The Energy Performance of In-roof PV

4
viridian solar R Get it first - new briefings direct to your inbox (max one/month) subscribe Photovoltaic panels installed integrated with the roof covering will have less ventilation of the rear of the panel, run at a higher temperature and so deliver less electricity than the same panel installed above the roof with an air gap behind. But by how much? Energy yield from a solar pv module drops as the operating temperature rises, for example EN61215 tests found that the Clearline PV15 modules used in the study have a power-temperature coefficient of -0.509%/˚C. Figure 1 shows how the power output varies with operating temperature. ...continues However, it is not clear how much of the cooling comes from rear ventilation compared to heat losses from the top face. In any case, depending on the details of the roof build-up, integrated panels may be cooled by air movement in the batten space behind the tiles. More and more customers for solar PV are seeking products that enhance the aesthetics and resale value of their property. With greater interest in roof integrated systems, it is becoming ever more important that the solar industry can give credible advice on their performance. A review of the literature reveals little published work in this area. For this reason engineers at Viridian Solar and Enphase collaborated with researchers at Cambridge University to conduct an experiment to assess the temperature response of solar PV modules across a range of installation situations. An annual energy yield for each installation type was then predicted using climate data and the power-temperature coefficient. Method A test rig was constructed with five Clearline PV15 (240Wp) monocrystalline solar photovoltaic panels installed in a range of typical roofing situations. See figure 2b. Free-standing The panel was installed free-standing on a framework of aluminium angle. Consequently the panel rear was completely ventilated. Above tiled roof The panel was installed above a roof of Marley Modern interlocking concrete tiles in grey. The panel was fixed to a pair of P1000T Unistrut beams of 21mm x 41mm section. The beam was supported on four roof anchors. The gap between the panel (rear of laminate) and the tiles below ranged from 170mm to 190mm. See figure 3b overleaf. In tiled roof, cold roof construction The solar panel was integrated with a roof covering of concrete interlocking tiles using a VAT flashing kit. The roofing membrane below the tile battens was draped by 20mm between the rafters. See figure 4b. In tiled roof, warm roof construction The roof detailing was as for the cold roof , but with 100 mm of rigid polyurethane insulation board tightly fitted between rafters leaving a ventilation gap of 25mm below the top face of the rafter. See figure 5b. In shingle roof, without ventilation A layer of 18 mm thick plywood sheeting was applied over the rafters and the solar panel fixed directly to this, completely enclosing the rear of the panel. Black ashphalt shingles were applied to the roof and the panel weathered with a VAS flashing kit. See figure 6b. All panels were installed at a tilt angle of 35 degrees and facing due south. The walls of the structure were boarded to enclose the area behind the roof. The batten The performance penalty for roof integrated solar PV panels is almost certainly less than you thought it was. January 2014 Image: Elliotts Premier Roofing 0 50 100 150 200 250 300 0 10 20 30 40 50 60 70 Power Output (W) Panel Temperature (°C) Power - Temperature Curve Clearline PV15 Photovoltaic Module Irradiaon: 1,000 W/m 2 The Energy Performance of In-roof PV Figure 1 Power curve for modules used in the study

description

The performance penalty for roof integrated solar PV panels is almost certainly less than you thought it was.

Transcript of The Energy Performance of In-roof PV

Page 1: The Energy Performance of In-roof PV

viridians o l a r

R

Get it first - new briefings direct to your inbox (max one/month)subscribe

Photovoltaic panels installed integrated with the roof covering will have less ventilation of the rear of the panel, run at a higher temperature and so deliver less electricity than the same panel installed above the roof with an air gap behind. But by how much?

Energy yield from a solar pv module drops as the operating temperature rises, for example EN61215 tests found that the Clearline PV15 modules used in the study have a power-temperature coefficient of -0.509%/˚C. Figure 1 shows how the power output varies with operating temperature.

...continues

However, it is not clear how much of the cooling comes from rear ventilation compared to heat losses from the top face. In any case, depending on the details of the roof build-up, integrated panels may be cooled by air movement in the batten space behind the tiles.

More and more customers for solar PV are seeking products that enhance the aesthetics and resale value of their property. With greater interest in roof integrated

systems, it is becoming ever more important that the solar industry can give credible advice on their performance.

A review of the literature reveals little published work in this area. For this reason engineers at Viridian Solar and Enphase collaborated with researchers at Cambridge University to conduct an experiment to assess the temperature response of solar PV modules across a range of installation situations. An annual energy yield for each installation type was then predicted using climate data and the power-temperature coefficient.

Method

A test rig was constructed with five Clearline PV15 (240Wp) monocrystalline solar photovoltaic panels installed in a range of typical roofing situations. See figure 2b.

Free-standingThe panel was installed free-standing on a framework of aluminium angle. Consequently the panel rear was completely ventilated.

Above tiled roofThe panel was installed above a roof of Marley Modern interlocking concrete tiles in grey. The panel was fixed to a pair of P1000T Unistrut beams of 21mm x 41mm section. The beam was supported on four roof anchors. The gap between the panel (rear of laminate) and the tiles below ranged from 170mm to 190mm. See figure 3b overleaf.

In tiled roof, cold roof constructionThe solar panel was integrated with a roof covering of concrete interlocking tiles using a VAT flashing kit. The roofing membrane below the tile battens was draped by 20mm between the rafters. See figure 4b.

In tiled roof, warm roof constructionThe roof detailing was as for the cold roof , but with 100 mm of rigid polyurethane insulation board tightly fitted between rafters leaving a ventilation gap of 25mm below the top face of the rafter. See figure 5b.

In shingle roof, without ventilation A layer of 18 mm thick plywood sheeting was applied over the rafters and the solar panel fixed directly to this, completely enclosing the rear of the panel. Black ashphalt shingles were applied to the roof and the panel weathered with a VAS flashing kit. See figure 6b.

All panels were installed at a tilt angle of 35 degrees and facing due south. The walls of the structure were boarded to enclose the area behind the roof. The batten

The performance penalty for roof integrated solar PV panels is almost certainly less than you thought it was.

January 2014Image: Elliotts Premier Roofing

0

50

100

150

200

250

300

0 10 20 30 40 50 60 70

Pow

er O

utpu

t (W

)

Panel Temperature (°C)

Power - Temperature CurveClearline PV15 Photovoltaic Module

Irradiation: 1,000 W/m2

The Energy Performance of In-roof PV

Figure 1 Power curve for modules used in the study

Page 2: The Energy Performance of In-roof PV

viridians o l a r

R

Get it first - new briefings direct to your inbox (max one/month)subscribe

y = 0.0143xR² = 0.869

-2.0

0.0

2.0

4.0

6.0

8.0

10.0

12.0

14.0

16.0

18.0

200 400 600 800 1000 1200

Free Standing

Delta

T fr

om A

mbi

ent (

degr

ees C

)

Irradiance (W/m2)

y = 0.0326xR² = 0.9282

-4.0

-2.0

0.0

2.0

4.0

6.0

8.0

10.0

12.0

14.0

16.0

18.0

20.0

22.0

24.0

26.0

28.0

30.0

32.0

34.0

36.0

38.0

0 200 400 600 800 1000 1200

Integrated in Pitched Warm Roof

Delta

T fr

om A

mbi

ent (

degr

ees C

)

Irradiance (W/m2)

y = 0.036xR² = 0.9388

-4.0

-2.0

0.0

2.0

4.0

6.0

8.0

10.0

12.0

14.0

16.0

18.0

20.0

22.0

24.0

26.0

28.0

30.0

32.0

34.0

36.0

38.0

40.0

42.0

44.0

0 200 400 600 800 1000 1200

Integrated in Pitched Shingle Roof

Delta

T fr

om A

mbi

ent (

degr

ees C

)

Irradiance (W/m2)

y = 0.0333xR² = 0.9529

-4.0

-2.0

0.0

2.0

4.0

6.0

8.0

10.0

12.0

14.0

16.0

18.0

20.0

22.0

24.0

26.0

28.0

30.0

32.0

34.0

36.0

38.0

40.0

0 200 400 600 800 1000 1200

Integrated in Pitched Cold RoofDe

lta T

from

Am

bien

t (de

gree

s C)

Irradiance (W/m2)

y = 0.0245xR² = 0.9229

-4.0

-2.0

0.0

2.0

4.0

6.0

8.0

10.0

12.0

14.0

16.0

18.0

20.0

22.0

24.0

26.0

28.0

30.0

32.0

0 200 400 600 800 1000 1200

Above Pitched Roof

Delta

T fr

om A

mbi

ent (

degr

ees C

)

Irradiance (W/m2)

Tile

180m

mPV module

Rail

Roof anchor

Tile batten

Rafter

PV module

Flashing

Plywoodsheet

Rafter

Ashphalt shingle

Tile

25mm

PV module

Flashing

Ventilatedbatten space

Tile batten

Rafter

Membrane

25mm

PV module

Flashing

Ventilatedbatten space

Tile batten

Insulation

Membrane

Tile

25m

m

Cold Roof

Above Roof

WeatherStation

ShingleRoof

Warm Roof

FreeStanding

Figure 3Roof build up - above roof

Figure 4Roof build up - cold roof

Figure 5Roof build up - warm roof

Figure 6Roof build up - shingle roof

Figure 7 Derived temperature Curves

Figure 2 Test rig

Page 3: The Energy Performance of In-roof PV

viridians o l a r

R

Get it first - new briefings direct to your inbox (max one/month)subscribe

space behind the tiles was sealed with expanding foam at the free edges of the tiles at verge and ridge, but left open at eaves.

The modules were wired to an Enphase M215 micro-inverter ensuring the electrical independence of each module.

Thermocouple temperature sensors were fixed to the solar panels at top centre (front and rear) and to the rear centre of the module. A pyranometer recorded the level of irradiation and a weather station recorded the ambient temperature, rainfall and wind speed and direction.

Over a period of 106 days from September 2013 to December 2013 data was collected every minute to a data logger. 152,640 data points were collected for each module.

Analysis

The temperature of each solar module minus the ambient temperature was plotted against the irradiation to produce a characteristic temperature-irradiation curve for each installation method.

Data was sorted to include only periods where:

irradiation was stable (+/- 10% for the previous 10 minutes), to reduce heat capacity effects.the wind speed was less than 4 m/smodules were not partially shaded (power output was within a band of +/-20% of the average)

The resulting scatter plots for each installation type are presented in Figure 7 and show good fit to a linear curve with r-squared values between 0.93 and 0.95.

Figure 8 compares best fit lines for each installation type. Lines with steeper gradient reach higher temperatures as light levels increase. As expected,

...continues

the results show a progression from lower to higher gradient as the installation method reduces the level of back ventilation.

It is interesting to observe that the temperature response of the ‘cold roof’ and ‘warm roof’ installations were almost identical. It seems that the presence of the ventilated batten space behind the roof integrated panel offers a similar level of cooling irrespective of the presence of the insulation layer found in a warm roof construction.

Impact on Annual Energy Yield

From Figure 8, it can be seen that at 1,000W/m2 (corresponding to bright, direct sunshine on the modules) that the free standing module would be expected to be around 15˚C above ambient, the above-roof around 25˚C and the in-roof modules around 33˚.

If under these light conditions the ambient temperature was 25˚C then based on the declared power-temperature coefficient the free standing module would have an output of 221Wp, the above roof module would have output 209Wp and the in-roof panel 200Wp.

However, considering only performance at high irradiation exaggerates the performance differences because the sky is not always clear and the sun is not always directly above the modules. Figure 9 shows the distribution of irradiation levels incident on the plane of a solar panel on a south facing roof from a year of climate data collected as part of an earlier study into the energy performance of roof-integrated Clearline solar thermal panels. It is clear that the a solar module only experiences irradiation at such a high level for only a small part of the year.

To arrive at a more meaningful comparison between the energy performance of the different installations this climate data was used to predict the annual power yield for each of the five installation methods.

Num

ber o

f Hou

rs in

Yea

r

Irradiation on Plane of Solar Panel (W/m2)

Hours at Irradiation Level South Facing Surface at 35 degree Pitch Angle, Cambridge, UK

April 2006 - March 2007

0

100

200

300

400

500

600

700

800

0

5

10

15

20

25

30

35

40

45

0 200 400 600 800 1000 1200

Tem

pera

ture

(°C

abo

ve a

mbi

ent)

Irradiation (W/m )

Temperature Characteristic

2

Free-standing

AboveRoof

Warm Roof

ColdRoof

Shingle Roof

Figure 8 Temperature characteristic of different installationsFigure 9 Hours of sunlight by irradiation level, UK

Page 4: The Energy Performance of In-roof PV

viridians o l a r

R

Get it first - new briefings direct to your inbox (max one/month)subscribe

Viridian SolarAtlas Building, 68 Stirling Way,Papworth, Cambridge UK CB23 3GY

Tel +44 (0)1480 [email protected]

The module temperature above ambient for each point in the data set is calculated from the measured irradiation using the temperature characteristic curves derived earlier (figure 8). The module operating temperature is simply calculated by adding the measured ambient temperature at the same time interval. The module instantaneous power output is calculated from the measured irradiation level taking into account the module temperature coefficient and the calculated operating temperature.

The energy output for each three minute interval is calculated and summed for the whole year.

Results

Figure 10 shows the relative annual energy output from each of the five installation methods, with in-roof (cold roof) set to 100%.

It can be seen that for the climate file used, the free-standing PV module with open rear would generate 6.0% more energy than the in-roof module, while the installation above the pitched roof produces only 3.1% more.

There is an very small difference (0.1%) between the cold roof build up and the warm roof build up for in-roof installations, reflecting the very similar temperature responses of the two construction methods.

The in-roof module fixed to plywood sheeting would produce 1.1% less energy than the cold roof detail.

A belief that solar PV should always be installed with the highest possible level of shade-side ventilation is widespread in the industry. This study provides evidence to temper that position and enable solar professionals to offer advice to prospective customers based on evidence rather than opinion.

The modest reduction in enegy yield may be a trade off that many customers are willing to make in return for the enhanced aesthetics of integrated solar installations.

Annual Energy Yield(Cold roof integrated = 100%)

92%

94%

96%

98%

100%

102%

104%

106%

108%

110%

Free Standing Above Roof Cold Roof Warm Roof Shingle Roof

In-roof

Figure 10 Impact of installation on annual energy yield