Technologies for Assessing the Condition of Water Mains NC AWWA Spring Conference 2014 Matt Shultz, PE - HDR
![Page 2: Technologies for Assessing the Condition of Water Mains · – DIPRA 10-Point (AWWA C105) ... tools match pipe size ... Technologies for Assessing the Condition of Water Mains](https://reader031.fdocuments.in/reader031/viewer/2022022509/5ad6da4e7f8b9a865b8b6a43/html5/thumbnails/2.jpg)
Condition Assessment
• Determining and documenting the physical state of infrastructure at a point in time
• Identify improvements to extend asset life • Prioritizing improvements
![Page 3: Technologies for Assessing the Condition of Water Mains · – DIPRA 10-Point (AWWA C105) ... tools match pipe size ... Technologies for Assessing the Condition of Water Mains](https://reader031.fdocuments.in/reader031/viewer/2022022509/5ad6da4e7f8b9a865b8b6a43/html5/thumbnails/3.jpg)
Aging Infrastructure is the driver for Condition Assessment and Renewal
Reference: AWWA, Buried No Longer: Confronting America’s Water Infrastructure Challenge, 2012
![Page 4: Technologies for Assessing the Condition of Water Mains · – DIPRA 10-Point (AWWA C105) ... tools match pipe size ... Technologies for Assessing the Condition of Water Mains](https://reader031.fdocuments.in/reader031/viewer/2022022509/5ad6da4e7f8b9a865b8b6a43/html5/thumbnails/4.jpg)
Water Main Failures Can Cause Problems
Photo: Bill O’Leary, Washington Post
![Page 5: Technologies for Assessing the Condition of Water Mains · – DIPRA 10-Point (AWWA C105) ... tools match pipe size ... Technologies for Assessing the Condition of Water Mains](https://reader031.fdocuments.in/reader031/viewer/2022022509/5ad6da4e7f8b9a865b8b6a43/html5/thumbnails/5.jpg)
….and have Consequences
Photo: Al Seib, LA Times
![Page 6: Technologies for Assessing the Condition of Water Mains · – DIPRA 10-Point (AWWA C105) ... tools match pipe size ... Technologies for Assessing the Condition of Water Mains](https://reader031.fdocuments.in/reader031/viewer/2022022509/5ad6da4e7f8b9a865b8b6a43/html5/thumbnails/6.jpg)
Three Components of Condition Assessment Determine Success and Usefulness
![Page 7: Technologies for Assessing the Condition of Water Mains · – DIPRA 10-Point (AWWA C105) ... tools match pipe size ... Technologies for Assessing the Condition of Water Mains](https://reader031.fdocuments.in/reader031/viewer/2022022509/5ad6da4e7f8b9a865b8b6a43/html5/thumbnails/7.jpg)
Assessment Technologies…there are a lot of them
Source: EPA, 2012 Condition Assessment Technologies for Water Transmission and Distribution Systems
![Page 8: Technologies for Assessing the Condition of Water Mains · – DIPRA 10-Point (AWWA C105) ... tools match pipe size ... Technologies for Assessing the Condition of Water Mains](https://reader031.fdocuments.in/reader031/viewer/2022022509/5ad6da4e7f8b9a865b8b6a43/html5/thumbnails/8.jpg)
Ductile and Cast Iron Pipe…aging is a problem
Aging can occur from: • Internal corrosion • External corrosion • Fatigue Failure Methods: • Pits or rust holes • Bursts (longitudinal) • Breaks (circumferential) • Leaks at joints or service taps
Pitting Corrosion
General Corrosion
![Page 9: Technologies for Assessing the Condition of Water Mains · – DIPRA 10-Point (AWWA C105) ... tools match pipe size ... Technologies for Assessing the Condition of Water Mains](https://reader031.fdocuments.in/reader031/viewer/2022022509/5ad6da4e7f8b9a865b8b6a43/html5/thumbnails/9.jpg)
Aging is a problem…but not always the answer
The Evolution of Iron Pipe is Dominated by Reduction in Wall Thickness
1928 Class D CI
1.58” 1952
Class 150 CI 1.22” 1957
Class 27 CI 0.94”
1957 Class 22 CI
0.87” 1965 Class 3 DI
0.58” 1976
Class 50 DI 0.43”
1991 Class 150 DI
0.38”
EXAMPLE FOR MINIMUM WALL 36-INCH IRON PIPE
![Page 10: Technologies for Assessing the Condition of Water Mains · – DIPRA 10-Point (AWWA C105) ... tools match pipe size ... Technologies for Assessing the Condition of Water Mains](https://reader031.fdocuments.in/reader031/viewer/2022022509/5ad6da4e7f8b9a865b8b6a43/html5/thumbnails/10.jpg)
External Corrosion…corrosive soils
Soil and Water Analysis • Resistivity, pH, Sulfate, Chloride, Redox Potential, Etc.
– DIPRA 10-Point (AWWA C105) • Linear Polarisation Resistance
![Page 11: Technologies for Assessing the Condition of Water Mains · – DIPRA 10-Point (AWWA C105) ... tools match pipe size ... Technologies for Assessing the Condition of Water Mains](https://reader031.fdocuments.in/reader031/viewer/2022022509/5ad6da4e7f8b9a865b8b6a43/html5/thumbnails/11.jpg)
External Corrosion… stray currents
ANODEGROUND BED
+
CATHODICALLY PROTECTEDSECTION OF PIPELINE A
-
POSITIVE DC CURRENT FLOW PIPELINE A
PIPELINE B
RECTIFIER
ACCELERATED CORROSIONON PIPELINE A
Overhead Power Transit Systems
Other Utilities
![Page 12: Technologies for Assessing the Condition of Water Mains · – DIPRA 10-Point (AWWA C105) ... tools match pipe size ... Technologies for Assessing the Condition of Water Mains](https://reader031.fdocuments.in/reader031/viewer/2022022509/5ad6da4e7f8b9a865b8b6a43/html5/thumbnails/12.jpg)
Ductile and Cast Iron – Assessment Technologies
Electromagnetic: Remote Field Eddy Current • PICA’s See Snake • Provides end to end 360-deg evaluation • Accurate determines pit size, depth, and location • Provides general corrosion loss • 2” to 36” pipes, tools match pipe size • Free swimming or tethered • Waterline can remain in service • Can navigate through bends
![Page 13: Technologies for Assessing the Condition of Water Mains · – DIPRA 10-Point (AWWA C105) ... tools match pipe size ... Technologies for Assessing the Condition of Water Mains](https://reader031.fdocuments.in/reader031/viewer/2022022509/5ad6da4e7f8b9a865b8b6a43/html5/thumbnails/13.jpg)
Design - PCCP Standards Changed Over Time …and not always for the better
![Page 14: Technologies for Assessing the Condition of Water Mains · – DIPRA 10-Point (AWWA C105) ... tools match pipe size ... Technologies for Assessing the Condition of Water Mains](https://reader031.fdocuments.in/reader031/viewer/2022022509/5ad6da4e7f8b9a865b8b6a43/html5/thumbnails/14.jpg)
Assessment Technology - PCCP Water Mains
![Page 15: Technologies for Assessing the Condition of Water Mains · – DIPRA 10-Point (AWWA C105) ... tools match pipe size ... Technologies for Assessing the Condition of Water Mains](https://reader031.fdocuments.in/reader031/viewer/2022022509/5ad6da4e7f8b9a865b8b6a43/html5/thumbnails/15.jpg)
Acoustic Events/Wire Breaks Leading up to SDCWA Failure
![Page 16: Technologies for Assessing the Condition of Water Mains · – DIPRA 10-Point (AWWA C105) ... tools match pipe size ... Technologies for Assessing the Condition of Water Mains](https://reader031.fdocuments.in/reader031/viewer/2022022509/5ad6da4e7f8b9a865b8b6a43/html5/thumbnails/16.jpg)
Asbestos Cement Pipe
Deterioration can occur from: • Soft Water Corrosion • Acidic Corrosion (low pH water) • Sulfate Corrosion • H2S Corrosion Failure Methods: • Bursts (longitudinal) • Breaks (circumferential)
![Page 17: Technologies for Assessing the Condition of Water Mains · – DIPRA 10-Point (AWWA C105) ... tools match pipe size ... Technologies for Assessing the Condition of Water Mains](https://reader031.fdocuments.in/reader031/viewer/2022022509/5ad6da4e7f8b9a865b8b6a43/html5/thumbnails/17.jpg)
AC Pipe: Acoustic Velocity Thickness
A comparison by Sweetwater Water Authority (CA) was promising
![Page 18: Technologies for Assessing the Condition of Water Mains · – DIPRA 10-Point (AWWA C105) ... tools match pipe size ... Technologies for Assessing the Condition of Water Mains](https://reader031.fdocuments.in/reader031/viewer/2022022509/5ad6da4e7f8b9a865b8b6a43/html5/thumbnails/18.jpg)
Technologies for Assessing the Condition of Water Mains NC AWWA Spring Conference 2014 Matt Shultz, PE - HDR