The Application and Costs of Lighting Controls...Automatic Lighting Shutoff –“Buildings… shall...
Transcript of The Application and Costs of Lighting Controls...Automatic Lighting Shutoff –“Buildings… shall...
![Page 1: The Application and Costs of Lighting Controls...Automatic Lighting Shutoff –“Buildings… shall be equipped with automatic control device to shut off lighting… based on either:”](https://reader033.fdocuments.in/reader033/viewer/2022060807/608c299bd7cc741d19018e51/html5/thumbnails/1.jpg)
The Application and Costs
of Lighting Controls
Efficiency Vermont
Better Buildings by Design Conference
February 6, 2014
![Page 2: The Application and Costs of Lighting Controls...Automatic Lighting Shutoff –“Buildings… shall be equipped with automatic control device to shut off lighting… based on either:”](https://reader033.fdocuments.in/reader033/viewer/2022060807/608c299bd7cc741d19018e51/html5/thumbnails/2.jpg)
Acknowledgements
Thanks to Green Light New York for funding the development
of this course material
Thanks to the following organizations and companies for
contributing material
2
www.greenlightny.org
![Page 3: The Application and Costs of Lighting Controls...Automatic Lighting Shutoff –“Buildings… shall be equipped with automatic control device to shut off lighting… based on either:”](https://reader033.fdocuments.in/reader033/viewer/2022060807/608c299bd7cc741d19018e51/html5/thumbnails/3.jpg)
Three Different “Levels” of Control Systems
3
1 • Stand Alone Controls
2 • Centralized Panel Controls
3 • Fully Integrated Networked,
Addressable Controls
![Page 4: The Application and Costs of Lighting Controls...Automatic Lighting Shutoff –“Buildings… shall be equipped with automatic control device to shut off lighting… based on either:”](https://reader033.fdocuments.in/reader033/viewer/2022060807/608c299bd7cc741d19018e51/html5/thumbnails/4.jpg)
Three Different “Levels” of Control Systems
4
1 • Stand Alone Controls
2 • Centralized Panel Controls
3 • Fully Integrated Networked,
Addressable Controls
How do these levels
correlate to:
• Costs?
• Savings?
• Complexity?
• Functionality?
• Occupant Satisfaction?
• Marketability / Rents?
![Page 5: The Application and Costs of Lighting Controls...Automatic Lighting Shutoff –“Buildings… shall be equipped with automatic control device to shut off lighting… based on either:”](https://reader033.fdocuments.in/reader033/viewer/2022060807/608c299bd7cc741d19018e51/html5/thumbnails/5.jpg)
Line Voltage Wall Switch
Two Zone or “Bi-Level” Occupancy/Vacancy Sensor
Stand-Alone Photocell w/ Relay/Power Pack
Stand-Alone Occupancy Sensor w/
Relay/Power Pack
Line Voltage Occupancy/Vacancy Sensor
Low-Voltage Relay-based
Ligh3ng Co n trol Panel
Power Pack
Low-Voltage
Controls
Light Fixtures
Low-Voltage
Wiring
Low-Voltage
Wiring
Line-Voltage
Wiring
Low-Voltage Relay-based
Ligh3ng Co n trol Panel
Power Pack
Low-Voltage
Controls
Light Fixtures
Low-Voltage
Wiring
Low-Voltage
Wiring
Line-Voltage
Wiring
Stand-Alone Controls
![Page 6: The Application and Costs of Lighting Controls...Automatic Lighting Shutoff –“Buildings… shall be equipped with automatic control device to shut off lighting… based on either:”](https://reader033.fdocuments.in/reader033/viewer/2022060807/608c299bd7cc741d19018e51/html5/thumbnails/6.jpg)
Stand-Alone Controls
Pros/Cons
Pros:
• May be less expensive
• Familiar wiring methods
Cons:
• Less Flexible
• Complicated to combine multiple control strategies
• Less energy savings
![Page 7: The Application and Costs of Lighting Controls...Automatic Lighting Shutoff –“Buildings… shall be equipped with automatic control device to shut off lighting… based on either:”](https://reader033.fdocuments.in/reader033/viewer/2022060807/608c299bd7cc741d19018e51/html5/thumbnails/7.jpg)
Low- Voltage
Wiring
Low- Voltage
Wiring
Line- Voltage
Wiring
Low-Voltage Relay-based Lighting
Control Panel
Power
Pack
Low-Voltage Relay-based
Ligh3ng Co n trol Panel
Power Pack
Low-Voltage
Controls
Light Fixtures
Low-Voltage
Wiring
Low-Voltage
Wiring
Line-Voltage
Wiring
Low-Voltage Relay-based
Ligh3ng Co n trol Panel
Power Pack
Low-Voltage
Controls
Light Fixtures
Low-Voltage
Wiring
Low-Voltage
Wiring
Line-Voltage
Wiring
Low-Voltage Relay-based
Ligh3ng Co n trol Panel
Power Pack
Low-Voltage
Controls
Light Fixtures
Low-Voltage
Wiring
Low-Voltage
Wiring
Line-Voltage
Wiring
Low-Voltage Relay-based
Ligh3ng Co n trol Panel
Power Pack
Low-Voltage
Controls
Light Fixtures
Low-Voltage
Wiring
Low-Voltage
Wiring
Line-Voltage
Wiring
Low-Voltage Relay-based
Ligh3ng Co n trol Panel
Power Pack
Low-Voltage
Controls
Light Fixtures
Low-Voltage
Wiring
Low-Voltage
Wiring
Line-Voltage
Wiring
Low-Voltage Relay-based
Ligh3ng Co n trol Panel
Power Pack
Low-Voltage
Controls
Light Fixtures
Low-Voltage
Wiring
Low-Voltage
Wiring
Line-Voltage
Wiring
Low-Voltage Relay-based
Ligh3ng Co n trol Panel
Power Pack
Low-Voltage
Controls
Light Fixtures
Low-Voltage
Wiring
Low-Voltage
Wiring
Line-Voltage
Wiring
Centralized Panel Controls
![Page 8: The Application and Costs of Lighting Controls...Automatic Lighting Shutoff –“Buildings… shall be equipped with automatic control device to shut off lighting… based on either:”](https://reader033.fdocuments.in/reader033/viewer/2022060807/608c299bd7cc741d19018e51/html5/thumbnails/8.jpg)
Centralized Panel
Controls Pros/Cons
Pros:
• More flexible
• Programming & monitoring from a centralized location
• Can be integrated into BAS systems (security, HVAC)
Cons:
• Requires low-voltage wiring to be installed
• Less familiar wiring methods may result in higher bid costs
• Limitations on zoning & no. of control strategies
![Page 9: The Application and Costs of Lighting Controls...Automatic Lighting Shutoff –“Buildings… shall be equipped with automatic control device to shut off lighting… based on either:”](https://reader033.fdocuments.in/reader033/viewer/2022060807/608c299bd7cc741d19018e51/html5/thumbnails/9.jpg)
Dali Gateway/Controller
Ethernet
Network
5 Core Electric Cabling
Active-Neutral-Earth-D1-D2
(free topology) Switch Plate
(via group/scene controller)
DALI Power Supply
DALI Ballast
Fluorescent Lamp
DALI Ballast
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
Fully-Integrated Addressable Control System
(Wired)
![Page 10: The Application and Costs of Lighting Controls...Automatic Lighting Shutoff –“Buildings… shall be equipped with automatic control device to shut off lighting… based on either:”](https://reader033.fdocuments.in/reader033/viewer/2022060807/608c299bd7cc741d19018e51/html5/thumbnails/10.jpg)
To more devices
Control Device
Light Fixtures
Branch Circuit Wire
Control Wiring
To another room
To panel
Conventional Addressable
To panel
Addressable systems can require up to 60%
less wiring
![Page 11: The Application and Costs of Lighting Controls...Automatic Lighting Shutoff –“Buildings… shall be equipped with automatic control device to shut off lighting… based on either:”](https://reader033.fdocuments.in/reader033/viewer/2022060807/608c299bd7cc741d19018e51/html5/thumbnails/11.jpg)
Space/ Zone Control
Components
System Control
ComponentsProducts
Zone 1 Additional zones
Wireless AreaController
Wireless Adapter(as required)
Software System Controller
Additional areas & buildings
Fully-Integrated Addressable Control System
(Wireless)
![Page 12: The Application and Costs of Lighting Controls...Automatic Lighting Shutoff –“Buildings… shall be equipped with automatic control device to shut off lighting… based on either:”](https://reader033.fdocuments.in/reader033/viewer/2022060807/608c299bd7cc741d19018e51/html5/thumbnails/12.jpg)
Cons:
• May have higher initial cost
• Proprietary products, trademarked DALI
• May require low-voltage wiring to be
installed (wired)
• Less familiar wiring methods may result in higher bid costs
• May require a computer server
• Commissioning can be more complicated and costly
Pros:
• More flexibility > potential for more energy savings
• Programming and monitoring from a centralized location
• Allows for multiple control strategies
• Can be easily reconfigured, re-zoned, for changes in space layout and tenants without requiring rewiring
Fully-Integrated Addressable Control System
![Page 13: The Application and Costs of Lighting Controls...Automatic Lighting Shutoff –“Buildings… shall be equipped with automatic control device to shut off lighting… based on either:”](https://reader033.fdocuments.in/reader033/viewer/2022060807/608c299bd7cc741d19018e51/html5/thumbnails/13.jpg)
Applying different “levels” of
controls to an example Office
Space
![Page 14: The Application and Costs of Lighting Controls...Automatic Lighting Shutoff –“Buildings… shall be equipped with automatic control device to shut off lighting… based on either:”](https://reader033.fdocuments.in/reader033/viewer/2022060807/608c299bd7cc741d19018e51/html5/thumbnails/14.jpg)
Review of Code Lighting Control Requirements
per IECC 2009
Automatic Lighting Shutoff
– “Buildings… shall be equipped with automatic control device to
shut off lighting… based on either:”
• Scheduled basis using time of day
• Occupant Sensor
• Signal from control or alarm system that indicates area is
unoccupied
Daylight Zone Control
– Daylight zones shall be provided with individual controls that
control the lights independent of general area lighting
14
![Page 15: The Application and Costs of Lighting Controls...Automatic Lighting Shutoff –“Buildings… shall be equipped with automatic control device to shut off lighting… based on either:”](https://reader033.fdocuments.in/reader033/viewer/2022060807/608c299bd7cc741d19018e51/html5/thumbnails/15.jpg)
2-Lamp T5 Troffers on 8’x10’ spacing
Four Private Offices
One Open Office
Vertical Glazing on East & North
![Page 16: The Application and Costs of Lighting Controls...Automatic Lighting Shutoff –“Buildings… shall be equipped with automatic control device to shut off lighting… based on either:”](https://reader033.fdocuments.in/reader033/viewer/2022060807/608c299bd7cc741d19018e51/html5/thumbnails/16.jpg)
First Approach Use Stand-alone
Controls to Meet the Code
Minimum
![Page 17: The Application and Costs of Lighting Controls...Automatic Lighting Shutoff –“Buildings… shall be equipped with automatic control device to shut off lighting… based on either:”](https://reader033.fdocuments.in/reader033/viewer/2022060807/608c299bd7cc741d19018e51/html5/thumbnails/17.jpg)
Open Office Control Strategies
• Timeclock scheduling (all zones)
Timeclock Panel
SSS
![Page 18: The Application and Costs of Lighting Controls...Automatic Lighting Shutoff –“Buildings… shall be equipped with automatic control device to shut off lighting… based on either:”](https://reader033.fdocuments.in/reader033/viewer/2022060807/608c299bd7cc741d19018e51/html5/thumbnails/18.jpg)
Open Office Control Strategies
• Timeclock scheduling (all zones)
• Manual switch for daylight zone luminaires
Manual Switch for
Daylight Zone
Luminaires
Timeclock Panel
SSS
S
![Page 19: The Application and Costs of Lighting Controls...Automatic Lighting Shutoff –“Buildings… shall be equipped with automatic control device to shut off lighting… based on either:”](https://reader033.fdocuments.in/reader033/viewer/2022060807/608c299bd7cc741d19018e51/html5/thumbnails/19.jpg)
Manual Switch for
Daylight Zone
Luminaires
Timeclock Panel
SSS
S
Open Office Control Strategies
• Timeclock scheduling (all zones)
• Manual switch for daylight zone luminaires
Private Office Control Strategies
• Line Voltage Vacancy Sensors
VS VS VS VS
Vacancy Sensor
![Page 20: The Application and Costs of Lighting Controls...Automatic Lighting Shutoff –“Buildings… shall be equipped with automatic control device to shut off lighting… based on either:”](https://reader033.fdocuments.in/reader033/viewer/2022060807/608c299bd7cc741d19018e51/html5/thumbnails/20.jpg)
Space Control Strategy
Controlled Fixture(s) % Savings
Total Project % Savings
Open Timeclock Scheduling Control
15% 14%
Open Daylight Zone Luminaires Switch
0% 0%
Private Vacancy Sensors 30% 2%
Total Cumulative Lighting Control
Savings: 16%
Savings Analysis using Stand-Alone Controls
![Page 21: The Application and Costs of Lighting Controls...Automatic Lighting Shutoff –“Buildings… shall be equipped with automatic control device to shut off lighting… based on either:”](https://reader033.fdocuments.in/reader033/viewer/2022060807/608c299bd7cc741d19018e51/html5/thumbnails/21.jpg)
What are the Pros & Cons
of this approach?
• Functionality
• Cost
• Wiring
• Energy Savings
• Flexibility
• Occupant Satisfaction
• Marketability & Rents
Manual Switch for
Daylight Zone
Luminaires
SSS
S
VS VS VS VS
Vacancy Sensor
Timeclock Panel
![Page 22: The Application and Costs of Lighting Controls...Automatic Lighting Shutoff –“Buildings… shall be equipped with automatic control device to shut off lighting… based on either:”](https://reader033.fdocuments.in/reader033/viewer/2022060807/608c299bd7cc741d19018e51/html5/thumbnails/22.jpg)
Second Approach Centralized
Relay Panel with Additional Control
Strategies
![Page 23: The Application and Costs of Lighting Controls...Automatic Lighting Shutoff –“Buildings… shall be equipped with automatic control device to shut off lighting… based on either:”](https://reader033.fdocuments.in/reader033/viewer/2022060807/608c299bd7cc741d19018e51/html5/thumbnails/23.jpg)
Low- Voltage
Wiring
Low- Voltage
Wiring
Line- Voltage
Wiring
Low-Voltage Relay-based Lighting
Control Panel
Power
Pack
Low-Voltage Relay-based
Ligh3ng Co n trol Panel
Power Pack
Low-Voltage
Controls
Light Fixtures
Low-Voltage
Wiring
Low-Voltage
Wiring
Line-Voltage
Wiring
Low-Voltage Relay-based
Ligh3ng Co n trol Panel
Power Pack
Low-Voltage
Controls
Light Fixtures
Low-Voltage
Wiring
Low-Voltage
Wiring
Line-Voltage
Wiring
Low-Voltage Relay-based
Ligh3ng Co n trol Panel
Power Pack
Low-Voltage
Controls
Light Fixtures
Low-Voltage
Wiring
Low-Voltage
Wiring
Line-Voltage
Wiring
Low-Voltage Relay-based
Ligh3ng Co n trol Panel
Power Pack
Low-Voltage
Controls
Light Fixtures
Low-Voltage
Wiring
Low-Voltage
Wiring
Line-Voltage
Wiring
Low-Voltage Relay-based
Ligh3ng Co n trol Panel
Power Pack
Low-Voltage
Controls
Light Fixtures
Low-Voltage
Wiring
Low-Voltage
Wiring
Line-Voltage
Wiring
Low-Voltage Relay-based
Ligh3ng Co n trol Panel
Power Pack
Low-Voltage
Controls
Light Fixtures
Low-Voltage
Wiring
Low-Voltage
Wiring
Line-Voltage
Wiring
Low-Voltage Relay-based
Ligh3ng Co n trol Panel
Power Pack
Low-Voltage
Controls
Light Fixtures
Low-Voltage
Wiring
Low-Voltage
Wiring
Line-Voltage
Wiring
Centralized Panel Controls
![Page 24: The Application and Costs of Lighting Controls...Automatic Lighting Shutoff –“Buildings… shall be equipped with automatic control device to shut off lighting… based on either:”](https://reader033.fdocuments.in/reader033/viewer/2022060807/608c299bd7cc741d19018e51/html5/thumbnails/24.jpg)
SSS
Low-Voltage Lighting Control Panel
Open Office Control Strategies:
• Timeclock scheduling by day
![Page 25: The Application and Costs of Lighting Controls...Automatic Lighting Shutoff –“Buildings… shall be equipped with automatic control device to shut off lighting… based on either:”](https://reader033.fdocuments.in/reader033/viewer/2022060807/608c299bd7cc741d19018e51/html5/thumbnails/25.jpg)
SSS
Low-Voltage Lighting Control Panel
O
S
O
S
Open Office Control Strategies:
• Timeclock scheduling by day
• Occupancy control at night
![Page 26: The Application and Costs of Lighting Controls...Automatic Lighting Shutoff –“Buildings… shall be equipped with automatic control device to shut off lighting… based on either:”](https://reader033.fdocuments.in/reader033/viewer/2022060807/608c299bd7cc741d19018e51/html5/thumbnails/26.jpg)
SSS
Low-Voltage Lighting Control Panel
O
S
O
S
Daylight
Zone 2
Daylight
Zone 1
Dual-Zone Daylightin
g Photocell to control first two
rows
P
C
Open Office Control Strategies:
• Timeclock scheduling by day
• Occupancy control at night
• Daylight responsive dimming for daylight zone luminaires (2 zones)
![Page 27: The Application and Costs of Lighting Controls...Automatic Lighting Shutoff –“Buildings… shall be equipped with automatic control device to shut off lighting… based on either:”](https://reader033.fdocuments.in/reader033/viewer/2022060807/608c299bd7cc741d19018e51/html5/thumbnails/27.jpg)
Open Office Control Strategies:
• Timeclock scheduling by day
• Occupancy control at night
• Daylight responsive dimming for daylight zone luminaires (2 zones)
Private Office Control Strategies:
• Vacancy Sensors with bi-level switching
SSS
Low-Voltage Lighting Control Panel
O
S
O
S
Daylight
Zone 2
Daylight
Zone 1
Dual-Zone Daylightin
g Photocell to control first two
rows
P
C
VS VS VS VS Bi-Level Vacancy Sensor
![Page 28: The Application and Costs of Lighting Controls...Automatic Lighting Shutoff –“Buildings… shall be equipped with automatic control device to shut off lighting… based on either:”](https://reader033.fdocuments.in/reader033/viewer/2022060807/608c299bd7cc741d19018e51/html5/thumbnails/28.jpg)
Space Control Strategy
Controlled Fixture(s) % Savings
Total Project % Savings
Open Timeclock by Day, Occupancy Control at night
21% 19%
Open Daylight Responsive Dimming for Daylight Zone Luminaires
23% 8%
Private Vacancy Sensors 30% 2%
Private Bi-Level Switching 9% 1%
Total Cumulative Lighting Control
Savings: 30%
Centralized Panel w Additional Control
Strategies Savings Analysis
![Page 29: The Application and Costs of Lighting Controls...Automatic Lighting Shutoff –“Buildings… shall be equipped with automatic control device to shut off lighting… based on either:”](https://reader033.fdocuments.in/reader033/viewer/2022060807/608c299bd7cc741d19018e51/html5/thumbnails/29.jpg)
What are the Pros & Cons
of this approach?
• Functionality
• Cost
• Wiring
• Energy Savings
• Flexibility
• Occupant Satisfaction
• Marketability & Rents SSS
Low-Voltage Lighting Control Panel
O
S
O
S
Daylight
Zone 2
Daylight
Zone 1
Dual-Zone Daylightin
g Photocell to control first two
rows
P
C
VS VS VS VS Bi-Level Vacancy Sensor
![Page 30: The Application and Costs of Lighting Controls...Automatic Lighting Shutoff –“Buildings… shall be equipped with automatic control device to shut off lighting… based on either:”](https://reader033.fdocuments.in/reader033/viewer/2022060807/608c299bd7cc741d19018e51/html5/thumbnails/30.jpg)
Third Approach Fully
Addressable, Wireless with
all Cost-effective
Control Strategies
![Page 31: The Application and Costs of Lighting Controls...Automatic Lighting Shutoff –“Buildings… shall be equipped with automatic control device to shut off lighting… based on either:”](https://reader033.fdocuments.in/reader033/viewer/2022060807/608c299bd7cc741d19018e51/html5/thumbnails/31.jpg)
Open Office Control Strategies:
• Timeclock scheduling by day
Wireless Area
Controller
CAT5
System Controller & Software
![Page 32: The Application and Costs of Lighting Controls...Automatic Lighting Shutoff –“Buildings… shall be equipped with automatic control device to shut off lighting… based on either:”](https://reader033.fdocuments.in/reader033/viewer/2022060807/608c299bd7cc741d19018e51/html5/thumbnails/32.jpg)
Open Office Control Strategies:
• Timeclock scheduling by day
• Occupancy control at night
Wireless Area
Controller
CAT5
System Controller & Software
Low-Voltage Relay-based
Ligh3ng Co n trol Panel
Power Pack
Low-Voltage
Controls
Light Fixtures
Low-Voltage
Wiring
Low-Voltage
Wiring
Line-Voltage
Wiring
SS
Wireless Override Switches
O
S
O
S Wireless Occupancy Sensor
![Page 33: The Application and Costs of Lighting Controls...Automatic Lighting Shutoff –“Buildings… shall be equipped with automatic control device to shut off lighting… based on either:”](https://reader033.fdocuments.in/reader033/viewer/2022060807/608c299bd7cc741d19018e51/html5/thumbnails/33.jpg)
Open Office Control Strategies:
• Timeclock scheduling by day
• Occupancy control at night
• Daylight responsive dimming for daylight zone luminaires
Wireless Area
Controller
CAT5
System Controller & Software
Low-Voltage Relay-based
Ligh3ng Co n trol Panel
Power Pack
Low-Voltage
Controls
Light Fixtures
Low-Voltage
Wiring
Low-Voltage
Wiring
Line-Voltage
Wiring
SS
Wireless Override Switches
O
S
O
S Wireless Occupancy Sensor
Wireless Photocell
P
C
Daylight
Zone 2
Daylight
Zone 1
![Page 34: The Application and Costs of Lighting Controls...Automatic Lighting Shutoff –“Buildings… shall be equipped with automatic control device to shut off lighting… based on either:”](https://reader033.fdocuments.in/reader033/viewer/2022060807/608c299bd7cc741d19018e51/html5/thumbnails/34.jpg)
Open Office Control Strategies:
• Timeclock scheduling by day
• Occupancy control at night
• Daylight responsive dimming for daylight zone luminaires
• Task Tuning
Wireless Area
Controller
CAT5
System Controller & Software
Low-Voltage Relay-based
Ligh3ng Co n trol Panel
Power Pack
Low-Voltage
Controls
Light Fixtures
Low-Voltage
Wiring
Low-Voltage
Wiring
Line-Voltage
Wiring
SS
Wireless Override Switches
O
S
O
S Wireless Occupancy Sensor
Wireless Photocell
P
C
Daylight
Zone 2
Daylight
Zone 1
![Page 35: The Application and Costs of Lighting Controls...Automatic Lighting Shutoff –“Buildings… shall be equipped with automatic control device to shut off lighting… based on either:”](https://reader033.fdocuments.in/reader033/viewer/2022060807/608c299bd7cc741d19018e51/html5/thumbnails/35.jpg)
Private Office Control Strategies:
• Vacancy sensors Wireless Area
Controller
CAT5
System Controller & Software
Low-Voltage Relay-based
Ligh3ng Co n trol Panel
Power Pack
Low-Voltage
Controls
Light Fixtures
Low-Voltage
Wiring
Low-Voltage
Wiring
Line-Voltage
Wiring
SS
Wireless Override Switches
O
S
O
S Wireless Occupancy Sensor
Wireless Photocell
P
C
Daylight
Zone 2
Daylight
Zone 1
Wireless Occupancy Sensor and Photocell
O
S
O
S
O
S
O
S
![Page 36: The Application and Costs of Lighting Controls...Automatic Lighting Shutoff –“Buildings… shall be equipped with automatic control device to shut off lighting… based on either:”](https://reader033.fdocuments.in/reader033/viewer/2022060807/608c299bd7cc741d19018e51/html5/thumbnails/36.jpg)
Private Office Control Strategies:
• Vacancy sensors
• Personal Dimming
Wireless Area
Controller
CAT5
System Controller & Software
Low-Voltage Relay-based
Ligh3ng Co n trol Panel
Power Pack
Low-Voltage
Controls
Light Fixtures
Low-Voltage
Wiring
Low-Voltage
Wiring
Line-Voltage
Wiring
SS
Wireless Override Switches
O
S
O
S Wireless Occupancy Sensor
Wireless Photocell
P
C
Daylight
Zone 2
Daylight
Zone 1
Wireless Occupancy Sensor and Photocell
O
S
O
S
O
S
O
S Low-Voltage Relay-based
Ligh3ng Co n trol Panel
Power Pack
Low-Voltage
Controls
Light Fixtures
Low-Voltage
Wiring
Low-Voltage
Wiring
Line-Voltage
Wiring
Wireless Dimming
D D D D
![Page 37: The Application and Costs of Lighting Controls...Automatic Lighting Shutoff –“Buildings… shall be equipped with automatic control device to shut off lighting… based on either:”](https://reader033.fdocuments.in/reader033/viewer/2022060807/608c299bd7cc741d19018e51/html5/thumbnails/37.jpg)
Private Office Control Strategies:
• Vacancy sensors
• Personal Dimming
• Task Tuning
Wireless Area
Controller
CAT5
System Controller & Software
Low-Voltage Relay-based
Ligh3ng Co n trol Panel
Power Pack
Low-Voltage
Controls
Light Fixtures
Low-Voltage
Wiring
Low-Voltage
Wiring
Line-Voltage
Wiring
SS
O
S
O
S Wireless Occupancy Sensor
Wireless Photocell
P
C
Daylight
Zone 2
Daylight
Zone 1
Wireless Occupancy Sensor and Photocell
O
S
O
S
O
S
O
S Low-Voltage Relay-based
Ligh3ng Co n trol Panel
Power Pack
Low-Voltage
Controls
Light Fixtures
Low-Voltage
Wiring
Low-Voltage
Wiring
Line-Voltage
Wiring
Wireless Dimming
D D D D
Wireless Override Switches
P
C
P
C
P
C
P
C
![Page 38: The Application and Costs of Lighting Controls...Automatic Lighting Shutoff –“Buildings… shall be equipped with automatic control device to shut off lighting… based on either:”](https://reader033.fdocuments.in/reader033/viewer/2022060807/608c299bd7cc741d19018e51/html5/thumbnails/38.jpg)
Space Control Strategy
Controlled Fixture(s) % Savings
Total Project % Savings
Open Office
High-end trim dimming 10% 9%
Open Office
Timeclock Scheduling Control during day, Occupancy Control at night
19% 17%
Open Office
Daylight Responsive Dimming for first two rows of luminaires near glazing
8% 7%
Private Office
High-end trim dimming 10% 1%
Private Office
Vacancy Sensors 27% 2%
Private Office
Personal dimming 10% 1% Total Cumulative Lighting Control
Savings: 37%
Fully Addressable Wireless w all Cost-
Effective Control Strategies Savings Analysis
![Page 39: The Application and Costs of Lighting Controls...Automatic Lighting Shutoff –“Buildings… shall be equipped with automatic control device to shut off lighting… based on either:”](https://reader033.fdocuments.in/reader033/viewer/2022060807/608c299bd7cc741d19018e51/html5/thumbnails/39.jpg)
What are the Pros & Cons
of this approach?
• Functionality
• Cost
• Wiring
• Energy Savings
• Flexibility
• Occupant Satisfaction
• Marketability & Rents
Wireless Area
Controller
CAT5
System Controller & Software
Low-Voltage Relay-based
Ligh3ng Co n trol Panel
Power Pack
Low-Voltage
Controls
Light Fixtures
Low-Voltage
Wiring
Low-Voltage
Wiring
Line-Voltage
Wiring
SS
O
S
O
S Wireless Occupancy Sensor
Wireless Photocell
P
C
Daylight
Zone 2
Daylight
Zone 1
Wireless Occupancy Sensor and Photocell
O
S
O
S
O
S
O
S Low-Voltage Relay-based
Ligh3ng Co n trol Panel
Power Pack
Low-Voltage
Controls
Light Fixtures
Low-Voltage
Wiring
Low-Voltage
Wiring
Line-Voltage
Wiring
Wireless Dimming
D D D D
Wireless Override Switches
P
C
P
C
P
C
P
C
![Page 40: The Application and Costs of Lighting Controls...Automatic Lighting Shutoff –“Buildings… shall be equipped with automatic control device to shut off lighting… based on either:”](https://reader033.fdocuments.in/reader033/viewer/2022060807/608c299bd7cc741d19018e51/html5/thumbnails/40.jpg)
Should more advanced
controls cost more?
![Page 41: The Application and Costs of Lighting Controls...Automatic Lighting Shutoff –“Buildings… shall be equipped with automatic control device to shut off lighting… based on either:”](https://reader033.fdocuments.in/reader033/viewer/2022060807/608c299bd7cc741d19018e51/html5/thumbnails/41.jpg)
• Life Cycle Cost Evaluation of Multiple Lighting Control Strategies
• Compares different levels of lighting control upgrades in Boston & Los Angeles
• Do or should Advanced Lighting Controls cost more?
• Do Advanced Lighting Controls save more?
Clanton Lighting Control Study
![Page 42: The Application and Costs of Lighting Controls...Automatic Lighting Shutoff –“Buildings… shall be equipped with automatic control device to shut off lighting… based on either:”](https://reader033.fdocuments.in/reader033/viewer/2022060807/608c299bd7cc741d19018e51/html5/thumbnails/42.jpg)
Analyzed 6 different levels of Lighting Control Upgrades
Networked Addressable
(6) Wireless Full Dimming
(5) Wireless Partial Dimming
(4) Addressable Ballasts
Central Panel
(3) Dimming Panel
(2) Relay Panel
Stand-Alone
(1) Localized control
![Page 43: The Application and Costs of Lighting Controls...Automatic Lighting Shutoff –“Buildings… shall be equipped with automatic control device to shut off lighting… based on either:”](https://reader033.fdocuments.in/reader033/viewer/2022060807/608c299bd7cc741d19018e51/html5/thumbnails/43.jpg)
Baseline Building
![Page 44: The Application and Costs of Lighting Controls...Automatic Lighting Shutoff –“Buildings… shall be equipped with automatic control device to shut off lighting… based on either:”](https://reader033.fdocuments.in/reader033/viewer/2022060807/608c299bd7cc741d19018e51/html5/thumbnails/44.jpg)
How much energy did each system save?
14% Below Baselin
e
20% Below Baselin
e
30% Below Baselin
e 47% Below Baselin
e
31% Below Baselin
e 49% Below Baselin
e
(1) Localiz
ed Control
(2) Relay Panel
(3) Dimming Panel
(4) Addressa
ble Ballasts
(5) Wireles
s Partial Dimming
(6) Wireles
s Full
Dimming
5.0
4.5
4.0
3.5
3.0
2.5
2.0
2.0
1.5
1.0
0.5
0.0
35
30
25
20
15
10
5
0
Annual Energy Density
[kwh/sf]
Annual Peak Monthly
Demand [kw]
Boston Avg. Peak Monthly Demand L.A. Avg. Peak Monthly Demand
Boston L.A.
![Page 45: The Application and Costs of Lighting Controls...Automatic Lighting Shutoff –“Buildings… shall be equipped with automatic control device to shut off lighting… based on either:”](https://reader033.fdocuments.in/reader033/viewer/2022060807/608c299bd7cc741d19018e51/html5/thumbnails/45.jpg)
Capital Costs
(1) Localiz
ed Control
(2) Relay Panel
(3) Dimming Panel
(4) Addressa
ble Ballasts
(5) Wireles
s Partial Dimming
(6) Wireles
s Full
Dimming
200%
180%
160%
140%
120%
100%
80%
60%
40%
20%
0%
Control Equipment Lighting System Devices Control System
Branch Circuit Wiring Lighting System Demo Controls Demolition Commissioning
![Page 46: The Application and Costs of Lighting Controls...Automatic Lighting Shutoff –“Buildings… shall be equipped with automatic control device to shut off lighting… based on either:”](https://reader033.fdocuments.in/reader033/viewer/2022060807/608c299bd7cc741d19018e51/html5/thumbnails/46.jpg)
Capital Costs
(1) Localiz
ed Control
(2) Relay Panel
(3) Dimming Panel
(4) Addressa
ble Ballasts
(5) Wireles
s Partial Dimming
(6) Wireles
s Full
Dimming
200%
180%
160%
140%
120%
100%
80%
60%
40%
20%
0%
Control Equipment Lighting System Devices Control System
Branch Circuit Wiring Lighting System Demo Controls Demolition Commissioning
• High
Cost
branch
circuit
and
control
wiring
• Lower
Cost for
Control
Equipme
nt
• Highest
Cost
branch
circuit
and
control
wiring
• Lower
Cost for
Control
Equipme
nt
• Highest
Cost
branch
circuit
and
control
wiring
• Lower
Cost for
Control
Equipme
nt
• Low
Cost
branch
circuit
and
control
wiring
• Highest
Cost for
Lighting
System • Lowest
Cost
branch
circuit
and
control
wiring
• Low
Cost
branch
circuit
and
control
wiring
• Highest
Cost for
Control
Eqiup
and
Devices
![Page 47: The Application and Costs of Lighting Controls...Automatic Lighting Shutoff –“Buildings… shall be equipped with automatic control device to shut off lighting… based on either:”](https://reader033.fdocuments.in/reader033/viewer/2022060807/608c299bd7cc741d19018e51/html5/thumbnails/47.jpg)
![Page 48: The Application and Costs of Lighting Controls...Automatic Lighting Shutoff –“Buildings… shall be equipped with automatic control device to shut off lighting… based on either:”](https://reader033.fdocuments.in/reader033/viewer/2022060807/608c299bd7cc741d19018e51/html5/thumbnails/48.jpg)
![Page 49: The Application and Costs of Lighting Controls...Automatic Lighting Shutoff –“Buildings… shall be equipped with automatic control device to shut off lighting… based on either:”](https://reader033.fdocuments.in/reader033/viewer/2022060807/608c299bd7cc741d19018e51/html5/thumbnails/49.jpg)
10-year Costs
0% 20% 40% 60% 80% 100% 120% 140%
(6) Wireless Full
Dimming
(5) Wireless Partial Dimming
(4) Addressable Ballasts
(3) Dimming Panel
(2) Relay Panel
(1) Localized Control
CONTROL EQUIPMENT
COMMISSIONING
COSTS
ENERGY COSTS
![Page 50: The Application and Costs of Lighting Controls...Automatic Lighting Shutoff –“Buildings… shall be equipped with automatic control device to shut off lighting… based on either:”](https://reader033.fdocuments.in/reader033/viewer/2022060807/608c299bd7cc741d19018e51/html5/thumbnails/50.jpg)
Key Findings of Clanton Study
Advanced Lighting Controls can achieve 50% less energy than
code-compliant lighting controls
Wireless Advanced Lighting Controls have lower capital costs
than other systems studied in office retrofit applications
Reduced labor & energy costs of advanced networked lighting
control systems can out-weigh increased equipment &
commissioning costs
Will this be true on your project?
50
![Page 51: The Application and Costs of Lighting Controls...Automatic Lighting Shutoff –“Buildings… shall be equipped with automatic control device to shut off lighting… based on either:”](https://reader033.fdocuments.in/reader033/viewer/2022060807/608c299bd7cc741d19018e51/html5/thumbnails/51.jpg)
Does uncertainty or lack
of familiarity increase bid price?
Will the wiring savings
be realized?
What can we do to address these challenges?
Challenges With
Pricing
![Page 52: The Application and Costs of Lighting Controls...Automatic Lighting Shutoff –“Buildings… shall be equipped with automatic control device to shut off lighting… based on either:”](https://reader033.fdocuments.in/reader033/viewer/2022060807/608c299bd7cc741d19018e51/html5/thumbnails/52.jpg)
Strategies to Reduce the Cost of Advanced
Controls
Hold mandatory pre-bid training for all bidders
– Highlight issue of controls pricing
– Communicate that you are looking to realize savings from
reduced wiring
– Controls pricing should not be based on standard $/SF
– Clearly explain how controls will be wired
– Clearly identify who is responsible for what
52
![Page 53: The Application and Costs of Lighting Controls...Automatic Lighting Shutoff –“Buildings… shall be equipped with automatic control device to shut off lighting… based on either:”](https://reader033.fdocuments.in/reader033/viewer/2022060807/608c299bd7cc741d19018e51/html5/thumbnails/53.jpg)
Strategies to Reduce the Cost of Advanced
Controls
Carefully and Fully Specify Controls
– Provide Design Narrative for all Controls
– Provide Control Intent and Zoning Diagrams
– Specify Initial Calibration Settings
– Identify who is responsible for what
– Align responsibility with who is most knowledgeable and/or cost-
effective for each task
• Example: Consider putting responsibility on Manufacturer for
Commissioning and System Functionality
• Example: Require the contractor is trained on control system
53
![Page 54: The Application and Costs of Lighting Controls...Automatic Lighting Shutoff –“Buildings… shall be equipped with automatic control device to shut off lighting… based on either:”](https://reader033.fdocuments.in/reader033/viewer/2022060807/608c299bd7cc741d19018e51/html5/thumbnails/54.jpg)
Strategies to Keep Advanced Controls on
Projects
Reduce the Costs per previous slides
Play up the benefits beyond energy savings:
54
![Page 55: The Application and Costs of Lighting Controls...Automatic Lighting Shutoff –“Buildings… shall be equipped with automatic control device to shut off lighting… based on either:”](https://reader033.fdocuments.in/reader033/viewer/2022060807/608c299bd7cc741d19018e51/html5/thumbnails/55.jpg)
Light Level Preferences A 2004 open office
study found that people exhibit a wide
range of light level preferences.
Energy Savings 5–20%
Source: LightRight Consortium
AVERAGE DESKTOP ILLUMINANCE (Lux)
30
20
10
0
100 300 500 700 900 1100
COUNT
![Page 56: The Application and Costs of Lighting Controls...Automatic Lighting Shutoff –“Buildings… shall be equipped with automatic control device to shut off lighting… based on either:”](https://reader033.fdocuments.in/reader033/viewer/2022060807/608c299bd7cc741d19018e51/html5/thumbnails/56.jpg)
Allowing workers to control
their light can result in higher productivity
and occupant satisfaction
People costs typically outweigh building
costs by 13:1
Investing in personal controls can lead to desirable financial
outcomes beyond energy savings
Reasons People Control Their Lights
60
50
40
30
20
10
COMPUTERS
COMPENSATE FOR DAYLIGHT
READING PRINTED TEST
CREATE ATMOSPHERE FOR
WORK
ENERGY
PERCENTAGE OF
RESPONDENTS
![Page 57: The Application and Costs of Lighting Controls...Automatic Lighting Shutoff –“Buildings… shall be equipped with automatic control device to shut off lighting… based on either:”](https://reader033.fdocuments.in/reader033/viewer/2022060807/608c299bd7cc741d19018e51/html5/thumbnails/57.jpg)
Green Buildings and Property Value / Rents / Lease Rates
Certification on Office Values, Fuerst et al,
2011 * 4-5% Rental Premium, 25% Sales Premium for LEED or ENERGY STAR
Buildings Sustainability and the
Dynamics of Green Building, Eichholtz et
al, 2010 * 6% Rental Premium, 11-13% Sales Premium
for LEED or ENERGY STAR Buildings
Green Design and the Market for Commercial Office Space, Wiley et
al, 2010 * 7-17% Rental Premium, 8-18% Sales Premium,
10-11% higher Occupancy Rates for ENERGY STAR or LEED Buildings,
![Page 58: The Application and Costs of Lighting Controls...Automatic Lighting Shutoff –“Buildings… shall be equipped with automatic control device to shut off lighting… based on either:”](https://reader033.fdocuments.in/reader033/viewer/2022060807/608c299bd7cc741d19018e51/html5/thumbnails/58.jpg)
Optimal Energy, Inc.
10600 Route 116, Suite 3
Hinesburg, VT 05461
802-482-5600
Thank You