TENDER DOCUMENT

FOR

COOLING WATER TREATMENT

PACKAGE

COMMERCIAL – SECTION

NATIONAL FERTILIZERS LIMITED

BATHINDA UNIT

JULY 2011

Page 2: TENDER DOCUMENT FOR COOLING WATER ... COMMERCIAL – SECTION NATIONAL FERTILIZERS LIMITED BATHINDA UNIT JULY 2011 2 TENDER DOCUMENTS FOR COOLING WATER TREATMENT PACKAGE ...

2

TENDER DOCUMENTS FOR COOLING WATER TREATMENT PACKAGE

(COMMERCIAL SECTION)

The Tender Particulars :-

1 I) Tender No. : NFB/PUR/SD/094007 dated 7.7.2011

ii) Requirement a) To formulate and specify Non-Chromate Stabilised

ortho-phosphate zinc (in single formulation )Cooling

Water Treatment programme for Cooling Towers

specified in Technical Section * Provide Services for

CW Treatment.

b) To supply chemicals so as to meet the Performance

Guarantees, as specified under Article 4.3 of Technical

Section.

c) To provide chemical dosing pumps and monitoring

equipments, free of charge on returnable basis.

iii) Quantity of offered

chemicals : to be specified by Vendor.

iv) Type of Tender : Two stage bidding as per details given in Clause No.15.

v) Earnest Money Deposit : Rs.1.00 Lacs (Rs.One Lac.only) as per clause No.13.

vi) Security Deposit cum

Performance Guarantee 20% of order value as per Clause No. 14

vii) Tender closing Date &

Time 2.30 P.M. on 28.7.2011

viii) Tender Opening Date &

Time 3.00 P.M. on 28.7.2011

ix) Tender validity Must be initially valid for 90 days from date of opening

of tender.

x) Delivery Please quote your earliest possible delivery schedule.

xi) Mode of dispatch By Road

xii) Tender shall be addressed to : Chief Manager (Materials) NFL , BATHINDA.

No telegraphic tenders shall be entertained.

xiii) In Technical Section (Section A, B, C), the scope of supply and responsibilities of the

supplier have been defined alongwith following:-

4.0 INSTRUCTIONS TO BIDDERS

4.1 Technical quote 4.2 Bid evaluation 4.3 Guaranteed overall Annual cost

4.4 Vendor’s Scope 4.5 Owner’s Scope

4.6 Trial Order 4.7 Contents of offer

xiv) Period of Contract

Contract shall be initially valid for a period of One year duration from the date of

issuance of LOI which on successful execution may be extended for a period of up to

another One year at the sole discretion of NFL. Vendors shall however quote for a period

of two years during which the quoted rate shall remain firm and valid.

Page 3: TENDER DOCUMENT FOR COOLING WATER ... COMMERCIAL – SECTION NATIONAL FERTILIZERS LIMITED BATHINDA UNIT JULY 2011 2 TENDER DOCUMENTS FOR COOLING WATER TREATMENT PACKAGE ...

3

xv) Staggered supply of Chemicals

At the commencement of the contract, supply shall be made for three months requirement

along with one lot of pre-cleaning, Passivation and contingency chemicals for each tower

and payment shall be released within 30 days of receipt and acceptance of the chemicals

excepting during trial run for which payment will be released as per clause No. 4.6. Section

C of Technical Section.

Thereafter, payment shall be restricted to 1/12th of the Guaranteed overall annual cost on

consumption basis.

The running inventory of one month requirement shall be included in the aforesaid

inventory on three months. Deliveries shall be made in such a way that inventory at NFL

stores does not fall below 2 months requirement at any point of time.

xvi) Firm Prices

Prices offered shall remain firm during the currency of the contract except variation of

statutory levies. Vendor should confirm the same specifically in the offer.

xvii) Payment Terms

No advance payments are allowed. Payments are made within 30 days of receipt and

acceptance of material at site, as per following details. However, during trial period of 6

months (only for parties who have been pre-qualified on trial basis) , payment will be

released in two installments of 3 months each, provided vendor has performed

satisfactory as per clause 4.6 of Section 'C'.

After the successful trial run, payment will be released on monthly basis , however payment shall be restricted to 1/12

th of the Guaranteed overall annual cost.

Further, the pre-cleaning , Passivation and contingency chemicals left over at the end of the

contract shall be taken back by the vendor and NFL shall recover the corresponding

amount from the vendor.

You have the option to receive payment through Electronics Fund Transfer (EFT) / RTGS

Process. For this option, you may submit your bank particulars; i.e. Name of the Party /

Beneficiary, Party’s Banker Name and Address, Branch Name, City, Branch Code (IFSC

Code of Bank, Bank Account No. (All digits in case of CBS Branches), E-mail of

Beneficiary to enable us to release payment accordingly. All bank charges will be to your

account.

xviii) Transportation

The responsibility of transportation of cooling water chemicals along with accessories

from vendor's works to NFL site shall be entirely of the vendor.

Supplier has to ensure that all statutory requirements are fulfilled which are needed

for the transportation of cooling water chemicals as per rules.

xix) Cost of Chemicals Consumed

Monthly consumption of the chemicals shall be indicated by the bidder based on the

design water analysis and parameters to be maintained as defined in TECHNICAL

SECTION.

The annual cost of chemicals consumption on the above basis shall be guaranteed by the

bidder. Any excess cost due to excess consumption of chemicals over the guaranteed one

shall be borne by the supplier. In case, the actual consumption is below guaranteed one,

payment will be restricted to actual consumption of chemicals.

Page 4: TENDER DOCUMENT FOR COOLING WATER ... COMMERCIAL – SECTION NATIONAL FERTILIZERS LIMITED BATHINDA UNIT JULY 2011 2 TENDER DOCUMENTS FOR COOLING WATER TREATMENT PACKAGE ...

4

xx) Maintenance of their own equipment supplied to NFL on loan basis required for cooling

water treatment shall be done by the vendor and at the end of the contract, same shall be

taken back by the vendor. The above will be at the risk and cost of the vendor.

2. Evaluation of bids shall be done with suitable loading, in case of any deviation to NFL terms &

conditions.

3. Any deviation in Technical and Commercial terms of NIT should be highlighted separately in

Part-I of offer, in envelope marked as "Technical and Commercial un-priced Offer."

4. Tender must reach on or before the tender closing time & date. Bids received after the closing

date and time will not be considered.

5. Request for extension of time for submission of tender shall not be entertained in any case.

6. NFL shall not accept delays in postal transit as ground for extension of tender submission

time or acceptance of tenders.

7. Tenders shall be submitted in duplicate in sealed covers.

8. Cover should bear following information:

a) Tender Number

b) Tender closing date & time

c) Tender opening date & time

d) Name and address of tenderer.

9. If the tenders’ covers are found / received opened not to comply with para 7 & 8 above,

the risk & responsibilities for losing tender confidentially shall rest with tenderer. NFL shall have

no obligation as a consequences thereof.

10. Any clarifications on procedure, tender specifications both technical & commercial can be

had from Chief Manager(Materials) any time before tender closing date and time either

personally or by post. Postal delays shall not cause postponement of tender processing dates

& tenderers in their own interest shall take all steps that are necessary for them to participate in

tender well in time.

11. All information sought by NFL during tender evaluation shall be provided within the time set

out in the communication on the subject. Failure of tenderer to comply with requirements of

NFL within stipulated time shall entitle NFL to proceed with the tenders on the basis of

information available. No responsibility for postal delays shall rest on NFL.

12. NFL shall reserve the right to postpone tender opening, withdraw the NIT or reject any or all

tenders or accept in whole or part any tender under intimation to the bidders without assigning any

reason thereof. No querry in this regard shall be entertained from tenderers.

13. Earnest Money Deposit (EMD)

a) Tender must be accompanied by requisite amount of Earnest Money as indicated at 1(v).

EMD shall be made in the form of Demand Draft in favour of National Fertilizers Ltd.,

payable at Bathinda unit. Cheque would not be accepted in any case.

b) Earnest money deposit shall be forfeited at the sole discretion of NFL in case the

tenderer, after intimation from NFL of the acceptance of his tender, either wholly or

in part fails to enter into a contract with NFL and/ or changes any of price and terms &

conditions of the tender within the validity period of the tender.

c) EMD shall be refunded to the unsuccessful tenderers after placement of order on

successful bidder.

d) No interest will be paid on the earnest money deposit of either the successful tenderer (s) or

unsuccessful tenderer (s).

e) EMD of successful tenderers shall be refunded on submission of SD-cum-PBG or can be

adjusted against SD-cum-PBG.

14. Security Deposit-cum- Performance Guarantee

Page 5: TENDER DOCUMENT FOR COOLING WATER ... COMMERCIAL – SECTION NATIONAL FERTILIZERS LIMITED BATHINDA UNIT JULY 2011 2 TENDER DOCUMENTS FOR COOLING WATER TREATMENT PACKAGE ...

5

a) Security deposit -cum-Performance guarantee equivalent to 20% of the order value shall

be deposited/ submitted by successful tenderer as stated in para (1) vi for faithful

performance of the contract Terms & Conditions within 15 days from the date of issue of

Order. The order value shall be guaranteed overall annual cost as detailed in Section-C

clause 4.4(a).

b) The Security Deposit cum Performance Guarantee can be furnished by either of following

modes.

i) Crossed demand draft payable at STATE BANK OF INDIA, SIBIAN, BATHINDA.

ii) Bank Guarantees in prescribed form from Nationalized Banks valid till one month after

completion of the contract period with further claim period of 6 months.

iii) Pledging of FDRs / govt. securities or call deposits.

c) The Security-cum-Performance Guarantee shall be retained by NFL till successful

completion of the contract.

d) In the event of termination of contract as per clause 3.8 of Section-B and 4.6 of Section-C,

NFL shall have the right to forfeit Security-cum-Performance Guarantee without

assigning any reason thereof.

e) The Security Deposit -cum- Performance Guarantee shall not bear any interest.

15. Tender shall be submitted in following manners Ist Envelope shall contain the following

a) Entire information sought under clause 4.7 Section C pertaining to "Contents of Offer".

b) Scope & technical specifications of services and materials offered & detailed literature

and drawing etc.

c) One set of tender document duly signed on each page as token of acceptance of NFL's

terms and conditions.

d) Letter stating acceptance of terms and conditions of tender documents. Statement of

deviations from the stipulated terms & conditions, if any, shall be furnished separately.

e) Earnest Money deposit of Rs.1.00 lakh (Rupees One Lakh only ) by way of bank draft &

Undertaking as per Annexure V.

f) Tender validity.

g) This Envelope shall be marked "Technical & Commercial unpriced offer along with

earnest money."

h) Power of Attorney as per clause No. 36 shall accompany the bid.

IInd Envelope

Item wise price of chemicals in Annexure-A and B.

This envelope shall be marked as "Price Offer"

Both the above envelopes shall be sealed & placed in another envelop & marked as per clause

No.8 above.

16. Destination for Despatch of Chemicals

Road Door delivery at BATHINDA unit

17. Consignee Manager Materials (Stores), NFL, BATHINDA

18. Our Banker STATE BANK OF INDIA, SIBIAN.

19. Transit Insurance will be arranged by Vendor.

20.

Packing and Forwarding Charges: These shall be included in the price which is on FOR

destination basis.

21. Price

The tenderer shall state item wise and total prices as under

i) Ex-works price

ii) Packing & Forwarding charges, excise duty, CST, Entry Tax etc.

iii) FOR station of dispatch.

iv) Freight by (a) Road

v) FOR destination price.

Page 6: TENDER DOCUMENT FOR COOLING WATER ... COMMERCIAL – SECTION NATIONAL FERTILIZERS LIMITED BATHINDA UNIT JULY 2011 2 TENDER DOCUMENTS FOR COOLING WATER TREATMENT PACKAGE ...

6

Tenderers should quote the rates both in figure and words. In case of any discrepancy, rates quoted

in words shall be applicable.

The supply shall be made on FOR destination basis.

22. Delivery Deliveries shall be made in such a way that

inventory at NFL stores does not fall below 2 months

requirement at any point of time.

23. Taxes and Duties

Shall be payable extra on actuals. Documentary evidence wherever applicable shall be

furnished. The rates as prevailing on the date of submitting tender shall be specified.

24. NFL shall have right to vary quantities wherever considered necessary without any liability of

any kind whatsoever.

25. Clear understanding The tenderers shall acquaint themselves fully with all the terms and conditions, limitations, local

conditions, scope, requirements and official / statutory regulations and rules, confirming and

subject to which services are to be performed. Failure to understand / comply with those

requirements will not absolve the tenderers of their obligations and duties under the contract in the

event of their tenders being accepted. No claim whatsoever on the plea of ignorance shall be

entertained.

26. Acceptance / Rejection of Tender

NFL reserves the right to accept or reject, at its sole discretion, any bid / all bids, in whole or in

part and / or accept other than the lowest bid without assigning any reasons thereof.

27. Award of contract

The terms & conditions as embodied in the purchase order shall be final and shall supersede any

other terms & condition that might have been indicated in the tender submitted by the tenderers.

28. Subletting of contract

The successful tender shall not sublet or assign the contract or any part of it without obtaining the

written permission of NFL in advance. In the event of successful tenderer's subletting or

assigning the contract or any part thereof without such permission, NFL shall be entitled to

cancel the contract and to purchase the goods/ award the contract elsewhere and successful tenderer

shall be liable to the National Fertilizers Ltd., for any loss or damage which NFL may sustain in

consequence or arising out of such purchases. Even in case subletting is permitted by NFL, NFL

shall not recognize any contractual obligation with the person or party to whom subletting is

permitted and shall hold the successful tenderer responsible for satisfactory and due & proper

fulfillment of the contract.

29. Force-Majeure

Neither party shall be liable for any claim on account of any loss, damage or compensation

whatsoever arising out of any failure to carry out the terms of this contract where such failure is

caused due to war, rebellion, mutiny, civil commotion, fire, riot , earthquake, draught, floods crop

failure, strike or act of God or due to any restraint or regulation of the State or Central Government

or a local authority/authorities. The party so affected shall give a notice of such occurrence to

the other party in writing within 10 days from the date of occurrence of the force-majeure

condition furnishing therewith a documentary evidence supporting the invoking of force-majeure

On cessation of the force-majeure the party invoking force-majeure shall inform the other

party of the period for which force condition continued and shall also give documentary evidence

thereof to this effect. Should one or both the parties be prevented from fulfilling their contractual

obligations by a state of force majeure lasting continuously for a period of 3 months, both the

parties shall meet and decide about the future course of action for implementation of the contract.

Page 7: TENDER DOCUMENT FOR COOLING WATER ... COMMERCIAL – SECTION NATIONAL FERTILIZERS LIMITED BATHINDA UNIT JULY 2011 2 TENDER DOCUMENTS FOR COOLING WATER TREATMENT PACKAGE ...

7

30. Arbitration

“EXCEPT WHERE OTHERWISE PROVIDED IN THE

CONTRACT ALL MATTERS, QUESTIONS, DISPUTES OR

DIFFERENCES WHATSOEVER, WHICH SHALL AT ANY

TIME ARISE BETWEEN THE PARTIES HERETO,

TOUCHING THE CONSTRUCTION, MEANING, OPERATION

OR EFFECT OF THE CONTRACT, OR OUT OF THE

MATTERS RELATING TO THE CONTRACT OR BREACH

THEREOF, OR RESPECTIVE RIGHTS OR LIABILITIES

OF THE PARTIES, WHETHER DURING OR AFTER

COMPLETION OF WORKS OR WHETHER BEFORE OF AFTER

TERMINATION SHALL AFTER WRITTEN NOTICE BY

EITHER PARTY TO THE CONTRACT BE REFERRED TO

THE ARBITRATION OF DESIGNATED CHAIRMAN &

MANAGING DIRECTOR, NATIONAL FERTILIZERS

LIMITED OR HIS/HER NOMINEE.

THE ARBITRATION & CONCILIATION ACT, 1996 OR

ANY STATUTORY MODIFICATION OF RE-ENACTMENT

THEREOF AND THE RULES MADE THERE UNDER SHALL

GOVERN THE ARBITRATION PROCEEDINGS.

THE CONTRACTOR HEREBY AGREES THAT HE SHALL

HAVE NO OBJECTION IF THE ARBITRATOR SO

APPOINTED IS AN EMPLOYEE OF NFL AND HE HAD TO

DEAL WITH THE MATTER TO WHICH THE CONTRACT

RELATES AND THAT IN THE COURSE OF HIS DUTIES

AS SUCH HE HAS EXPRESSED HIS VIEWS ON ALL OR

ANY OF THE MATTER IN DISPUTE OR DIFFERENCE.

IF THE ARBITRATOR TO WHOM MATTER IS REFERED,

VACATES HIS/HER OFFICE BY ANY REASON

WHATSOEVER THEN THE NEXT ARBITRATOR SO

APPOINTED BY THE AUTHORITY REFERRED ABOVE MAY

START THE PROCEEDINGS FROM WHERE HIS

PRODECESSOR LEFT OR AT ANY SUCH STAGE HE MAY

DEEM FIT”

“ IT IS AGREED BY AND BETWEEN THE PARTIES THAT

IN CASE A REFERENCE IS MADE TO THE ARBITRATOR

OR THE ARBITRAL TRIBUNAL FOR THE PURPOSE OF

RESOLVING THE DISPUTES/ DIFFERENCES ARISING

OUT OF THE CONTRACT BY AND BETWEEN THE PARTIES

HERETO, THE ARBITRATOR OR ARBITRAL TRIBUNAL

SHALL NOT AWARD INTEREST ON THE AWARDED AMOUNT

MORE THAN THE RATE SBI PLR/BASE RATE AS

APPLICABLE TO NFL ON THE DATE OF AWARD OF

CONTACT”.

31. JURISDICTION

All actions at law or suits arising out of or in connection with the contract or the subject matter

thereof shall be instituted in a court of competent jurisdiction at Bathinda.

32. PENALTY FOR LATE DELIVERY Time shall be deemed to be essence of the contract. In case of delay in supplies, unless extension of

delivery has been granted, in writing by NFL on application by the supplier. NFL may at their

option:-

i) recover from the supplier as liquidated damages a sum of equal to half percent per

week or part thereof the value of stores not delivered subject to a maximum of 5% of

value of the order OR

ii) purchase elsewhere on account of and at the risk and cost of the supplier the stores not

delivered OR

iii) cancel the order without prejudice to the rights of NFL under (i) and (ii) above.

Page 8: TENDER DOCUMENT FOR COOLING WATER ... COMMERCIAL – SECTION NATIONAL FERTILIZERS LIMITED BATHINDA UNIT JULY 2011 2 TENDER DOCUMENTS FOR COOLING WATER TREATMENT PACKAGE ...

8

33. SECRECY

Any information delivered or otherwise communicated by NFL to supplier in connection

with the contract shall be regarded as secret and confidential and shall not without the written

consent of NFL be published or disclosed to any third party or made use of by the supplier

except for the purpose of implementing the contract.

34. The tenderer shall indemnify NFL with all Statutory requirements and laws in performing the

contract. The responsibility for action / safety of his employees during the contract period

shall be solely his.

35. The tenderer shall indemnify NFL against any infringement of trademark or title to goods by him

and shall be solely responsible for the goods offered for sale.

Should a tenderer or contractor have a relations or in firm case of company or contractors, one or

more of its shareholders or relations of shareholders employed in the NFL. The tenderer must

disclose the names of such relation(s) while submitting his offer, failing which NFL may in its own

discretion reject the tender or rescind the contract.

36. Laws Governing Purchase Order

The purchase order shall be governed by the Laws of Union of India for the time being in force.

36 The bid shall be signed by the authorized / Principal offer(s) of the bidder. Power of Attorney

granted in favour of any other person for such purpose shall accompany the bid.

37 NFL reserves the right to demand from the tenderers any information / clarifications related to and

incidental to the tender.

38. Bidder will be responsible for any compensation/insurance as per Compensation Act-

1923 of the persons engaged for carrying out the job. Bidder will be solely responsible

for any liability of any person engaged for carrying out the job at NFL Site. Bidder will

ensure compliance of Indian Labour Laws and NFL shall be under no obligation to

accept/admit any claim on this behalf.

39. YOU CAN ACCESS THIS NIT ON OUR WEBSITE www.nationalfertilizers.com

40. YOUR VENDOR USER ID IS BT AND YOUR PASSWORD IS BT =======================================================================

Authorized Signatory

Page 9: TENDER DOCUMENT FOR COOLING WATER ... COMMERCIAL – SECTION NATIONAL FERTILIZERS LIMITED BATHINDA UNIT JULY 2011 2 TENDER DOCUMENTS FOR COOLING WATER TREATMENT PACKAGE ...

9

Annexure-III

UNDERTAKING BY THE BIDDER

Chief Manager (Mtls.)

National Fertilizers Limited,

Bathinda.

Sub: Your Tender No. NFB/PUR/SD/094007 dated 7.7.2011 for Cooling Water

Treatment Programme.

Dear Sir,

With reference to above we hereby confirm that-

1. Tender documents have been read, understood with all clarifications pertaining to various

provided therein.

2. Terms & Conditions laid out in the tender documents are fully acceptable to us and we have

signed each page of the tender document as a token of acceptance of the same.

3. No deviation to any of the terms & conditions of NIT has been quoted by us.

4. Our offer is valid for acceptance for a period of 90 days from the date of opening of the tender.

5. Earnest Money Deposit is enclosed with the following details (In case, the EMD has been

deposited through more than one DD the details may be furnished separately).

DDNo._____________________ Dated ____________ Amount__________ Drawn on

(Bank)____________________ Payable at __________________.

6. Rates quoted are on FOR, NFL Stores basis and the rates including transportation charges shall

remain firm till the complete execution of the order.

7. This is to certify that none of the NFL employee is related to owners/directors. (In case any

relative is working in NFL, furnish details separately).

8. This is to certify that none of NFL’s ex-employee is employed with us. (In case any ex-

employee of NFL is employed, furnish details separately).

9. None of blood relation of the owners/directors is participating in this tender in the name of other

firm.

10. We have not been de-listed/ blacklisted by any institutional Agency/Govt. department for

participation in the tender & no other Firm/Sister Concern/Associate belongs to the same group in

participating /submitting the tender for job.

Dated : Signature of Tenderer or

their Authorised Representative : _________________

Place: Name & Address of Tenderer : _________________

_________________

_________________

Phone No. :_________________

Fax No. :_________________

E.mail :_________________

Page 10: TENDER DOCUMENT FOR COOLING WATER ... COMMERCIAL – SECTION NATIONAL FERTILIZERS LIMITED BATHINDA UNIT JULY 2011 2 TENDER DOCUMENTS FOR COOLING WATER TREATMENT PACKAGE ...

10

Draft

TECHNICAL SECTION

OF

TENDER DOCUMENTS

FOR

COOLING WATER TREATMENT PACKAGE

AT

NATIONAL FERTILIZERS LIMITED

BATHINDA

July -2011

Page 11: TENDER DOCUMENT FOR COOLING WATER ... COMMERCIAL – SECTION NATIONAL FERTILIZERS LIMITED BATHINDA UNIT JULY 2011 2 TENDER DOCUMENTS FOR COOLING WATER TREATMENT PACKAGE ...

11

INDEX

(Technical Section)

Sr. No. Description Page

SECTION – A

1.0 INTRODUCTION

2.0 DETAILS OF EXISTING COOLING WATER SYSTEM

2.1 Cooling Towers

2.2 Filtration System

2.3 Blow down

2.4 Chlorination and Acid dozing system

2.5 CW Heat Exchangers and Operating Temperature

2.6 Make up water characteristics

2.7 Present cooling water treatment programme

SECTION - B

3.0 TECHNICAL REQUIREMENTS OF PROPOSED COOLING

WATER TREATMENT PROGRAMME

3.1 General requirements of cooling water treatment package

3.2 Cooling Water Treatment Scheme

3.3 Contingency treatment

3.4 Alternative chemicals for water treatment

3.5 Mobilization and stabilization

3.6 Monitoring

3.7 Essentials / Performance Guarantees

3.8 Penalties and termination

SECTION - C

4.0 INSTRUCTIONS TO BIDDERS 4.1 Technical quote

4.2 Bid evaluation

4.3 Guaranteed overall annual cost

4.4 Vendor’s Scope

4.5 Owner’s Scope

4.6 Trial order

4.7 Contents of offer

4.8 Splitting of the Contract

4.9 Availability of chemicals without interruption

ANNEXURES

I Make up water analysis for last one year

II a, b, c Heat Exchangers - data

TECHNICAL SECTION

SECTION – A

Page 12: TENDER DOCUMENT FOR COOLING WATER ... COMMERCIAL – SECTION NATIONAL FERTILIZERS LIMITED BATHINDA UNIT JULY 2011 2 TENDER DOCUMENTS FOR COOLING WATER TREATMENT PACKAGE ...

12

TECHNICAL SPECIFICATIONS OF EXISTING COOLING WATER SYSTEM AND

TREATMENT PROGRAMME

TENDER DOCUMENT FOR COOLING WATER TREATMENT PROGRAMME

1.0 Introduction

NFL BATHINDA Fertilizer complex consists of Fuel Oil based Ammonia Plant (900 MTPD) &

Urea plant (1550 MTPD), Captive Power Plant integrated with Steam Generation Plant,

Ammonia Storage facilities, Water Treatment Plants, Cooling Water system, Effluent Treatment

plant, Bagging Plant etc.

Plants have been commissioned in November/ December '78 and are operating with capacity

utilization exceeding 100 %.

The revamping of Ammonia Plant i.e. change over from fuel oil based to gas based is expected

to be completed by December-2012, Cooling water Circulation rate for Ammonia

Cooling Tower (CT-1) after revamping will be 15000 M3/Hr (Approx).

2.0 DETAILS OF THE COOLING WATER SYSTEM

2.1 Cooling Towers: -

Ammonia Urea CPP

MAKE

TYPE

FRAMEWORK

FILLING

BASIN

Paharpur Cooling Towers

Model 664-3-08 bolts SS/CS

Himalaya Pine / fir

Treated Pine / fir

Concrete

NO. OF CELLS 10 4 3

TEMP. IN / OUT ºC. (Max) 46/36 44/36 42/35 COOLING WATER CIRCULATION (NORMAL) M³/Hr 18000 8000 to 10000 8000 DRIFT LOSS M³/Hr 18 10 8 EVAPORATION LOSS M³/Hr 324 129.60 100.8 BLOW DOWN RATE APPROX. M³/Hr 45.0 30.0 15.0 SYSTEM VOLUME (APPROXIMATE) M

3 6000 3000 1800

2.2 Filtration: -

Ammonia Urea CPP

NO. OF FILTERS 3 2 3

TYPE OF FILTER PRESSURE SAND

FILTERS

(HORIZONTAL)

PRESSURE SAND

FILTERS

(HORIZONTAL)

PRESSURE SAND

FILTERS

(VERTICAL)

EXTENT OF FILTRATION (M³/Hr.) 400 200 240

2.3 Blow down:

Blow down for Ammonia, Urea and CPP Cooling Towers combined is within 100 M3/Hr, including

intermittent blow down from cooling tower cells and sand filters.

2.4 Chlorination And Acid dozing System:

Following dosing systems are available for all the cooling water systems:

Page 13: TENDER DOCUMENT FOR COOLING WATER ... COMMERCIAL – SECTION NATIONAL FERTILIZERS LIMITED BATHINDA UNIT JULY 2011 2 TENDER DOCUMENTS FOR COOLING WATER TREATMENT PACKAGE ...

13

(a) Sulphuric acid dosing is done for maintaining pH of the circulation water system of

CT-1, CT-2 & CPP cooling towers.

(b) Chlorine is being dozed through vacuum type chlorinator for maintaining free chlorine level in

return water.

(c) Chemicals are at present being dozed through electronic metering pumps supplied by the party.

2.5 Cooling Water Heat Exchangers and Operating Temperatures: -

2.5.1 Ammonia Plant

Shell and tube heat exchangers with cooling water, mainly, on tube side are in operation. The

material of construction is generally stainless steel type 304. The Synth. Gas Compressor inter

coolers (3 nos.), Synth. Gas water cooler AEA-603, Oxygen Gas Compressor inter-coolers and

after-coolers (6 nos.) are having cooling water on shell side. It may be noted that maximum

temperature on process side is about 175 Deg.C and Cooling water outlet is 45 Deg.C

2.5.2 Urea Plant:

The material of construction is generally stainless steel in heat exchangers. In CO2 compressor

intercoolers, the cooling water is on shell side for 1st stage intercooler & in others, it is on the tube

side. It may be noted that the maximum temperature on process side of the coolers is as high as

200o C.

The operating data of various important heat exchangers in Ammonia, Urea Plants and CPP on the

process and waterside is listed in Annexure-II a,b & c respectively.

2.6 Make-up Water Characteristics:

2.6.1 The make up water to all the three Cooling Towers is filtered water coming from Raw Water

filtration Plant after clari-flocculation and filtration through gravity sand filters.

Design basis: -The make up filtered water analysis is generally in following range

Parameters Unit Range

Total Hardness as CaCO3 ppm 82~ 115

Calcium Hardness as CaCO3 ppm ppm 60 ~ 85

Magnesium Hardness as CaCO3ppm ppm 22 ~ 35

Silica as SiO2 (ppm) ppm 1.8 ~ 4.5

Chloride as CaCO3 (ppm) ppm 3.5 ~5.5

M-alkalinity as CaCO3 (ppm) ppm 50 ~75

Sulphates as CaCO3 (ppm) ppm 35 ~55

TDS ppm 150 ~225

PH 7.2 – 8.0

Iron ppm 0.07~ 0.10

2.6.2 Treated water is not being used as make-up water.

2.7 Present Cooling Water Treatment Programme (Circulating Water Parameters):

Parameters Unit Ammonia Urea CPP

Total hardness As Ca CO3 ppm 620 ~ 880 450 ~ 650 620 ~ 880

Calcium Hardness As Ca CO3 ppm 450– 600 325 ~ 450 400 ~ 600

Magnesium Hardness As Ca CO3 ppm 170– 280 125 - 200 170 ~ 280

Chloride ppm 100 – 250 100-250 100-250

PH 6.8 – 7.8 6.8 – 7.8 6.8 – 7.8

Page 14: TENDER DOCUMENT FOR COOLING WATER ... COMMERCIAL – SECTION NATIONAL FERTILIZERS LIMITED BATHINDA UNIT JULY 2011 2 TENDER DOCUMENTS FOR COOLING WATER TREATMENT PACKAGE ...

14

Turbidity NTU Less than 20 Less than 20 Less than 20

Total Inorganic Phosphate ppm 9~11 9~11 9~11

Zinc ppm Min. 1.0 Min. 1.0 Min. 1.0 Iron as Fe ppm <1.0 <1.0 <1.0 Total Ammonia ppm 25 – 60 100 – 250 0 - 20

2.7.1 The following chemicals are being used in the present Cooling Water Treatment

Programme, in all the three cooling towers

Name/Trade No. Function

Maxtreat 7702,7710H Corrosion inhibitor

Maxtreat –2021,7080 Dispersant

Maxtreat-7002 Anti-foulant / Bio-dispersant

Maxtreat -40 Non-oxidizing biocide

Maxtreat -652 Non-oxidizing biocide

Maxtreat –608C Non-oxidizing biocide

Maxtreat -7961 Chlorine dioxide precursor.

Maxtreat –7960S Chlorine based Bromine activator.

Maxtreat-801 Acid inhibitor

Maxtreat -DOSS Oil Contingency Chemical

SECTION – B

3.0 Technical Requirements for Proposed Cooling Water Treatment Programme

3.1 General Requirements for Cooling Water Treatment package

a) NFL requires vendors to provide Non-Chromate, ortho-phosphate- Zinc, based cooling

water treatment package for the cooling towers of Fuel oil at Bathinda plant. The cooling

water treatment shall comprise of Zinc as the cathodic inhibitor and stabilized ortho-

phosphate as the anodic inhibitor combined as a single formulation. Individual chemicals

as cathodic and anodic inhibitors in basic chemical form are not acceptable. The products

offered should be field tested and proven.

b) A dedicated scale inhibitor- cum-dispersant shall also be included in the programme for

dispersion of iron, general scale, and sludge and to take care of chances of scaling due to

Page 15: TENDER DOCUMENT FOR COOLING WATER ... COMMERCIAL – SECTION NATIONAL FERTILIZERS LIMITED BATHINDA UNIT JULY 2011 2 TENDER DOCUMENTS FOR COOLING WATER TREATMENT PACKAGE ...

15

operation at high pH. Treatment should ensure no scaling in the heat exchangers. There

should not be reduction in heat transfer capacity of heat exchangers, due to fouling or

formation of deposits.

c) Effective control of biological growth shall be provided by using suitable biocide, bio-

dispersant together with chlorine dioxide. Vendor should quote for 3 or more non-

oxidizing biocides. Doses should correspond to MIC of the particular biocide.

d) It is desirable to have continuous dozing of chemicals preferably by metering pumps for

good control.

e) Blow down should be suitable for discharge into the inland surface water drains which

should be within the IS: 2490 (1981) and MINAS specifications. Chemicals and

treatment programme should meet this requirement without exception. The total quantity

of blow down from all cooling towers needs to be maintained below the present level as

given at 2.3 with the indicative make up water analysis specified at 2.6.1. The SRB limits

in make-up water shall be 5 Nos. per 100 ml (normal) and 20 Nos. Per 100 ml (max.).

Vendors should mention the water blow-down after each non-oxidizing biocide dosage at

percent (%) of system volume and quantity. Excess blow down or make up if resorted to

without valid reasons, NFL reserves the right to recover the cost of excess water

consumed along with cost of chemicals from the party.

f) Treatment programme should be capable of sustained operation under the prevailing

conditions and should be able to tolerate, ingress of ammonia, urea dust and oil, etc. In

case of Fuel oil based Plants, occasional ingress of Coal dust fly ash, H2S vapours, etc., in

the cooling towers may also take place. Details of contingency limits are indicated at 3.3

below.

g) Changeover of cooling water treatment shall be on line i.e without plant interruption. On

line changeover chemicals, if required, shall be indicated separately but form a part of the

contract.

h) Chemicals shall be supplied in new HDPE containers. The containers must be properly

sealed and also shall be labeled properly with name, brand name, batch no, expiry date

etc. Each batch of chemicals should have test certificate that all the chemicals are bio-

degradable (preferably within 24 hrs), environment friendly and do not fall under banned

category

i) Total quantity of chemicals, to be supplied by the Vendor, should be adequate for 365

days operation of the plant in a year.

j) The offer should be realistic. Under quoting or offering lower doses of chemicals than

required will call for rejection. NFL reserves the right of increasing doses of the

chemicals offered by the parties based on the past experience, in case the programme is

falling short to meet the requirements.

k) Vendors are advised to visit plant site and submit proposal only after extensive plant

survey, ascertaining quality of make up, circulating water, blow down, equipment

metallurgy etc. Vendor is free to quote chemicals over and above the ones specified in

this document to meet the guarantees. No complaints of the vendor will be entertained

after issue of work order.

l) Vendor shall provide analytical method of analysis along with active content, details of

instruments/reagents required for analysis of various Chemicals active content in bulk

chemicals & their value. If these methods are not submitted by the vendors, price bid

will not be opened. NFL has the right to check the analysis.

Corrosion Inhibitor % of Total phosphate as PO4

% of Zinc as Zn

Dispersant % of Organo-phosphonate

Sequestration value mg/ml (minimum)

Bio dispersant % Active ingredient & physical property

NaClO2 % active content

Non- Oxidizing Biocide as described

Page 16: TENDER DOCUMENT FOR COOLING WATER ... COMMERCIAL – SECTION NATIONAL FERTILIZERS LIMITED BATHINDA UNIT JULY 2011 2 TENDER DOCUMENTS FOR COOLING WATER TREATMENT PACKAGE ...

16

m) Vendor shall carry out daily water analysis to monitor the necessary treatment

parameters. NFL has the right to check the analysis. Lab facilities shall be provided to

the vendor for the above analysis. However, for analysis of chlorine dioxide and Zinc,

spectrophotometer shall be provided by the vendor. All reagents for testing/analysis are

in the scope of vendor.

n) Corrosion coupon will be assessed jointly by NFL and vendor.

o) Microbiological analysis will be carried out by NFL in the presence of Vendors'

representative.

3.2 CW Treatment Scheme

3.2.1 pH Control

Treatment program should be designed in such a way that the pH of circulating water in

return header is kept within 6.8-8.0. pH in circulating water shall not be allowed to go

below 6.5 at any time.

Vendor shall maintain the same with his treatment and by dosing concentrated sulphuric acid.

Based on site conditions, pH may also be controlled by dosing Soda Ash, if so required,

under exceptional circumstances after discussion and information to NFL citing reasons

for use of the same.

a) pH reduction due to microbiological activity should be avoided. In case of such

occurrence, reasons for such an occurrence shall be established to the satisfaction of NFL

and corrective action must be taken immediately for which vendor shall use biocide. If

pH reduction is due to other reasons, the contractor may be allowed by NFL to use Soda

Ash. Bidder shall intimate the quantities of Soda Ash to be consumed for each cooling

tower separately in techno-commercial bid, which shall be to bidder’s account and

arranged by bidder. The maximum quantity of soda ash permitted per year for all towers

taken together will be limited to 24 tons/year.

Any extra quantity of soda ash consumed other than that mentioned above will also be to

the bidders account.

b) In case of pH reduction due to ingress of acidic gases, soda ash dosing shall be permitted

for pH correction, which will be in NFL’s account. Such dosing shall be decided by

mutual consent in writing prior to start of dosing.

3.2.2 Corrosion Inhibitor and Anti-scaling Dispersant: The treatment programme should be

capable of maintaining corrosion rate less than 3.0 mpy on MS un- passivated sand

blasted corrosion coupons manufactured as per ASTM, to be supplied by NFL and shall

be installed in return header every month in each cooling tower. Corrosion racks and

necessary fittings to be provided by vendor.

One additional rack shall be available as common spare (standby) for all towers. The corrosion

coupons shall be sealed by NFL and party’s representative will be associated with such

sealing. All keys shall be kept with plant authorities.

a) Party should give percent (%) composition of total phosphate & Zinc in their corrosion

inhibitor. Normal of 9 -11 ppm of total inorganic phosphate is to be maintained by regular

chemical dosing at all times. Quantity of phosphate should be worked out at 10 ppm total

inorganic phosphate dosing for the purpose of evaluation. Minimum 1 ppm of Zinc is to

be maintained in circulating water.

b) The scale inhibitor-cum-dispersant shall take care of chances of scaling due to operation at

high pH and high temperature. Procedure for analysis of dispersant in circulating cooling

water is essential along with the technical bid. To take care of the adverse effects of higher

pH during monsoon season, doses of dispersant are to be maintained on sufficiently higher

side to avoid scale formation in critical exchangers where cooling water is on shell side

with low velocity. The dispersant offered should be proven and supporting documents for

the same to be provided

c) In case of some critical exchangers, a need may arise for localized (satellite) dosing of

Page 17: TENDER DOCUMENT FOR COOLING WATER ... COMMERCIAL – SECTION NATIONAL FERTILIZERS LIMITED BATHINDA UNIT JULY 2011 2 TENDER DOCUMENTS FOR COOLING WATER TREATMENT PACKAGE ...

17

dispersant. The Vendor should be ready with necessary arrangements for the same. Doses

of dispersant should be selected accordingly.

d) Dispersant Test: Recommended dispersant should give min. 95 % of Ca3 (PO4) 2

inhibition test at 50 % of the recommended dose level under test condition which are

pH: 8, Ortho-PO4: 8 ppm, temperature - 70OC and Ca hardness 500 ppm as CaCO3 in

presence of total iron of 1mg / lit in cooling water system. NFL reserves the right to test

the dispersant.

3.2.3 Micro Biological Control:

i) Chlorination shall be done continuously to maintain a free residual chlorine level of

0.2 ppm in return header of each cooling tower.

ii) Any excess of chlorine should be avoided due to its harmful effects.

iii) Chlorine dioxide shall be dozed for which vendor shall provide a chlorine dioxide

generator for in-situ generation.

iv) At least three non-oxidising biocides out of the following suggestive biocides are to

be recommended by the vendor so as to achieve the guaranteed figure as per clause

No. 3.7. Minimum active contents of biocide and ppm dose based on hold up volume

for effective bio control shall be as follows

S.

No

Biocide type Minimum

(%) Active

content

Minimum (ppm)

dose based on

Hold up

1 Quaternary Ammonium

compounds (QUAT)

40 25

2 Carbamate based 45 30

3 Isothiozoline based 1.4 30

4 Methylene bis thiocynate

(MBT) based

9 25

5 Diclorophene based 40 30

Minimum dosing frequency of non-oxidising biocide will be once in two weeks per

tower and a minimum of 26 doses per year per tower, preferably, with sequential

dosing. Changes in the biocides, if any, will be reviewed after actual application and

monitoring of the system.

v) Party shall submit procedure for analysing active ingredients of all the offered

biocides. If offered biocide active contents and/or dose are less than the above, NFL

reserves the right to reject the bid technically or modify the dose to arrive at aforesaid

minimum requirement and load the additional quantity. If offered concentration/dose

is more than specified above, then offered quantity shall be considered for evaluation.

Vendors can also quote biocides other than listed above. However vendor shall

submit adequate proof that the offered non-oxidising biocide with indicated

active ingredient and dosage has been used successfully for at least 2 years in

other ammonia/urea cooling towers, backed up by user certificate.

Effectiveness of biocide at quoted levels can be independently verified by NFL

through certified laboratories. If dosage level is found inadequate, then quantity can

be enhanced by NFL, cost of which will be borne by vendor. Result of test will be

binding on the party.

vi) A dedicated bio-dispersant shall be dosed on continuous basis to keep the system free

from bio-film formation. Minimum dosage of 3.0 ppm of bio dispersant in

circulating water is to be maintained.

3.2.4 Operating Parameters: In addition to details specified above, the vendor should also

consider the following, while designing the treatment.

a) Holding time index / large system volume and limitation in blow down rate. COC should

be in the range of 6-8 b) Water quality as specified at 2.6.1.

Page 18: TENDER DOCUMENT FOR COOLING WATER ... COMMERCIAL – SECTION NATIONAL FERTILIZERS LIMITED BATHINDA UNIT JULY 2011 2 TENDER DOCUMENTS FOR COOLING WATER TREATMENT PACKAGE ...

18

c) High temperatures in the CW heat exchangers (both on process and CW sides). Material

of construction of heat exchangers as given at annexure-II.

Vendor will provide following circulating water parameters to be measured on daily

basis:

Parameter Unit Normal Maximum*

pH

Free residual chlorine ppm as

Cl2

-

Chlorine Dioxide (ClO2)

Oxygen reduction potential

(ORP)

Turbidity

Total hardness as CaCO3

Calcium hardness as CaCO3

Zinc ppm

Ortho phosphate as PO4 (ppm)

Total Phosphate ppm PO4

Scale Dispersant ppm

Silica as SiO2

Bio dispersant

Chloride as Cl

Cycle of Concentration

M alkalinity as CaCO3

Iron content

Nitrifying bacteria should be maintained preferably less than 25 counts/ml. On a

monthly basis.

Maximum value shall be applicable based on the quality of make up water as mutually

agreed before starting the treatment. It is desired that normal control limits should not be

crossed. In case of exceeding the normal limits, necessary information shall be conveyed

to Production Incharge and corrective action taken immediately.

3.3 Contingency Treatment:

3.3.1 The vendor shall have a contingency treatment programme to take care of the effect of

various contaminants.

The limits of contaminants in CW circulating water shall be as follows:

Contaminants Ammonia CT

PPM (Max)

Urea CT

PPM (Max)

CPP CT

PPM (Max)

Ammonia 60 250 20

Urea 10 10 10

Oil 10 10 10

3.3.2 Contingency shall be decided at the time of its occurrence by mutual consent, in writing,

by NFL. Same shall be approved by Unit In-charge prior to the start of contingency

treatment. A contingency shall be declared, if disturbed condition persists for 48 hrs

(forty eight hours) for ammonia and Urea and immediately on detection of oil. The bidder

should indicate the details of chemicals to be used along with quantity for meeting each

contingency for each tower separately. This treatment shall remain effective for 72 hours.

Loading of quotations against contingencies shall be made based on the number of

Page 19: TENDER DOCUMENT FOR COOLING WATER ... COMMERCIAL – SECTION NATIONAL FERTILIZERS LIMITED BATHINDA UNIT JULY 2011 2 TENDER DOCUMENTS FOR COOLING WATER TREATMENT PACKAGE ...

19

contingencies as stipulated below:

Ammonia CT Urea CT CPP CT

Oil 1 1 1

Ammonia 1 3 0

Urea 0 0 0

In case, the contingency like leakage of cooling water from underground header etc, is

not controlled within a reasonable time and NFL decides to continue with it in order to

avoid plant interruption, then the modalities of using additional chemicals shall be

discussed and agreed mutually. The continuation of contingency as well as additional

expenditure on this account shall require prior approval of the Unit In-charge.

3.4 Alternative chemicals for water treatment

The contractor may sometimes find it necessary to change one or two chemicals during

the treatment based on his experience regarding efficacy of the chemical in use. Since the

contractor shall be in a better position to know regarding nature of make up water,

circulating water and effectiveness of the treatment, after carrying out the treatment for

some time, allowing use of alternative chemicals is considered in the interest of achieving

better results.

For this purpose vendor shall specify all such alternative chemicals along with their unit

rates in the quotation itself. Main chemical shall be taken for the purpose of bid

evaluation and calculating guaranteed cost. Any chemical not in bidding list, if needed

can be agreed after mutual discussion and prior approval of Unit In-charge.

However, the overall guaranteed cost shall remain the same.

3.5 Mobilization Period & stabilization period: Mobilization period for starting the

treatment shall be one-month maximum from the award of contract or as mutually

agreed. However, Contract period for the purpose of calculation of the number of days

shall be with effect from the actual date of start of treatment programme. Stabilization

period shall be one month (max. ) from the start-up of the Cooling Water Treatment as

mutually agreed. The trial period of six months where ever applicable shall include one

month of stabilization period. No penalty shall be levied during stabilization period. If

existing vendor continues for the next contract, there shall be no stabilization period.

3.6 Monitoring:

3.6.1 Monitoring Tools: Vendor should be equipped with gadgets for monitoring the health of

the cooling water system, including simulation capabilities for trouble-shooting. Gadgets

for studying fouling factor, heat flux etc. on line shall be required. Vendors should clearly

mention the details of the monitoring instruments which will be supplied free of cost with

the package for use at site on returnable basis.

Following online / other monitoring instruments are to be provided for each tower from

the Vendors:

a) Bio-fouling monitors (with differential pressure gauge)

b) Online Deposit monitors.

c) Corrosion racks with necessary fittings and screws compatible with corrosion coupon.

d) Analytical kit for field testing (with reagents replenishment).

e) Corrator facility for instantaneous corrosion rate (Minimum twice in month during

normal operation)

f) ORP monitor

g) Dosing system including metering pumps and replacement of spares as and when

required. Vendor shall keep necessary spare dosing and monitoring system and spares

Page 20: TENDER DOCUMENT FOR COOLING WATER ... COMMERCIAL – SECTION NATIONAL FERTILIZERS LIMITED BATHINDA UNIT JULY 2011 2 TENDER DOCUMENTS FOR COOLING WATER TREATMENT PACKAGE ...

20

parts at site so that chemical dosing system and monitoring system can be kept in

service uninterrupted. If the vendor fails to maintain the system in healthy condition

the same will be attended by NFL at the cost and risk of the vendor. To ensure precise

addition of chemicals on continuous basis, the dosing system shall comprise all the

parts/pumps /equipments/pipelines/valves to ensure the dosing of different chemicals

from dosing tank right up to the basin and any other equipment required to achieve the

dosing on continuous and uniform basis.

h) PC based Software and hardware for trend check.

i) Any other instrument for simulation and diagnostic study

3.6.2 Vendor should have access to a full-fledged R & D facility of his own. The party should have

properly trained team for trouble-shooting of the problems associated with this cooling water

treatment.

3.6.3 Monitoring Services: Vendor should carry out:

a) Continuous monitoring and supervision by his specialist(s) during pre-cleaning &

passivatrion initially and also on day-to-day basis, during normal operation.

b) Reporting to plant personnel & submission of daily analysis report to Plant In-charge by

4.00 pm every day. Involve NFL personnel in the operation and control of the treatment.

c) Submission of monthly report on water quality and monthly consumption of chemicals.

d) Reports with detailed analysis and corrective actions for excess consumption of normal

and / or contingency chemicals, if any.

e) Trouble shooting as and when required through vendor's resident expert.

f) Training of NFL personnel periodically w.r.t cooling water treatment developments.

3.6.4 Vendor should depute a supervisor cum Chemist at their cost for trouble-shooting and

analysis to take care of the on-going cooling water treatment. The qualification &

experience in fertilizers industry cooling water treatment of the supervisors should be

submitted along with the technical bid.

3.6.5 Dosing of all chemicals (regular as well as contingency) shall be the total responsibility

of the Vendor. In case the plant is being operated under disturbed conditions of leakage

etc leading to deviation in cooling water parameters, pH of cooling water will be checked

every 2 hours for 2-3 days to find optimum dosage of chemicals to take care of the

situation.

3.7 Essentials/Performance Guarantees Vendor will furnish the following guarantees for the performance of their C.W. treatment

programme. Written procedure shall be submitted for analysis and ascertaining the

guarantees, which shall be approved by NFL.

3.7.1 Corrosion Rate: The corrosion rate as measured on sand blasted MS Unpassivated Test

Coupons (ASTM: 179 Steel) as per ASTM procedure separately for each tower should not

exceed 3.0 mpy (measured in return header).

a) Analysis shall be reported as a rational number up to one decimal place after rounding off

as per procedure laid down in IS: 2-1960.

b) The test coupon shall be removed normally after duration of 30 days. However, in case of

any exigencies, the time limit may vary by plus minus 5 days after approval of Unit in-

charge.

Page 21: TENDER DOCUMENT FOR COOLING WATER ... COMMERCIAL – SECTION NATIONAL FERTILIZERS LIMITED BATHINDA UNIT JULY 2011 2 TENDER DOCUMENTS FOR COOLING WATER TREATMENT PACKAGE ...

21

c) In case of completion of 6 months of trial period, if the test coupon has not completed 30

days, another 15 days (max.) shall be allowed to ascertain the performance for 30 days,

which shall be allowed after approval of Unit head.

d) In case cooling water circulation is stopped for more than 8 hours, the test coupons shall

be rejected.

3.7.2 Micro Biological Count: Bidder shall guarantee cooling water system free of

undesirable biological growth (to be measured every week) throughout the period of

operation.

Total bacterial count (TBC) should not exceed 1.0 lac/ml on fortnightly basis

Sulphate Reducing Bacteria (SRB) should not exceed 100/100 ml on fortnightly basis.

3.7.3 Iron in circulating water < 1.0 ppm on fortnightly average of iron analyzed on

daily basis.

3.7.4 There should not be any tube leakage or fouling of heat exchangers due to inadequacy in

the C.W. treatment, which may result in stoppage of plant. Inspections during planned

shutdowns should reveal that heat exchangers and cooling water system is in good

condition without serious corrosion, pitting, scaling or fouling.

3.8 Penalties and termination

In case, the conditions, mentioned under the ‘Guarantees’, are not met, the following penalties

shall be levied on a yearly basis (including trial order period, if any)

3.8.1 Corrosion rate:

a) If the guaranteed corrosion rate for any one of the Cooling Towers exceeds 3.0 mpy,

Rs.25, 000/- per tower, shall be deducted for each of such failure.

b) In addition to above deduction, if the failure occurs consecutively in the

following month for same tower 20% of the SD-cum-PBG on pro-rata

basis (Total PBG Amount * number of towers where failure occurred /

total number of towers being treated) will be forfeited and vendor shall

be given 30 days from occurrence to rectify the same, failing which the

balance SD-cum-PBG shall be forfeited and contract is liable to be

terminated.

c) If corrosion rate exceeds 3.0 mpy on three occasions in same tower, the entire SD-

cum-PBG amount shall be forfeited and contract is liable to be terminated.

3.8.2 If any of the three parameters, (TBC, SRB and Fe), individually exceeds the limits in

any one tower mentioned above during the term of the contract, vendor

shall be allowed to modify treatment at his cost. If any one or more of the

parameters remain out in consecutive reading, 5% of the SD-cum-PBG

on pro rata basis (Total PBG amount * number of towers where failure

occurred / total number of towers being treated) will be forfeited. It is

further clarified that the maximum liability per fortnight per tower is 5%

of the SD-cum-PBG (on pro rata basis) against three parameters stated

herewith.

Page 22: TENDER DOCUMENT FOR COOLING WATER ... COMMERCIAL – SECTION NATIONAL FERTILIZERS LIMITED BATHINDA UNIT JULY 2011 2 TENDER DOCUMENTS FOR COOLING WATER TREATMENT PACKAGE ...

22

3.8.3 a) If any two out of the three parameters (i.e. TBC, SRB, and Fe) are more

than guaranteed values for consecutive 3 readings, in same tower, 10% of

the SD-cum-PBG on prorata basis (Total PBG amount * number of towers

where failure occurred / total number of towers being treated) will be

forfeited. It is further clarified that the maximum liability per fortnight

per tower for third consecutive failure on this account is 10% of the SD-

cum-PBG (on pro rata basis) against three parameters stated herewith.

b) If any two out of the three parameters i.e. (TBC, SRB and Fe) are more

than guaranteed values for consecutive 4 readings in same tower, 10% of

the SD-cum-PBG on prorata basis (Total PBG amount * number of

towers where failure occurred / total number of towers being treated) will

be forfeited and vendor will be given 30 days from occurrence to rectify the

same failing which the contract is liable to be terminated. During the

period of 30 days given to contractor from occurrence, no penalties will be

levied. It is further clarified that maximum liability per fortnight per

tower for fourth consecutive failure on this account is 10% of the SD-cum-

PBG (on pro rata basis) against three parameters stated herewith 3.8.4 NFL shall have the right to terminate the contract, in case of any eventual unsatisfactory

performance including heavy fouling of heat exchangers due to which plant has to be

stopped, notwithstanding various provisions of the contract.

3.8.5 In case due to unsatisfactory performance of the contract, termination

clause becomes operative, a termination notice of 15 days (minimum) to 3

months shall be given to the vendor. The contract shall be terminated after

expiry of the notice period. During the notice period, all terms and

conditions, as applicable in the contract, shall apply. Penalties applicable

during the period when termination clause becomes operative and party is

informed regarding the same, till termination, shall be as per clause 3.8.1

(a). No penalties w.r.t. Other guaranteed parameters of TBC, SRB, Fe

shall be applicable.

3.8.6 The total liability of the vendor during one year term of contract on

account of failure to meet guarantees of corrosion rate, SRB, TBC, Fe will

be limited to SD-cum-PBG amount plus penalty amount deducted under

clause 3.8.1(a)

.

Page 23: TENDER DOCUMENT FOR COOLING WATER ... COMMERCIAL – SECTION NATIONAL FERTILIZERS LIMITED BATHINDA UNIT JULY 2011 2 TENDER DOCUMENTS FOR COOLING WATER TREATMENT PACKAGE ...

23

SECTION - C

4.0 Instruction to Bidders for bidding documents

4.1 Technical Quote

1. Bidder shall quote separately for Ammonia, Urea and CPP (wherever applicable) Cooling

Water treatment in respect of control parameters of circulating water, chemical dosing

rate, chemical consumption, Unit rates etc.

2. Bidder shall indicate the maximum consumption of each regular chemical to be supplied

by him, for each cooling tower per month. Maximum payable/guaranteed contract

amount shall be calculated for all towers taken together, on yearly consumption based on

365 days of regular operation of cooling towers.

3. Bidder shall also mention tower wise maximum consumption of sulphuric acid and

chlorine to be supplied by NFL as free issue materials.

4. Any extra chemicals, required for change over from existing treatment to new treatment

shall be mentioned separately.

5. After annual shutdown and draining of Cooling Tower, the requirement of Pre-cleaning/

bio- cleaning and passivation chemicals as well as one extra charge required due to

refilling of cooling tower, should be indicated separately.

6. Contingency chemicals and their quantities for contingency, as foreseen by Bidder (Ref

Clause 3.3) for each cooling tower, shall be indicated separately. Same shall be included

in evaluation of bid.

7. In case of any additional shutdown during the year which has resulted in draining of the

water from the cooling tower (s), the additional initial fill, pre-cleaning/ bio-cleaning and

passivatrion chemicals including biocide and bio dispersant whichever required, shall be

allowed after approval of competent authority

8. Bidder should specify the time period for stabilization before start of normal treatment

programme. Maximum stabilization period shall be 30 days from start up of cooling

water treatment. In case of any interruption in this duration, due to shut down resulting in

draining of cooling towers, stabilization period shall be extended suitably after mutual

discussions with NFL. However, contract period shall remain the same and payment shall

be released for chemical consumption on actual but limited to overall cost of all the

towers taken together on yearly basis.

9. Chemical consumption shall be calculated on the basis of C.O.C., blow down quantity as

mentioned in ‘details of existing cooling water system’ in Section-A. Bidder shall furnish

calculations for the same.

10. Contract shall initially be for one-year duration, which on successful execution may be

extended for another year. Vendor shall, however, quote for a period of two years during

which the quoted rates shall remain firm.

4.2 Bid Evaluation: Following shall be considered for the purpose of bid evaluation

only:

• For the purpose of evaluation, cost of all towers shall be clubbed together on an annual

basis.

• Cost of chemicals for regular treatment based on bidders quotation in terms of quantity

and unit rates shall be considered for 365 days of operation in a year

• Cost of chemicals required for change over from existing treatment to new treatment.

Page 24: TENDER DOCUMENT FOR COOLING WATER ... COMMERCIAL – SECTION NATIONAL FERTILIZERS LIMITED BATHINDA UNIT JULY 2011 2 TENDER DOCUMENTS FOR COOLING WATER TREATMENT PACKAGE ...

24

• Cost of Pre-cleaning/ bio- cleaning and passivation chemicals as well as one charge

required due to refilling of cooling tower, after annual shutdown and draining of Cooling

Tower.

• Cost of Contingency chemicals based on quantities indicated by bidder for each

contingency and for number of contingencies as listed at 3.3 for each cooling tower.

• Equivalent cost of sulphuric acid and chlorine to be supplied by NFL, based on

maximum quantities indicated by bidder for 365 days.

It is however, clarified that guaranteed overall annual cost shall be calculated as detailed

at 4.3 below.

4.3 Guaranteed overall annual cost

a) Vendor shall guarantee the overall annual cost of treatment chemicals, which shall be

worked out as follows. However payment shall be released based on actual consumption

of chemicals limited to overall guaranteed cost.

b) Guaranteed overall annual cost shall be worked out as follows:

• The cost shall be clubbed for all the towers on yearly basis

• Landed Cost of chemicals for regular treatment based on bidders quotation in

terms of quantity and unit rates shall be considered for 365 days of operation in a

year. In case there is a variation in actual operating days, adjustment shall be

made on pro-rata basis for either side. Any excess consumption above the

adjusted quoted value shall be, to the vendor’s account.

• The quantity of sulphuric acid, which is supplied to the vendor as free issue

materials by NFL, shall be clubbed for all the towers. Any additional quantity

consumed over and above the quoted quantity shall be to the bidders account.

• The quantity of chlorine, which is supplied to the vendors as free issue materials

by NFL, shall be clubbed for all the towers. Any additional quantity consumed

over and above the quoted quantity shall be to the bidders account.

• Quantity of sulphuric acid and chlorine as quoted by the bidders shall be

considered separately. These shall not be adjusted against each other nor these

shall be included in the Guaranteed overall annual cost.

• Any extra chemicals, required for change over from existing treatment to new

treatment shall be mentioned separately. These shall not be included in

Guaranteed annual cost. Payment against these chemicals shall be made on the

basis of actual consumption, limited to quoted value, over and above the

Guaranteed overall annual cost

• Pre-cleaning/ bio- cleaning and passivation chemicals as well as one charge for

refilling of cooling tower after annual shutdown, should be indicated separately

and shall be paid additionally, on actual consumptions. These shall not be

included in Guaranteed annual cost.

• The contingency chemicals as quoted by the bidders shall not be included in

Guaranteed overall annual cost. Payment against these chemicals shall be made

on the basis of actual consumption, limited to quoted value, over and above the

Guaranteed overall annual cost.

c) Any excess consumption of sulphuric acid or chlorine shall be charged at current

price. Current price shall mean landed price for the period after vendor has

consumed the total quantity of these chemicals as specified in contract. No

departmental charges shall be charged for over consumption.

d) Any chemical, other than sulphuric acid and chlorine shall not be supplied by

NFL. The chemicals like Soda Ash etc. (if required) shall be in the scope of the

Contractor.

Page 25: TENDER DOCUMENT FOR COOLING WATER ... COMMERCIAL – SECTION NATIONAL FERTILIZERS LIMITED BATHINDA UNIT JULY 2011 2 TENDER DOCUMENTS FOR COOLING WATER TREATMENT PACKAGE ...

25

4.4 Vendor’s Scope

Vendor’s scope of work, supply and services shall be as described below:

1. Design of suitable cooling water treatment programme to meet the system

requirements and technical specifications.

2. Supply of chemicals for initial change over, normal operations, contingencies and

extra charge for refilling of cooling tower after annual shutdown.

3. To provide and maintain dosing system inclusive of metering pumps for chemical

dozing, including the pumps for chemicals for pH control; special instruments for

monitoring the treatment programme; Corrosion rack, bio-fouling monitors and scale

monitors etc. free of cost to NFL, on returnable basis.

4. Supervision by Vendor’s specialist(s) during initial commissioning, change over and

stabilization of treatment package followed by round the clock regular supervision

during normal operations. Vendor specialist shall be well qualified and experienced.

Vendor shall obtain approval of bio data of his specialists from NFL prior to his

appointment at site.

5. Training of NFL personnel in the operation and monitoring of cooling water

treatment.

6. Chlorine dioxide generator and Spectrophotometer for analyzing Chlorine dioxide

along with reagent to be provided by vendor, which shall be taken back after

completion of contract.

4.5 Owners Scope

NFL’s scope of supply and responsibilities shall include the following: -

1. Sulphuric Acid (98% concentration) shall be made available in the storage tanks

near the Cooling Tower.

2. Chlorine in One Tonne cylinders shall be placed at the specified locations.

3. In general, NFL shall not supply any additional chemical other than chlorine and

sulphuric acid. However, in case NFL agrees on emergency basis as a special

case, same shall be supplied by NFL on chargeable basis with additional 25%

departmental charges.

4. Power connections shall be provided to all the equipments/ instruments for dozing

operations and monitoring.

5. Laboratory assistance, to the extent available, shall be provided.

6. NFL shall make available test coupons manufactured as per ASTM specifications.

7. NFL shall operate the system under guidance of Vendor’s specialist.

8. Accommodation to site engineers of vendor shall be furnished subject to the

availability and on chargeable basis at commercial rates.

9. RAX telephone facility will be provided at the residence of the vendor in township

for better communication.

4.6 Trial order

4.6.1 If vendor has been pre-qualified for placement of order on trial basis then order shall be

placed on trial basis for a period of six months (Including stabilization period). Once

trial is successfully executed, the order shall be extended by another six

months to make one full year term which will be further extendable for

another one year provided the Unit feels that the contractor has executed

the contract in its true spirit. 4.6.2 In case of orders placed on trial basis, vendor shall submit SD-cum-PBG equivalent to

20% of the value of the annual contract. Even if the order is placed on trial

basis and then extended for the balance six months, penalties/guarantees

Page 26: TENDER DOCUMENT FOR COOLING WATER ... COMMERCIAL – SECTION NATIONAL FERTILIZERS LIMITED BATHINDA UNIT JULY 2011 2 TENDER DOCUMENTS FOR COOLING WATER TREATMENT PACKAGE ...

26

and other terms and conditions will be applied for one year.

4.6.3 Payment to vendor during trial period (six months) shall be made in two installments i.e.

after successful completion of a period of 3 months each.

4.6.4 In case of failure of trial order, no payment shall be released to vendor and amount

equivalent to 20% of the guaranteed order value for 6 months shall be forfeited from the

SD-cum-PBG. If party performs satisfactorily in first three months of trial period, but

fails in succeeding three months, payment for first three months shall be released while

the SD-cum-PBG equivalent to 20% of order value for six months shall be forfeited.

4.7 Contents of Offer

4.7.1 Bidder shall furnish details of the treatment programme including the following: -

a) Descriptions of programme.

b) Chemicals used, giving name, code number and function i.e. passivating agent, anti-

Scaling, dispersant, bio-dispersant, biocide and any other specific chemicals along with

active matter, concentration and percentage kill of biocides.

c) Dozing rates, monthly consumption as well as yearly consumption of chemicals for each

Cooling Tower. This shall include the quantity of sulphuric acid, chlorine as well as soda

ash (if required). These shall be supported by design calculations.

4.7.2 The treatment program for each cooling tower should be separately indicated for (a) Pre-

cleaning and passivation, (b) Normal Treatment, (c) Contingency treatment for each

contingency tower wise.

Vendor shall submit complete procedure and time required for the change-over of the new

treatment.

4.7.3 Detailed description of the philosophy and working of the automatic feed monitoring and

dosing system (wherever applicable). 4.7.4 Source of supply of the chemicals, including quality control system.

4.7.5 Details regarding similar experience in implementing cooling water treatment programs.

These shall include name, location and details of the plant, specification of treatment system,

period of operation, analysis / inspection report.

4.7.6 Data sheets containing product specifications, special precautions for handling the

chemicals, disposal of empty containers, remedial measures to be taken in case of

spillage and ingress into human body etc. shall be furnished.

4.7.7 The chemicals shall be supplied in good quality containers. Vendor shall take back all the

used containers.

4.7.8 The chemicals that shall be left over after the contract is closed shall normally be taken

back by the vendor. However in case, it is desired by NFL, then full/part of the left over

chemicals shall be retained by NFL and the payment against the same shall be made separately.

4.8 Splitting of Contract

All cooling towers in the Unit shall be clubbed in a single package for the purpose of bid

evaluation and subsequently placement of order.

4.9 Availability of chemicals without interruption

Page 27: TENDER DOCUMENT FOR COOLING WATER ... COMMERCIAL – SECTION NATIONAL FERTILIZERS LIMITED BATHINDA UNIT JULY 2011 2 TENDER DOCUMENTS FOR COOLING WATER TREATMENT PACKAGE ...

27

Bidder shall guarantee supply of chemicals as per agreed schedule without interruption. Normal

schedule of supplies shall be every three months, so that the site inventory level does not

fall below 2 month’s requirement. Additional one-month’s chemicals are considered

during transit. However, during last month of the contract period, the spare inventory of

regular chemicals as mentioned above shall not fall below one month’s requirement.

Further the pre-cleaning, passivation and contingency chemicals leftover at the end of the

contract shall be taken back by the vendor and NFL shall recover the corresponding

amount from the vendor, if already paid for.

---------------------------

Annexure-I

N.F.L. BATHINDA UNIT

Normal Make up water analysis.

Months

Characteristics July

Aug Sep Oct Nov Dec Jan Feb Mar April May June

TH 92 91 88 88 97 102 101 106 104 105 110 104

Page 28: TENDER DOCUMENT FOR COOLING WATER ... COMMERCIAL – SECTION NATIONAL FERTILIZERS LIMITED BATHINDA UNIT JULY 2011 2 TENDER DOCUMENTS FOR COOLING WATER TREATMENT PACKAGE ...

28

Ca – H 69 66 64 62 70 73 71 75 73 73 77 71

Mg – H 23 25 24 26 27 29 30 31 31 32 33 33

Chloride 5 5 5 5 5 5 5 5 5 5 5 5

M-alk 63 65 63 65 71 74 74 74 74 73 75 74

Silica as Sio2 3.08 2.92 3.12 3.25 3.3 3.33 3.20 2.98 2.87 2.98 3.03 3.12

pH 7.8 7.8 7.8 7.8 8.0 8.0 8.0 8.0 7.9 7.8 7.8 7.8

Annexure-II (a)

AMMONIA PLANT EXCHANGERS’ DATA Exchanger Name/Code Cooling Water in

Tube side/Shell side

Material of

Construction of tubes Heat Duty

(MKcal/Hr.)

A-BE-001-GB-5 Condenser Tube side SS 2.5

A-EA-102-A/B Carbon Scrubber Water

Cooler

T.S. SS 4.476

A-EA-103-A/B Return Water Cooler T.S. SS 4.476

A-EA-104-A/B Gasifier C.W. Cooler T.S. SS 0.30

A-EA-106 Slurry Tank Condenser T.S. SS 1.70

A-EA-108 Condensate Cooler T.S. SS 1.80

A-EA-203 Recycle Gas Cooler Shell side MS 0.053

A-EA-208-A/B Claus Gas Condenser T.S. M.S. 1.90

A-EA-603 Synthesis Water Cooler Shell side S.S. 8.20

A-GB-001 Surface condenser Tube side SS 30.214

AGB-001-E1 Inter-cooler T.S. SS 6.93

AGB-001-E2 After cooler T.S. SS 6.765

AGB-002-E1 Inter cooler Shell side SS 0.531

AGB-002-E2 -do- SS 0.778

Page 29: TENDER DOCUMENT FOR COOLING WATER ... COMMERCIAL – SECTION NATIONAL FERTILIZERS LIMITED BATHINDA UNIT JULY 2011 2 TENDER DOCUMENTS FOR COOLING WATER TREATMENT PACKAGE ...

29

AGB-002-E3 Shell side SS 0.873

AGB-002-E4 -do- SS 0.758

AGB-002-E5 -do- SS 0.8522

AGB-002-E6 -do- SS 0.9995

AGB-002 S.C. Tube side SS 14.5

AGB-004 S.C. -do- SS 11.874

GB-004-E1 -do- SS 0.993

GB-004-E2 -do- SS 1.462

GB-004-E3 -do- SS 1.156

AGB-004-E4 -do- SS 1.33

AGB-601 S.C. -do- SS 22.2

AGB-601-E1 Shell side SS 3.485

AGB-601-E2 -do- SS 3.663

AGB-601-E3 -do- MS 2.358

AGC-601 S.C. Tube side SS 7.35

AGC-601-E1-A/B Ammonia Condenser -do- SS 10.1

AGB-001-T Ejector Condenser -do- SS 0.0773/0.1505

AGB-004-T -do- SS 0.607/0.105

AGB-601-T -do- SS --

AGC-601-T -do- SS --

AGB-001-E4-A/B -do- SS --

AGB-002-E A/B Tube side SS 0.317

AGB-004-E6-A/B -do- SS 0.162

AGB-601-E4-A/B -do- SS --

AGC-601-E2 -do- SS --

AGA-402-A-T L.O. Cooler -do- M.S. 0.0122

AGA-404-A-T L.O. Cooler -do- M.S. 0.0122

AGA-701 S.C. -do- SS 8.320

AGA-701-T E.C. -do- SS --

AGA-701-E1-A/B -do- SS 0.066

AGC-001-EA-1 (KPC) -do- SS --

A-BE-001 GB-5 L.O.Cooler -do- SS

ABE-401 EA-4 (ARU) -do- SS 7.2

ABE-401-EA-5-A/B (ARU) -do- SS 9.8

Annexure-II (b)

UREA PLANT HEAT EXCHANGER DATA SHEET -

Sl.No. Name of Exchanger Heat Duty Material of Construction CW Flow

IN

MMKCal/hr

Shell Tube

1 Condensate cooler U-EA-103 0.727 SA 516G x 60 SS-304 Tube

2. Turbine. Surface Cond.U-EA-104 10.800 IS-2062 SS-305 Tube

3. High Pr.Ab. Cooler U-EA-401 - SA 516 GH 70 Tube

3 -

4 Low Pr. Absorber UEA-402 7.252 SA-249 GH 304 SA-213 TP304 Tube

5 Purge NH3 Cond. UEA-403 3.83 SA 516 Gr 60 SS-304 Tube

6 NH3 Condenser UEA-404 A-E 3.028 x 5 SA 516 Gr 61 SS-304 Tube

7 NH3 Recovery Ab. UEA-405 (1/4,2/4, 3/4, 4/4) 0.586

SA 516 Gr 62 SA-304 Tube

0.244

Page 30: TENDER DOCUMENT FOR COOLING WATER ... COMMERCIAL – SECTION NATIONAL FERTILIZERS LIMITED BATHINDA UNIT JULY 2011 2 TENDER DOCUMENTS FOR COOLING WATER TREATMENT PACKAGE ...

30

0.16

8 Off gas condenser UEA-406 2.088 SA-240 Gr. 304

SA-213 TP 304 Tube

9 Off gas abs. Final cooler 0.0909 SA-240 Gr. 305 SA-213 TP 305 Tube

10 Cooler for UDA-402 UEA-408 1.011 SA-240 Gr. 306 SA-213 TP 306 Tube

11 UGB-101 E1 1.10 A-515 Gr. 60 SS-304 Shell

E2 1.86 A-515 Gr. 61 SS-304 Tube

E3 1.40 A-515 Gr. 62 SS-304 Tube

12 CO2 booster oil cooler SA-106 Gr.B SS-304 Tube

13 CO2 booster turbine ejector condenser UGB-101-E5 - IS-2026 A-249 TD 304 Tube

14 Inter cooler for GB-102 U-EA-107 1.800 SS-41 A-213 TP-304 Shell

15 UGB-102 LO Cooler 0.0227 STPG-38 A 53

Gr.A SS-304 Tube

Annexure II (C)

HEAT EXCHANGER DATA SHEET – CPP (BATHINDA)

Name of

Exchanger

Heat Duty Material of

Construction

CW Flow in

Surface Condenser of

TG-1 & 2

22 x 106

Joules/sec S.S. 304 TUBE

Page 31: TENDER DOCUMENT FOR COOLING WATER ... COMMERCIAL – SECTION NATIONAL FERTILIZERS LIMITED BATHINDA UNIT JULY 2011 2 TENDER DOCUMENTS FOR COOLING WATER TREATMENT PACKAGE ...

31

Page 32: TENDER DOCUMENT FOR COOLING WATER ... COMMERCIAL – SECTION NATIONAL FERTILIZERS LIMITED BATHINDA UNIT JULY 2011 2 TENDER DOCUMENTS FOR COOLING WATER TREATMENT PACKAGE ...

32

Annexure-B

FORMAT FOR PRICE BID

(COOLING TOWERS)

(FOR CALCULATING LANDED PRICE SEE NOTES BELOW)

2. Online Change Over (at the start of treatment prior to commencement of stabilization period) Ammonia Cooling Tower Urea Cooling Tower CPP Cooling Tower Description of

material

Basic Rate

Rs. Per Kg.

Quantity

( Kg.)

Amount Quantity

( Kg.)

Amount Quantity

( Kg.)

Amount

Total quantity (Kg) ) Total Value (Rs.)

3. Initial Fill (if required refilling) after Shutdown Ammonia Cooling Tower Urea Cooling Tower CPP Cooling Tower Description of

material

Basic Rate

Rs. Per Kg.

Quantity for

one charge (Kg)

Amount

Quantity for

one charge (Kg)

Amount

Quantity for

one charge(Kg)

Amount

Total quantity (Kg) Total Value (Rs.)

4. Pre-cleaning/Biocleaning after Shutdown Ammonia Cooling Tower Urea Cooling Tower CPP Cooling Tower Description of

material

Basic Rate

Rs. Per Kg.

Quantity for

one

charge(Kg)

Amount

Quantity for

one

charge (Kg)

Amount

Quantity for one

charge(Kg)

Amount

Total quantity (Kg) Total Value (Rs.)

Page 33: TENDER DOCUMENT FOR COOLING WATER ... COMMERCIAL – SECTION NATIONAL FERTILIZERS LIMITED BATHINDA UNIT JULY 2011 2 TENDER DOCUMENTS FOR COOLING WATER TREATMENT PACKAGE ...

33

5. Passivation after Shutdown Ammonia Cooling Tower Urea Cooling Tower CPP Cooling Tower Description of

material

Basic Rate

Rs. Per Kg.

Quantity for

one

charge(Kg)

Amount

Quantity for

one

charge (Kg)

Amount

Quantity for one

charge(Kg)

Amount

Total quantity (Kg) Total Value (Rs.)

6. Contingency Chemicals for Oil Ammonia Cooling Tower Urea Cooling Tower CPP Cooling Tower Description of

material

Basic Rate

Rs. Per Kg.

Quantity (Kg)

for

one charge

Amount

Quantity (Kg) for

one charge

Amount

Quantity (Kg) for

one charge

Amount

Total quantity (Kg) Total Value (Rs.)

7. Contingency Chemicals for Ammonia Ammonia Cooling Tower Urea Cooling Tower Description of

material

Basic Rate Rs. Per Kg.

Quantity (Kg) for

one charge

Amount

Quantity (Kg) for

Three charge

Amount

Total quantity (Kg) Total Value (Rs.)

8. Contingency Chemicals for Urea ( If ingress of Urea is more than 10ppm) Ammonia Cooling Tower Urea Cooling Tower Description of

material

Basic Rate Rs. Per Kg.

Quantity (Kg) for

one charge

Amount

Quantity (Kg) for

one charge

Amount

Total quantity (Kg) Total Value (Rs.)

Page 34: TENDER DOCUMENT FOR COOLING WATER ... COMMERCIAL – SECTION NATIONAL FERTILIZERS LIMITED BATHINDA UNIT JULY 2011 2 TENDER DOCUMENTS FOR COOLING WATER TREATMENT PACKAGE ...

34

9. Free issue chemicals to be supplied by NFL. Ammonia Cooling Tower Urea Cooling Tower CPP Cooling Tower Total quantity (Kg) Description of material

Quantity for one year (Kg.) based on 365

days

Quantity for one year (Kg.) based on 365

days

Quantity for one year (Kg.) based on 365

days

a) Chlorine a) Sulphuric Acid

10. Soda Ash (As per Para 3.2.1(b) Of Section B of Technical Section) CHEMICAL BASIC PRICE RS./Kg. Landed price in Rs./Kg.

Soda Ash

NOTE :

1. No other cost shall be admissible other than stated above.

2. Transit Insurance shall be arranged by the supplier at their cost.

3. Vendor should intimate following considered for arriving ‘LANDED PRICE’

A) Excise duty rate (if any) payable extra ………………………………………………… = ______ %

B) Education Cess on Excise duty (if any) payable extra………………………………… = ______ %

C) Central /Sales Tax rate (if any) payable extra

or Local VAT rate (if any) against VAT D-1 Form ……………………………. = ______ %

D) Freight upto NFL Stores Bathinda (if any) payable extra in Rs. Per Kg against vendor bill for supply = ______ Rs. Per Kg.

Page 35: TENDER DOCUMENT FOR COOLING WATER ... COMMERCIAL – SECTION NATIONAL FERTILIZERS LIMITED BATHINDA UNIT JULY 2011 2 TENDER DOCUMENTS FOR COOLING WATER TREATMENT PACKAGE ...

35

E) Entry Tax as applicable ……………………….…………………………………………… = ______ %

4. The ‘LANDED PRICE’ for above price bid format must be calculated as per following on NFL Stores basis:

LANDED PRICE (RS./KG) = (BASIC RATE (RS./KG) X TOTAL QUANTITY) + (EXCISE DUTY) + (EDUCATION CESS ON EXCISE DUTY) + SALES TAX + FREIGHT

UPTO NFL STORES BATHINDA + ENTRY TAX

5. Any chemical not attracting ‘Excise Duty & Education Cess’ must be clearly confirmed in the quotation & accordingly landed price for said chemical must be calculated without (excise

duty + cess) in the price bid format.

6. TDS will be deducted as per prevailing Govt. rules, if applicable.

DATED :

SIGNATURE

Page 36: TENDER DOCUMENT FOR COOLING WATER ... COMMERCIAL – SECTION NATIONAL FERTILIZERS LIMITED BATHINDA UNIT JULY 2011 2 TENDER DOCUMENTS FOR COOLING WATER TREATMENT PACKAGE ...

36

ANNEXURE- A

PROFORMA FOR SCHEDULE OF QUANTITIES AND RATES

1. Regular Treatment Chemicals:-

Ammonia Cooling Tower Urea Cooling Tower CPP Cooling Tower

S.

No.

Product Quantity for 365days

of plant operation in

Kg.

Basic

Unit

Rate

(Rs)/

Kg.

Amount

(Rs)

Quantity for

365 days of

plant operation

in Kg

Basic

Unit

Rate

(Rs)/Kg

Amount

(Rs)

Quantity for

365 days of

plant operation

in Kg

Basic

Unit Rate

(Rs)/Kg

Amount

(Rs)

Total Amount (Rs)

(Sum of Columns

3 + 6 + 9)

1 2 3 4 5 6 7 8 9

1. Chemical A

2. Chemical B

3. Chemical C

4. Chemical D

5. Chemical E

6. Chemical F

7. Chemical G