gas generators

Was an attractive alternative to other load-following generators

Page 11: The Role of Energy Storage with Renewable Electricity ... · The Role of Energy Storage with Renewable Electricity Generation (Report Summary) Outline • Operation of the Electric

11

Limited Storage Built after 1980

National Renewable Energy Laboratory Innovation for Our Energy Future11

• Collapse of oil and gas prices

• Repeal of fuel use act

• High-efficiency low cost gas turbines become available

• Storage development limited to ~20GW of pumped hydro storage, 1 CAES plant plus a few batteries and demonstration projects

Page 12: The Role of Energy Storage with Renewable Electricity ... · The Role of Energy Storage with Renewable Electricity Generation (Report Summary) Outline • Operation of the Electric

12

Revised Interest in Energy Storage

National Renewable Energy Laboratory Innovation for Our Energy Future12

• Advances in storage technologies

• Increases in fossil fuel prices

• Energy markets

• T&D siting challenges

• Perceived need for storage with renewables

Page 13: The Role of Energy Storage with Renewable Electricity ... · The Role of Energy Storage with Renewable Electricity Generation (Report Summary) Outline • Operation of the Electric

13

Value of Storage in Restructured MarketsHistorical Values of Energy Storage in Restructured Electricity Markets

Market Evaluated

Location Years Evaluated

Annual Value ($/kW)

Assumptions

Energy Arbitrage

PJMa 2002-2007 $60-$115 12 hour, 80% efficient device. Range of efficiencies and sizes evaluated[1]

NYISOb 2001-2005 $87-$240 (NYC)$29-$84 (rest)

10 hour, 83% efficient device. Range of efficiencies and sizes evaluated.

USAc 1997-2001 $37-$45 80% efficient device, Covers NE, No Cal, PJM

CAd 2003 $49 10 hour, 90% efficient device.

Regulation NYISOb 2001-2005 $163-248

USAe 2003-2006 $236-$429 PJM, NYISO, ERCOT, ISONE

Contingency Reserves

USAe 2004-2005 $66-$149 PJM, NYISO, ERCOT, ISONE

a Sioshansi et al. 2009b Walawalkar et al. 2007c Figueiredo et al. 2006 d Eyer et al. 2004e Denholm and Letendre 2007

13National Renewable Energy Laboratory Innovation for Our Energy Future

Page 14: The Role of Energy Storage with Renewable Electricity ... · The Role of Energy Storage with Renewable Electricity Generation (Report Summary) Outline • Operation of the Electric

14

Historical Value of Energy Storage in U.S. Markets

National Renewable Energy Laboratory Innovation for Our Energy Future14

0

500

1000

1500

2000

2500

3000

3500

4000

0 50 100 150 200 250 300 350

Annual Benefit of Storage ($/kW)

Requ

ired

Stor

age

Capi

tal C

ost (

$/kW

)9.8%12.0%13.9%

Capital Charge Rate

Arbitrage Only

Contingency Only

Regulation Only

Relationship between total installed cost and annualized cost

Greatest value is frequency regulation – focus of many applications (flywheels, vehicle to grid). Arbitrage alone is generally insufficient to support most storage technologies, which are generally >$1,000/kW

Page 15: The Role of Energy Storage with Renewable Electricity ... · The Role of Energy Storage with Renewable Electricity Generation (Report Summary) Outline • Operation of the Electric

15

Applications of Energy Storage

ApplicationDescription Timescale of Operation

Load Leveling/Arbitrage

Purchasing low-cost off-peak energy and selling it during periods of high prices.

Response in minutes to hours. Discharge time of hours.

Firm Capacity Provide reliable capacity to meet peak system demand.

Must be able to discharge continuously for several hours or more.

Operating Reserves

Regulation

ContingencySpinning Reserve[1]

Replacement/Supplemental

Fast responding increase or decrease in generation (or load) to respond to random, unpredictable variations in demand.

Fast response increase in generation (or decrease load) to respond to a contingency such as a generator failure.

Units brought on-line to replace spinning units.

Unit must be able to respond in seconds to minutes. Discharge time is typically minutes. Service is theoretically “net zero” energy over extended time periods.

Unit must begin responding immediately and be fully responsive within 10 minutes. Must be able to hold output for 30 minutes to 2 hours depending on the market. Service is infrequently called.[2]

Typical response time requirement of 30-60 minutes depending on market minutes. Discharge time may be several hours.

Ramping/Load Following

Follow longer term (hourly) changes in electricity demand.

Response time in minutes to hours. Discharge time may be minutes to hours.

T&D Replacement and Deferral

Reduce loading on T&D system during peak times.

Response in minutes to hours. Discharge time of hours.

Black-Start Units brought online to start system after a system-wide failure (blackout).

Response time requirement is several minutes to over an hour. Discharge time requirement may be several to many hours.[3]

End-Use ApplicationsTOU Rates

Demand ChargeReduction

Backup Power/UPS/Power Quality

Functionally the same as arbitrage, just at the customer site.Functionally the same as firm capacity, just at the customer site.

Functionally the same as contingency reserve, just at the customer site.

Same as arbitrage.

Same as firm capacity.I

nstantaneous response. Discharge time depends on level of reliability needed by customer.

15National Renewable Energy Laboratory Innovation for Our Energy Future

Page 16: The Role of Energy Storage with Renewable Electricity ... · The Role of Energy Storage with Renewable Electricity Generation (Report Summary) Outline • Operation of the Electric

16

Impacts of Renewables on the Grid

• Storage is often perceived as “necessary” for renewables to achieve a large (>10%? >20%?) penetration.

• Renewables are seen as a source of value for storage

• Can renewables be used without storage?

• How do renewables impact the grid?

National Renewable Energy Laboratory Innovation for Our Energy Future16

Page 17: The Role of Energy Storage with Renewable Electricity ... · The Role of Energy Storage with Renewable Electricity Generation (Report Summary) Outline • Operation of the Electric

17

Impacts of Renewables on the Grid

National Renewable Energy Laboratory Innovation for Our Energy Future17

0

5000

10000

15000

20000

25000

30000

35000

40000

45000

50000

1-Apr 8-Apr 15-Apr

MW

Load Wind Net Load

Variation in wind output increases net load ramp ate (Increases in this period from 4,052 MW/hour to 4,560 MW/hour)

Uncertainty in wind output increases uncertainty in net

load to be met with conventional generators

Ramp Range (Increases in this two-week period from

19.3 GW/day to 26.2 GW/day)

Four major impacts of variable generation (VG) on the grid:1) Increased need for frequency regulation2) Increase in hourly ramp rate3) Increase in uncertainty of net load4) Increase in ramp range

Page 18: The Role of Energy Storage with Renewable Electricity ... · The Role of Energy Storage with Renewable Electricity Generation (Report Summary) Outline • Operation of the Electric

Costs of Wind Integration

• Simulate system with and without solar and wind

– Use unit commitment software includes existing generation mix, transmission system

– Use lots of wind and solar simulations to consider spatial diversity

– May involve substantial costs

• Evaluate costs of:– Additional regulation reserves– Additional load following– Wind uncertainty

18National Renewable Energy Laboratory Innovation for Our Energy Future

Page 19: The Role of Energy Storage with Renewable Electricity ... · The Role of Energy Storage with Renewable Electricity Generation (Report Summary) Outline • Operation of the Electric

19

Costs of Wind Integration

Date Study

Wind Capacity Penetration

(%)

Regulation Cost

($/MWh)

Load-Following Cost

($/MWh)

Unit Commitment Cost ($/MWh)

Other($/MWh)

Total Oper. Cost Impact

($/MWh)

2003 Xcel-UWIG 3.5 0 0.41 1.44 Na 1.85

2003 WE Energies 29 1.02 0.15 1.75 Na 2.92

2004 Xcel-MNDOC 15 0.23 na 4.37 Na 4.6

2005 PacifiCorp-2004 11 0 1.48 3.16 Na 4.64

2006 Calif. (multi-year)a 4 0.45 trace trace Na 0.45

2006 Xcel-PSCob 15 0.2 na 3.32 1.45 4.97

2006 MN-MISOc 36 na na na na 4.41

2007 Puget Sound Energy 12 na na na na 6.94

2007 Arizona Pub. Service 15 0.37 2.65 1.06 na 4.08

2007 Avista Utilitiesd 30 1.43 4.4 3 na 8.84

2007 Idaho Power 20 na na na na 7.92

2007 PacifiCorp-2007 18 na 1.1 4 na 5.1

2008 Xcel-PSCoe 20 na na na na 8.56a Regulation costs represent 3-year average.b The Xcel/PSCO study also examine the cost of gas supply scheduling. Wind increases the uncertainty of gas requirements and may increase

costs of gas supply contracts. c Highest over 3-year evaluation period. 30.7% capacity penetration corresponding to 25% energy penetrationd Unit commitment includes cost of wind forecast error.e This integration cost reflects a $10/MMBtu natural gas scenario. This cost is much higher than the integration cost calculated for Xcel-PSCo in 2006, in large measure due to the higher natural gas price: had the gas price from the 2006 study been used in the 2008 study, the integration cost would drop from $8.56/MWh to $5.13/MWh.

19National Renewable Energy Laboratory Innovation for Our Energy Future

Page 20: The Role of Energy Storage with Renewable Electricity ... · The Role of Energy Storage with Renewable Electricity Generation (Report Summary) Outline • Operation of the Electric

20

Conclusions of Wind Integration Studies (<30% Penetration)

• Challenges are unit commitment, regulation and load following

• Integration costs are modest (typically less than $5/MWh)

• Increased variability can be accommodates by existing generator flexibility and other “low-cost” flexibility such as increased balancing area cooperation (balancing wind generation and load over larger areas to “share” the increased variability.

• Spatial diversity smooth's aggregated wind output reducing short-term fluctuations to hour time scales

• Storage would “help” but is not needed, and the integration costs would not “pay” for currently expensive storage technologies.

20National Renewable Energy Laboratory Innovation for Our Energy Future

Page 21: The Role of Energy Storage with Renewable Electricity ... · The Role of Energy Storage with Renewable Electricity Generation (Report Summary) Outline • Operation of the Electric

21

Limits to VG Penetration - Curtailment

• At high penetration, economic limits will be due to curtailment

– Limited coincidence of VG supply and normal demand

– Minimum load constraints on thermal generators

– Thermal generators kept online for operating reserves

• Results from EWITS and WWSIS, along with other studies, indicate that beyond 30% VG, new sources of flexibility will be needed

National Renewable Energy Laboratory Innovation for Our Energy Future

Page 22: The Role of Energy Storage with Renewable Electricity ... · The Role of Energy Storage with Renewable Electricity Generation (Report Summary) Outline • Operation of the Electric

22

High Penetration Limits

0

10000

20000

30000

40000

50000

60000

70000

0 24 48 72 96Hours

MW

Load Net Load Load Met by Inflexible Generation Wind

Dispatch with low VG penetration (wind providing 8.5% of load)

0

10000

20000

30000

40000

50000

60000

70000

0 24 48 72 96

MW

Hours

Wind Net Load Met by Inflexible Generation

Curtailed Wind Net Load Met by Flexible Generation

Load

Dispatch with higher VG penetration (wind

providing 16% of load)

Inflexible systems may be unable to accommodate

large amounts of wind

22National Renewable Energy Laboratory Innovation for Our Energy Future

Page 23: The Role of Energy Storage with Renewable Electricity ... · The Role of Energy Storage with Renewable Electricity Generation (Report Summary) Outline • Operation of the Electric

0

50

100

150

200

250

0 10000 20000 30000 40000 50000 60000

Load (MW)

Who

lesa

le P

rice

($/M

Wh)

0

5

10

15

20

25

30

35

18000 20000 22000 24000 26000Load (MW)

Who

lesa

le P

rice

($/M

Wh)

23

Current System FlexibilityLimited by Baseload Capacity

Price/Load Relationship in PJM

Below Cost Bids

Plant operators would rather sell energy at a loss than incur a

costly shutdown. Wind may be curtailed under these conditions

23National Renewable Energy Laboratory Innovation for Our Energy Future

Page 24: The Role of Energy Storage with Renewable Electricity ... · The Role of Energy Storage with Renewable Electricity Generation (Report Summary) Outline • Operation of the Electric

24

Increased Flexibility is Required

0%10%20%30%40%50%60%70%80%90%

100%

0% 10% 20% 30% 40% 50%

Minimum Load as a Fraction of Peak Load

% o

f Ene

rgy

From

Infle

xibl

e G

ener

ator

s

50%60%70%80%90%100%

Flexibility Factor

Typical Minimum Load in Current

Systems

At current minimum loads, baseload generators provide 60-70% of generation, leaving only 30%-40% for VG.

24National Renewable Energy Laboratory Innovation for Our Energy Future

Page 25: The Role of Energy Storage with Renewable Electricity ... · The Role of Energy Storage with Renewable Electricity Generation (Report Summary) Outline • Operation of the Electric

25

Decreased Minimum Load

Simulations based on 2005 load and weather

Inflexible System -Minimum Load of 21 GW (65% FF)

More Flexible System -Minimum Load of 13 GW (80% FF)

0

5000

10000

15000

20000

25000

30000

35000

40000

45000

50000

0 24 48 72 96

MW

Hours

Load Met by Renewable Energy Net Load Met by Flexible Generation

Curtailed Renewable Energy Net Load Met by Inflexible Generation

Renewable Energy

0

5000

10000

15000

20000

25000

30000

35000

40000

45000

50000

0 24 48 72 96

MW

Hours

Net Load Met by Inflexible Generation Curtailed Renewable Energy

Net Load Met by Flexible Generation Load Met by Renewable Energy

Renewable Energy

25National Renewable Energy Laboratory Innovation for Our Energy Future

Needed to accommodate greater amounts of VG without significant curtailment

Decreased curtailment

Page 26: The Role of Energy Storage with Renewable Electricity ... · The Role of Energy Storage with Renewable Electricity Generation (Report Summary) Outline • Operation of the Electric

26

Curtailment as a Function of Flexibility

0%

5%

10%

15%

20%

25%

30%

35%

40%

45%

50%

0% 10% 20% 30% 40% 50% 60% 70% 80%

Fraction of Energy From RE

Aver

age

VG C

urta

ilmen

t21 GW Min Load(65% FF)12 GW Min Load(80% FF)6 GW Min Load(90% FF)

FF=Flexibility Factor

Average curtailment rate as a function of VG penetration for different flexibilities in ERCOT

26National Renewable Energy Laboratory Innovation for Our Energy Future

Page 27: The Role of Energy Storage with Renewable Electricity ... · The Role of Energy Storage with Renewable Electricity Generation (Report Summary) Outline • Operation of the Electric

27

Curtailment as a Function of Flexibility (cont.)

0%

5%

10%

15%

20%

25%

30%

35%

40%

45%

50%

0% 10% 20% 30% 40% 50% 60% 70% 80%

Fraction of Energy From RE

Mar

gina

l VG

Cur

tailm

ent

21 GW Min Load(65% FF)

12 GW Min Load(80% FF)

6 GW Min Load(90% FF)

FF=Flexibility Factor

Marginal curtailment rate as a function of VG penetration for different system flexibilities in ERCOT (marginal curtailment is defined as the

percentage curtailed as a function of the incremental penetration)

27National Renewable Energy Laboratory Innovation for Our Energy Future

Page 28: The Role of Energy Storage with Renewable Electricity ... · The Role of Energy Storage with Renewable Electricity Generation (Report Summary) Outline • Operation of the Electric

28

VG Curtailment May Result In Unacceptably High Costs at High Penetration

1.0

1.1

1.2

1.3

1.4

1.5

1.6

1.7

1.8

1.9

2.0

0% 10% 20% 30% 40% 50% 60% 70% 80%

Fraction of Energy From Wind and Solar

Rela

tive

Cost

of V

G (A

vera

ge)

21 GW Min Load(65% FF)

12 GW Min Load(80% FF)

6 GW Min Load(90% FF)

1.0

1.1

1.2

1.3

1.4

1.5

1.6

1.7

1.8

1.9

2.0

0% 10% 20% 30% 40% 50% 60% 70% 80%

Fraction of Energy From Wind and Solar

Rela

tive

Cost

of V

G (M

argi

nall)

21 GW Min Load(65% FF)

12 GW Min Load(80% FF)

6 GW Min Load(90% FF)

Relative cost of VG – average (top chart) and marginal (bottom chart) – as a

function of VG penetration for different system flexibilities in ERCOT

28National Renewable Energy Laboratory Innovation for Our Energy Future

Page 29: The Role of Energy Storage with Renewable Electricity ... · The Role of Energy Storage with Renewable Electricity Generation (Report Summary) Outline • Operation of the Electric

29

Renewables-Driven Grid Applications Storage and Flexibility Options

• At high penetration of VG, additional flexibility is required

• What are the options?

29National Renewable Energy Laboratory Innovation for Our Energy Future

Page 30: The Role of Energy Storage with Renewable Electricity ... · The Role of Energy Storage with Renewable Electricity Generation (Report Summary) Outline • Operation of the Electric

30

Renewables-Driven Grid Applications Storage and Flexibility Options (cont.)

While storage provides an “obvious” answer to the problem of supply-demand coincidence, there are a number of options

30National Renewable Energy Laboratory Innovation for Our Energy Future

Page 31: The Role of Energy Storage with Renewable Electricity ... · The Role of Energy Storage with Renewable Electricity Generation (Report Summary) Outline • Operation of the Electric

31

Flexibility Supply Curve

Based on an original by Nickell 2008

The cost of all options has yet to be determined. Currently, energy storage is expensive and incurs the penalty of round-trip losses.

31National Renewable Energy Laboratory Innovation for Our Energy Future

Page 32: The Role of Energy Storage with Renewable Electricity ... · The Role of Energy Storage with Renewable Electricity Generation (Report Summary) Outline • Operation of the Electric

32

Energy Storage Can Reduce VG Curtailment

FF=80% (12 GW min load)

0%

5%

10%

15%

20%

25%

30%

35%

40%

45%

50%

0% 10% 20% 30% 40% 50% 60% 70%

Fraction of Energy From Wind and Solar

Aver

age

RE C

urta

ilmen

t

No Storage

5% Storage Capacity

5% Storage IncludingMinimum Load Reduction

Energy storage can reduce curtailment both by shifting otherwise unusable generation, and also increase system flexibility by providing reserves (reducing the need for partially loaded thermal generators) and replacing “must-run” capacity

32National Renewable Energy Laboratory Innovation for Our Energy Future

Page 33: The Role of Energy Storage with Renewable Electricity ... · The Role of Energy Storage with Renewable Electricity Generation (Report Summary) Outline • Operation of the Electric

33

Dedicated Renewable Storage?

• Dedicated renewable storage is generally a non-optimal use

• Could have scenarios where one storage device is charging while another is discharging simultaneously in the same system

• “Renewable specific” applications are already typically captured in grid operations

RE Specific Application “Whole Grid” Application

Transmission Curtailment Transmission Deferral

Time Shifting Load Leveling/Arbitrage

Forecast Hedging Forecast Error

Frequency Support Frequency Regulation

Fluctuation Suppression Transient Stability

33National Renewable Energy Laboratory Innovation for Our Energy Future

Page 34: The Role of Energy Storage with Renewable Electricity ... · The Role of Energy Storage with Renewable Electricity Generation (Report Summary) Outline • Operation of the Electric

34

Storage Technologies

Not shown – thermal storage in end use and in CSP plants

Common Name Example Applications Discharge Time Required

Power Quality Transient Stability, Frequency Regulation Seconds to Minutes

Bridging Power Contingency Reserves, Ramping Minutes to ~1 hour

Energy Management Load Leveling, Firm Capacity, T&D Deferral Hours

National Renewable Energy Laboratory Innovation for Our Energy Future

Page 35: The Role of Energy Storage with Renewable Electricity ... · The Role of Energy Storage with Renewable Electricity Generation (Report Summary) Outline • Operation of the Electric

35

Caveats

• Efficiency– Not uniformly defined (should be AC-AC, but sometimes

stated in terms of DC-DC, which doesn’t capture conversion)– May not include parasitics– CAES (which uses natural gas) and thermal storage cannot

be easily compared to pure electricity storage devices such as pumped hydro

• Cost– Many technologies have not been deployed as large scale,

so costs are largely unknown– Commodity prices affect estimates from different years– Difficult to compare devices that offer different services

(power vs. energy)

35National Renewable Energy Laboratory Innovation for Our Energy Future

Page 36: The Role of Energy Storage with Renewable Electricity ... · The Role of Energy Storage with Renewable Electricity Generation (Report Summary) Outline • Operation of the Electric

36

Storage Devices for Power Quality

• Requires response time of seconds or less, discharge time of up to 10 minutes

• Flywheels– Currently targeted toward frequency

– Regulation applications

• Capacitors– Limited deployment to date (low energy capacity)

• Superconducting Magnetic Energy Storage (SMES)– Limited deployment to date due to high cost and

low energy density

36National Renewable Energy Laboratory Innovation for Our Energy Future

Page 37: The Role of Energy Storage with Renewable Electricity ... · The Role of Energy Storage with Renewable Electricity Generation (Report Summary) Outline • Operation of the Electric

37

Storage Devices for Bridging Power

• Rapid response (seconds to minutes)

• Discharge time of up to 1 hour

• May also provide power quality services

• Several battery technologies– lead-acid

– nickel-cadmium

– nickel-metal hydride

– lithium-ion

37National Renewable Energy Laboratory Innovation for Our Energy Future

Page 38: The Role of Energy Storage with Renewable Electricity ... · The Role of Energy Storage with Renewable Electricity Generation (Report Summary) Outline • Operation of the Electric

38

Storage Devices for Energy Management

• Discharge time of several hours

• Some technologies also provide power quality and bridging power

• Would be the most important class of storage devices for decreasing VG curtailment

• High energy batteries

• Pumped hydro

• Compressed Air

• Thermal Storage

38National Renewable Energy Laboratory Innovation for Our Energy Future

Page 39: The Role of Energy Storage with Renewable Electricity ... · The Role of Energy Storage with Renewable Electricity Generation (Report Summary) Outline • Operation of the Electric

39

High Energy Batteries

• High-temperature batteries– Sodium sulfur – the most widely deployed battery with more

than 270 MW installed

– Sodium-nickel chloride (early commercialization stage)

• Liquid electrolyte “flow” batteries– Feature separate power and energy components

– All in the early commercialization stage

– Vanadium redox

– Zinc-bromine

– Other chemistries being pursued

39National Renewable Energy Laboratory Innovation for Our Energy Future

Page 40: The Role of Energy Storage with Renewable Electricity ... · The Role of Energy Storage with Renewable Electricity Generation (Report Summary) Outline • Operation of the Electric

40

Pumped Hydro Storage

• Only technology deployed on a gigawatt scale– ~20 GW in the U.S. at 29 sites– ~100 GW worldwide

• Installations in the U.S. range from <50 MW to 2,100 MW

• Can exceed 75% AC-AC round-trip efficiency

• Permitting is difficult and time-consuming, but ~ 30 GW of proposed new capacity in the U.S.

40National Renewable Energy Laboratory Innovation for Our Energy Future

Page 41: The Role of Energy Storage with Renewable Electricity ... · The Role of Energy Storage with Renewable Electricity Generation (Report Summary) Outline • Operation of the Electric

41

Compressed Air Energy Storage (CAES)

• Hybrid technology that a gas turbine and burns natural gas

• Single point efficiency not easily defined– Better to use electricity energy ratio (0.6-0.8 kWh in per kWh

out) and heat rate (4000-4300 BTU/kWh)

• Two sites – U.S. (110 MW) and Germany (270 MW)

• Alternative designs proposed including adiabatic (no fuel input)

Alabama CAES Plant (110 MW)

41National Renewable Energy Laboratory Innovation for Our Energy Future

Page 42: The Role of Energy Storage with Renewable Electricity ... · The Role of Energy Storage with Renewable Electricity Generation (Report Summary) Outline • Operation of the Electric

42

Thermal Storage

• End-use thermal storage in buildings– Hot or cold– Very high round-trip efficiencies (near 100% in

some applications)– Commercially available

• Thermal storage for CSP– Very high round-trip efficiency

(stores energy before Carnot losses)

• Both applications are tied to a specific use and difficult to compare to more flexible storage technologies

42National Renewable Energy Laboratory Innovation for Our Energy Future

Page 43: The Role of Energy Storage with Renewable Electricity ... · The Role of Energy Storage with Renewable Electricity Generation (Report Summary) Outline • Operation of the Electric

43

Electric Vehicles and Vehicle-to-Grid

• Potential valuable source of distributed storage• More likely to be used for ancillary services than bulk

energy shifting due to high battery cost• Active area of research

43National Renewable Energy Laboratory Innovation for Our Energy Future

Page 44: The Role of Energy Storage with Renewable Electricity ... · The Role of Energy Storage with Renewable Electricity Generation (Report Summary) Outline • Operation of the Electric

44

Conclusions

• The role of storage is an economic issue – does the value of storage exceed its benefits?

• Storage is undervalued in existing markets and it is still difficult to assess the true value and opportunities for energy storage in the current and future grid

• Renewables increase the value of storage, but the current grid can accommodate substantially increased amount of renewables with options that appear to be lower cost than new dedicated storage

• At penetrations of wind and solar that exceed 30%, increased curtailment will require new sources of grid flexibility

• New models and analysis will be required to evaluate the benefits of energy storage in the future electric grid.

National Renewable Energy Laboratory Innovation for Our Energy Future

Page 45: The Role of Energy Storage with Renewable Electricity ... · The Role of Energy Storage with Renewable Electricity Generation (Report Summary) Outline • Operation of the Electric

45

For More Information

Full Report:

Denholm, P.; Ela, E.; Kirby, B.; Milligan, M. (2010). Role of Energy Storage with Renewable Electricity Generation. NREL Report No. TP-6A2-47187.

Available at:http://www.nrel.gov/docs/fy10osti/47187.pdf

National Renewable Energy Laboratory Innovation for Our Energy Future