The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A...

63
The Relevance of Protocol, API, and Modeling Standards to Control Centers Ralph Mackiewicz SISCO, Inc. 2004 EMS Users Group Conference 14 September, 2004 St. Louis, MO

Transcript of The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A...

Page 1: The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A Layered Standard Mapping to MMS Protocol - IEC61850-8-1 Abstract Service Model - IEC61850-7-2

The Relevance of Protocol, API, and Modeling

Standards to Control Centers

Ralph MackiewiczSISCO, Inc.

2004 EMS Users Group Conference14 September, 2004

St. Louis, MO

Page 2: The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A Layered Standard Mapping to MMS Protocol - IEC61850-8-1 Abstract Service Model - IEC61850-7-2

Objective

To provide an overview of the rational for developing and the

benefits of using a comprehensive set of standards for model driven integration in the electric utility

environment.

Page 3: The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A Layered Standard Mapping to MMS Protocol - IEC61850-8-1 Abstract Service Model - IEC61850-7-2

Definitions:

InteroperabilityInteroperabilityThe ability of computer systems

to exchange information with other systems.

Page 4: The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A Layered Standard Mapping to MMS Protocol - IEC61850-8-1 Abstract Service Model - IEC61850-7-2

Definitions:

IntegrationIntegrationThe ability of computer based

applications to interact with other systems in order to perform a useful

function for the user.

Page 5: The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A Layered Standard Mapping to MMS Protocol - IEC61850-8-1 Abstract Service Model - IEC61850-7-2

Interoperability and Integration• Easy to Achieve:

Page 6: The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A Layered Standard Mapping to MMS Protocol - IEC61850-8-1 Abstract Service Model - IEC61850-7-2

A Better Way• Interoperability and Integration without

having to program it all yourself:• “Plug-and-Play” where applications are inherently

capable of interoperating with other systems and performing integrated application functions.

• This is only possible if there are standards to enable it.

• This work is progressing.

Page 7: The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A Layered Standard Mapping to MMS Protocol - IEC61850-8-1 Abstract Service Model - IEC61850-7-2

A Cautionary Note

• Plug and Play of applications is a path, not an end point.

• By the time we get to were we are going today, someone will have moved the goal.

• If you don’t set out on the path, you will never make any progress.

• The first on the path will work the hardest and will also reap the most reward.

Page 8: The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A Layered Standard Mapping to MMS Protocol - IEC61850-8-1 Abstract Service Model - IEC61850-7-2

Obligatory Motivational Quote

“Obstacles are those frightful things that appear when you take your eyes off your objective.”

- Henry Ford

Page 9: The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A Layered Standard Mapping to MMS Protocol - IEC61850-8-1 Abstract Service Model - IEC61850-7-2

The Interoperability Dilemma

HUNDREDS OF PROTOCOLS!Meter RTU Recloser Breaker Transformer

Diff.Relay

O.C.Relay SOEMeter RTU Recloser Breaker Transformer

Diff.Relay

O.C.Relay SOEMeter RTU Recloser Breaker Transformer

Diff.Relay

O.C.Relay SOEMeter RTU Recloser Breaker Transformer

Diff.Relay

O.C.Relay SOEMeter RTU Recloser Breaker Transformer

Diff.Relay

O.C.Relay SOEMeter RTU Recloser Breaker Transformer

Diff.Relay

O.C.Relay SOEMeter RTU Recloser Breaker Transformer

Diff.Relay

O.C.Relay SOE

HUNDREDS OF SUBSTATIONS!

DMS CIS EMS/SCADA OMS

Way Too Expensive

Page 10: The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A Layered Standard Mapping to MMS Protocol - IEC61850-8-1 Abstract Service Model - IEC61850-7-2

RTU

Meter RTU Recloser Breaker TransformerDiff.Relay

O.C.Relay SOE

RTU

Meter RTU Recloser Breaker TransformerDiff.Relay

O.C.Relay SOE

RTU

Meter RTU Recloser Breaker TransformerDiff.Relay

O.C.Relay SOE

RTU

Meter RTU Recloser Breaker TransformerDiff.Relay

O.C.Relay SOE

RTU

Meter RTU Recloser Breaker TransformerDiff.Relay

O.C.Relay SOE

RTU

Meter RTU Recloser Breaker TransformerDiff.Relay

O.C.Relay SOE

RTU

Meter RTU Recloser Breaker TransformerDiff.Relay

O.C.Relay SOE

The Interoperability Dilemma

DMS CIS EMS/SCADA OMS

Meter RTU Recloser Breaker TransformerDiff.Relay

O.C.Relay SOE

RTU

Way Too Expensive

Page 11: The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A Layered Standard Mapping to MMS Protocol - IEC61850-8-1 Abstract Service Model - IEC61850-7-2

The Integration Dilemma

RTU

Meter RTU Recloser Breaker TransformerDiff.Relay

O.C.Relay SOE

RTU

Meter RTU Recloser Breaker TransformerDiff.Relay

O.C.Relay SOE

RTU

Meter RTU Recloser Breaker TransformerDiff.Relay

O.C.Relay SOE

RTU

Meter RTU Recloser Breaker TransformerDiff.Relay

O.C.Relay SOE

RTU

Meter RTU Recloser Breaker TransformerDiff.Relay

O.C.Relay SOE

RTU

Meter RTU Recloser Breaker TransformerDiff.Relay

O.C.Relay SOE

RTU

Meter RTU Recloser Breaker TransformerDiff.Relay

O.C.Relay SOEMeter RTU Recloser Breaker Transformer

Diff.Relay

O.C.Relay SOE

RTU

DMS CIS EMS/SCADA OMS

GIS WOM MaintVSAWay Too Complex

Page 12: The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A Layered Standard Mapping to MMS Protocol - IEC61850-8-1 Abstract Service Model - IEC61850-7-2

Standards are Good!

“Standards are great. Everyone should have one.”

– Bob Metcalfe, Co-inventor of Ethernet

Fewer of the Right Standards are Better

Page 13: The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A Layered Standard Mapping to MMS Protocol - IEC61850-8-1 Abstract Service Model - IEC61850-7-2

Traditional Protocol Standards

• Specified how you arrange bytes on the wire in order to transfer bytes of data between a device and an application

• Good News: It worked! Device communications costs were lowered.

• Bad News: No standard for data representation or how devices should look and behave to network applications.

Page 14: The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A Layered Standard Mapping to MMS Protocol - IEC61850-8-1 Abstract Service Model - IEC61850-7-2

Typical Legacy Protocol Data Model

I need the Phase A voltage for the 345KV primary feeder

It is in Register 4023 and 4024

That’s intuitive?

Page 15: The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A Layered Standard Mapping to MMS Protocol - IEC61850-8-1 Abstract Service Model - IEC61850-7-2

Behavior Modeling

• Assume R400220 holds breaker status.• Does 1 mean open or closed?• Can I write this object to operate the breaker?• Where is the select?• Is it selected?

• Even if every device used R400220 to hold breaker status this still isn’t enough to provide interoperability.

Page 16: The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A Layered Standard Mapping to MMS Protocol - IEC61850-8-1 Abstract Service Model - IEC61850-7-2

A New Approach Needed

• For protocols to provide interoperability at the system level they need to:

• Specify the bytes/format of the data on the wire• Specify the meaning of data• Specify the behavior of the data

Page 17: The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A Layered Standard Mapping to MMS Protocol - IEC61850-8-1 Abstract Service Model - IEC61850-7-2

IEC61850 – A Layered Standard

Mapping to MMS Protocol Mapping to MMS Protocol -- IEC61850IEC61850--88--11

Abstract Service Model Abstract Service Model -- IEC61850IEC61850--77--22

Device Object Models Device Object Models -- IEC61850IEC61850--77--3, 73, 7--44

Device ModelDevice Model Data ObjectsData Objects Data TypesData Types Naming ConventionsNaming Conventions

Communication Stack ProfilesCommunication Stack Profiles

ISO/OSI protocol stackISO/OSI protocol stack TCP / IP protocol stackTCP / IP protocol stack

InitiateInitiate InfoReportInfoReport.. GetNameListGetNameList WriteWrite VariableListVariableList JournalsJournals

AssociateAssociate ReportingReporting SelfSelf--DescriptionDescription ControlControl Data SetData Set LogsLogs

Page 18: The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A Layered Standard Mapping to MMS Protocol - IEC61850-8-1 Abstract Service Model - IEC61850-7-2

Layering Benefits

• Enables definition beyond just the bytes on the wire.

• Each layer is optimized independently.

• Enables protocols to be separated from application functions to enable use of existing standards.

Page 19: The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A Layered Standard Mapping to MMS Protocol - IEC61850-8-1 Abstract Service Model - IEC61850-7-2

IEC61850 Data Model

Physical Device(network address)

Logical Device(e.g. Relay1)

MMXU1 MMXU2

MXMX

APhV

Logical Nodes

Functional Constraints

Object Name =MMXU2$MX$A =

Feeder #2 Current MeasurementsNetwork

Measurement Node

Measurements

CurrentVoltage

Page 20: The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A Layered Standard Mapping to MMS Protocol - IEC61850-8-1 Abstract Service Model - IEC61850-7-2

IEC61850 Overview

• IEC61850 is an object oriented substation automation protocol that provides standardized names, data meaning, device behavior, self-describing devices, and a common configuration language.

• Available now.• Major demo at CIGRÉ 2004.

Page 21: The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A Layered Standard Mapping to MMS Protocol - IEC61850-8-1 Abstract Service Model - IEC61850-7-2

CIGRÉ 2004

Protocol Standardization Works!

Page 22: The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A Layered Standard Mapping to MMS Protocol - IEC61850-8-1 Abstract Service Model - IEC61850-7-2

Standardized

Interfacing Protocols to AppsApplication

1

Driver 1

Application2

Driver 2

Application3

Driver 3

Application4

Driver 4

Application5

Driver 5

Not Standardized

Standardized Protocol

Page 23: The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A Layered Standard Mapping to MMS Protocol - IEC61850-8-1 Abstract Service Model - IEC61850-7-2

Impact of Lack of API Standards

• Each application developer had to develop drivers for all popular protocols.

• Application developers spent considerable resources on drivers instead of applications.

• Result:• Less application functionality• Higher application costs

Page 24: The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A Layered Standard Mapping to MMS Protocol - IEC61850-8-1 Abstract Service Model - IEC61850-7-2

Using Protocols: API Standards Useful

Application1

Driver

Application2

Driver

Application3

Driver

Application4

Driver

Application5

Driver

Page 25: The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A Layered Standard Mapping to MMS Protocol - IEC61850-8-1 Abstract Service Model - IEC61850-7-2

API Standards• Enables 3rd party market for drivers

• Enables niche application players to exist

• Allows more resources for applications• All parties have a self-interest in seeing

that this works• Results

• More Choice• Less Work• Lower Costs

Page 26: The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A Layered Standard Mapping to MMS Protocol - IEC61850-8-1 Abstract Service Model - IEC61850-7-2

DDE

• Dynamic Data Exchange (DDE) introduced in Windows 3.1

• Enabled DDE servers for protocols to be used for any application supporting DDE interface

• Created a market for third party communications drivers.

Page 27: The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A Layered Standard Mapping to MMS Protocol - IEC61850-8-1 Abstract Service Model - IEC61850-7-2

DDE Limits

• Designed for linking data between spreadsheets:

• Resource intensive• Low throughput• No pre-defined structure

• Interface was standard, but the configuration and usage was different between drivers.

Page 28: The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A Layered Standard Mapping to MMS Protocol - IEC61850-8-1 Abstract Service Model - IEC61850-7-2

OPC – OLE for Process Control

• Based on MS Object Linking and Embedding (OLE) and Component Object Model (COM) technology.

• Rigorous defined resource efficient API that provides plug’n play of applications and drivers.

• Result: Widespread usage and many off-the-shelf interoperable products available.

Page 29: The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A Layered Standard Mapping to MMS Protocol - IEC61850-8-1 Abstract Service Model - IEC61850-7-2

OPC Today• Hundreds of protocols and applications.

• Data Access• Historical Data Access• Alarms and Events• Data Exchange• XML Messaging• Complex Data• Commands

Page 30: The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A Layered Standard Mapping to MMS Protocol - IEC61850-8-1 Abstract Service Model - IEC61850-7-2

OPC Shortcomings

• Windows specific. What about Unix used in many EMS/SCADA?

• Data was still a collection of items without context (the meaning of the data).

Page 31: The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A Layered Standard Mapping to MMS Protocol - IEC61850-8-1 Abstract Service Model - IEC61850-7-2

The Common Information Model

Switch

MeasurementsTerminals

Breaker

ConductingEquip.

BaseVoltageBusMeasurements

XFMRWindingTAPChanger

Substation

XFMR

VoltageLevel

Measurements

Page 32: The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A Layered Standard Mapping to MMS Protocol - IEC61850-8-1 Abstract Service Model - IEC61850-7-2

CIM Transformer Model in UML

ConductingEquipment(from Core)

Equipment(from Core)

PowerSystemResource(from Core)

RegulationSchedule

TapChanger

0.. 1

0.. n

+RegulationSchedule0..1

+ TapChangers

0..n

WindingTest

HeatExchanger

TransformerWinding

0..n

1

+TapChangers

0..n

+TransformerWinding

1

1

0..n

+From_TransformerWinding1

+ From_WindingTests0..n1

0..n

+To_WindingTest1

+To_TransformeWindings0..n

PowerTransformer

0..1

1

+HeatExchanger 0..1

+PowerTransformer 1

1..n

1

+ Contains _TransformerWindings

1..n

+MemberOf_PowerTransformer

1

Page 33: The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A Layered Standard Mapping to MMS Protocol - IEC61850-8-1 Abstract Service Model - IEC61850-7-2

Benefits of Models• Models give context and meaning to data

improving integration and interoperability.

• The information contained in the model enables automation of setup and maintenance tasks.

• Model aware applications can be made independent of the data.

Page 34: The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A Layered Standard Mapping to MMS Protocol - IEC61850-8-1 Abstract Service Model - IEC61850-7-2

Legacy View of SCADA Data

ClientFlat set of

tags

SCADA

Access by tag name

Page 35: The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A Layered Standard Mapping to MMS Protocol - IEC61850-8-1 Abstract Service Model - IEC61850-7-2

CIM View Of SCADA Data

ClientHierarchy changes

with network model changes

SCADA

Bus

XFMR XFMR XFMR XFMR

Bus

Substation

Device or other

system related views

supported

Access by Description

Page 36: The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A Layered Standard Mapping to MMS Protocol - IEC61850-8-1 Abstract Service Model - IEC61850-7-2

CIM – IEC61970 & IEC61968

• Originally developed by EPRI’s Control Center API (CCAPI) Workshop.

• Now progressing as IEC standards.• IEC61970 (widely used):

• Power System Modeling & SCADA

• IEC61968 (increasing usage):• Asset Mgmt, Billing, GIS, Work Mgmt, etc.

Page 37: The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A Layered Standard Mapping to MMS Protocol - IEC61850-8-1 Abstract Service Model - IEC61850-7-2

CIM and IEC61850

• CIM has power system, asset, business process, work management models.

• IEC61850 has device models

• How do they fit?

Page 38: The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A Layered Standard Mapping to MMS Protocol - IEC61850-8-1 Abstract Service Model - IEC61850-7-2

TC57 ArchitectureCIM IEC61850

Power

System

Models

Device

Models

Measurements Measurements

Relay1/MMXU1.PhV.cVal.mag.fAlias

Page 39: The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A Layered Standard Mapping to MMS Protocol - IEC61850-8-1 Abstract Service Model - IEC61850-7-2

The Next Step:APIs and Models – GID

• With CIM, programs still need a method for accessing both the data and the model information about the data (meta-data)

• EPRI CCAPI project submitted the Generic Interface Definition (GID) to the IEC WG13 for standardization in IEC61970.

Page 40: The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A Layered Standard Mapping to MMS Protocol - IEC61850-8-1 Abstract Service Model - IEC61850-7-2

The GID

• GID Application Programming Interfaces (APIs) reference all data in the context of a common data exchange model, the CIM.

• Based on previous work within both OPC and the Object Management Group (OMG)

Page 41: The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A Layered Standard Mapping to MMS Protocol - IEC61850-8-1 Abstract Service Model - IEC61850-7-2

GID APIs• Generic Data Access (GDA) for

reading/writing modeling information

• High-Speed Data Access (HSDA) for reading/writing real-time data

• Time Series Data Access (TSDA) for reading/writing historical data

• Generic Events and Subscriptions (GES) for publishing and subscribing to generic XML messages

Page 42: The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A Layered Standard Mapping to MMS Protocol - IEC61850-8-1 Abstract Service Model - IEC61850-7-2

GID APIs vs. OPC

• Namespaces:• OPC interfaces present a namespace that are

specific to the particular server. • GID interfaces present a namespace based on the

model.

• Platforms:• OPC is currently Windows specific• GID is platform independent

Page 43: The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A Layered Standard Mapping to MMS Protocol - IEC61850-8-1 Abstract Service Model - IEC61850-7-2

GID – OPC - OMG

AEAlarms & Events

GESGeneric Eventing and Subscriptions

DAFData Access Facility

GDAGeneric Data Access

HDAISHistorical Data Access from

Industrial Systems

HDAHistorical Data Access

TSDATime Series Data Access

DAISData Access from Industrial Systems

DAData Access

HSDAHigh Speed Data Access

OMGOPCGID API

Page 44: The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A Layered Standard Mapping to MMS Protocol - IEC61850-8-1 Abstract Service Model - IEC61850-7-2

IEC TC57 Standards

• The IEC TC57 standards are specifying a model driven architecture for electric utility integration

• Protocols - Messages• Models• APIs

• A common approach across industries

Page 45: The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A Layered Standard Mapping to MMS Protocol - IEC61850-8-1 Abstract Service Model - IEC61850-7-2

GID – Generic Interface Definition Services (IEC61970-4xx)

Field Devices

CIM - Common Information Model (IEC61970-3xx)

Administrative Services

OMObject Models(IEC61850-7-3 & 7-4)

SMService Models(IEC61850-7-2)

CPCommunication Profiles &Mapping (IEC61850-8 & 9)

Application DomainsCommunicationLevel

Integrated Energy and communication System Architecture (IECSA)

FieldC

ontrol C

enter

Applications and Databases

SA

(Substation)

DE

R(D

istributed Resources)

DA

(Distribution A

utomation)

CU

S(C

ustomer)

GE

N (G

eneration)

Other …

..

CFL

Configuration Language (IE

C61850-6+)

SE

CS

ecurity (TBD

)

CN

MN

etwork M

anagement (TB

D)

Page 46: The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A Layered Standard Mapping to MMS Protocol - IEC61850-8-1 Abstract Service Model - IEC61850-7-2

ISA S.95 – IEC62264• An ISA standard for the interface between

automation and production control.• Addresses both discrete and continuous

process industries.• Specifies models and terminology for

production orders, scheduling, planning, etc.

• S.95 is just now becoming used.

Page 47: The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A Layered Standard Mapping to MMS Protocol - IEC61850-8-1 Abstract Service Model - IEC61850-7-2

CIM vs. SP95

ConductingEquipment(from Core)

Equipment(from Core)

PowerSystemResource(from Core)

RegulationSchedule

TapChanger

0..1

0.. n

+RegulationSchedule0..1

+ TapChangers

0.. n

WindingTest

HeatExchanger

TransformerWinding

0..n

1

+TapChangers

0..n

+TransformerWinding

1

1

0..n

+From_TransformerWinding1

+ From_WindingTests0..n1

0..n

+To_WindingTest1

+To_TransformeWindings0..n

PowerTransformer

0..1

1

+HeatExchanger 0..1

+PowerTransformer 1

1..n

1

+ Contains _TransformerWindings

1..n

+MemberOf_PowerTransformer

1

MaintenanceRequest

MaintenanceRequest

MaintenanceWork Order

MaintenanceWork Order

MaintenanceResponse

MaintenanceResponse

May be generated for0..n

1..1

1..1

1..1

EquipmentClass Property

EquipmentClass Property

EquipmentProperty

EquipmentProperty

EquipmentCapability TestSpecification

EquipmentCapability TestSpecification

EquipmentClass

EquipmentClass

Hasvalues for

0..n

0..n

0..n

0..n

0..n

EquipmentEquipment

EquipmentCapability Test

Result

EquipmentCapability Test

Result

0..n

0..n1..n

Hasproperties

of

Is testedby a

Maps to

Defined by

Records theexecution of

0..n

0..n May result in

0..1

May be up of Is against

Is madeagainst

0..n

0..n

Defines aprocedure forobtaining a

CIMCIM

S.95S.95

Page 48: The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A Layered Standard Mapping to MMS Protocol - IEC61850-8-1 Abstract Service Model - IEC61850-7-2

Impact of Being Model Neutral

• Increased data independence.

• Enables user specific customizations without affecting coding.

• Enables application of adapters across industries increasing 3rd party interest in supporting product based adapters.

Page 49: The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A Layered Standard Mapping to MMS Protocol - IEC61850-8-1 Abstract Service Model - IEC61850-7-2

Impact: Self Description

• Applications obtain the description of the data from the source of the data.

• Eliminates a great deal of configuration and errors.

• Improves understanding of data• Increases independence of applications from the

sources of data• LOWERS THE COST OF USING

TECHNOLOGY

Page 50: The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A Layered Standard Mapping to MMS Protocol - IEC61850-8-1 Abstract Service Model - IEC61850-7-2

Impact: Model Awareness• Applications and users can see the meaning of

data and its relationship to other data.

• Allows configuration in the context of the power system.

• Avoids arcane proprietary tag naming conventions.

• Allows model changes to be propagated automatically

• LOWERS THE COST OF USING TECHNOLOGY

Page 51: The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A Layered Standard Mapping to MMS Protocol - IEC61850-8-1 Abstract Service Model - IEC61850-7-2

Impact: Application Independence

• Application can be independent of the data required by finding what is needed in the model automatically.

• No need to preconfigure each instance of data to be operated on.

• Enables reusability of applications without configuration.

• LOWERS THE COST OF USING TECHNOLOGY

Page 52: The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A Layered Standard Mapping to MMS Protocol - IEC61850-8-1 Abstract Service Model - IEC61850-7-2

Data Dependent Application

Read TSUB23PHA4023Read TSUB23PHB4023Read TSUB23PHC4023Read TSUB24PHA6187

Read TSUB76PHB5865Read TSUB76PHC5865Read TSUB76PHA5977Read TSUB76PHB5977Read TSUB76PHC5977

.....

Read All Transformer Voltages

Other algorithms possible. But, regardless of

algorithm, programs generally contain

hard coded references to either names or tables to

access.

Page 53: The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A Layered Standard Mapping to MMS Protocol - IEC61850-8-1 Abstract Service Model - IEC61850-7-2

Data Independent ApplicationRead All Transformer Voltages

Find Next Substation

Find NextTransformer

Find NextVoltage

Read

Every name is either defined by CIM or

defined in the model

Page 54: The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A Layered Standard Mapping to MMS Protocol - IEC61850-8-1 Abstract Service Model - IEC61850-7-2

Impact: Leverage Existing Technology

• The layered approach enables utility specific functions to be added to existing generic technology that is in widespread use.

• Minimizes the utility specific technology (lower volume) required.

• LOWERS THE COST OF USING TECHNOLOGY

Page 55: The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A Layered Standard Mapping to MMS Protocol - IEC61850-8-1 Abstract Service Model - IEC61850-7-2

About Benefits & Justification

• Identify all the benefits (obvious).• Identify ALL the costs:

– Equipment– Installation– Engineering– Commissioning– Utilization Costs– Impact on External Systems– Costs to Change/Migrate in Future– Intangibles (new capability)

Page 56: The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A Layered Standard Mapping to MMS Protocol - IEC61850-8-1 Abstract Service Model - IEC61850-7-2

Identifying ALL Costs• Requires a complete view of cost.

You can’t justify a system by examining only the price.

- OR -

The benefit of a system is not in the price.

Page 57: The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A Layered Standard Mapping to MMS Protocol - IEC61850-8-1 Abstract Service Model - IEC61850-7-2

Identifying ALL Costs• Requires a longer time frame.

It is hard to justify any system by examining only the purchase price.

- OR -

Benefits are received as systems are used, not when they are purchased.

Page 58: The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A Layered Standard Mapping to MMS Protocol - IEC61850-8-1 Abstract Service Model - IEC61850-7-2

Model-Driven Cost JustificationC

ost

TimePurchase

Payback

BENEFITTraditionalApproaches

ModelDriven

Approaches

Page 59: The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A Layered Standard Mapping to MMS Protocol - IEC61850-8-1 Abstract Service Model - IEC61850-7-2

Example: Power Plant Dispatch

HMI/SCADAPackage

PLC Driver

CorporateNetwork

Control Center

1 of 32 Power Plants ICCP-TASE.2 Interface

OPC ServerOPC Client

OPC ServerOPC Client

PLCI/O

PLC Network

GeneratorExisting Systems

InterfaceAdded

Page 60: The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A Layered Standard Mapping to MMS Protocol - IEC61850-8-1 Abstract Service Model - IEC61850-7-2

Example: Plug’n Play With OPCOPC Gateway

IEC61850

OPC

Server

DNP3

OPC

Server

OPC Client APIOPC Client API

OPC Server API OPC Server API

ToIEC61850Devices

ToDNP3

Devices

Simple Gateway Using OPC

Page 61: The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A Layered Standard Mapping to MMS Protocol - IEC61850-8-1 Abstract Service Model - IEC61850-7-2

Example: Substation and EMS Integration

OPC Based Product

Substation EquipmentMaintenance Models(CIM) & Applications

AssetMgmt.Models

EMS

Utility Integration Bus

GDA server& client TSDA

GDA TSDA

Historian AdapterHistorian

ModelDatabase

(CIM)

Archive

GDA HDA DA

ICC

P

Power SystemModels (CIM)

GDA Server

GDA

Power Sys.Analysis

GDA HSDA

GDA HSDA

EquipmentModels

Power SystemModels

Can be added without disrupting existing systems.

OPCDA

GDAClient

OPCHDA

Page 62: The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A Layered Standard Mapping to MMS Protocol - IEC61850-8-1 Abstract Service Model - IEC61850-7-2

UCA – Protocols, Models, and APIs

The UCA® International Users Group is a forum where interested parties can

meet and cooperate in the implementation and usage of IEC

TC57 standards.http://www.ucainternational.org

Page 63: The Relevance of Protocol, API, and Modeling Standards to ... Base/EMS 2004... · IEC61850 – A Layered Standard Mapping to MMS Protocol - IEC61850-8-1 Abstract Service Model - IEC61850-7-2

Thank You

Ralph Mackiewicz6605 19½ Mile Road

Sterling Heights, MI 48314 USATel: +586-254-0020 x103

Fax: +586-254-0053E-Mail: [email protected]