The right ITK UPS. · 2019. 7. 31. · Voltage range 81-145 VAC or 162-290 VAC Frequency range...

22
1 radog.com The right ITK UPS. raDOG

Transcript of The right ITK UPS. · 2019. 7. 31. · Voltage range 81-145 VAC or 162-290 VAC Frequency range...

Page 1: The right ITK UPS. · 2019. 7. 31. · Voltage range 81-145 VAC or 162-290 VAC Frequency range 50/60Hz ±10% auto-sensing OUTPUT Voltage Regulation ±10% for both AC mode and Battery

1

radog.com

The right ITK UPS.

raDOG

Page 2: The right ITK UPS. · 2019. 7. 31. · Voltage range 81-145 VAC or 162-290 VAC Frequency range 50/60Hz ±10% auto-sensing OUTPUT Voltage Regulation ±10% for both AC mode and Battery

Line InteractiveAiO All-in-OneAiO 600 & AiO 800

The AiO All-in-One UPS series, featured with smart microprocessor control design, AVR boost and Buck, Smart USB communication interface and cold start function, is an ideal solution for protecting household and small office systems. In addition the UPS is built-in USB charger, which may charge your mobile, PAD, etc. alone.

Features:• Boost and Buck AVR corrects either under-voltage or over-voltage condition to minimize the

usage of battery energy, hence to extend the life of the battery.

• Built-in USB charger supplies feasible access to recharge your mobile or PAD alone.

• With ergonomic cable management design, all the access of the cables is from top only.

• Cold Start Function aids user to tudn on the UPS without connecting the Utility.

• Smart USB Interface for Power Management supports real-time powerrand UPS status monitoring. Automatic shutdown, schedule and many other advance power management functions.

• Auto-restart Function enables the UPS may be automatically re-started when Utility recovers.

Page 3: The right ITK UPS. · 2019. 7. 31. · Voltage range 81-145 VAC or 162-290 VAC Frequency range 50/60Hz ±10% auto-sensing OUTPUT Voltage Regulation ±10% for both AC mode and Battery

3

AIO ALL-IN-ONEMODEL

600 800CAPACITY 600VA / 360W 800VA / 480W

INPUTVoltage 110/120 VAC or 220/230/240 VACVoltage range 81-145 VAC or 162-290 VACFrequency range 50/60Hz ±10% auto-sensing

OUTPUT

Voltage Regulation ±10% for both AC mode and Battery modeFrequency Range (Batt. Mode) 60Hz or 50Hz ±1HzTransfer Time Typical: 2-6ms, 10ms maxWaveform (Batt. Mode) Simulated sine wave

BATTERYBattery Type & Number 12V/7AH × 1 12V/9AH × 1Typical Recharge Time 6-8 hours recover to 90% capacity

INDICATORSAC Mode Green LED lightningBattery Mode Amber LED lightningFault Red LED lightning

PROTECTION Full Protection Overload and overcharge protection

ALARM

Battery Mode Sounding every 10 secondsLow Battery Sounding every secondOverload Sounding every 0,5 secondBattery Replacement Alarm Sounding every 2 secondsFault Continuously sounding

PHYSICAL

Dimensions D×W×H (mm) 270 × 190 × 90

Details

Net Weight 3,55 4,9OPERATING ENVI-RONMENT

Humidity 0-90% RH @ 0~40ºC (non condensing)Noise Level Less than 40dB

MANAGEMENT Optional USB Port Supports Windows®, Linux, Unix and MACUSB CHARGER for mobile & PAD charging

Page 4: The right ITK UPS. · 2019. 7. 31. · Voltage range 81-145 VAC or 162-290 VAC Frequency range 50/60Hz ±10% auto-sensing OUTPUT Voltage Regulation ±10% for both AC mode and Battery

Line Interactive

4

Line Interactive

The Micropower LCD series, featured with smart microprocessor control design, AVR boost and buck, smart USB interface and cold start function, is a cost effective solution to your mission critical PC valuble peripherals.

The AVR Boost and Buck automatically corrects either undervoltage or overvoltage condition without unnecessary drain and extends the life of the battery.

• Line-interactive technology (VI)

• Automatic Voltage Regulator (AVR, “Boost and Buck”)

• Transfer to battery at under and overvoltage

• Big LCD display

• Self-diagnostic function

• Battery cold start

• Genset-compatible

• Auto-charging in Off-mode

• Auto-restart function

• Automatic computer shutdown

• Audible and visible alarm

• Surge protection

• RJ45/11 protection (EMI/RFI filtering)

• USB interface includin software

• 2 years warranty

MICROPOWER600 - 3000VA

Page 5: The right ITK UPS. · 2019. 7. 31. · Voltage range 81-145 VAC or 162-290 VAC Frequency range 50/60Hz ±10% auto-sensing OUTPUT Voltage Regulation ±10% for both AC mode and Battery

5

MICROPOWERMODEL

600 800 1000 1500 2000 3000Nominal capacity (VA) 600 800 1000 1500 2000 3000Power (Watt) 360 480 600 900 1200 1800Voltage 220/230/240Vac / 110/120VacInput voltage range 162-290Vac / 81-145VacVoltage stabilizer-AVR Boost & BuckInput frequency 50/60Hz (auto-sensing)Output voltage (AC/battery mode) +/- 10HzOutput frequency (battery mode) 50/60Hz ±1HzTransfer time to battery Typical: 2-6ms / maximum: 10msWaveform Simulated sine waveBattery (voltage and quantity) 1 × 12V7Ah 1 × 12V9Ah 2 × 12V7Ah 2 × 12V9Ah 4 × 12V9AhBackup time 5 - 10 minutes at 70% of nominal loadTypical recharge time 6-8 hours recover to 90% capacityOutlets IEC (Schuko on request) 4 outlets (650-1300VA) / 6 outlets (1600-2200VA) IEC320 C13Interface USB-portProtection Overvoltage, short-circuit, overload, battery deep dischargeLCD information Big LCD displayAcoustic information Battery mode - low battery - overload - battery replacement alarm - faultHumidity / Noise level 0-90% at 0-40ºC (non-condensing) / less than 40dB

Dimensions W×D×H (mm) 101 × 302 × 142 149 × 338 × 160 158 × 380 × 196 150 × 430 ×

210Weight 4,3kg 4,9kg 7,8kg 11,1kg 11,5kg 23,2kgWarranty 2 yearsSoftware For Windows, Mac, Linux

Page 6: The right ITK UPS. · 2019. 7. 31. · Voltage range 81-145 VAC or 162-290 VAC Frequency range 50/60Hz ±10% auto-sensing OUTPUT Voltage Regulation ±10% for both AC mode and Battery

On-LineMEMOPOWER III1 - 3kVA, PF 1,0

6

The Memopower III PF 1.0 double conversion true on-line series, superior input voltage window for energy saving, ECO mode, super powerful charger, is an ideal solution to your computer center, network center, communication system, automatic control system or other critical systems.

Features:

• True Online Double Conversion

• Mimic LCD Display with Multifunction Parameter Settings & Operational status

• Wide input voltage range for the harshest environment

• Support Generator Input

• Super Powerful Charger for battery backup extension

• Support Economic Operation Mode

• Emergency power off function (EPO)

• Cold stard Function is built-in

• Bundled Communication Software supports Windows application, etc.

• Matching Battery Pack

• Smart Battery Charging Design for Optimizing Battery Performance

• Output Power Factor 1.0

• >92% High Efficiency Models Avalible

• Input power factor 0.99 (With PFC)

Page 7: The right ITK UPS. · 2019. 7. 31. · Voltage range 81-145 VAC or 162-290 VAC Frequency range 50/60Hz ±10% auto-sensing OUTPUT Voltage Regulation ±10% for both AC mode and Battery

7

MEMOPOWER IIIMODEL

1000 2000 3000CAPACITY (VA/WATTS) 1000VA / 1000W 2000VA / 2000W 3000VA / 3000W

INPUT

Phase Single phase with groundNominal Voltage 200 / 208 / 220 / 230 / 240 Vac

Operating voltage range

Low line transfer

160Vac±5% at 100%~80% load; 140Vac±5% at 80%~70% load; 120Vac±5% at 70%~60% load; 110Vac±5% at 60%~0% load (Ambient temp.<35ºC)

Low line comback

175Vac±5% at 100%~80% load; 155Vac±5% at 80%~70% load; 135Vac±5% at 70%~60% load; 125Vac±5% at 60%~0% load (Ambient temp.<35ºC)

High line transfer 300Vac ±5%

High line comback 290Vac ±5%

Input Voltage Range 55~150Vac or 110-300Vac at 60% load, 80~145Vac or 160~300Vac at 100% loadOperating frequency range 40~70HzPower Factor 0,99Generator input Support

OUTPUT

Output Voltage 200 / 208 / 220 / 230 / 240VacPower Factor 1.0Voltage Regulation ±1%

FrequencyLine mode (Sync. mode) 47~53Hz or 57~63Hz

Battery mode (50/60±0,1) HzCrest Factor 3:1

Harmonic Distortion (THDv)≤2% THD (Linear load)

≤4% THD (Non-linear load)Waveform 2 Pure Sinewave

Transfer Time

AC mode <-> Batt. Mode Zero

Inverter <-> Bypass 4ms (Typical)

EFFICIENCYAC Mode 88% 92%Battery Mode 85% 86% 87% 88% 89% 90%

BATTERY

Battery Type 12V9Ah N/ANumbers 2 3 4 6 8Backup time Long run depends on the capacity of external batteriesTypical recharging time (Standard model) 4 hours recover to 90% capacity

Charging voltage 27,4VDC±1% 41,1VDC±1% 54,7VDC±1% 82,1VDC±1% 109,4VDC±1%Charging current (max.) 1A 12A 1A 12A 1A 12A

SYSTEM FEA-TURES

Line modeAmbient temp. <35ºC

105%~110%: UPS transfer to bypass after 10 minutes when the utility is normal 110%~130%: UPS transfer to bypass after 1 minute when the utility is normal

35ºC<ambient temp.<40ºC105%~110%: UPS transfer to bypass after 1 minute when the utility is normal

110%~130%: UPS transfer to bypass after 5 seconds when the utility is normal>130%: UPS transfer to bypass immediately when the utility is normal

Battery mode

Short circuit Hold whole system

Overheat Line mode: Switch to bypass Backup mode: Shut down UPS immediately

Battery low Alarm and switch offEPO (optional) Shut down UPS immediatelyAudible & Visual alarms Line failure, Battery low, Overload, System faultCommunication interface USB, RS232, SNMP Card, Relay Card (Optional)

PHYSICALDimensions W×H×D (mm) 144×209×293 144×209×309 191×337×460 144×209×309Net Weight (kg) 9,8 4,1 17 6,8 27,6 7,4

ENVIRONMENT

Operating temperature 0 ~ 40ºCStorage temperature -25ºC ~ 55ºCHumidity range 20~90% RH at 0~40ºC (non-condensing)Altitude <1500mNoise Level Less than 50dBA at 1 meter

STANDARDSSafety IEC/EN6204-1, IEC/EN60950-1

EMC IEC/EN62040-2, IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-8

Page 8: The right ITK UPS. · 2019. 7. 31. · Voltage range 81-145 VAC or 162-290 VAC Frequency range 50/60Hz ±10% auto-sensing OUTPUT Voltage Regulation ±10% for both AC mode and Battery

On-LineMEMOPOWER RT III1 - 3kVA, PF 1,0

8

The Memopower RT III convertible double conversion true on-line series, superior input voltage window for energy saving, ECO mode, super powerful charger, is an ideal solution to your computer center, network center, communication system, automatic control system or other critical systems.

Features

• True Online Double Conversion

• Mimic LCD display with Multifunction Parameter Settings & operational status

• Wide input voltage range for the harshest envvironment

• Support Generator input

• Super Powerful Charger for Battery backup eytension

• Support Economic Operation Mode

• Power Shedding Function

• Hot-Swappable Battery

• Cold Start Function is built-in

• Bundled Communication Software supports Windows application, etc.

• Matching Battery Pack

• Output Power Factor 1.0

• Up to 92% High Efficiency Models Available

Page 9: The right ITK UPS. · 2019. 7. 31. · Voltage range 81-145 VAC or 162-290 VAC Frequency range 50/60Hz ±10% auto-sensing OUTPUT Voltage Regulation ±10% for both AC mode and Battery

9

MEMOPOWER RT III, PF 1.0MODEL

1KVA 2KVA 3KVACAPACITY (VA/WATTS) 1000VA / 1000W 2000VA / 2000W 3000VA / 3000W

INPUT

Phase Single phase & GroundRelated Voltage 200* / 208* / 220 / 230 / 240 Vac

Voltage range

160Vac±5% at 100%~80% load; 140Vac±5% at 80%~70% load; 120Vac±5% at 70%~60% load; 110Vac±5% at 60%~0% load (Ambient temp.<35ºC)

175Vac±5% at 100%~80% load; 155Vac±5% at 80%~70% load; 135Vac±5% at 70%~60% load; 125Vac±5% at 60%~0% load (Ambient temp.<35ºC)

300Vac ±5%290Vac ±5%

Frequency Range 40Hz ~70Hz (auto detect)Power Factor ≥0.99

Bypass Voltage Range230-264: setting the high voltage point in LCD from 230Vac to 264Vac (Default: 264Vac)

170-220: setting to low voltage point in LCD from 170Vac to 220Vac (Default: 170Vac)

ECO Range Same as the bypassGeneral Input Support

OUTPUT

Phase Single phase & GroundRated Voltage 200 / 208 / 220 / 230 / 240VacPower Factor 1Voltage Regulation ±1%

Frequency Utility Mode 47~53Hz (for 50Hz) or 57~63Hz (for 60Hz)Battery Mode 50/60±0,01 Hz

Crest Factor 3:1

Harmonic Distortion (THDv) ≤3% THD with linear load ≤6% THD with non-linear load

Waveform Pure SinewaveEFFICIENCY AC Mode (full load) >88% >92%

BATTERY

Voltage 24Vdc 36Vdc 48Vdc 72Vdc 96VdcQuantity 2 3 4 6 8Capacity (standard unit) 12V/9Ah N/A 12V/9Ah N/A 12V/9Ah N/ABackup Long run unit depends on the capacity of external batteriesRecharge time to 90% 4 hoursCharging Current (Built-in/Max) 2A Max. 12A 2A Max. 12A 2A Max. 12A

TRANSFER TIME Utility to Battery: 0ms, Utillity to bypass <4ms

PROTECTION

Overload

AC mode Ambient Temp. <35ºC105%~110%: UPS transfer to bypass after 10 minutes when the utility is normal

110%~130%: UPS transfer to bypass after 1 minute when the utility is normal130%~150%: UPS transfer to bypass after 5 seconds when the utility is normal

>150%: UPS transfer to bypass immediately when the utility is normal<35ºC < Ambient Temp. <40ºC

105%~110%: UPS transfer to bypass after 1 minute when the utility is normal110%~130%: UPS transfer to bypass after 5 seconds when the utility is normal

>130%: UPS transfer to bypass immediately when the utility is normal

Battery Mode

Bypass Mode 10A (Input breaker) 16A (Input breaker) 20A (Input breaker)Short circuit Hold whole system

Overheat Line mode: Switch to bypass Backup mode: Shut down UPS immediately

Battery low Alarm and switch offEPO (optional) Shut down UPS immediatelyBattery Advanced Battery Management

ALARMS Audible & Visual Line failure, Battery low, Overload, System fault

COMMUNICATION INTERFACE

Status LED & LCD Line Mode, Backup Mode, Eco Mode, Bypass Mode, Battery Low, Battery Bad, Overload & UPS Fault

Reading on the LCD Input Voltage, Input Frequency, Output Voltage, Output Frequency, Load Percentage, Battery Voltage

PHYSICAL Dimensions W×H×D (mm) 440×86,5×305 440×86,5×460 440×86,5×435 440×86,5×600(2U)440×131×460(3U) 440×86,5×435

Net Weight (kg) 11,3 5,6 19,1 8,3 26,2 / 25,8 8,6COMMUNICATION INTERFACE

Communication Port RS232 or USBCommunication Slot SNMP Card, Relay Card, etc.

ENVIRONMENT

Operating temperature 0 ~ 40ºCStorage temperature -25ºC ~ 55ºCHumidity 20~90% RH non-condensingAltitude <1500m (derating while >1500m)Noise < 50dB at 1 meter

SAFETY CONFORMANCE IEC/EN62040-1-1, IEC/EN62040-2

*Derate to 80% of capacity when the output voltage is adjusted to 200/208VAC

Page 10: The right ITK UPS. · 2019. 7. 31. · Voltage range 81-145 VAC or 162-290 VAC Frequency range 50/60Hz ±10% auto-sensing OUTPUT Voltage Regulation ±10% for both AC mode and Battery

On-LineMEMOPOWER III6 - 10kVA, PF 1,0

10

The Memopower III 6-10kVA 1.0 PF Parallel Redundancy on-line series, featured with N+X Parallel Redundancy, DSP-controlled technology, high input & output power factors, superior input voltage window for energy saving ECO mode, is an ideal solution to your server, bank, industrial equipment, IT equipment, communication system and other networking equipment, whic is demanding for thorough protection.

Features

• N+X Parallel Redundancy

• Online Double Conversion with DSP Control

• Built--in Power Charger can be set from 1A to 10A

• Unity Input Power Factor with low input current distortion

• High Input Power Factor at 1.0 PF

• Low Input Current Distortion <3%

• Green Concept design with Superior Input Voltage Window for Energy Saving

• Support Generator Input

• Estimated Remaining Time displayed on the LCD

• Support Evonomic (ECO) Operation Mode

• Settable Battery Voltage

• Automatic Battery Test Settable from LCD

• Load - controlled fan

• Matching Battery Pack with Powerful Charger Built-in

• Common Battery When UPS in Parallel Mode

• Versatile Communication Interfaces Available

• Cold Start

• Communicaton Software

• Frequency Converter Mode

• Settable Charge Current

• De-rating Operation Available

Page 11: The right ITK UPS. · 2019. 7. 31. · Voltage range 81-145 VAC or 162-290 VAC Frequency range 50/60Hz ±10% auto-sensing OUTPUT Voltage Regulation ±10% for both AC mode and Battery

11

MEMOPOWER III, PF 1.0MODEL

6KVA 10KVACAPACITY (VA/WATTS) 6kVA/6kW 10kVA/10kW

INPUT

Nominal Voltage 220 / 230 / 240 VacOperating Voltage Range 120 ~ 276 VacFrequency Range 50Hz: 45~55Hz; 60Hz: 54~66Hz (auto sensing)Power Factor ≥0.99

Bypass voltage range

Max. voltage 220V: +25% (optional +10%, +15%, +20%)Bypass voltage

230V: +20% (optional +10%, +15%)240V: +15% (optional +10%)

Min. voltage -45% (optional -20%, -30%)Bypass frequency Range Frewuency protection range ±10%ECO range Same as the bypassHarmonic distortion (THDi) <3% (100% linear load)Generator input Support

OUTPUT

Output Voltage 220 / 230 / 240 VacPower Factor 1Voltage Regulation ±1%

Frequency Line Mode ±1% / ±2% / ±4% / ±5% / ±10% of rated frequency (optional)Battery Mode 50/60 (±0,01) Hz

Crest Factor 3:1

Harmonic Distortion (THDv) ≤2% THD with linear load ≤5% THD with non-linear load

Efficiency >93%

BATTERY

Voltage ±96 / 108 / 120Vdc (Settable)Capacity (standard unit) 12V/7Ah or 12V/9AhTypical recharging time 6 ~ 8 hours (to 90% of full capacity)Charging Current 1A 10A 1A 10A

SYSTEM FEATURES

Transfer time Mains to battery: 0msMains to bypass: 0ms

Overload Line modeLoad ≤110%: last 10minLoad ≤130%: last 1min

>130% turn to bypass mode immediatelyBypass mode 63A (Breaker) 80A (Breaker)

Short Circuit Hold whole system

Overheat Line mode Turn to bypassBat. mode Shut down UPS immediately

Battery low Alarm and switch offSelf-diagnostics Upon power on and software controlBattery Advanced battery managementAudible and visual alarms Line failure, Battery low, Overload, System fault

LED & LCD display Line mode, Bat. mode, Eco mode, Bypass mode, Battery under voltage, Overload & UPS fault

LCD displayInput voltage, Input frequency, Output voltage, Output frequency, Load

percentage, Battery voltage, Inner temperature & Remaining battery backup time

Communication interface RS232, USB, SNMP card (optional), Parallel card (optional), Relay card (optional)

ENVIRONMENT

Operating temperature 0ºC ~ 40ºCStorage temperature -25ºC ~ 55ºCHumidity range 0~95% (non-condensing)Altitude <1500mNoise level < 50dB

PHYSICAL Dimension W×H×D (mm) 191×660×460 191×330×405 191×660×460 191×330×405Net weight (kg) 65 18 69 20

STANDARDSSafety IEC/EN62040-1, IEC/EN60950-1

EMC IEC/EN62040-2, IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-8

Page 12: The right ITK UPS. · 2019. 7. 31. · Voltage range 81-145 VAC or 162-290 VAC Frequency range 50/60Hz ±10% auto-sensing OUTPUT Voltage Regulation ±10% for both AC mode and Battery

On-LineMEMOPOWER RT III6 - 10kVA, PF 1.0

12

The Memopower RT III on-line UPS series, featured with up to 93,5% efficiency, rack/tower convertible, N+X Parallel Redundancy, DSP-controlled technology, high input & output power factors, superior input voltage window for energy saving, ECO mode, is an ideal solution to your server, bank, industrial equipment, IT equipment, communication system and other networking equipment, which is demanding for thorough protection.

Features

• Rack/Tower Convertible

• Graphic LCD Display with Multifunction Parameter Settings & Mimic Diagram

• Hot Swappable Battery

• N+X Parallel Redundancy

• Online Double Conversion with DSP Control

• High Output Power Factor at 1.0PF

• Low Input Current Distortion

• Green Concept design with Superior Input Voltage Window for Energy Saving

• Efficiency up to 93,5%

• Emergency Power Off

• Support Economic (ECO) Operation Mode

• Settable Battery Voltage

• Temperature-controlled Fan

• Matching Battery Pack

• Common Battery When UPS in Parallel Mode

• Versatile Communication Interfaces Availiable

• Cold start

• Communication Software

• Settable Charge Current

• Optional Frequency Converter Mode Supported

• Transformer Module for Galvanic Isolation

Page 13: The right ITK UPS. · 2019. 7. 31. · Voltage range 81-145 VAC or 162-290 VAC Frequency range 50/60Hz ±10% auto-sensing OUTPUT Voltage Regulation ±10% for both AC mode and Battery

13

MEMOPOWER RT III, PF 1.0MODEL

6kVA 10kVACAPACITY (VA/WATTS) 6kVA/6kW 10kVA/10kW

INPUT

Nominal Voltage 208 / 220 / 240 VacOperating Voltage Range 110 ~ 300 VacFrequency Range 45~55Hz / 54~66HzPower Factor ≥0.99 at Nominal voltage (100%)

Bypass voltage range Max. voltage

220Vac: 10%, 15%, 20% or 25%; default: 25%230Vac: 10%, 15% or 20%; default: 20%

240Vac: 10% or 15%; default: 15%)Bypass frequency Range ±1%, ±2%, ±4%, ±5%, ±10%, ECO range Same as the bypassHarmonic distortion (THDi) ≤3% (100% linear load), ≤5% (100% non linear load)Generator input Support

OUTPUT

Output Voltage 208/ 220 / 230 / 240 VacPower Factor 1.0Voltage Regulation ±1%

Frequency Line Mode Synchronize to MainsBattery Mode 50/60 (±0,01) Hz

Crest Factor 3:1Harmonic Distortion (THDv) ≤3% THD with linear load, ≤5% THD with non-linear loadEfficiency >93,5%

BATTERY

Voltage ±96 / 108 / 120VdcCapacity (standard unit) 12V/5Ah or 12V/7Ah or 12V/9AhTypical recharging time 6 ~ 8 hours (to 90% of full capacity)

Charging Current 1A (Standard Unit); Max. Current: 10A (Long run unit); Charging current can be set according to battery capacity installed

SYSTEM FEATURES

Transfer time Mains to battery: 0ms Mains to bypass: 0ms

Overload Line mode Load ≤110%: last 60min, Load ≤125%: last 1minLoad ≤150%: last 200ms turn to bypass mode immediately

Bypass mode 40A (Breaker) 63A (Breaker)Short Circuit Hold whole systemBattery low Alarm and switch offSelf-diagnostics Upon power on and software controlBattery Advanced battery managementAudible and visual alarms Line failure, Battery low, Overload, System fault

LED & LCD display Line mode, Bat. mode, Eco mode, Bypass mode, Battery under voltage, Overload & UPS fault

LCD display Input voltage, Input frequency, Output voltage, Output frequency, Load percentage, Battery voltage, Inner temperature, etc.

Communication interface RS232, USB, Parallel card, EPO and communication slot for optional SNMP card, Relay card or Modbus card

ENVIRONMENT

Operating temperature 0ºC ~ 40ºCStorage temperature 25ºC ~ 55ºCHumidity range 0~95% (non-condensing)Altitude <1500mNoise level (at 1m) < 50dB

PHYSICAL Dimension W×H×D (mm) 440×88×585Net weight (kg) 14 18

STANDARDSSafety IEC/EN62040-1, IEC/EN60950-1

EMC IEC/EN62040-2, IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-8

Page 14: The right ITK UPS. · 2019. 7. 31. · Voltage range 81-145 VAC or 162-290 VAC Frequency range 50/60Hz ±10% auto-sensing OUTPUT Voltage Regulation ±10% for both AC mode and Battery

On-LineMEMOPOWER PLUS 3/1 Phase6 - 10kVA

14

Up to 4 Memopower Plus 3/1 Phase systems can be connected in parallel to get maximum power capacity. Only one battery is necessary in the parallel redundancy mode.

Features

• On-line “double conversion” technology (VFI)

• DSP (Digital Signal Processor) technology

• Internal static and manual bypass

• Input power factor up to 0.99

• Wide input voltage range

• Up to 4 units in parallel

• Battery (DC) cold start

• Common or separate battery in parallel mode

• Charging current 1-10A

• Selectable battery voltage (16/18/20 batteries)

• ECO mode for energy saving

• Site wiring fault indication

• Self testing at UPS startup

• Intelligent management through ES485, USB, DB9

• Backfeed protection

Options

• SNMP card adapter

• Relay card (dry contacts)

• Additional / external battery packs

• 2 years warranty

Page 15: The right ITK UPS. · 2019. 7. 31. · Voltage range 81-145 VAC or 162-290 VAC Frequency range 50/60Hz ±10% auto-sensing OUTPUT Voltage Regulation ±10% for both AC mode and Battery

15

MEMOPOVER PLUS 3/1 PHASEMODEL

6kVA 10kVAPOWER (kW) 5,4 9

INPUT

Nominal Voltage 220 / 230 / 240 Vac, optional 380 / 400 / 415 VacInput Voltage Range 120-276Vac (1/1), 208-478Vac (3/1)Frequency range 45-55Hz for 50Hz, 55Hz-65Hz for 60Hz (auto-sensing)Input power factor ≥ 0,99Bypass voltage range -45% / +15%Harmonic distortion (THDi) ≤ 5% at 100% non-linear load

OUTPUT

Voltage 208/220/230/240Vac selectableWaveform Pure sine waveHarmonic distortion (THD) ≤ 2 THD at 100% linear loadFrequency 50/60Hz ±2%Voltage regulation ±2% at nominal voltageCrest factor 3:1Efficiency at 75-100% load >92% (AC mode) / >95% (battery mode) / >97% (ECO mode)

BATTERY(INTERNAL)

Type VRLA, AGMVoltage 240Vdc (selectable 192/210/240Vdc)Standard backup time 6-8min at nominal load 3-5min at nominal loadPower of the internal charger 1-10A adjustable

PROTECTIONInput/Output Overvoltage, short-circuit, battery deep discharge, thermal protecionOverload capability AC/Battery mode

≤110% load 3min/30sec, ≤125% load 30sec/3sec, ≤150% load 1sec/200ms

ALARMS - INFOR-MATIONS

Audible Battery backup, battery low, overload status, fault statusLED Mains, inverter, bypass, fault, battery levelLCD Input and output voltage, load, battery voltage, error codes

BYPASS Type Internal static bypass (automatic) and manual bypass / External bypass optional

ENVIRONMNETTemperature / altitude / humidity 0-40ºC / less than 1500m / 0-95% non-condensing

Audible noise at 1m < 50dB

INTERFACEStandard USB, RS232, EPOOptions SNMP, relay card, parallel card

DIMENSIONSDimension W×H×D (mm) 250×510×620 (UPS), 250×600×620 (battery cabinet)Weight (with internal batteries) kg 70 80

STANDARDS CE-certificate, EN/IEC 62040-2, EN/IEC 62040-1, GOST

Page 16: The right ITK UPS. · 2019. 7. 31. · Voltage range 81-145 VAC or 162-290 VAC Frequency range 50/60Hz ±10% auto-sensing OUTPUT Voltage Regulation ±10% for both AC mode and Battery

On-LineMEMOPOWER PLUS RT 3/1 Phase6 - 10kVA

16

Up to 4 MP RT II systems can be connected in parallel to get maximum power capacity. Only one battery is necessary in the parallel redundancy mode.

Features

• On-line “double conversion” technology (VFI)

• DSP (Digital Signal Processor) technology

• Wide input voltage range (120-276V or 208-478V)

• Wide frequency range 40-70Hz ±0,5Hz

• Input power factor up to 0.99 and high output power factor 0.9

• Parallel connection up to 4 units (N+1)

• Rack/Tower design with convertible display

• Input power factor correction (PFC)

• Battery (DC) cold start

• Genset compatible

• ECO mode for energy saving

• Self testing at UPS startup

• Internal static and manual bypass

• Selectable amount of batteries : 16/18/20pcs

• Common or separate battery in parallel mode

• Backup-time indication on the display

• Adjustable charger 1-10A

• Fixing for tower and rackmount included

• EPO contact (Emergency Power off)

• Intelligent management trough RS232 slot, USB

• Including monitoring software

• Backfeed protection

Options

• SNMP card, relay card

• External maintenance bypass

• Galvanic isolaion transformer

• 2 years warranty

Up to 4 units in parallel

Common battery in parallel mode

Page 17: The right ITK UPS. · 2019. 7. 31. · Voltage range 81-145 VAC or 162-290 VAC Frequency range 50/60Hz ±10% auto-sensing OUTPUT Voltage Regulation ±10% for both AC mode and Battery

17

MEMOPOVER PLUS 3/1 PHASEMODEL

6kVA 10kVAPOWER (kW) 5,4 9

INPUT

Connection L-N (single phase), optional: 3L-N 4 wires (three phase)Nominal voltage 220/230/240Vac, optional 380/400/415VacInput voltage range 120-276Vac (1/1), optional 208-478Vac (3/1)Frequency range 45-55Hz for 50Hz, 55Hz-65Hz for 60Hz (auto-sensing)Power factor > 0,99Harmonic distortion (THDi) ≤ 3% at 100% non-linear load

Bypass voltage range +25% (+10%, +20% -option), -45% (-20%,-30% -option), frequency range: ±10%

OUTPUT

Output connection 2 × IEC-C13Voltage 208/220/230/240VacType of wave Pure sine waveHarmonic distortion (THD) ≤ 2 THD (linear load), ≤ 5% THD (no-linear load)Frequency 50/60Hz ±0,02HzVoltage regulation ±2% at nominal voltageCrest factor 3:1Efficiency at 75-100% laod >92% (AC mode) / >94% (battery mode) / 97% (ECO mode)

BATTERY (EXTER-NAL)

Voltage 16/18/20pcs 12V - only external batteries (modules)Charge current 1-10A adjustableParallel systems Common or separate battery possible

PROTECTION

Input/Output Overvoltage, short-circuit, battery deep discharge, thermal protecion

Overload capability

AC mode Load ≤110% : 3min, ≤125% : 30sec, ≤150% : 1sec, >150 : switching to bypass

battery mode Load ≤110% : 30sec, ≤125% : 1sec, ≤150% : 200msec, >150 : shut down of the UPS

bypass Input fuse 40A Input fuse 63A

Type Internal static bypass (automatic) and manual bypass / External bypass optional

ALARMS - INFOR-MATIONS

Audible Battery backup, battery low, overload, short-circuit, fault and error modeLED AC, battery, bypass, working modes, overload, error

LCD Voltage / frequency, load %, battery voltage, temperature, remaining backup time

Audible noise at 1m <55dBBYPASS Type Internal static bypass / external maintenance bypass (option)

CERTIFICATESEMC protection CE, EN/IEC 62040-2, EN/IEC 62040-1-1Protection class IP20 (up to IP55 on option)

INTERFACEStandard USB, parallel port, EPO, RS232, intelligent slotOptions SNMP, relay card

DIMENSIONSDimensions W×D×H (mm) 440×580×130 (3U)Weight (kg) 23 25

EXTERNAL BAT-TERY MODULES

Battery 16/18/20pcs per 12V/9AhDimensions W×D×H (mm) / weight 440×720×132 (3U) / 67kg

Connections input/output/battery modules Terminals

Page 18: The right ITK UPS. · 2019. 7. 31. · Voltage range 81-145 VAC or 162-290 VAC Frequency range 50/60Hz ±10% auto-sensing OUTPUT Voltage Regulation ±10% for both AC mode and Battery

On-LineMEMOPOWER PLUS 3/1 Phase10 - 20kVA, PF 0,9

18

Features

• N+X parallel redundancy

• Online double conversion with DSP control

• Input current harmonic: <5%

• Optimization battery group, the quantity of battery: 16/18/20 pieces (optional)

• Factor can change when selection different battery quantity 16pcs: 0,7PF; 18pcs: 0,8PF; 20pcs: 0,9PF

• Wide input voltage range: 208 ~ 478Vac

• Wide input frequency range (50Hz: 45 ~ 55Hz / 60Hz: 54 ~ 66Hz)

• Support genereator input

• Support economic (ECO) operation mode

• Self-testing when UPS startup

• Options: SNMP card / Relay card / Parallel board

• Cold start

Control panel

Relay card

SNMP

Parallel board

Battery cabinets (optional)

Page 19: The right ITK UPS. · 2019. 7. 31. · Voltage range 81-145 VAC or 162-290 VAC Frequency range 50/60Hz ±10% auto-sensing OUTPUT Voltage Regulation ±10% for both AC mode and Battery

19

MEMOPOVER PLUS 3/1 PHASEMODEL

10kVA 15kVA 20kVACAPACITY (VA / WATTS) 10k/ 9k 15k / 13,5k 20k / 18k

INPUT

Nominal voltage 380/400/415Vac; (3Ph+N+PE)Operating voltage range 208 ~ 478VacOperating frequency range 45~55Hz for 50Hz, 54Hz~66Hz for 60Hz (auto-sensing)Power factor ≥ 0,99

Bypass voltage range

Max. voltage; 220V: +25% (optional +10%, +15%, +20%)230V: +20% (optional +10%, +15%)

240V: +15% (optional +10%)Min. voltage: -45% (optional -20%, -30%)

Bypass frequency range Frequency protection range: ±10%ECO range Same as the bypassHarmonic distortion (THDi) <5% (100% linear load)Generator input Support

OUTPUT

Rated Voltage 220 / 230 / 240 VacPower factor 0,9Voltage regulation ±1%

FrequencyLine mode ±1% / ±2% / ±4% / ±5% / ±10% of the rated frequency (optional)Batt. mode 50 / 60 (±0,1)Hz

Crest factor 3:1

Harmonic distortion (THDv) ≤2% with linear load≤5% with non-linear load

Efficiency >93,5% <94,5

BATTERY

Battery voltage ± 96 / 108 / 120Vdc (optional)Capacity (Standard unit) 12V / 7Ah / 9AhTypical recharging time 6 ~ 8 hours (to 90% of full capacity)Charging current 1A (10kVA standard unit); max current 10A (Long run unit)

SYSTEM FEATURES

Transfer time Mains to battery; 0ms; Mains to bypass: 0ms

OverloadLine mode Load ≤110%: 60min, ≤125%: last 10min, ≤150%: last 1min, >150 turn to

bypass mode immediatelyBypass mode 63A (Breaker) 100A (Breaker) 125A (Breaker)

Short circuit Hold whole systemOverheat Line mode: Turn to bypass, Bat. mode: Shut down UPS immediatelyBattery low Alarm and switch offSelf-diagnostics Upon power on and software controlBattery Advanced battery managementAudible & Visual alarms Line failure, Battery under voltage, Overload & UPS fault

LED & LCD display Line mode, Battery mode, ECO mode, Bypass mode, Battery under voltage, Overload & UPS fault

LCD displayInput voltage, Input frequency, Output voltage, Output frequency, Load

percentage, Battery voltage, Inner temperature & Remaining battery backup time

Communication interface RS232, USB, SNMP card (optional), Parallel board (optional), Relay card (optional)

ENVIRONMENT

Operating temperature 0 ~ 40ºCStorage temperature -25 ~ 55ºCHumidity range 0 ~ 95% (Non-condensing)Altitude < 1500mNoise level <55dB <58dB

PHYSICALDimension D×W×H (mm) 597×250×655(S)/502×250×616(H) 502×250×616Net weight (kg) 76(S) / 35(H) 45 46

STANDARDS Safety IEC/EN62040-1, IEC/EN60950-1

EMC IEC/EN62040-2, IEC61000-4-2, IEC61000-4-3, IEC61000-4-4,IEC61000-4-5, IEC61000-4-6, IEC61000-4-8

BATTERY BANKModel MP-BT SeriesBattery type & max. quantity 2×20pcs / 7Ah (9Ah)

PHYSICAL OF BAT-TERY BANK

Dimension D×W×H (mm) 597×250×616Net weight (kg) 122 / 134

Page 20: The right ITK UPS. · 2019. 7. 31. · Voltage range 81-145 VAC or 162-290 VAC Frequency range 50/60Hz ±10% auto-sensing OUTPUT Voltage Regulation ±10% for both AC mode and Battery

On-LineMEGAPOWER 3/3 Phase10 - 40kVA, PF 1,0

20

The Megapower 3/3 Phase 1,0PF parallel redundancy online UPS series, featured with 7" color Monitor display, smallest footprint cabinet, built-in batteries up to 40kVA, DSP Control, Common Battery, Programmable battery voltage, 3-lvel intelligent charge mode with powerful battery charges, is an ideal budget-concerned solution to your server, bank, industrial equipment, internet data center, telecom, IT equipment and other mission-critical application.

Features

• Built-in Batteries supports 4 ~ 30min autonomy at 60% load.

• Parallel Redundancy up to 4 units

• Wide Input Voltage and Frequency Windows

• Unity Power Factor and Low Input Distrotion

• Output Power Factor 1,0

• ECO Mode for Energy Saving

• Common Battery

• Programmable Battery Voltage Reduces unnecessary investment and increases your competition

• Module-type design speeds up maintenance work & reduces MTTR

• Highest Efficiency up to 94,5%

• Matching Batttery Packs

• 3-level Intelligent Charge Modes with Smart Charge Current Adjustment

• Powerful Charger up to 15A

• Versatile Communication Interfaces Provided for different applications

• Superior Overload Capability

• Programmable Control and Monitoring Software via RS232 port

• Emergency Power Off

• DC Start

• 7" Color Monitor display supports up to 9 different languages.

Page 21: The right ITK UPS. · 2019. 7. 31. · Voltage range 81-145 VAC or 162-290 VAC Frequency range 50/60Hz ±10% auto-sensing OUTPUT Voltage Regulation ±10% for both AC mode and Battery

MEGAPOWER 3/3 PHASEMODEL

10kVA 15kvA 20kVA 30kVA 40kVACAPACITY (VA / WATTS) 10k / 10k 15k / 15k 20k / 20k 30k / 30k 40k / 40k

INPUT

Rectifer input

Rated AC Input Voltage 380 / 400 / 415Vac, (3PH+N+PE)Input Voltage Range 305 ~ 478Vac (Full load); 208 ~ 478Vac (50% load)Frequency 50 or 60Hz (40 ~ 70Hz Range)Power factor 0,99Harmonic distortion (THDi) ≤2% (100% nonlinear load)

Bypass input

Bypass voltage rangeMax. voltage; 220V: +25% (optional +10%, +15%, +20%), 230V: +20% (optional +10%, +15%), 240V:

+15% (optional +10%)Min. voltage: -45% (optional -20%, -30%)

Bypass frequency range ±10%Synchronization - Window ±1% / ±2% / ±4% / ±5% / ±10% optional (default ±10%)Max current Breaker 20A Breaker 32A Breaker 40A Breaker 63A Breaker 80AUpstream protection, bypass line

Thermomagnethic circuit-breaker, rated up to 125% of nominal ouput current. IEC 60947-2 curve C

Current rating of neutral cable (A) 1,7 × In

Generator input Support

OUTPUTInverter Output

Power factor 1,0Rated AC Voltage 1 300 / 400 / 415 Vac, (3Ph+N+PE)Voltage Regulation ± 1%Transient Voltage Response ±5% (linear load)

Phase Balance 120˚ ±1˚ (100% unbalanced load)

Frequ-ency

Line mode synchronize with input; when input frequency > ±10% (±1% / ±2% / ±4% / ±5% optional),output (50/60±0,1%) Hz

Battery mode 50/60±0,1%) HzCrest factor 3:1Harmonic distortion (THD) <1% (linear load), <3% (non-linear load)Overload capacity

AC mode Load ≤110%: last 60min, ≤125% last 10min, ≤150% last 1min, >150% turn to bypass immediatelyBattery mode Load ≤110%: last 10min, ≤125% last 1min, ≤150% last 5s, >150% shut down UPS immediately

Efficiency Normal mode 93,5% 94,5

BATTERY

Battery voltage

Standard unit

±120Vdc (20pcs 12V9Ah); (2×20pcs 12V9Ah; 3×20pcs 12V9Ah optional)

±120Vdc (2×20pcs 12V9Ah); (3×20pcs 12V9Ah optional)

±120Vdc (3×20pcs 12V9Ah)

±180Vdc (2×30pcs 12V9Ah)

Long run unit ±96 / 108 / 120 /132 / 144Vdc

±180/192/204/216/228/240/252/264/276/288/300Vdc (30/32/34/36/38/40/42/44/46/48/5

0pcs optional)Float voltage 2,25V/cell (selectable from 2,20~2,29V/cell) Constant current and constant voltage charge mode Boost Charge Voltage 2,30V/cell (selectable from 2,30~2,40V/cell) Constant current and constant voltage charge mode End of Discharge 1,75V/cell (selectable from 1,60 or 1,90V/cell)Charge Current (A) (charge current can be set according to battery capacity installed)

Standard unit 1,35A (2,7; 4,05A optional)

2,7A (4,05A optional) 4,05A 2,7A

Long run unit max. current 15A (limited by input current)

SYSTEM FEATURES

Transfer TimeSynchronous Utility to Battery: 0ms / Utility to bypass: 0msAsynchronous 15ms (50Hz), 13,3ms (60Hz)

Alarms Overload, utility abnormal, UPS fault, battery low, etc.Protection short circuit, overload, over temperature, battery low, fan fault alarm

Communication Interface USB, RS232, Paralel port, Dry contact, Intelligent slotOptional: SNMP card, Relay card, Battery temperature sensor

ENVIRON-MENTAL

Operating Temperature 0ºC ~ 40ºCStorage Temperature -25ºC ~ 55ºC (no battery)Humidity 0 ~ 95% non condensingAcoustical Noise (from 1m distance) <55dB <58dBAltitude < 1500m De-rating when >1500m

STAND-ARDS

Safety certifications IEC/EN62040-1, IEC/EN60950-1EMC IEC/EN62040-2, IEC/EN61000-4-4, IEC/EN61000-4-5, IEC/EN61000-4-6, IEC/EN61000-4-8

21