The Benefits of Partial Discharge Monitoring
Ben Jones Site Electrical Services Superintendent 5th November, 2015
![Page 2: The benefits of pd monitoring Ben Jones](https://reader031.fdocuments.in/reader031/viewer/2022022409/58e7c3521a28ab0a228b4db5/html5/thumbnails/2.jpg)
Introduction
Ben Jones – Site Electrical Services Superintendent OneSteel Newcastle – A division of Arrium Mining & Materials Commenced working career on the Newcastle site for BHP in
1997 Have been responsible for the Newcastle High Voltage Network
since 2004
![Page 3: The benefits of pd monitoring Ben Jones](https://reader031.fdocuments.in/reader031/viewer/2022022409/58e7c3521a28ab0a228b4db5/html5/thumbnails/3.jpg)
2000 – New company Onesteel from the demerger of BHP - Steel 2005 – began exporting iron ore - Mining 2007 – acquired Smorgon Steel & Recycling business 2010 – purchase of Moly-Cop – Mining Consumables
2012 – changed name to ARRIUM Mining and Materials to reflect our diversity into Mining
![Page 4: The benefits of pd monitoring Ben Jones](https://reader031.fdocuments.in/reader031/viewer/2022022409/58e7c3521a28ab0a228b4db5/html5/thumbnails/4.jpg)
Partial Discharge (PD) is a localised dielectric breakdown of a small portion of the electrical insulation system under high voltage stress, which does not completely bridge the space between two conductors.
What is Partial Discharge (PD)?
PD usually begins within voids, cracks, or
inclusions within a solid dielectric, in bubbles within liquid dielectrics or with the ionisation of air around a high voltage conductor commonly referred to as Corona.
![Page 5: The benefits of pd monitoring Ben Jones](https://reader031.fdocuments.in/reader031/viewer/2022022409/58e7c3521a28ab0a228b4db5/html5/thumbnails/5.jpg)
Internal Discharge
PD spark occurs within the voids due to the dielectric constant of the void being lower than the
insulation. As the voltage across the void exceeds the Corona Inception Voltage PD occurs.
![Page 6: The benefits of pd monitoring Ben Jones](https://reader031.fdocuments.in/reader031/viewer/2022022409/58e7c3521a28ab0a228b4db5/html5/thumbnails/6.jpg)
Surface Discharge Corona Discharge is an electrical discharge brought on by the ionisation of air surrounding a High Voltage conductor due to the intensity of the magnetic field.
![Page 7: The benefits of pd monitoring Ben Jones](https://reader031.fdocuments.in/reader031/viewer/2022022409/58e7c3521a28ab0a228b4db5/html5/thumbnails/7.jpg)
Accelerated HV Breakdown Test
![Page 8: The benefits of pd monitoring Ben Jones](https://reader031.fdocuments.in/reader031/viewer/2022022409/58e7c3521a28ab0a228b4db5/html5/thumbnails/8.jpg)
What does PD do? Besides creating light, audible noise and ozone gas it can also: Generate ultra violet radiation which will degrade fibres and polymers such as
polypropylene and polyethylene. Ionises the air around conductors Create nitric oxide and in the presence of moisture nitric acid which oxidises
surrounding exposed metals. Cause progressive deterioration of insulating materials, ultimately leading to
electrical breakdown.
![Page 9: The benefits of pd monitoring Ben Jones](https://reader031.fdocuments.in/reader031/viewer/2022022409/58e7c3521a28ab0a228b4db5/html5/thumbnails/9.jpg)
Arrium Major HV Failure Data 2007>2010
• Average 3 failures per year • Costing on average $5M per
failure
![Page 10: The benefits of pd monitoring Ben Jones](https://reader031.fdocuments.in/reader031/viewer/2022022409/58e7c3521a28ab0a228b4db5/html5/thumbnails/10.jpg)
11kV High Voltage Failure of YSF6 Yorkshire Switch Board
![Page 11: The benefits of pd monitoring Ben Jones](https://reader031.fdocuments.in/reader031/viewer/2022022409/58e7c3521a28ab0a228b4db5/html5/thumbnails/11.jpg)
22kV High Voltage Termination Box Failure
![Page 12: The benefits of pd monitoring Ben Jones](https://reader031.fdocuments.in/reader031/viewer/2022022409/58e7c3521a28ab0a228b4db5/html5/thumbnails/12.jpg)
33kV High Voltage Sefton Termination Box Failure
![Page 13: The benefits of pd monitoring Ben Jones](https://reader031.fdocuments.in/reader031/viewer/2022022409/58e7c3521a28ab0a228b4db5/html5/thumbnails/13.jpg)
Each of the above failures resulted in days of limited or no production capacity. Costs quickly escalated in some cases to millions of dollars when lost production and repair costs were calculated.
Luckily none of the above events resulted in personal injury but we
must not forget the potential for such an occurrence to cause serious harm or even death.
Impact
![Page 14: The benefits of pd monitoring Ben Jones](https://reader031.fdocuments.in/reader031/viewer/2022022409/58e7c3521a28ab0a228b4db5/html5/thumbnails/14.jpg)
Locating Partial Discharge
The emissions generated by Partial Discharge allows it to be to be located by the use of a sensitive listening device such as the UltraTEV Plus.
This instrument is used to test for Transient Earth Voltages (TEV) and Ultrasonic signals emanating from discharge occurring within the High Voltage asset.
PD can be detected reliably in HV systems >4.1kV This method of condition monitoring can be completed safely with
the equipment energised and without the need to remove any covers exposing potential shock or arc fault hazards to technicians.
![Page 15: The benefits of pd monitoring Ben Jones](https://reader031.fdocuments.in/reader031/viewer/2022022409/58e7c3521a28ab0a228b4db5/html5/thumbnails/15.jpg)
Partial Discharge Severity
TEV’s are induced voltage spikes on the surfaces of the surrounding metalwork of high voltage assets. The resulting readings are directly proportional to the condition of the insulation.
For Ultrasonic detection dB is
used to determine severity.
![Page 16: The benefits of pd monitoring Ben Jones](https://reader031.fdocuments.in/reader031/viewer/2022022409/58e7c3521a28ab0a228b4db5/html5/thumbnails/16.jpg)
Successful PD Detections • PD detected using contact
probe on the external surface of the 33kV
termination box.
• Opening box found a large amount of condensation and formulation of white
powder on the termination creepage extension sheds.
![Page 17: The benefits of pd monitoring Ben Jones](https://reader031.fdocuments.in/reader031/viewer/2022022409/58e7c3521a28ab0a228b4db5/html5/thumbnails/17.jpg)
Successful PD Detections
• PD detected using contact probe on the external surface of the 33kV termination box.
• Opening box found
breakdown of the termination kits where insufficient air gap between conductors was maintained.
![Page 18: The benefits of pd monitoring Ben Jones](https://reader031.fdocuments.in/reader031/viewer/2022022409/58e7c3521a28ab0a228b4db5/html5/thumbnails/18.jpg)
• PD detected using the extension microphone in
and around an 11kV circuit breaker.
• Discharge was occurring
between two covers protecting the live
terminations underneath.
Successful PD Detections
![Page 19: The benefits of pd monitoring Ben Jones](https://reader031.fdocuments.in/reader031/viewer/2022022409/58e7c3521a28ab0a228b4db5/html5/thumbnails/19.jpg)
• PD detected using the extension microphone in and around an 11kV circuit breaker.
• Discharge was occurring between the connecting cluster and outer insulating spouts.
Successful PD Detections
![Page 20: The benefits of pd monitoring Ben Jones](https://reader031.fdocuments.in/reader031/viewer/2022022409/58e7c3521a28ab0a228b4db5/html5/thumbnails/20.jpg)
Successful PD Detections PD detected using the
ultrasonic probe attached to the outside of the 11kV
termination box enclosure
![Page 21: The benefits of pd monitoring Ben Jones](https://reader031.fdocuments.in/reader031/viewer/2022022409/58e7c3521a28ab0a228b4db5/html5/thumbnails/21.jpg)
Successful PD Detections PD detected using the ultrasonic
probe attached to the outside 11kV termination box enclosure.
![Page 22: The benefits of pd monitoring Ben Jones](https://reader031.fdocuments.in/reader031/viewer/2022022409/58e7c3521a28ab0a228b4db5/html5/thumbnails/22.jpg)
• PD detected using contact probe on the external surface of the 33kV termination box.
• Opening box found
breakdown of the termination kits where insufficient air gap between conductors was maintained.
Successful PD Detections