The new Generation Wood Gasification Boilers
Transcript of The new Generation Wood Gasification Boilers
The New Generation Ventum Series leaps forward in gasification technology making them the fastest selling boilers in their class across Europe. It is designed for efficiency, economy and protection of the environment. With 92% efficiency, emissions (250 mg/m3 CO) below European and German regulations, adaptable to wood fuel moistures up to 33%, superior health and safety features and easy to use electronic controls, this gasification boiler is a testament of quality and perfection.
Ventum Series The new Generation Wood Gasification Boilers
Büyükelçi Sokak No:9 Kavaklıdere - Ankara / Türkiye T: +90 312 468 09 11 F: +90 312 468 45 96 www.arikazan.com
Tech
nica
l Spe
cific
atio
nsO
PERA
TIN
G C
ON
DIT
ION
S
97
85-55
55
3
4.5
230 Vac, 50 Hz
Ø80 x500mm Ø80 x 700mm
10
89 113 137 200
70504030
<60dB
1000 1500
5
2000 3000
125
11,0 3,2 5,5 23,0
110 140 230
Hard Wood, 15% < Humidity < 30%*
°C
-
°C
°C
-
-
Pa
Pa
mbar
lt
dB
lt
h
kg
bar
bar
Safety Limit Temperature
Boiler Class
Setting Range of Operating Temperature
Min. Water Return Temperature
Operating Pressure
Boiler Test Pressure
Electrical Connection
Recommended Fuel Types
Minimum Required Stack Draught
Boiler Gas Side Resistance
Boiler Water Side Pressure Drop ΔT = 10 °C
Fuel Filling Volume
Noise Level
Required Accumulation Tank Volume
Apx. Combustion Endurance
W1 - Width
W2 - Total width with cover plates
mm
mm
mm
mm
mm
mm
mm
mm
mm
mm
mm
mm
in stand-by
in full load, 100%
mm
W
W
lt
kg
600
650
1060
1060 13101210 1360
1165
715 865 955 1005
1437
890
90 104 104 168
385
740x1100x1355 740x1100x1495 740x1100x1595 740x1410x1650
425 450 600
146514151315
1360
125 - 130 146 -150
1 1⁄2”
1 1⁄2”
3⁄4”
1⁄2”
1137 1287 1387
590
380
975
57
1,8
1125
64
2,3
1225
70
2,9
1275
79
4,6
inch
inch
inch
L1 - Length
H1 - Height
H2 - Total Height
H6 - Height of Stack Connection
Stack Diameter ØD1 (inner-outer)
Water Content
Approx. Empty Weight
Tranport Dimensions
Hot Water OutletConnection
Water InletConnection
Safety Cooling Heat Exchanger15 °C, 2 bar cold water
Filling & Drain Connection
Flue Gas Temperature
Average Mass Flow Rate of Solid Pollutants (dust)
Average Electricity Consumption
CO
Diameter, ØD2
Diameter, ØD3
Diameter, ØD4
Diameter, ØD2
Position, H3
Position, H4
Position, H5
Position, L2
MA
IN D
IMEN
SIO
NS
EMIS
SIO
NRA
TES
POW
ERCO
NSU
MP-
TIO
NS
TECHNICAL SPECIFICATION OF VENTUM TYPE WOOD GASIFICATION BOILERS
CAPA
CITY Nominal Heat Output
kW
kcal/h 17.200
20
90,1
30
90,4
CLASS 5 acc. To EN 303-5
40
91,2
60
91,7
25.800 34.400 51.600
%Direct E�ciency
BOILER TYPE
VG20 VG30 VG40 VG60UNIT
°C
g/h
mg/m3
145-165
<700
3
Europe’s Fastest Selling Wood Gasification Boiler.
Ventum Series Wood Gasification Boilers FEATURES
As a stand-alone boiler or integrated with other heat systems the Ventum Gasification Boiler is fully adaptable and connectable with summer / winter season adjustment. Combined with a buffer tank, efficiency and performance is further increased as well as decreasing refuelling intervals.
• Independently adjustable primary and secondary combustion air.• Functional and User Friendly Control Panel.• Modulating induced draft fan.• Vertical heat exchanger tubes with turbulators.• Easy cleaning without removing any plate,• Newly designed Refractory Concrete parts are: - Smaller and Lighter for easy servicing, - Modular for easy replacement, • Bypass duct is larger than ever. A mechanical switch senses the door is open and orders the fan to work in full capacity.• Ellipsoid form of the combustion chamber allows more fuel to be loaded.• Boiler basement design allows both Forklift and pallet truck transport with ease.• Long service life with robust structure.• Interior negative pressure ensures safety.• Interchangeableemergencyheatdischargesystem”.• Dual purpose Anti-Tarring Plates: - Prevents and reduces condensation in the boiler - Increases efficiency by acting as a pre-heating intake air duct• Large collection tray for ease of cleaning and ash removal.
Why the Ventum is Europe’s Fastest Selling Wood Gasification Boiler
Special air ducts inside the doors allowspre-heating combustion air via natural air flow
Cleaning made easier by a simple swing of anexternal lever
Electronic Management with Smart Control panel is able to checkflue gas temperature and regulate the fan for optimal
heat production output.
*Large loading door at waist level
Interchangable Overheat Discharge Assembly
Observation Glass to Monitor Gasification Process
Bypass system automatically engages and prevents smokebursts when the door is open meeting highest Health and Safety
Standards in force.
Independently adjustable Primary and seconday air inlets
Robust and years of prooven hinge system Induced draft fan keeps the system in constant vacuumeliminating the possibility of a smoke leakage
to the ambient
Faster and longer gasification
• High > 92 % net.• Low emissions < 250 mg/m3 CO
• Only 15 mg/m3 dust.
Ventum SeriesWood Gasification Boilers FEATURES
As a stand-alone boiler or integrated with other heat systems the Ventum Gasification Boiler is fully adaptable andconnectable with summer / winter season adjustment. Combined with a buffer tank, efficiency and performance is furtherincreased as well as decreasing refuelling intervals.
• Independently adjustable primary and secondary combustion air.• Functional and User Friendly Control Panel.• Modulating induced draft fan.• Vertical heat exchanger tubes with turbulators.• Easy cleaning without removing any plate,• Newly designed Refractory Concrete parts are: - Smaller and Lighter for easy servicing, - Modular for easy replacement,• Bypass duct is larger than ever. A mechanical switch senses the door is open and orders the fan to work in full capacity.• Ellipsoid form of the combustion chamber allows more fuel to be loaded.• Boiler basement design allows both Forklift and pallet truck transport with ease.• Long service life with robust structure.• Interior negative pressure ensures safety.• Interchangeable emergency heat discharge system”.• Dual purpose Anti-Tarring Plates: - Prevents and reduces condensation in the boiler - Increases efficiency by acting as a pre-heating intake air duct• Large collection tray for ease of cleaning and ash removal.
Why the Ventum is Europe’s Fastest Selling Wood Gasification Boiler
Special air ducts inside the doors allows pre-heating combustion air via natural air flow
Cleaning made easier by a simple swing of an external lever
Electronic Management with Smart Control panel is able to check flue gas temperature and regulate the fan for optimal
heat production output.
*Large loading door at waist level
Interchangable Overheat Discharge Assembly
Observation Glass to Monitor Gasification Process
Bypass system automatically engages and prevents smokebursts when the door is open meeting highest Health and Safety
Standards in force.
Independently adjustable Primary and seconday air inlets
Robust and years of prooven hinge system Induced draft fan keeps the system in constant vacuumeliminating the possibility of a smoke leakage
to the ambient
Faster and longer gasification
High > 92 % ne o e i ion < 250 mg/m3 CO
nly 15 mg/m3 d
Ventum SeriesWood Gasification Boilers FEATURES
As a stand-alone boiler or integrated with other heat systems the Ventum Gasification Boiler is fully adaptable andconnectable with summer / winter season adjustment. Combined with a buffer tank, efficiency and performance is furtherincreased as well as decreasing refuelling intervals.
• Independently adjustable primary and secondary combustion air.• Functional and User Friendly Control Panel.• Modulating induced draft fan.• Vertical heat exchanger tubes with turbulators.• Easy cleaning without removing any plate,• Newly designed Refractory Concrete parts are: - Smaller and Lighter for easy servicing, - Modular for easy replacement,• Bypass duct is larger than ever. A mechanical switch senses the door is open and orders the fan to work in full capacity.• Ellipsoid form of the combustion chamber allows more fuel to be loaded.• Boiler basement design allows both Forklift and pallet truck transport with ease.• Long service life with robust structure.• Interior negative pressure ensures safety.• Interchangeable emergency heat discharge system”.• Dual purpose Anti-Tarring Plates: - Prevents and reduces condensation in the boiler - Increases efficiency by acting as a pre-heating intake air duct• Large collection tray for ease of cleaning and ash removal.
Why the Ventum is Europe’s Fastest Selling Wood Gasification Boiler
Special air ducts inside the doors allowspre-heating combustion air via natural air flow
Cleaning made easier by a simple swing of anexternal lever
Electronic Management with Smart Control panel is able to checkflue gas temperature and regulate the fan for optimal
heat production output.
*Large loading door at waist level
Interchangable Overheat Discharge Assembly
Observation Glass to Monitor Gasification Process
Bypass system automatically engages and prevents smoke bursts when the door is open meeting highest Health and Safety
Standards in force.
Independently adjustable Primary and seconday air inlets
Robust and years of prooven hinge system Induced draft fan keeps the system in constant vacuum eliminating the possibility of a smoke leakage
to the ambient
Faster and longer gasification
High > 92 % neo e i ion < 250 mg/m3 CO
nly 15 mg/m3 d
The New Generation Ventum Series leaps forward in gasification technology making them the fastestselling boilers in their class across Europe. It is designed for efficiency, economy and protectionof the environment. With 92% efficiency, emissions (250 mg/m3 CO) below European and Germanregulations, adaptable to wood fuel moistures up to 33%, superior health and safety featuresand easy to use electronic controls, this gasification boiler is a testament of qualityand perfection.
Ventum Series The new Generation Wood Gasification Boilers
Büyükelçi Sokak No:9 Kavaklıdere - Ankara / Türkiye T: +90 312 468 09 11 F: +90 312 468 45 96 www.arikazan.com
Tech
nica
l Spe
cific
atio
nsO
PERA
TIN
G C
ON
DIT
ION
S
97
85-55
55
3
4.5
230 Vac, 50 Hz
Ø80 x500mm Ø80 x 700mm
10
89 113 137 200
70504030
<60dB
1000 1500
5
2000 3000
125
11,0 3,2 5,5 23,0
110 140 230
Hard Wood, 15% < Humidity < 30%*
°C
-
°C
°C
-
-
Pa
Pa
mbar
lt
dB
lt
h
kg
bar
bar
Safety Limit Temperature
Boiler Class
Setting Range of Operating Temperature
Min. Water Return Temperature
Operating Pressure
Boiler Test Pressure
Electrical Connection
Recommended Fuel Types
Minimum Required Stack Draught
Boiler Gas Side Resistance
Boiler Water Side Pressure Drop ΔT = 10 °C
Fuel Filling Volume
Noise Level
Required Accumulation Tank Volume
Apx. Combustion Endurance
W1 - Width
W2 - Total width with cover plates
mm
mm
mm
mm
mm
mm
mm
mm
mm
mm
mm
mm
in stand-by
in full load, 100%
mm
W
W
lt
kg
600
650
1060
1060 13101210 1360
1165
715 865 955 1005
1437
890
90 104 104 168
385
740x1100x1355 740x1100x1495 740x1100x1595 740x1410x1650
425 450 600
146514151315
1360
125 - 130 146 -150
1 1⁄2”
1 1⁄2”
3⁄4”
1⁄2”
1137 1287 1387
590
380
975
57
1,8
1125
64
2,3
1225
70
2,9
1275
79
4,6
inch
inch
inch
L1 - Length
H1 - Height
H2 - Total Height
H6 - Height of Stack Connection
Stack Diameter ØD1 (inner-outer)
Water Content
Approx. Empty Weight
Tranport Dimensions
Hot Water OutletConnection
Water InletConnection
Safety Cooling Heat Exchanger15 °C, 2 bar cold water
Filling & Drain Connection
Flue Gas Temperature
Average Mass Flow Rate of Solid Pollutants (dust)
Average Electricity Consumption
CO
Diameter, ØD2
Diameter, ØD3
Diameter, ØD4
Diameter, ØD2
Position, H3
Position, H4
Position, H5
Position, L2
MA
IN D
IMEN
SIO
NS
EMIS
SIO
NRA
TES
POW
ERCO
NSU
MP-
TIO
NS
TECHNICAL SPECIFICATION OF VENTUM TYPE WOOD GASIFICATION BOILERS
CAPA
CITY Nominal Heat Output
kW
kcal/h 17.200
20
90,1
30
90,4
CLASS 5 acc. To EN 303-5
40
91,2
60
91,7
25.800 34.400 51.600
%Direct E�ciency
BOILER TYPE
VG20 VG30 VG40 VG60UNIT
°C
g/h
mg/m3
145-165
<700
3
Europe’s Fastest Selling Wood Gasification Boiler.
TECHNICAL SPECIFICATION OF VENTUM TYPE WOOD GASIFICATION BOILERS Unit
BOILER TYPE
VG20 VG30 VG40 VG60 VG80 VG100
CAPACITY Nominal Heat Output kW 20 30 40 60 80 100
kcal/h 17.200 25.800 34.400 51.600 68.800 86.000
Direct Efficiency % 90,1 90,4 91,2 91,7 91,5 91,3
OPERATING CONDITIONS
Boiler Class - CLASS 5 acc. To EN 303-5
Safety Limit Temperature °C 97
Setting Range of Operating Temperature °C 85 - 55
Min. Water Return Temperature °C 55
Operating Pressure bar 3
Boiler Test Pressure bar 4,5
Electrical Connection - 230 Vac , 50 Hz
Recommended Fuel Types - Ø80x500 mm Ø80x700 mm Ø80x1000 mm 2xØ80x500mm
Hard Wood, 15% < Humidity < 30% *
Minimum Required Stack Draught Pa 10
Boiler Gas Side Resistance Pa 125 110 140 230 240 250
Boiler Water Side Pressure Drop
DT = 20 °C mbar 11,0 3,2 5,5 23,0 25,0 28,0
Fuel Filling Volume lt 89 113 137 200 385
kg 30 40 50 70 135
Approximatelly Combustion Period h 5
Required Accumulation Tank Volume lt 1000 1500 2000 3000 4500 5500
Airborne Noise Level dB < 60 dB
MAIN DIMENSIONS
Boiler Width, W1 mm 600 650
Total Width with Cover Plates, W2 mm 650 700
Boiler Lenght, L1 mm 1060 1360 1635 1805
Boiler Height, H1 mm 1060 1210 1310 1360 1610
Total Height, H2 mm 1165 1315 1415 1465 1715
Stack Diameter, ØD1 (inner-outer) mm 125-130 146-150 176-180
Height of Stack Connection, H6 mm 715 865 955 1005 1225
Water Content lt 90 104 114 168 285 345
Approx. Empty Weight kg 385 425 450 600 860 960
Hot Water Outlet Connection
Diameter, ØD2 inch 1 1/2” 2’’
Position, H3 mm 1137 1287 1387 1437 1766
Position, L2 mm 590 890 1147 1317
Water Inlet Connection
Diameter, ØD2 inch 1 1/2” 2’’
Position, H4 mm 380 435
Safety Cooling Heat Exchanger 15 °C, 2 bar cold water
Diameter, ØD3 inch 3/4”
Position, H5 mm 975 1125 1225 1275 1525
Filling & Drain Connection
Diameter, ØD4 mm 1/2”
EMISSION RATES Flue Gas Temperature °C 145-165
Average Mass Flow Rate of Solid Pollutants (dust)
g/h 1,8 2,3 2,9 4,6 9 10
CO mg/m³ < 700
POWER CONSUMPTIONS
Average Electricity Consumption
in stand-by W 3
in full load, 100% 57 64 70 79 85 90
Technical Specifications