![Page 1: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/1.jpg)
Technical Specifications i
JORDAN WATER COMPANY – MIYAHUNA LLC
C-T-21-0005 FARA Phase II Restructuring, Isolation & Rehabilitation of BA08 DMA in
Zarqa Gov.
2021
TENDER DOCUMENTS
VOLUME III
Technical Specifications Preamble to the Bill of Quantities (BOQ), BOQ and Detailed Datasheets for Meter
![Page 2: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/2.jpg)
Technical Specifications
1
1
ACRONYMS
ANSI American National Standards Institute
AWWA American Water Works Association
ASME American Society of Mechanical Engineers
ASTM American Society for Testing and Materials
BS British Standards
BOQ Bill of Quantities
DAP Delivered At Place
DI Ductile Iron
DN Nominal Diameter
DZ
EN
District Zone
European standards
EPDM Ethylene-Propylene-Diene Terpolymer
FARA Fixed Amount Reimbursement Agreement
GIS Geographic Information System
HDPE High Density Polyethylene
ISO International Organization for Standardization
NBR Nitrile Butadiene Rubber
NRW
NSF
Non-Revenue Water
National Science Foundation
PN Nominal Pressure
PRV Pressure Reducing Valve
RPM Revolution Per Minute
SDR Standard Dimension Ratio
SS Stainless Steel
USAID United States Agency for International Development
![Page 3: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/3.jpg)
Technical Specifications
2
2
TECHNICAL SPECIFICATIONS
- All Items shall be procured according to item O under Part IX: Responsibilities of the Parties in the Umbrella FARA, which states that: the authorized USAID Principal Geographic Code for the procurement of goods and services under this associate FARA is Code 937 (the United States, the recipient country, and developing countries other than advanced developing countries). The intent of these specifications is to allow fair competition for suppliers in these geographical locations.
- Certificate of Conformity shall be submitted upon shipping.
![Page 4: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/4.jpg)
Technical Specifications
3
3
1. GENERAL
• AMBIENT CONDITIONS
All pipes, materials and equipment shall be in every respect suitable for storage, installation, use and operation in the conditions of temperature, humidity and The PH and water quality appertaining in Jordan.
Atmospheric temperature in Jordan varies between -10˚C and 50 ˚C.
• POTABLE WATER CERTIFICATION
All pipes, valves, gaskets and materials shall be certified for potable water use by an independent testing laboratory. All material in contact with or likely to come into contact with water for public shall introduced with the requirements of NSF/ANSI 61 (Drinking Water System Components) or BS 6920 (suitability for non metallic products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water intended for human consumption) as well as the Jordanian standard (JS 286/2008), and whenever the regulation is changed it is the supplier responsibility to ensure conformity with any new requirements.
Potable water certificate shall also be submitted for the same batch delivered to Miyahuna, certificates must be in English.
• TOXIC MATERIALS
Pipes and pipeline components, including their protective coatings and joint materials, that will or may come into contact with potable water shall not constitute a toxic hazard, shall not support microbial growth, shall not cause taste or odour, cloudiness or discoloration of the water and shall contain no ingredients that may migrate into water in amounts that are considered to be toxic or otherwise dangerous for health. Non toxicity certificate should be provided in English.
• THIRD PARTY WITNESS
The supplier/contractor shall furnish an original accredited certificate of conformity from the third party inspection agency showing all test results and analysis required by the applicable standard according to which the materials have been manufactured. The third party inspection agency shall under this contract, have witnessed the manufacture and testing operation to verify compliance with the technical specifications and the relevant standard. All certification should be from a certified third party, and the certification should be valid and up to date, in English, and it must be shown in the certificate which batch is being tested to make sure that this certificate is for the right batch delivered to Miyahuna.
The supplier shall propose in his offer at least 3 different international third party companies where Miyahuna will choose one of them.
The third party inspection agency shall verify that all materials used are eligible for the relevant standard productions requirements. No material shall be accepted unless all type and batch release tests have been passed. The third party must clearly identify the material production date / code marked on the pipes, with each batch test performed.
The third party inspection tests certificates shall include the following stages:
![Page 5: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/5.jpg)
Technical Specifications
4
4
1. During manufacturing and testing.
2. Final.
3. Packing.
And the kind of inspection:
1. Review document.
2. Witness inspection (visual and tests).
And the test certificates must show the results.
The manufacture place of all materials, the pipes, specials, fittings and accessories shall be open to inspection by the third party team If any of the supplies, whether complete or in the course of production, were rejected by the Client, they shall be marked or segregated in such a manner satisfactory to the Client as to ensure their subsequent identification as rejected supplies. Disposal of rejected supplies shall be done by and at the Contractor's own expense.
• TESTING AFTER DELIVERY
All materials supplied shall be subjected to acceptance tests carried out by the Royal Scientific Society to confirm that the material are manufactured according to the applicable standards.
In the case the delivery was made on more than one consignment, each consignment will be tested to confirm the compliance with above standard.
NOTE:
ALL TESTS’ COSTS BEFORE AND AFTER THIS ITEM AND WHETHER LOCAL OR ABROAD SHALL BE BORNE BY THE CONTRACTOR AND THE COSTS SHALL BE INCLUDED IN THE TENDER UNIT RATES.
• HANDLING AND TRANSPORTATION
The handling and transportation shall be in accordance with the manufacturer’s recommendations.
The cost of packing shall be included in the contractor rates.
All materials shall be securely packed in crates or boxes for protection against damage during transportation.
All plain ends shall be adequately protected by straw rope secured in place by binding wire or strap. None of the packing will be returnable. The materials supplied shall be of the appropriate grade and quality and shall be adequately protected against the climatic conditions in the Middle East.
All plastic materials shall be protected from direct sunlight and appropriate coverings supplied for use at the delivery and storage areas.
• TRANSPORT AND DELIVERIES
The Contractor shall send to the Engineer, one-week advance notice of all consignments of materials. Every consignment shall be accompanied by a detailed delivery note.
![Page 6: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/6.jpg)
Technical Specifications
5
5
The Contractor shall deliver to and off load the materials onto the storage area as directed by the Engineer. All materials delivered will be examined and inspected by the Engineer and taken over by him.
The Contractor shall provide necessary details to the shipping line on precautions to be taken during loading/unloading, handling & transport of the pipes & fittings and other components. Contractor shall provide to the Engineer a set of recommendations of manufacturer for handling, loading, unloading, transporting and storing of polyethylene pipes and fittings
The Contractor shall arrange reception and storage areas only. aslo shall be responsible for off-loading all materials.
The Contractor shall also be responsible for all handling and transport activities up to and from Miyahuna store-yard, Amman.(Materials provided by Miyahuna)
• The (DDP) price shall include all costs relating to above-mentioned requirements.
• IDENTIFICATION
The contractor shall be responsible to ensure that each separate item, crate, or package has permanently attached to it, in a conspicuous position, an identification plate of weather - resistant material on which are engraved or stamped;
• The Manufacturers Name.
• Contents Description and Quantity.
• Serial Number or Reference Number Identifiable on the Delivery Note and Cross Referenced to the Purchase Order Item References.
• Weight.
The shipment containers shall be marked with the following address;
• Jordan Water Company/ MIYAHUNA L.L.C.
In addition the container shall be marked with the following information;
• Total gross weight.
• Total net weight.
• Packing list reference number.
• MARKINGS OF PIPES AND FITTINGS
Each pipes and fittings shall bear clear and permanent markings. Markings on pipe lengths shall always be at the same end. Painting of data shall be acceptable for all pipe material.
The first five marking given below shall be cast on or cold stamped, the other marking applied by permanent painting.
The marking shall show at least the following information:
• The manufacturer‘s name or mark.
• The identification of the year of manufacture.
![Page 7: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/7.jpg)
Technical Specifications
6
6
• The identification as ductile iron.
• The DN.
• The PN rating of flanges when applicable.
• The reference tops this standard.
• The class designation of centrifugally cast pipes when other than K9.
• Third party.
• MIYAHUNA tender No.
• Dimension (wall thickness).
• Production period ((YEAR)).
• Water,” to indicate that pipes or fittings are intended for potable water”.
• Serial number.
• Batch number.
• Ladle number.
• DOCUMENTS TO BE PROVIDED AT TIME OF TENDER
• Manufacturer’s Authorization Form.
• Potable water certificate.
• Manufacturer experience certificates; a certificate from the manufacturer (self declaration) that he has at least 10 years in the field of production for pipes and fittings.
• Quality assurance certificate (ISO 9001).
• Internal Quality System.
• The supplier/ contractor shall supply full technical specifications and catalogues highlighting the items to be supplied at the time of tender.
• Method of traceability system followed by the manufacturer.
All above documents must be valid and in English.
• DOCUMENTS TO BE PROVIDED UPON DELIVERY
The contractor shall submit at least the following documents:
• Certificate of origin.
• Packing list.
• Third Party certificates.
• Full instruction manuals, which describe the correct methods and procedures necessary to construct the pipeline system in accordance with best practice.
• Upon request, the Contractor has to provide test certificates from the manufacturer’s internal quality control.
![Page 8: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/8.jpg)
Technical Specifications
7
7
• Any other documents requested by the Engineer and the hand over committee.
All above documents must be valid and in English.
Traceability System
At the time of tender the manufacturer shall clearly mention the method by which he can keep records and trace of the manufactured pipes, fittings,…etc. to ensure the capability of going back to the records for the manufactured item in case any problems accrues after the installation.
• SCOPE (FOR SUPPLY AND INSTALL TENDERS)
The Contractor shall furnish and deliver to the site, all pipes and fittings, bolts, nuts, and gaskets, jointing materials and appurtenances as specified and required, to the correct standards and specifications to complete the Works. Pipe fittings and valves shall, if required be suitable for buried installation.
The Contractor shall check for compatibility between all pipes and fittings, either existing or new prior to installation.
• STORAGE OF MATERIALS (SUPPLY AND INSTALL TENDERS)
The Contractors shall be responsible for the storage of all materials purchased under this Contract.
The Contractor shall manage and maintain stockyards that can accommodate all materials purchased and approved by the Engineer under this Contract.
All the materials shall be stored under cover (indoor) and all the fittings should be on sleeves, as required by the manufacturer/supplier /contractor instructions, and shall be regularly inspected by the Engineer staff and maintained to the Engineer’s satisfaction.
The contractor should have a Stock Inventory Material System on software (computerized) and he should generate reports upon request.
• INSPECTION AND REJECTION
The pre-shipment and manufacturer inspection is obligatory and cost for travelling of the appointed member from the Employer as follows
1. (3 persons) for fittings factory 2. (3 persons) for materials (valves , PRV, meters….)
“the pre‐shipment inspection is obligatory and the full cost for travelling for Miyahuna
representatives ("Overseas Pre shipment and inspection for engineers for a week, with all related
expenses including Visas arrangements and costs, hotels transportation and all related fees taxes
airfare tickets and per diems equal to one hundred fifty JD per day for the staff and 250 JD for
top management , director or CEO per day ") shall be borne by the supplier/contractor and
shall be incorporated in the tender prices.
![Page 9: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/9.jpg)
Technical Specifications
8
8
• REFERENCE STANDARDS
Table 1-1: Reference Standards
Standard Number Description
EN 545-2010 Ductile iron pipes, Fittings, accessories and their joints for water pipe lines Requirements and test methods
EN 15664 influence of metallic materials on water intended for human consumption
ISO 4427-1 :2007 Plastics piping systems -- Polyethylene (PE) pipes and fittings for water supply
Part 1 - General
ISO 4427-2 :2007 Part 2 – pipes
ISO 4427-3 :2004 Part 3 - Fittings
EN12201-1 :2010 Plastic piping System for Water Supply – polyethylene (PE)
Part 1-General.
EN12201-2 :2003 Part 2 – pipes
EN12201-3 :2003 Part 3 - Fittings
BS 6920 Testing of non-metallic components with regards to their effect of the quality of water
ISO 14236 :2000 Plastics pipes and fittings – Mechanical joint compression fittings for use with polyethylene pressure pipes in water supply system
ISO 11413: 1996 Plastics pipes and fittings – preparation of test piece assemblies between a polyethylene (PE) pipe and electro fusion fittings
ISO 13954: 1997 Plastics pipes and fittings – peel decohesion test for polyethylene (PE)electro fusion
assemblies of nominal outside diameter greater than or equal to 90 mm
ISO 13955 Plastics pipes and fittings – Crushing decohesion for polyethylene (PE) electro fusion assemblies
ISO 3458: 1976 Assembled joints between fittings and polyethylene (PE) pressure pipes –Test of leakproofness under internal pressure
ISO 3459: 1976 Polyethylene (PE) pressure pipes – Joints assembled with mechanical fittings – Internal under pressure test method and requirements.
ISO 3501 : 1976 Assembled joints between fittings and polyethylene ( PE) pressure pipes –Test of
resistance to pull out
ISO 3503 :1976 Assembled joints between fittings and polyethylene (PE) pressure pipes – Test of leakproofness under internal pressure when subjected to bending.
ISO 3506 Mechanical properties of corrosion-resistant stainless steel fasteners - Part 1: Bolts, screws and studs
EN 681-1 Elastomeric seals - Material requirements for pipe joint seals used in water and drainage applications - Part 1: Vulcanized rubber
EN 681-2 Elastomeric seals - Material requirements for pipe joint seals used in water and drainage
applications - Part 2: Thermoplastic elastomers
EN 601 Aluminium and aluminium alloys - Castings - Chemical composition of castings for use in contact with foodstuff
![Page 10: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/10.jpg)
Technical Specifications
9
9
Standard Number Description
ISO 12176 Plastics pipes and fittings -- Equipment for fusion jointing polyethylene systems -- Part 1: Butt fusion
ISO 13953 Determination of the tensile strength and failure mode of test pieces from a butt-fused joint
ISO 11414 Preparation of polyethylene (PE) pipe/pipe or pipe/fitting test piece assemblies by butt
fusion
![Page 11: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/11.jpg)
Technical Specifications
10
10
2. DUCTILE IRON PIPES
Ductile Iron Pipes specifications
1. General 1.1 Ambient Conditions
All pipes, materials and equipment shall be in every respect suitable for storage, installation, use and operation in the conditions of temperature, humidity and The PH and water quality appertaining in Jordan.
Atmospheric temperature in Jordan varies between -10˚C and 50 ˚C.
1.2 Potable Water Certification
All pipes, gaskets and materials shall be certified for potable water use, and all pipes and materials should be certified as safe for transporting potable water by an independent testing laboratory. All material in contact with or likely to come into contact with water for public shall introduced with the requirements of BS 6920 (suitability for non metallic products for use in contact with drinking water) or any equivalent standard as well as the Jordanian standard (JS 286/2008) and the requirements of EN 15664 ( influence of metallic materials on water intended for human consumption ) or any equivalent standard and the World Health Organization standard (WHO), and whenever the regulation is changed it is the supplier responsibility to ensure conformity with any new requirements. Potable water certificate submitted must be for the same batch delivered to Miyahuna, certificates must be in English and from third party.
1.2 Toxic Materials
All pipes, coating, sealing and lining material shall be certified for potable water use and shall contain no ingredients that may migrate into water in amounts that are considered to be toxic or otherwise dangerous for health. Pipes and pipeline components, including their protective coatings and joint materials, that will or may come into contact with potable water shall not constitute a toxic hazard, shall not support microbial growth, shall not cause taste or odour, cloudiness or discolouration of the water and shall contain no ingredients that may migrate into water in amounts that are considered to be toxic or otherwise dangerous for health . Non toxicity certificate should be provided in English. 1.3 Third Party Witness/pipes
The supplier/contractor shall furnish an original certificate from third party inspection agency showing
all test results and analysis required by the applicable standard according to which the materials have been
manufactured. The third party inspection agency shall under this contract, have witnessed the
manufacture and testing operation to verify compliance with the technical specifications and the relevant
standard. All certification should be from an third party, and the certification should be valid and up to
date, in English, and it must be shown in the certificate which batch is being tested to make sure that this
certificate is for the right batch delivered to Miyahuna.
![Page 12: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/12.jpg)
Technical Specifications
11
11
The supplier shall propose in his offer at least 3 different international third party companies where Miyahuna will choose one of them.
The third party inspection agency shall verify that all materials used are eligible for the relevant standard
productions requirements. No pipe shall be accepted unless all type and batch release tests have been
passed. The third party must clearly identify the pipe production date / code marked on the pipes, with
each batch test performed.
The third party inspection tests certificates shall include the following stages:
1) During manufacturing
2) Final
3) Packing
And the kind of inspection:
1) Review document
2) Witness inspection ( visual and tests)
And the test certificates must show the results.
Before dispatching the supplies another visual inspection shall be done in respect of proper packing and to certify
the Bill of Lading for each shipment.
The manufacture place of all materials the pipes, specials, fittings and accessories shall be open to inspected by the
third party team If any of the supplies, whether complete or in the course of production, is rejected by the Engineer,
they shall be marked or segregated in such a manner satisfactory to the Engineer as to ensure their subsequent
identification as rejected supplies. Disposal of rejected supplies shall be done by and at the Contractor's own
expense.
1.4 Testing at Place of Manufacture/ Mill testing
On the request of the engineer, the contractor/ supplier shall submit a certificate from the manufacturer certifying
that all the items have been mill tested (at the manufactory) and those they have successfully passed the relative
tests prescribed by the relative standards specifications.
1.5 Testing after delivery
All materials supplied shall be subjected to acceptance tests carried out by the Royal Scientific Society to confirm
that the pipes are manufactured according to EN 545-2010.
In the case the delivery was made on more than one consignment, each consignment will be tested to confirm the
compliance with above standard.
NOTE :
ALL COST TESTS BEFORE AND AFTER THIS ITEM AND WETHER LOCAL OR ABROAD SHALL BE BORNE BY THE CONTRACTOR AND THE COSTS SHALL BE INCLUDED IN THE TENDER UNIT RATES.
![Page 13: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/13.jpg)
Technical Specifications
12
12
1.6 Documents to be provided at Time of Tender
1. Conformity to Standard certificate from third party
a. This certificate must confirm the ability of the manufacturer to fulfill all Miyahuna required
specifications and standard including coating and lining for the specified pipes.
b. The certificate should be certified from Jordan Institution for Standard and Metrology (JISM)
with an official letter, the letter should be renewed annually.
2. Potable water certificate from third party
3. Quality assurance certificate (ISO 9001).
4. Internal Quality System
5. Upon request, the Contractor has to provide test certificates from the manufacturer’s internal quality
control.
6. The supplier/ contractor shall supply full technical specifications and catalogues for the items to be
supplied at the time of tender. In addition he shall provide full instruction manuals, which describe the
correct methods and procedures necessary to construct the pipeline system in accordance with best
practice.
7. Detailed manufacturer's proposals for pipes and fittings manufacture, coating and lining etc
8. Method of traceability system followed by the manufacturer
a) All above documents must be valid and in English.
1.7 Documents to be provided upon delivery
The contractor shall submit at least the following documents:
• Certificate of origin.
• Packing list
• Third Party inspection reports (inspection report must include all the tests required in the standard)
• Any other documents requested by the Engineer and the hand over committee
b) All above documents must be valid and in English.
1.8 Traceability System:
At the time of tender the manufacturer shall clearly mention the method by which he can keep records and trace
of the manufactured pipes, fittings,…etc. to ensure the capability of going back to the records for the manufactured
item in case any problems accrues after the installation.
1.8 Supply & Quality of Materials
All materials supplied shall be subject to the Engineer’s approval as following:
![Page 14: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/14.jpg)
Technical Specifications
13
13
c) Approval of the “master list” provided by the Contractor for all supplies and certified by the Engineer
prior to shipment and
d) Pre-shipment inspection and certified quality and quantity of the supplies by must be approved
including verification of all shipment documents. A pre-dispatch inspection shall be done in the
factory prior to supply to MHYA. stores by the third party
e) Inspection and approval of all supplied materials on arrival on site, of quality and quantity by the Engineer.
and this activities will not cancel any local required test
Locally manufactured materials in Jordan must be tested and marked by RSS. Inspection or approval by the
Engineer of any equipment or materials shall not release the Contractor from any of his obligations under this
Contract.
All information and specifications relating to products and materials proposed for this Contract, must accompany
each tender submission.
All information and copy of detailed specifications related to all products and materials proposed
for this Contract must be attached to submittals, in addition to all items mentioned under 1.6
section.
1.13 Scope (for Supply and install Tenders)
• The Contractor shall furnish and deliver to the site, all pipes and fittings, bolts, nuts, and gaskets, jointing
materials and appurtenances as specified and required, to the correct standards and specifications to
complete the Works. Pipe fittings and valves shall, if required be suitable for buried installation.
• The Contractor shall check for compatibility between all pipes and fittings, either existing or new prior to
installation.
1.14 Markings of Pipes and fittings
Each pipes and fittings shall bear clear and permanent markings. Markings on pipe lengths shall always be at
the same end. Painting of data shall be acceptable for all pipe material.
The first five marking given below shall be cast on or cold stamped, the other marking applied by permanent
painting .
The marking shall show at least the following information:
• The manufacturer ‘s name or mark
• The identification of the year of manufacture
• The identification as ductile iron
• The DN
• The PN rating of flanges when applicable
• The reference top this standard
• The class designation of centrifugally cast pipes
• Third party
• MIYAHUNA tender No
• Dimension (wall thickness)
![Page 15: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/15.jpg)
Technical Specifications
14
14
• Production period (( YEAR ) )
• Water , ” to indicate that pipes or fittings are intended for potable water”
• Serial number
• Batch number
• Ladle number
1.15 Handling and transportation
• The cost of packing shall be included for in the contractor rates.
• All materials shall be securely packed in crates or boxes for protection against damage during transportation.
• All plain ends shall be adequately protected by straw rope secured in place by binding wire or strap. None of
the packing will be returnable. The materials supplied shall be of the appropriate grade and quality and shall be
adequately protected against the climatic conditions in the Middle East.
• All plastic materials shall be protected from direct sunlight and appropriate coverings supplied for use at the
delivery and storage areas.
1.16 Identification
• The contractor shall be responsible to ensure that each separate item, crate, or package has permanently
attached to it, in a conspicuous position, an identification plate of weather - resistant material on which are
engraved or stamped;
• The Manufacturers Name
• Contents Description and Quantity
• Serial Number or Reference Number Identifiable on the Delivery Note and Cross Referenced to the Purchase
Order Item References.
• Weight
• The shipment containers shall be marked with the following address;
• Jordan Water Company/ MIYAHUNA L.L.C.
• In addition the container shall be marked with the following information;
• Total gross weight
![Page 16: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/16.jpg)
Technical Specifications
15
15
• Total net weight
• Packing list reference number
1.17 Storage of Materials (Supply and Install Tenders)
• The Contractors shall be responsible for the storage of all materials purchased under this Contract.
• The Contractor shall manage and maintain stockyards that can accommodate all materials purchased and
approved by the Engineer under this Contract.
• All the materials shall be stored under cover (indoor) and all the fittings should be on sleeves, as required
by the manufacturer/supplier /contractor instructions, and shall be regularly inspected by the Engineer
staff and maintained to the Engineer’s satisfaction.
• The contractor should have a Stock Inventory Material System on software (computerized) and he should
generate reports upon request.
1.18 Reference standards
• Table 2.2 Reference Standards
Standard Number Description
EN 545 -2010 Ductile iron pipes, Fittings, accessories and their joints for water pipe lines
Requirements and test methods
ISO 4179-1985 Ductile iron pipes for pressure and non-pressure pipelines –Centrifugal cement mortar lining – General Requirements
ISO 8179-1 Ductile iron pipes –External zinc coating
Part 1: Metallic zinc with finishing layer
ISO 8179-2 Ductile iron pipes –External zinc coating
Part 2: Zinc Rich paint with finishing layer
EN 15664 influence of metallic materials on water intended for human consumption
ISO 9001 Quality Management Systems
![Page 17: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/17.jpg)
Technical Specifications
16
16
2. Technical Specifications 2.1 General
DI pipes shall be centrifugally cast (C Class), with socket and spigot ends, EPDM rubber gaskets, according to
EN545:2010
2.2 Pipe selection
DI PIPES ACCORDING TO EN 545-2010
The joints of ductile iron (DI) pipes and fittings shall be TYTON type.
• Outside protection coating:
Shall be of 400 g/m² metallic zinc Aluminum Alloy (85%+15%) plus epoxy finishing coat according to EN 545,
applied also on socket inside, suitable for ground condition I and II and III. The external surface of the pipe spigot
end at a minimum length of 250 mm shall have nontoxic epoxy paint applied to a minimum dry film thickness of
100 microns. The internal surface of the socket end shall be painted with a layer of zinc rich epoxy paint 150
g/m²(zinc content not less than 85%° plus a layer of non toxic epoxy paint to a minimum dry film thickness of
100 microns.
• Inside protection lining:
Cement mortar according to ISO 4179 – 1985.
2.2 Length of Pipes
Standard length for pipes is 6 meter for transport in bundles or 5.5 -5.8 meters for transport in open top containers.
2.3 Testing
The manufacturer shall demonstrate the conformity of his products with the standards by submitting the below
performance tests specified in the standards:
• Compressive strength of the cement mortar lining.
• Leak tightness of flexible joints to positive internal pressure.
![Page 18: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/18.jpg)
Technical Specifications
17
17
• Leak tightness of flexible joints to negative internal pressure.
• Leak tightness of flexible push-in joints to positive external pressure.
• Leak tightness of flexible joints to dynamic internal pressure.
• Leak tightness and mechanical resistance of flanged joints.
• Leak tightness and mechanical resistance of screwed and welded flanges.
The test should include:
• Dimensions Examination.
• Wall Thickness.
• External Diameter.
• Internal Diameter.
• Length
• Straightness of the pipes
• Ovality Test of the Pipes.
• Cement Lining Thickness.
• Tensile Test.
• Elongation test
• Hydrostatic pressure test.
• Hardness Test.
• Microstructure Examination supported by pictures
• thickness of external paint coating
• works leak tightness test for pipes and fittings
![Page 19: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/19.jpg)
Technical Specifications
18
18
Appendix 1
SCHEDULES OF PARTICULARS
DUCTILE IRON PIPES
DESCRIPTION DETAILS
________________________________________________________________________________
DUCTILE IRON PIPES
Diameter : ___________________________________
Manufacturer : ___________________________________
Country of Origin : ___________________________________
Type : ___________________________________
Type of sockets (not restrained) : ____________________________________
Type of sockets (restrained) : ____________________________________
According to EN Standard : ____________________________________
Outside corrosion protection (material1/material2): ____________________________________
Thickness of corrosion protection [mm1/mm2]: ____________________________________
Suitable for ground condition* : ____________________________________
Rubber gaskets (material/standard): ____________________________________
Non Toxic Certificate provided for Lining Material : _______________
![Page 20: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/20.jpg)
Technical Specifications
19
19
Non Toxic Certificated provided for Rubber Seals : _______________
* optional
PIPE Diameter DN _______:
Outside diameter [mm] : ____________________________________
Wall thickness [mm] : ____________________________________
Internal cement lining [mm] : ____________________________________
PFA (allowable operating pressure) [bar] : ____________________________________
Weight [kg] : ____________________________________
PIPE Diameter DN _______ :
Outside diameter [mm] : ____________________________________
Wall thickness [mm] : ____________________________________
Internal cement lining [mm] : ____________________________________
PFA (allowable operating pressure) [bar] : ____________________________________
Weight [kg] : ____________________________________
PIPE Diameter DN _______:
Outside diameter [mm] : ____________________________________
Wall thickness [mm] : ____________________________________
Internal cement lining [mm] : ____________________________________
PFA (allowable operating pressure) [bar] : ____________________________________
Weight [kg] : ____________________________________
![Page 21: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/21.jpg)
Technical Specifications
20
20
PIPE Diameter DN _______:
Outside diameter [mm] : ____________________________________
Wall thickness [mm] : ____________________________________
Internal cement lining [mm] : ____________________________________
PFA (allowable operating pressure) [bar] : ____________________________________
Weight [kg] : ____________________________________
NOTE:
1) If features are not applicable - enter N / A
2) Data have to be filled in „LEGIBLY“
The following technical documents shall be submitted together with this „Schedule of Particulars“:
a) a technical leaflet of DI pipe with specification
b) all nontoxic certificates
![Page 22: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/22.jpg)
Technical Specifications
21
21
3. HIGH DENSITY POLYETHYLENE PIPES
1. General 1.1 Ambient Conditions
All pipes, materials and equipment shall be in every respect suitable for storage, installation, use and operation in the conditions of temperature, humidity and The PH and water quality appertaining in Jordan.
Atmospheric temperature in Jordan varies between -10˚C and 50 ˚C.
1.2 Potable Water Certification
All pipes and materials shall be certified for potable water use, and all pipes and materials should be certified as safe for transporting potable water by an independent testing laboratory. All material in contact with or likely to come into contact with water for public supply shall be introduced with the requirements of BS 6920 (suitability for non metallic products for use in contact with drinking water) or any equivalent standard as well as the Jordanian standard (JS 286/2008) and the World Health Organization standard (WHO), and whenever the regulation is changed it is the supplier responsibility to ensure conformity with any new requirements. Potable water certificate submitted must be for the same batch delivered to Miyahuna, certificates must be in English 1.3 Toxic Materials
Pipes and pipeline components, including their protective coatings and joint materials, that will or may come into contact with potable water shall not constitute a toxic hazard, shall not support microbial growth, shall not cause taste or odour, cloudiness or discolouration of the water and shall contain no ingredients that may migrate into water in amounts that are considered to be toxic or otherwise dangerous for health . Non toxicity certificate should be provided. 1.4 Third Party Witness
1.4.1 General
The supplier shall furnish an original certificate from third party inspection agency showing all test results and
analysis required by the applicable standard (ISO 4427 /2007) according to which the materials have been
manufactured. The third party inspection agency shall under this contract, have witnessed the manufacture and
testing operation to verify compliance with the technical specifications and the relevant standard. The third party
inspection agency shall verify that all materials used are eligible for the relevant standard productions requirements.
All certification should be from a certified and approved third party, and the certificates must be related to the
same batch delivered to Miyahuna, all certificates must be valid and written in English.
1.4.2 Pipes
For pipes third Party shall verify that all pipes are produced in compliance with ISO 4427-2/2007, EN12201 or
equivalent, all batch release tests shall be witnessed and certified by an approved third party, and No pipe shall be
accepted unless all type and batch release tests have been passed. The third party must clearly identify the pipe
production date / code marked on the pipes, with each batch test performed.
![Page 23: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/23.jpg)
Technical Specifications
22
22
1.5 Testing after delivery
All materials supplied to the site in Jordan shall be subjected to acceptance tests carried out by the Royal Scientific Society. Or similar accredited authority. The test should confirm that the materials and pipes are manufactured according to ISO 4427, EN12201 or equivalent; all Tests required for polyethylene pipes must be performed according to the above standards. If any of the tests mentioned in the standards cannot be performed by the Royal Scientific Society then the supplier should provide a third party certificate for those tests taking into considerations all the statements mentioned in “third party witness” section.
All testing costs should be borne by the supplier in all cases.
1.6 Pipes Packing and Protection
• All pipes shall be bundled or packaged in such a manner as to provide adequate support and protection for the
ends during transportation from the manufacturer to the Purchaser. All special provisions for ocean shipment
shall be provided.
• The packaging of pipes by the manufacturer is normally consistent with the requirement to prevent damage
and to comply with safety considerations. Usually pipes are delivered strapped into convenient bundles or banded
coils. All ends must be closed with caps.
1.7 Identification
The supplier shall be responsible to ensure that each separate item, crate, or package has permanently attached to it, in a conspicuous position, an identification plate of weather - resistant material on which are engraved or stamped;
• The Manufacturers Name
• Contents Description and Quantity
• Serial Number or Reference Number Identifiable on the Delivery Note and Cross
Referenced to the Purchase Order Item References.
• Weight
The shipment containers shall be marked with the following address;
Jordan Water Co. – MIYAHUNA L.L.C.
Tender Number – variable
In addition the container shall be marked with the following information;
• Total gross weight
• Total net weight
• Packing list reference number
1.8 Transport and Deliveries
![Page 24: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/24.jpg)
Technical Specifications
23
23
• The supplier shall send to the Purchasers, one-week advance notice of all consignments of materials.
Every consignment shall be accompanied by a detailed delivery note.
• The supplier shall deliver to and off load the materials onto the storage area as directed by the Purchasers.
All materials delivered will be examined and inspected by the Purchaser and taken over by him.
• The Supplier shall provide necessary details to the shipping line on precautions to be taken during
loading/unloading, handling & transport of the pipes & fittings and other components. Supplier
shall provide to the purchaser a set of recommendations of manufacturer for handling, loading,
unloading, transporting and storing of polyethylene pipes and fittings
• The Purchaser shall arrange reception and storage areas only. The supplier shall be responsible for off-
loading all materials.
• The materials shall be delivered to the Purchaser at Miyahuna stores, Amman or any other place chosen
by the Purchaser.
• The supplier shall also be responsible for all handling and transport activities up to Miyahuna store-yard,
Amman
• The (DDP) price shall include all costs relating to above-mentioned requirements.
1.9 Handling
Care shall be taken during loading, transporting, and unloading to prevent damage to the pipes,. Under no circumstances shall pipes or fittings be dropped or rolled against one another. All pipes and fittings shall be examined. Any damaged materials must be rejected by the Purchasers.
1.10 Details to be provided at the time of tender
1. Conformity to standard certificate from third party
2. Manuals and technical catalogues
3. Dates of batches or consignment deliveries.
4. The supplier shall state which of the sections of the schedule of requirements he proposes to price and
supply.
5. Any alternative standards proposed including demonstration of equivalency or superiority to the standard
specified, if allowed.
6. Any alternative materials proposed including demonstration of equivalency or superiority to the standard
specified, these alternative materials should be subjected to the clients approval.
7. Where the supplier offers alternative standards, materials to those specified, the supplier shall provide
prices for those specified and the alternatives proposed.
![Page 25: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/25.jpg)
Technical Specifications
24
24
8. The supplier shall include in his price for the training elements related to the materials he proposes to
supply and shall list the elements of training offered, if needed or requested.
9. The supplier shall provide prices for the equipment applicable to the sections of the schedule of
requirements he intends to price.
10. The supplier shall provide full details of his materials tests and procedures.
11. Any alternative proposed specification for combined tracer and marker tape.
12. ISO or EN certification for management and product.
13. CV’s of proposed training staff, if necessary.
14. Costs of Trainers expenses, if requested.
15. Training program, if requested.
1.11 Manuals and Technical Specifications
The supplier shall supply full technical specifications for the items to be supplied at the time of tender. In addition
he shall provide full instruction manuals, which describe the correct methods and procedures necessary to
construct the pipeline system in accordance with best practice. Conformity to standard certificate must be supplied
at time of tender where this certificate must be issued from third party and valid up to date.
1.12 Additional Services
The supplier shall provide details of additional services, which he can provide e.g. technical advice and support
and, in particular, shall state his capability for supporting the project in the Amman location at the time of tender.
2. Polyethylene pipes 2.1 Technical specifications
The polyethylene pipes shall conform to the requirements of Polyethylene (PE) pipes for water supply under
pressure – Specification (ISO 4427-1/2:2007), (EN12201-1, EN12201-2) or equivalent standard in which a
supplier must submit a copy of that standard and a proof of equivalency to the above specifications.
Conformity to standard certificate must be supplied at time of tender where this certificate must be issued from
third party and valid up to date.
The pipes should have the following properties:
• Pressure class : PN 16 or PN 25 ( According to contract documents)
• The Standard Dimension Ratio (SDR) : SDR 11
![Page 26: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/26.jpg)
Technical Specifications
25
25
• Material Designation : PE 100
2.2 Length of Pipes
The following table shows the length of the pipes according to the diameter.
Table 3.1 length of pipe
Diameter of pipe(mm) Length of pipe (m)
Up to 63 50 or 100
125 ( 50 or 100 :coils) (upon request), Or
( 12 m : standard pipes ) ( for maintenance dept. uses ) ( upon request)
180 and above 12 or standard pipes
2.3 Markings of Pipes
All PE pipes shall be indelibly marked at maximum intervals of one meter.
The marking shall show at least the following information:
• “MIYAHUNA”
• Manufacture’s name, logo and/or trade mark
• Dimensions (nominal diameter)
• Materials, material class (i.e. PE 100) and pressure class (PN 16)
• Production period (date and code)
• “Water” to indicate that pipes are intended for potable water
• Serial number
• Batch number
• Standard number
• Standard Dimension Ratio (SDR).
For direct purchase procurements order the marking depends on the value of the procurements order
Appendix 1
Reference standards
![Page 27: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/27.jpg)
Technical Specifications
26
26
Standard Number Description
ISO 4427-1 :2007 Plastics piping systems -- Polyethylene (PE) pipes and fittings for water supply Part 1 - General
ISO 4427-2 :2007 Part 2 – pipes
ISO 4427-3 :2004 Part 3 - Fittings
EN12201-1 :2010 Plastic piping System for Water Supply – polyethylene (PE) Part 1-General.
EN12201-2 :2003 Part 2 – pipes
EN12201-3 :2003 Part 3 - Fittings
BS 6920 Testing of non-metallic components with regards to their effect of the quality of water
ISO 14236 :2000 Plastics pipes and fittings – Mechanical joint compression fittings for use with polyethylene pressure pipes in water supply system
ISO 11413: 1996 Plastics pipes and fittings – preparation of test piece assemblies between a polyethylene (PE) pipe and electro fusion fittings
ISO 13954: 1997 Plastics pipes and fittings – peel decohesion test for polyethylene (PE)electro fusion assemblies of nominal outside diameter greater than or equal to 90 mm
ISO 13955 Plastics pipes and fittings – Crushing decohesion for polyethylene (PE) electro fusion assemblies
ISO 3458: 1976 Assembled joints between fittings and polyethylene (PE) pressure pipes –Test of leakproofness under internal pressure
ISO 3459: 1976 Polyethylene (PE) pressure pipes – Joints assembled with mechanical fittings – Internal under pressure test method and requirements.
ISO 3501 : 1976 Assembled joints between fittings and polyethylene ( PE) pressure pipes –Test of resistance to pull out
ISO 3503 :1976 Assembled joints between fittings and polyethylene (PE) pressure pipes – Test of leakproofness under internal pressure when subjected to bending.
ISO 3506 Mechanical properties of corrosion-resistant stainless steel fasteners - Part 1: Bolts, screws and studs
EN 681-1 Elastomeric seals - Material requirements for pipe joint seals used in water and drainage applications - Part 1: Vulcanized rubber
EN 681-2 Elastomeric seals - Material requirements for pipe joint seals used in water and drainage applications - Part 2: Thermoplastic elastomers
EN 601 Aluminium and aluminium alloys - Castings - Chemical composition of castings for use in contact with foodstuff
ISO 12176 Plastics pipes and fittings -- Equipment for fusion jointing polyethylene systems -- Part 1: Butt fusion
ISO 13953 Determination of the tensile strength and failure mode of test pieces from a butt-fused joint
ISO 11414 Preparation of polyethylene (PE) pipe/pipe or pipe/fitting test piece assemblies by butt fusion
![Page 28: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/28.jpg)
Technical Specifications
27
27
4. GALVANIZED IRON PIPES
1. General 1.1 Ambient Conditions
All pipes, materials and equipment shall be in every respect suitable for storage, installation, use and operation in the conditions of temperature, humidity and The PH and water quality appertaining in Jordan.
Atmospheric temperature in Jordan varies between -10˚C and 50 ˚C.
1.2 Potable Water Certification
All pipes and materials shall be certified for potable water use, and all pipes and materials should be
certified as safe for transporting potable water by an independent testing laboratory. All material in
contact with or likely to come into contact with water for public shall introduced with the requirements
of BS 6920 (suitability for non metallic products for use in contact with drinking water) or any equivalent
standard as well as the Jordanian standard (JS 286/2008) and the requirements of EN 15664 ( influence
of metallic materials on water intended for human consumption ) or any equivalent standard and the
World Health Organization standard (WHO), and whenever the regulation is changed it is the supplier
responsibility to ensure conformity with any new requirements.
Potable water certificate submitted must be for the same batch delivered to Miyahuna, certificates must
be in English and from a third party.
1.3 Toxic Materials
Pipes and pipeline components, including their protective coatings and joint materials, that will or may come into contact with potable water shall not constitute a toxic hazard, shall not support microbial growth, shall not cause taste or odour, cloudiness or discolouration of the water and shall contain no ingredients that may migrate into water in amounts that are considered to be toxic or otherwise dangerous for health . Non toxicity certificate should be provided. 1.4 Third Party Witness
The supplier must submit at least 3 different international third party companies where Miyahuna will choose one of them.
The supplier shall furnish an original certificate from the third party inspection agency showing all test results and analysis required by the applicable standard (EN 10255) according to which the materials have been manufactured. The third party inspection agency shall under this contract. The third party inspection agency shall verify that all materials used are eligible for the relevant standard productions
![Page 29: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/29.jpg)
Technical Specifications
28
28
requirements. All certification should be from a certified and approved third party, and the certificates must be related to the same batch delivered to Miyahuna, all certificates must be valid and written in English. For local manufactured pipes where the third party is the RSS, the testing certificate must be submitted.
1.5 Testing after delivery
All materials supplied to the site in Jordan shall be subjected to acceptance tests carried out by the Royal Scientific Society. Or similar accredited authority. The test should confirm that the materials and pipes are manufactured according to EN 10255 or equivalent; all Tests required in this standard must be performed. If any of the tests mentioned in the standards cannot be performed by the Royal Scientific Society then the supplier should provide a third party certificate for those tests taking into considerations all the statements mentioned in “third party witness” section.
All testing costs should be borne by the supplier in all cases.
1.6 Pipes Packing and Protection
• All pipes shall be bundled or packaged in such a manner as to provide adequate support and protection
for the ends during transportation from the manufacturer to the Purchaser. All special provisions for
ocean shipment shall be provided.
• The packaging of pipes by the manufacturer is normally consistent with the requirement to prevent
damage and to comply with safety considerations. Usually pipes are delivered strapped into convenient
bundles or banded coils. All ends must be closed with caps.
1.7 Transport and Deliveries
• The supplier shall send to the Purchasers, one-week advance notice of all consignments of
materials. Every consignment shall be accompanied by a detailed delivery note.
• The supplier shall deliver to and off load the materials onto the storage area as directed by the
Purchasers. All materials delivered will be examined and inspected by the Purchaser and taken
over by him.
• The Supplier shall provide necessary details to the shipping line on precautions to be taken during
loading/unloading, handling & transport of the pipes & fittings and other components. Supplier
shall provide to the purchaser a set of recommendations of manufacturer for handling, loading,
unloading, transporting and storing of polyethylene pipes and fittings
• The Purchaser shall arrange reception and storage areas only. The supplier shall be responsible
for off-loading all materials.
• The materials shall be delivered to the Purchaser at Miyahuna stores, Amman or any other place
chosen by the Purchaser.
![Page 30: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/30.jpg)
Technical Specifications
29
29
• The supplier shall also be responsible for all handling and transport activities up to Miyahuna
store-yard, Amman
• The (DDP) price shall include all costs relating to above-mentioned requirements.
1.8 Handling
Care shall be taken during loading, transporting, and unloading to prevent damage to the pipes. Under no circumstances shall pipes or fittings be dropped or rolled against one another. All pipes and fittings shall be examined. Any damaged materials must be rejected by the Purchasers.
1.9 Details to be provided at the time of tender
• Conformity to standard certificate from a third party.
• Potable water certificate.
• ISO 9001.
• Manuals and technical catalogues
• Dates of batches or consignment deliveries.
• The supplier shall state which of the sections of the schedule of requirements he proposes to
price and supply.
• Any alternative standards proposed including demonstration of equivalency or superiority to
the standard specified, if allowed.
• Where the supplier offers alternative standards, materials to those specified, the supplier shall
provide prices for those specified and the alternatives proposed.
• The supplier shall provide full details of his materials tests and procedures.
1.10 Documents to be provided upon delivery
The contractor shall submit at least the following documents:
![Page 31: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/31.jpg)
Technical Specifications
30
30
• Certificate of origin.
• Packing list
• Third Party inspection reports (inspection including all the tests required in the standard)
• Any other documents requested by the Engineer and the hand over committee
• All above documents must be valid and in English.
• 1.11 Manuals and Technical Specifications
The supplier shall supply full technical specifications for the items to be supplied at the time of tender.
In addition he shall provide full instruction manuals, which describe the correct methods and procedures
necessary to construct the pipeline system in accordance with best practice. Conformity to standard
certificate must be supplied at time of tender where this certificate must be issued from a certified third
party and valid up to date.
• 1.12 Additional Services
The supplier shall provide details of additional services, which he can provide e.g. technical advice and
support and, in particular, shall state his capability for supporting the project in the Amman location at
the time of tender.
![Page 32: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/32.jpg)
Technical Specifications
31
31
2. Galvanized Iron pipes
1. Galvanized steel pipes must be seam-welded, galvanized threaded pipes (Heavy series) in accordance
with BS.EN 10255 latest edition.
2. The dimensions of the pipes must be according to EN 10255: 2004 as shown in table below:
Nominal Size (DN)
Designation of thread
Outside diameter Wall Thickness
Mass per unit length of bare tube ”socketed “ (kg/m)
Max (mm) Min(mm)
15 1/2” 21.8 21 3.2 1.45
20 3/4 “ 27.3 26.5 3.2 1.88
25 1” 34.2 33.3 4 2.95
50 2” 60.8 59.7 4.5 6.26
80 3” 89.5 88 5 10.5
100 4” 115 113.1 5.4 14.8
3. The pipe shall be supplied screwed in accordance to BS EN 10226-1 part ( 1) and EN 10226-2 part (2)
pipe Threads. And shall have the screw threads clean, well cut and square with axis of the pipe and be
free from excessive burrs. Each pipe shall be supplied with a socket at one end and shall have protecting
ring affixed to the unsocketed end, to prevent damage to the leading thread. The end of each socket shall
chamfered internally.
4. The galvanization shall be done by hot-dip zinc coating process according to EN10240.
5. All pipes shall be straight, cleanly finished, and free from cracks, surface flaws laminations and other
defects and shall have reasonably smooth surface. The overall pipe length when one socket has been
fitted to be (6) meters plus or minus 150 mm.
6- The socket shall in accordance with EN 10255 latest editions.
7- Galvanization test as in EN 10255 latest edition.
8- Each pipe and fitting shall bear the mark of the year of manufacturer, nominal diameter, and the letter
GS on the body of the pipe and fitting. The marks maybe cast on, painted or cold stamped.
![Page 33: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/33.jpg)
Technical Specifications
32
32
Specifications for Welded Steel Pipes DN≥10”
1. General
1.1 Potable Water Certification All pipe, fittings and coating materials shall be certified for potable water use and shall contain no ingredients that may migrate into water in amounts that are considered to be toxic or otherwise dangerous for health, All material in contact with or likely to come into contact with water for public shall introduced with the requirements of Jordanian standard (JS 286) Whenever regulation changed it is the supplier /contractor responsibility to ensure conformity with any new requirements All pipes shall be certified as safe for transporting potable water from third party.
1.2 Toxic Materials
All pipes, coating, sealing and lining material shall be certified for potable water use and shall contain no ingredients that may migrate into water in amounts that are considered to be toxic or otherwise dangerous for health. The Contractor is prohibited to import or to use any of toxic or poisonous materials or sub materials used in piping, kinds of concrete or in soil in any kind of usage.
1.3 Manuals and Technical Specifications 1. The supplier/ contractor shall supply full technical specifications and catalogues for the items to be supplied at the time of tender. In addition he shall provide full instruction manuals, which describe the correct methods and procedures necessary to construct the pipeline system in accordance with best practice.
2. The supplier/ contractor shall provide, at the time of tender, details of the of the equipment necessary to correctly install the pipeline system including welding machines, pipe cutters, chamfering (beveling) tools, joint making equipment, lubrication materials and loose tools.
1.4 Internal Quality System On request of the Engineer, the Contractor has to provide test certificates from the manufacturer’s internal quality
control.
Quality certified ISO 9001, which have continues quality control protocols and which are certified by third party
quality control which is efficient for prove of quality of a particular supply or manufacturer’s batch to be shipped
to Jordan
1.5 Tests and Manufacture Certification The supplier shall submitted the certificates from the manufacture that all pipe and fittings that all pipe and fitting
which supplied under this contract are comply in all respects with the requirement and the standards.
A test certificate that all pipe and fitting have tested in according the requirement and the standards.
1.6 Third Party witness The supplier/contractor shall furnish an original certificate from third party inspection agency showing all test
results and analysis required by the applicable standard according to which the materials have been manufactured.
![Page 34: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/34.jpg)
Technical Specifications
33
33
The third party inspection agency shall under this contract, have witnessed the manufacture and testing operation
to verify compliance with the technical specifications and the relevant standard. All certification should be from a
third party, and the certification should be valid and up to date, in English, and it must be shown in the certificate
which batch is being tested to make sure that this certificate is for the right batch delivered to Miyahuna.
The third party inspection agency shall verify that all materials used are eligible for the relevant standard
productions requirements. No fittings shall be accepted unless all type and batch release tests have been passed.
The third party must clearly identify the fittings production date / code marked on the fittings, with each batch
test performed.
The supplier must submit at least 3 different international third party companies where Miyahuna will
choose one of them.
1.7 Inspections and Testing after Delivery The supplier shall submit a certificate, prior to any delivery, certifying that all items have been mill tested and that
they have successfully passed the relative tests prescribed by the relative standard specifications
Any or all materials and manufactured articles supplied for use in any of the works, shall if so required by the
engineer, shall be tested in advance at the supplier expense in accordance with the tests specified in EN, BS or
ISO or other approved equal standards.
The quality of all materials, the process of manufacture, and the finished materials shall be subject to inspection
and approval by the Purchasers. Such inspection may be made at the site after delivery, and the materials shall be
subject to rejection at any time on account of failure to meet any of the specification requirements. All the expenses
involved in inspection and testing material shall be borne by the supplier.
1.8 Tests and Manufacture Certification
The supplier shall submitted the certificates from the manufacture that all pipe and fittings that all pipe and fitting
which supplied under this contract are comply in all respects with the requirement and the standards. A test
certificate that all pipe and fitting have tested in according the requirement and the standards. All pipe and fitting
shall be tested hydraulically before coating, all pipe and fitting shall be capable of withstanding a hydraulic test
pressure of 1.5 the nominal pressure. Holiday test and adhesion test should be also to be done.
1. 9 Handling and transportation The coated and lined pipes shall be transported through extreme climate, so manufacturer must take into
account the choice of material.
• The cost of packing shall be included for in the contractor rates.
• Protection of coated and lined pipes against damages during storage, transport and handling is required either
by using straw or wood wool pads.
![Page 35: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/35.jpg)
Technical Specifications
34
34
2. 1. 10 Documents to be provided at Time of Tender
9. Conformity to Standard certificate from third party
a. This certificate must confirm the ability of the manufacturer to fulfill all Miyahuna required
specifications and standard including coating and lining for the specified pipes.
b. The certificate should be certified from Jordan Institution for Standard and Metrology (JISM)
with an official letter, the letter should be renewed annually.
2. Potable water certificate
3. Quality assurance certificate (ISO 9001).
4. Internal Quality System
5. Upon request, the Contractor has to provide test certificates from the manufacturer’s internal quality
control.
6. The supplier/ contractor shall supply full technical specifications and catalogues for the items to be supplied
at the time of tender.
7. Detailed manufacturer's proposals for pipes and fittings manufacture, coating and lining etc
All above documents must be valid and in English.
3. 1.11 Documents to be provided upon delivery
The contractor shall submit at least the following documents:
1. Certificate of origin.
2. Packing list
3. Third Party inspection reports (inspection including all the tests required in the standard)
4. Any other documents requested by the Engineer and the hand over committee
All above documents must be valid and in English.
2. Technical Specifications
2.1 Materials Sheet metal used for spiral welded steel pipes must have the same quality over the whole length of the tube; beads must have no sharp, cutting or protruding edges neither on the inside nor the outside. They shall be continuously welded. Tubes must be exposed to a hydraulic pressure test at the factory which, unless specified otherwise, shall be carried out at such pressures that the strain which the metal is subjected during tests will not exceed 48% of the minimum breaking strength. These tests are to be carried out correctly and the Contractor will furnish proof that factory tests were duly carried out.
2.2 Length of Pipes
Pipes shall have an average length of 6 and / or 12 meters and as approved by the Engineer
![Page 36: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/36.jpg)
Technical Specifications
35
35
2.3 Steel Grade The pipes shall be in accordance with (API - 5L, Grade of steel, x 42), or approved equivalent standards, high-tensile, welded steel pipes.
2.4 Dimensions
The wall thickness and the minimum mill-inspection test pressures shall be as follows:
Nominal dia. (ND) inch
Outside diameter (mm) (inch)
Wall Thickness ( mm )
Test Pressure (kg/cm2)
10 ¾” 273.10 10 3/4” 5.6 100
12 ¾” 323.9 12 3/4” 6.4 96
16” 406.40 16” 6.4 77
20” 508.00 20” 7.1 73
24” 610.00 24” 7.1 61
32” 813.00 32” 9.5 61
2.5 Working Pressure The nominal working pressure of all pipes shall not be less than 60 bar
2.6 Joints
Option 1 : Socket & Spigot Joints Joints shall be slip joints (socket and spigot), joints shall meet all radiography, X-ray, thickness,
dimension, mechanical and other requirements of DIN.
The thickness of the slip joint, which must be part of the pipe, shall be greater than or equal to the pipe
thickness.
The joint shall be welded externally in the field and shall be completed internally by a rubber ring built
into the socket. The length of the socket shall be such that the rubber ring does not undergo any damage
during the field welding operation.
The jointing ring shall be of ethylene propylene rubber (EPDM) or styrene butadiene rubber (SBR) to
an approved shape and shall be securely fitted, by gluing in the plant into the sockets against the cement
mortar lining.
All welded and flanged joints of steel pipes shall be protected and coated with the same coating material
of pipes.
Option 2 : Beveled end End of pipes must be calibrated and beveled by 30º degrees ( plus or minus 5º degrees ) for elecric
fusion butt welding.
![Page 37: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/37.jpg)
Technical Specifications
36
36
All welded and flanged joints of steel pipes, shall be protected and coated with the same coating
materials of the steel pipes.
2.7 Internal lining and external coating
2.7.1 Internal Lining
The internal cement mortar lining shall be of 6.0 mm. and conform to all relevant requirements of BS. 534 / 1990 or AWWA. C.205 - 85 .
The unlined and / or uncoated wall of the pipe shall be protected by suitable harmless approved bituminous or epoxy paint .
The internal lining thickness shall not be less than the minimum thicknesses given in the following table :
Nominal Diameter (ND) inch
Minimum thickness (mm) BS.534.1990 AWWA.C.205-85
10 6 (+2 , -0) 6 (+3.2 , -1.6)
12 6 (+2 , -0) 8 (+3.2 , -1.6)
16 7 (+2 , -0) 8 (+3.2 , -1.6)
20 7 (+2 , -0) 8 (+3.2 , -1.6)
24 7 (+2 , -0) 10 (+3.2 , -1.6)
32 10 (+3.2 , -1.6)
2.7.2 External coating
External coating of steel pipes and fittings shall be polyethylene sheathing (reinforced type) according to DIN. (30670), designation: Reinforced sheathing (V). The polyethylene sheathing shall be applied at manufacturer's works (plant) extruded and melted on and homogeneous to steel pipes with API 5L-X42 for buried installation . Between the polyethylene sheathing and the pipe steel there shall be an adhesive film which is applied electro-statically. The polyethylene sheathing shall be made continuous extrusion and the adhesive film shall be firmly bonded to the steel surface. The coating shall be spark-free when tested with a Holiday detector at 25000 volts. The minimum coating thickness shall be 3.0 mm for pipes of nominal diameters up to 20”, and 3.50 mm for 24” diameter pipes. In addition to tests to DIN 30670 for coating and coating materials, the coating shall be tested for cathodic disbonding in accordance with ASTM G8. The polyethylene coating shall be capable of operating at a continuous temperature up to 50 C. without any effect on coating and bonding. The polyethylene and adhesive shall stop at a distance of 100mm plus the insert of the pipe for the spigot and 100mm for the end of the socket of the pipe.
![Page 38: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/38.jpg)
Technical Specifications
37
37
2.8 Marking The material shall be marked with the manufacturer's symbol or mark in addition to the code number, standard specification, and the inspector stamp. The pipes as well shall be stamped with the purchaser symbol, "Miyahuna"
Insulation Materials for Joints of All Pipes Sizes: Sufficient quantity of insulating materials shall be included to cover the joints and fittings after welding the pipes and its cost shall be deemed to be included in the respective unit price .
The bidder must give full information, details, technical data require in attached sheets and must also give full technical specifications of his bid in addition to manufacturer catalogue and standards, as well as the chemical and physical analysis.
Item 1 2 3 4 5 6
Diameter 10” 12” 16” 20” 24” 32”
Nominal Diameter
Outside Diameter
Wall Thickness
Working pressure
Test pressure
Wt/meter (bare)
WT/meter with
Length of pipe
Standards
Manufacturer
Country of origin
Welding process
Type of welding
Type of lining
Thick. Of lining
Type of coating
Thick. of coating
![Page 39: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/39.jpg)
Technical Specifications
38
38
2-DUCTILE IRON FITTINGS PECIFICATIONS
Ductile Iron Fittings Specifications
Table of Contents 1. General ............................................................................................................................................................ 43
1.1 Potable Water Certification ................................................................................................................... 43
1.2 Toxic Materials ........................................................................................................................................ 43
1.3 Third Party witness ................................................................................................................................. 32
1.4 Testing after delivery............................................................................................................................... 43
1.5 Fittings packaging .................................................................................................................................... 43
1.6 Identification ............................................................................................................................................ 43
2. DUCTILE IRON FITTINGS .................................................................................................................... 40
2.1 General ...................................................................................................................................................... 40
2.2 Materials .................................................................................................................................................... 41
2.3 Design ....................................................................................................................................................... 41
2.4 COATING ............................................................................................................................................... 41
2.5 Documents to be provided at Time of Tender .................................................................................. 59
2.6 Documents to be provided upon delivery .......................................................................................... 34
2.7 Markings of fittings.............................................................................................................................. 43
•
• 1. General
2. 1.1 Potable Water Certification
All fittings, gaskets and materials shall be certified for potable water use, and all pipes and materials should be
certified as safe for transporting potable water by an independent testing laboratory. All material in contact with
![Page 40: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/40.jpg)
Technical Specifications
39
39
or likely to come into contact with water for public shall introduced with the requirements of BS 6920 (suitability
for non metallic products for use in contact with drinking water) or any equivalent standard as well as the Jordanian
standard (JS 286/2008) and the requirements of EN 15664 ( influence of metallic materials on water intended for
human consumption ) or any equivalent standard and the World Health Organization standard (WHO), and
whenever the regulation is changed it is the supplier responsibility to ensure conformity with any new requirements.
Potable water certificate submitted must be for the same batch delivered to Miyahuna, certificates must be in
English and from third party.
3. 1.2 Toxic Materials
All fittings, coating, sealing and lining material shall be certified for potable water use and shall contain no ingredients that may migrate into water in amounts that are considered to be toxic or otherwise dangerous for health. Pipes and pipeline components, including their protective coatings and joint materials, that will or may come into contact with potable water shall not constitute a toxic hazard, shall not support microbial growth, shall not cause taste or odour, cloudiness or discolouration of the water and shall contain no ingredients that may migrate into water in amounts that are considered to be toxic or otherwise dangerous for health . Non toxicity certificate should be provided in English.
4. 1.3 Third Party witness
The supplier/contractor shall furnish an original certificate from third party inspection agency showing
all test results and analysis required by the applicable standard according to which the materials have been
manufactured. The third party inspection agency shall under this contract, have witnessed the
manufacture and testing operation to verify compliance with the technical specifications and the relevant
standard. All certification should be from third party, and the certification should be valid and up to date,
in English, and it must be shown in the certificate which batch is being tested to make sure that this
certificate is for the right batch delivered to Miyahuna.
The third party inspection agency shall verify that all materials used are eligible for the relevant standard
productions requirements. No fittings shall be accepted unless all type and batch release tests have been
passed. The third party must clearly identify the fittings production date / code marked on the fittings,
with each batch test performed.
The supplier must submit at least 3 different international third party companies where Miyahuna will choose one of them.
5. 1.4 Testing after delivery
All materials supplied shall be subjected to acceptance tests carried out by the Royal Scientific Society to confirm
that the pipes are manufactured according to EN 545-2010.
In the case the delivery was made on more than one consignment, each consignment will be tested to confirm the
compliance with above standard.
NOTE :
![Page 41: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/41.jpg)
Technical Specifications
40
40
ALL COST TESTS BEFORE AND AFTER THIS ITEM AND WETHER LOCAL OR ABROAD SHALL BE BORNE BY THE CONTRACTOR AND THE COSTS SHALL BE INCLUDED IN THE TENDER UNIT RATES.
6. 1.5 Fittings packaging
• All fittings must be packed in such a way to allow instant use on site without additional cleaning.
• All fittings shall be securely packed in crates and boxes to prevent damage during delivery. The cost of packing
shall be deemed to be included in the Contract Rates and crates will not be returned.
• Fittings are normally supplied in separate cartons together with any associated small items, such as bolts and
gaskets.
7. 1.6 Identification
The supplier shall be responsible to ensure that each separate item, crate, or package has permanently attached to
it, in a conspicuous position, an identification plate of weather - resistant material on which are engraved or
stamped;
• The Manufacturers Name
• Contents Description and Quantity
• Serial Number or Reference Number Identifiable on the Delivery Note and Cross
Referenced to the Purchase Order Item References.
• Weight
The shipment containers shall be marked with the following address;
Jordan Water Co. – MIYAHUNA L.L.C.
Tender Number – variable
In addition the container shall be marked with the following information;
• Total gross weight
• Total net weight
• Packing list reference number
• 2. DUCTILE IRON FITTINGS
8. 2.1 General
1. Ductile iron fittings shall comply with all specifications and standards mentioned below or
equivalent and compatible.
2. Ductile iron fittings shall be sand cast in accordance with the European Standard EN 545:2010 or
![Page 42: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/42.jpg)
Technical Specifications
41
41
equivalent and compatible.
3. Each Socket joint shall be supplied with its EPDM gasket.
4. All fittings must confirm with the requirements of norms and standards, and should be suitable to
be used in conjunction with pressure pipes to the appropriate EN standards.
5. All fittings must have molded-in identification and appropriate product information
6. All fittings must be packed in such a way as to avoid surface oxidation and should only require
cleaning before installation.
7. The joints of ductile iron (DI) fittings shall be according to the above mentioned standards, and all
flanged for Tapers and T-Piece and for bends spigot-socket TYTON.
9. 2.2 Materials
1. of ductile iron EN-GJS-400-18 acc. to EN 1563 (GGG 400 - DIN 1693) or equivalent and compatible.
2. All gaskets shall be of EPDM rubber according to EN681-1:2006 or equivalent and compatible.
3. Flat gaskets shall be fiber reinforced for PN16, or Flat gaskets of NBR rubber, according to EN681-1:2006 or equivalent and compatible.
10. 2.3 Design
1. Dimension Range: above DN 100
2. Working pressure: PN 16, PN25 or PN40 (based on BOQ)
3. Fittings unless otherwise specified shall be of flanged type compatible with the pipe system
4. Flange dimensions and drilling according to EN 1092-2.
5. Flanged fittings shall be supplied with flat gasket, galvanized 8.8 bolts & nuts & washers according to required
length and size M16, M20, M24, M27.
6. The DI bends shall be designed and manufactured as automatic push-on joint type installed along and with DI
pipes of type socket-spigot, fittings such as T-pieces and tapers shall be of flanged type drilled to required PN.
7. Bolts shall be according to ISO 4016 and nuts to EN 24034 inclusive washers.
11. 2.4 COATING
Epoxy powder coated inside and outside:
All fittings, accessories and pipes not centrifugally cast shall be delivered externally and internally coated either by
a paint coating in conformity with 4.6.2 or by an epoxy coating in conformity with EN 14901
in accordance with quality and test requirements of RAL-GZ 662, RAL 5015 or RAL 5005.
• coating thickness: min. 250 μm
• The epoxy coating adhesion shall achieve an average value of at least 8 MPa and a
minimum single value of 6 MPa
![Page 43: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/43.jpg)
Technical Specifications
42
42
12. 2.5 Documents to be provided at Time of Tender
1. Conformity to Standard certificate from third party. (EN 545:2010) or equivalent and compatible.
a. This certificate must confirm the ability of the manufacturer to fulfill all required
specifications and standard .
b. The certificate should be certified from Jordan Institution for Standard and Metrology
(JISM) with an official letter, the letter should be renewed annually
2. Potable water certificate
3. Quality assurance certificate (ISO 9001).
4. Internal Quality System
5. Upon request, the Contractor has to provide test certificates from the manufacturer’s internal quality control.
6. The supplier/ contractor shall supply full technical specifications and catalogues for the items to be supplied at
the time of tender.
7. Detailed manufacturer's proposals for pipes and fittings manufacture, coating and lining etc
All above documents must be valid and in English.
13. 2.6 Documents to be provided upon delivery
The contractor shall submit at least the following documents:
1. Certificate of origin.
2. Packing list
3. Third Party inspection reports from third party (inspection including all the tests required in the standard)
4. Any other documents requested by the Engineer and the hand over committee
All above documents must be valid and in English.
14. 2.7 Markings of fittings
All fittings shall be legibly and durably marked and shall bear at least the following information:
The marking shall show at least the following information:
• The manufacturer ‘s name or mark
• The identification of the year of manufacture
![Page 44: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/44.jpg)
Technical Specifications
43
43
• The identification as ductile iron
• The DN
• The PN rating of flanges when applicable
• The reference top this standard
• The class designation of centrifugally cast pipes when other than K9
• Third party
• MIYAHUNA tender No
• Production period (( YEAR ) )
• Water , ” to indicate that pipes or fittings are intended for potable water”
![Page 45: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/45.jpg)
Technical Specifications
44
44
3-HIGH DENSITY POLYETHYLENE FITTINGS
1. General 1.1 Ambient Conditions
All fittings, materials and equipment shall be in every respect suitable for storage, installation, use and operation in the conditions of temperature, humidity and The PH of water appertaining in Jordan.
Atmospheric temperature in Jordan varies between varies between -10˚C and 50 ˚C.
1.2 Potable Water Certification
All fittings and materials shall be certified for potable water use, and all fittings and materials should be certified
as safe for transporting potable water by an independent testing laboratory.
All material in contact with or likely to come into contact with water for public supply shall be introduced with the
requirements of BS 6920 (suitability for non metallic products for use in contact with drinking water) or any
equivalent standard as well as the Jordanian standard (JS 286/2008) and the requirements of EN 15664 ( influence
of metallic materials on water intended for human consumption ) or any equivalent standard and the World Health
Organization standard (WHO), and whenever the regulation is changed it is the supplier responsibility to ensure
conformity with any new requirements.
Potable water certificate submitted must be for the same batch delivered to Miyahuna, certificates must be in
English
1.3 Toxic Materials
fittings and pipeline components, including their protective coatings and joint materials, that will or may come into
contact with potable water shall not constitute a toxic hazard, shall not support microbial growth, shall not cause
taste or odour, cloudiness or discolouration of the water and shall contain no ingredients that may migrate into
water in amounts that are considered to be toxic or otherwise dangerous for health .
Non toxicity certificate should be provided.
1.4 Third Party Witness
1.4.1 General
The supplier must submit at least 3 different international third party companies where Miyahuna will choose one of them. The supplier shall furnish an original certificate from the third party inspection agency showing all test results and
analysis required by the applicable standard (ISO 4427 /2007) according to which the materials have been
manufactured. The third party inspection agency shall under this contract, have witnessed the manufacture and
testing operation to verify compliance with the technical specifications and the relevant standard. The third party
inspection agency shall verify that all materials used are eligible for the relevant standard productions requirements.
![Page 46: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/46.jpg)
Technical Specifications
45
45
All certification should be from a certified and approved third party, and the certificates must be related to the
same batch delivered to miyahuna, all certificates must be valid and written in English.
1.4.2 Fittings
For fittings third Party shall verify that fittings are produced in compliance with ISO 4427-3/ 2003, EN12201 or
equivalent, all batch release tests shall be witnessed and certified by an approved third party, and No fitting shall
be accepted unless all type and batch release tests have been passed. The third party must clearly identify the fittings
production date / code marked on the fittings, with each batch test performed
1.5 Testing after delivery
All materials supplied to the site in Jordan shall be subjected to acceptance tests carried out by the Royal Scientific
Society. Or similar accredited authority. The test should confirm that the materials and fittings are manufactured
according to ISO 4427, EN12201 or equivalent; all Tests required for polyethylene fittings must be performed
according to the above standards. If any of the tests mentioned in the standards cannot be performed by the Royal
Scientific Society then the supplier should provide a third party certificate for those tests taking into considerations
all the statements mentioned in “third party witness” section.
All testing costs should be borne by the supplier in all cases.
1.6 Fittings Packing and Protection
• All fittings must be packed in such a way to allow instant use on site without additional cleaning.
• All electro-fusion fittings must be packed in transparent protective bags. The electro-fusion fittings must then
be packed in carton boxes.
• All fittings shall be securely packed in crates and boxes to prevent damage during delivery. The cost of packing
shall be deemed to be included in the Contract Rates and crates will not be returned.
• Fittings are normally supplied in separate cartons together with any associated small items, such as bolts and
gaskets.
1.7 Identification
The supplier shall be responsible to ensure that each separate item, crate, or package has permanently attached to it, in a conspicuous position, an identification plate of weather - resistant material on which are engraved or stamped;
• The Manufacturers Name
• Contents Description and Quantity
• Serial Number or Reference Number Identifiable on the Delivery Note and Cross
Referenced to the Purchase Order Item References.
• Weight
The shipment containers shall be marked with the following address;
Jordan Water Co. – MIYAHUNA L.L.C.
Tender Number – variable
In addition the container shall be marked with the following information;
![Page 47: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/47.jpg)
Technical Specifications
46
46
• Total gross weight
• Total net weight
• Packing list reference number
1.8 Transport and Deliveries
• The supplier shall send to the Purchasers, one-week advance notice of all consignments of materials.
Every consignment shall be accompanied by a detailed delivery note.
• The supplier shall deliver to and off load the materials onto the storage area as directed by the Purchasers.
All materials delivered will be examined and inspected by the Purchaser and taken over by him.
• The Supplier shall provide necessary details to the shipping line on precautions to be taken during
loading/unloading, handling & transport of the pipes & fittings and other components. Supplier
shall provide to the purchaser a set of recommendations of manufacturer for handling, loading,
unloading, transporting and storing of polyethylene pipes and fittings
• The Purchaser shall arrange reception and storage areas only. The supplier shall be responsible for off-
loading all materials.
• The materials shall be delivered to the Purchaser at Miyahuna stores, Amman or any other place chosen
by the Purchaser.
• The supplier shall also be responsible for all handling and transport activities up to Miyahuna store-yard,
Amman
• The (DDP) price shall include all costs relating to above-mentioned requirements.
1.9 Handling
Care shall be taken during loading, transporting, and unloading to prevent damage to the pipes, or fittings. Under no circumstances shall pipes or fittings be dropped or rolled against one another. All pipes and fittings shall be examined. Any damaged materials must be rejected by the Purchasers.
1.10 Details to be provided at the time of tender
• Dates of batches or consignment deliveries.
• The supplier shall state which of the sections of the schedule of requirements he proposes to price and
supply.
• Any alternative standards proposed including demonstration of equivalency or superiority to the
standard specified, if allowed.
![Page 48: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/48.jpg)
Technical Specifications
47
47
• Any alternative materials proposed including demonstration of equivalency or superiority to the
standard specified, these alternative materials should be subjected to the clients approval.
• Where the supplier offers alternative standards, materials to those specified, the supplier shall provide
prices for those specified and the alternatives proposed.
• The supplier shall include in his price for the training elements related to the materials he proposes to
supply and shall list the elements of training offered, if needed or requested.
• The supplier shall provide prices for the equipment applicable to the sections of the schedule of
requirements he intends to price.
• The supplier shall provide full details of his materials tests and procedures.
• Any alternative proposed specification for combined tracer and marker tape.
• ISO or EN certification for management and product.
• CV’s of proposed training staff, if necessary.
• Costs of Trainers expenses, if requested.
• Training program, if requested.
1.11 Documents to be provided upon delivery
The contractor shall submit at least the following documents:
• Certificate of origin.
• Packing list
• Third Party inspection reports (inspection including all the tests required in the standard)
• Any other documents requested by the Engineer and the hand over committee
• All above documents must be valid and in English.
1.12 Manuals and Technical Specifications
The supplier shall supply full technical specifications for the items to be supplied at the time of tender. In addition
he shall provide full instruction manuals, which describe the correct methods and procedures necessary to
construct the pipeline system in accordance with best practice.
1.13 Additional Services
The supplier shall provide details of additional services, which he can provide e.g. technical advice and support
and, in particular, shall state his capability for supporting the project in the Amman location at the time of tender.
![Page 49: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/49.jpg)
Technical Specifications
48
48
2. Polyethylene Fittings
2.1 fittings used for existing networks
Fittings used for polyethylene pipes must be manufactured and tested according to the standards shown in the
following tables. As shown, table 2.1 is standards for fittings for Miyahuna uses, such as maintenance purposes
and storing in warehouses.
2.2 fittings used for new installations
For the new projects, Miyahuna recommends that all fittings should be installed using electro-fusion technology,
table 3.2 shows the standards for the fittings used in the new projects.
2.3 Connection Type
Table 2.3 Connection Type
Diameter of pipe(mm)
Connection Type Standard
25-125 Mechanical or Electro-fusion According to tables: 3.1.a , 3.1.b and 3.2
125 and above Butt welding or Electro-fusion
Machine : ISO 12176 ISO 13953, ISO 11414
The Butt welding machine must be fully automatic
2.4 Design Requirements:
- The design of fittings must ensure that the wires which coiled around the inner part of electro fusion
fittings are built in the body of fittings not separated from it.
- The cutter of PE EF Tapping shall be certified for potable water use.
![Page 50: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/50.jpg)
Technical Specifications
49
49
Table 2.1 Polyethylene fittings on Polyethylene pipes:
No. Description Installation /Type
Standard No Testing method
1. PE Connector
(25mm,32 mm, 63 mm)
Compressio
n
ISO 14236:2000 ISO 3501,ISO 3503,
ISO 3458,ISO 3459
2. PE EF Collar
( 125mm , 180 mm,250 mm,25 mm,32
mm, 63 mm)
Electro
Fusion
ISO 4427:2004 or
Equivalent:
EN 12201-3 :2003
ISO 13955,ISO
13954,
ISO 11413
3. PE Reducer
( 32mmX25mm , 63mmX25mm,63X32)
Compression
ISO 14236:2000 ISO 3501,ISO 3503,
ISO 3458,ISO 3459 4. PE Adaptor
( 2” (63mm) Male, 1” (32mm) Male,
3/4” (25mm) Male) a
Compression
5. PE Flange Adaptor
(125mm , 180 mm, 250 mm)
Electro
Fusion
ISO 4427:2004 or
Equivalent:
EN 12201-3 : 2003
ISO 13955, ISO
13954, ISO 11413
6. PE Tee
(63X63X63mm, 32X32X32mm,
25X25X25mm, 63X63X32
,63X63X25,32X32X25) b
Compression
ISO 14236:2000 ISO 3501,ISO 3503,
ISO 3458,ISO 3459
7. PE EF Tee 180X125(socket) Electro
Fusion
ISO 4427:2004 or
Equivalent:
EN 12201-3 : 2003
ISO 13955, ISO
13954, ISO 11413
8. PE End Cap
(63mm, 32 mm, 25 mm,.......)
Compression
ISO 14236:2000 ISO 3501,ISO 3503,
ISO 3458,ISO 3459 9. PE Elbow 63mm, 32mm ,25 mm Compressio
n 10. PE EF Elbow 900
(180(socket), 125 mm, 250 mm , .....)
Electro
Fusion
ISO 4427:2004 or
Equivalent:
EN 12201-3 : 2003
ISO 13955, ISO
13954, ISO 11413
11. Electro fusion end cap
( 125 mm , 180 mm )
Electro
Fusion
12. PE EF Tapping
( 125*25 , 180*25 , 125*63 ,
125*32,63*32 ,63*25, )
Electro
Fusion
13. PE EF Elbow 450
(180, 125 mm, 250 mm , .....)
Electro
Fusion
ISO 4427:2004 or
Equivalent:
ISO 13955, ISO
13954, ISO 11413
![Page 51: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/51.jpg)
Technical Specifications
50
50
EN 12201-3 : 2003
Table 2.2: Fittings for new installation Tenders
No. Description Installation/ Type
Standard No Testing method
1. PE Connector
(25mm,32 mm, 63 mm)
Electro Fusion
ISO
4427:2
004 o
r E
quiv
alen
t:
EN
12201-3
: 2003
ISO
13955, I
SO
13954, IS
O 1
1413
2. PE EF Collar
(125mm , 180 mm,250mm,25 mm,32mm,
63mm)
Electro Fusion
3. PE Reducer Electro Fusion
4. PE Adaptor
( 2” (63mm), 1” (32mm), 3/4” (25mm) )
Electro Fusion
5. PE Flange Adaptor
(125mm , 180 mm, 250 mm)
Electro Fusion
6. PE Tee b PE Tee
(63X63X63mm, 32X32X32mm,
25X25X25mm, 63X63X32
,63X63X25,32X32X25) b
Electro Fusion
7. PE EF Tee (socket) or saddle branch ( line to
line)
(180X125, 180X180,......)
Electro Fusion
8. PE End Cap
(63mm, 32 mm, 25 mm, ........)
Electro Fusion
9. PE Elbow 63mm Electro Fusion
10. PE EF Elbow (socket)
(180 mm, 125 mm,250mm ......)
Electro Fusion
11. Electro fusion end cap
( 125 mm , 180 mm )
Electro Fusion
12. PE EF Tapping
( 125*25 , 180*25 , 125*63 , 125*32,63*32
,63*25, )
Electro Fusion
13. Connector (25 mm, 32 mm) c Compression ISO 14236:2000 ISO 3501,ISO 3503,
ISO 3458,ISO 3459
a Adapter is used to connect Polyethylene pipes to pipe made from another material, and it should be compression from
one side and male threaded from the other side b It is not allowed to use the weldable outlet Kit c when the installation is near to the customer cabinet ,whether the connection was straight connection or using elbow ,
compression fittings should be used
![Page 52: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/52.jpg)
Technical Specifications
51
51
Annex 1
Reference standards
Standard Number Description
ISO 4427-1 :2007 Plastics piping systems -- Polyethylene (PE) pipes and fittings for water supply Part 1 - General
ISO 4427-2 :2007 Part 2 – pipes
ISO 4427-3 :2004 Part 3 - Fittings
EN12201-1 :2010 Plastic piping System for Water Supply – polyethylene (PE) Part 1-General.
EN12201-2 :2003 Part 2 – pipes
EN12201-3 :2003 Part 3 - Fittings
BS 6920 Testing of non-metallic components with regards to their effect of the quality of water
EN 15664 influence of metallic materials on water intended for human consumption
ISO 14236 :2000 Plastics pipes and fittings – Mechanical joint compression fittings for use with polyethylene pressure pipes in water supply system
ISO 11413: 1996 Plastics pipes and fittings – preparation of test piece assemblies between a polyethylene (PE) pipe and electro fusion fittings
ISO 13954: 1997 Plastics pipes and fittings – peel decohesion test for polyethylene (PE)electro fusion assemblies of nominal outside diameter greater than or equal to 90 mm
ISO 13955 Plastics pipes and fittings – Crushing decohesion for polyethylene (PE) electro fusion assemblies
ISO 3458: 1976 Assembled joints between fittings and polyethylene (PE) pressure pipes –Test of leakproofness under internal pressure
ISO 3459: 1976 Polyethylene (PE) pressure pipes – Joints assembled with mechanical fittings – Internal under pressure test method and requirements.
ISO 3501 : 1976 Assembled joints between fittings and polyethylene ( PE) pressure pipes –Test of resistance to pull out
ISO 3503 :1976 Assembled joints between fittings and polyethylene (PE) pressure pipes – Test of leakproofness under internal pressure when subjected to bending.
ISO 3506 Mechanical properties of corrosion-resistant stainless steel fasteners - Part 1: Bolts, screws and studs
![Page 53: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/53.jpg)
Technical Specifications
52
52
EN 681-1 Elastomeric seals - Material requirements for pipe joint seals used in water and drainage applications - Part 1: Vulcanized rubber
EN 681-2 Elastomeric seals - Material requirements for pipe joint seals used in water and drainage applications - Part 2: Thermoplastic elastomers
EN 601 Aluminium and aluminium alloys - Castings - Chemical composition of castings for use in contact with foodstuff
ISO 12176 Plastics pipes and fittings -- Equipment for fusion jointing polyethylene systems -- Part 1: Butt fusion
ISO 13953 Determination of the tensile strength and failure mode of test pieces from a butt-fused joint
ISO 11414 Preparation of polyethylene (PE) pipe/pipe or pipe/fitting test piece assemblies by butt fusion
![Page 54: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/54.jpg)
Technical Specifications
53
53
4-GALVANIZED IRON FITTINGS
General 1.1 Ambient Conditions
All Fittings, materials and equipments shall be in every respect suitable for storage, installation, use and operation in the conditions of temperature, humidity and The PH and water quality appertaining in Jordan.
Atmospheric temperature in Jordan varies between -10˚C and 50 ˚C.
1.2 Potable Water Certification
All Fittings and materials shall be certified for potable water use, and all fittings and materials should be
certified as safe for transporting potable water by an independent testing laboratory. All material in
contact with or likely to come into contact with water for public shall introduced with the requirements
of BS 6920 (suitability for non metallic products for use in contact with drinking water) or any equivalent
standard as well as the Jordanian standard (JS 286/2008) and the requirements of EN 15664 ( influence
of metallic materials on water intended for human consumption ) or any equivalent standard and the
World Health Organization standard (WHO), and whenever the regulation is changed it is the supplier
responsibility to ensure conformity with any new requirements.
Potable water certificate submitted must be for the same batch delivered to Miyahuna, certificates must
be in English from third party.
1.3 Toxic Materials
Fittings and components, including their protective coatings and joint materials, that will or may come into contact with potable water shall not constitute a toxic hazard, shall not support microbial growth, shall not cause taste or odour, cloudiness or discolouration of the water and shall contain no ingredients that may migrate into water in amounts that are considered to be toxic or otherwise dangerous for health . Non toxicity certificate should be provided. 1.4 Third Party Witness
The supplier must submit at least 3 different international third party companies where Miyahuna will choose one of them.
The supplier shall furnish an original certificate from a third party inspection agency showing all test results and analysis required by the applicable standard (EN 10255/ BS 143) according to which the materials have been manufactured. The third party inspection agency shall under this contract. The third party inspection agency shall verify that all materials used are eligible for the relevant standard productions requirements. All certification should be from a certified and approved third party, and the
![Page 55: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/55.jpg)
Technical Specifications
54
54
certificates must be related to the same batch delivered to Miyahuna, all certificates must be valid and written in English. 1.5 Testing after delivery
All materials supplied to the site in Jordan shall be subjected to acceptance tests carried out by the Royal Scientific Society. Or similar accredited authority. The test should confirm that the materials and fittings are manufactured according to EN 10255 or BS 143 or equivalent; all Tests required in this standard must be performed. If any of the tests mentioned in the standards cannot be performed by the Royal Scientific Society then the supplier should provide a third party certificate for those tests taking into considerations all the statements mentioned in “third party witness” section.
All testing costs should be borne by the supplier in all cases.
1.6 Fittings Packing and Protection
• All fittings must be packed in such a way to allow instant use on site without additional cleaning.
• All fittings shall be securely packed in crates and boxes to prevent damage during delivery. The cost
of packing shall be deemed to be included in the Contract Rates and crates will not be returned.
• Fittings are normally supplied in separate cartons together with any associated small items, such as
bolts and gaskets.
1.7 Transport and Deliveries
• The supplier shall send to the Purchasers, one-week advance notice of all consignments of
materials. Every consignment shall be accompanied by a detailed delivery note.
• The supplier shall deliver to and off load the materials onto the storage area as directed by the
Purchasers. All materials delivered will be examined and inspected by the Purchaser and taken
over by him.
• The Supplier shall provide necessary details to the shipping line on precautions to be taken during
loading/unloading, handling & transport of the fittings & fittings and other components. Supplier
shall provide to the purchaser a set of recommendations of manufacturer for handling, loading,
unloading, transporting and storing of polyethylene fittings
• The Purchaser shall arrange reception and storage areas only. The supplier shall be responsible
for off-loading all materials.
• The materials shall be delivered to the Purchaser at Miyahuna stores, Amman or any other place
chosen by the Purchaser.
• The supplier shall also be responsible for all handling and transport activities up to Miyahuna
store-yard, Amman
• The (DDP) price shall include all costs relating to above-mentioned requirements.
![Page 56: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/56.jpg)
Technical Specifications
55
55
1.8 Handling
Care shall be taken during loading, transporting, and unloading to prevent damage to the fittings. Under no circumstances shall fittings or fittings be dropped or rolled against one another. All fittings and fittings shall be examined. Any damaged materials must be rejected by the Purchasers.
1.9 Details to be provided at the time of tender
• Conformity to standard certificate from third party.
• Potable water certificate.
• ISO 9001.
• Manuals and technical catalogues
• Dates of batches or consignment deliveries.
• The supplier shall state which of the sections of the schedule of requirements he proposes to
price and supply.
• Any alternative standards proposed including demonstration of equivalency or superiority to
the standard specified, if allowed.
• Where the supplier offers alternative standards, materials to those specified, the supplier shall
provide prices for those specified and the alternatives proposed.
• The supplier shall provide full details of his materials tests and procedures.
1.10 Documents to be provided upon delivery
The contractor shall submit at least the following documents:
• Certificate of origin.
• Packing list
• Third Party inspection reports (inspection including all the tests required in the standard)
• Any other documents requested by the Engineer and the hand over committee
• All above documents must be valid and in English.
1.11 Manuals and Technical Specifications
The supplier shall supply full technical specifications for the items to be supplied at the time of tender.
In addition he shall provide full instruction manuals, which describe the correct methods and procedures
necessary to construct the pipeline system in accordance with best practice. Conformity to standard
![Page 57: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/57.jpg)
Technical Specifications
56
56
certificate must be supplied at time of tender where this certificate must be issued from a certified third
party and valid up to date.
2. Galvanized Steel fittings
1. Scope of use
The fitting must be according to EN 10255 or BS 143 or equivalent and shall be used with heavy series
of pipes according to BS EN 10255.
It must also be suitable for potable water use.
2- Designation
The fittings shall be Malleable Cast-Iron Screw down pipe fittings in accordance with BS EN 10242-1995 or
approved equal.
3- Threading
Threads must be in accordance with EN 102266-1 and EN 10226-2 and EN 10226-3
4- Working pressure
![Page 58: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/58.jpg)
Technical Specifications
57
57
Working pressure shall not be less than 16 bar with 24 bar hydrostatic pressure test.
5- Galvanization
The fittings shall be (EE, GF, CRANE or equivalent in quality) , andhave an adequate corrosion protection of
internal and external surfaces by mean of hot dip galvanization according BS EN ISO 1461:1999 galvanization test
is required .
6- Marking
Each fitting shall bear the mark of the year of manufacturer, nominal diameter, and the letter GS on the body of
fitting. The marks maybe cast on, painted or cold stamped.
Specifications for Black Steel Fittings
1. General
1.1 Potable Water Certification All pipe, fittings and coating materials shall be certified for potable water use and shall contain no ingredients that may migrate into water in amounts that are considered to be toxic or otherwise dangerous for health, All material in contact with or likely to come into contact with water for public shall introduced with the requirements of Jordanian standard (JS 286) Whenever regulation changed it is the supplier /contractor responsibility to ensure conformity with any new requirements All pipes shall be certified as safe for transporting potable water by an independent testing laboratory. Potable water certificate submitted must in English and from third party.
1.2 Toxic Materials
All fittings, coating, sealing and lining material shall be certified for potable water use and shall contain no ingredients that may migrate into water in amounts that are considered to be toxic or otherwise
![Page 59: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/59.jpg)
Technical Specifications
58
58
dangerous for health. The Contractor is prohibited to import or to use any of toxic or poisonous materials or sub materials used in piping, kinds of concrete or in soil in any kind of usage.
1.3 Manuals and Technical Specifications 1. The supplier/ contractor shall supply full technical specifications and catalogues for the items to be supplied at the time of tender. In addition he shall provide full instruction manuals, which describe the correct methods and procedures necessary to construct the pipeline system in accordance with best practice.
2. The supplier/ contractor shall provide, at the time of tender, details of the of the equipment necessary to correctly install the pipeline system including welding machines, pipe cutters, chamfering (beveling) tools, joint making equipment, lubrication materials and loose tools.
1.4 Internal Quality System On request of the Engineer, the Contractor has to provide test certificates from the manufacturer’s internal quality
control.
Quality certified ISO 9001, which have continues quality control protocols and which are certified by third party
quality control which is efficient for prove of quality of a particular supply or manufacturer’s batch to be shipped
to Jordan
1.5 Tests and Manufacture Certification The supplier shall submitted the certificates from the manufacture that all pipe and fittings that all pipe and fitting
which supplied under this contract are comply in all respects with the requirement and the standards.
A test certificate that all pipe and fitting have tested in according the requirement and the standards.
1.6 Third Party witness The supplier/contractor shall furnish an original certificate from third party inspection agency showing all test
results and analysis required by the applicable standard according to which the materials have been
manufactured. The third party inspection agency shall under this contract, have witnessed the manufacture and
testing operation to verify compliance with the technical specifications and the relevant standard. All certification
should be from a third party, and the certification should be valid and up to date, in English, and it must be
shown in the certificate which batch is being tested to make sure that this certificate is for the right batch
delivered to Miyahuna.
The third party inspection agency shall verify that all materials used are eligible for the relevant standard
productions requirements. No fittings shall be accepted unless all type and batch release tests have been passed.
The third party must clearly identify the fittings production date / code marked on the fittings, with each batch
test performed.
The supplier must submit at least 3 different international third party companies where Miyahuna will choose
one of them.
![Page 60: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/60.jpg)
Technical Specifications
59
59
1.7 Inspections and Testing after Delivery The supplier shall submit a certificate, prior to any delivery, certifying that all items have been mill tested and that
they have successfully passed the relative tests prescribed by the relative standard specifications
Any or all materials and manufactured articles supplied for use in any of the works, shall if so required by the
engineer, shall be tested in advance at the supplier expense in accordance with the tests specified in EN, BS or
ISO or other approved equal standards.
The quality of all materials, the process of manufacture, and the finished materials shall be subject to inspection
and approval by the Purchasers. Such inspection may be made at the site after delivery, and the materials shall be
subject to rejection at any time on account of failure to meet any of the specification requirements. All the expenses
involved in inspection and testing material shall be borne by the supplier.
1.8 Tests and Manufacture Certification The supplier shall submitted the certificates from the manufacture that all pipe and fittings that all pipe and
fitting which supplied under this contract are comply in all respects with the requirement and the standards.
A test certificate that all pipe and fitting have tested in according the requirement and the standards. All pipe
and fitting shall be tested hydraulically before coating, all pipe and fitting shall be capable of withstanding a
hydraulic test pressure of 1.5 the nominal pressure. Holiday test and adhesion test should be also to be done.
1. 9 Handling and transportation • The cost of packing shall be included for in the contractor rates.
• Protection of coated and lined pipes against damages during storage, transport and handling is required either
by using straw or wood wool pads.
4. 1.10 Documents to be provided at Time of Tender
1. Conformity to Standard certificate from third party.
2. Potable water certificate
3. Manufacturer experience certificates
4. Quality assurance certificate (ISO 9001).
5. Internal Quality System
6. Upon request, the Contractor has to provide test certificates from the manufacturer’s internal quality control.
7. The supplier/ contractor shall supply full technical specifications and catalogues for the items to be supplied at
the time of tender.
8. Detailed manufacturer's proposals for pipes and fittings manufacture, coating and lining etc
All above documents must be valid and in English.
1.11 Documents to be provided upon delivery
The contractor shall submit at least the following documents:
![Page 61: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/61.jpg)
Technical Specifications
60
60
1. Certificate of origin.
2. Packing list
3. Third Party inspection reports (inspection including all the tests required in the standard)
4. Any other documents requested by the Engineer and the hand over committee
All above documents must be valid and in English.
2. Technical Specifications
2.1 Scope of use
The fittings must be made of seamless pipes and shall be in accordance with ANST (B.16.9). The fittings shall be welded to black steel pipes type (API. 5L - X 42).
2.2 Fabrication of Fittings
The fabrications of fittings shall be as follows:
1. Elbows must be fabricated by forging or by hot or cold forming of seamless pipes. 2. Reducers must be fabricated by hot or cold forming and annealing of seamless pipes. 3. Tees must be fabricated by forming of seamless pipe or by cold or hot forming and annealing of seamless
pipes. 4. Caps must be fabricated by hot or cold stamping or forging of plates heat treated. - Fabrication fittings by welding pieces of pipes is not accepted.
2.3 Materials of Fittings
Elbows, Tees, Reducers etc ... must be made of seamless pipe grade WPB. (ASTM. A 234) or approved
equivalent.
2.4 Fittings Thickness & Pressure
The minimum thickness of the black steel fittings shall be sufficient to withstand the pressure rating of their respective pipelines.
2.5 Elbows Bends The Elbows must be of long radius type, but short radius elbows can be offered as an alternative.
![Page 62: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/62.jpg)
Technical Specifications
61
61
2.6 Reducers
The reducers must be concentric. Thickness of each side shall be equal to thickness of related nominal diameter, if thickness of reduced size equal to the thickness of the bigger size, higher thickness will be accepted.
2.7 Straight Equal Tees The straight equal tees, in which the run and branch (out let) is equal in nominal diameter, thickness must
be equal to the thickness of its related nominal diameter.
2.8 Tees Reducing Tees Reducing, in which the Run is bigger than branch (out let) in nominal diameter thickness of the run,
must be equal to the thickness of its related diameter, thickness of the branch (outlet) must equal to its related nominal diameter.
2.9 Coating and Lining All fittings must be lined by corrosion proof materials and must be suitable for potable water. Coating and lining must stop at the beveled ends for the purpose of welding.
2.10 Marking Every fitting must be marked with: - Trade mark. - Nominal Diameter. - Thickness. - Standard.
2.11 Certificate of Compliance Certificates of compliance of required standards must submit.
![Page 63: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/63.jpg)
Technical Specifications
62
62
5. REPAIR CLAMPS
• SCOPE
This Specification specifies the requirements for the design, materials and in-service performance of mechanical stainless steel repair clamps for waterworks purposes.
This Specification designated for applications involving rigid pipes, typically ductile iron (DI), grey cast iron (CI), and steel (S). Also, for applications involving flexible pipes, typically un-plasticized polyvinlchloried (PVC-U) and high-density polyethylene (HDPE).
All materials and equipment shall be in every respect suitable for storage, installation, use and operation in the conditions of temperature, humidity and The PH and water quality appertaining in Jordan.
Atmospheric temperature in Jordan varies between -10˚C and 50 ˚C.
• APPLICATION
Stainless steel repair clamps complying with this specification are intended for use in repair of water supply pipelines of the size designated in Table 8-1, with a maximum service temperature of 50°C and up to an allowable operating pressure of 16 bars for ranges diameter up to 250 mm. Repair clamps have limited ability to accommodate axial deflection and are, therefore, not generally intended for use as couplings to join two pipes together. However, they are commonly utilized for repair situations at full pipe break, where the pipe ends are considered stable. In addition, repair clamps complying with this specification are intended to provide a permanent means of preventing loss from or contamination of pipelines that have been affected by corrosion or mechanical damage in both above-ground and buried applications.
• MATERIALS
The material of Clamps shall be in accordance with the following standards or any other equivalent standards.
Bands: Stainless Steel Grade AISI 304(A2) to BS1449:1991: part 2 or Grade AISI 316(A4) stainless steel to BS 1449:1991: part 2, for corrosion resistance.
Bolts shall be Stainless Steel A2, Teflon coated, or mild steel. Nuts & washers shall be Stainless Steel A2, or mild steel class 4.6 to BS EN20898: Part 1. Receiver bars shall be TIG- welded to shell to form strong fusion, and fully passivated after welding,
Gasket shall have a gridded pattern for positive sealing, and to be made of specially compounded NBR rubber specially formulated for water service or EPDM. Compound Grade E to BS2494:1990
• DESIGN
The Clamps shall be used for permanent repair of cracks, holes, or complete breakages of steel, ductile Iron, PVC and HDPE pipes.
The Clamps shall be suitable for potable water for Temperature range (-10 to 50) C. Potable water certificate must be submitted.
![Page 64: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/64.jpg)
Technical Specifications
63
63
Repair Clamps shall be standard full circle single band for diameter 150mm or less. And full circle double band for diameter more than 150mm, length and number of bolts not less than the values in Table 8-1 for each diameter.
Gasket shall provide a 360o sealing surface and of such size and shape to provide an adequate compressive force against the pipe after assembling to affect a positive seal under all combinations of joint and gasket tolerances. And heavy gauge Type 304 stainless Steel bridge plate shall be attached into the gasket end to span the lug area and to make installation quick and easy.
Bolt retainer assembly or lugs shall be of a type 304 stainless steel, and shall be MIG welded to receiver bar and fully passivated after welding. Lugs may be cast, forged or cold formed of type 304 stainless steel, and may include a high impact polycarbonate plastic, non corrosive retainer. Lug design shall be such that the band fully compresses the gasket to the complete working width of the repair clamp without deformation of the band.
Table 5-1: Repair clamps sizes
Bands Nominal Pipe
Size (Inch)
Clamps O.D Rang
Length (mm) No. bolts Inches Millimetres
Min Max Min Max
Sin
gle
Ban
d
2 2.32 2.64 59 67 150 2
3 3.39 3.66 86 93 150 2
4 3.94 4.33 100 110 150 2
5 4.88 5.28 124 134 150 2
6 6.06 6.38 154 162 200 3
6(PE) 6.93 7.32 176 186 200 3
Do
ub
le B
and
s
8 8.268 9.06 210 230 300 3*
10 10.63 11.22 270 285 300 3*
12 12.40 13.189 315 335 500 5*
16 16.34 17.32 415 440 600 6*
24 24.41 25.59 620 650 600 6*
32 32.28 33.46 820 850 800 8*
36 36.61 37.8 930 960 1000 10*
* Number of bolts for each band side.
** Clamps O.D Range could be acceptable within (±4%) for the minimum and maximum dimensions.
![Page 65: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/65.jpg)
Technical Specifications
64
64
6. INSTALLATION OF PIPES AND FITTINGS
• GENERAL
The installation of pipes and fittings including: excavation, laying and backfilling, reinstatement, etc. shall be according to the specifications of Miyahuna attached in annex 1.
![Page 66: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/66.jpg)
Technical Specifications
65
65
7. DISINFECTION OF PIPELINES
• GENERAL
All pipes, fittings, valves and appearances shall be disinfected according to the specification of Miyahuna listed below.
• DISINFECTION OF PIPELINES
After the completed pipeline is tested, approved and backfilled, disinfections shall be performed in the following manner: after flushing the pipes, the system shall be drained completely, all valves shall be closed carefully and the system filled with a chlorine solution.
All pipes, fittings, valves and appurtenances shall be disinfected by the Contractor as specified herein unless otherwise directed by the Engineer’s Representative. The Contractor is also responsible for conducting bacteriological test for all pipe laying through a laboratory. The cost of disinfection and the bacteriological test shall be borne by the Contractor.
The contractor should use potable water to execute the bacteriological test, and has three options to fulfil the specs:
• Using Miyahuna water direct from the network by installing a bypass connection and as instructed by the concerned people in Miyahuna. The costs for the mentioned connection as well as required material, labour, etc. will be borne by the contractor.
• Using Miyahuna tankers
• By using private tankers the water should be tested first by Miyahuna to ensure that the delivered water is potable water before executing any bacteriological tests. The costs to ensure the water quality will be borne by the contractor.
The attention of the Contractor is directed to the requirements of the Contract whereby he is responsible for preventing the entry of foreign material of any kind from entering the pipe. The Contractor shall take extreme care to keep the interior of the pipelines free of dirt and other foreign material. If in the opinion of the Engineer’s or the Employer, dirt or other foreign material entered a pipe which cannot be removed by flushing, then the Contractor shall clean and swab the interior of the pipe with a five percent hypo-chlorite disinfecting solution to the satisfaction of the Engineer’s Representative.
The Contractor shall, during the initial filling of the pipeline, concurrently introduce feed of chlorine at the same point where the pipeline is being filled. The rate of filling and the feed rate of the chlorine shall be proportioned so that the initial concentration of the chlorine in the water in the pipeline is between 50 and 100 milligrams per litre. To assure that this concentration is maintained, the chlorine residual shall be measured at blow-off, combination air valves, or other locations during the filling operation.
The following is the amount of chlorine required, if either liquid chlorine (gas at atmospheric pressure) or a one percent chlorine solution is used, to produce a 100 milligram per litre concentration in 100 meters of pipe for the various diameters of pipe to be disinfected under this Contract.
Table 7-1: Liquid Chlorine Required for Disinfecting 100 Meters of Pipes
![Page 67: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/67.jpg)
Technical Specifications
66
66
Nominal Pipe Diameter (mm) 100% Liquid Chlorine
(kg) 1% Chlorine Solution
(Litres)
800 3.60 360
600 2.97 297
400 1.30 130
300 0.75 75
250 0.51 51
200 0.33 33
150 0.18 18
100 0.08 8
80 0.05 5
50 0.02 2
The use of liquid chlorine shall only be permitted when suitable equipment consisting of a solution feed chlorinator together with a booster pump of injecting the chlorine gas-water mixture into the pipeline to be disinfected is used. Introduction of chlorine gas directly from the supply cylinder shall not be allowed.
After completion of the disinfections operation for one pipeline section the Contractor may reuse this chlorinated water to disinfect adjacent sections of the pipeline by adding additional chlorine as required to produce the specified concentration of chlorine.
The Contractor shall submit a detailed description of the procedure he proposes to use to disinfect the pipeline including a description of all equipment to be used for the Engineer’s Representative approval prior to starting the disinfections operations.
Payment for all labour, material, and equipment, including the cost of all water and chlorine required to disinfect the pipeline and appurtenances shall be included in the costs for meter run of the pipe.
The chlorinated water shall remain in each section of the pipeline for at least 24 hours and during this period all valves and blow-off shall be operated in order to disinfect these appurtenances. At the end of the 24-hour period, the water in the pipeline shall contain no less then 25 milligrams chlorine per litre throughout the length of the pipeline. Shall the pipeline fail to have the specified chlorine concentration at the end of the 24-hour period, the Contractor shall repeat the operation as necessary to provide complete disinfections.
• FLUSHING OF THE PIPELINE
All pipelines shall be flushed by the Contractor after all hydrostatic pressure tests and disinfections operations have been performed and accepted by the Engineer’s Representative.
Water for flushing the pipes shall be provided by the contractor as indicated under section – Disinfection of Pipelines.
After draining the chlorine solution the pipe system shall be flushed with potable water until the free chlorine content is between 2 to 4 milligrams per litre.
![Page 68: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/68.jpg)
Technical Specifications
67
67
8. VALVES AND ACCESSORIES
• GENERAL
Valves and accessories must conform to current EN standards, ISO standards or equivalent with respect to nomenclature, classification, symbols, and conditions of manufacturing, properties and tolerances, conditions for the preparation of specimen, test rules, identification labels and acceptance clauses.
Moulded pieces must have perfect outer surfaces without chips and must be finished by means of debarring or filing.
Connecting surfaces of all flanges have to be machined. Flanges must also have one or several circular grooves in order to facilitate grip. All surfaces which are subject to friction must be machined; bore holes in covers, blind flanges, and flanges which connect pipes have to be produced by means of drills. Manual precision grinding of valve seats and surfaces of sluice valves is required for purposes of stability and accuracy of shut-off elements.
Operating stems must be made of stainless steel. They must be machined complete with straight edges and show no defects or scarcity of material. Toric ring seals must be used for sealing.
Seal bush must be replaceable under pressure.
Manufacturer's marks, flow diameter and an arrow indicating flow direction must be visible on the device's outer surface.
Punched or forged special elements will have this information stamped upon them.
Before materials are accepted or used the Contractor may be required to supply the Supervisor with a sample piece of every hydraulic equipment, fitting, valve and accessory, etc.... that he wishes to install.
All shut-off devices shut in a clockwise sense. This will be indicated by 'O' (open) and 'C' (closed) with arrows either on the hand wheel or the head of a piece. Operation of shut-off devices must be easy both for opening and closing. All valves will be flanged.
The following nominal pressures are stipulated:
Table 8-1: Nominal Pressure
Nominal Pressure Pressure Tes6t Body Seat (Sealing)
10 bar 16 bar 10 bar
16 bar 25 bar 16 bar
25 bar 37.5 bar 25 bar
40 bar 60 bar 40 bar
12 Third Party Witness
The supplier shall furnish an original accredited certificate of conformity from the third party inspection agency
showing all test results and analysis required by the applicable standard (EN 12266-1/2), where test certificates is
required. The third party inspection agency shall under this contract, have witnessed the manufacture and testing
operation to verify compliance with the technical specifications and the relevant standard. The third party
![Page 69: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/69.jpg)
Technical Specifications
68
68
inspection agency shall verify that all materials used are eligible for the relevant standard productions requirements.
All certification should be from a certified and approved third party, and the certificates must be related to the
same batch delivered to Miyahuna, all certificates must be valid and written in English.
13 Testing after delivery
All valves supplied to the site in Jordan shall be subjected to acceptance tests carried out by the Royal Scientific
Society. Or similar accredited authority. Final inspection tests must be done in accordance with the test
requirements of EN 12266-1/2. If any of the tests mentioned in the standards cannot be performed by the Royal
Scientific Society then the supplier should provide a third party certificate for those tests taking into considerations
all the statements mentioned in “third party witness” section.
All testing costs should be borne by the supplier in all cases.
14 Valves Packing and Protection
• All valves must be packed in such a way to allow instant use on site without additional cleaning.
• All valves shall be securely packed in crates and boxes to prevent damage during delivery. The cost of packing shall be deemed to be included in the Contract Rates and crates will not be returned.
• Valves are normally supplied in separate cartons together with any associated small items, such as bolts and gaskets.
15 Identification
The supplier shall be responsible to ensure that each separate item, crate, or package has permanently attached to
it, in a conspicuous position, an identification plate of weather - resistant material on which are engraved or
stamped;
• The Manufacturers Name.
• Contents Description and Quantity.
• Serial Number or Reference Number Identifiable on the Delivery Note and Cross Referenced to the Purchase Order Item References.
• Weight.
The shipment containers shall be marked with the following address;
Jordan Water Co. – MIYAHUNA L.L.C.
Tender Number – Variable
In addition the container shall be marked with the following information;
• Total gross weight.
• Total net weight.
![Page 70: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/70.jpg)
Technical Specifications
69
69
• Packing list reference number.
16 Transport and Deliveries
The Contractor shall send to the Engineer, one-week advance notice of all consignments of materials. Every consignment shall be accompanied by a detailed delivery note.
The Contractor shall deliver to and off load the materials onto the storage area as directed by the Engineer. All materials delivered will be examined and inspected by the Engineer and taken over by him.
The Contractor shall provide necessary details to the shipping line on precautions to be taken during loading/unloading, handling & transport of the pipes & fittings and other components. Contractor shall provide to the Engineer a set of recommendations of manufacturer for handling, loading, unloading, transporting and storing of polyethylene pipes and fittings
The Contractor shall arrange reception and storage areas only. aslo shall be responsible for off-loading all materials.
The Contractor shall also be responsible for all handling and transport activities up to and from Miyahuna store-yard, Amman.(Materials provided by Miyahuna)
• The (DDP) price shall include all costs relating to above-mentioned requirements.
17 Handling
Care shall be taken during loading, transporting, and unloading. Under no circumstances shall valves be dropped
or rolled against one another. All valves shall be examined. Any damaged materials must be rejected by the
Purchasers.
18 Details to be provided at the time of tender
1. Conformity to standard certificate from a certified third party.
2. Manuals and technical catalogues.
3. Dates of batches or consignment deliveries.
4. The supplier shall state which of the sections of the schedule of requirements he proposes to price and supply.
5. Any alternative standards proposed including demonstration of equivalency or superiority to the standard specified, if allowed.
6. Any alternative materials proposed including demonstration of equivalency or superiority to the standard specified, these alternative materials should be subjected to the clients approval.
7. Where the supplier offers alternative standards, materials to those specified, the supplier shall provide prices for those specified and the alternatives proposed.
8. The supplier shall include in his price for the training elements related to the materials he proposes to supply and shall list the elements of training offered, if needed or requested.
9. The supplier shall provide prices for the equipment applicable to the sections of the schedule of requirements he intends to price.
![Page 71: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/71.jpg)
Technical Specifications
70
70
10. The supplier shall provide full details of his materials tests and procedures.
11. Any alternative proposed specification for combined tracer and marker tape.
12. ISO or EN certification for management and product.
13. CV’s of proposed training staff, if necessary.
14. Costs of Trainers expenses, if requested.
15. Training program, if requested.
19 Manuals and Technical Specifications.
The supplier shall supply full technical specifications for the items to be supplied at the time of tender. In addition
he shall provide full instruction manuals, which describe the correct methods and procedures necessary to
construct the pipeline system in accordance with best practice. Conformity to standard certificate must be supplied
at time of tender where this certificate must be issued from a certified third party and valid up to date.
20 Additional Services
The supplier shall provide details of additional services, which he can provide e.g. technical advice and support
and, in particular, shall state his capability for supporting the project in the Amman location at the time of tender.
• BALL VALVES
Technical specifications Ball Valve specifications
1. General 1.1 Ambient Conditions
All valves and their accessories shall be in every respect suitable for storage, installation, use and operation in the conditions of temperature, humidity and The PH and water quality appertaining in Jordan.
Where the valve must withstand the following conditions:
• Liquid : Chlorinated , 3-5 ppm, potable water • Working Temperature: Reaches up to 40˚ C
Atmospheric temperature in Jordan varies between -10˚C and 50 ˚C.
![Page 72: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/72.jpg)
Technical Specifications
71
71
1.2 Potable Water Certification
All valves shall be certified for potable water use, and all valves and their accessories should be certified as safe for being use for potable water by an independent testing laboratory. All material in contact with or likely to come into contact with water for public supply shall be introduced with the requirements of BS 6920 (suitability for nonmetallic products for use in contact with drinking water) or any equivalent standard and the requirements of EN 15664 (influence of metallic materials on water intended for human consumption ) or any equivalent standard as well as the Jordanian standard (JS 286/2008) and the World Health Organization standard (WHO), and whenever the regulation is changed it is the supplier responsibility to ensure conformity with any new requirements. Potable water certificate submitted must be submitted at time of tender. Certificates must be in English. Offers without potable water certificates will be rejected. 1.3 Toxic Materials
Valves, their protective coatings and accessories, that will or may come into contact with potable water shall not constitute a toxic hazard, shall not support microbial growth, shall not cause taste or odour, cloudiness or discolouration of the water and shall contain no ingredients that may migrate into water in amounts that are considered to be toxic or otherwise dangerous for health . Non toxicity certificate should be provided. 1.4 Third Party Witness
The supplier shall furnish an original certificate from third party inspection agency showing all test results and
analysis required by the applicable standard (EN 12266-1/2), where test certificates is required. The third party
inspection agency shall under this contract, have witnessed the manufacture and testing operation to verify
compliance with the technical specifications and the relevant standard. The third party inspection agency shall
verify that all materials used are eligible for the relevant standard productions requirements. All certification should
be from a certified and approved third party, and the certificates must be related to the same batch delivered to
Miyahuna, all certificates must be valid and written in English.
where Miyahuna will sthird party companie The supplier must submit at least 3 different international choose one of them.
1.5 Testing after delivery
All valves supplied to the site in Jordan shall be subjected to acceptance tests carried out by the Royal Scientific Society. Or similar accredited authority. Final inspection tests must be done in accordance with the test requirements of EN 12266-1/2. If any of the tests mentioned in the standards cannot be performed by the Royal Scientific Society then the supplier should provide a third party certificate for those tests taking into considerations all the statements mentioned in “third party witness” section.
All testing costs should be borne by the supplier in all cases.
1.6 Valves Packing and Protection
• All valves must be packed in such a way to allow instant use on site without additional cleaning.
• All valves shall be securely packed in crates and boxes to prevent damage during delivery. The cost of
packing shall be deemed to be included in the Contract Rates and crates will not be returned.
![Page 73: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/73.jpg)
Technical Specifications
72
72
• Valves are normally supplied in separate cartons together with any associated small items, such as bolts
and gaskets.
1.7 Identification
The supplier shall be responsible to ensure that each separate item, crate, or package has permanently attached to it, in a conspicuous position, an identification plate of weather - resistant material on which are engraved or stamped;
• The Manufacturers Name
• Contents Description and Quantity
• Serial Number or Reference Number Identifiable on the Delivery Note and Cross
Referenced to the Purchase Order Item References.
• Weight
The shipment containers shall be marked with the following address;
Jordan Water Co. – MIYAHUNA L.L.C.
Tender Number – variable
In addition the container shall be marked with the following information;
• Total gross weight
• Total net weight
• Packing list reference number
1.8 Transport and Deliveries
• The supplier shall send to the Purchasers, one-week advance notice of all consignments of materials.
Every consignment shall be accompanied by a detailed delivery note.
• The supplier shall deliver to and off load the materials onto the storage area as directed by the Purchasers.
All materials delivered will be examined and inspected by the Purchaser and taken over by him.
• The supplier shall provide necessary details to the shipping line on precautions to be taken during
loading/unloading, handling & transport of the valves and other components. Supplier shall provide to
the purchaser a set of recommendations of manufacturer for handling, loading, unloading, transporting
and storing of valves.
• The Purchaser shall arrange reception and storage areas only. The supplier shall be responsible for off-
loading all materials.
• The materials shall be delivered to the Purchaser at Miyahuna stores, Amman or any other place chosen
by the Purchaser.
![Page 74: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/74.jpg)
Technical Specifications
73
73
• The supplier shall also be responsible for all handling and transport activities up to Miyahuna store-yard,
Amman
• The (DDP) price shall include all costs relating to above-mentioned requirements.
1.9 Handling
Care shall be taken during loading, transporting, and unloading. Under no circumstances shall valves be dropped or rolled against one another. All valves shall be examined. Any damaged materials must be rejected by the Purchasers.
1.10 Details to be provided at the time of tender
Conformity to standard certificate from third party
Manuals and technical catalogues
Dates of batches or consignment deliveries.
The supplier shall state which of the sections of the schedule of requirements he proposes to price and supply.
Any alternative standards proposed including demonstration of equivalency or superiority to the standard
specified, if allowed.
Any alternative materials proposed including demonstration of equivalency or superiority to the standard
specified, these alternative materials should be subjected to the clients approval.
Where the supplier offers alternative standards, materials to those specified, the supplier shall provide prices
for those specified and the alternatives proposed.
The supplier shall include in his price for the training elements related to the materials he proposes to supply
and shall list the elements of training offered, if needed or requested.
The supplier shall provide prices for the equipment applicable to the sections of the schedule of requirements
he intends to price.
The supplier shall provide full details of his materials tests and procedures.
Any alternative proposed specification for combined tracer and marker tape.
ISO or EN certification for management and product.
CV’s of proposed training staff, if necessary.
Costs of Trainers expenses, if requested.
![Page 75: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/75.jpg)
Technical Specifications
74
74
Training program, if requested.
1.11 Manuals and Technical Specifications
The supplier shall supply full technical specifications for the items to be supplied at the time of tender. In addition
he shall provide full instruction manuals, which describe the correct methods and procedures necessary to
construct the pipeline system in accordance with best practice. Conformity to standard certificate must be supplied
at time of tender where this certificate must be issued from a certified third party and valid up to date.
1.12 Additional Services
The supplier shall provide details of additional services, which he can provide e.g. technical advice and support
and, in particular, shall state his capability for supporting the project in the Amman location at the time of tender.
2.1 Technical specifications
• Working pressure: 16 bar or higher
• Nominal Diameter: 1/2" , 3/4" , 1" and 2"
• The design of the ball valve must ensure completely clear of the waterway when valve is full
open, in such away permitting a “full flow” throw the valve equal to the nominal pipe
diameter.
2.2 Material
The Material of each part of the ball valve is shown in table 2.1 below.
Table 2.1 Materials
NO PART NAME MATERIAL
1 BODY Stainless Steel : EN -10088-3-2 Or CW617N according to EN 12165:2011 EN 1982
2 BALL CW617N according to EN 12165:2011 chromium plated Ball Or Stainless Steel : EN -10088-3-2
3 HANDLE Steel or Aluminum
2.3 Design of valve
1. Full bore ball valve.
2. Two piece design.
3. Double female threaded in accordance with BS 21.
4. Lever operated.
![Page 76: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/76.jpg)
Technical Specifications
75
75
2.4 Coating
Coating material if applicable must be suitable for potable water uses.
2.5 Marking
Markings shall be in accordance with EN 19 and shall include the following:
• Nominal Size.
• Working pressure.
• name of manufacturer,
• Year of manufacture.
• “Miyahuna”.
For direct procurements order the marking is depends on the value of the procurements order.
![Page 77: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/77.jpg)
Technical Specifications
76
76
Appendix 1
Reference standards
Standard Number Description
BS 6920 Testing of non-metallic components with regards to their effect of the quality of water
EN 15664 influence of metallic materials on water intended for human consumption
EN 12266-1 Industrial valves - Testing of metallic valves - Part 1: Pressure tests, test procedures and acceptance criteria - Mandatory requirements
EN 12266-2 Industrial valves - Testing of metallic valves - Part 2: Tests, test procedures and acceptance criteria - Supplementary requirements
EN 12165:2011 Copper and copper alloys. Wrought and unwrought forging stock
EN 10088-2 Stainless steels. Technical delivery conditions for sheet/plate and strip for general purposes
EN 10088-3 Stainless steels. Technical delivery conditions for semi-finished products, bars, rods, wire, sections and bright products of corrosion resisting steels for general purposes
EN 1982 Copper and copper alloys. Ingots and castings
EN 19 Marking of general purpose industrial valves
• Gate Valve Specifications
![Page 78: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/78.jpg)
Technical Specifications
77
77
9. 1. GENERAL
• POTABLE WATER CERTIFICATION
All valves and its coating materials shall be certified for potable water use and shall contain no ingredients that may migrate into water in amounts that are considered to be toxic or otherwise dangerous for health, All material in contact with or likely to come into contact with water for public shall introduced with the requirements of Jordanian standard (JS 286) Whenever regulation changed it is the supplier /contractor responsibility to ensure conformity with any new requirements. Whenever potable water certificate is submitted for the coating material not the valve, the supplier shall furnish a document that relates this certificate with the valve itself. All valves shall be certified as safe for transporting potable water by an independent testing laboratory.
• TOXIC MATERIALS
All valves, coating, sealing and lining material shall be certified for potable water use and shall contain no
ingredients that may migrate into water in amounts that are considered to be toxic or otherwise dangerous for
health. The Contractor is prohibited to import or to use any of toxic or poisonous materials or sub materials used
in piping, kinds of concrete or in soil in any kind of usage.
• THIRD PARTY WITNESS
12 1.3.1 General
The supplier/contractor shall furnish an original certificate from the third party inspection agency showing all test
results and analysis required by the applicable standard according to which the materials have been manufactured.
The third party inspection agency shall under this contract, have witnessed the manufacture and testing operation
to verify compliance with the technical specifications and the relevant standard. All certification should be from a
certified third party from the applied standard (American Standard) and approved by Miyahuna, and the
certification should be valid up to date and it should be written in English, and it must be shown in the certificate
which batch is being tested to make sure that this certificate is for the right batch.
13 1.3.2 Valves
No valve shall be accepted unless all type and batch release tests have been passed. The contractor also is required to submit quality assurance certificates, standard compliance and witness test certificate, from third party from the applied standard (American Standard) and approved by Miyahuna, that the components of the network must not be of any way toxic to the water being conveyed. And can be fully used for the distribution of potable water to a temperature up to 50° C.
Before dispatching the supplies another visual inspection shall be done in respect of proper packing and to certify
the Bill of Lading for each shipment.
• TESTING AT PLACE OF MANUFACTURE
The Contractor shall submit a certificate from the manufacturer certifying that all the items have been mill tested
(at the manufactory) and those they have successfully passed the relative tests prescribed by the relative standards
specifications.
![Page 79: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/79.jpg)
Technical Specifications
78
78
• TESTING AFTER DELIVERY
Valves supplied shall be subjected to acceptance tests carried out by the Royal Scientific where Final inspection
test must be done according to EN 12266-1/2
NOTE:
ALL COST TESTS BEFORE AND AFTER THIS ITEM AND WETHER LOCAL OR ABROAD SHALL BE BORNE BY THE CONTRACTOR AND THE COSTS SHALL BE INCLUDED IN THE TENDER UNIT RATES.
• VALVES PACKAGING
• All valves must be packed in such a way to allow instant use on site without additional cleaning.
• All valves shall be securely packed in crates and boxes to prevent damage during delivery. The cost of
packing shall be deemed to be included in the Contract Rates and crates will not be returned.
• Valves are normally supplied in separate cartons together with any associated small items, such as bolts
and gaskets.
• IDENTIFICATION
The supplier shall be responsible to ensure that each separate item, crate, or package has permanently attached to
it, in a conspicuous position, an identification plate of weather - resistant material on which are engraved or
stamped;
• The Manufacturers Name
• Contents Description and Quantity
• Serial Number or Reference Number Identifiable on the Delivery Note and Cross
Referenced to the Purchase Order Item References.
• Weight
The shipment containers shall be marked with the following address;
Jordan Water Co. – MIYAHUNA L.L.C.
Tender Number – variable
In addition the container shall be marked with the following information;
• Total gross weight
• Total net weight
• Packing list reference number
![Page 80: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/80.jpg)
Technical Specifications
79
79
• DOCUMENTS TO BE PROVIDED AT TIME OF TENDER
2. CONFORMITY TO STANDARD CERTIFICATE FROM THIRD PARTY (AFFIDAVIT OF COMPLIANCE) ACCORDING TO (ANSI/AWWA C509 OR C515) OR EQUIVALENT AND COMPATIBLE.
A. THIS CERTIFICATE MUST CONFIRM THE ABILITY OF THE MANUFACTURER TO FULFILL ALL REQUIRED SPECIFICATIONS AND STANDARD .
B. THE CERTIFICATE SHOULD BE CERTIFIED FROM JORDAN INSTITUTION FOR STANDARD AND METROLOGY (JISM) WITH AN OFFICIAL LETTER, THE LETTER SHOULD BE RENEWED ANNUALLY
2. Potable water certificate from Third Party NSF 61
3. The CONTRACTOR shall provide detailed repair manuals for the gate valves supplied;
4. Quality assurance certificate (ISO 9001).
5. Upon request, the Contractor has to provide test certificates from the manufacturer’s internal quality control.
6. The supplier/ contractor shall supply full technical specifications and catalogues for the items to be supplied at
the time of tender.
• DOCUMENTS TO BE PROVIDED UPON DELIVERY
The contractor shall submit at least the following documents:
1. Certificate of origin.
2. Packing list
3. Third Party certificates (Affidavit of Compliance)
4. Warranty.
5- Installation and maintenance manual
6. Any other documents requested by the Engineer and the hand over committee
All above documents must be valid and in English.
![Page 81: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/81.jpg)
Technical Specifications
80
80
• MARKING
Markings shall include size, working pressure, name of manufacturer, and year of manufacture.
![Page 82: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/82.jpg)
Technical Specifications
81
81
10. TECHNICAL SPECIFICATIONS
• GENERAL
8. Gate valves shall be Resilient seated, non rising stem and shall be comply with all specifications
and standards mentioned below or equivalent and compatible.
9. Valves must be according to ANSI/AWWA C509 or C515, conformity to standard certificate must
be submitted at time of the tender.
10. All valves shall have flanged ends design. push-on joint submitted upon request.
11. The valve must be submitted with the following accessories :
• Flanges
• Gaskets
• Bolts, nuts and washers
• Surface box
• Hand wheel
• MATERIAL
•
Part Name Material
Body, wedge and bonnet (16-25 bar)or (250-300 PSI)
ductile iron shall conform to the requirements of ASTM A395 or ASTM A536..
Gaskets and O- rings Gasket material shall be made of inorganic mineral fiber, rubber composition, or paper that is fee from corrosive ingredients. O-Rings or other suitable elastomeric seals may be used for gaskets.
Hand Wheel and Bonnet Cap
ductile iron shall conform to the requirements of ASTM A395 or ASTM A536..
seat
Resilient seat Wedge full lining with EPDM for water system for pressure (16 – 25 ) bars or (250-300) PSI. According to AWWA C509 or C515.
Valve stem(shaft) cast, forged or rolled bronze grade B, C, D or E Stem nuts shall be grade A,B,C,D or E bronze.
Stem nuts low zinc bronze, SS304, SS316, nickel copper alloy
External nuts, ,washer and bolts
Stainless Steel . ASTM A240, UNS Designation S30400 or S31600, ASTM A276, UNS Designation S30400 or S31600, ASTM A743, grade CF8 or CF-8M, or ASTM A564, UNS Designation S17400
![Page 83: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/83.jpg)
Technical Specifications
82
82
• DESIGN
1. Gate valve is face to face dimensions and shall be flanged design in accordance with EN1092-2 / ISO 7005 for pressure range (16, 25) bar. or equivalents, in accordance with the details stated on the Drawings and in the Bill of Quantities.
2. ROTATION OF OPENING:
All valves shall open by turning to the left or counterclockwise, when viewed from the stem. All gate valves shall have closing, opening indicators and an arrow cast in the metal to indicate the direction to open.
• COATING
All iron components of the valve shall be coated (internal and external ) with a minimum 250µm fusion bonded epoxy coating in accordance with AWWA C550 and shall be ANSI/NSF 61 and NSF 372 certified, the coating shall be non-toxic and impart no taste to water.
• VALVE TESTING
Prior to shipment from the factory, 5% of each size and class should be tested with a minimum (one valve of each
size and class), the tests should be applied in accordance with AWWAC509/C515 Hydrostatic test, Torque test,
Leakage test and Pressure Test , all reports should be in English, and it must be shown in the certificate it is for
the right batch delivered to Miyahuna.
• BUTTERFLY VALVES
![Page 84: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/84.jpg)
Technical Specifications
83
83
11. 1. GENERAL
• POTABLE WATER CERTIFICATION
All valves and its coating materials shall be certified for potable water use and shall contain no ingredients that may migrate into water in amounts that are considered to be toxic or otherwise dangerous for health, All material in contact with or likely to come into contact with water for public shall introduced with the requirements of Jordanian standard (JS 286) Whenever regulation changed it is the supplier /contractor responsibility to ensure conformity with any new requirements. Whenever potable water certificate is submitted for the coating material not the valve, the supplier shall furnish a document that relates this certificate with the valve itself. All valves shall be certified as safe for transporting potable water by an independent testing laboratory.
• TOXIC MATERIALS
All valves, coating, sealing and lining material shall be certified for potable water use and shall contain no
ingredients that may migrate into water in amounts that are considered to be toxic or otherwise dangerous
for health. The Contractor is prohibited to import or to use any of toxic or poisonous materials or sub
materials used in piping, kinds of concrete or in soil in any kind of usage.
• THIRD PARTY WITNESS
12 1.3.1 General
The supplier/contractor shall furnish an original certificate from the third party inspection agency
showing all test results and analysis required by the applicable standard according to which the materials
have been manufactured. The third party inspection agency shall under this contract, have witnessed the
manufacture and testing operation to verify compliance with the technical specifications and the relevant
standard. All certification should be from a certified third party from the applied standard (American
Standard) and approved by Miyahuna, and the certification should be valid up to date and it should be
written in English, and it must be shown in the certificate which batch is being tested to make sure that
this certificate is for the right batch.
13 1.3.2 Valves
No valve shall be accepted unless all type and batch release tests have been passed. The contractor also is required to submit quality assurance certificates, standard compliance and witness test certificate, from third party from the applied standard (American Standard) and approved by Miyahuna, that the components of the network must not be of any way toxic to the water being conveyed. And can be fully used for the distribution of potable water to a temperature up to 50° C. Before dispatching the supplies another visual inspection shall be done in respect of proper packing and
to certify the Bill of Lading for each shipment.
![Page 85: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/85.jpg)
Technical Specifications
84
84
• TESTING AT PLACE OF MANUFACTURE
The Contractor shall submit a certificate from the manufacturer certifying that all the items have been
mill tested (at the manufactory) and those they have successfully passed the relative tests prescribed by
the relative standards specifications.
• TESTING AFTER DELIVERY
Valves supplied shall be subjected to acceptance tests carried out by the Royal Scientific where Final
inspection test must be done according to EN 12266-1/2
NOTE:
ALL COST TESTS BEFORE AND AFTER THIS ITEM AND WETHER LOCAL OR ABROAD SHALL BE BORNE BY THE CONTRACTOR AND THE COSTS SHALL BE INCLUDED IN THE TENDER UNIT RATES.
• VALVES PACKAGING
• All valves must be packed in such a way to allow instant use on site without additional cleaning.
• All valves shall be securely packed in crates and boxes to prevent damage during delivery. The
cost of packing shall be deemed to be included in the Contract Rates and crates will not be
returned.
• Valves are normally supplied in separate cartons together with any associated small items, such
as bolts and gaskets.
• IDENTIFICATION
The supplier shall be responsible to ensure that each separate item, crate, or package has permanently
attached to it, in a conspicuous position, an identification plate of weather - resistant material on which
are engraved or stamped;
• The Manufacturers Name
• Contents Description and Quantity
• Serial Number or Reference Number Identifiable on the Delivery Note and Cross
Referenced to the Purchase Order Item References.
• Weight
The shipment containers shall be marked with the following address;
![Page 86: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/86.jpg)
Technical Specifications
85
85
Jordan Water Co. – MIYAHUNA L.L.C.
Tender Number – variable
In addition the container shall be marked with the following information;
• Total gross weight
• Total net weight
• Packing list reference number
• DOCUMENTS TO BE PROVIDED AT TIME OF TENDER
3. CONFORMITY TO STANDARD CERTIFICATE FROM THIRD PARTY (AFFIDAVIT OF COMPLIANCE) ACCORDING TO (ANSI/AWWA C504 AND/OR C519) EQUIVALENT AND COMPATIBLE.
A. THIS CERTIFICATE MUST CONFIRM THE ABILITY OF THE MANUFACTURER TO FULFILL ALL REQUIRED SPECIFICATIONS AND STANDARD .
B. THE CERTIFICATE SHOULD BE CERTIFIED FROM JORDAN INSTITUTION FOR STANDARD AND METROLOGY (JISM) WITH AN OFFICIAL LETTER, THE LETTER SHOULD BE RENEWED ANNUALLY
2. Potable water certificate from Third Party NSF 61 and 372.
3. The CONTRACTOR shall provide detailed repair manuals for the gate valves supplied;
4. Quality assurance certificate (ISO 9001).
5. Upon request, the Contractor has to provide test certificates from the manufacturer’s internal quality
control.
6. The supplier/ contractor shall supply full technical specifications and catalogues for the items to be
supplied at the time of tender.
• DOCUMENTS TO BE PROVIDED UPON DELIVERY
The contractor shall submit at least the following documents:
1. Certificate of origin.
2. Packing list
3. Third Party certificates (Affidavit of Compliance)
![Page 87: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/87.jpg)
Technical Specifications
86
86
4. Warranty, installation and maintenance manual
5. Any other documents requested by the Engineer and the hand over committee
All above documents must be valid and in English.
• MARKING
Markings shall include size, working pressure, name of manufacturer, and year of manufacture.
![Page 88: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/88.jpg)
Technical Specifications
87
87
• GENERAL
1. Butterfly valves shall comply with all specifications and standards mentioned above or equivalent
and compatible..
2. butterfly valves shall be of the tight closing, rubber 3. Valve discs shall rotate 90 degrees from the full open position to the tight shut off position. 4. Double eccentric design for pressure range (16-25)bar or (250-300)PSI
• MATERIAL
Part Name Material
Body
Ductile cast iron, ASTM 536 65-45-12 or ASTM 345 60-40-18
Disk ductile cast iron, ASTM 536 65-45-12 or ASTM 345 60-40-18
Shaft Stainless steel ASTM A240 or A267 or A743 grade 304,316,316L,17-4 PH and high strength 2205 duplex or Nickel copper alloy ASTM B127
Rubber seat Rubber seats shall be field replaceable and shall be applied to the disc with AISI 316 stainless steel seat retainer. The seat retainer shall be counter bored and drilled. Seat retaining fasteners shall be AISI 316 Stainless-steel or nickel-copper alloy. Rubber seats shall be of new natural or synthetic rubber (EPDM), and may be reinforced Buna-N.
Mating surfaces (Body seats) Body seat shall be made of stainless steel 304, 316 or high nickel alloy and
applied to the valve body by means of a machined weld overlay process
eliminating the possibility of leakage through the body/seat joint.
Shaft bearings Valve shaft bearings shall be corrosion resistant, self-lubricating sleeve type
made of bronze.
Internal bolts and pins
low zinc bronze ,SS304,SS316, nickel copper alloy
O-rings O-rings shall be of EPDM
• DESIGN
1. Face to face 2. Flanged accordance to EN 1902-2. 3. Flanged connection to DIN 2501. 4. Soft sealing 5. Glands shall be O-ring 6. Valves shall be suitable for installation in either horizontal or vertical position.
![Page 89: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/89.jpg)
Technical Specifications
88
88
• COATING
All iron components of the valve shall be coated (internal and external) with a minimum 250µm fusion bonded epoxy coating in accordance with AWWA C550 and shall be ANSI/NSF 61 and NSF 372 certified, the coating shall be non-toxic and impart no taste to water.
ACTUATION
All butterfly valves shall be equipped, if not otherwise requested in the bill of quantity, with gear box and hand
wheel.
Manual Actuators: Actuators shall conform to ANSI/AWWA C540 or equivalent,
All actuators shall be self-locking worm gear type and shall hold the valve disc in the closed, open and any
intermediate position without creeping or fluttering and be supplied from known and reputable gear
manufacture.
An adjustable mechanical dial position indicator shall be provided.
All bearings shall be maintenance-free of a self-lubricating or sealed-for-life type suitable for at least 10,000
operation cycles.
• VALVE TESTING
Prior to shipment from the factory, 5% of each size and class should be tested with a minimum (one
valve of each size and class), the tests should be applied in accordance with AWWAC509/C515
Hydrostatic test, Torque test, Leakage test and Pressure Test , all reports should be in English, and it
must be shown in the certificate it is for the right batch delivered to Miyahuna.
![Page 90: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/90.jpg)
Technical Specifications
89
89
• AIR VALVES
12 General
This specification describe ½-in. (13 mm) through 6 in (150-mm) air-release valves and ½-in. (13-mm) through 20-in. (500-mm) and combination air valves. The valves are designed for use in water systems with maximum working pressures of 25 bar and water temperatures ranging from above freezing to a maximum of 125°F (52°C).
The working pressure of air valves shall be 250, 300 PSI or 16, 25 bar as specified in the Bill of Quantities.
Air valves shall conform to the latest edition of AWWA C512 or BS EN 1074.
The air valve shall be tested and certified as a complete drinking water valve according to NSF 61, WRAS, or equivalent recognized standards.
Air Valves smaller than DN 50 mm shall be female thread inlet connection and larger air valves shall have Flanged inlet, the flange shall comply with (EN 1092-2 / ISO 7005) PN16 and PN25 or 250, 300 PSI as specified in the Bill of Quantities.
Single Air Release Valve
The air release valve shall be of the float operated, simple lever or compound lever design, and capable of automatically releasing accumulated air from a fluid system while the system is pressurized and operating.
The valve body and bonnet (cover) shall be of ductile iron ASTM A536 65-45-12 or EN-JS 1030 (GGG 40) according to EN 1563 or cast iron to Cast Iron ASTM A126 Class B or BS EN 1561 EN-GJL-250.
The cover shall be bolted to the body and all internal components shall be replaceable through the cover.
Valve internal and exteriors shall be coated with a minimum 250µm fusion bonded epoxy coating in accordance with AWWA C550 or EN 14901 Float balls shall be of stainless steel, all seals shall be of EPDM or Buna-N Rubber suitable and approved for potable water and all internal parts shall be of stainless steel.
All bolts and nuts shall be of stainless steel.
Combination Air Valve
![Page 91: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/91.jpg)
Technical Specifications
90
90
Combination Air Valves shall be in two body style: large orifice air and vacuum valve and small orifice air release valve.
The valve shall be with a venting orifice no smaller than the nominal valve size.
All Internal parts and the float ball shall be spherical and made of stainless steel grade 316.
Body and bonnet (cover) shall be of ductile iron ASTM A536 65-45-12 or EN-JS 1030 (GGG 40) according to EN 1563 or cast iron to Cast Iron ASTM A126 Class B or BS EN 1561 EN-GJL-250.
The cover shall be bolted to the body and all internal components shall be replaceable through the cover.
Float balls shall be of stainless steel, all seals shall be of EPDM or Buna-N Rubber suitable and approved for potable water and all internal parts shall be of stainless steel.
Valve internal and exteriors shall be coated with a minimum 250µm fusion bonded epoxy coating in accordance with AWWA C550 or EN 14901
13 Marking
Each valve shall be marked by body markings or a corrosion-resistant nameplate, or both, that clearly indicate the manufacturer’s name or trademark, size of the valve, and the designation of the maximum working pressure rating of the valve for water service and year of manufacture and model number.
14 Data to Be Provided by Manufacturer or Supplier at time of tender
The manufacturer or supplier shall provide the following information:
• Conformity to Standard certificate from third party (latest edition of AWWA C512 .)
• Catalog data. The catalog data shall include illustrations, valve performance data, a parts schedule that identifies the materials used for various parts, and the total net assembled weight for each valve size.
• Certified drawings, a set of certified drawings shall include principal dimensions, construction details, and materials used for all parts of the valve.
• Operating manual. An operating manual shall include the manufacturer’s installation and operating instructions, a recommended list of spare parts, and the maintenance procedures. The contents shall be sufficiently detailed to direct the assembly and disassembly of the valve and for the ordering of parts.
15 Data to Be Provided by Manufacturer or Supplier upon delivery
1. Certificate of origin.
2. Packing list
3. The supplier/contractor shall furnish a testing report from the internal quality
assurance in the factory showing all test results and analysis required by the applicable
standard (Shell test, Hydrostatic test and Operational test). All reports should be in
![Page 92: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/92.jpg)
Technical Specifications
91
91
English, and it must be shown in the certificate which batch is being tested to make
sure that this certificate is for the right batch delivered to Miyahuna.
4. Warranty, installation and maintenance manual
5. Any other documents requested by the Engineer and the hand over committee
All above documents must be valid and in English.
• PRESSURE REDUCTION VALVE (PRV)
DIAPHRAGM TYPE PRESSURE REDUCING VALVES
12. GENERAL:
Diaphragm type pressure reducing valves shall be line pressure driven, hydraulically operating, pilot controlled, single diaphragm actuated, globe pattern valves to reduce a variable inlet pressure to a constant preset lower discharge pressure at variable flow rates to meet downstream system demand. The valves shall utilize upstream and downstream line pressure to modulate the position of the valve disc to provide downstream pressure control without the required of any external source of power. Valves shall conform to AWWA C-530. Valve design shall provide for replacement of the valve diaphragm and seats by removing only control piping and the valve cover, and shall not require removal of the valve body from the line.
A. Each valve shall be globe pattern design with a circular port and guided disc to provide tight closure and modulating service for downstream pressure control. The valve shall consist of a body with installed seat, body cover, disc, and diaphragm assembly. The diaphragm assembly shall be the only moving part and shall form a sealed chamber in the upper portion of the valve, separating operating pressure from line pressure. The valve shall not utilize packing glands or stuffing boxes and shall not utilize pistons to operate the main valve or the pilot controls. Valve port size shall be equal to the line size.
B. Valves 75 mm diameter and larger shall be flanged end to ISO 7005-2 or equivalent, Valves
less than 75 mm diameter shall be threaded.
C. The valve body and cover shall be of cast ductile iron ASTM A536, EN 1563, coated on all
surfaces, inside and outside with heat fusion bonded epoxy compliant with NSF 61 with minimum thickness of ( 250 microns ). The valve body seat shall be a replaceable, one-piece design of Type 316 stainless steel, threaded or otherwise mechanically attached within the valve body, to allow the seat to be removed and replaced. The seat face shall be contoured
![Page 93: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/93.jpg)
Technical Specifications
92
92
to mate with the disc to provide a tight shut-off. Bolts and hardware to secure the cover to the body shall be of stainless steel
D. The valve disc retainer assembly shall be of Type 316 stainless steel and shall retain a resilient
synthetic rubber EPDM or Buna-N Rubber Disc to engage the body seat. The disc retainer assembly shall provide for attachment of anti-cavitation devices as may be required to eliminate the potential for valve cavitation under the operating conditions specified in the BoQ. Furnish Type 316 stainless steel anti-cavitation devices on valves designated to require cavitation protection. Provide throttling ports on the disc to provide for low flow throttling service for enhanced low flow operation.
E. The disc assembly shall be attached to a Type 316 stainless steel stem guided in nickel
aluminum bronze guides or Stainless Steel to assure alignment of the disc seat with the body seat under all hydraulic conditions. The stem shall incorporate a valve position indicator to show percent opening.
F. The diaphragm assembly shall consist of a flexible diaphragm mounted on its outer periphery
to provide contoured contact surfaces for the diaphragm to assure no concentrated loads on the diaphragm. The diaphragm shall be fully supported in the valve body and cover. The diaphragm of be on non-wicking, NSF approved peroxide cured EPDM or Buna-N Rubber material for potable water service bonded with nylon fabric. A stainless steel spring shall be mounted on the valve stem arranged to assist tight closure of the valve.
G. (Pilot Spec.) Each valve shall be provided with an external pilot control assembly to provide
modulating, pressure regulating control of the main valve, the pilot system shall be factory pre-piped, installed on the main valve and tested as an assembly and factory adjusted to customer requirements
1. Pilot control tubing, accessories and fittings shall be rated to at least the pressure rating
of the main valve body, and shall be of Type 316 stainless steel or bronze and Pilot System tubes in copper.
2. Provide enough isolation valves to facilitate removal and maintenance of the pilot
system without disturbing the main valve. 3. Provide pressure gauges at the upstream and downstream taps to the main flow. Select
pressure gauges with a scale range to place the normal operating pressure at approximately mid scale. Pressure gauges shall be liquid filled, minimum 50 mm diameter, provided with isolation valves.
4. Provide for control of the rate of opening and closure of the main valve by the use of
throttling needle valves in the control tubing to restrict the rate of flow in the control tubing.
5. Provide a filter in the control tubing immediately downstream of the tap to the main valve
to filter contaminates from the flow that may clog the needle valves.. The valve shall be equipped with Position Indicator to show percentage of opening, and
with an opening and closing speed control valve.
![Page 94: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/94.jpg)
Technical Specifications
93
93
6. The pilot control valve shall be a low volume, direct-acting, adjustable, spring-loaded, normally open diaphragm valve, designed to permit flow when controlled pressure is less than the spring setting. The valve shall maintain a constant downstream pressure within close limits and regardless of varying inlet pressure.
H. For valves that must provide a large range of downstream flows that cannot be covered by
the main valve, provide a low capacity bypass pilot valve assembly mounted on the main valve with settings coordinated with the main valve settings to allow the main valve to close completely and the bypass to provide low flow pressure control.
I. Each valve shall be tested at the manufacturer’s shop prior to shipment. Testing shall consist
of a hydrostatic test at two times the maximum working pressure, a tight seating test at the design working pressure of the valve, and a performance test under simulated field conditions. Submit certified test results.
J. The manufacturer shall provide full technical catalogue and data sheet contain cavitation, flow
and performance charts….and also shall provide installation and maintenance manual in English.
K. If required and according to the design and manufacturer requirement PRV Anti-cavitation
Trim –is equipped with slot's disc guide and seats sets with radial slots (materials stainless steel).
L. The PRV shall be (open architecture) and suitable / ready to work as a modulator in any
existing pressure management system.
13. TESTING The media of the test shall be water. Pre-shipment test: The supplier shall conduct on his expense the entire listed down test prior of shipping the valves. 1- Performance test. Prior to shipment, valves and pilot systems shall be factory tested to demonstrate the ability to fully stroke from close to open and then from the open to close position. 2- Seat leakage test. Valves shall be shop tested for seat leakage for duration of 2 minutes. There shall be no indication of leakage past the valve seat during this test period. The test pressure shall be either the hydrostatic pressure equivalent to working pressure. The test pressure shall be applied to the seat in the fluid flow direction. 3- Valve body hydrostatic test. Valve bodies and cover cavities shall be subjected to an internal hydrostatic pressure equivalent to 1.5 times the rated pressure, during the hydrostatic test, there shall be
![Page 95: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/95.jpg)
Technical Specifications
94
94
no leakage through the valve body, the end joints, or the stem seals, nor shall any part of the valve have any permanent visible deformation as a result of this test. The test duration shall be 2 minutes. The manufacturer shall provide a certified statement that proof-of-design tests were performed as described in the standard and all requirements were successfully met.
14. MARKING: Markings shall be cast on the body with raised letters or provided on a corrosion-resistant plate. The markings shall show the valve size, manufacturer, pressure class, model number or serial number, and year of manufacture.
15. DOCUMENT TO BE SUBMITTED WITH THE OFFER:
- NSF/ANSI 61–certified (Hygienic certificate)
- AWWA 530 conformity
- All required data sheet and catalogs includes (dimension, drawings
16. DOCUMENT TO BE SUBMITTED ON DELIVERY:
- Test result Certificate as describe in the specifications.
- Certificate of Origin.
• ELECTROMAGNETICFLOW METERS (MAINS VERSION)
• Flow meters must be certificated as MID – Measurement Instrument Directive, according to European Directive 2004/22/CE, MI-001, for cold drinkable water measurement according to MI-001, or equivalent.
• Flow meters must be compliant to OIML R-49: 1-2006, or equivalent.
• Flow meters or components in contact with drinkable water must have a Sanitary Compliance Certificate, from a European Origin. (e.g. – ACS France), or equivalent.
• The Manufacturer has to be certified an ISO 9001: 2008 quality certificate and present proof of certificate.
• The Manufacturer has to be certified an ISO 14001: 2004 quality certificate and present proof of certificate.
12 In Line Type
1. Construction
• The flow meter shall comprise of 2 parts: the flow sensor and the converter.
• The flow meter shall be delivered either in compact configuration where the converter is mounted on the flow sensor with no cable connecting between them or remote version with cable connecting between them depending on the configuration required.
• For remote version, the cable connecting between the flow sensor and converter shall be double shielded twin-core type or higher with a length from 5m to 20m maximum.
![Page 96: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/96.jpg)
Technical Specifications
95
95
• The flow meter power shall be 220 volt AC 50 Hz.
• Water temperature range of flow meter shall be between 0 C to 50 C.
• Ambient temperature range of flow meter shall be between -10 C to 55 C.
• The flow meter shall be compatible with any Automatic Meter Reading system measuring instantaneous flow rate by time measuring between 2 pulses.
• . For the remote version, the flow sensor shall be IP68 and suitable for buried installation, and the converter shall be at least IP67 and suitable for wall mounting.
• The lining of flow sensor shall be constructed of PTFE. Or Hard rubber
• The flow sensor electrodes shall be made of suitable nickel alloys or stainless steel for durability in abrasive water.
• The flow sensor shall be of no internal moving parts.
• The flow sensor shall be at least PN16.
• The flow sensor shall be configured to be installed in any orientation without affecting the accuracy of the meter.
• The flow meter status information, such as flow direction and empty pipe detection must be available and displayed on the converter display.
• The flow meter pressure loss shall not be more than 0.006 bar at 2 m/s and 0.1 bar at 4 m/s.
• The electrical conductivity of the medium measured shall be not less than 20 uS/cm (drinking water, raw water, and irrigation water).
2. Principle of Operation
• The principle of operation shall be in accordance with Faraday’s Law of Induction.
• The flow meter shall be capable of measuring flow rate and volume total in both directions, with two independent totalizers for network management purposes.
• The accuracy shall be better than Class 1 of OIML R-49:1-2006.
• A calibration certificate for each delivered flow meter shall be provided.
• The flow meter installation shall not require more than 5D of straight length upstream and more than 2D downstream of the meter to secure its accuracy.
• The flow meter shall offer lifetime stable zero so that routine zeroing is not required.
• The flow meter shall indicate empty pipe detection when no water is present.
3. Physical Requirements
The flow meter shall be built as follow:
Sizes From DN25 to DN800
Medium Compatibility Compatible with raw, ground & surface water, potable water & irrigation water. Electrical conductivity ≥ 20 µS/cm 0 °0 C to +55°C
Sensor Housing Sheet polyurethane coated or stainless steel
Electrodes Stainless steel
![Page 97: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/97.jpg)
Technical Specifications
96
96
Flange Steel
Environment IP68 to 2m submergence in water
Connections DIN, ASME
4. Communication Output Specifications
The meter should have at least one or two pulse output (passive) and one or two status output (passive):
• Pulse output:
2 Passive pulse outputs
Volume / pulse is programmable
Pulse width is selectable: 1 ms, 5 ms, 50 ms, 100 ms
• Status output:
2 Passive status outputs
Function [selectable]: self checking, battery pre warning, battery final warning, counter overrun.
• Analog Output: 4-20 mA current output proportional to span
• The flow meter must support HART communication
• ELECTROMAGNETICFLOW METERS (BATTERY VERSION)
• Flow meters must be certificated as MID – Measurement Instrument Directive, according to European Directive 2004/22/CE, MI-001, for cold drinkable water measurement according to MI-001, or equivalent.
• Flow meters must be compliant to OIML R-49: 1-2006, or equivalent.
• Flow meters or components in contact with drinkable water must have a Sanitary Compliance Certificate, from a European Origin. (e.g. – ACS France), or equivalent.
• The Manufacturer has to be certified an ISO 9001: 2008 quality certificate and present proof of certificate.
• The Manufacturer has to be certified an ISO 14001: 2004 quality certificate and present proof of certificate.
12 In Line Type
1. Construction
• The flow meter shall comprise of 2 parts: the flow sensor and the converter.
• The flow meter shall be delivered either in compact configuration where the converter is mounted on the flow sensor with no cable connecting between them or remote version with cable connecting between them depending on the configuration required.
• For remote version, the cable connecting between the flow sensor and converter shall be double shielded twin-core type or higher with a length from 5m to 20m maximum.
• The flow meter battery operated with Lithium ion battery pack that can last at least 10 years of operation.
![Page 98: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/98.jpg)
Technical Specifications
97
97
• Water temperature range of flow meter shall be between 0 C to 50 C.
• Ambient temperature range of flow meter shall be between -10 C to 55 C.
• The flow meter shall be compatible with any Automatic Meter Reading system measuring instantaneous flow rate by time measuring between 2 pulses.
• . For the remote version, the flow sensor shall be IP68 and suitable for buried installation, and the converter shall be at least IP67 and suitable for wall mounting.
• The lining of flow sensor shall be constructed of PTFE. Or Hard rubber
• The flow sensor electrodes shall be made of suitable nickel alloys or stainless steel for durability in abrasive water.
• The flow sensor shall be of no internal moving parts.
• The flow sensor shall be at least PN16.
• The flow sensor shall be configured to be installed in any orientation without affecting the accuracy of the meter.
• The flow meter status information, such as flow direction and empty pipe detection must be available and displayed on the converter display.
• The flow meter pressure loss shall not be more than 0.006 bar at 2 m/s and 0.1 bar at 4 m/s.
• The electrical conductivity of the medium measured shall be not less than 20 uS/cm (drinking water, raw water, and irrigation water).
2. Principle of Operation
• The principle of operation shall be in accordance with Faraday’s Law of Induction.
• The flow meter shall be capable of measuring flow rate and volume total in both directions, with two independent totalizers for network management purposes.
• The accuracy shall be better than Class 1 of OIML R-49:1-2006.
• A calibration certificate for each delivered flow meter shall be provided.
• The flow meter installation shall not require more than 5D of straight length upstream and more than 2D downstream of the meter to secure its accuracy.
• The flow meter shall offer lifetime stable zero so that routine zeroing is not required.
• The flow meter shall indicate empty pipe detection when no water is present.
3. Physical Requirements
The flow meter shall be built as follow:
Sizes From DN25 to DN800
Medium Compatibility Compatible with raw, ground & surface water, potable water & irrigation water. Electrical conductivity ≥ 20 µS/cm 0 °0 C to +55°C
Sensor Housing Sheet polyurethane coated or stainless steel
Electrodes Stainless steel
Flange Steel
![Page 99: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/99.jpg)
Technical Specifications
98
98
Environment IP68 to 2m submergence in water
Connections DIN, ASME
4. Communication Output Specifications
The meter should have at least one or two pulse output (passive) and one or two status output (passive):
• Pulse output:
2 Passive pulse outputs
Volume / pulse is programmable
Pulse width is selectable: 1 ms, 5 ms, 50 ms, 100 ms
• Status output:
2 Passive status outputs
Function [selectable]: self checking, battery pre warning, battery final warning, counter overrun.
• The flow meter must support HART communication
FLOW CONTROL VALVE
1-NEEDLE VALVE (PLUNGER)
1.1.1.1 General
All valves shall have flanged ends design both sides acc. to EN 1092-2, ISO 7005/2
Control valve in straightway type.
All valves shall be customized with control device depending on operating conditions (With electric actuator)
All valves shall be manufactured and designed with low actuating torque due to pressure balanced valve piston
All valves shall be manufactured and designed with rotationally symmetrical flow guidance
All valves shall be manufactured and designed with annular flow cross section in each position
All valves shall be manufactured and designed with axial movement of the plunger by means of crank gear mechanism
![Page 100: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/100.jpg)
Technical Specifications
99
99
All valves shall be manufactured and designed with self-locking worm gear unit including position indicator
All valves shall be manufactured and designed with No blocking due to long piston guide rails
All valves shall be manufactured and designed with Elastic profile sealing ring located in the no-flow zone for high durability
All valves shall be manufactured and designed with Wear-resistant, corrosion-resistant and infiltration-proof piston guides in the body by micro-finished bronze weld overlay
All valves shall be manufactured and designed with Piston sealed by Quad Ring
The valve must be submitted with the following accessories:
1) Gaskets
2) Bolts
1.1.1.2 1.1 Potable Water Certification
All valves and its coating materials shall be certified for potable water use and shall contain no ingredients that may migrate into water in amounts that are considered to be toxic or otherwise dangerous for health, All material in contact with or likely to come into contact with water for public shall introduced with the requirements of Jordanian standard (JS 286) Whenever regulation changed it is the supplier /contractor responsibility to ensure conformity with any new requirements. Whenever potable water certificate is submitted for the coating material not the valve, the supplier shall furnish a document that relates this certificate with the valve itself.
All valves shall be certified as safe for transporting potable water by an independent testing laboratory.
1.2 Toxic Materials
All valves, coating, sealing and lining material shall be certified for potable water use and shall contain no ingredients that may migrate into water in amounts that are considered to be toxic or otherwise dangerous for health. The Contractor is prohibited to import or to use any of toxic or poisonous materials or sub materials used in piping, kinds of concrete or in soil in any kind of usage.
1.3 Third Party Witness
1.3.1 General
The supplier/contractor shall furnish an original certificate from the third party inspection agency showing all test results and analysis required by the applicable standard according to which the materials have been manufactured. The third party inspection agency shall under this contract, have witnessed the manufacture and testing operation to verify compliance with the technical specifications and the relevant standard. All certification should be from a certified third party from the applied standard (American Standard) and approved by Miyahuna, and the certification should be valid up to date and it should be written in English, and it must be shown in the certificate which batch is being tested to make sure that this certificate is for the right batch.
1.3.2 Testing
The media of the test shall be water.
![Page 101: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/101.jpg)
Technical Specifications
100
100
Pre-shipment test:
The supplier shall conduct on his expense the entire listed down test prior of shipping the valves.
1- Performance test. Prior to shipment, valves and pilot systems shall be factory tested to demonstrate the ability to fully stroke from close to open and then from the open to close position.
2- Seat leakage test. Valves shall be shop tested for seat leakage for duration of 2 minutes. There shall be no indication of leakage past the valve seat during this test period. The test pressure shall be either the hydrostatic pressure equivalent to working pressure. The test pressure shall be applied to the seat in the fluid flow direction.
3- Valve body hydrostatic test. Valve bodies and cover cavities shall be subjected to an internal hydrostatic pressure equivalent to 1.5 times the rated pressure, during the hydrostatic test, there shall be no leakage through the valve body, the end joints, or the stem seals, nor shall any part of the valve have any permanent visible deformation as a result of this test. The test duration shall be 2 minutes.
The manufacturer shall provide a certified statement that proof-of-design tests were performed as described in the standard and all requirements were successfully met.
1.3.3 Valves
No valve shall be accepted unless all type and batch release tests have been passed. The contractor also is required to submit quality assurance certificates, standard compliance and witness test certificate, from third party from the applied standard (American Standard) and approved by Miyahuna, that the components of the network must not be of any way toxic to the water being conveyed. And can be fully used for the distribution of potable water to a temperature up to 50° C.
Before dispatching the supplies another visual inspection shall be done in respect of proper packing and to certify the Bill of Lading for each shipment.
1.4 Testing at Place of Manufacture
The Contractor shall submit a certificate from the manufacturer certifying that all the items have been mill tested (at the manufactory) and those they have successfully passed the relative tests prescribed by the relative standards specifications.
NOTE:
ALL COST TESTS BEFORE AND AFTER THIS ITEM AND WETHER LOCAL OR ABROAD
SHALL BE BORNE BY THE CONTRACTOR AND THE COSTS SHALL BE INCLUDED IN
THE TENDER UNIT RATES.
![Page 102: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/102.jpg)
Technical Specifications
101
101
1.6 valves packaging
•All valves must be packed in such a way to allow instant use on site without additional cleaning.
•All valves shall be securely packed in crates and boxes to prevent damage during delivery. The cost of packing shall be deemed
to be included in the Contract Rates and crates will not be returned.
•Valves are normally supplied in separate cartons together with any associated small items, such as bolts and gaskets.
1.7 Identification
The supplier shall be responsible to ensure that each separate item, crate, or package has permanently attached to it, in a
conspicuous position, an identification plate of weather - resistant material on which are engraved or stamped;
•The Manufacturers Name
•Contents Description and Quantity
•Serial Number or Reference Number Identifiable on the Delivery Note and Cross Referenced to the Purchase Order Item
References.
•Weight
The shipment containers shall be marked with the following address;
Jordan Water Co. – MIYAHUNA L.L.C.
Tender Number – variable
In addition the container shall be marked with the following information;
•Total gross weight
•Total net weight
•Packing list reference number
1.8 Documents to be provided at Time of Tender
1. Potable water certificate from Third Party NSF 61
2. The CONTRACTOR shall provide detailed repair manuals for the gate valves supplied;
3. Quality assurance certificate (ISO 9001).
4. Upon request, the Contractor has to provide test certificates from the manufacturer’s internal quality control.
5. The supplier/ contractor shall supply full technical specifications and catalogues for the items to be supplied at the time of
tender.
![Page 103: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/103.jpg)
Technical Specifications
102
102
1.9 Documents to be provided upon delivery
The contractor shall submit at least the following documents:
1. Certificate of origin.
2. Packing list
3. Third Party certificates (Affidavit of Compliance)
4. Warranty.
5- Installation and maintenance manual
6. Any other documents requested by the Engineer and the hand over committee
All above documents must be valid and in English.
1.10 Marking
Markings shall include size, working pressure, name of manufacturer, and year of manufacture and model number or serial
number.
−
1.1.1.3 Material
Table 2:
Part Name Material
body ductile iron shall conform to the requirements of ASTM A395 or ASTM A536..
Piston guide rails overlay welded cast, forged or rolled bronze grade B, C, D or E
O-Ring NBR
Shaft Stainless steel 1.4021, AISI 420ASTM A240, UNS Designation S30400 or S31600, ASTM A276, UNS Designation S30400 or S31600, ASTM A743, grade CF8 or CF-8M, or ASTM A564, UNS Designation S17400
Piston and Rod Stainless steel ASTM A240, UNS Designation S30400 or S31600, ASTM A276, UNS Designation S30400 or S31600, ASTM A743, grade CF8 or CF-8M, or ASTM A564, UNS Designation S17400
Valve sealing: NBR
Shutter
Fork
Seal Ring
Stainless steel ASTM A240, UNS Designation S30400 or S31600, ASTM A276, UNS Designation S30400 or S31600, ASTM A743, grade CF8 or CF-8M, or ASTM A564, UNS Designation S17400
![Page 104: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/104.jpg)
Technical Specifications
103
103
Part Name Material
Body Seat
Bolts: Stainless steel ASTM A240, UNS Designation S30400 or S31600, ASTM A276, UNS Designation S30400 or S31600, ASTM A743, grade CF8 or CF-8M, or ASTM A564, UNS Designation S17400
Bearing bush cast, forged or rolled bronze grade B, C, D or E
Eye bolts for lifting: Stainless steel A4 (DIN EN ISO 3506) ASTM A240, UNS Designation S30400 or S31600, ASTM A276, UNS Designation S30400 or S31600, ASTM A743, grade CF8 or CF-8M, or ASTM A564, UNS Designation S17400
1.1.1.4 Design
Face to face dimension for the pressure range PN 16 and PN 25 or 250-300 PSI
Needle Valve (Plunger) shall be flanged design on request according to EN 1092-1 for the Steel flanges, and in accordance
with EN1092-2 cast carbon steel for pressure range (10-25) bar.
ROTATION OF OPENING: All valves shall open by turning to the left or counter clockwise, when viewed from the stem.
1.1.1.5 Coating
All iron components of the valve shall be coated (internal and external ) with a minimum 250µm fusion bonded epoxy
coating in accordance with AWWA C550 and shall be ANSI/NSF 61 and NSF 372 certified, the coating shall be non-toxic
and impart no taste to water..
.
• WASHOUTS
The types of Washout specified for this Contract, whether in concrete chambers or buried type, are as shown on the drawings. All Washouts shall be constructed as indicated on the drawings or as instructed by the Engineer.
If the flow cannot be discharged by gravity, flooded-manholes can also be constructed opposite the concrete wash-out chambers within the road corridor. Additional excavation and backfilling works shall be included in the unit rates of the washout.
The lengths of washout discharge lines may vary according to the location requirements on site and shall be agreed with the Engineer’s Representative prior to installation. Discharge lines shall be paid for as per unit rates of pipelines included in the Bills of Quantities.
![Page 105: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/105.jpg)
Technical Specifications
104
104
At place shown on the drawings or directed by the engineer, wash-outs shall be installed as follows:
a. For ductile iron main pipeline, the Contractor shall install a suitable flanged tee (T) to install the flanged washout valve. The branch shall be ½ of diameter of the main pipe diameter.
b. The washout shall have gate valve installed directly at the branch from the main pipe with all fittings and accessories as per drawings.
c. The wash-out pipes shall be extended to such a length and reach discharge area as is required for every particular site condition as not to flood the trenches or cause any damage to the surrounding area. In case no Wadi is available a flooded-manhole shall be constructed at the nearest road.
The unit rate washout pipe work shall include for the outlet structure and riprap, as shown on the standard drawings, unless noted otherwise.
• PRESSURE GAUGES
Pressure gauges shall be installed at all pressure reducing valves upstream and downstream of the valve and at selected strategic points in the distribution system for monitoring pressure fluctuation. They shall be of the bourdon tube type with sensor (for positive and negative pressures). All moving parts shall be of stainless. The dial face diameter shall be 160 mm and the accuracy class 1.6. The gauge must be suitable for a pressure range up to 16 bars.
The installation of the gauge shall be complete and shall include the connecting fittings to the main pipe, the gauge inlet pipe with 3 way cock and screwed joints.
• DISMANTLING JOINTS
Dismantling joints shall be installed where indicated on the drawings for convenient installation or re-installation of valves or similar items.
For prevention of any movement of the pipe joints adjacent to closed valves, dismantling joints shall be provided in general by restrained dismantling pieces (short version) or flanged adaptors as indicated on drawings or as directed by the Engineer.
Body and glands of steel welded dismantling pieces shall be capable of standing a working pressure of 16, 25 and 40 bars (according to the final design performed by the contractor and approved by the engineer) with bolts and nuts of stainless steel. The surface protection shall be epoxy powder coating. Rubber sealing rings made of Perbunan material, nitrile rubber or equivalent quality shall be used and shall be suitable and approved for the use with potable water.
• SPARE FLANGES, FLANGE ADAPTORS, COUPLINGS,
RESTRAINER CLAMPS
All spare flanges, flange adaptors and couplings shall be made of ductile iron GGG or GG shall comply with DIN equivalent ISO Norm and EN-GJS-400-18 / EN 1563.Flanges shall conform to the dimensions and drillings of the DIN 2501 / EN 1092-2 - PN 16.
All flanges and couplings shall be epoxy powder coated according to ISO14901 or to DIN 30677 Part 2, coating thickness shall be minimum 250µm, freedom from imperfections shall be tested by high-voltage method and shall be suitable and approved for the use with potable water.
![Page 106: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/106.jpg)
Technical Specifications
105
105
Seals shall be made of EPDM or NBR suitable an approved for potable water.
Restrained Flanges shall have a grip ring of steel for DI and ST pipes and a grip ring of Ms 58 (CuZn36Pb3) for uPVC pipes.
Wide range coupling or flange adaptors for Asbestos Cement / DI connections as indicated on the Drawings and in the Bill of Quantities.
Couplings shall be made of Steel, epoxy powder coated, with sealing rubber rings and lock-head bolts.
For connection of the existing to the new pipeline system, flexible couplings shall be installed as indicated on the drawings or as directed by the Engineer.
![Page 107: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/107.jpg)
Technical Specifications
106
106
17. PRESSU
RE TESTING
17.1 HYDROSTATIC PRESSURE TESTING OF DI PIPES
After completing the installation of a water main, or a section of the line, and before the joints are covered, a hydrostatic test of the line shall be made by the Contractor. A sufficient time for the curing of concrete thrust blocks must be allowed before the test is made. All backfilling and compaction over and around the pipes and thrust blocks must be completed except for the pipe joints to be left open for observation of any leaks, before the test is made. In accordance with EN 805, pipelines have to undergo an internal pressure test. The definitive criteria for performing this test on water pipelines are EN 805 and the DVGW’s worksheet W 400-2.
12 Test sections
If necessary, longer pipelines should be divided into sections. The test sections should be arranged so that the
• test pressure is reached at the lowest point of every test section;
• at the highest of point of each test section at least 1.1 times the level of the system test pressure
is reached;
• the amount of water required for the pressure test can be supplied and drained off; and
• the maximum length to be tested does not exceed 2.5 – 3 km.
13 The pipeline should be vented as well as possible with ‘pigs’ and filled from its lowest point with drinking water. Backfilling and interlocking
If necessary, pipes must be covered with filling material before the pressure test to avoid any changes in length. Backfilling the connections are optional. Pipelines that are not longitudinally force-locked must be anchored at their ends, bends, branches and reducers against the forces produced by the internal pressure. Assessment of the supports needed for this purpose should be done as per specifications.
There is no need for supports on longitudinally force-locked systems, provided that in each case the lengths to be restrained have been installed in compliance with the specifications.
Squeezing against a closed shut-off valve serves no purpose. The temperature on the outer wall of the pipe should be kept as steady as possible and must not exceed 20°C.
14 Filling of the Pipeline
For drinking water pipes, initial disinfection should be carried out along with the pressure test. This requires a concentration of at least 50 mg of chlorine per litre of water. Depending on how dirty the pipeline is, the level of chlorine can be increased to 150 mg per litre of water. The relationship of the volume of water added to the increase in pressure can give a clue to any leaks or insufficient venting. As the pressure increases, the rate of water consumption should therefore be noted bar by bar.
Where a line has been laid and is vented properly, the amount of water that needs to be pumped per bar of increased pressure is almost constant. Taking into account the compressibility of water and the elastic property of the pipe, it is (theoretically) c. 50 ml/m³ pipeline content/bar. In practice, this figure is around 1.5 to 2 times higher, as trapped air in the fittings and pipe and fitting connections has to be compressed.
![Page 108: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/108.jpg)
Technical Specifications
107
107
The table indicates the amounts of water required in liters per 1 bar of increased pressure for pipeline lengths of 100 up to 1,000 m, assuming a 100% extra allowance for trapped air.
Performing a pressure test
The following procedure for carrying out a pressure test on ductile cast iron pipes is described in DVGW worksheet W 400-2:
▪ Standard method (for all DNs, with and without CM lining)
▪ Shortened method procedure (up to DN 600, with CM lining)
We describe below the two most frequently used methods: the standard method and the shortened procedure.
The level of test pressure in both procedures is as follows:
![Page 109: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/109.jpg)
Technical Specifications
108
108
▪ For pipelines with allowable operating pressure of up to 10 bar:
1.5 x nominal pressure
▪ For pipelines with allowable operating pressure of over 10 bar: Nominal pressure + 5 bar.
The standard methodfor DI pipes
The standard method is carried out in three stages:
▪ Preliminary test
▪ Pressure loss test
▪ Main test
Preliminary Test
The purpose of the preliminary test is to saturate the Cement Mortar (CM) lining and to stretch the pipeline. To do this, the test pressure is kept constant for a period of 24 hours by permanently pumping in more air as and when required. If any leaks are found or any changes in length occur beyond what is allowed, then the pressure must be released from the pipeline and the cause remedied.
Pressure loss test
The purpose of the pressure loss test is to establish freedom of air movement in the pipeline. Air pockets in the pipeline can lead to incorrect measurements and/or cover up small leaks. A sufficient volume of water (ΔV) is drawn off from the line until a drop in pressure (Δp) of at least 0.5 bar materialises. The volume of water (ΔV) drawn off is then measured. The test pressure is subsequently restored. The pipeline is deemed to be adequately vented if ΔV is not greater than the allowable change in volume (ΔVzul ). If this is not the case, the line must be vented again. ΔVzul is calculated as follows: ΔVzul = 1.5 x a x Δp x L ΔVzul = allowable change in volume [cm³] Δp = measured drop in pressure [bar] L = length of the tested section [m] a = pressure constants that distinguish the type of pipe [cm³/(bar x m)]
➔ see following table
Main Test
Following the pressure loss test, the main test is then carried out. The duration of the test is as follows: Up to DN 400 3 h DN 500 up to DN 700 12 h over DN 700 24 h
![Page 110: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/110.jpg)
Technical Specifications
109
109
The test criteria are deemed to have been met if at the end of the test the drop in pressure is not greater than specified below: Nominal Pressure Test P ressure Max. Pressure loss.
10 15 bar 0.1 bar 16 21 bar 0.15 bar over 16 PN + 5 bar 0.2 bar
Test Report A test report should be produced. Templates for test reports are included in DVGW worksheet W 400-2. These contain the necessary details such as:
▪ Description of the line
▪ Test details
▪ Description of the test procedure
▪ Findings during the test
▪ Check note
The shortened standard method for DI pipes
The advantage of the shortened standard method is largely one of enormous savings in time. The time required is approx. just 1.5 hours The shortened standard method is carried out in three stages:
▪ Saturation stage
▪ Pressure loss test
▪ Leak test
Saturation level In order to achieve a high level of saturation, the test pressure is kept constant for half an hour by permanently pumping water. The key factor for saturation is first and foremost the level of test pressure. Unduly low pressure cannot be compensated for by prolonging the saturation level. Pressure loss test The purpose of the pressure loss test is to establish freedom of air movement in the pipeline. Air pockets in the pipeline can lead to incorrect measurements and/or cover up small leaks. At test pressure, a volume of water (ΔV) is drawn off from the pipeline. The resultant drop in pressure (Δp) is measured. In the subsequent leak test this becomes the allowable pressure loss (Δpzul). Following the pressure loss test, the test pressure is restored. ΔVzul is calculated as follow: ΔVzul = (DN x L) / (100 x k) ΔVzul = allowable change in volume [cm³] L = length of the tested section [m] 100 x k = proportionality factor, k = 1 m/cm³ The pipeline is deemed to be adequately vented if when drawing off the volume of water ΔVzul, the drop in pressure is greater than or equal to the minimum levels specified for Δp specified in the table below.
![Page 111: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/111.jpg)
Technical Specifications
110
110
Leak test
The pipeline is deemed to be air-tight if the fall in pressure (Δp) goes down at a constant rate over equal periods of time and over the duration of the leak test does not exceed the level ascertained (Δpzul) in the pressure loss test. The duration of the test is one hour.
Test Report A test report should be produced. Templates for test reports are included in DVGW worksheet W 400-2. These contain the necessary details such as:
▪ Description of the line
▪ Test details
▪ Description of the test procedure
▪ Findings during the test
▪ Check note
15 Stop Ends
A simple TEST END (Test facility) consists of a standard FG flanged-spigot pipe made of DI according to standard length for each diameter (about 0.5-1.0m long) onto which a threaded flange with a 2” (DN50) opening for accommodating ingoing water and out coming air. The TEST END may also include an opening through which the test water may be pumped from the line, if necessary. The test end shall be jointed to the pipe to be tested by means of a standard coupling (e.g. VJ Coupling) or two spare flanges. The Test End shall be secured with a temporary anchorage to hold it in place against the test pressure.
![Page 112: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/112.jpg)
Technical Specifications
111
111
16 Air Removal before Test
Before applying the test pressure, all air shall be expelled from the pipe. After all the air has been expelled, all stop cocks shall be closed and the test pressure applied as specified above. The line shall be filled slowly to prevent possible water hammer.
17 Examination during Test
All exposed pipes, fittings, valves, hydrants and joints shall be carefully examined during the pressure test. All joints showing leaks shall be rejoined until tight, or the pipe material replaced. Any defective pipes or joints, fittings or valves discovered as a result of this pressure test shall be repaired or removed and replaced by the Contractor at his own expense with sound material and the test shall be repeated until proved satisfactory to the Engineer’s Representative.
18 Cost of Testing
The Contractor shall provide a sufficient quantity of gauges, pumps, stop ends, and connections and all things necessary and suitable for the testing of all pipes as described herein. The Contractor shall also provide all necessary temporary works in connection with test, and shall remove the same on successful completion of the test. All tests shall be done in the presence of the Engineer’s Representative (Resident Engineer) and the results of such tests shall be elaborated in a test report and signed by the Contractor and Resident Engineer and handed over to the Resident Engineer. Payment according to schedule for pipe laying is based on such reports. All equipment, labour, materials, and water necessary for the carrying out of these tests to the complete satisfaction of the Engineer shall be provided by the Contractor at his own expense. Shall any test fail, the Contractor shall, after repairing and making good any leaks, carry out further tests all as described above until such test meets the requirements contained herein. All such tests and retests shall be at the expense of the Contractor.
17.2 PRESSURE TEST OF HDPE PIPES
19 Pressure inspection in accordance with the contraction method
The test procedure shall be carried out according to EN805:2000 in up to three steps:
▪ preliminary test;
▪ pressure drop test;
▪ main pressure test;
Preliminary test HDPE Pipes
The pipeline shall be divided into practicable test sections, completely filled with water and vented. After that the pressure shall be raised continuously and quickly (in less than 10 minutes) to the system test pressure (STP) at the lowest point shell be fixed at 16 bars. Maintain STP for a period of 30 minutes by pumping continuously or at short intervals. During this time carry out an inspection to identify any obvious leaks. Allow a further period of 1 h without pumping during which the pipeline may stretch by visco-elastic creep. Measure the remaining pressure at the end of this period. If the pressure has decreased by more than 30%, interrupt the preliminary phase and depressurize the test section. Check the test conditions e.g. influence of temperature, indication of leakage, and rectify the defaults. Only resume the test procedure after a relaxation period of at least 60 minutes.
![Page 113: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/113.jpg)
Technical Specifications
112
112
Pressure drop test HDPE Pipes
Reduce rapidly the remaining actual pressure measured at the end of the preliminary phase by discharging water from the system to produce a ∆p of 10-15% of STP. Measure precisely the removed volume ∆V. Calculate the allowable water loss ∆Vmax using the following formula and check that the removed volume ∆V does not exceed ∆Vmax. ∆Vmax = 1,2 x V x ∆p x (1/EW + D/e x ER) Where ∆Vmax is the allowable water loss in litres; V is the volume of the tested pipeline section in litres; ∆p is the measured pressure loss in kilopascals; EW is the bulk modulus of water in kilopascals; D is the internal pipe diameter in metres; e is the wall thickness of the pipe in metres; ER is the modulus of elasticity of the pipe wall in the circumferential direction in
kilopascals; 1,2 is an allowance factor (e.g. for air content) during the main test phase; For the interpretation of the result it is important to use the exact value of ER considering the temperature and the duration of the test. Especially for smaller diameters and shorter test sections ∆p and ∆V should be measured as accurately as possible. If ∆V is more than ∆Vmax interrupt the test procedure and vent again after the pipeline has been depressurized.
Main test HDPE Pipes
The visco-elastic creep due to the stress caused by STP is interrupted by the integrated pressure drop test. The rapid decrease of the pressure leads to a contraction of the pipeline. Observe for a period of 30 min (main test phase) the increase of pressure resulting from the contraction. The main test phase is considered to be successful if the pressure curve shows an increasing tendency and does not decrease at any time of this 30 min period. If during that period the pressure curve shows a falling tendency, it indicates a leak within the system. In case of doubt extend the main test phase to 90 min. In that case the pressure loss is limited to 25 kPa from the maximum value occurring within the contraction phase. If the pressure drops by more than 25 kPa the test fails. Rectify any defect in the installation revealed by the test and repeat the test. The repetition of the main test phase may only be done by carrying out the whole procedure including the relaxation period of 60 min in the preliminary phase.
![Page 114: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/114.jpg)
Technical Specifications
113
113
18. PAYME
NT
20 General Instruction to the contractor
Besides the replacement of house connections and tertiary main pipes most efforts must be driven by the contractor to decommission the old GI, ST, PVC and DI (DI pipes if in bad condition or DN80) pipes by disconnection completely from the existing system. In other words, the GI, ST, PVC and DI pipes which were selected by the Consultant and found by the contractor during construction in bad condition to be replaced by DI and HDPE pipes must be completely empty and entirely disconnected from the system. The contractor shall prove to the Engineer that all to be decommissioned pipes are empty and disconnected from the system and all house connections from such pipes are transferred to the operating system. It's the contractor responsibility to reconnect/ immigrate all connections & customers whether allocated inside the project area or outside which were connected to the old disconnected network to the new network whether discovered during work or during 3 consecutive supply rationing time, THE CONTRACTOR shall be borne any water tanks needed for disconnected real states as per Engineer Instructions . Only if the Contractor can prove the full decommissioning of old GI and ST pipes to the fully satisfaction of the Engineer the last remuneration for pipe laying will done to the Contractor as listed below:
Activities to be completed for remuneration Remuneration
in per cent (%) of Total
Remuneration in per cent
(%) in Total
Excavation, pipe laying, bedding an cover of pipes, backfilling
40% 40%
Pressure testing, road reinstatement 40% 80%
Sterilization, flushing, chlorination of the new pipes, prove of entirely disconnected decommissioned GI and ST pipes and submittal of the as-build drawings
20% 100%
As indicated in the Preamble to the BoQ,– Payment upon “Installation”, the contractor has successfully complete all the activities, as indicated in the table above for each row, to get the relevant remuneration (per cent in each row) as mentioned in the same row.
![Page 115: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/115.jpg)
Technical Specifications
114
114
19. ANNEX
1
-:ايثيلين البولي المجلفنو الحديد و الدكتايل و الحديد لخطوط التمديدات طريقة": أولا
تحضير الخندق و الطمم السفلي و الجانبي: - أ
الضروري ان يتوفر للتربه حيثما يلزم دعما ثابتا و دائما لاجل الحصول على تمديد سليم للمواسير. من -( ملم تحت خط الماسوره و يملْا بمواد ذات مواد 150الصخريه يحفر الخندق على عمق لا يقل عن ) للارض -
اسفل الخندق غير منتظم فقد يكون ناعمة و عندما تكون التربه مبتله او اذا كان الاساس طريا او حيثما بكون من الضروري زيادة هذة السماكه, و على المقاول القيام بهذه الاعمال على حسابه
ارضية تسوية يمكن حيثما و الصلبه الاجسام او القاسي الحجر من الخاليه الطريه او الترابيه الاراضي في اما - المهندس قناعات حسب و طولها على للمواسير نتظمام دعما لتعطي فراغات وجود دون مستويه تسويه الخندق
الماسوره تحتاسفل اكثر عمق الى الخندق ارضية اسفل على مباشرة المواسير بتمديد يسمح ان الممكن من فانه .ادناه المواصفات حسب و المشرف المهندس موافقة حسب و الناعمه المواد لوضع يكفي
عدم يجب و الممكنه بالسرعه المواسير دفن يجب كما المواسير تمديد قبل كبيره لمسافه الخندق حفر عدم يجب - .الدائم او المؤقت للدعم الماسوره تحت الصلبه الاجسام و الطوب وضع
BEDDING AND SIDE BEDDING:الانبوب حول الطمم -ب
( ملم فوق ظهر الماسوره و تدك يدويا و 300( ملم تحت اسفل الماسوره و حتى منسوب ) 150جميع الخنادق بمسافة ) تردم -
( ملم للسماكه المدكوكه 100بانتظام على طبقات لا تزيد عن )
الخالي من الشوائب. صويلح رمل منمواد الطمم السفليه و الجانبيه و حول الماسوره يجب ان تكون -
-: التاليه والمواصفات التدرج وحسب الشوائب من الخالي لحل صويرم .1
ر %امال نسبة لخنالم حجم
الوزن%من 1 عن لاتزيد الطينيهالكتله -
- CL الوزن من% 0ر1 عنلاتزيد
- So3 الوزن%من 0ر4 عنلاتزيد
- Coal and Lignite 0الوزن من% 1 عنلايزيد
("8/3ملم )9ر5
(4 قمر) ملم 4ر75
(16 قمملم )ر1ر18
(50 قمملم )ر0ر30
(100 قمملم )ر0ر15
(200 قمملم )ر0ر075
100
95-100
45-80
10-30
2-10
0-3
-:العلوي السطح الى الطمم ج
:الخنادق: اولا وضع قبل امكن ما الخندق تنظيف يتضمن العمل و الجلفانيز و الحديد و الديكاتيل مواسير فوق ووضعه صويلح رمل توريد -
.التامينذات تدرج ( او/و مواد .B.Cالخنادق من منسوب ما بعد التامين الى منسوب سطح الأرض من بيس كورس ) مطم إعادة -
المواصفات والمخططات النموذجية وجبمهبيلع تواحد) فوليه (و باطون للمقاطع العرضية مع اعاده الأوضاع الى ما كانو الدك بالاجهزه لمختصهتاالجها قبل من المحددة الأماكن الى موقعوتعليمات المهندس بما في ذلك نقل الفائض خارج ال
( ملم ودرجه الدك بما لا يقل 200الميكانيكية مع الرش بالماء و الدحل على طبقات بحيث لا تزيد سماكه كل طبقه منها عن )
% من الكثافة الجافه 95عن
( : الارصفه, الساحات, الشوارع) المعبده السطوح في الخنادق: ثانيا
![Page 116: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/116.jpg)
Technical Specifications
115
115
وحسب اتوالارصفه والاطاريف الى ما كانت عليه سابقا" يجب ان يتم بموجب المواصف وضع الشوارع و الساحات ةان اعاد - .المهندس وبموافقة المخططات على المبينه التفاصيل
والجسور الطرقلاعمال العامه الفنيه اتفواصمال يف ورد لما مطابقه بها المتعلقه عماللاا افةوك عملهستلما موادتكون ال - .تعديلات نعليها م طرأاوم 1991 لسنة والاسكان العامه الاشغال وزارة عن الصادره
و الافرادية الاسعار ضمن مشمولة الانقاض ترحيل و إزالة و عليه كانت ما الى السطوح وضع اعادة تكاليف تعتبر - .الكميات جدول فى ذلك خلاف يذكر لم ما علاوات اى لذلك يدفع لا
-والساحات المعبده )المسفلته(: الشوارع .1
-:كمايلي معبدهطوح الالس ضاعتعاد او - -المهندس كمايلي :موافقة على والحصول اللازم منسوبل الى الالوصوو دكالو الطمم عمالا من نتهاءبعد الا سم 15% حسب تجربة بروكترالمعدل وبسماكة 95وخلط وفرش ورش بالماء والدحل لدرجة توزيعتوريد و -أ
(. Sub-Base Courseى )ولبعد الدحل وذلك لطبقة الاساس الا
اكة م% حسب تجربة بروكتر المعدل وبس100ء والدحل لدرجة بالماش ورش وفر وخلط زيعتوريد وتو -ب
( . Base Course) الثانيه الاساس قةبطكللذو الدحل بعد سم15
1-3)فصل رجسووال الطرق لاعمال العامه المواصفات حسب متدرجه والثانيه الاولى الطبقتين ادتكون مو -ج
(. ب صنف 2-3 ولجد
ويتم الرش 2كغم/م1ر5( بمعدل MC-70) ت( من اسفل Prime Coat) يسيأسلتا الوجه رشو توريد -د
".ميكانيكا( وبسماكة حسب سماكه الطبقه Hot Bituminous Concrete) الساخنه الاسفلتيه الخلطه ودحل فرشتوريد و -هـ
في حال كانت الخلطة الاسفلتية طبقه واحدة . وفي حال وجود الدحل عدسم ب 8القائمة على الواقع وبحيث لاتقل عن
م لكل طبقة وترش طبقة لاصقة بين س 5طبقتين او اكثر يتم اعادة الاوضاع على اكثر من طبقه وبسماكة لاتقل عن
. 2كغم /م 5.و بمعدل RC 250الطبقات
مائل" اوبشكل رضيا)ع المعنيه البلديه او العامة الأشغال ووزارة الكبرى عمان امانه تصنيف حسب يسيهعند قطع الشوارعالرئ - 2
-:المعبده يجب ان تكون كمايلي ةالسطحل طبققب لطمما ادمو ان( ف
في مبين هو كما"( ايوم 28بعد 2كغم/سم200) تقلعنلا صغري مكعبي كسر وبقوة سم( 30) سماكة العاديه انهسمن الخر -1
".سابقا عليه كانت كما السطوح اعادة ويجب المخططات
.B.C) مواد من الطمم ادمو نتكو نباجي ين( اعلاه ولغاية طبقة التأم1البند ) يفليها ا لمشارا يهادالعمن اسفل طبقة الخرسانه -2
. واحد تدرج اتذ مهن في المخططات او بحصيبومهوكما" سابقا وتدككماورد وتردم ادناه واصفات( حسب الم
(( RC250من الخرسانه فانه يتم رشها بالاسفلت اللاصق رهخيالا الطبقه تكون عندما العرضيه طعامقال حالات في -ى
.2/م كغم 0.5 دلبمع
لانشاءات هالقياسي ردنيهلاا فاتاصموحسب ال ها( عند فحص .B.C) الحصويه الفرشيات مادة تدرج باتان متطل
كالتالي تكونب( ) صنف 2-3 دولج 1-3الفصل 1991لسنة لاسكاناهوماعال الاشغال وزارة عن صادرهالطرق والجسور ال
:-
خلحجم المن
% الوزن سبالمار ح الفتحات بعمنخل مر
100 "(2ملم ) 50ر0
100-70 "(1و1/2ملم ) 37ر5
85-55 "(1ملم ) 25ر0
80-50 "(3/4ملم ) 19ر0
----- "(1/2ملم ) 12ر5
70-40 "( 3/8ملم ) 9ر5
60-30 (4 رقمملم )ل 4ر75
50-20 (10 قمملم )ر 2ر00
![Page 117: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/117.jpg)
Technical Specifications
116
116
30-10 (40 قمملم )ر0ر425
15-5 (200ملم )رقم 075
.40 منخل منالمار 3/2 عن 200 رقم المنخل من المار نسبة تزيدوبحيث لا
-الارصفه : : ب
صفهوالحصول على موافقة المهندس تعاد وضعالار زمول الى المنسوب اللاوالوص والدك الطمم اعمال من نتهاءبعد الا سم 10 سماكة خرسانية مدة وشاملا المهندس تعليمات بموجب و المخططات و المواصفات حسب" قاباانت عليهسماك الى
.البلاط تحت
-: فالاطاري : ج .الحاله عليه ماتكون وحسب الصنع جاهزه الخرسانه اومن حجريه اما طاريفتكون الا
قاعدهوالعمل يشمل ال 3-1مونه الاسمنت والرمل بنسبة لباستعما لاصليا هاضعو حسب طاريفتركب الا
المهندس وبموافقة الاعمال جميع عيوما"(م28بعد 2كغم/سم200) لعاديها الخرسانه من الحجر خلف صفيحتلاانيهوخرسال
.المشرف
-:ايثيلينمواسير البولي -10
ملم 110من مواسير البولي ايثيلين قطر ( Service Lines )وتمديد واتمام وفحص خطوط مياه توريدعلى المقاول .1
الخ وجميع ما يلزم …شاملا كافة ما يلزم من مفاتيح وقطع من مرابط واكواع وتيهات وسدادات وقطع خاصةاو اقل
ليمات المهندس المشرف . حسب المواصفات الفنية لاعمال خطوط المياه والمخططات التفصيلية وحسب تعمن مواسير البولي ايثلين و اقل على خطوط المياه القائمة PE 63( قطر Service Lines) المياهيتم توصيل خطوط .2
:كمايلي المقترحةاو Under خاصهعلى خطوط مواسير الدكتايل الرئيسة سواء كانت محتويه على الماء او فارغه باستعمال قطع .أ
Pressure Tapping Gunmetal Ferrule and Saddle installed on the mains وحسب ماهو مبين
.المشرفعلى المخططات وبموجب تعليمات المهندس :كالتاليعلىخطوط مواسير الحديد يتم التوصيل .ب
ليتم التوصيل ولحام " مفة " بالقطر المطلوب ىعمل فتحة في الخط الرئيس يتم القائمةللوصلات المنزلية .1 عليها .
، يتم قص الخط الرئيس وتركيب ولحام " تي " بقطر يساوي قطر ”2قطرللخطوط الفرعية ) الخدمية ( .2
.عليها" ليتم التوصيل 3" او 2الخط الرئيس وفرع قطر
مواسير البولي ايثلين ( يتم اعادة ربطها وتوصيلها على من كونهاللوصلات المنزليه القائمة )في حال .3 Self - tapping Ferrule and saddle باستعمالالخطوط الفرعيه من مواسير البولي ايثلين المقترحة
placed on the service line, or equal tee as indicated on the Drawings وحسب تعليمات
.المشرفالمهندس حسب المواصفات المرفقة ( Ferrous Tracking Tape ) تحذيريعلى المقاول توريد وتمديد شريط .4
وذلك لمواسير البولي ايثيلين فوق طبقة الطمم الناعم )طبقة التأمين (مباشرة وتعتبر التكاليف كاملة مشمولة ضمن الاسعار الافرادية لاعمال تمديد مواسير البولي ايثيلين .
( من المواصفات 5 – 3كون المقاول مسؤولا عن تزويد اسياخ اللحام من اجود الانواع حسب البند ) ي -ج
العامه و الات اللحام و القص و عدد كافي من شفرات القص و المعدات و الكهرباء لعمل و صلات انابيب الحديد و كذلك المعجون الخاص الخالي من الرصاص للوصلات المسننه الخاصه بالانابيب المجلفنه
( و lubrication Pasteبيب الدكتايل )المستعمله لتنفيذ و صلات انا والمعجونه ايثيلينوأنابيب البولي
مواصفات العامة وموافقة المهندس المشرف و تعتبر تكاليف حسب الوصلاتكذلك مواد عزل وتغليف .المياهالاعمال المذكوره اعلاه مشموله ضمن السعر الفردي لاعمال تمديد انابيب
المتطلبات الاساسيه لاعمال تمديد انابيب المياه باقطارها وانواعها المختلفه بموجب المواصفات و -د :يليالمخططات و حسب تعليمات المهندس المشرف لكافة البنود كما
![Page 118: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/118.jpg)
Technical Specifications
117
117
.عمالهتنظيف و تسوية و تحضير مواقع و مسارات خطوط المياه لافساح المجال امام معدات المقاول و .1ع التربه سواء كانت ترابيه او صخريه او حوريه او غيرها و بسطوح مختلفه اجميع انو حفر الخنادق في .2
درج اسفلت و غيرها و اعادة اوضاع السطوح كما كانت عليه ترابي،خرساني،بلاط،سواء كانت ) .سابقا
قطع وتمديد كافة انواع المواسير واقطارها شاملا جميع القطع من تيهات و اكواعونقاصات و ال توريد .3الوصلات السليمه للمواسير و تغليف الوصلات و كل ما يلزم لتمديد المواسير على عمل شاملاالخاصه
.العقداكمل وجه حسب شروط و مواصفات وتركيب كافة انواع واقطار المفاتيح وعدادات المياه مع القطع الملائمه من فلنجات و براغي توريد .4
الخ وكافة ما يلزم لاتمام العمل على اكمل وجه.… وصواميل و كسكيتات " و ما فوق و محابس 8توريد جميع المواد اللازمه و انشاء غرف المفاتيح ) وذلك للمحابس قطر .5
وما فوق (. من الخرسانه المسلحه كامله و السعر يشمل ايضا الحفريات اللازمه "1 2/1الهوايات قطر
و الخرسانه العاديه للنظافه و حديد التسليح و اعادة الردم حسب المواصفات و الاعمال المعدنيه الخاصه Extension....... الخ و كذلك وصلات الاعمده و علب السطح ) درجاتبالغرف من اغطية و
Spindle & Surface Box و جميع ما يلزم بموجب المخططات التفصيليه و المواصفات و حسب )
.المهندستعليمات حيثما تتقاطع مع خطوط الصرف الصحي أو عند مرورها الخرسانةالمسلحةو عمل تغليف للمواسير من اللازمةتوريد جميع المواد
( حيثما يلزم Thrust Blocks) الخرسانيةالمسلحةلدعامات في الاوديه وحيثما يلزم وحسب تعليمات المهندس وكذلك ل
بموجب المخططات الأعمالاللازمةوجميع والطوباروحديد التسليح العاديةللنظافةحفريات لازمه والخرسانه أيضاأيةويشمل والمواصفات وحسب تعليمات المهندس
Electrofusionاللحام الكهربائي بواسطة 125اللازمة لاعمال تمديد مواسير البولي ايثلين المواصفات**
.للقطع الصانعة الشركة مواصفات وحسب البعض بعضها مع الكهربائي اللحام والمواسير القطع قابلية من التاكد •
بالموقع الا الاكياس هذه فتح وعدم المباشرة للشمس لاتتعرض وان مغلقة اكياس ضمن موجودة اللحام قطع ان من التاكد • مباشرة اللحام عملية اجراء وعند
تكون ماكنة اللحام ومنطقة اللحام موجودة تحت نفس الظروف الجوية ان •
-م10- من الحرارة درجة تتراوح وان والثلج والمطر الريح مثل مناسبة الغير الجوية الظروف من اللحام منطقة حماية •
م45
والشحوم والزيوت والدهون الغبار مثل الملوثات انواع كافة من القطعة على او الماسورة على سواء اللحام منطقة حماية • PEال بتنظيف الخاصة بالمادة التنظيف اعادة يجب ذلك حدوث حال وفي بالايدي المنطقة هذه لمس وعدم
اجراء عملية اللحام خطوات
عامودي بشكل وقطعها الماسورة على العمل منطقة تنظيف •
مبين ماهو عند التقشير طبقة لاتزيد ان على المتاكسدة الطبقة لازالة بذلك الخاصة الاداة بواسطة العمل منطقة تقشير • :التالي بالجدول
الاقصى لطبقة التقشير الحد الادنى لطبقة التقشير الحد الخارجي للماسورة القطر
ملم. 2 ملم. 2 ملم 20-25
. ملم 25 ملم. 2 ملم 32-63
. ملم 3 . ملم 2 ملم 75-225
. ملم 35 ملم. 2 ملم 225 اكبر
حسب تعليمات الخاصة بالشركة الصانعة او
PEمنطقة العمل بواسطة المنظف الخاص بمادة ال تنظيف •
العلامات على الماسورة واحضار القطع اللازمة توضع •
![Page 119: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/119.jpg)
Technical Specifications
118
118
مسبقا الموضوعة العلامات حسب القطعة تدخل •
القطعة بواسطة اداة التثبيت الخاصة بذلك تثبيت •
الشركة طريقة وحسب الحام بماكنة الخاصة والاجرءات التعليمات واتبع ماكنة مع القطعة الاقطاب توصل • .الصانعة
الفترة وتكون التثبيت اداة تزال ثم للتبريد اللازمة الفترة وتترك الاقطاب ازالة تتم الحام عملية من الانتهاء بعد • :التالي بالجدول مبين هو كما للتبريد اللازمة
الادنى للوقت اللازم للقطع والسوكت الحدSDR11
اداة ازالة قبل اللازمة الفترة الخارجي ملم القطر (دقيقة) التثبيت
( دقيقة) الضغط فحص اجراء قبل اللازمة الفترة
بار 6اكثر من الضغط بار 6اقل من الضغط
20-32 6 10 30
75-110 10 20 60
125-160 15 30 75
20 45 90
SDR17
الخارجي القطر )ملم(
اداة قبل اللازمة الفترة )دقيقة(التثبيت
(دقيقة) الضغط فحص اجراء قبل اللازمة الفترة
بار 6اكثر من الضغط بار 6اقل من الضغط
125-160 15 30 75
180-225 20 45 90
Saddlesالادنى للوقت اللازم ل الحد
بار 6اكثر من الضغط بار 6اقل من الضغط )ملم(القطر40 10 30
63-315 20 60
-: الخاصة القطع و المفاتيح و المواسير كميات -19على المقاول ان يعمل مسحا للخطوط و تقديم مخططات تنفيذيه و التاكد من نقاط الربط ومن الاطوال من كل من المواسير
المطلوبة باقطارها المختلفة وكذلك كميات القطع من تيهات و اكواع و سدادات ونقاصات ...... الخ و المفاتيح بانواعها . لازمة لاتمام الاعمال و اخذ الموافقه عليها قبل استيرادهاو اقطارها المختلفة و القطع الخاصة ال
-الجداول:-20
جداول التطابق: Technical Catalogue & Compliance Tablesالنشرات الفنية وجداول التطابق
على المقاول أن يقدم النشرات الفنية لكافة المواد التي تدخل في عمل المشروع وأن يقدم النشرة الفنية الأصلية للمادة المعروضة تماما" الخاصة بها بالذات أو التي تشملها فنيا" مع التأشير على المادة طرازها في النشرات الفنية المرفقة
المادة المعروضة وطرازهاوالمطلوبة )وطرازها أن ذكر في العطاء ( والمواصفات تقديم جدول مقارنة مفصلا" فيه أسمونها وأي ملاحظة على ذلك كما يالفنية الكاملة للمعروض مقارنة بالمطلوب في العطاء وبيان الاختلاف والتطابق فيما ب
الاختلافات أو التطابقات الفنية وذلك ويجب تقديم المواصفات القياسية المصنعة عليها المادة المطلوبة والمعروضة لاثبات لاخذ موافقة المهندس المشرف .
![Page 120: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/120.jpg)
Technical Specifications
119
119
-:الخرسانية الدعامات -25
ملائمة عدم حالة وفى بار 16 ضغط ذات المياه لخطوط هى النموذجية المخططات فى الواردة الخرسانية الدعامات
للمهندس تقديمها و المناسبة الدعامة بتصميم المقاول يقوم الخط لضغط المخططات فى الواردة الخرسانية الدعامة اضافية تكاليف باى المطالبة بدون و عليها للموافقة المشرف
المشرف المهندس قبل من عليها الموافق الكميات حسب المحاسبة ويتم
26- The following rules shall be considered for the design and installation of house connections:
If the house connection lines are close enough, it can be installed in the same trench but will be tapped separately.
House connections for a single customer shall be connected separately if the meter locations are more than 10 meters apart from each other.
Buildings with 1 (one) up to 4 (four) water meters shall be tapped once at the main line using a pipe HDPE ISO25.
Buildings with 5 (five) up to 20 (twenty) water meters shall be tapped once at the main line using a pipe HDPE ISO32.
Buildings with 21 (twenty one) and above water meters shall be tapped once at the main line using a pipe HDPE ISO63.
If mains are laid on one side of the road, connections on the other side shall be connected once with an appropriate diameter and then split into individual connections. (e.g. 10 houses on opposite side, tapping ISO32 (DN25), split into 10 individual ISO 25 (DN20) connections). For installing a separate service valves at the tapping to close these sections without interrupting supply to an entire area during repairs, the contractor has to receive the approval from the Engineer in corporation with the client.
Commercial, institutional and industrial customers shall receive individual connections and has to be decided with the Engineer and the Client.
Water meters shall be moved to suitable locations close to the entrance of a building or plot if possible.
Water meters shall be protected by lockable meter cardboards. The contractor shall report missing or damaged meter boxes to the Engineer. Meter box installation is not the responsibility of the contractor.
In the case where buildings do not have property walls and the buildings are far from the street, the meters shall be installed at the building wall nearest to the street or road.
The size of the service connection shall be ranked according to the number of flats connected to one main customer connection as follows:
Table 19-1: House Connection Collection Pipes (Sub-Mains)
Max. No. of Flats / Plots
Size of HDPE
before meters
inch (BS)
Size HDPE
Diameter Nominal
DN mm
Outside Diameter
ISO
mm
≤ 4 3/4" DN 20 25
5-20 1" DN 25 32
![Page 121: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/121.jpg)
Technical Specifications
120
120
21-50 2" DN 50 63
For big consumers such as schools, hospitals, and other large community buildings, the diameter of service connections shall be ISO 32mm minimum; according to the existing diameter, or as calculated according to the actual demand.
![Page 122: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/122.jpg)
Technical Specifications
121
121
20. ANNEX
2
الجرثومي الفحص اجراء :الجرثومي الفحص اجراء عند مايلي مراعاة مقاولال على
للغسيل من مصادر المياه التابعة لشركة مياهنا ) الخط الذي سيتم الشبك عليه او محطات يقوم المقاول باخذ المياه – 1
شركة مياهنا القريبة ( او اي مصدر مائي معنمد من قبل سلطة المياه و على نفقة المقاولتبقى مسؤولية المقاول قائمة لحين ظهور نتائج عينات الفحص الجرثومي و في حال فشل العينات الجرثومية يقوم – 2
المقاول باعادة التعقيم من جديد ويتم اخذ عينات جرثوميه حتى تنجح العينه . اثمان وتقدر المياه اثمان حيث من المقاول نفقة على والغسيل المقاول حساب على المياه واثمان المخبريه الفحوصات تكاليف تكون (. الصهاريج سعر) مياهنا لشركة الرسمي السعر اضعاف بثلاثة المياه
: الفحوصات انواع قبل من معتمد مختبر اي او مياهنا شركة مختبرات في ذلك و الخاصة نفقتة على و التالية الفحوصات اجراء المقاول على
الغاية لهذه المختصة الجهات1 –PH
2 –Turbidity
3 –R-CL2
2 SURVEY and EARTH WORKS 2.1 SURVEYING, PIPE and NODE LOCATING and MARKING
surveying, pipe and node locating and marking includes as follows:
- Surveying,
- Pipe and Node location with electronic equipment, and trial pits
- Marking and recording of the route of the existing and new constructed pipeline, valves, interconnections, etc. Any surveying works shall be borne by the contractor as per engineer's instructions .
![Page 123: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/123.jpg)
Technical Specifications
122
122
21. ANNEX
3
: الميداني المكتب تجهيزات
العطاء وثائق في الاضافية الخاصة الشروط في وارد ماهو حسب
![Page 124: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/124.jpg)
Technical Specifications
123
123
22. ANNEX
4
Environmental Mitigation and Monitoring plan for Associate FARA00 (BA-
08))
![Page 125: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/125.jpg)
0 | P a g e
1 INTRODUCTION
1.1. USAID Regulations:
Source and Nationality of Procurements (Attached)
Except as specified in this contract or as USAID may otherwise agree in writing, all goods financed under this contract shall have their “source,” and the suppliers of all goods and services financed under this contract shall have their “nationality,” in countries included in Geographic Code 937. Goods and services financed under this contract must be available for purchase in the applicable Geographic Code at the time of purchase. Geographic Code 937 includes: Jordan, the United States or a developing country (for a list of eligible developing countries, please see:
https://www.usaid.gov/sites/default/files/documents/1876/310maa.pdf.
“Source” means the country from which a commodity is shipped to Jordan or Jordan itself if the commodity is located in Jordan at the time of the purchase. Where, however, a commodity is shipped from a free port or bonded warehouse in the form in which received therein, ‘‘source’’ means the country from which the commodity was shipped to the free port or bonded warehouse.
“Nationality” refers to the place of legal organization, ownership, citizenship, or lawful permanent residence (or equivalent immigration status to live and work on a continuing basis) of suppliers of commodities and services.
Any individual transaction not exceeding $25,000, excluding those specifically requiring USAID approval, may be procured from any non-prohibited source or nationality, Geographic Code 935. Geographic Code 935 includes any country is not a prohibited source. For a list of prohibited sources, please see: https://www.usaid.gov/sites/default/files/documents/1864/310mac.pdf.
In addition to the source and nationality requirements above, any motor vehicles purchased with funds under this contract must be manufactured in the United States, or a waiver from USAID must be approved.
1.2. The Bill of Quantities (BOQ) includes this preamble and the various bills of
quantities.
1.3. The BOQ shall be read in conjunction with the conditions of contract, the
technical specifications, this preamble and the detailed tender drawings. The BOQ
is a combined material supply &installation BOQ.
1.4. The quantities set out in the BOQ are close estimated quantities required for
Installation or Supply and installation quantities and they shall not be taken as
![Page 126: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/126.jpg)
1 | P a g e
100% accurate quantities required for the finalisation of the works to be executed
by the Contractor in fulfilment of his obligations under the Contract.
1.5. If the Quantity of the Installation of any item increased or decreased compared to
the BOQ – the Contractor has no right to change the unit rate or to claim more or
additional costs.
1.6. The Bill of Quantities is based on Unit Rates. The contractor is obliged initially
order within the“ 1stList of Order ”50% (fifty per cent) of the material needed for
the works as an initial required quantity of materials, within 2 weeks after awarding
the contract, to avoid delays in the installation upon the Engineer and Miyahuna
approval
The contractor can get paid 60% for the material on site, according to the
purchase invoice from the manufacturer supplier. The contractor has to submit,
together with the mentioned invoice, a detailed Price Analysis List (cost
breakdown) for each delivered material item. During execution, the payment will
be deducted from the contractor’s interim invoices according to the executed and
installed amount for the material items.
During the initial supply procurement, the contractor shall review the design
drawings and execute the survey work under the Engineer supervision to
elaborate so called shop-drawings. As for the final material procurement, so
called “2nd List of Order”, the contractor should submit the shop drawings and
the quantities needed for the project within 90 days from the commencement
date for all the works as the 1st order of material mentioned above should be
delivered onsite otherwise; no interim payment will be paid for the contractor’s
work until all the materials required for the project is ordered, approved and
submitted including the evidence for ordering these material such as Proforma
invoice.
Also the 2nd List of Order is subjected to the Engineers and Miyahuna approval
and has also contain material, quantity, manufacturer, country of origin, supplier
in accordance with his approved contract.
For the 2nd List of Order, the contractor can get paid 60% for the material on
site according to the purchase invoice from the manufacturer supplier, included a
Price Analysis List (cost breakdown) for each delivered material item, as indicated
before. The payment, and later on, the deduction from the contractor’s interim
invoice will be as same as by the 1storder.
Oversupply, if needed by Miyahuna, shall be handed over to a location given by
Miyahuna, and shall beproperly documented with accurate quantities listed and
approved by the Engineer, after commissioning and handover of a complete
tender batch.
![Page 127: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/127.jpg)
2 | P a g e
The oversupply of materials shall be paid according to an agreed price, for each
material item, after negotiations between the contractor and the Employer. The
Client has the right to buy the oversupplied materials or to reject these extra
materials which will be then the property of the contractor.
1.7. The permanent works shall be subject to measurement as practiced in unit price
contracts, notwithstanding any general or local customs, except where otherwise
specifically described or prescribed in the Contract.
1.8. The unit rates and unit prices in the BOQ shall, except where otherwise provided
in the Contract cover all the Contractor's obligations under the Contract, such as
verification survey (setting-out), pipe and valve tracing, test pits, existing pipes
locating for connection, indication and marking in the field, preparation of Shop
Drawings, labour, materials, supervision, stores management, maintenance,
insurance, profit, overheads, risk, taxes and duties for the proper construction and
completion of the works including testing, operational and any required training of
nominated staff, maintenance during the defects liability phase, and remedy works
of detects as specified in Contract.
1.9. Payments will be made strictly according to actual measurement of units in the
field. Any supply &installation for which no unit rate exists in the BoQ, such unit
prices will be requested from the Contractor prior to execution of such works on
the day of amendment.
1.10. Contractor shall conduct survey for the whole road width and locate all existing
utilities, and shall be responsible for the coordination with all authorities and
utilities providers.
1.11. All works necessary in one area must be finalised (final road reinstatement
excepted) before permit for excavation in next area will be given.
1.12. The prices and rates entered by the Contractor in the BOQ shall cover the
complete and finished supply &installation in final position as required by the
Contract Document including all costs and expenses which may be required in and
for the construction and maintenance of the works together with all risks liabilities,
insurance and obligations imposed or implied by the Contract and disconnection
of existing pipes shall include investigation, with all the material needed to do
the wet dry test per district successfully with all the needed connections and
disconnections .
1.13. Prices must correspond to the relative value of such items in relation to the total
amount of the tender. They must in particular not be of such nature as to distort
the comparison of tenders or to result in interim payments which are clearly
disproportional to the normal value of the services to be rendered.
1.14. Without affecting the generality of the foregoing provisions, the Tenderer will be
deemed to have taken full account of all requirements and obligations, whether
![Page 128: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/128.jpg)
3 | P a g e
expressed or implied, covered by the documents and to have priced the items
herein accordingly. The rates must therefore include for all incidental and
contingent expenses and risks of every kind necessary to fulfil the Contractor’s
obligations in accordance with the Contract. The Contractor shall be obliged to
follow all latest revision of regulation and specification required by relevant
Authorities (e.g. GAM and MPWH) and include in the rates all cost and expenses
arisen from these regulation and specification.
The rates entered by the Contractor in the BOQ are deemed to include for all
costs and expenses involved with the works (installations) including (but not
limited to) the following:
a. The provision, storage, transport, handling, delivery of procured material,
equipment, use, distribution and maintenance of all materials, plant, equipment,
machinery and tools including all costs, charges, dues, demurrage or other outlays
involved in transport and importation;
b. The provision and maintenance of all staff and labour and their payment,
accommodation, transport fares and other requirements;
c. Setting out, including the location and preservation of survey markers, measurement
and supervision, update of tender drawings to works drawings in regards to actual
proposed pipe location;
d. The provision, operation, maintenance and removal upon completion of the
Contract of all Contractors’ site installations;
e. The provision, storage, transport, use, handling, distribution and maintenance of all
consumable stores, fuel, water and electricity for the Contractor's site installations;
f. the provision and maintenance of all temporary detours, of traffic control measures
and of reinstatement upon completion of the existing roads;
g. paying fees and giving notice to Authorities
h. emergency water supply to customers of Miyahuna if necessary
i. preservation of a clean site and reinstatement of site after completion of works
j. protection of adjoining property;
k. all contractual submissions by the Contractor;
l. all quality control measures including inspections and tests;
m. all works and materials of permanent and temporary nature required for execution
of works in compliance with regulation and specification given by authorities;
n. damage caused to the works under construction, plant, materials and consumable
stores by weather;
o. repairs to the works either prior to or during the defects liability period;
p. co-ordination with other Contractors or Authorities carrying out work either in
connection with or adjacent to the works;
q. Overheads, on-costs and profit
r. Exchange Rate fluctuations
s. Material cost increases
t. all temporary works including watching, lighting and temporary access
![Page 129: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/129.jpg)
4 | P a g e
u. clearing away rubbish as it accumulates and keeping the site in a tidy condition
1.15. No claim will be considered for further payment in respect of any work or method
of execution which may be described in the Contract or is inherent in the
undertaking of the works or detailed in the drawings.
1.16. A price or rate shall be entered against each item in the BOQ whether quantities
are stated or not. Items against which no price or rate is entered shall be deemed
to be included in other units or items of the BOQ. The unit price or rate entered
against any item shall take precedence over any miscalculation in the total sum
against that item. Where separate items have not been provided in the BOQ for
work required under the Contract then the cost of such work shall be deemed to
have been included in the prices and rates for other items.
1.17. The total quantity included in the final measurement of each item shall be measured
to the nearest integer relative to that item, or to one decimal place if so indicated
in the BOQ.
1.18. The pipe quantities are expected to be in the paved streets. However, in the case
of the need for construction in natural ground surfaces, 15% of the price provided
for construction in asphalt surfaces shall be deducted for the same item.
1.19. The following abbreviations are used in the Bill of Quantities:
mm millimetre
m meter
m³ cubic meter
m² square meter
km kilometre
kg kilogram
t tonne
No number
h hour
€ EURO (European Currency)
mth month
% percentage
OD Outside Diameter
DN Diameter Nominal
PN Pressure Nominal
L length
LS Lump Sum
JOD
W.O
Jordanian Dinar
Wash-Out
1.20. The item descriptions in the BOQ are only in sufficient detail to ensure
identification of the supply &installation covered under the technical
![Page 130: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/130.jpg)
5 | P a g e
specifications, contract conditions, and as shown on the detailed drawings.
Therefore, the BOQ shall be read together with the rest of the tender documents.
Descriptions of the supply &installation given in the specifications or drawings are
not necessarily repeated in the identifying descriptions of the items in the BOQ.
1.21. The items in the BOQ describe in detail, what supply, works and cost shall be
included in such unit. The Contractors pricing the BOQ shall be aware that this
BOQ is a UNIT PRICE contract. The Contractor shall update the submitted
tender drawings after his survey and pipe detection with his proposal for the new
pipe installation locations as “Shop Drawings”, which will be subject to approval
by the Engineer.
1.22. For other items to be installed as network Nodes with or without Gate Valves, Air
Valves, additional Gate Valves, disconnection of to be decommissioned pipes, the
detail drawings are binding, but subject to amendment on site if necessary.
1.23. Further requirements for the supply &installation in question may be stated in
other clauses in the specification or on the drawings and the Contract rates shall
be deemed to cover also the cost of complying with any such further requirements.
1.24. The materials and equipment offered by the Contractor must fulfil the
specifications set for this contract and are binding throughout this contract.
1.25. The project is funded by the United States Agency for International Development
(USAID) by which Jordan Water Company ( Miyahuna) has entered into an
agreement which has a fixed time-frame and payment schedule payable to
Miyahuna based on completion of predetermined Milestones. The Milestones will
be provide to the contractor at an early stage and the contractor must take into
account the priorities of Milestones in his work plan and implementation schedule
to avoid any damages to the employer or hinder Miyahuna from submitting its
invoices to the USAID, as a result of the failure to complete any or all items
included in the contract within the allocated time. Miyahuna reserves all the
contractual and financial rights in case of non-compliance by the contractor with
the above.
2 SCHEDULES OF PAYMENTS
2.1 Interim Payment
The interim payments to be made to the Contractor are paid according to actual measurements on site with all supporting documentation such as drawings and material lists. Interim payment requests shall be presented to the Engineer including all measurement sheets, material lists, stock cards, day work schedules, drawings and amendment orders, elaborated by the Contractor in full compliance with the contractual requirements set in the conditions of contract and specifications
![Page 131: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/131.jpg)
6 | P a g e
on either monthly basis or if minimum amount (see Appendix to Tender) for such interim payment is reached or according to agreement of date with the Engineer. Only the payments made under final payment certificate are considered as payments for the permanent works completed. If at any time, prior to the issue defects liability certificate, the quality or quantity of the works are found to be unsatisfactory or do not conform to the requirements of the Contract, the Engineer is entitled to deduct or withhold the amount sufficient to remedy such unsatisfactory works from the successive interim or other payments to the Contractor. All interim payments are subject to the deduction of retention money as specified in the Condition of Contract.
2.2 Payment upon “Installation“
The supply &installation described in the Bill of Quantities will be paid only upon completion and acceptance of the supply &works as required by the contract. The Contractor may request for interim payments at installation not exceeding following schedule according the Particular Technical Specifications, The contractor has to complete successfully all the activities, as indicated in the table below for each row, to get the relevant remuneration (per cent in each row) as mentioned in the same row.
Activities to be completed for remuneration Remuneration in percent (%)
of Total
Remuneration in percent (%)
in Total
Excavation, pipe laying, bedding an cover of pipes, backfilling
40% 40%
road reinstatement 20% 60%
Pressure testing 20% 80%
Sterilization, flushing, chlorination of the new pipes, prove of entirely disconnected decommissioned GI and ST pipes existing line (ex. HDPE, ST, GI,...etc) and submittal of the as-build drawings
20% 100%
2.3 Payment upon “Installation of Chambers“
Activities to be completed for remuneration Remuneration in percent (%)
of Total
Remuneration in percent (%)
in Total
Excavation, Civil Works 30% 30%
Installation of Mechanical works 30% 60%
Commissioning 20% 80%
submittal of the as-build drawings 20% 100%
3 DESCRIPTION OF BOQ ITEMS
The following chapter describing the main BOQ items referring to the attached BoQ, including the main tasks for the mentioned items and the contractor shall also refer to the drawings, technical specifications and conditions of contract.
![Page 132: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/132.jpg)
7 | P a g e
1. DUCTILE IRON PIPES
See Technical Specifications and drawings.
SUPPLY & INSTALLATION of Ductile Iron Pipes C class
The item for INSTALLATION of Ductile Iron pipes includes the following:
- installation of Ductile Iron pipelines and supply and install all required fittings and accessories according to the Technical Specifications,
- Marking of pipe trench location,
- Cutting of road surface (asphalt) and removal of asphalt,
- Careful removal and storage of side walk tiles or plastering stones,
- Excavation in any type of soil of trench to the depth of bottom of pipe plus sand bedding according to diameter as specified in the Specifications,
- Trench protection by timbering,
- Transport and disposal of excavated material,
- Import of appropriate sand, sand bedding below, aside and above according to Specifications and detailed drawings,
- Including all required thrust blocks and encasement whenever required in accordance with the technical specifications and drawings,
- Backfilling of trench with imported material compaction in layers according to Specifications of the authority owning the road,
- Supply and Installation of a warning and tracing tape for pipes according to the technical specifications,
- Reinstatement of surfaces as specified in the detailed standard drawings and to the specifications of the authority owning the road,
- Cleaning and flushing the interior of the pipes after installation,
- Pressure testing of pipeline, including the filling of the line with water for the entire pipeline section including bends and T-Pieces`, Valves, AV, and also with all pipe saddles installed as part of the main pipe,
- Including provision of the testing equipment, water shall be supplied and paid by the contractor,
- Flushing of the pipeline,
- Chlorine, disinfection of the pipeline,
- Final flushing and tests,
- Survey of the new pipeline and elaboration of as-built drawings,
- Including all connection and disconnection points shown on the drawings.
- Including all required test pits to locate the connections and disconnection points.
- Including disconnection of any redundant pipe, reconnection / immigrate of all connections and costumers whenever required, whether allocated inside or outside the project area.
In case the road was newly asphalted by GAM the Contractor should gain the permit and stick to GAM’s regulation and specification as regard the reinstatement of the road which includes a concrete slab across and along the paved road using a fast hardening concrete, in addition using the Finisher during asphalting with a minimum width of 2 m on two layers using Basalt Paving, using an compactor of min 2 ton weight with a driver, where the price shall not exceed 115% of the regular asphalted road as per the contract specs.
![Page 133: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/133.jpg)
8 | P a g e
2. HDPE PIPES
SUPPLY & INSTALLATION of HDPE PIPES, PE100, PE63, PN16,
The item for INSTALLATION of HDPE PIPES, PE100, PE63, PN16, ISO63 and above, in classic trench excavation includes the following:
- installation of a linear meter of HDPE pipeline according to the Technical Specifications,
- Include supply and install all electro-fusion fittings, connectors and bends,
- Marking of pipe trench location,
- Cutting of road surface (asphalt) and removal of asphalt,
- Careful removal and storage of side walk tiles or plastering stones,
- Excavation in any type of soil of trench to the depth of bottom of pipe plus sand bedding according to diameter as specified in the Technical Specifications,
- Trench protection by timbering,
- Transport and disposal of excavated material,
- Supply of appropriate sand, sand bedding below, aside and above according to Technical Specifications and detailed drawings,
- Including all required thrust blocks and encasement whenever required in accordance with the technical specifications and drawings,
- Including all connection and disconnection points shown on the drawings.
- Supply and Installation of HDPE pipes, inclusive cutting and chamfering of ends,
- Backfilling of trench with imported material, compaction in layers of 20cm according to Specifications of the authority owning the road,
- Supply and Installation of a warning and tracing tape for pipes according to the technical specifications,
- Reinstatement of surfaces as specified in the detailed standard drawings and to the specifications of the authority owning the road,
- Cleaning and flushing the interior of the pipes after installation,
- Pressure testing of pipeline according EN 805, including the filling of the line with water for the entire pipeline section including bends and T-Pieces, Valves, AV, and also with all pipe saddles installed as part of the main pipe, as indicated in the technical specifications,
- Including provision of the testing equipment, water shall be supplied and paid by the contractor,
- Test according EN 805 with Test certificate and procedure,
- Flushing of the pipeline,
- Chlorine, disinfection of the pipeline,
- Final flushing and tests,
- Survey of the new pipeline and elaboration of as-built drawings,
- Including disconnection, reconnection / immigrate of all connections and costumers, whether allocated inside or outside the project area which are connected to the existing pipe network lines.
- Isolation: shall be proved by the successful wet dry test performed by the contractor and approved by the Engineer.
- In case the road was newly asphalted by GAM the Contractor should gain the permit and stick to GAM’s regulation and specification as regard the reinstatement of the road which includes a concrete slab across and along the paved road using a fast hardening concrete, in addition using the Finisher during asphalting with a
![Page 134: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/134.jpg)
9 | P a g e
minimum width of 2 m on two layers using Basalt Paving, using an compactor of min 2 ton weight with a driver, where the price shall not exceed 115% of the regular asphalted road as per the contract specs.
HDPE Pipe installation with HDD Trenchless Technology
The HDD trenchless technology shall be used if necessary and only after getting the approval of the Engineer and the Client and where the contractor will not get an excavation permit, only but not entirely, especially not necessarily for low traffic road, narrow roads in residential areas or interconnections with sewer lines and septic tanks. This technology shall be executed to avoid traffic hazards and problems with road excavation permits required from the Municipality. Without any additional Cost, On the BoQ Items.
3. SUPPLY & INSTALLATION OF HOUSE CONNECTION FOR A SINGLE AND MULTIPLE CUSTOMERS WATER METERS
See Technical Specifications and drawings.
The item for SUPPLY & INSTALLATION of HOUSE CONNECTION for a single and multiple customer water meters includes the following:
- SUPPLY & Installation of SINGLE House Connection HDPE Pipes PE100, PN16, , according to the Technical Specifications and drawings,
- SUPPLY & installation of house connection includes an average of length 8 m of HDPE pipeline,
- SUPPLY & installation of pipe saddle for DI pipes or electro-fusion pipe saddles for HDPE pipes at tapping points, according to the technical specifications and drawings,
- installation of a linear meter of HDPE pipeline
- Includes all electro-fusion connector and bends,
- Marking of pipe trench location,
- Cutting of road surface (asphalt) and removal of asphalt,
- Careful removal and storage of side walk tiles or plastering stones,
- Excavation in any kind of soil of trench to the depth of bottom of pipe plus sand bedding according to diameter as specified in the Particular Technical Specifications,
- Trench protection by timbering,
- Transport and disposal of excavated material,
- Supply of appropriate sand, sand bedding below, aside and above according to Technical Specifications and detailed drawings,
- Supply and Installation of HDPE pipes, inclusive cutting and chamfering of ends,
- Inclusive Backfilling of trench with imported material, compaction in layers of 20cm according to Specifications of the Municipality of Greater Amman,
![Page 135: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/135.jpg)
10 | P a g e
- Supply and Installation of a warning and tracing tape for pipes according to the technical specifications,
- Reinstatement of surface on the payment with tiles or plastering stones,
- Reinstatement of road surfaces as specified in the detailed standard drawings and according to the specifications of the authority owning the road,
- Cleaning and flushing the interior of the pipes after installation,
- Pressure testing of pipeline according EN 805, including the filling of the line with water for the entire pipeline section including bends and T-Pieces, Valves, AV, and also with all pipe saddles installed as part of the main pipe, as indicated in the technical specifications,
- Including provision of the testing equipment, water shall be supplied and paid by the contractor,
- Test according EN 805 with Test certificate and procedure,
- Flushing of the pipeline,
- Chlorine, disinfection of the pipeline,
- Final flushing and tests,
- Survey of the new pipeline and elaboration of as-built drawings,
- Including supply and installation of material according to the General- and Particular Technical Specifications,
- Including the galvanized milled steel pipes (GMS) of approx. 10m, including all fittings,
- Including all necessary bends for connections through walls and floors inside of Customers Property,
- Works includes break off of bricks and walls,
- Including all necessary wall clamps, or any material needed to work be done as per engineer's Instructions
- Including excavation in any type of soil and backfilling works, if necessary,
- Including reinstatement works for inside house connections as shown on drawings and technical requirements,
- Task includes all works and material for the connection after the water meters until the place of the existing connection.
- Including disconnection, reconnection / immigrate of all connections and costumers, whether allocated inside or outside the project area which are connected to the existing pipe network lines.
- Transfer meters with cabinets (Disconnection/connection) from their current location to the main gate of the structure or building as per Miyahuna specification for meters location.
4. SUPPLY AND INSTALLATION OF
See Technical Specifications and drawings. Supply and INSTALLATION of Isolation Valves
4.1. The item for Supply and installation of isolation Valves includes as follows:
- Including supply and installation of all material and all accessories to get the work done according to the Technical Specifications,
- Cutting of road surface (asphalt) and removal of asphalt,
- Careful removal and storage of side walk tiles or plastering stones,
![Page 136: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/136.jpg)
11 | P a g e
- Inclusive Excavation in any type of soil of trench to the depth of bottom of connecting pipe plus sand bedding according to the Technical Specifications,
- Including supply and install of all concrete and civil works required in the technical specifications and drawings,
- Inclusive all mounting parts and manhole cover according to the Technical Specifications,
- Securing and protection of the trench/pit,
- disposal of excavated material,
- Inclusive supply and installation of extension spindles whenever required based on the technical specifications and drawings,
- Inclusive Backfilling of trench with imported material, compaction in layers of 20cm according to Specifications of the authority owning the road,
- Reinstatement of surfaces as specified in the detailed standard drawings and according to the specifications of the authority owning the road,
- Inclusive installation of surface boxes, after backfilling and reinstatement of surface whenever required in accordance with the technical specifications and drawings,
- Installation either into existing or new installation in new system.
4.2. SUPPLY & INSTALLATION of Combination Air Valves
The item for supply and installation of Combination Air Valves includes the following:
- Including supply and installation of material according to the Technical Specifications and drawings,
- Cutting of road surface (asphalt) and removal of asphalt,
- Careful removal and storage of side walk tiles or plastering stones,
- Inclusive Excavation in any type of soil of the trench to the depth of bottom of connecting pipe plus sand bedding according to the Technical Specifications and drawings,
- Securing and protection of the trench/pit,
- disposal of excavated material,
- Supply and installation of combination Air Valve and all required material in accordance with the technical specifications and drawings,
- Inclusive all construction, civil and concrete material and works for the Air Valve Chamber, according to the Technical Specifications and drawings,
- Inclusive all mounting parts and manhole cover according to the Technical Specifications and drawings,
- Inclusive Backfilling of trench with imported material, compaction in layers of 20cm according to Specifications of the authority owning the road,
- Reinstatement of surfaces as specified in the detailed standard drawings and according to the specifications of the authority owning the road,
- Installation either into existing or new installation in new system.
- The Contractor is responsible to allocate ARV's specific locations regarding to operation needs, or relocate any ARV location on design drawings where needed under Engineer Approval.
![Page 137: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/137.jpg)
12 | P a g e
4.3. SUPPLY &INSTALLATION of Wash-Outs
The item for supply and installation of a Wash-Out includes the following:
- Including supply and installation of material including pipes, valves, fittings, accessories … etc., according to the Technical Specifications and drawings,
- Cutting of road surface (asphalt) and removal of asphalt,
- Careful removal and storage of side walk tiles or plastering stones,
- Inclusive Excavation in any type of soil of the trench to the depth of bottom of connecting pipe plus sand bedding according to the Technical Specifications,
- Securing and protection of the trench/pit,
- disposal of excavated material,
- Wash-out pipe HDPE ISO125, shall be extended to such a length to reach the discharge area as is required for every particular site conditions,
- Inclusive all construction, civil and concrete material and works for the Wash-out chamber, according to the Technical Specifications and drawings,
- Inclusive all mounting parts for fixing the pipe,
- Inclusive Backfilling of trench with imported material, compaction in layers of 20cm according to Specifications of the Municipality of Greater Amman,
- Inclusive reinstatement of surfaces as specified in the detailed standard drawings and according to the Specifications of the authority owning the road,
- Installation either into existing or new installation in new system.
- Inclusive flood manholes in case there isn’t any location to drain the pipe.
- The Contractor is responsible to allocate Wash-Out specific locations regarding to operation needs, or relocate any W.O location on design drawings where needed under Engineer Approval.
4.4 INSTALLATION IN CHAMBERS
4.4.1 Construction an new manhole for DM only (Civil work only) new or Ex. pipes
The item includes the following:
- Including supply and installation of all required material to complete the task according to the Technical Specifications, site requirements and drawings,
- Supply and Install the chamber’s steps according to the typical drawings.
- Cutting of road surface (asphalt) and removal of asphalt,
- Careful removal and storage of side walk tiles or plastering stones,
- Inclusive Excavation in any type of soil of trench to the depth of bottom of connecting pipe plus sand bedding according to the Technical Specifications,
![Page 138: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/138.jpg)
13 | P a g e
- Including supply and install of all concrete and civil works required such as chambers, encasements, installation of fittings … etc. as in the technical specifications and drawings,
- Inclusive all mounting parts and manhole cover according to the Technical Specifications,
- Securing and protection of the trench/pit,
- disposal of excavated material,
- Inclusive Backfilling of trench with imported material, compaction in layers of 20cm according to Specifications of the authority owning the road,
- Reinstatement of surfaces as specified in the detailed standard drawings and according to the specifications of the authority owning the road.
- The Contractor is responsible for structural design (Rebar, dimensions, etc...) under manufacturer recommendation and engineer approval.
4.4.2 Construction an new manhole for prv and DM (Civil work only) new or Ex. pipes
The item includes the following:
- Including supply and installation of all required material to complete the task according to the Technical Specifications, site requirements and drawings,
- Supply and Install the chamber’s steps according to the typical drawings.
- Cutting of road surface (asphalt) and removal of asphalt,
- Careful removal and storage of side walk tiles or plastering stones,
- Inclusive Excavation in any type of soil of trench to the depth of bottom of connecting pipe plus sand bedding according to the Technical Specifications,
- Including supply and install of all concrete and civil works required such as chambers, encasements, installation of fittings … etc. as in the technical specifications and drawings,
- Inclusive all mounting parts and manhole cover according to the Technical Specifications,
- Securing and protection of the trench/pit,
- disposal of excavated material,
- Inclusive Backfilling of trench with imported material, compaction in layers of 20cm according to Specifications of the authority owning the road,
- Reinstatement of surfaces as specified in the detailed standard drawings and according to the specifications of the authority owning the road.
The Contractor is responsible for structural design (Rebar, dimensions, etc...) under manufacturer recommendation and engineer approval.
4.4.3 Supply and Installation ELECTROMAGNETIC FLOW Meter Only
![Page 139: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/139.jpg)
14 | P a g e
The item for supply and installation of District Electromagnetic Flow Meter as follows:
- Including supply and installation of all required material to complete the task according to the Technical Specifications, site requirements and drawings,
- Inclusive supply and installation of all required material, valves, fittings, Reducers, strainers (if needed), and accessories as indicated in the detail drawings.
- District meters data sheets are attached to the BOQ.
- Installation either into existing or new installation in new system.
- The quantities given in the BOQ are approximated according to preliminary studies by Miyahuna and can be changed according to design submitted by the contractor and engineer's approval based on manufacturer recommendation..
- The Contractor is responsible to make the appropriate Design and Sizing for the Flow Meter to get the best operational efficiency.
- Any changes in BOQ Flow meter diameters will be paid as follows : 1- That was an increase from BOQ item no. (5.2) 2- That was a decrease; the contractor will be paid as a similar item
in the BOQ.
5. MISCELLANEOUS
5.1 Provisional Sum for unforeseen works as deemed appropriate by the Engineer and the Employer
As indicated in the Technical Specifications and BOQ.
5.2Provisional Sum for safety measures and EMMP
As indicated in the Technical Specifications–Annex 5 Environmental Mitigation and Monitoring plan for Associate FARA (ZARQA) and BOQ .
6 PRELIMINARIES
6.1 Mobilisation & Site Installation
Site installation is in accordance with the special Conditions, the technical specifications including all facilities required for the construction and installation works on site of the project. The item for Mobilisation & Site installation includes the following:
- Supply, transport and installation of machinery, equipment and plant, - Storage of material and equipment, - Safe guarding of the site installations, - Elaboration of the site installation plan(s),
![Page 140: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/140.jpg)
15 | P a g e
- Earthwork (cleaning, profiling, levelling, excavations etc.) necessary for the site installation,
The site installation includes provision of a site laboratory according to the
Technical Specifications and conditions for the Engineer and Employer and as indicated in the BoQ, Bill 6 – Preliminaries.
- The invoice of the lump sum for site installation and payment will be done in the 1st interim certificate. (Zarqa office as per Engineer instructions)
6.2 Office accommodations
The item for the office accommodations for the engineer and the owner includes
the following:
- Engineer's office in a central location with all facilities and furniture provided for the duration of the Contract according to the Particular Technical Specifications and conditions.
- Including any delays or extension as indicated in the Particular Technical Specifications.
- The cost includes provisions for communication as indicated in the Particular Technical Specifications and conditions.
- The item for the office accommodations Client’s- and the Engineer representative as well as the as indicated in the BoQ, Bill 6– Preliminaries.
7 ISOLATION WORKS AND TETING :
One of the main steps of implementing NRW reduction practices in Zarqa
Governorate is to isolate BA-8 DMAs. The process of isolation will start after installing a
dedicated main feeder for each DMA to ensure the adequate water supply. Each DMA
will be metered with an electromagnetic bulk water flow meter installed at the entrance
of that DMA measuring the amount of water that is supplied to that specific district. The
isolation process for DMAs will reduce NRW significantly since Isolation activities may
reveal leaks and/or connections to redundant mains, which will be corrected during this
process.
Isolation process includes; conducting Wet/Dry test and/or conducting pressure tests it
may require installing boundary meters and/or valves and/or installing new pipes or end
caps.
All DMAs could be considered hydraulically isolated by comparing flow data and
pressure changes of boundary valve operations. In case of not having an isolated DMA,
it is required to repeat the pressure test by installing pressure loggers across boundary
valves to identify variances or to carry out wet/dry test again.
To examine isolation, Wet/Dry test will be carried out for both inside and outside the
boundary of a DMA. A survey will take place around the boundary of the DMA to check
![Page 141: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/141.jpg)
16 | P a g e
the status of water supply and produce isolation inspection report. In case of having an
isolated DMA other NRW reduction activities will take place accordingly. However, if
the isolation test failed more investigation will take place, including the employment of
underground pipe locating equipment to locate, identify and rectify any potential
unknown cross connected water lines. Then another wet/dry test will be repeated until it
shows comprehensive isolation.
During the implementation of water balance test for specific selected DMAs, a limited
customer survey will take place to upgrade CIS and GIS accordingly There are two
methods to quantify NRW, the first one is the Flow Balance (FB), and the second one is
Minimum Night flow (MNF). The flow balance (FB) calculation is the difference
between the total amounts of water supplied to a certain DMA with sum of the water
consumed within that DMA for a certain period of time. In case of have difference, this
difference could be leakage, metering inaccuracies or unknown water usage. Multiple FBs
calculation will be taken place for the selected DMAs at BA-8; one FB will be conducted
after isolation then the one will be after the implementation of each NRW reduction
activity such as disconnecting of the redundant mains, meter replacement, etc.
The second method is by conducting MNF which can provide information about the
level of physical losses. MNF will be carried out for selected DMAs at BA-8. In case of
having large number of customers MNF is considered easier than FB which would
require huge efforts to read all customers’ meters in a very short period of time.
تشغيل العمالة المحلية 8.1
)نظام الزامية تشغيل العمالة الاردنية من ابناء المحافظة في مشاريع 2016لسنة 131مرفقا بطيه نسخة عن نظام رقم
.1993( لسنة 7( من قانون البناء الوطني رقم )14الاعمار المنفذة فيها والصادر بمقتضى المادة )
للعمل بما جاء فيه والالتزام بتسعيره في جدول الكميات.
![Page 142: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/142.jpg)
17 | P a g e
BILL OF QUANTITIES
SUPPLY and INSTALLATION
ZARQA-BA08
Contract No. :
ITEMS / CONTENT BILLS
DUCTILE IRON PIPES BILL 1
HDPE PIPES BILL 2
HOUSE CONNECTIONS BILL 3
VALVES AND DISTRICT METERS BILL 4
MISCELLANEOUS SUPPLY and WORKS (Provisional sum) BILL 5
PRELIMINARIES BILL 6
Mandatory operating system BILL 7
TOTAL SUMMARY SUMMARY
![Page 143: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/143.jpg)
18 | P a g e
Item No.:
Description Unit Quantity in project
area
Construction costs
Unit Price Total Price
[JOD] [JOD]
1 SUPPLY AND INSTALLATION OF DUCTILE IRON PIPES C Class
The included tasks for this item as indicated in the Technical Specifications for Pipes, fittings, accessories, pipe Laying Method, drawings, and Preamble to BOQ.
Prices for construction in natural ground shall be calculated in accordance with item number 1.15 in the preamble
Material for Ductile Iron Pipes C class as indicated in the Technical Specifications.
1.1. DI Pipes laid in Asphalted Surfaces, concrete or tiles:
1.1.1 DN 150 m 1,540
Bill 1 SUPPLY AND INSTALLATION OF DUCTILE IRON Pipes
(Carried forward to Grand Summary items)
0
![Page 144: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/144.jpg)
19 | P a g e
Description Unit
Quantity in
project area
Construction costs
Unit Price
Total Price
[JOD] [JOD]
Supply and Installation of HDPE PE100 Pipes ISO63 and above , PN16, including all fittings and accessories.
The included tasks for this item as as indicated in the Technical Specifications for Pipes, fittings, accessories, pipe Laying Method, drawings and Preamble to BOQ.
Prices for construction in natural ground shall be calculated in accordance with item number 1.15 in the preamble
HDPE PE100 Pipes laid in Asphalted Surfaces, concrete or tiles:
ISO63 = DN50 = 2" HDPE pipe, PN16 m 900
ISO125 = DN100 = 4" HDPE pipe, PN16 m 14,350
ISO180 = DN150 = 6" HDPE pipe, PN16 m 8,140
HDPE Pipes Laid in natural surface:
SUPPLY AND INSTALLATION OF HDPE pipes (Carried forward to
Grand Summary items)
0
![Page 145: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/145.jpg)
20 | P a g e
Item No.:
Description Unit
Quantity in
project area
Construction costs
Unit Price Total Price
[JOD] [JOD]
3. SUPPLY AND INSTALLATION OF HOUSE CONNECTION
for single and multiple customers water meters
Supply and Installation of Material for House Connection HDPE Pipes PE100, PN16.
The included tasks for this item as indicated in the technical specifications, drawings and Preamble to the BoQ.
HDPE Pipes shall be PN16 only, PE100. All fittings shall be electrofusion.
3.1 Supply of Material and Installation for House Connection installed under any Surface (Asphalt, Side Walk and natural Ground):
ISO25 = DN20 = 3/4" HDPE pipe, PN16, inclusive all fittings and reconnection to existing or relocated meter station, Branched from ISO180 HDPE
NO 72
3.1.1 ISO25 = DN20 = 3/4" HDPE pipe, PN16, inclusive all fittings and reconnection to existing or relocated meter station, Branched from ISO125 HDPE
No 285
3.1.2 ISO25 = DN20 = 3/4" HDPE pipe, PN16, inclusive all fittings and reconnection to existing or relocated meter station, Branched from ISO63 HDPE
No 145
ISO32 = DN25 = 1" HDPE pipe, PN16, inclusive all fittings and reconnection to existing or relocated meter station, Branched from ISO180 HDPE
No 72
3.1.3 ISO32 = DN25 = 1" HDPE pipe, PN16, inclusive all fittings and reconnection to existing or relocated meter station, Branched from ISO125 HDPE
No 285
3.1.4 ISO32 = DN25 = 1" HDPE pipe, PN16, inclusive all fittings and reconnection to existing or relocated meter station, Branched from ISO63 HDPE
No 145
3.2 Supply of Material and Installation of required Gulvanized Iron works for House Connections:
3.2.1
Supply and install 1" GI pipes above ground (horizontal or vertical) with all required fittings and accessories according to the tender documents and approval of the Engineer
m 500
![Page 146: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/146.jpg)
21 | P a g e
3.2.2
Supply and install 3/4" GI pipes above ground (horizontal or vertical) with all required fittings and accessories according to the tender documents and approval of the Engineer
m 900
3.2.3
Supply and install 1/2" GI pipes above ground (horizontal or vertical) with all required fittings and accessories according to the tender documents and approval of the Engineer
m 200
BILL 3
SUPPLY and INSTALLATION OF HOUSE CONNECTIONS
(Carried forward to Grand Summary items)
![Page 147: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/147.jpg)
22 | P a g e
Item No.:
Description Unit
Quantity in
project area
Construction costs
Unit Price Total Price
[JOD] [JOD]
4 SUPPLY AND INSTALLATION of VALVES and METERS
The included tasks for this item as indicated in the Technical Specifications, drawings, and Preamble to BOQ including all required, chambers, material and fittings to complete the works stated in the tender documents.
4.1 Isolation valves
DN 50 PN 16 Gate Valve NO. 15
4.1.2. DN 100 PN 16 Gate Valve No. 40
4.1.3. DN 150 PN 16 Gate Valve No. 8
4.2. Air Release Valves
4.2.1. Single Air valve for DN 100 pipe No. 2
4.2.2. Single Air valve for DN 150 pipe No. 2
4.3. Washout
4.3.1. Washout construction in pipe DN150 No. 2
4.4. District Electromagnetic Water Flow Meter
Supply and Installation of Electromagnetic Water Flow Meters and chambers, as specified in the Technical Specifications, preamble to BOQ and Drawings including all required valves, fittings and items to complete the works. The meters shall be sized based on the DM datasheet attached to this BOQ.
The included tasks for this item as indicated in the Preamble to the BoQ.
4.4.1 New Chamber, New DM on EX. 250 PE for BA08-1 LS 1
4.4.2 New Chamber, New DM on New 150 DI for BA08-2 LS 1
Bill 4
SUPPLY and INSTALLATION OF VALVES AND METERS (Carried forward to Grand Summary items)
![Page 148: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/148.jpg)
23 | P a g e
Item No.:
Description Unit Quantity in project
area
Construction costs
Unit Price Total Price
[JOD] [JOD]
5 MISCELLANEOUS
Provisional Sum
5.1 Provisional Sum for unforeseen works as deemed appropriate by the Engineer and the Employer
PS PS
10,000.00 10,000.00
5.2
Cost for applying safety measures and EMMP; not less than 5% of the total value (excluding Bills no.5 and 6) of the assignment to implement the EMMP plan listed in Annex 4 (EMMP) and by weight of each item according to Table 4.1 in the EMMP. Each item shall be evaluated by a mark from 1-4 Where 1 indicates the non-application and 5 indicate the full application of the EMMP and price includes the application of the safety requirements for excavations. The Engineer is responsible for the evaluation of the contractor's application of this item and the reimbursement will be on that basis. Payment is made with each claim on the basis of proportion and proportionality of the above and according to the tables attached to the above annex.
% 5
BILL 5
MISCELLANEOUS (Carried forward to Grand Summary items)
![Page 149: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/149.jpg)
24 | P a g e
Item Description Unit Quantity
Unit Price Total Price
No. [JOD] [JOD]
6 PRELIMINARIES for WORKS
6.1 Mobilisation & Site Installation
The included tasks for this item as indicated in the Preamble to the BoQ, technical specification and conditions of contract
6.1.1 Site installation and mobilisation for the works in this contract (Zarqa)
LS 1
6.2. Office accommodations
The included tasks for this item as indicated in the Preamble to the BoQ, technical specification and conditions of contract
6.2.1. Operation and maintenance of the Engineer's Office (Zarqa)( Miyahuna need to confirm)
mth 12
Bill 6 PRELIMINARIES for WORKS (Carried forward to Grand
Summary items)
![Page 150: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/150.jpg)
25 | P a g e
البند
بيان الاعمال
الحد الادنى للبدل
الشهري للفرد دينار
(أ) * أردني
العدد
)ب(
المدة
بالأشهر
)ج(
البدل
الشهري
** )د(
المبلغ
الإجمالي )
ب*ج*د(
دينار دينار الرقم
نظام إلزامية التشغيل
7
بالعدد :
تعيين الكادر المبين أدناه حيث يجب على المقاول
بكوادره الرئيسية جهاز مساعد حسب أن يلحق
نظام الزامية -2016( لعام 131رقم ) النظام
الأردنية من أبناء المحافظةتشغيل العمالة
.لمشاريع الإعمار المنفذة فيها
7.1 مهندس حديث التخرج حسب التخصصات
12 4 400 المطلوبة.
12 6 250 فنيون 7.2
12 15 220 عمال 7.3
12 1 250 سكرتاريا 7.4
12 1 270 مالي 7.5
12 1 300 إداري 7.6
12 1 200 مراسل 7.7
* * سيتم التأكد من إلتزام المقاولين بدفع البدل
الشهري للعاملين بما لايقل عن الحد الادنى
المنصوص عليه في البند )أ( من هذا الجدول
** البند )د( هو الحد الادنى للبدل الشهري للفرد
وارباحه عن بالاضافة إلى قيمة مصاريف المكتب
الفرد
في حال عدم التعيين وتشغيل العمالة الاردنية
المطلوبة وكما ورد اعلاه يتم حسم ضعف قيمة
الحد الادنى المشار إليه في العمود )أ( من هذا
الجدول
في حال استدعت طبيعة الأعمال في المشروع
الموجودة في تعيين أعداد وخبرات إضافية غير
وثائق العطاء تكون جميع تكاليفها محملة على
الأسعار الإفرادية للعطاء طيلة مدة تنفيذ
المشروع.
Bill 7 المجموع ينقل إلى الخلاصة تشغيل العمالة المحليةBILL no. 7
![Page 151: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/151.jpg)
26 | P a g e
TOTAL SUMMARY - SUPPLY and INSTALLATION
ZARQA-BA08
Contract No.
TOTAL SUMS FOR BILLS
Bills [JOD]
DUCTILE IRON PIPES
HDPE PIPES
HOUSE CONNECTIONS
VALVES AND METERS
MISCELLANEOUS
PRELIMINARIES
1 GRAND TOTAL
2 PROVISIONAL SUMS
3 SUB-TOTAL (GRAND TOTAL LESS PROVISIONAL SUMS (1-2))
4 PERCENT ADDITION/REDUCTION FOR (3)
5 VALUE FOR ADDITION OR REDUCTION = (3X4)
تشغيل العمالة المحلية 6
7 TOTAL = (3+5+6)
TOTAL AMOUNT INCLUDING PROVISIONAL SUMS JOD (WRITING AND NUMBERING)
(carried forward to Bid Form)
Signed this day ______________ of _______________ 2021
Stamp and Signature
By : ____________________________________________________________
Position : _______________________________________________________
Duly authorized to sign the Tender for and on behalf of the Bidder
![Page 152: TENDER DOCUMENTS VOLUME III Technical Specifications ... · products for use in contact with drinking water) and the requirements of EN 15664 (influence of metallic materials on water](https://reader036.fdocuments.in/reader036/viewer/2022071417/6114e3a38f6f8c0c2e29f345/html5/thumbnails/152.jpg)
27 | P a g e