Page 1: Tecnair close control serie P ENG 0511 - Climalux.ro · Air Conditioners for Close Control and Data Centers high energy ef® ciency and minimum environmental impact 3 aM in characteristics

Air Conditionersfor Close Control and Data Centers

TECNAIR LVCLOSE CONTROL AIR CONDITIONERS

TECNAIR LV

GOST certifi cation

Page 2: Tecnair close control serie P ENG 0511 - Climalux.ro · Air Conditioners for Close Control and Data Centers high energy ef® ciency and minimum environmental impact 3 aM in characteristics

TECNAIR LVCLOSE CONTROL AIR CONDITIONERS

TECNAIR LV

Page 3: Tecnair close control serie P ENG 0511 - Climalux.ro · Air Conditioners for Close Control and Data Centers high energy ef® ciency and minimum environmental impact 3 aM in characteristics

Air Conditioners for Close Control and Data Centers high energy effi ciency and minimum environmental impact

3

Main characteristicsTecnair LV’s “P” Series air conditioners for

close control are special machines with design

and operating features which clearly differentiate

them from standard air conditioning units.

The total cooling capacity coverage of the

models with direct expansion - OPA with up-

fl ow air discharge and UPA with down-fl ow -

ranges from 7 up to 90 kW.

The same machines are available in chilled

water versions - OPU and UPU - with capacities

of up to approximately 200kW.

The “P” Series air conditioners offer very

high energy effi ciency values in all operating

conditions which translates into less CO2

emissions and particularly low running costs.

Though optimized for use in data centers and

telephone exchanges, they are equally valid

in special applications such as measurement

laboratories, TV recording studios, musical

instrument storage areas, museums, control

rooms for electricity power stations and railway

junctions and other areas in general where

there are prevalent sensible thermal loads and

crowding is negligible.

Their application is also ideal in widely varied

industrial sectors: optics, electronics, electro-

medical equipment, electronic equipment

production, musical instrument production etc.

In these applications an integrated system of

treatment of the external air may be requested.

ISO 9001Cert. n° 273GOST certifi cation

Page 4: Tecnair close control serie P ENG 0511 - Climalux.ro · Air Conditioners for Close Control and Data Centers high energy ef® ciency and minimum environmental impact 3 aM in characteristics

OPU: with chilled water coil

Models 302 372 422 512 612 662 852 932

Performance

Tot. cooling cap. kW: 31,4 39,2 43,4 53,1 63,1 70,0 89,8 99,6

Sens cooling cap. kW: 28,7 32,2 42,4 47,4 60,0 63,4 71,3 88,7

Airfl ow m3/h: 8.700 8.700 14.500 14.500 17.900 17.900 17.900 22.500

Condenser Model 2xACC 25 2xACC 29 2xACC 32 2xACC 42 2xACC 50 2xACC 55 2xACC 61 2xACC 74

EER 3,40 3,14 3,29 3,25 3,32 3,38 3,47 3,64

LPS:dB(A) 58 58 63 63 68 68 68 69

Dimensions & weight

Lenght mm. 1.410 1.410 1.750 1.750 2.300 2.300 2.300 2.640

Depth mm. 880 880 880 880 880 880 880 880

Height mm. 1.990 1.990 1.990 1.990 990 990 990 1.990

Net weight kg. 300 315 420 440 420 490 315 330

Models 10 20 30 50 80 110 160 220

Performance

Tot. cooling cap. kW: 11,3 19,6 31,7 39,8 70,9 89,3 152,8 178,8

Sens cooling cap. kW: 9,6 15,9 28,4 34,4 61,2 74,1 122,0 148,7

Airfl ow m3/h: 2200 3400 7800 8.300 16000 17.000 26.400 34800

LPS:dB(A) 47 49 57 56 59 61 64 82

Dimensions & weight

Lenght mm. 750 750 860 860 1750 1.750 2.640 3496

Depth mm. 630 630 880 880 880 880 880 880

Height mm. 1990 1990 1990 1990 1990 1.990 1.990 1990

Net weight kg. 155 155 180 250 450 450 650 900

TECN

AIR

LVPerformance as the test conditions TECNAIR LVOPA: direct expansion air conditioners with air cooled or water condensersModels 71 111 141 211 251 301 361 461

Performance

Tot. cooling cap. kW: 7,0 11,4 15,3 21,6 25,6 31,1 38,9 48,1

Sens cooling cap. kW: 6,8 11,1 12,7 20,8 22,6 28,7 36,3 43,9

Airfl ow m3/h: 2200 3200 3200 7000 7000 8700 14.500 14.500

Condenser Model ACC 11 ACC 16 ACC 21 ACC 32 ACC 42 ACC 50 ACC 55 ACC 74

EER 3,01 3,11 3,47 3,29 3,13 3,28 3,50 3,52

LPS:dB(A) 49 49 49 56 56 58 63 63

Dimensions & weight

Lenght mm. 750 750 750 860 860 750 1.750 1.750

Depth mm. 630 630 630 880 880 880 880 880

Height mm. 1990 1990 1990 1.990 1.990 1965 1.990 1.990

Net weight kg. 170 170 170 210 270 270 330 400

22

Upfl ow air supply

Page 5: Tecnair close control serie P ENG 0511 - Climalux.ro · Air Conditioners for Close Control and Data Centers high energy ef® ciency and minimum environmental impact 3 aM in characteristics

seriePPerformance as the test conditions TECNAIR LVUPA: direct expansion air conditioners with air cooled or water condensersModels 71 111 141 211 251 301 361 461

Performance

Tot. cooling cap. kW: 7,0 11,4 15,3 21,6 25,6 31,1 38,9 48,1

Sens cooling cap. kW: 6,8 11,1 12,7 20,8 22,6 28,7 36,3 43,9

Airfl ow m3/h: 2200 3200 3200 7000 7000 8700 14.500 14.500

Condenser Model ACC 11 ACC 16 ACC 21 ACC 32 ACC 42 ACC 50 ACC 55 ACC 74

EER 3,07 3,43 3,58 3,74 3,26 3,39 3,74 3,67

LPS:dB(A) 49 49 49 56 56 58 63 63

Dimensions & weight

Lenght mm. 750 750 750 860 860 750 1.750 1.750

Depth mm. 630 630 630 880 880 880 880 880

Height mm. 1990 1990 1990 1.990 1.990 1965 1.990 1.990

Net weight kg. 170 170 170 210 255 270 330 400

Models 302 372 422 512 612 662 852 932

Performance

Tot. cooling cap. kW: 31,4 39,2 43,4 53,1 63,1 70,0 89,8 99,6

Sens cooling cap. kW: 28,7 32,2 42,4 47,4 60,0 63,4 71,3 88,7

Airfl ow m3/h: 8.700 8.700 14.500 14.500 17.900 17.900 17.900 22.500

External static pressure (Pa) 30 30 30 30 30 30 30 30

Condenser Model 2xACC 25 2xACC 29 2xACC 32 2xACC 42 2xACC 50 2xACC 55 2xACC 61 2xACC 74

EER 3,50 3,25 3,46 3,40 3,46 3,46 3,55 3,79

LPS:dB(A) 58 58 63 63 68 68 68 69

Dimensions & weight

Lenght mm. 1.410 1.410 1.750 1.750 2.300 2.300 2.300 2.640

Depth mm. 880 880 880 880 880 880 880 880

Height mm. 1.990 1.990 1.990 1.990 990 990 990 1.990

Net weight kg. 300 315 420 440 420 470 315 330

UPU: with chilled water coilModels 10 20 30 50 80 110 160 220

Performance

Tot. cooling cap. kW: 11,3 19,6 31,7 39,8 70,9 89,3 152,8 178,8

Sens cooling cap. kW: 9,6 15,9 28,4 34,4 61,2 74,1 122,0 148,7

Airfl ow m3/h: 2200 3400 7800 8.300 16000 17.000 26.400 34800

LPS:dB(A) 47 49 57 56 59 61 64 82

Dimensions & weight

Lenght mm. 750 750 860 860 1750 1.750 2.640 3496

Depth mm. 630 630 880 880 880 880 880 880

Height mm. 1990 1990 1990 1990 1990 1.990 1.990 1990

Net weight kg. 155 155 180 250 450 450 650 900

Notes:

The performances are referred to: refrigerant R410; condensing temperature: 45°C; inlet air: 24°C - 50% RH; for chilled water: 7/12°C; The SPL is referred to 2 m distance, 1,5 m height, free fi eld and sound damped discharge mouth. Available static pressure: 30 Pa. EER = Electro Effi ciency Ratio = Total cooling capacity / compressors power input + fans power input. The above performances don’t consider the heat generated by the fans which must be added to the thermal load of the system.