Tesla Powerwall 2 Datasheet - GEM Energy · Optimizes the contribution between renewable energy...

4
TESLA.COM/ENERGY MICROGRID CONTROLLER OVERVIEW Optimizes the contribution between renewable energy resources, energy storage systems, and diesel generators in microgrids Curtails the renewable energy resources during low load periods in order to prevent over-supply conditions Manages the energy storage system state-of-energy Dispatches and switches between diesel generator(s) as needed Seamlessly transitions microgrids between Islanded and grid-connected configurations using an islanding contactor relay (SEL700G supported) Manages the site net output during grid-connected operations Provides a real-time monitoring and control interface Reports the system status variables to upstream supervisory systems (i.e. SCADA, EMS, Data Historian) RELIABILITY Warranty 10 years ENVIRONMENTAL SPECIFICATIONS Operating temperature -40 C to 75 C Relative humidity 5% to 95% non-condensing Maximum altitude 2000m o o 2017-03-02

Transcript of Tesla Powerwall 2 Datasheet - GEM Energy · Optimizes the contribution between renewable energy...

Page 1: Tesla Powerwall 2 Datasheet - GEM Energy · Optimizes the contribution between renewable energy resources, energy storage systems, and diesel generators in microgrids Curtails the

TESLA.COM/ENERGY

MICROGRID CONTROLLER

OVERVIEW

Optimizes the contribution between renewable energy resources, energy storage systems, and diesel generators in microgridsCurtails the renewable energy resources during low load periods in order to prevent over-supply conditionsManages the energy storage system state-of-energyDispatches and switches between diesel generator(s) as needed Seamlessly transitions microgrids between Islanded and grid-connected configurations using anislanding contactor relay (SEL700G supported)Manages the site net output during grid-connected operationsProvides a real-time monitoring and control interface Reports the system status variables to upstream supervisory systems (i.e. SCADA, EMS, Data Historian)

RELIABILITY

Warranty 10 years

ENVIRONMENTAL SPECIFICATIONS

Operating temperature -40 C to 75 C

Relative humidity 5% to 95% non-condensing

Maximum altitude 2000m

o o

2017-03-02

Page 2: Tesla Powerwall 2 Datasheet - GEM Energy · Optimizes the contribution between renewable energy resources, energy storage systems, and diesel generators in microgrids Curtails the

TESLA.COM/ENERGY

COMPLIANCE INFORMATION

Compatible with Substation Environmental Immunity Standards

IEC 61000-4-2, IEEE C37.90.3, IEC 61000-4-3, IEEE C37.90.2, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-6, IEC 61000-4-8, IEEE C37.90.1, IEC 60255-26, IEC 60255-21-1

Client Server CommunicationProtocol Support

Modbus RTU, Modbus TCP, DNP3 serial, DNP3 LAN/WAN, IEC 61850 GOOSE, IEC 60870-5-101/104, IEC 61850 MMS

Security

Protection against malware and other cyber security threatsUser and role-based account authenticationLDAP compatibility for central user authenticationCompliant with NERC CIP user authentication, logging and port control requirements

Interactions with SCADA/EMS The System Status Parameters, Controls and Alarms data points listed in the following sections are available via Modbus and DNP3 maps. The control system can also send Email and SMS notifications when alarms are triggered.

SYSTEM STATUS PARAMETERS

Load Status

Per-phase active/reactive power demandPower factorPer-phase current

Power Quality

Per-phase voltageFrequencyTotal harmonic distortion

Photovoltaic System

PV Inverters active/reactive power outputPower factorPer-phase voltage and currentPV inverters fault codesInverter availability status (in-service, faulted, ready, operating)Solar irradiance dataTemperature

Diesel Generator(s)

Active/reactive power outputPower factorPer-phase voltage and currentCircuit breaker statusFault codesRuntime

Energy Storage System

Active/reactive power outputPower factorPer-phase voltage and currentMaximum charge and discharge powerState-of-energyState-of-chargeBESS availability status (in-service, faulted, ready, operating)BESS frequency and voltage droop settings

Protection Relays Breaker status

Controls

Black-start via the energy storage systemBlack-start via the diesel generator(s) System emergency shutdownEnergy storage system reserve energy level settingEquipment lock-out/tag-out for maintenance

ALARMS

Generation/Storage Resources

Active power and reactive power controls failureGenerator remote startup/shutdown failureFault codes reported by the energy storage system, inverters, generator controllersEnergy storage system low state of energy

Protection and metering systemBreakertripSelf-diagnosis alarms

Power Quality Frequency and voltage out of range

Communications StatusLoss of communications with the generator controllers, inverters, battery manage system, IEDs

2017-03-02

Page 3: Tesla Powerwall 2 Datasheet - GEM Energy · Optimizes the contribution between renewable energy resources, energy storage systems, and diesel generators in microgrids Curtails the

TESLA.COM/ENERGY

Monitoring and Control Interface

2017-03-02

Page 4: Tesla Powerwall 2 Datasheet - GEM Energy · Optimizes the contribution between renewable energy resources, energy storage systems, and diesel generators in microgrids Curtails the

TESLA.COM/ENERGY

Monitoring and Control Interface

2017-03-02