MACROTEST5035 Microprocessor Based Instrument for Testing of Electrical Installations VDE 0413 MACROTEST 5035 is an essential instrument to check safety of electrical installations and take measurements according to EN 61010.Friendly to use thanks to a powerful microprocessor it provides a completely automatic system to record test results. The serial output RS232 permits to transfer stored data to PC for further processing. MACROTEST 5035 can be employed for testing civil and industrial electrical installations, tracking faults due to bad insulation, checking proper working of RCDs, measuring earth resistance of both simple (TT) and complex (TN) systems as well as measuring ground resistivity for designing of the earth installation. Functions: Continuity test of protective and potential equalizing conductors Two-three- and four-wire earth resistance measurement with rods Measurement of ground Resistivity Insulation resistance measurement with voltages of 50-100-250-500-1000V DC Frequency measurement Short circuit impedance measurement Fault loop impedance measurement Prospective short circuit current Phase sequence indication Tripping time and current measurement of RCDs type A-AC and selective Contact voltage measurement Measurement of total earth resistance without RCD tripping Serial output RS232 for connection to PC Weight and dimensions approx 1200g-229x165x105mm Due to our policy of continual product development, we reserve the right to amend the specifications of all mentioned products without prior notice. MACROTEST5035_PS_v01 Created on 12/2/2005 2:24:38 PM Prepared by Fung Page 1of 6

description

testiranje elektroinstalacija

Transcript of Tester Macrotest

  • MACROTEST5035 Microprocessor Based Instrument for Testing of Electrical Installations VDE 0413 MACROTEST 5035 is an essential instrument to check safety of electrical installations and take measurements according to EN 61010.Friendly to use thanks to a powerful microprocessor it provides a completely automatic system to record test results. The serial output RS232 permits to transfer stored data to PC for further processing. MACROTEST 5035 can be employed for testing civil and industrial electrical installations, tracking faults due to bad insulation, checking proper working of RCDs, measuring earth resistance of both simple (TT) and complex (TN) systems as well as measuring ground resistivity for designing of the earth installation. Functions: Continuity test of protective and potential equalizing conductors Two-three- and four-wire earth resistance measurement with rods Measurement of ground Resistivity Insulation resistance measurement with voltages of 50-100-250-500-1000V DC Frequency measurement Short circuit impedance measurement Fault loop impedance measurement Prospective short circuit current Phase sequence indication Tripping time and current measurement of RCDs type A-AC and selective Contact voltage measurement Measurement of total earth resistance without RCD tripping Serial output RS232 for connection to PC Weight and dimensions approx 1200g-229x165x105mm Due to our policy of continual product development, we reserve the right to amend the specifications of all mentioned products without prior notice. MACROTEST5035_PS_v01 Created on 12/2/2005 2:24:38 PM Prepared by Fung

    Page 1of 6

  • Accessories 3-wire shuko cable (C2033) Kit of 3 cables,4 crocodiles and 2 test lead (KITGE80) Carrying case containing 4 cables banana-banana and 4 earth rods (KITTERRNE) Software on CD-ROM (EUROLINK2000) Serial cable (C2001 RS232) Carrying bag (BORSA2050) Calibration certificate ISO9000 Instruction manual Optional accessories Accessory for impedance measurement at high resolution.(IMP57) Kit of strap and hooks to hang the instrument on the neck.(CN0050) Standards CE mark Continuity test (EN 61557-4) Insulation Resistance (EN 61557-2) Earth resistance (EN 61557-5) RCD test (EN 61557-6) EMC Standards (EN 61326) Safety of electrical devices equipment (EN 60204-1) Type-tested assemblies TTA and partially type-tested assemblies PTTA (IEC 60439-1) EN 61008 EN 61009 EN 61010-1 16th edition HD 384 VDE 0413 Due to our policy of continual product development, we reserve the right to amend the specifications of all mentioned products without prior notice. MACROTEST5035_PS_v01 Created on 12/2/2005 2:24:38 PM Prepared by Fung

    Page 2of 6

  • 1. TECHNICAL SPECIFICATIONS CONTINUITY TEST ON PROTECTIVE AND EQUALIZING CONDUCTORS (modes: AUTO, RTimer+, RTimer-)

    Range [] Resolution [] Accuracy* 0.01 - 19.99 0.01 20.0 - 99.9 0.1

    (2% reading + 2 dgt)

    * after cable calibration (which eliminates the cable resistance) Test current > 200mA DC for R 5 (after calibration) Current measurement resolution: 1mA Open-circuit voltage: 4V Vo 24V INSULATION RESISTANCE (modes: MAN, TIMER)

    Test voltage [V] Range [M] Resolution [M] Accuracy

    0.01 -19.99 0.01 20.0 -49.9 0.1

    (2% reading + 2 dgt) if V/R>1A 50

    50.0 -99.9 0.1 (5% reading + 2 dgt) if V/R1A 0.01 -19.99 0.01 20.0 -99.9 0.1

    (2% reading + 2 dgt) if V/R>1A 100

    100.0 -199.9 0.1 (5% reading + 2 dgt) if V/R1A 0.01 -19.99 0.01 20.0 -199.9 0.1 200 -249 1

    (2% reading + 2 dgt) if V/R>1A 250

    250 -499 1 (5% reading + 2 dgt) if V/R1A 0.01 -19.99 0.01 20.0 -199.9 0.1 200 -499 1

    (2% reading + 2 dgt) if V/R>1A 500

    500 -999 1 (5% reading + 2 dgt) if V/R1A 0.01 -19.99 0.01 20.0 -199.9 0.1 200 -999 1

    (2% reading + 2 dgt) if V/R>1A 1000

    1000 -1999 1 (5% reading + 2 dgt) if V/R1A Open-circuit voltage: 1.3 x nominal test voltage Short circuit current: 2.2mA on 230k load others >1mA on 1k*Vnom RCD TEST Nominal tripping currents (IN) 10mA, 30mA, 100mA, 300mA, 500mA RCD type AC, A General and Selective Phase-Earth voltage 100V - 265V 50 Hz Tripping time tN of GENERAL, SELECTIVE, A AND AC RCDs

    Range [ms] Resolution [ms] Accuracy IN, IN 0-999 2 IN 0-200 general 0-250 selective 5 INRCD 0-50 general 0-160 selective

    1 (2% reading+2dgt)

    500mA x 5 not available Due to our policy of continual product development, we reserve the right to amend the specifications of all mentioned products without prior notice. MACROTEST5035_PS_v01 Created on 12/2/2005 2:24:38 PM Prepared by Fung

    Page 3of 6

  • Contact voltage Ut Range [V] Resolution [V] Accuracy 0 - 2Utlim 0.1 - 0%, +(2% reading + 2 dgt)

    Ut LIM (UL): 25V o 50V Earth resistance RA without tripping of RCDs

    Range [] Resolution [] Accuracy IN 1 -1999 1 - 0%, +(5% reading + 2 dgt)

    Test current 0.5 IN set for Ut test 15mA for Ra 15mA test Tripping Current IN of GENERAL A AND AC RCDs IN 10mA

    RCD Range IN [mA] Resolution [mA] Accuracy IN AC (0.5 -1.4) IN 0.1 IN - 0%, +5% IN A (0.5 -2.4) IN 0.1 IN - 0%, +5% IN

    IN > 10mA RCD Range IN [mA] Resolution [mA] Accuracy IN AC (0.5 -1.4)IN 0.1 IN - 0%, +5% IN A (0.5 -2) IN 0.1 IN - 0%, +5% IN

    FREQUENCY

    Range (Hz) Resolution (Hz) Accuracy 47.0 -63.6 0.1 (0.1% reading+1 dgt)

    Loop and RCD measurements are active only at 50Hz VOLTAGE (RCD, LOOP, PHASE SEQUENCE)

    Range [V] Resolution [] Accuracy 0 - 460 1 (3% reading + 2 dgt)

    LINE IMPEDANCE (phase to phase, phase to neutral)

    Range [] Resolution [] Accuracy 0.01 -19.99 0.01 20.0 -199.9 0.1

    (5% reading + 3 dgt)

    Maximum peak current at the test voltage: 127V 3.65A 230V 6.64A 400V 11.5A Test voltage phase-neutral/phase-phase: 100 - 265V / 100 - 460V 50Hz FAULT LOOP IMPEDANCE (phase to earth)

    Range [] Resolution [] Accuracy 0.01 -19.99 0.01 20.0 -199.9 0.1 200 -1999 1

    (5% reading + 3 dgt)

    Maximum peak current at the test voltage 127V 3.65A 230V 6.64A Test voltage phase-earth: 100 - 265V 50Hz

    Due to our policy of continual product development, we reserve the right to amend the specifications of all mentioned products without prior notice. MACROTEST5035_PS_v01 Created on 12/2/2005 2:24:38 PM Prepared by Fung

    Page 4of 6

  • FAULT LOOP IMPEDANCE WITHOUT RCDs TRIPPING (phase to earth Ra 15mA ) Range [] Resolution [] Accuracy

    1 -1999 1 -0%,+(5%Lettura+3digit) Test current 15mA Test voltage phase-earth: 100 - 265V 50Hz EARTH RESISTANCE WITH RODS

    Range RE [] Resolution [] Accuracy 0.01 - 19.99 0.01 20.0 - 199.9 0.1 200 - 1999 1

    (5% reading + 3 dgt)

    Test current

  • WORKING ENVIRONMENTAL CONDITIONS Reference temperature 23 5C Working temperature 0 - 40C Allowed relative humidity < 80% Storage temperature -10 - 60C Storage humidity < 80% RIFERIMENTI NORMATIVI GENERALI Safety of measuring instruments EN 61010-1 + A2 (1997) Product type standard IEC61557-1, -2, -3, -4, -5, -6 Insulation class 2 Pollution degree 2 Over voltage category CATIII 460V~ / 265V~ to earth Indoor use; max altitude: 2000m EMC EN61326-1 (1997) + A1 (1998) This instrument complies with the European Directive for CE marking.