Testing EHV Secondary Arcs

download Testing EHV Secondary Arcs

of 6

Transcript of Testing EHV Secondary Arcs

  • 8/16/2019 Testing EHV Secondary Arcs

    1/6

    Paper acceptcd for prcscntation at PPT 2001

    2001

    IEEE Porto Power Tech Conference

    I O t h

    -13‘”

    September, Porto, Portugal

    Testing EHV Secondary Arcs

    G

    Ban, Fellow IEEE

    L.

    Prikler, Member IEEE

    G

    Banfai, Member IEEE

    Abstract--The protection of the environment requires

    compact EHV tower constructions. This trend results in

    decreasing the clearances and phase-to-phase distances. I t is

    expectable, that both the number of faults and the amplitude

    of the secondary arc current

    will

    grow in the future.

    All

    these

    make necessary to improve the efficiency of single-phase

    reclosing. Secondary arc duration values gained at field tests

    show a big spread and therefore they do not provide a reliable

    basis for selecting a suitable dead time. Analyzing the main

    processes affecting on the secondary arc duration, authors

    conclude that traveling wave phenomena arising in the

    intermittent period of secondary arcing have a determining

    effect on the arc duration. Considering the difficulties

    connected with field tests and the big influence of the weather

    conditions

    on

    the secondary arc duration, authors propose to

    complete laboratory test circuits by such components, which

    effectuate the simulation of the wave processes.

    A

    method for

    the detection of the secondary arc extinction of good

    experiences

    on 750

    and

    400

    kV lines is mentioned, which offers

    a possibility to prevent inefficient reclosures.

    Index

    Terms--Compacting power lines, dead time, EHV line

    faults, field test, laboratory test, secondary arc, shunt reactor,

    single-phase reclosing, traveling wave process.

    I. INTRODUCTION

    integrate transmission lines into the environment, the

    T

    imensions of the towers, the clearances, phase-to-

    phase spacing are to be reduced. Besides it is difficult to find

    a new right-of-way. To operate lines on a higher voltage

    level, than their original nominal voltage offers a possibility

    to overcome this problem. Transmission lines of lower

    voltage level contain single phase-conductors. When

    uprating lines, they have to be replaced by bundle

    conductors

    or

    the number of subconductors

    has to

    be

    increased. All these solutions result in decreasing the

    clearance and increasing the phase-to-phase capacitance. It

    is expected, that the number of faults due to lightning

    strokes will increase, if the dimensions of the towers will be

    reduced in proportion of the possible rate of switching

    overvoltages limitation.

    The activity reported in

    the

    paper has been partly supported by the

    Hungarian Research Fund under contract

    No. OTKA

    T

    026054

    Gabor Ban, Laszl6 Prikler and Gyorgy BBnfai are with the Department of

    Electric Power Systems, Budapest University

    of

    Technology and Economics,

    Egry J. U. 18, H-1 111 Budapest, Hungary.

    Authors’ e-mail addresses: [email protected], [email protected]  

    Single phase reclosing seems to be an efficient tool to

    compensate the expectable growth in the number of EHV

    line faults, since they are single phase-to-ground ones and

    not permanent in the overwhelming majority of cases.

    Stability requirements determine the upper limit of the dead

    time; generally dead times exceeding

    1.5 -

    2

    s

    are not

    permissible. When tripping the faulty phase, a secondary arc

    forms in the hot plasma remaining from the primary arc.

    The secondary arc is sustained by the capacitive and

    inductive coupling between the healthy and faulty phase

    conductors. The amplitude of the continuous secondary

    current lies in the range of

    10

    Amps. The secondary arc

    extinguishes spontaneously as a rule, however its duration

    depends on many factors. Long duration secondary arcs

    endanger the efficiency of single-phase reclosing, if the

    secondary arc does not extinguish during the dead time, the

    reclosure is followed by three-phase tripping the line.

    Consequently, the lower limit of the dead time to be adjusted

    in the reclosing automation is prescribed by the expectable

    duration of the secondary arcs. Considering the increased

    phase-to-phase capacitance of compact and uprated lines,

    higher secondary arc currents have to be expected, that will

    result in longer secondary arc duration.

    Numerous tests have been carried out on real lines and in

    laboratories to get a picture about the expectable secondary

    arc duration. However, the results published in technical

    papers show a significant spread. To prescribe the lower

    limit of the dead time starting from the longest secondary

    arc extinction time experienced does not seem economical.

    On the other hand, utilities want to keep the same reliability

    level for compact lines with reduced clearances and

    increased phase-to-phase capacitance, as for the

    conservative line constructions. It is easy to see, that exact

    and reliable data about the expectable secondary arcing

    times are necessary for the new tower constructions and it is

    recommendable to reconsider the technique of secondary arc

    testing.

    Authors participated in field testing of a

    420

    kV

    interconnecting line of

    3 10

    km length, without shunt

    compensation, in November and December

    1999.

    Seven

    staged faults were carried out, aiming to predict the

    expectable secondary arcing times. The shortest extinction

    time recorded during the tests reached

    0.05

    s and the longest

    4 s.

    The secondary arc did not extinguish during 27

    s

    on one

    test, so the line was tripped. The

    T, = 4 s

    and T, >

    27

    0-7803-7139-9/01/ 10.00 02001

    IEEE

    mailto:[email protected]:[email protected]

  • 8/16/2019 Testing EHV Secondary Arcs

    2/6

    extinction times have been measured at calmness and

    T,= 0.05 s 0.69 s values at small wind velocity 3

    -

    4 d s .

    The big spread of the extinction times and very long arcing

    times experienced in two cases correspond to the data about

    extinction times published in former papers containing

    generalizing diagrams

    [3].

    The voltage and currents records

    as well as shots made about the arc movement make possible

    to investigate the secondary arcing process in details. The

    purposes of this investigation are:

    -

    to explain the big spread of the secondary arc extinction

    times,

    -

    to study the factors influencing on the secondary arcing

    process,

    to improve the technique of field tests to get more reliable

    data,

    - to elaborate a correct test circuit for laboratory studies,

    - to find a way for establishing a dead time which is

    acceptable both from stability and single phase reclosure

    efficiency point of view.

    Authors considered also their former experiences and results

    gained at former field tests on a shunt compensated 750 kV

    line of 479 kilometers length and numerous 400 kV lines.

    The paper analyses the following points:

    -

    the shape and the amplitude of the secondary arc current,

    -

    the impact of the wind velocity,

    -

    the technique of the secondary arc initiation,

    11. THESHAPE AND

    THE

    AMPLITUDEF

    THE

    SECONDARYRCCURRENT

    The dependency of the secondary arc extinction time on

    the sinusoidal, steady state arc current is given in the

    generalizing papers. This current can be calculated using the

    circuit in Fig. 1, where Ua U,, U, are the phase voltages,

    Cab-the hase-to-phase, Co-thezero sequence capacitance,

    a) three-phase network

    b) equivalent circuit

    Fig. 1.

    a.

    -the secondary arc current. The fault is modeled by switch

    S,. The secondary current contains an induced component

    as well due to the inductive coupling between the phase

    conductor and an inductive one caused by the distributed

    character of

    C a b

    and the lumped character of the fault. The

    induced and the inductive components may be neglected

    usually due to their small amplitude. These components play

    an important role only when the capacitive component is

    compensated artificially (e.g. by neutral reactors).

    The predominant part of the published laboratory tests

    was carried out using the circuit in Fig. l/b. However, this

    circuit gives a reference about the steady state secondary

    current only. As numerous records of single phase switching

    tests on transmission lines show the character of secondary

    arcing is intermittent during a significant part of the

    process. The extinction of the secondary arc is always

    preceded by an intermittent interval, containing current

    impulses. The amplitude of these impulses can be much

    higher than in the steady-state interval (Fig.2). This part of

    the arcing process can be explained by the thermal effect of

    the high current primary arc which generates a.powerfu1 air

    movement resulting in a speedy elongation of the secondary

    arc and producing separated from each other plasma clouds.

    Wind can have the same effect on the secondary arcing.

    When the transient recovery voltage, arising along the arc

    channel, exceeds the critical value, sufficient to reignite the

    arc, traveling waves start on the line. The superposition of

    the reflected waves produces a current zero at the fault and

    mostly partial arc extinction. The length

    of

    the current

    impulses depends on the place of the fault. If the fault is in

    the middle point, the impulse length is equal to the travel

    time along the line

    T).

    For the predominant part

    of

    the line

    length, the duration of the impulse is 2T. The shape of the

    impulse and its thermal effect is depending on the line

    b.

    600

    400

    200

    0

    200

    400

    600

    0 .6 0 7

    0 8 0.9 1

    o

    1 1

    Typical secondary arc voltage and the current measured)

    Fig. 2

  • 8/16/2019 Testing EHV Secondary Arcs

    3/6

    ............

    ............ ............ ............. ........ ........

    1

    4 0 0 I

    0.67

    0.69

    0.71 0.73 0.75 0.77

    Fig.

    3.

    Measured secondary arc voltage and current

    configuration (discontinuity points) as well. The actual value

    of the recovery voltage at the moment of the restrike

    determines the peek value of the current impulse. The

    energy of the current impulse is higher, when the restrike

    occurs near to, but before the peek of the recovery voltage

    (see Fig.3).

    A

    high current impulse containing a relatively high

    amount of energy is able to re-ionize a large amount of

    plasma, to shift back the process into the quasi-sinusoidal

    interval and elongate the secondary arc duration. From these

    effects it emerges, that traveling wave phenomena have a

    big influence on intermittent arcing process and

    consequently on the secondary arc duration. Thus circuits

    applied for testing secondary arc in laboratory cannot

    furnish correct data without modeling the wave processes

    during the intermittent interval. The shape and the

    amplitude of the recovery voltage arising after the partial

    extinctions of the secondary arc must have also an effect on

    the arc duration. These parameters also strongly depend on

    the wave phenomena.

    Shunt reactors connected directly to a power line affect

    both on the arc current and the recovery voltage. From the

    equivalent circuit created for this configuration (Fig.

    4)

    follows, that here the recovery voltage is of beating

    character, it contains

    two

    frequencies: the power and the

    transient frequency of the circuit. Consequently the partial

    -u /2

    LO

    Fig. 4. Equivalent circuit for shunt compensated lines

    or final arc extinctions are followed by a modulated voltage

    oscillation, the amplitude of which may be rather high,

    depending on the compensation degree of the line.

    As another effect of shunt reactors, a DC component

    occurs in the initial part of the secondary arc current, caused

    by the magnetic energy stored in the reactor at the moment

    of tripping the faulty phase. The circuit in Fig. 4 simulates

    this

    DC

    component, which affects

    on

    the arc duration only

    when four legged shunt reactor sets are connected to the

    line. Besides, the shunt reactor of the faulty phase generates

    a DC component in the secondary arc during each arc

    reignition. Fig. 5 shows, that the shunt reactor current

    Ir)

    is

    opposite to the current wave

    I,,

    reflected at the line end, if

    the arc reignites before the peek of the recovery voltage UIec.

    In case of a reignition after the peek of

    U,

    (this happens

    frequently when the gaps in the secondary arc channel

    increase) the directions of I, and I,, are equal. As a result,

    the first zero transition of the arc current becomes very

    steep, and the arc can not extinguish in the first current

    zero, the length of the restrike elongates by 10 milliseconds.

    Occurring long duration restrikes can delay the final

    extinction of the secondary arc for a long time. As a matter

    of course the circuit shown in Fig. 4 does not simulate the

    wave process.

    111. THEEFFECT

    F

    THE WIND V E L O C I T Y

    The secondary arc forms inside the plasma left by the

    primary arc which is moving upwards due to its high

    temperature and in horizontal direction due to the wind.

    After a short while individual plasma clouds will be

    separated from each other by cold channel zones due to the

    elongation of the arc channel and the thermal losses.

    0.10 0 . 1 2 0 . 1 4

    0 . i 6

    o . i s

    0.50

    0 52

    upper curves:

    I

    green) and

    Iarc=I,+lcw,

    ower curve:

    U,

    Fig

    5

  • 8/16/2019 Testing EHV Secondary Arcs

    4/6

    The secondary arc extinguishes finally, when the voltage

    necessary to break down the high resistance channel zones,

    exceeds the recovery voltage. So it is evident, that the wind

    velocity is a determining factor of the secondary arc

    extinction process. Unfortunately, most papers do not

    publish the wind parameters during the tests.

    At calmness no horizontal component of the arc motion,

    the plasmas left by the primary arc and generated by the

    secondary one move slowly, without any significant channel

    elongation (Fig. 6/a). Ions generated during the intermittent

    arc interval remain in the environment of the arc. These

    circumstances make the self-extinction time very long. At

    small wind velocities the elongation of the arc is slow. Due

    to the electromagnetic field, loops occur in the arc channel

    (Fig.

    6h . So

    parts of the arc channel, which are electrically

    far from each other, may get close geometrically. If the

    recovery voltage is sufficient to produce a breakdown,

    bridging a significant length of the arc channel, the arcing

    process may return to the condition of steady state burning,

    remarkably elongating the self-extinction time.

    The formation of loops is of random character; as a

    consequence the spread of the self-extinction times is

    relatively big at small wind velocities. There is an

    interesting interaction of the loop formation and the wave

    processes. Being the motion of the arc channel slower, than

    increasing the recovery voltage, a breakdown between two

    plasma clouds occurs mainly at the peek of the recovery

    voltage. Such a breakdown results in a high current impulse

    that

    is

    not able to extinguish at the first zero transition

    producing a high energy elongated restrike (see the first and

    second restrikes in Fig.

    7),

    which sets back the intermittent

    arcing

    into the

    steady-state one.

    In strong wind the distances between the active parts of

    the inhomogeneous arc channel increase quickly.

    Consequently, the re-ignition voltage does not take long to

    excess the recovery voltage, resulting in a short extinction

    time.

    Iv . THETECHNIQUEF

    THE

    SECONDARYARC INITIATION

    Secondary arc tests on real lines are often carried out by

    omitting the primary arc; the secondary arc is initiated by a

    thin wire in such cases. This method of testing is based on

    the conclusion drawn from numerous field tests [6], that the

    primary arc does not affect the self extinction time, as far as

    the secondary arc duration excesses 0.7 s. Considering, that

    the omission of the primary arc makes the tests more simple

    and less dangerous for the system, and secondary arc

    durations shorter than 0 7 s are allowed from stability point

    of view as a rule, this way of testing seems to be attractive.

    In case of a real phase-to-ground fault the secondary arc

    develops inside the primary plasma, along its whole length

    (Fig. 6/c). Our field test results show, that the thickness of

    the wire and the way of its connection to the arcing honis

    may influence on the self-extinction time, particularly at

    middle and big wind velocities, when the speeds of the arc

    elongation and wire evaporation are commensurable.

    In such cases the arc may extinguish due to the

    elongation caused by the wind before the wire evaporates

    along its whole length (Fig. 6/d). The arc initiation by

    means of a wire may result in shorter extinction times than

    under natural conditions.

    v.

    DETECTION

    F

    THE SECONDARY

    ARC

    EXTINCTION

    As it was mentioned before, the final extinction of the

    secondary arc is preceded by an intermittent interval during

    which the arc current is of impulse character. Every

    impulse is initiated by a breakdown between the individual

    plasma clouds, as a consequence, the breakdown is followed

    by starting steep front waves along the line. Waves, reflected

    on the open ends of the faulty phase conductor result in a

    current transition and mostly an intermediate extinction at

    the place

    of

    the fault.

    So

    both the front and the tail of the

    current impulse are relatively steep, causing two individual

    transients on the line. Both transients result in a voltage

    oscillation on the line ends. The frequency of the breakdown

    transient depends on the situation of the fault. The frequency

    of the extinction transient is depending on the line length

    only. This frequency can be calculated very exactly, taking

    into consideration the effect of the healthy phases on the

    process. Therefore

    it can be used as a signal for the

    detection.

    The device, elaborated in the Budapest University of

    Technology and Economics for the detection of the final

    extinction

    of

    the secondary arc has been based

    on

    sensing

    the presence of the extinction transients by means of special

    filters on the line ends. As long as the intermittent

    secondary arc exists, a high voltage occurs on the outputs of

    the filters. Dropping the output voltage to a low level

    indicates the final extinction of the secondary arc. The ten

    years experience on

    75

    kV and 400 kV lines was positive:

    the disturbance recorders showed, that the devices operated

    correctly at every fault.

    The scheme has been completed by a sensor which detects

    the amplitude of the recovery voltage and serves for

    establishing the arc extinction in that rare cases when no

    intermittent interval occurs.

    Summarizing: one may choose

    an

    optimum dead time

    from stability point of view, knowing that the above

    described device blocks the reclosure when the secondary

    arc does not extinguish in time.

  • 8/16/2019 Testing EHV Secondary Arcs

    5/6

    a)

    secondary arc at calmness

    b)

    secondary arc in m iddle velocity wind

    c)

    formation

    of

    the secondary arc inside the primary plasma

    d)

    extinction of the secondary arc

    before

    reaching its whole length

    Fig. 6 . Second ary arc tests on a 400 kV line

  • 8/16/2019 Testing EHV Secondary Arcs

    6/6

    3. One can decide the question about the validity of tests

    without primary arc and select the optimal way of arc

    initiation using the test circuit mentioned above.

    4. The negative consequences of the big spread of

    extinction times experienced on transmission lines and in

    laboratories can be reduced by applying an automation,

    which establishes the moment of the final extinction of the

    actual secondary arc and prevents the reclosure when it did

    not extinguish in time. Such a device has been developed in

    Hungary and used on 750 kV and 400 kV lines [7].

    0 8

    0.4

    0.41

    v

    0.8

    I I I I

    I

    I I

    0.096 0.100 0.104 0 108 0.1 12

    Fig.

    8.

    Two restrikes on the power line and in the laboratory test circuit

    calculated). Upper curves: recovery voltage; lower curves: arc current

    VI. CONCLUSIONS

    1. Field tests aiming to predict the secondary arc duration

    for a new line need long preparation and stress the power

    system. On the other hand, a big spread characterizes the

    results gained from the individual tests due to the

    differences in the wind velocities, arc initiation, line

    construction, shunt compensation degree etc. In order to

    reduce this spread, correct recording of the wind velocity

    and a detailed description of the way of arc initiation are

    recommended.

    2.

    Systematic laboratory tests at which the wind velocity

    can be controlled and all parameters can be correctly

    adjusted, furnish reliable and generalizing data. Laboratory

    test circuits have to simulate the wave processes during

    intermittent arcing; it can be effectuated by using a simple

    reference circuit of the line

    [5]

    that takes into consideration

    the wave process both in the faulty and healthy phases. As

    Fig. 8  shows, one can realize a suitable similarity of the

    processes in such a way. The shapes of the current impulses

    differ to a certain degree, but the integrals, being responsible

    for the thermal effect, are identical.

    VII. ACKNOWLEDGEMENT

    Authors acknowledge the contribution of the Hungarian

    Power Companies Ltd.

    VIII. REFERENCES

    [ l ]

    Fukinishi,M. et al.: “Laboratory Study on Dead Time

    of

    High

    Speed Reclosing of 500 kV Systems” CIGRE 1970, Rep.

    [2] Haubrich, H.J. et al.: “Single-phase Auto-Reclosing in EHN

    Systems” CIGRE

    1974,

    Rep.

    31-09

    [3] Rashkes, V.S.: “Generalizationof the Operation Experiences,

    Connected with the Efficiency of Single-phase Reclosing,

    Experimental Data about the Extinction Time of the

    Secondary Arc” Elektricheskie Stancii

    1989. No.3

    (in

    Russian)

    [4] Esztergalyos, J. et al.: “Single-phase Tripping and Auto

    Reclosing of Transmission Lines (IEEE Committee Report)”,

    IEEE Trans. Power Deliveiy vol.

    7, No 1 .

    pp.

    182-192,

    January 1992

    [5]

    G. Ban,

    L.

    Prikler: “ReferenceCircuits for the Investigation of

    Power Systems Transients” in Proc o International

    Conference

    on

    Power Systems Transients

    Lisbon, 1995,

    [6] Beliakov et al.: “Investigation of Single-phase Reclosing on

    750 kV shunt-compensated transmission lines”

    Elektrichestvo 1981

    No.7 in Russian).

    [7]

    Ban, G.: “Adaptive Single-Pole Reclosing Experience” Proc.

    o

    the 33th Session o CIGRE 1990 Gr. 34, pp. 28-29.

    3 1-03

    pp.5

    1 56.