TECHNICAL SPECIFICATION AND REQUIREMENTS 

OF 

BIOMETRIC ACCESS CONTROL SYSTEM 

 

 

 

 

   

 

 

ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE

ISRO, Department of Space

August – 2017

Page 2: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 1 of 59

 

PART‐A  

1.0 Introduction  ISTRAC  invites  bids  from  interested  vendors  for  the  TURN‐KEY  work  for  supply, 

installation,  integration  and maintenance  of  Finger  print  based  biometric  Access 

Control System  (ACS) at  ISRO Telemetry Tracking and Command Network  (ISTRAC), 

BANGALORE.  There  are  six  locations  of  ISRO  Telemetry  Tracking  and  Command 

Network viz. SCC, MOX and IDSN, all at Bangalore, ISTRAC Lucknow Facility, Lucknow, 

and  ISTRAC  Port  Blair  Facility,  Port  Blair.  All  the  locations  are  connected  through 

ISTRAC LAN network.

Smart card (Mifare) based Access Control System  is operational at main gates (first 

level/peripheral) of ISTRAC SCC, MOX and IDSN for managing entry/exit of personnel 

as well as second level ACS is also operational for managing entry/exit of personnel 

at technical areas in ISTRAC main campus.

Present ACS consists of smart card fixed readers (fixed), Turnstile gates, EM locks for 

technical  areas,  server,  card  printer,  card  personalization  unit with  software,  ACS 

report software, management/monitoring software, UPS and network infrastructure.

This RFP  is  to  replace/augment  the  existing ACS with  Finger print  and  smart  card 

based  ACS  at main  gates  and  second  level  entry  at  ISTRAC  with  interoperability 

across  all  DOS/ISRO  Centres/Units.  The  proposed  Biometric  based  Access  Control 

system shall be  installed and commissioned seamlessly with the existing system by 

the Vendor.

 2.0 General Provisions 

 2.1 DEFINITIONS 

 2.1.1 Department:  Department  means  the  ISRO  Telemetry  Tracking  and  Command 

Network (ISTRAC), Department of Space of the Government of India. 

2.1.2 Contract/  Purchase  Order:  The  term  Contract/  Purchase  Order  shall  mean 

agreement  executed  between  the Department  and  Contractor,  together with  the 

document  as  referred  to  therein  including  the  functional  requirements, 

specifications, drawing and  instructions  issued within  the Contract provisions  from 

time  to  time  by  the  Contract Manager  and  all  those  documents  taken  shall  be 

complementary to one another. 

2.1.3 Vendor/  Contractor:  Vendor/  Contractor  means  any  individual,  Body  Corporate, 

Company, Undertaking, Establishment or Legal Entity entering  into a contract with 

the  Department  &  shall  include  all  heirs,  Legal  representatives,  successors  and 

permitted assigns. 

2.1.4 Contract Administrator/ Manager/ Department Representative/Key Personnel: The 

term shall mean the appropriate authority declared by the Department who shall co‐

ordinate the tasks in the execution of this contract. 

Page 3: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 2 of 59

2.1.5 Site Engineer: The  term Site Engineer  shall mean  the authorized  representative of 

the Contractor who shall co‐ordinate the execution of the contract. 

2.1.6 Site: The term Site shall mean the actual place of the proposed work or other places 

on  which  work  is  to  be  executed  under  the  Contract  which may  be  allotted  by 

Department for the purpose of carrying out the work.  

2.1.7 Works:  The  term Works  shall mean  the  places where work  is  performed  by  the 

Contractors. 

2.1.8 Bidder  shall  mean  any  individual,  Body,  Corporate,  Company,  Undertaking, 

Establishment or Legal Entity who quotes against the Proposal/ specification. 

2.1.9 Manufacturer refers to an  individual, Body, Corporate, Company or firm who  is the 

producer and  furnisher of material to either the  'Department or the Contractor' or 

both under the 'Contract' 

2.1.10 Specification/Proposal shall mean collectively all the terms & conditions contained 

in those portions of the 'Contract' known as 'General & special terms and conditions 

of  contract  for  supply,  installation,  testing  and  Commissioning',  the  specifications 

and  such Amendments,  revisions or  additions, as may be made  in  the Agreement 

and  all written  Agreements made  or  to  be made  pertaining  to  the method  and 

manner of performing the work or to the quantities and qualities of the materials to 

be furnished under the 'Contract'. 

2.1.11 Contract Price shall mean,  if  there  is a  formal agreement, the prices referred  to  in 

the agreement or if there is no formal agreement, the price agreed to be the value of 

the ‘Contract’ 

2.1.12 Date  of  Contract  shall  mean  the  calendar  date  on  which  the  Department  and 

Contractor  / Manufacturer have  signed  the  ‘Contract’.  ‘Effective Date of Contract’ 

shall mean the calendar date on which the Department has issued to the Contractor 

the  ‘Purchase Order’ or as otherwise mutually agreed  to between  the Department 

and Contractor. 

2.1.13 Contract Period shall mean the period during which the ‘Contract’ shall be executed 

as agreed between ‘Contractor/ Manufacturer and Department’. 

2.1.14 Guarantee period shall mean  the period during which  the  ‘System’ or  ‘Equipment’ 

shall give the same performance guaranteed by the Contractor/ Manufacturer in the 

'Schedule of Guarantee’ or as in the `Specification'. 

2.1.15 Performance Tests shall mean such tests as are prescribed in the specification to be 

done  by  the  Contractor  before  the  system  is  taken  over  under  guarantee  by  the 

Department. 

 

2.2     Glossary of terms relevant to this RFP 

 

ACS      Access Control System 

AMC      Annual Maintenance Contract 

A&M      Administration& Maintenance 

ATP      Acceptance Test Plan 

BOM      Bill Of Material 

EM      Electro Magnetic 

GA      General Administration 

Page 4: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 3 of 59

O&M      Operations & Maintenance 

OEM      Original Equipment Manufacturer 

OS      Operating System 

PFC      Potential Free Contract 

PCC      Police Clearance Certificate 

PDI      Pre Dispatch Inspection 

RTC      Real Time Clock 

VMS      Visitor Management System 

 

2.3 Executing authority of contract: Contract Manager 

The clauses and terms and conditions of the contract shall be executed on behalf of 

the Department only by or through the executing authority of contract who shall be 

named  in the contract as Contract Manager. The Contract Manager so named shall 

not be changed except  through a written communication  to  the Contractor by  the 

Department. 

The Contractor shall,  in  this respect, give  the contract manager of  the Department 

access  and  arrange  to  give  access  to  his  sub‐vendors/  sub‐contractors  to  his 

premises and shall give all necessary assistance  in order that the contract manager 

may fulfill his task. 

 

2.4 Communications 

All  communications  affecting  the  terms  and  conditions  of  the  contract  and 

concerning its execution shall be made or confirmed in writing. 

 

2.5 Publicity relating to contracts 

Advertisements, press  release or other  specialized publicity documents, which  are 

related to or reveal the existence of a contract and are  intended by the Contractor 

for public distribution and/or the press, broadcasting, or television, shall be notified 

to  the  Department.  The  Department may  direct  the  Contractor  to withhold  such 

publicity or  to  require modifications  to  the publicity material. The Contractor  shall 

comply with such direction. 

 

3.0 Brief Scope of Work 

a) The scope involves installation and integration of security components to include 

Access  Control,  Restricting  and  Monitoring  movement  of  personnel,  Vehicle 

Identification, authentication and Boom Barriers. The appropriate “system” shall 

allow  for  the  integration  of  the  aforementioned  components,  such  that  the 

management of all sub‐systems resides within a single data‐base application. The 

“system”  shall  have  the  ability  for  managing  every  subsystem  at  different 

locations by an appropriate `Administrator’ from a control room.  

b) Schematic diagram as shown  in Figure‐1 of the required system  is provided  for 

information.  Bidder  shall  propose  and  submit  suitable  solution  with  system 

configurations,  detailed  block  diagrams  and  necessary  techno‐commercial 

details. 

Page 5: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 4 of 59

c) The  scope  of  work  for  this  contract  shall  include  design,  supply,  installation, 

integration,  testing,  commissioning, maintenance  and  associated  services  for  a 

fully  operational  finger  print  &  smart  card  based  ACS,  that  provide  central 

security management, integrated control and remote monitoring of the intended 

site, including the interfacing of all existing facilities.  

d) All necessary tools, equipments, hardware, software and software user  licenses 

required as described  in this document for the complete  installation of the ACS 

shall be supplied and installed under this contract.  

e) All equipments supplied by the successful tenderer shall be installed, configured, 

programmed, tested and commissioned. The tenderer shall supply all materials 

and services necessary for or incidental to the installation and commissioning of 

the  systems.  Tenderer will  supply material  to  respective  locations  (SCC, MOX 

and  IDSN, all at Bangalore,  ISTRAC Lucknow Facility, Lucknow, and  ISTRAC Port 

Blair Facility, Port Blair) as per installation requirements. 

f) The entire ACS and subsystems  including all  its hardware, peripherals, software 

and  software  licenses  as  specified within  this  document  shall  be  supplied  and 

provided as part of this contract to the respective locations as per the quantities 

and locations mentioned in Annexure‐VI.  

g) Detailed Technical Specification of material  required  is given  in Part‐B and un‐

installation of existing items as per list given in Part‐C. 

 

Page 6: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 5 of 59

Figure – 1 – Biometric based ACS Architecture

Page 7: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 6 of 59

4.0 Eligibility Criteria for Bidding 

(a) The prospective bidder should have a minimum of Five years of experience  in 

the Security Management System business. 

(b) The bidder/firm should have a turn‐over of not less that Rs.100 lakhs during the 

last three financial years. 

(c) The bidder/firm should have earned profit during the last three years. 

(d) The  bidder/firm  should  have  sufficient  technical  expertise  and  logistics  to 

execute the project in different locations (including Port Blair) in India.  

(e) The  bidder/firm  should  have  prior  experience  in  executing  similar  projects 

(please provide documentary evidence for executing two such projects).  

(f) The  bidder/firm  should  have  supplied,  installed  and  commissioned  ACS  at 

private/public/government organization within the  last  five years. At  least one 

of those installations should have set‐up of Finger print Biometric based ACS for 

more  than 1000/ 500 users on daily access with physical barrier  like  turnstile. 

The  documentary  evidence(s)  like  Purchase  Order  copies,  acceptance  / 

completion  report and user  satisfaction  certificate(s) with user  contact details 

should be submitted along with the technical proposal. 

(g) A  ‘Bank  Solvency  Certificate’  issued  not  before  31 December  2016  for  Rs.50 

lakhs should be attached along with ‘Technical Bid’ failing which the tender will 

not be considered.

(h) The bidder should furnish a certificate, in original, from the Original Equipment 

Manufacturers  (OEM)  for  the  ACS  certifying  that  the  bidder  is  an  authorized 

dealer/agent  for  the  OEM  and  the  OEM  shall  be  responsible  for  after‐sales 

service, if the bidder is unable to give proper service.  

5.0 Instruction to Bidders  

5.1 Tender Document 

a) Interested prospective bidders are advised to go through the Tender documents 

carefully before participating in the bid. 

b) The  proposal  shall  be  completely  filled  in  all  respects  and  shall  be  tendered 

together with requisite  information and Annexure. Any offer  incomplete  in any 

particulars  is  liable  to be  rejected. Compliance  statement  should be  supported 

with objective evidence and shall be traceable. 

c) Bidders  shall  set  their  quotations  in  firm  figures  and without  qualifications  or 

variations  or  additions  in  the  terms  of  the  Proposal  documents.  Proposal 

containing qualifying expressions such as “subject  to minimum acceptance " or     

" subject to prior sale" or any other qualifying expressions or incorporating terms 

and  conditions  at  variance with  the  terms  and  conditions  incorporated  in  the 

Proposal documents are liable to be rejected.  

 

 

Page 8: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 7 of 59

 

5.2 Preparation of bids  

5.2.1 Site Visit 

Bidder  is advised  to visit and examine  the existing Access Control System  items at 

site, to  familiarise himself of the existing system and environment and shall collect 

all other  information  (including quantity of  accessories) which he may  require  for 

preparing  and  submitting  the  Bid  and  entering  into  the  contract.  Claims  and 

objections due to ignorance of existing conditions or inadequacy of information will 

not  be  considered  after  submission  of  the  Bid  and  during  implementation.  The 

bidder must do the site survey within ten days after release of tender during working 

days  (Monday to Friday excluding holidays), between 14:00 Hrs to 15:30 Hrs., with 

prior  appointment.  For  site  survey,  bidder  may  contact  Ms  Hemalatha  K  G 

([email protected]). 

Bid  shall  remain valid  for acceptance  for a period of 6  (six) months  from  the due 

date of submission of the Bid. The Bidder shall not be entitled during the said period 

to revoke or cancel his Bid or to vary the Bid except and to the extent required by 

Department  in writing. Bid shall be  revalidated  for extended period as  required by 

Department  in writing.  In  such  cases,  unless  otherwise  specified,  it  is  understood 

that validity  is sought and provided without varying either the quoted price or any 

other terms and conditions of Bid finalized till that time. 

5.2.2 Cost Of Bidding 

All direct and  indirect costs associated with  the preparation and submission of  the 

Bid (including clarification meetings and site visit, if any), shall be to Bidder's account 

and  the  Department  will  in  no  case  be  responsible  or  liable  for  those  costs, 

regardless of the conduct or outcome of the Bid process. 

 

5.2.3 Instructions for two part Bids 

 

Part‐ I: Should contain Technical and Commercial only 

Part‐ II: Should contain Price details only

Procedure to be followed by bidders 

 PART‐ I : TECHNICAL and  COMMERCIAL  a. Tender  document  contains  technical  requirements  and  specification  of  Finger 

print  based  Biometric  Access  Control  System.  The  detailed  technical 

specifications of tenderer’s offer should be covered in this part.  This part should 

not contain Price Details.  

b. The  commercial  terms  to be  covered  in  this part  like Delivery  Terms, Delivery 

period,  Payment  terms,  Validity  of  the  offer,  Warranty,  Guarantee,  security 

deposits, Performance Guarantee, Liquidated Damages (for delayed supply), etc.

c. The Bidder is required to confirm acceptance of all terms and conditions (clause 

wise). 

Page 9: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 8 of 59

 

PART‐ II : PRICE BID  

a. The price of the item should be indicated in this part with unit rate as specified in 

Annexure‐V.  The prices are to be mentioned both in figures as well as in words.  

b. Any  quotation  received  deviating  the  above  instruction  shall  be  liable  to  be 

rejected.   Hence please adhere  to  the above details and submit quotations before 

due date and time.   

5.2.4 Technical & Commercial Bid (Part‐I) 

The technical & commercial bid should comprise of following: 

a) Bidder’s Profile as per Annexure‐I.

b) A  Technical  compliance  statement  related  to  Technical  Specifications  as  per 

Annexure‐II. Deviations if any shall be brought out clearly. Bidder has to provide 

the  compliance  statements  for  each of  the  specification  for  equipments/items 

under Sl No 1.0 to 12.0 of Part‐B. 

c) Make  and model  no.  of  each  item  along with  technical  data  sheet/literature 

highlighting the compliance to specifications. 

d) Unpriced version  (price masked) of bill of materials with all other  commercial 

terms  and  conditions  indicating  payment  terms,  validity  etc  duly  filled,  as  per 

Annexure – IV. Deviations if any shall be brought out clearly.

e) Additional item, if any, required to realise this turn‐key work shall be included in 

bill of material in the offer as per Annexure – III along with technical details and 

justifications.

f) Audited balance  sheet  including profit and  loss account  for  last  three  financial 

years showing annual turnover.  

g) Latest solvency certificate from a scheduled bank.  

h) Documentation (Product Brochures, leaflets, manuals, etc.) 

i) List  of  projects  related  to  security management  system  in  hand &  completed 

during  last  3  financial  years  indicating  the  name  of  client,  contact  person, 

contract value, nature of work, work completed, work balance, month & year of 

commencement & completion etc. 

j) Organisation chart for the proposed work with bio data of key personnel 

k) Execution Plan. 

l) Delivery, Installation, Commissioning and Acceptance schedule. 

m) Any other relevant document, bidder desires to submit.

 5.2.6 Price Bid (Part‐II) 

The price quoted in Price Bid should be inclusive of following: 

a. Total  cost  of  the  ‘ACS’  inclusive  of  the  entire  scope  of  work,  supply, 

installation  and  commissioning  charges,  transportation  and  all  taxes  and 

duties. 

b. Cost of un‐installation (removal) of existing items  

c. Cost of training to be imparted. 

Page 10: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 9 of 59

d. Three  years  comprehensive  on‐  site  warranty  covering  the  entire  ACS 

encompassing all  software/hardware  items, all parts,  services, consumables 

and labour after acceptance by owner.

e. Post  warranty  Comprehensive  AMC  (CAMC)  charges  for  three  years 

covering, the entire ACS encompassing all software/hardware items, all parts, 

services, consumables and labour after acceptance by owner.. 

The schedule of prices shall be read in conjunction with all the sections of tender 

document. The price bid should not contradict the Technical bid in any manner. 

The price must be  filled  in  the  format  for  ‘Bill of Material and Price Schedule’ as per 

Annexure‐V. The unit rates quoted shall be firm and fixed. The total contract price shall 

be arrived at based on unit rates quoted and the quantity specified in the proposal. The 

unit rates quoted shall be valid for any variation in quantity up to ± 25 % of the total 

contract value. 

 

5.2.7 Bid Evaluation 

a) During evaluation, Department may  request Bidder  for any  clarification on  the 

bid,  additional  documents.  Bidder  shall  submit  all  additional  documents  in 

original.  

b) Techno‐commercial discussion  shall be arranged with Bidder,  if needed. Bidder 

shall  depute  his  authorized  representatives  for  attending  discussions.  The 

representatives  attending  the  discussions  shall  produce  authorization  from  his 

organisation to attend the discussion and sign minutes of meeting on behalf of 

his organisation  if  required. The authorised  representative must be  competent 

and empowered to settle/decide on all technical and commercial issues. 

c) The  complete  scope  of work  is  defined  in  the  Tender  document.  Only  those 

Bidders who  undertake  total  responsibility  for  the  complete  scope  of work  as 

defined in the Tender document shall be considered. 

d) In case Bid does not fully comply with the requirement of Tender document and 

the  bidder  stipulates  deviations  to  the  clauses  of  the  tender,  which  are 

unacceptable to the Department, the Bid will be rejected. 

e) Performance  of  Bidder  on  similar  nature  of works  executed/  under  execution 

shall be taken into consideration before selecting the Bidder for opening his price 

bid.  

f) Technically  complied  bidder  will  be  called  for  technical  presentation 

/demonstration.  During  presentation  following  technical  capabilities  of  bidder 

shall be evaluated: 

1. Experience for ACS installations / maintenance 

2. Reading and preparation of DOS/  ISRO  compatible  smart  card  (with 

Key‐A & B ) as per the requirement of the organisation. 

3. Demonstration  of  readers  for  the  inter‐operability  in  all modes  of 

inputs  

4. ACS Software with in‐house modification capability 

g) The  time  schedule  for  completion  is  given  in  the  Tender  document.  Bidder  is 

required to confirm the completion period unconditionally. 

Page 11: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 10 of 59

h) Only those Bids will be evaluated which are found to be fulfilling all the eligibility 

and  qualifying  requirements  of  the  tender  document  both  technically  and 

commercially.  

i) The bidders  shall  clearly mention  the make and model of  the  items quoted  in 

their bid documents. The detailed data sheets for the products/items offered by 

the bidders are required to be submitted by them along with compliance sheets 

to  ascertain  their  compliance  with  regard  to  the  product  specifications 

mentioned  in  the  tender  document.  The  bidders  must  attach  Authorization 

Letter from OEMs to support the offered hardware and software for the ACS.  

j) Price Bids of only those Bidders will be opened whose Technical Bids would clear 

the technical evaluation.  

k) The  bidders  shall  submit  their  commercial  bid  strictly  as  per  the  prescribed 

format.  The  Lowest  Bid will  be  decided  upon  the  lowest  price  quoted  by  the 

particular Bidder as per the Price Format. The Total Cost of all the items including 

applicable  GST,  Installation,  Commissioning  &  Testing,  Training, Warranty  for 

three years and Post warranty for next 3 years shall be the criteria for deciding 

the Lowest Bidder. 

l) The Bidders are required to offer Comprehensive Annual Maintenance Contract 

(CAMC)  for next  three years after  three years warranty periods.  Further,  they 

have to provide training to support staff and deploy resident technical engineer 

after commissioning of the system at Bangalore and Lucknow during warranty 

and CAMC periods.  

m) Department reserves the right to accept a bid other than a lowest and to accept 

or reject any bid  in full or part without assigning any reasons. Such decisions by 

the  Department  shall  bear  no  liability  whatsoever  consequent  upon  such 

decision.  

n) The Bidder, whose bid is accepted by the Department, shall be issued a Letter of 

Intent  (LOI)  to  proceed  with  the  work.  Bidder  shall  confirm  acceptance  by 

returning a signed copy of  the LOI. Thereafter Department may  issue purchase 

order or Department will sign the Contract with successful Bidder  

o) Department  shall  not  be  obliged  to  furnish  any  information  /  clarification  to 

unsuccessful bidder as regard to non‐acceptance of their Bids.  

 

5.2.8 Security Deposit a) The contractor whose  tender  is accepted will be  required  to  furnish by way of 

Security Deposit for the due fulfillment of the contract such a sum as will amount 

to 10 % of the contract price of the work awarded. 

b) The  security  deposit  (bearing  no  interest)  shall  be  held  by  the Department  as 

security  till  satisfactory completion,  testing and handing over of all  the  system 

and for the due performance of all contractor’s obligations under the contract as 

per delivery period or extension granted thereof by the Department. 

c) The  contractor, within  10 days of  Purchase Order or  signing of Contract,  shall 

deposit with the Sr Accounts officer/IFA, ISTRAC, Bangalore as detailed above by 

any one or more of the following modes namely 

Page 12: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 11 of 59

i. By a crossed demand draft  in favour of ISTRAC, Bangalore drawn on SBI and 

payable at Bangalore.

ii. By an acceptance bank guarantee as per format provided by the Department. 

The bank guarantee shall be from a Nationalised bank for & shall be valid for 

30 days beyond completion period. 

d) In case of breach of contract, the Security deposit shall stand forfeited in addition 

to other relief available to the Department under this contract. 

 

6.0 General Financial Provisions 

Prices quoted shall be for supply, transportation from place of manufacture to site, 

handling &  storage  at  site,  installation,  testing &  commissioning  including  all  risks 

coverage during  transit,  storage,  installation,  testing &  commissioning  including all 

taxes & duties as applicable except sales tax, works contract tax, service tax which 

shall  be  indicated  separately  in  price  bid. However  a  copy  of  the  Price  offer  duly 

masking the prices shall be enclosed to commercial terms offer also for information. 

All rates of Taxes /Duties /Levies applicable with details of percentages & applicable 

portion of the price should be spelt out clearly in the offer. Any variation in taxes & 

duties from the base date of offer during the contract period till the scheduled date 

of  delivery  shall  be  reimbursed  by  Department  subject  to  production  of 

documentary evidence by Contractor.  

If  new  Taxes &  duties  become  applicable  after  conclusion  of  contract  during  the 

contract period till the scheduled date of delivery, the same shall be reimbursed to 

the contractor on production of documentary proof. 

Bidders shall not  indicate any discount separately and quoted price should be after 

deducting the discount.  

6.1    Terms of Payments

  Payment will be divided in parts as follows:   

a) 60 % for Supply items against delivery of material. 

b) 40  %  payment  after  satisfactory  commissioning  in  all  respect,  acceptance  of 

operational system by Department and against submission of Performance bank 

guarantee of proportionate amount. 

c) The performance bank guarantee  (as per  format provided by  the Department) 

shall be from a Nationalised bank & shall be valid for a period of 38 months from 

the effective date of acceptance of the entire system by Department. 

d) Warranty  starts  from  the  acceptance  date &  performance  guarantee  valid  for 

entire ten years of service period from the accepted date. 

e) Warranty payment shall be made after completion of each quarter and bill duly 

certified by ISTRAC engineer and approved by Competent Authority.  

f) Post Warranty Comprehensive AMC payment shall be made after completion of 

each  quarter  and  bill  duly  certified  by  ISTRAC  engineer  and  approved  by 

Competent Authority.  

 

 

 

Page 13: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 12 of 59

6.2  Penalty during warranty and Post Warranty Comprehensive AMC 

Penalty deduction will be linked with up‐time of the system (in percentage) and shall 

be deducted from warranty charges/bank guarantee as below: 

i. If up‐time below 90 %, there will not be any payment to contractor 

ii. If up‐time between 91 to 95%, Penalty @ 10%  

iii. If up‐time above 95 %, no penalty ‐ full payment 

 

7.0  Time Frame for completion  

The  entire  ACS  system  is  required  to  be  completed  by  the  successful  bidder  in 

maximum of  six months  from  the date of LOI or Purchase Order whichever  issued 

earlier.  The  bidder will  ensure  the  schedule  for  implementation  of  entire  ACS  as 

below at all locations. ( Bangalore, Lucknow and Port Blair ) 

 

LOI or PO released   T0 

Delivery of all material  T0 + 60 days

Acceptance of the system  T0 + 180 days 

 

8.0 Guarantees 

The  ACS  including  all  components  delivered  to  the  Department  should  be  brand 

new.  The  Contractor  should  also  guarantee  that  all  the  software  /  components 

supplied by the Contractor is licensed and legally obtained.  

9.0 Availability of Spares 

Spares for the product offered should be available for at least 10 years.  

10.0 Warranty 

a) Contractor must include comprehensive on‐site warranty for THREE YEARS from 

the  effective  date  of  acceptance  of  the  entire  system  by Department.  During 

warranty, Contractor shall maintain ACS system with minimum 95 % up‐time. 

b) Contractor shall be  fully responsible  for the manufacturer’s warranty  in respect 

of proper design, quality and workmanship of all equipments, accessories, etc., 

covered by  the offer. The Contractor must warrant all equipment, accessories, 

spare parts etc., against any manufacturing defects during the warranty period. 

During  the warranty  period  the  Contractor  shall maintain  the  equipment  and 

repair / replace all the defective components at the installed site at no additional 

charge of whatsoever nature to the Department.

c) The Contractor should ensure that the defects in the ACS system reported on any 

working day  is set right within two hours on the same day and  in no case more 

than four hours on the same day.  In case, the system or any equipment cannot 

be  repaired  within  the  stipulated  period,  the  Contractor  should  provide  a 

replacement till the system/equipment is returned duly repaired.

d) Emergency  services  shall  be  provided  by  vendor  during  off‐office  hours  and 

holidays, whenever  required at a very short notice, without any extra payment. 

Page 14: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 13 of 59

During off‐office hours, site engineer will attend the fault within three hours and 

resolve the fault within three hours on same day. 

e) If  required,  additional  qualified  engineer  and  senior  engineers  should  be 

deployed. 

f) Warranty  shall  include  preventive  &  unlimited  break‐down maintenance  calls 

including repair/replacement of material, spares, modules, software, etc. 

g) In the event of the contractor’s failure to supply & provide allied services within a 

reasonable  period,  the  Department  on  its  own  will  get  the  defects  rectified 

through another agency at  the  risk and cost  to contractor and  repairs  rectified 

through another agency in such circumstance will not affect the liabilities of the 

contractor  on  the  warranty  for  its  remaining  period  nor  will  it  affect  the 

contractor's  liabilities  on  the  stipulated  post‐warranty  Annual  Maintenance 

Contracts. 

h) Contractor  shall  supply  replacement  of  spare/item  of  same make  and model 

against  faulty  component  during  warranty.  In  case  the  manufacturer 

discontinues any model, Contractor shall supply spare/item with higher model of 

supplied make with better specifications at no extra cost and ensure that it gets 

integrated within the system.

i) All the mechanical parts of the system like readers, turnstiles, EM locks, printers, 

exit  switches  shall  be  maintained  periodically  by  cleaning,  lubricating  and 

alignment. Wear  out mechanical  parts  shall  be  replaced  at  periodical  interval. 

Disk Retention Clause ‐ HDD & Flash Memory would not be allowed to take it to 

Vendor/Contractor premises 

j) Contractor  shall  carry out  alignment of doors  at buildings  and  laboratories  for 

proper functioning of EM locks as and when required. 

k) During warranty period, the contractor will be required to carry out maintenance 

and  repairs  including  replacement of  spares/equipment without any additional 

cost.  

l) During Warranty  period  of  three  years,  the  contractor shall deploy two  trained 

Resident Technical Engineers  (one at  ISTRAC SCC, Bangalore and one at  ISTRAC 

Lucknow  Facility)  at  site  for  the  operation  and  maintenance of ACS.  These 

engineers  deployed  at  ISTRAC  SCC,  Bangalore will  also  be  responsible  for  the 

maintenance  of  ACS  at  MOX,  Bangalore  and  IDSN,  Bangalore  campuses. 

They shall be available on all working days of department during office hours (30 

minutes before and after the office hours).   The system maintenance at  ISTRAC 

Port  Blair  Facility  shall  be  on  call‐basis  during  breakdown.  However  they  can 

perform  system  administration  and maintenance  pertaining  to  Port  Blair  from 

Bangalore, when ever possible. 

m) Deployed resident technical engineer shall perform: 

i. Preventive and break down maintenance of the system. 

ii. Management of the spare parts, materials and consumables. 

iii. Periodical database back‐up and preparation of weekly, monthly and quarterly 

report on system performance in prescribed format. 

iv. Any  other  technical  work  like  Network  Trouble  Shooting  etc.  assigned  by 

Department from time to time 

Page 15: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 14 of 59

n) The  deputed  Resident  Technical  Engineer  should  be  on  the  payroll  (bona‐fide 

employees)  of  Contractor  and  due  Police  Clearance  Certificate  (PCC) must  be 

obtained before deputing in ISTRAC campuses. ISTRAC reserves right to disqualify 

any  Resident  Technical  Engineer  deputed,  for  reasons  like  technical 

incompetence,  indiscipline,  irregularity,  insincerity,  disobedience,  doubtful 

credentials/ integrity, etc.

o) The  resident  engineer  cannot  take  any  data  outside  ISTRAC  and  cannot  use  it 

without  unless  asked  by  ISTRAC  Administration.  They  cannot  use  ISTRAC 

infrastructure for their personal use in any case.  

11.0 Comprehensive Annual Maintenance Contract 

a) The  Contractor  is  expected  to  maintain  the  ACS  including  all 

accessories/components  and  software  supplied  for  three  years  (4th  year  to  6th 

year) after the expiry of warranty period (Three years). 

b) Comprehensive  on‐site  annual  maintenance  charges,  for  the  post  warranty 

period, must be quoted per year in the Price bid. 

c) During  the  comprehensive  AMC  period,  the 

contractor shall deploy trained Resident  Technical  Engineers  at  sites  (one  at 

ISTRAC SCC, Bangalore and one at ISTRAC Lucknow Facility) for the operation and 

maintenance of ACS. 

d) The  Contractor  shall maintain  the  equipment  and  repair/replace  all  defective 

components, major or minor and spares or consumables at no additional charge 

other than the AMC contract charges.

e) The AMC charges will be released  in four  installments at the end of every three 

months  period  from  the  date  of  the  expiry  of  warranty,  on  satisfactory 

performance of the ACS and against submission of a service report. 

f) During AMC period, Deployed resident technical engineer shall perform: 

i. Preventive and break down maintenance of the system. 

ii. Management of the spare parts, materials and consumables. 

iii. Periodical  database  back‐up  and  preparation  of  weekly,  monthly  and 

quarterly report on system performance in prescribed format. 

iv. Any other technical work like Network Trouble Shooting etc. assigned by 

Department from time to time. 

v. The maintenance of Port Blair system can be taken care in remote mode, 

whenever possible. However bidder has to take the responsibility of the 

functioning of the system by sending the company person to Port Blair, in 

case of  requirement and  resolve  the  issue, as  the  systems are  covered 

under CAMC. 

g) The  deputed  Resident  Technical  Engineer  should  be  technically  qualified 

personnel with  sufficient experience  in maintenance of BACS and  should be on 

the  payroll  (bona‐fide  employees)  of  Contractor  and  due  Police  Clearance 

Certificate (PCC) must be obtained before deputing in ISTRAC.

h) ISTRAC reserves right to disqualify any Resident Technical Engineer deputed,  for 

reasons  like  technical  incompetence,  indiscipline,  irregularity,  insincerity, 

disobedience, doubtful credentials/ integrity, etc.

Page 16: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 15 of 59

i) The resident engineer cannot take any data outside ISTRAC and cannot be use  it 

without  unless  asked  by  ISTRAC  Administration.  They  cannot  use  ISTRAC 

infrastructure for their personal use in any case.  

13.0 Force Majeure 

Should a part or whole work covered under this contract be delayed due to reasons 

of Force Majeure which  shall  include  legal  lockouts,  strikes,  riots, civil commotion, 

fire accident, quarantines, epidemic, acts of God and Government, fright embargoes, 

the completion period  for work, plant or equipment referred to  in this contract be 

extended  by  a  period  not  in  excess  of  the  duration  of  such  Force Majeure.  The 

occurrence shall be notified by either party within reasonable time. 

 

14.0 Delay in Completion/ Liquidated Damages 

In the event of the Contractor failing to complete the work within the time specified 

in  the  contract  agreement  or  in  extension  agreed  thereto,  the  Department  shall 

reserve the right to recover from the Contractor as liquidated damages, a sum of one 

half percent (0.5%) per week or part thereof of the undelivered portion of the total 

contract price of plant, equipment or work. The Total  liquidated damages shall not 

exceed the ten percent (10.0%) of the total Contract price. 

15.0 Arbitration 

If at any time any question, disputes or differences whatsoever shall arise between 

the purchaser and  the  contractor upon or  in  connection with  this  contract, either 

party may  forthwith  due  to  the  other  notices  in writing  of  the  existence  of  such 

question, dispute or difference and the same shall be referred to the adjudication of 

two arbitrator or one to be nominated by purchaser, other by contractor. The award 

of the arbitrator shall be binding on the parties to the dispute. However, any party 

aggrieved by such award may make a further reference for setting aside or revision 

of the award to the Law Secretary, Department of  legal affairs, Ministry of Law and 

Justice, Government of  India. Upon such reference the dispute shall be decided by 

the Law Secretary or the special Secretary/Additional Secretary when so authorized 

by  the  law  secretary, whose  decision  shall  be  binding  on  the  parties  finally  and 

conclusively. The parties to the dispute will share equally the cost of arbitration as 

intimated by the arbitrator. In the event of either party ceases to be an undertaking 

of Government of  India, arbitration & conciliation act 1996 shall be applicable. The 

venue of arbitration should be the same place where centre is located.

 

16.0 Disclosure and use of information by the Contractor 

Contractor shall guarantee that all information and data received during execution of 

Contract  from Department shall be classified as confidential within  the meaning of 

the Official  Secrets  Act  and will  not  be  divulged  to  any  third  party without  prior 

written permission of Department. All drawings & documents shall be returned after 

execution of work.  

17.0 Fall Clause 

Page 17: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 16 of 59

The prices charged by the bidder for the similar items/sub‐systems shall in no event 

exceed the  lowest prices offered to other organisation parties during the validity of 

the  contract.  If, at any  time during  said period,  the bidder/contractor  reduces  the 

prices  for  the  items/sub‐systems,  the  contractor  shall  forthwith  notify  such 

reduction of prices applicable to the Department and the prices payable under this 

contract for the services shall stand correspondingly reduced. 

18.0 Infringement of third‐party rights 

a) Unless otherwise  stipulated  in  the contract,  the Contractor  shall  indemnify  the 

Department  from  and  against  all  claims,  proceeding,  damages,  costs  and 

expenses arising from or for the infringement of Third party Intellectual Property 

rights  in  respect  of  patent  rights,  copy  rights  or  other  protected  rights  with 

respect  to  the  subject  of  the  contractor  excluding  any  infringement  resulting 

from the use of designs, plans, diagram, documents, patterns drawings or goods 

supplied  by  the  Department  which  may  be  made  or  brought  against  the 

Department,  or  to  which  the  Department  may  be  put  by  reasons  of  such 

infringement or alleged infringement. 

b) The Department shall notify the Contractor  immediately of the written claim or 

notice  of  infringement  of  third‐party  rights,  which  it  receives  concerning  the 

contract. The Contractor  shall  immediately  take  all necessary  steps  at his own 

expense within his competence to prevent or end a dispute and shall assist the 

Department  to defend against, or make  settlement  in  respect of, any  claim or 

notice  of  infringement  or  suit  for  infringement. Written  claims  or  notices  of 

infringements of  third‐party  rights will be accepted or met by  the Department 

only in agreement with the Contractor. 

c) In  the event of any designs, drawings, plans or diagrams or any manufacturing 

methods or processes  furnished by  the Contractor constituting  infringement of 

Third  Party  Intellectual  Property  Rights  in  respect  of  patent  or  any  other 

protected  rights and use  thereof  is  restrained,  the Contractor  shall procure  for 

the Department, at no cost to the latter, the rights to continue using the same or 

to the extent it is possible to replace the same so as to avoid such infringement 

and subject to approval by the Department or modify them so that they become 

non‐infringing but such modifications shall otherwise be to the entire satisfaction 

of the Department.  

d) The  parties  shall  notify  each  other  of  any  known  intellectual  property  rights 

connected  with  the  use  of  designs,  plans,  diagrams  documents,  patterns, 

drawings and goods supplied by the one party to the other connected with the 

execution of the specification laid down by the other party. 

e) The  provision  of  this  clause  shall  remain  effective  and  binding  upon  the 

Contractor even after the completion, expiration or termination of the contract.  

 

19.0 Non‐Disclosure Agreement (NDA) 

Personnel  deputed  by  contractor  during warranty  period  and AMC  shall maintain 

absolute secrecy and security of the ACS data stored on various computing systems 

at ISTRAC. The data / information provided by ISTRAC from time to time, are for the 

Page 18: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 17 of 59

execution  of  this  work  only;  and  should  not  be  used  /  copied  /  reproduced  / 

published  in any  form or disclosed to third party, by contractor or their personnel. 

Thus, contractor is required to sign a Non‐Disclosure Agreement (NDA) with ISTRAC. 

Contractor will also be responsible for any violation or infringement of NDA by their 

personnel. 

20.0 Termination of Contract  

Under normal circumstances, termination of the contract  is not foreseen. However, 

the Department shall have the right to terminate this Contract in part or in full in any 

of the following clause:‐ 

(a)  The  delivery  of  the  material  is  delayed  for  causes  not  attributable  to  Force 

Majeure for more than two months after the scheduled date of delivery. 

(b)  The Contractor fails to comply with any of the provisions in the contract. 

(c)  The  Contractor  is  declared  bankrupt  or  becomes  insolvent. 

Page 19: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 18 of 59

 

PART‐B 

Technical Specification

1.0  ACS System features 

1.1  Finger print based biometric with smart card (Mifare) based ACS for IN & OUT at Main 

gate  entry  (through  Turnstile)  of  ISTRAC  for  employees  and  non‐employees  like 

research  fellows,  retired  employees,  contract  manpower,  apprentices  &  trainees, 

visitors  etc.  PIN Authentication  to  be  part  of  the  system  in  the  smart  card 

authentication logic & associated hardware & software elements.

1.2  Finger  print  based  biometric with  smart  card  (Mifare)  based  ACS  for  IN  &  OUT  at 

second level access control (using EM Lock) for employees and non‐employees.   

1.3  Redundant servers with mirrored database with a provision for daily back up.

1.4  Biometric with  smart  card  readers with  PoE  Ethernet  connectivity  and with  suitable 

enclosure to work in the outdoor environment. 

1.5  Handheld wireless Biometric with Smartcard  readers with Wi‐Fi connectivity  for data 

transfers  to  server  in  Real‐Time  for  senior  officials  entering  through  vehicles  and 

additional  Ethernet  interface.  Readers  on  pole  at  ISTRAC  main  campus  and  other 

locations for other vehicles. 

1.6  Photo  display  system  at  Main  gates  for  employees  and  non‐employees  entering 

through turnstile. 

1.7  RFID based Vehicle Access Control System  integrated with Boom barrier for  identified 

vehicle and associated report generation. 

1.8  During  network  failure  at  any  of  remote  location  from  ISTRAC main  campus  local 

transaction  data  storage  shall  be  available  at  respective  locations.  In  this  condition, 

forwarding  of  remote  location  data  through  alternate  route  (without  human 

interactions) and or manually shall be planned out. Once network is available, remote 

location  data  shall  be  updated  to  mirrored  servers  at  ISTRAC  main  campus 

automatically.   Vendor shall specify  required hardware and or software  in BOM with 

required quantity and specifications. 

 

1.9  Readers & other accessories should not generate unnecessary traffic in the network

 

2.0  System Requirements 

 

2.1  Smart  card  and  finger  print  verification  in  1:1 mode  for Main  gate  entry/exit  for  all 

employees and for non‐employees like contract personnel, apprentices & trainees, CISF 

personnel, etc. 

Finger print verification in 1:1 mode for visitors, construction labourers, etc.  

Validation of smart card of employees and non‐employees shall be carried out on  the 

basis of biometric template stored  in smart card  in  ISO  format. Whereas, validation of 

smart card of employees from other Centre/Unit of DOS/ISRO shall be carried out on the 

basis of biometric template stored in smart card in ISO format. 

2.2  Smart  card  and  finger  print  verification  in  1:1  mode  for  second  level  at  critical 

laboratories/buildings in the campus for authorized personnel. 

Page 20: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 19 of 59

2.3  Two templates of  left & right hand  index fingers to be enrolled for each person and to 

be  stored  in 4K  smart  card  (Mifare)  for  verification  in  ISO    formats  as per  the  sector 

details to be provided by DOS/ISRO during implementation 

2.4  ACS  equipments  like  readers,  servers,  PCs,  LED monitor  displays,  network  switches, 

Access points, etc. shall be connected  through  ISTRAC LAN and system should update 

the transaction data to the ACS Servers in real time over network. 

2.5  ACS system should have web based work flow software to update details of shift duty, 

tour and leave. 

2.6  System  shall  handle  denial  of  entries  to  black  listed  cards  of  all  Centres/Units  of 

DOS/ISRO.  List  of  black  listed  cards  at  each  Centre/Unit  shall  be  available  from 

Centralized  Server  (Centralized  Server will  be  located  in  any  of  the  Centre/Unit  of 

DOS/ISRO and hence, realisation of Centralized Server is not a part of this tender). 

2.7  The ACS hardware and software shall be scalable for the future expansion requirements 

in terms of additions of turnstiles and EM locks. 

2.8  ACS database should have direct access to the transaction data stored for the  last five 

years, at any instance. 

2.9  Vehicle Authentication through long range RFID reader with Boom Barrier as actuator in 

closed loop system. 

2.10  All  outdoor  installations  are  to  be  IP‐54  Compliant.  All  Electrical  Equipment  shall  be 

CE/UL Compliant. 

2.11  The Installation and Commissioning process shall be of seamless migration from existing 

system to new system.  

3.0  Specifications for ACS Equipments 

3.1  Biometric and smart card readers with built‐in controller (IN and OUT)

3.1.1  Biometric type  Finger print

3.1.2  Sensor Type Optical (Minimum 500 dpi)

3.1.3  Finger print sensor Make  Sagem/ Suprema/ Secugen

3.1.4  CPU  32 bit

3.1.5  Enrollment size  512 bytes for ISO 19794 format for each finger template.

3.1.6  Operation mode  Shall support (Finger +  Smart card),  (Finger +  Smart card  

+ PIN), (Finger + PIN), (Smart Card + PIN), Finger only, Smart 

Card only for single/multiple user/s. 

3.1.7  Keypad  Keypad for PIN entry and local operations with Numeric 

and functional keypad. 

3.1.8  Storage capacity  Minimum 10,000 finger print template storage capacity 

3.1.9  Transaction capacity  Minimum 50,000 events

3.1.10  Verification time  Less than one second for 1:1 biometric verification

3.1.11  Actuators  To handle Turnstile & EM lock

3.1.12  Smart card reading 

capability 

Mifare  13.56 MHz  with  sector  reading  (32  bit  format  in 

accordance  with  ISO  14443  series  with    dual  key 

authentication ( Both Key A and B of Mifare architecture) 

3.1.13  Sensor sensing conditions Should  be capable  for  reading  finger  in  mild  dry,  wet, 

mehandi and oily conditions 

3.1.14  Smart card read range  1 to 3 cm and to accommodate +/‐ 30 deg elevation error 

Page 21: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 20 of 59

during presentation by the user.

3.1.15  Interfaces  POE  enabled Ethernet port, RS232, RS485, Weigand 

3.1.16  Input / Output  Two input and Two output 

3.1.17  LCD display with backlit  To show day, date & time by default. To display the details 

of valid / invalid entry with Name and Employee’s ID at the 

time  (24  Hrs.  Format)  of  card  flashing.16  Character  or 

better display is preferable.  

3.1.18  LED indication  To  show  power  on,  valid  entry,  invalid  entry,  Network 

availability or any error. 

3.1.19  Audible alarm  For valid entry,  invalid entry and any error. Alarm shall be 

audible in outdoor conditions. 

3.1.20  Real Time Clock (RTC)   RTC  with  battery  backup.  Reader  RTC  time  shall  be 

synchronized with server time. 

3.1.21  Data & time retention  In case of power failure, the data retention to be provided 

using  flash memory  and  the  Real  Time  Clock  of  the  unit 

should be retained with current date and time. 

3.1.22  Local & remote admin  The  reader  shall  support  local  and  remote  administration 

and  maintenance  through  network.  The  reader  to  be 

invoked remotely when the reader goes to sleep time. 

3.1.23  Anti‐pass back  The reader shall have facility for global and  local Anti‐pass 

back. 

3.1.24  Protection of transaction 

data 

In  case  memory  is  full,  the  reader  shall  disable  further 

transactions  to  protect  over‐writing  of  transactions  data. 

Message shall be displayed on reader and admin alert shall 

be sent to administrator. 

3.1.25  Event/ Alarm logger  Event  logging  in  the  onboard  memory  for  the  alarm 

observed at each location along with time shall be archived 

and  retrieved.  To  raise  alarm or  any  log  in  the  system  to 

alert  the  administrator  in  case  of  any  tampering  of  the 

reader. 

3.1.26  Safety certification  The device shall be UL/CE certified 

3.1.27  Operating conditions  Shall  be  weather  proof  (Polycarbonate  enclosure)  and 

capable  for  operation  in  outdoor  condition  under  canopy 

without interference from day light illumination considering 

all the seasons .(IP54 or better) 

3.1.28  Power requirement  230 V AC ± 10 %, 49‐51Hz, PoE  adapter to be supplied.

3.1.29  Environmental  Shall operate at  0o to 50o C, RH 10% to 90% 

 

3.2  Handheld readers – Biometric and smart card with built‐in controller

3.2.1  Biometric type  Finger print

3.2.2  Sensor Type Optical (  Minimum 500 dpi)

3.2.3  Finger print sensor Make  Sagem/ Suprema/ Secugen

3.2.4  CPU  32 bit

3.2.5  Enrolment size  512 bytes for ISO 19794 format for each finger template.

3.2.6  Operation mode  Shall  support  (Finger    +    Smart  card),    Finger only,  Smart 

Page 22: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 21 of 59

Card only for single / multiple user/s. 

3.2.7  Storage capacity  Minimum 2,000 finger print template storage capacity 

3.2.8  Transaction capacity  Minimum 5,000 events 

3.2.9  Verification time  Less than one second for 1:1 biometric verification

3.2.10  Smart card reading 

capability 

Mifare  13.56 MHz  with  sector  reading  (32  bit  format  in 

accordance with  ISO  14443  series with    dual  key  A  &  B 

authentication) 

3.2.11  Smart card read range  1  to  3 cm  minimum  and  to  accommodate  +/‐ 30  deg 

elevation error during presentation by the user. 

3.2.12  Interfaces  PoE enabled Ethernet, RS232, RS485, Weigand 

Wi‐Fi  (15 meters range) with WEP, WPA/WPA2 encryption 

and Ethernet. 

3.2.13  LCD display with backlit  To show day, date & time by default. To display the details 

of valid /  invalid entry with name/employee ID at the time 

of card flashing.16 Character or better display is preferable. 

3.2.14  LED indication  To show power on, valid entry, invalid entry or any error.

3.2.15  Audible alarm  For valid entry,  invalid entry and any error. Alarm shall be 

audible in outdoor conditions. 

3.2.16  Real Time Clock (RTC)   RTC  with  battery  backup.  Reader  RTC  time  shall  be 

synchronized with server time. 

3.2.17  Data retention  Data retention to be provided using flash memory.

3.2.18  Configuration   Configurable for IN/OUT using toggle switch 

3.2.19  Weight  Less than 500 grams with battery 

3.2.20  Battery backup  Rechargeable  battery  to  withstand  12  hrs.  of  operations 

with  indication  for  available  battery  capacity.  Battery 

charger  shall  be  like  that  of  cordless  telephone  charging 

type and not of mobile phone type. 

3.2.21  Power save  Provision to go to power save mode  if not  in operation for 

more than 30 seconds  

3.2.22  Protection of transaction 

data 

In  case  memory  is  full,  the  reader  shall  disable  further 

transactions  to  protect  the  earlier  transactions  data. 

Message  shall  be  displayed  on  reader  and  alert  shall  be 

sent to administrator. 

3.2.23  Safety certification  The device shall be UL/CE certified 

3.2.24  Operating conditions  Shall  be  weather  proof  (Polycarbonate  enclosure)  and 

without interference from day light illumination considering 

all the seasons.(IP54 or better)  

3.2.25  Case for carrying and 

protection 

Leather pouch 

3.2.26  Battery charger  Compatible battery charger for 230 VAC±10%,49‐51Hz

3.2.27  Environmental  Shall operate at 0o to 50o C, RH 10% to 90% 

3.2.28  Sensor sensing conditions Should  be  capable  for  reading  finger  in  mild  dry,  wet, 

mehandi and oily conditions 

3.2.29  Power requirement  230 V AC ± 10 %, 49‐51Hz, PoE adapter to be supplied.

Page 23: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 22 of 59

3.2.30  Event/ Alarm logger  Event  logging  in  the  onboard  memory  for  the  alarm 

observed at each location along with time shall be archived 

and retrieved. 

 

3.3 Dual Lane Full height turnstile

3.3.1 Working environment Outdoor environment

3.3.2 Turnstile Type Dual lane Full Height Turnstile with 3 x 120 degree U bar

3.3.3 Dimensions 2200 mm(length) x 2235 mm(height) x 1315 mm (width/depth) Minimum walkway to be 450mm

3.3.4 Minimum height of Turnstile

2150 mm (Approximately 7 feet )

3.3.5 Locking Type Electromechanical

3.3.6 Material of Construction

Stainless Steel SS304

3.3.7 Turnstile Operation Freely open, direction of passage, emergency, wrong direction, counting impulse and card-reader locking. Shock absorber to be designed with damping mechanism for smooth rotation & positioning

3.3.8 U bar construction a) Spacing between U bar shall not exceed 160 mm.

b) Height of U bar shall be less than 110 mm

c) The clearance between U bar and static barrier shall be at-least 25 mm

d) The U bar should be directly welded to the centre pole and the above dimensional criteria shall be maintained throughout its length.

e) The barrier shall not expose vertically any area more than 200 mm.

3.3.9 Intelligence Limit Switch shall be used with Turnstile Controller.

3.3.10 Operating Voltage DC 24 volts

3.3.11 Max. power consumption

Less than 100 Watts

Page 24: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 23 of 59

3.3.12 Controller Type 32 bit Microcontroller or Microprocessor based Logical control

3.3.13 Solenoid Control Semiconductor switched two outputs for use with standard turnstile solenoid.

3.3.14 Digital Inputs Minimum 3 to control IN and OUT movements and for emergency exit

3.3.15 Relay outputs At least 5 for use with alarm, gate usage and pulse counting.

3.3.16 Watchdog Timer The controller shall be equipped with watchdog timer such that its failure shall result in an alarm trigger.

3.3.17 Field customization The controller shall provide 1, 2, 3 delay timings

3.3.18 Data Interface RS232

3.3.19 Operating Temperature

00 to 500 C

3.3.20 Certification The turnstile controller should be UL or CE certified. Proof of certification is to be enclosed.

3.3.21 Material Anodized aluminum casing & Anti-tamper jam nuts

3.3.22 Annunciation RED/GREEN LED indication

3.3.23 Emergency Exit switch Exit switch with glass enclosure with mechanism to open the doors from inside in case of emergency situations and reader failure.

3.3.24 Fail Safe Mode In case of power failure/emergency, arm dropping function providing free and unobstructed safe passage to users without manual intervention. Implementation strategy shall be such that this feature shall not be misused by the intruder.

3.3.25 Duty Cycle 100 %

3.3.26 Throughput 40 persons per minute, excluding validation time.

3.3.27 Operation Microprocessor / Microcontroller / Controlled. All functions should be configured on site. Manual Bi directional rotation

 

 

Page 25: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 24 of 59

3.4  Boom Barrier with RFID Tags for Vehicle Access Control System 

  The  boom  barrier  is  a  physical  barrier  used  for  controlling  vehicle  passage  into  the 

campus. This will be integrated with RFID tags (UHF Range) and long range UHF reader 

to automatically control vehicle movement  for  registered vehicles having affixed RFID 

tags  (UHF  Range).  The  readers  shall  be  installed  to  perform  the  operations without 

collision. 

This solution will have the following components: 

a) Boom Barrier with motorized control 

b) RFID long range reader with suitable arrangement for installation 

c) RFID tags d) Associated software for enrolment, management and reporting 

 

3.4.1  Boom Barrier Specifications (4.5 meter)

a  Duty Cycle  100%

b.  Mechanism Electrically operate

c.  Closing Time 

(after vehicle passage) 

1‐6 Sec (adjustable)

d.  Cycles per hour  100

e.  Cycles per day  2000

f.  Arm Dimension and 

Construction 

Length  4.5  meters.  Aluminium  Boom  bar  to  be  used. 

Complete  length of the arm shall be pasted with reflective 

Red and White Strips for day & night visibility 

g.  Power Supply  Single phase motor operated 230 VAC±10%, 49‐51Hz

h.  Operating Options  RFID based activation, Remote Control and Push Button     ( 

Manual ) 

i.  Operation during power 

failure 

Open/Close option with mechanical handle 

j.  Control Panel  To provide a compact console for operating the boom 

barrier conveniently 

k.  Shock Resistance  High Level and extremely sturdy

l.  Finishing Treatment  Zinc Coating (inside out), stainless steel cover & anti‐

corrosion treatment  

m.  Water Proof and 

protection 

The device should be splash proof. (IP‐54) 

n.  Operating Temperature  00 to 500 C 

o.  Safety Features  Bright LED lights mounted around the arm on both sides 

and shall be visible even in bright daylight. 

   

3.4.2  Long Range RFID Readers for Vehicles

a. 

The  long range RFID reader shall be used for vehicle access through Boom Barrier. The 

read range for this reader should be up to 8 mtrs. The reader should support Gen2 tags. 

The reader should be with inbuilt controller and antenna. 

b.  Frequency Range  865 to 928 MHz (UHF)

c.  Read Range Up to 8 mtrs

Page 26: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 25 of 59

d.  Antenna  Inbuilt antenna and controller

e.  Communication  Wiegand, RS232, RS422

f.  Network Interface  Ethernet

g. Annunciation  LED to indicate RFID transaction and audible alarm for 

error reporting 

h.  External input  Four

i.  External Output  Four

j.  Certification The device shall be UL/CE certified 

k.  Power Supply  230 V AC ± 10 %, 49‐51Hz

l. Packing  Weather Proof integrated antenna enclosure 

 

 

3.4.3 

 

RF ID TAGS ( For Vehicles) 

  RFID Tags: These  tags shall conform  to EPC Gen2  tags operating  in UHF  frequency  for 

long  read  range. The  tags should be  tamper  resistant after  it  is affixed  to  the vehicle. 

Generally  it shall be fixed on the front portion of the vehicle to  interact with reader at 

long range. 

  RFID Tag Specification 

   

a) Passive  Gen  2  tags  shall  be  used  for  vehicle 

access.  

b) The operating frequency shall be compatible with 

the RFID Reader’s operating frequency.  

c) It should be capable of read range up to 8 mtr. 

d) Form Factor : Button Shaped 

e) Installable  on  :  Vehicle  Windshield  Glass  /  on 

front portion of the vehicle 

f) The tag shall have unique number. 

3.4.4  Vehicle Access Software

  Associated software for enrolment, management and reporting of Vehicles. The 

software shall be integrated with main ACS software for all activities. 

  Enrolment  a) RFID  tag  reader  with  associated  software  for 

enrolment  

b) Each enrolment data  shall  contain RFID Tag number, 

Vehicle  Registration  Number,  Date  of  enrolment, 

Validity date and remarks 

  Management  a) It  should  be  possible  to  enable/disable  a  particular 

vehicle. 

b) Authentication  of  the  vehicle  and  events  shall  be 

transferred to server in real time. 

c) In case of denial, alarm should be  raised  to alert  the 

security. 

  Reporting  a) Daily and between dates (date+time) entry/exit report

b) Report based on vehicle number 

c) Vehicle denial report. 

d) Report of RFID tag inventory 

e)  

Page 27: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 26 of 59

3.5  Photo Display at Main Gates during entry

  This  system  will  facilitate  display  of  Photo  of  employees,  non‐employee  and  visitor 

during  their  entry  into  the  main  gate.  Photo  flashing  logic  to  be  as  per  the 

authentication  logic  &  DOS  requirement.  The  system  shall  realize  the  following 

functionalities: 

3.5.1  Employee Photo Display  The employee photo shall be  fetched  from  the server and 

displayed. Employee ID from card swiped by the employee 

shall be used for linking photo. 

3.5.2  Non‐employee Photo 

Display 

Non‐employee provided with Smartcard based  Id card will 

have photo display as per 3.6.1.  

3.5.3  Visitor’s Photo Display 

 

 

 

 

Visitor will be authenticated by finger print reader using 1: 

N mode  of  authentication.  The  verification  of  the  visitor 

shall be carried out. Upon verification success, the visitor ID 

(created during personalization of the visitor) shall be used 

to fetch photo from server and displayed. 

3.5.4  Output Display  a) Suitable LED monitor display (minimum 21”) shall be 

supplied  by  the  vendor  and  shall  be  suitably 

mounted  for  clear  visibility  to  identify  the  photo 

from  a  distance  of  about  12‐15  feet  against  each 

lane. 

b) Photo of authenticated person from each  lane  is to 

be displayed optimally. 

c) If  photo  is  not  found  in  the  server,  message 

indicating  “Photo  not  found”  error  shall  be 

displayed. 

d) Suitable  hardware  with  video  interface  shall  be 

used. This shall have backend Ethernet connectivity 

with server for fetching data. 

e) Output  display  should  be with minimum  500 NITS 

and should be 24x7 operation  type with the screen

saver features with black colour. 

3.6  EM lock for Single door with exit switch

3.6.1  Holding Force  1200 lbs. minimum

3.6.2  Protection level  Flame  tamper proof, weather proof 

3.6.3  Operating  voltage  Dual voltage selectable (12 VDC or 24 VDC)  

3.6.4  Mode  Automatic release by powering off  

3.6.5  Monitoring Feature to monitor door sensor for door Status

3.6.6  Features  Built‐in Door Status sensor with voltage spike suppressor

3.6.7  Certification  UL/CE Certified

3.6.8  Mounting Accessories  EM  Lock  shall be  supplied with all  required accessories 

for mounting on a single door 

3.6.9  Material  Anodized  aluminium  casing  with  anti‐rust  surface 

treatment & Anti‐tamper jam nuts  

3.6.10  LED indication  RED/GREEN LED indication for EM lock status 

3.6.11  Emergency Exit switch   Exit switch with glass enclosure with mechanism to open 

Page 28: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 27 of 59

the  doors  from  inside  in  case  of  emergency  situations 

and reader failure. 

3.6.12  Temperature & Relative 

Humidity 

 

 

0o to 50 o C,  RH 10% to 90%  

3.7 EM lock for Double door with Exit switch

3.7.1 Holding Force 1200 lbs. minimum x 2 for dual doors

3.7.2 All other specifications as per 3.7.2 to 3.7.12

3.8 Network Infrastructure Elements and Installation

3.8.1 Network Infrastructure Elements( Brand: AMP/ Panduit/Belden/D-Link) 3.8.1.1 Cat-6 UTP Cables:- Color: Grey  Standards/certifications: CAT‐6 or above, TIA/EIA‐568‐B.2‐1, ISO/IEC 

11801:2002        Length:‐1000 Ft.  Quantity: 100 Nos. 3.8.1.2 UTP Patch Cords:- Color: Grey  Standards/certifications: CAT‐6 or above, TIA/EIA‐568‐B.2‐1, ISO/IEC 

11801:2002        Length1: 03 Mtr 

Length2: 01 Mtr 

Length3: 10 Mtr 

Length3: 05 Mtr   3.8.1.3 Information Outlets: - Color: Grey  Standards/certifications: CAT‐6 or above, ISO/IEC 11801:2002        Type: ‐Should be compatible with the offered Face Plates and Patch Panels. Quantity: 300 Nos. 3.8.1.4 Loaded 24-port 1U Modular Patch Panel: - Color: Black  Standards/certifications: CAT‐6 or above   Type: ‐ 24‐Port Fully Loaded, Made up of Steel, Compatible with the 

offered information outlets. 3.8.1.5 Dual Port Face Plates with Labels and 3”X3” Back-Boxes  Color: White  Standards/certifications: CAT‐6 or above   Type of Face‐Plate: ‐ Dual Port with shutters included made up of Steel, 

3”X3” PVC Material, Should be compatible with the offered information outlets. 

Type of 3”X3” Back‐Boxes: PVC Material with ISI Mark, White color with 

Page 29: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 28 of 59

sufficient depth to accommodate I/O with Cat‐6 Cable.  

3.8.1.5 PVC Casing/Piping and accessories: - Should be of good quality and ISI Mark Brand  2‐inch PVC Casing and Piping   1‐inch PVC Casing and Piping  2‐inch PVC Pipe(Black)  Conduit/Elbow/Joints  3X3 PVC Back‐Boxes 3.8.1.6 CAT-6 I/O Point Termination: - Definition of one I/O Point or Point: ‐ Laying of Cable from Patch Panel to 

Face‐plate, Termination on Both end and Labeling of Cable using PVC Tube and Labeling of Face Plate& Patch Panel and finally Testing/Certification of each Point. 

3.8.2 Installation & Commissioning: - Vendor shall terminate CAT‐6 UTP Cable, which include laying of cables 

through casing/piping, termination, labeling of cable, Face‐Plate and I/O.  All Cables shall be labeled with Cat‐6 Compliant PVC Tubes for on either 

Side of the termination.  Vendor need to provide a certification document for Each Network Point.  Installation and commissioning charge of termination of each point shall be 

on pro‐rate basis as per the actual terminations.  Vendor shall bring all accessories like screws/Nuts/Brackets required for 

installation of casing/Piping and All tools required for Termination/Patching, Labeling and Testing/Certification of Cables.

 

4.0  ACS software   Vendor  shall  provide  Software  Requirement  Specifications  (SRS)  based  on the 

requirements mentioned  in  Para.  4.1  to  4.6  below.  Vendor  can  also  add  additional 

features that would be absolutely necessary for implementation of the system. SRS shall 

be mandatorily approved by Department. Vendor shall supply source code with API. 

4.1  Integrated web based software

4.1.1  Integrated web based ACS  software  forms  the critical component which  integrates all 

the software and hardware elements. The key software components shall interact with 

readers on Ethernet and provide seamless connectivity with server and database for the 

following requirements.  

a) Biometric  enrolment,  smart  card  personalization  and  authentication  software  for 

entrants as per the requirement of the organization. 

b) Real time ACS report for Main gate entry and second  level entry of employees and 

non‐employees 

c) Scheduled update from legacy database of employees and non‐employees 

d) Visitor Management System (VMS) software.  

f) Administration & Maintenance software 

g) Photo display during entry at Main gate for all personnel 

h) RFID  based Vehicle Access Control  System  (Complying  the  requirement  in  section  

3.5.4 of this RFP and to be interfaced with the main module) 

4.1.2  Handling of black‐listed cards of all Centres/Units of DOS/ISRO. All software shall have 

role based access. 

Page 30: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 29 of 59

4.1.3  All Transactions that occur at Main gates and second level access control shall be logged 

in flash memory of respective readers as event with transaction data. Transaction data 

which  include date, time, ID of employee/non‐employee/visitor, reader ID, direction of 

movement (IN/OUT), transaction ID and error code/status shall be transferred to server 

in real time through network. 

4.1.4  In case of failure in network, Transaction data shall remain stored in reader and shall be 

updated to server as and when network is restored.  

4.1.5  The  system  shall use  a  standard open  source RDBMS package  like MYSQL, Maria‐DB. 

However,  if commercial RDBMS package  is proposed, the bidder should provide all the 

required appropriate licenses as per the quoted solution.  

4.1.6  The  provision  should  be  available  to  transfer  employee  data  through ODBC/JDBC  for 

porting to other legacy applications. 

4.1.7  Provision  for  periodical  data  backup  /  restore  shall  be  available  e.g.  daily,  weekly, 

monthly, etc. through automatic schedules. 

4.1.8  All the generated reports shall have options to view on screen, print and exporting to a 

text, excel and PDF file. 

4.1.9  Vendor should be capable for modification/update in ACS software for customization to 

meet Department requirements at free of cost during warranty period.  

4.1.10  Vendor  shall  provide  source  code  along  with  API  and  documentation  of  integrated 

software. 

4.1.11  Web based software shall support latest version of Internet explorer and Mozilla Firefox 

with backward compatibility of minimum last two version. 

4.1.12  Personalization  and  other  software  modules  of  integrated  software  shall  support 

validation scheme for verification of a smart card presented on a Biometric with smart 

card reader for ACS at main gate entry and second level access control as per DOS/ISRO 

requirements.   

4.1.13  Validation of smart card of employees and non‐employees shall be carried out on  the 

basis of biometric template stored  in smart card  in  ISO  format. Whereas, validation of 

smart card of employees from other Centre/Unit of DOS/ISRO shall be carried out on the 

basis of biometric template stored in smart card in ISO format. 

4.1.14  Validation shall ensure denial of entry to the black listed smart cards  

4.1.15  Validation of smart card at peripheral main gate of each Centre/Unit and second  level 

access control shall be on the basis of valid  list or  invalid  list and as per the validation 

scheme of DOS/ISRO. 

4.2  Biometric  enrolment,  smart  card  personalization  and  authentication  software  for 

entrants 

4.2.1  This software shall include following three major functions.

a) Photo capturing, smart card layout design and biometric template enrolment 

b) Card printing and personalization 

c) Authentication to readers at Main gates & second level access  

4.2.2  This software shall be used at multiple locations for enrolment & card personalization of 

employees, non‐employees and visitors. 

4.2.3  Software shall have the provision to create the Master card to store the dual keys  for 

sector authentication of smart card. Accordingly the same master card shall be used to 

create,  personalize  and  authenticate  the  respective  cards  and  enable  the  readers  to 

Page 31: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 30 of 59

read the cards. 

4.2.4  Software shall fetch the data of employees and non–employees from the legacy system. 

4.2.5  Software  shall  collect data  like Chip  Serial Number  (CSN)  and  allowed  time  zone  and 

generate unique access code for each individual during personalization. This access code 

shall be used for authentication at main gate and second level access control. 

4.2.6  Selection of any two fingers for enrollment and duplicate search facility in order to avoid 

multiple enrollment of same individual. Biometric template in ISO 19794 format shall be 

saved in server database. 

4.2.7  Software shall capture the photograph of an  individual, processed for editing and shall 

be stored in the server and associated with employee record. 

4.2.8  Software  shall  have  provision  for  smart  card  layout  design  with  bi‐lingual  (Hindi 

(Unicode fonts) & English) text capability & Barcode printing on any side of card. 

4.2.9  Software shall format and personalize the card as per DOS/ISRO card format with dual 

key  authentication.  Software  shall  have  provision  to  read  contents  of  already 

personalized card with edit/modify/disable options. 

4.2.10  The software shall maintain  inventory of Smart Card usage and maintain  inventory  for 

its life cycle. (from card creation till it is disposed) 

4.2.11  The  newly  personalized  /  enrolled  card  details  shall  be  broadcast/multicast  to  all 

selected readers instantly or with delay not more than one minute. The readers shall be 

selected  from  the  list  of  locations  at Main  gate  and  location  of  second  level  access 

control. The acknowledgement shall also be sent to the server as an event and shall be 

reflected in Authentication software module. 

4.2.12  The system should facilitate online data updating to reader without disabling the unit.

4.2.13  The  software  should  be  able  to  read  the  data  for  debugging  purpose  after 

personalization of Card.  Software  should  capable  to  show  sector‐wise written data  in 

the card.   

4.2.14  Cards personalized through software will be randomly checked at other DOS Centres for 

its proper functioning and as per DOS standard personalization.  

4.3  Real time ACS report of Employees and Non‐employees

4.3.1  This  software  shall provide generation of various access control monitoring  report  for 

Main  gate  entry  and  access  report  for  second  level  entry  for  all  the  categories  of 

employees and non‐employees. 

4.3.2  Access control report shall include leave, tour and shift details of every individual.

4.3.3  All access control reports shall be based on various shifts operated by ISTRAC . Defining 

shift schedules and report generation shall be as per divisions/group/area. 

4.3.4  The  software  shall  have  provision  for  entering/updating  leave  and  tour  details  by 

individual  employee with work  flow  based  authentication  from  respective  approving 

authority. 

4.3.5  The  software  shall  generate  access  control  report  for  individual  and  entities  as  per 

organization chart on hierarchical basis. 

4.3.6  Authorization for viewing access control report shall be on hierarchy and role based i.e. 

Division  head  can  view  access  control  report  of  the  employees  of  the  concerned 

Division, Group head for the group, etc.  

4.3.7  The  system  should generate  following access  control  reports  for employees and non‐

employees with date and time window on daily, monthly, for a given duration, date wise 

Page 32: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 31 of 59

for individual, division wise, group wise, area wise, centre wise & all. 

a) Present & Absent report with tour, leave, holiday & overtime details  

b) Late comers, early goers 

c) Inter campus movement  

d) Number of hours of stay in office  

e) Current  count  strength  (Count  provided  for  employees,  non‐employees,  other 

centre employees and visitors) 

f) Head count at any given time for main gate and second level with details 

g)  Employees & Non‐employees strength  

h) Chronic late comers & early goers  

i) Customized reporting based on Query builder  

j) Shift/tour details  

k) Working day & hour calculation  

l) Holiday attendance report  

m) Overtime report 

n) Second level access control report 

o) Internal movement within campus  

p) Allowed / restriction detail  for individual in second level access control 

q) Other Centre/Unit employee & Non‐employee access control report 

r) Details  of  personnel  who  have  over  stayed  beyond  stipulated  time  to  be made 

available to the concerned authority. 

4.3.8  Access  failure  reports:  The  software  shall  provide  detailed  access  failure  reports  by 

generating  error/status  code  for  each  transaction.  The  report  shall  display  the  user 

details, date & time, location and nature of error/status for the following cases : 

a) Finger print verification failure  

b) Unauthorized attempt by making swipe of card to any location (card source is 

Unknown– system shall log the card details in addition to updating error codes.)  

c) Finger and / or card not authorized entry to particular location 

d) Finger and / or card not authorized entry at particular time 

e) Anti pass back error 

f) Detail of personnel not entered after valid authentication 

4.3.9  All the report shall be customized as per requirements.

4.4  Scheduled database update from Legacy database of Employee/Non‐employee

4.4.1  The software should have interface to update employee/non‐employee data (Employee 

code, Designation and other data attributes as specified by Department) at scheduled 

time  interval  for  updating  the  ACS  database  from  Legacy  Employee/Non‐employee 

database. Appropriate ODBC connectivity will be provided by Department. 

4.4.2  The  software  should provide  interface  to  read employee  code and other details  from 

smart card using any smart card reading device (personalized through DOS/ISRO Master 

card with dual key authentication) as input device for any software development or for 

integration with other service/application. 

4.5  Visitor Management System (VMS) Software

4.5.1  VMS shall be finger print based using 1:1 authentication for visitors. Each visitor shall be 

provided  with  unique  ID  (specific  to  Centre/Unit)  as  per  the  structure  provided  by 

Department. 

Page 33: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 32 of 59

4.5.2  VMS should be capable of maintaining the visitor details including finger print template, 

name, designation, nationality, visitor type, address, phone nos., email  id, photograph, 

passport, aadhaar details and provision to scan and store documents/images. 

4.5.3  Visitor  database  shall  seamlessly  integrate with  Access  Control  System  database  for 

sharing visitor information and approval logic. The Data for visitor shall be stored in the 

server as separate independent database. 

4.5.4  Software  shall  provide  online  workflow  based  visitor  management  which  includes 

request,  approval  and  visitor  pass  generation  through  web  portal  with  following 

features: 

a) Visitor request generation from employee  

b) Request shall be automatically forwarded to designated approving authority  

c) SMS/Email  based  alerting  and  approval  system  shall  be  incorporated  (vendor  to 

supply the associated hardware and software elements) 

d) Visitor pass generation  (The visitor pass  format will be bi‐lingual but dynamic data 

will be in English.) 

e) The format of visitor request form and visitor pass shall be provided. 

4.5.5  Visitor pass  generation  shall  include  registration of  individual  visitor by  capturing  the 

photograph  and/or  signature,  scanning  the  visitor’s  photo  id  or  business  card, 

enrolment of finger print template, personalization of smart card, generation of physical 

gate pass, restrictions for access area (buildings/laboratories) and validity date & time. 

4.5.6  Each visitor shall be provided with printed gate pass. 

4.5.7  Printed visitor pass shall be printed through  laser printer attached with VMS PC  in the 

prescribed format and shall be  issued to each visitor.  It shall  include visitor details  like 

visitor name, photograph, company name, contact person name, validity‐ date & time, 

visit area/s & purpose of visit. 

4.5.8  Visitor  enrolment  and  biometric  details  for  each  visitor  shall  be  uploaded  to  all 

concerned readers and servers within a minute. 

4.5.9  Software  should  provide  the  reports  with  respect  to  company,  visitor  type,  visiting 

frequency for various combinations of time Zones / date / durations.  

4.5.10  The system shall generate following reports on daily/weekly/monthly / between dates. 

a) No. of visitors 

b) Visitors who have over stayed. 

c) No. of foreign nationals visited 

d) Visitor access / movement reports for Main gate and second level. 

e) Visitor for selected area/group/division,  

f) Regular visitor, VIP visitor 

g) Visitor in the denied list  

h) Customized reporting based on Query builder 

4.5.11  The  software  should  cater  provision  for  generation  of  denied  list  which  will  be 

controlled by administrator for the visitor module. Whenever there is a re‐visit of visitor 

in the denied list there should be an alarm at the request & registration level. 

4.6  Administration & Maintenance software

4.6.1  Administrative software shall provide tools for : 

a) Role based login creations and assigning privileges 

b) Authorize  and  blocking  the  access  and movement  of  personnel  at Main  gate  and 

Page 34: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 33 of 59

second level access control.

c) To set reader / location wise access permission 

d) To view access control report of Entrants / Vehicles 

e) To  authorize  VMS,  tour,  leave  modules,  ACS  complaints,  Administrator  for  the 

second level Access control. 

4.6.2  Software shall define a set of rights that may be associated with an individual or group 

of individuals. 

4.6.3  Software  shall  provide  health  monitoring  of  different  hardware  components  like 

readers, , network components, etc. In case of failure of any component, pop‐up screen 

shall be generated with relevant details on virtual location map. 

4.6.4  Details of break‐down and preventive calls shall be generated 

4.6.5  Software  shall provide online  complaint  logging  from users with detail of  log‐in date, 

time, location, type of fault, etc. System shall automatically generate the complaint no. 

Service engineer  shall update  the complaint details with name,   actions  taken,  spares 

replaced detail, complaint closing date & time, etc. 

4.6.6  Event  logs on data upload/download, backups, scheduled scripts or any other event  in 

the system shall be made available. 

4.6.7  Provision for displaying raw data captured for employees and non‐employees from the 

selected or all reader/s should be provided to administrators. 

4.6.8  Any  loss of  communication  should  be  logged  as  event providing details of  reader  ID, 

date & time and nature of failure. 

4.6.9  Door open time at second level access control shall be logged and alerted when door is 

left opened for long duration. (User defined ) 

4.6.10  The  system  shall  cater  to  various  reports  for  trouble  shooting  and  performance 

monitoring.  The  performance  logs  shall  be  generated  catering  to  diagnostics  of  the 

system (ACS Hardware). 

4.7  Photo display during entry at Main gate for all personnel

  Integrated web  based ACS  software should  support  for  photo  display  of  employees, 

 non‐employees and visitors during their entry  into Main gate at   Centre/Unit shall be 

facilitated as per section 3.6 

 

4.8  RFID based Vehicle Access control system

  Integrated web based ACS software should support the requirement  in section 3.5.4 of 

this RFP for RFID based vehicle ACS. 

4.9  Handling of black‐listed cards across all centres/Units

4.9.1  Department will provide centralized database server at any one of the  Centres/Units 

( Not to be realised as a part of this tender). This centralized server shall host database 

of employees of all Centre/Unit in two separate tables (Valid list and Invalid list) with all 

historical evidences. This database will be maintained in any of RDBMS like MYSQL, MS‐

SQL, ORACLE, and SYBASE. Managing Central server  is the responsibility of DOS/ISRO. 

For  this purpose an  interface software shall be provided at  the ACS server of  ISTRAC  

for data exchange. 

4.9.2  Valid &  Invalid  lists  of  ISTRAC    are  required  to  be  updated  at  Centralized  server  to 

maintain upto date consolidated  lists. Likewise, consolidated Valid & Invalid  lists of all 

employees from all Centres/Units, maintained at centralized server, are required to be 

Page 35: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 34 of 59

updated at ACS server of ISTRAC . 

4.9.3  Exchange of Valid & Invalid lists shall be through intermediate tables without accessing 

directly to the database. 

4.9.4  Integrated software at  ISTRAC shall make available two separate tables as mentioned 

above  for Valid and  Invalid  lists of smart card details of employees  for the use of the 

DOS/ISRO  software.  Likewise  the DOS/ISRO  software provides  the  consolidated Valid 

and  Invalid  lists at the ACS server of  ISTRAC  for the use of  Integrated software at the 

ACS server.  

4.9.5  Centralized server will update data from ACS server of ISTRAC  in round robin mode at 

scheduled intervals through network. In similar fashion, ACS server at ISTRAC would be 

scheduled to update consolidated Valid & Invalid lists from the central server.  

4.9.6  Valid  list will  have  only  the  latest  issued  smart  card  personalization  details  for  each 

DOS/ISRO employee of all Centres/Units. 

4.9.7  Invalid  list  will  have  all  smart  card  details  of  lost  and  blocked/disabled  cards  with 

historical data.  

4.9.8  Smart card details for Valid & Invalid list shall contain the details required by DOS/ISRO.

4.9.9  Like  the  exchange  of  Valid  and  Invalid  lists,  the  transaction  data  of  other  centre 

employees  are  required  to  be  exchanged  using  intermediate  tables.  Integrated 

software  should  make  available  the  transaction  data  for  employees  of  other 

Centre/Unit.  Centralized  server  shall  take  this  transaction  data  from  ACS  server  of 

ISTRAC in round robin mode at scheduled interval through network. In similar fashion, 

ACS  server at  ISTRAC  shall be  scheduled  to  take consolidated  transaction data which 

includes the transaction data of the employees of ISTRAC from the central server.   

4.9.10  Integrated  software  shall  provide  access  control  report  for  the  employees  including 

tour details to other Centre/Unit of DOS/ISRO.  

5.0  Enrolment and personalization for Entrants/Vehicles

5.1  Biometric enrollment station

5.1.1  The Enrollment station with optical sensor shall capture finger print template and store 

details  in server and smart card memory as per DOS/ISRO  requirements.  It shall work 

with enrollment  software  to upload employee data  into  central  server  from where  it 

shall be transferred to reader’s memory.  

5.1.2  Enrollment station shall be  interfaced with the desktop PC having enrollment software 

through USB interface. 

5.1.3  Verification  time  shall  be  less  than  1  second  for  1:1 mode  and  2‐3  seconds  for  1: N 

mode. 

5.1.4  Resolution :  Minimum 500 dpi

5.1.5  Shall capture in ISO 19794 Format for Interoperability.

5.2  Smart card personalization reader

5.2.1  The smart card Reader/Writer shall be PC connected reader and shall read & write to a 

13.56 MHz contact less smart card – Mifare standard (ISO 14443A) cards of 4K memory. 

5.2.2  Personalization reader shall be connected with desktop PC through USB/Network.

5.2.3  Reader shall be compatible with personalization software to format and personalize the 

card as per DOS/ISRO compatible format. The details of same shall be provided. 

5.3  Card printer with cartridge

5.3.1  Print resolution of 300 dots per inch, 16.7 million colors

Page 36: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 35 of 59

5.3.2  Accepts  ID‐1/CR‐80  size  cards measuring 3.370  in.  x 2.125  in.(85.6 mm  x 53.98 mm); 

accepts  glossy‐surfaced  PVC  cards;  other  core materials with  PVC  over  laminates  are 

optional 

5.3.3  Accepts card  thickness  from 0.02  to 0.05  in.  (0.51 mm  to 1.27 mm)   + 10%,  for print‐

only; 0.03 to 0.05 in. (0.76mm to 1.27mm) + 10% for print and laminate 

5.3.4  Operating system support:

Microsoft Windows Vista, Windows XP, Windows 7, Windows 8, Windows 10,  Windows 

2003 Server,Windows 2008 Server, Windows 2012 or better supported  printer drivers 

5.3.5  Dual  sided printing &  lamination, photo  and  other  information  should not  fad out  in 

minimum three years 

5.3.6  Agency approvals: UL, cUL, FCC, CE, CCC, Ctick, RoHS

5.3.7  Security Features: Physical lock to secure printer cartridge removal, card intake and exit 

hoppers.  Resin‐erase feature to eliminate personal data on used ribbon panels. 

5.3.8  Printing: Over  the edge, one or  two  sided UV printing with  fluorescent panel  ribbons. 

Continuous‐tone for full‐color or black‐and‐white photos 

5.3.9  Printing of Alphanumeric text,  logos, Holograms and digitized signatures, variety of bar 

codes and background patterns. 

5.3.10  Automatic printer  settings and offsets, automatic  ribbon  identification,  validation and 

low ribbon warning. 

5.3.11  Full‐color print speed of up to 40 cards per hour (two sided, print and laminate)

5.3.12  Choose patch lamination with superior coverage or lamination without printing

5.3.13  Connectivity:  Bi‐directional  USB  and  Ethernet  10/100/1000  Base‐T  bi‐directional 

networking 

5.3.14  Printer  driver  features  user‐adjustable  image  and  color  controls,  stand‐alone  driver 

diagnostics,  color  image and  text  card preview, online user help, add  text, pattern or 

image to topcoat, and supply usage tab 

5.3.15  Audible and visual message prompts on printer and PC

5.3.16  Automatic card feed 

5.3.17  Quick‐change ribbon and laminate cartridges

5.3.18  Electrical requirements of  230 V AC ± 10 %, 49‐51Hz

5.3.19  Operating Temperature: Up to 35°C and non‐condensing humidity from 20% to 80%

5.3.20  Print Head Warranty: Lifetime.

5.3.21  Cartridges and lamination sheets for printing and laminating cards shall be supplied with 

the printer as per  the  requirement mentioned  in  the BOM. The quantity of cartridges 

and lamination sheets shall be mentioned clearly by vendor.  

 

5.4  Web Camera (To be used at Front Office / Reception )

5.4.1  Sensor resolution: Minimum 1.3 MP,  Video resolution: 1.3 MP, Snapshot resolution: 1.3 

MP 

5.4.2  LCD clamp / CRT stand / Desktop stand

5.4.3  PC Link: USB 2.0 

5.4.4  RAM memory: 512 MB RAM

5.4.5  Card printing software shall support online picture capture, uploading for card printing, 

manual operation will not be accepted. 

 

Page 37: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 36 of 59

5.5  Signature pad with pen 

5.5.1  Interface: USB  

5.5.2  Optical Resolution: Up to 900 dpi

5.5.3  Sampling rate: up to 400 samples / second

5.5.4  Pressure‐sensitive pen  for  input, which  allows  to  capture handwritten  signatures  and 

attach the signatures to ACS applications.  

5.5.5   Display: LED preferrable 

5.6  Mifare 4K Smart Cards 

5.6.1  Mifare smart card compliant with ISO 14443A

5.6.2  Read range of 1 to 3 cms 

5.6.3  CR 80 Standard 

5.6.4  Memory of 4 KB 

5.6.5  Card shall have unique 7‐byte Chip Serial Number (CSN) 

 

6.0  Server, Desktop, Laptop, Laser Printer, Network Switches & UPS 

6.1  Server 

6.1.1  Preferred Make : HP / IBM / Dell / Fujitsu (1U/2U Rack Mountable) 

6.1.2  Processor  : Single  Intel Xeon processors of E52600 product  family or better series, 2.4 

GHz  or  better,  Minimum  8  MB  L3  cache,  Quad‐core,  Dual  processor  Capable 

motherboard   

6.1.3  Chipset : Intel C600 or better compatible with the above processor 

6.1.4  Memory : 8 GB – DDR3 ECC buffered RAM, 1600 MHz 

6.1.5  Hard Disk and controller: 5x300 GB @ 15 K RPM, hot plug SAS drives, storage system 

should Raid 0, 1, 3 & 5. Hard drives to be hot‐pluggable. 

6.1.6  Expansion  slots:  Minimum  of  one  (1  no.)  of  PCIe/PCI/PCI‐X  based  free  slots  after 

installation of all required devices. 

6.1.7  Monitor, keyboard & Mouse: 22  inch wide Full HD LED monitor, Keyboard and Optical 

Scroll mouse.  

6.1.8  Networks & I/O: Dual Gigabit Ethernet 10/100/1000 ports with RJ45 connectors, 2 Serial 

Ports, 2 Front and 2 Rear USB 2.0 Ports. 

6.1.9  Management:  Should  provide  remote management  port  and management  software 

capable of providing graphical interface. Server management software should be of the 

same brand as the supplier. 

6.1.10  OS: Redhat Linux  latest version or MS Window 2012 server or  latest version. OS  shall 

carry license. 

6.1.11  Power  supply: 230 V AC ± 10 %, 49‐51Hz with  rack power  cords. Dual  redundant hot 

plug Power supply should have minimum 80 % efficiency. 

6.1.12  Media drive : 16X DVD ‐/+ RW 

6.1.13  Chassis / Acoustic : Rugged Tower, Low acoustic noise

6.1.14  Others: Redundant hot plug power supply. Redundant hot plug fan. 

6.1.15  Certification : UL/CE Certified

6.1.16  Backup  tape  :  DDS3/4  supporting  DAT  320  Tapes,  25  data  cartridges,  5  cleaning 

cartridges, external USB 2.0 tape drive  

6.1.17  Database  : MySQL(Preferred) or  Standard  Licensed Microsoft  SQL  2008  or  higher  or 

Page 38: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 37 of 59

Oracle or Sybase Database with original media and serial no. and appropriate licenses in 

the name of ISTRAC.  

   

6.3  Desktop PCs 

6.3.1  Preferred Make : HP / Dell / Lenovo   

6.3.2  Processor : Intel Core i7 6700 (8 M Cache, up to 3.6 Ghz) or better 

6.3.3  Chipset : Intel express chipset or better 

6.3.4  Memory : 4 GB – DDR4  RAM

6.3.5  Hard disk : 2 x 1 TB SATA HDD 

6.3.6  Expansion slots: 1 no. of PCI and 1 no. of PCIe/PCI‐X based free slots after installation of 

all required devices. 

6.3.7  Network  and  I/O: Gigabit  Ethernet  10/100/1000  ports with  RJ45  connectors.  1  Serial 

Port, 2F+2R USB 2.0 Ports. Multimedia with Speakers, Multimedia Keyboard and Optical 

Scroll mouse.  

6.3.8  Monitor : 22” wide Full HD LED monitor

6.3.9  OS: Windows 7/10 preloaded with licensed original CD Media / recovery disks.

If the solution is implemented based on Linux environment, the desktop should be Linux 

certified and preloaded with support Linux version with media CD/DVD 

6.310  Power supply : 230 V AC ± 10 %, 49‐51Hz

 

6.3.11  Media drive : 16X DVD ‐/+ RW or Better 

 

6.3.12  Chassis / Acoustic : Rugged tower low acoustic noise

 

6.4  Laptop 

6.4.1  Preferred Make : HP / Dell / Lenovo / SONY

6.4.2  Processor : Intel Core i7‐6500U Processor (4MB Cache, up to 3.10 GHz) or better

6.4.3  Chipset : Intel express or better 

6.4.4  Memory : 4 GB – DDR4 RAM or higher

6.4.5  Hard disk : 500 GB SATA HDD or Higher 

6.4.6  Network  and  I/O  :  802.11  bg/bgn Wi‐Fi,    10  /  100  /  1000  Ethernet    ports with  RJ45 

connectors, 2 nos. USB 2.0 Ports. multimedia with  in‐built speakers, wireless keyboard 

and mouse.  

6.4.7  Monitor : 14” HD WLED or higher

6.4.8  OS: Windows 7 /10 preloaded with licensed Original CD Media / recovery disks.

If the solution is implemented based on Linux Environment, the laptop should be Linux 

certified and preloaded with support Linux version with media CD/DVD 

6.4.9  Power supply : 230 V AC ± 10 %, 49‐51Hz, Power adapter

Battery : 12 cell for minimum six hours back‐up and charging adapter 

6.4.10  Media drive : 16X DVD ‐/+ RW or Better 

6.4.11  Carry bag: Back Pack. 

6.5  Laser printer ( To be used at Front Office / VMS area )

6.5.1  Printing speed: Minimum 28 PPM – Black & white or higher (A4 size), Full duplex

6.5.2  Resolution: 1200 x 1200 DPI or better

6.5.3  Standard Memory, minimum size, default: 64 MB

Page 39: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 38 of 59

6.5.4  High‐speed USB 2.0 printer cable and power cord for 230 V AC ± 10 %, 49‐51Hz

6.5.5  Standard Printer Languages supported: Postscript‐3, PCL6 

Software drivers for Windows 2000 / 2003 / XP  / Vista / Linux 

6.5.6  Interfaces : USB 2.0 & Ethernet with cables

6.5.7  Two additional  black Print Cartridge for printing yield of 5000 pages or higher

6.6  Network switches 

6.6.1  24 Port L3 managed switch with Single mode fiber module and POE  ports.  

10/100/1000 Mbps   with wall mounting arrangement 

Power supply : 230 V AC ± 10 %, 49‐51Hz, Power adapter 

 6.6.2  

Outdoor Access Point :  IEEE 802.11b/g/n  AP with PoE  connection facility and two Omni 

directional antenna 

Indoor Access Point :  IEEE 802.11b/g/n  AP with POE  connection facility and two Omni 

directional antenna 

 

6.9  Flatbed A4 size color scanner

6.9.1  Optical resolution ‐ 4800 x 9600 dpi, Interface: USB 2.0 or higher 

6.9.2         One touch scan, copy, create PDFs and email through ACS software  

6.10 IDcardprintersupportinglaminationInterface6.10.1 PrintMethod: Dye‐Sublimation/ResinThermalTransfer6.10.2 Resolution: 300dpi6.10.3 Colors: Upto16.7million/256shadesperpixel

6.10.4 PrintRibbonCapacity: •Full‐color,YMC,750printsminimum•Full‐colorwithresinblack,YMCK,500prints minimum•Full‐colorwithtworesinblackpanels,YMCKK,500prints minimum

6.10.5 HDPFilmcapacity : •Clear(1,500printsminimum)

•CustomHolographic(500printsminimum)6.10.6 Overlaminatecapability: •ThermalTransferOverlaminate,0.25milthick,500

prints minimum•PolyGuardOverlaminate,1.0miland0.6milthick,250printsminimum

6.10.7 PrintSpeedinbatchmode: <=24secondspercard(YMCwithtransfer)<=29secondspercard(YMCKwithtransfer)<=40secondspercard(YMCKKwithtransfer)<=35secondspercard(YMCKwithtransferanddual‐sided,simultaneouslamination)<=48secondspercard(YMCKKwithtransferanddual‐sided,simultaneouslamination)

6.10.8 AcceptedStandardCardSizes: CR‐80(3.370”Lx2.125”W)6.10.9 PrintArea: Over‐the‐edgeonCR‐80cards6.10.10 AcceptedCardThickness: •Printonly:0.030”(30mil)to0.050”(50mil)

•Print/Lamination:0.030”(30mil)to0.050”(50mil)6.10.11 AcceptedCardTypes: LaminatedPVC,smartcards,opticalmemorycards6.10.12InputCardCartridgeCapacity: 100cards(0.030”)6.10.13 OutputHopperCardCapacity: 200cards(0.030”)6.10.14 CardCleaning: Replaceablecleaningroller(tobeincludedwith

eachprintribbon)

Page 40: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 39 of 59

6.10.15 Display: User‐friendly,SmartScreenLCDControlPanel6.10.16 SoftwareDrivers: CompatibleforWindows8/7/Server2008&

2003/&Linux6.10.17 Interface: USB2.0(highspeed)andEthernetwithinternal

printserver6.10.18 OperatingTemperature: 18°to32°C6.10.19 Humidity: 20‐80%non‐condensing6.10.20 Certifications: UL,CE,IC,FCCClass‐A,CCC,BSMI,KC,MIC6.10.21 Warranty: •Printer–ThreeyearsandoptionalExtended

Warranty Program•Printhead–Lifetime;unlimitedpass

6.10.22 Modulesrequired: •Dualcardinputhoppermoduleand200‐cardinputhopper•Cardlaminationmodule–singlesided•Doorandcartridgelocks•Printercleaningkit

 

7.0  Accessories, Cables and Conduits

  Preferred Cable Make: Polycab, Finolex, Systimax, D‐Link

ISI  Certification  shall  be  submitted.  All  the  cables  should  be  weatherproof,  outdoor 

grade &as per BIS standard. 

During site visit, bidder will survey for quantity required of each accessory and mention 

the  same  in offer with per meter cost. Payment  shall be made as per actual quantity 

used for installation. 

   

7.1  Power Cable 

  3 Core 1.5 sq.mm 

7.2  4 core Shielded Cable 

  0.75 sq.mm each core 

7.3  8 core Shielded Cable 

  0.75 sq.mm each core 

7.4  PVC Conduit for Cable laying

  Bidder shall specify the size compatible with cables

7.5  SS Pole 

  SS  Pole  of  suitable  height  for  installing  readers  for  senior  officials  entering  through 

vehicles.  SS  pole  shall  be  with  suitable  environmental  protection  (IP54  or  better) 

including weather shade. Vendor shall take prior approval from ISTRAC. 

7.6  Any additional item required

  Additional  items  if  any  required  for  realization  of  this  TURN‐KEY  work,  Bidder  shall 

specify with details as per Annexure ‐ III. 

8.0  System integration requirements

8.1  Contractor  shall  provide  the  block‐diagram  depicting  the  integration  of  various 

hardware and software components  like readers, turnstiles, readers on pole, EM  locks, 

server,  enrollment &  personalization  units, VMS,  servers with  database. Vendor  shall 

clearly mention the installation requirements. 

8.2  Throughput  for minimum  10  persons  per minute  per  lane  at Main  gate.  This  value 

should be attainable within 15 days of familiarization. 

Page 41: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 40 of 59

8.3  Integration  of  turnstile  and  EM  lock  should  provide  emergency  exit  with  adequate 

instruction of safety warning. Location of exit switch should be placed appropriately for 

access during emergency. 

8.4  Database  in both  servers and application  software  should be backed‐up automatically 

using scheduler. Reliable backup plan should be provided using DAT tapes and external 

backup media. 

8.5  Design of  the  system  shall  ensure  reliability  and minimum down  time of  the  system. 

Single point  failure  like  server, database or network  should not bring down  the basic 

operation of ACS system. 

8.6  Server  shall  support  various  protocols  to  update  its  date  and  time with  reference  to 

source.  The  server  shall  in  turn,  ensure  synchronization  of  RTC  of  all  readers  and 

components connected to it across all locations of ISTRAC. 

8.7  All the installation protected by password should be made available to ACS in‐charge as 

hard  copy  and  soft  copy  in  CD media.  Password  shall  provide  details  of  web  links, 

application path and help information on usage of the same. 

8.8  Contractor  shall  remove  all  the  components  of  existing  access  control  equipment  at 

Main gate & second  level and  install &  integrate all the  items of new ACS side by side 

without interrupting operations of existing ACS. 

8.9  Contractor  shall  carry out  initial one  time process  for enrolment, personalization  and 

card printing  for all personnel  (employees and non‐employees) during  installation and 

commissioning before ATP. 

 

9.0  Acceptance Test Plan ( ATP )

9.1  Acceptance Test will be conducted only after successful  installation and uninterrupted 

operation of the entire system at site for minimum period of 15 days. 

9.2  Contractor  shall  submit  details  of  ATP  to  centre  for  an  approval  as  per  tender 

specifications & shall demonstrate ACS specifications as per tender document based on 

approval. 

9.3  During  ATP,  Contractor  will  use  their own  tools  &  equipments.  Department  will  not 

provide any test instrument/tools.  

 

10.0  Training 

10.1  Contractor shall impart one week training for all the items of ACS to at least three 

Department’s personnel at Contractor’s premise. 

10.2  Contractor  shall  upon  completion  of  the  installation  provide  complete  training  with 

documentations on the configuration, operation and maintenance of the systems to the 

required Department’s personnel assigned by the Department. 

10.3  Training  should  include  documentation  required  for  understanding  the  system,  its 

working concepts and basic trouble shooting guidelines. 

10.4  Training shall be arranged  to security personnel  (CISF) on basic operation of  turnstiles 

gates,  reception  and  administration  staff  for  VMS,  enrollment  &personalization.  It 

should cover aspects related to emergency exit, exigency operation, etc.  

10.5  All above training shall be part of integration and acceptance of the system. 

 

 

Page 42: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 41 of 59

 

11.0  Documentation 

11.1  Contractor shall submit documents for operation and maintenance of the entire system.

11.2  Systems block diagram along with wiring layout of all the items of ACS Systems shall be 

submitted. 

11.3  ACS software with media for all the application.

11.4  Software  description manual which  shall  include  customization  as  per  requirements, 

flow charts, operating procedures for all applications. 

11.5  OS  for  Servers  and  PCs  shall  be  supplied with  license (OEM/full)  along with  original 

media with key no. on the name of ISTRAC. 

11.6  All the documents shall be provided in CD media in two copies. 

 

12.0  Special Conditions 

12.1  The  extent  of  the  contract works  shall  include  necessary  cabling  to  interconnect  the 

various  security  systems,  central  equipment,  hardware  and  devices  and  like  for  it  to 

provide the performance as specified in this contract document. 

12.2  All  cable  enclosures  including  conduits,  cable  trays,  ducts,  wall  boxes,  termination 

panels and the like that are required to as part of this contract. 

12.3  Contractor shall supply material such as pipe, bricks, sand, stone‐chips, cement, cables, 

PVC casing/capping etc. to carry out turnstiles & poles fixation works, fitting of EM locks, 

readers, adapters, exit switch, etc. for erection and commissioning of the system. 

12.4  All  proposed  security  field  devices  installation  shall  not  only  to  operate  functionally, 

they have also to blend with the interior design of the building.  

12.5  All  installations  carried  out  shall  conform  to  the  national  standards  and  code  of 

practices. 

12.6  All the systems shall have antivirus software with facility of offline updation.

12.7  The Contractor shall ensure that the ACSmust be expandable in the following areas:

a) The  system  shall  be  designated  to  allow  foreseeable  organizational  changes  and 

procedural changes beyond current plans, 

b) Additional  hardware  units  shall  easily  be  added without  any modification  to  the 

existing hardware, software and network configuration. 

12.8  Contractor  shall  provide  site  requirements,  power  supply  &  environmental 

requirements, accessories requirements at work site. 

12.9  Contractor shall carry out customization of all the components of hardware and 

software as per requirements. 

12.10  IN/OUT lane no., reader ID, readers on pole, exist switch, etc. shall be marked with 

suitable color radium stickers at all installed locations of Main gate and second level 

ACS. 

12.11  Contractor  shall  ensure  the  inter‐operability &  compatibility  for  all  types  of  readers, 

turnstiles, software for all requirements, servers, EM  locks, printers, PCs, enrollment & 

personalization stations and interfacing with network. 

Page 43: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 42 of 59

PART‐C 

 

 List of materials of Access Control System to be un-installed at Bangalore :

Sl.No Description Qty Location

1 Personal Computer, Make: Compaq 1 no. SCC

2 Contact less Smartcard reader, Make: Electron India, BT-843

16 nos. SCC

3 Smart card programmer with s/w modules 1 no. SCC

4 Badge Printing Software 1 no. SCC

5 Electro Magnetic Locks 8 nos. SCC

6 Emergency Buttons 8 nos. SCC

7 Attendance Software 1 no. SCC

8 Windows Operating System 1 no. SCC

9 Smart card readers 20 nos. SCC=8, Mox=4, RDA=4, IDSN=4

10 2 reader Controller 10 nos. SCC=4, Mox=2, RDA=2, IDSN=2

11 Electro Magnetic Lock (Single) 4 nos. SCC=2, RDA=1, spare=1

12 Electro Magnetic Lock (double) 1 no. SCC

13 Turnstile gate – Full Height 2 nos. SCC

14 Smart card Programmer with software modules

1 no. SCC

15 Visitor module 1 no. SCC

16 Mobile card readers 2 nos. SCC

17 Emergency buttons 5 nos. SCC=2, RDA=1, spare=2

18 Dual Lane Turnstile gate 3 nos. RDA=1, MOX=1, IDSN=1

19 UHF reader

2 Nos SCC

20 Pedestal readers

2 nos. SCC

21 Web cam

2 nos SCC

22 Photo display reader

1 no SCC

23 Photo display PC

1 no SCC

24 Boom Barrier 1 no SCC

Page 44: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 43 of 59

List of materials of Access Control System to be un-installed at Lucknow:

Sl.No Description Qty

1 Smartcard Reader 18 nos.

2 2 reader controller 9 nos.

3 Electro magnetic Locks (single) 6 nos.

4 Emergency buttons 8 nos.

5 Turnstile gate – Full height 1 no.

6 Windows 2003 server 1 no.

7 PC for visitor module and Attendance Monitoring software 2 nos.

8 Printer for visitor module 1 no.

9 MS SQL server database 1 no.

10 Electromagnetic Locks (double) 2 nos.

11 Smartcard programmer 1no.

12 Web camera 1 no.

13 SHDSL Modem 6 nos.

14 8 port switch 6 nos.

15 Smartcard Readers with RS232 (canteen) 2 nos.

16 POS printer 2 nos.

17 Wall mountable enclosure 2 nos.

18 Single Lane Turnstile gate 1 no

  

Page 45: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 44 of 59

Annexure ‐ I  

BIDDER’S PROFILE 

1.  Name of the Organization and Address :

2.  Year of Establishment : 

3.  Status of the firm 

(Whether Pvt. Ltd. company / Pubic Ltd. company/ Partnership Firm) : 

4.  Name of the Chairman/Managing Director/CEO (as the case may be) : 

5.  Whether registered with the Registrar of Companies/Registrar of Firms  in India? If so, 

mention number and date and enclose Registration Certificate copy : 

6.  Name and address of Bankers:

a) 

 

b) 

7.  Turnover of the Company/Firm in  2014‐15, 2015‐16 and 2016‐17: 

(Please attach a copy of audited Profit & Loss Account for the above three years): 

2014‐15 : 

2015‐16 : 

2016‐17 : 

8.  Whether  registered  for  sales  tax  purposes?  If  so, mention  number  and  date.  Also 

furnish copies of sales tax clearance certificate: 

9.  Permanent Account Number (Furnish copies of Income tax clearance certificates):

10.  Is the Company / Firm a manufacturer of ACS System? If yes,

a) Give the Name of the place where manufacturing unit is located: 

b) Mention the address and phone number of the company’s Bangalore office:  

c) Give the date of opening of company’s Bangalore office: 

11.  Give  details  of  the  after‐sales  service  facility  in  terms  of  technical manpower  and 

spares provided by the company in Bangalore : 

12.  Since when and how long Company/firm has been manufacturing ACS Systems: 

13.  Whether company has been pre‐qualified by other Central Government organization 

for ACS? (Furnish organizations names, category and date of registration): 

14.  Furnish  the  names  of  renowned  organizations,  where  company  has  installed  ACS 

Systems  in  India  in the  last three years ending 31 March 2017 (Work of value of  less 

than Rs 50 lakhs should not be reported). 

 

Name of Organization with 

Address 

Year of 

Installation 

Value of orders 

1. 

2. 

3. 

Self attested copies of Performance Certificate ( please do not enclose any work order) 

issued by organization after completion of work must be enclosed failing which  it will 

be treated that company has no past experience in the field of ACS. 

Page 46: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 45 of 59

15.  Details of Technical Staff in Bangalore :

 

Sl. No.  Name  Qualification Post Held Experience 

   

 

16.  Bank Solvency Certificate for Rs.50 Lakhs (Furnish Bank Solvency Certificate issued not 

before 31st March 2017): 

17.   Whether  company  is  an  authorized  dealer/agent  for  the  original  equipment 

manufacturer?  (If  so,  furnish  a  certificate  in  original  from  the  original  equipment 

manufacturer) 

   

 

                                 

Page 47: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 46 of 59

  

D E C L A R A T I O N 

 

a) I / We have read and understood the Tender document and I / We understand that if 

any  false  information  is  detected  at  a  later  date,  any  future  contract made  between 

ourselves and ISTRAC, on the basis of the information given by me / us can be treated as 

invalid by the ISTRAC, and I / We will be solely responsible for the consequences. 

b) I / We agree that the decision of ISTRAC, in selection of contractors will be final and 

binding to me / us. 

c) All  the  information  furnished  by  me  hereunder  is  correct  to  the  best  of  my 

knowledge and belief. 

d) I  / We agree  that  I  / we have no objection  if enquiries are made about  the work 

listed by me / us in the accompanying sheets. 

e) I  / We  agree  that  I  / We  have  not  applied  in  the  name  of  sister  concern  for  the 

subject empanelment process. 

f) I  / We hereby  certify  that none of my  relative(s)  is/are employed  in DOS/ISRO.  In 

case  at  any  stage  it  is  found  that  the  information  given  by me/us  is  false/incorrect, 

DOS/ISRO  shall have  the  absolute  right  to  take  any  action as deemed  fit without any 

prior intimation to me/us. 

g) I / We have understood the terms and conditions of the tender document and fully 

agree with same.

 

 

 

 

Place:                                                                                                 SIGNATURE 

Date:                                                                                   NAME & DESIGNATION 

SEAL OF ORGANISATION 

     

         

 

Page 48: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 47 of 59

 

Annexure – II 

 

TECHNICAL COMPLIANCE STATEMENT  

 

Note: Suppliers should state  ‘Yes’  if their offer conforms to the Requirements as stated  in 

Part‐B of the Tender document, or else they should state ‘No’ with reasons. 

Sl. No  Requirements  Compliance  Reasons/Statement for  Non‐

Compliance 

    Yes  No   

1.0  Proposed system with accessories 

is UL/CE (latest editions) listed and 

comply  to  specifications  laid  by 

DOS.  

     

2.0  Proposed  Access  control  shall  be 

able  to  integrate  following 

outcomes: 

     

2.1  Single  window  Access  card 

enrollment  for  all  access  control 

system.  

     

2.2  Alarms  and  events monitoring  at 

single  common  monitoring 

window. 

     

2.3  Reports  generation  from  single 

common application. 

     

3.0  Specification of :       

3.1  Biometric and smart card readers 

with built‐in controller 

(Article no. 3.1 of Part‐B) 

     

3.2  Hand held readers        

(Article no. 3.2 of Part‐B) 

     

3.3  Dual lane turnstiles  (Article no. 

3.3 of Part‐B) 

     

3.4  Boom barrier with RFID tags       

Page 49: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 48 of 59

(Article no. 3.4 of Part‐B) 

3.5  Photo display during entry 

(Article no. 3.5 of Part‐B) 

     

3.6  EM lock for single door with exit 

switch.  

(Article no. 3.6 of Part‐B) 

     

3.7  EM lock for Double door with Exit 

switch 

(Article no. 3.7 of Part‐B) 

     

3.8  Network Infrastructure Elements 

and Installation 

(Article no. 3.8 of Part‐B) 

     

4.0  ACS Software       

4.1   Integrated web based software 

(Article no. 4.1 of Part‐B) 

     

4.2   Biometric enrolment, smart card 

personalization and 

authentication software 

(Article no. 4.2 of Part‐B) 

     

4.3  Real time ACS report 

(Article no. 4.3 of Part‐B) 

     

4.4  Scheduled database update from 

legacy database 

(Article no. 4.4 of Part‐B) 

     

4.5  Visitor management system 

software 

(Article no. 4.5 of Part‐B) 

     

4.6  Administration and maintenance 

software 

(Article no. 4.6 of Part‐B) 

     

4.7  Photo display during entry 

(Article no. 4.7 of Part‐B) 

     

4.8  RFID based vehicle access control 

(Article no. 4.8 of Part‐B) 

     

Page 50: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 49 of 59

4.9  Handling of black‐listed cards 

across all Centre/Unit 

(Article no. 4.9 of Part‐B) 

     

5.0  Enrolment and personalization of 

entrants/Vehicles 

(Article no. 5.0 of Part‐B) 

     

6.0   Server, desktop, laser printer, 

scanners 

(Article no. 6.0 of Part‐B) 

     

7.0  Accessories, Cables and conduits 

(Article no. 7.0 of Part‐B) 

     

7.1  List of Additional items required, if 

any, for realization of contract. 

(Specify with details as per 

Annexure‐III) 

     

8.0  System integration requirements 

(Article no. 8.0 of Part‐B) 

     

9.0  Acceptance test plan 

(Article no. 9.0 of Part‐B) 

     

10.0  Training 

(Article no. 10.0 of Part‐B) 

     

11.0  Documentation 

(Article no. 11.0 of Part‐B) 

     

12.0  Special conditions 

(Article no. 12.0 of Part‐B) 

     

 

 

 

Place:                                                                                 SIGNATURE 

Date:                                                                                  NAME & DESIGNATION 

SEAL OF ORGANISATION 

 

  

Page 51: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 50 of 59

 Annexure – III 

 

ADDITIONAL ITEMS 

 

Note: Additional items, if any required, for realization of this turn‐key work shall be listed 

with details  

 

Sl. No.  Items Quantity Make Justification for the item

   

  

   

  

   

  

   

  

   

  

 

 

Place:                                                                                SIGNATURE 

Date:                                                                                  NAME & DESIGNATION 

SEAL OF ORGANISATION

Page 52: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 51 of 68

Annexure‐IV 

UNPRICED VERSION (PRICE MASKED) OF BILL OF MATERIALS 

Note: 1. Prices are not to be furnished in this Annexure 

2. Bidder should only confirm in the respective columns i.e., Make, rates of Taxes /Duties /Levies applicable with details of 

percentages, additional items and warranty and training. 

I) Items to be considered for total cost of ownership  

Sl. 

No.Description  Make  GST 

Installation, 

commissioning and 

testing 

Service 

Tax Quantity  Unit 

1 Biometric Smart Card Readers (One for IN and One for Out)  34 Nos 

2 Vehicle Readers cum Controller (One for IN and One for Out)  10 Nos 

3  Hand Held Biometric Readers  2 Nos 

4  Boom Barriers  5 Nos 

5  LED Panel Display for Photo Flashing (21")  8 Nos 

6 Biometric Smart Card Reader for Second Level Entry (Technical Areas) IN  122 Nos 

7 Biometric Smart Card  Reader for Second Level Entry (Technical Areas) Out  122 Nos 

8  EM Lock for Single Door with Exit Switch  16 Nos 

9  EM Lock for Double Door with Exit Switch  95 Nos 

10 

Integrated Web based Software (Licences for software as per section 4 of RFP to meet all module requirements of SCC, MOX, IDSN, Lucknow)  4 Licences 

11 

Biometric Enrolment stations at SCC, MOX, IDSN, Lucknow (Two at each location)  8 Nos 

12 Smart Card Personalizer at SCC, MOX, IDSN, Lucknow (Two at each location)  6 Nos 

13 Web Camera at SCC, MOX, IDSN, Lucknow (One at each location)  5 Nos 

Page 53: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 52 of 68

14 Signature Pad with Pen at SCC, MOX, IDSN, Lucknow (Two sets at each location)  8 Nos 

15  4K Mifare Smart Cards  1700 Nos 

16  Rack Mountable Servers (1U) at SCC  2 Nos 

17 

DeskTop Systems for VMS, AMS & Photoflashing Operations at SCC, MOX, IDSN, Lucknow  8 Nos 

18 Laser Printer for VMS at SCC, MOX, IDSN, Lucknow   4 Nos 

19 Flatbed A4 Size colour Scanner at SCC, MOX, IDSN, Lucknow  4 Nos 

20  Laptop at BLR, Lucknow  2 Nos 

21  Power Cable (in metres)  1300 Metres 

22  4 core shielded cable (in metres)  1300 Metres 

23  8 core shielded cable (in metres)  1300 Metres 

24  PVC Conduit for cable laying (in metres)  1900 Metres 

25 Supply and Installation of additional items as in Annexure III  2 Lot 

26 Uninstallation and Reinstallation of existing items as given in Part C  2 Lot 

27 Training of personnel at SCC, Bangalore and Lucknow  2 Sessions 

28 

Hardware and Software requirement during Network Failure (As per 1.8 of Part‐B)  2 Lot 

29  Vehicle RFID Tag  120 Nos 

30  SS Pole for Vehicle Readers  8 Nos 

31 ID card printer supporting lamination Interface  2 Nos 

32 

Dual Lane Full height turnstile (through Buy‐Back scheme for the available turnstile gates)  5 Sets 

33  Cat 6 UTP LAN Cable Box(1000 Ft.)  100 Box 

34  UTP Patch Cords(1M)  400 Nos 

35  UTP Patch Cords(3M)  100 Nos 

Page 54: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 53 of 68

36  UTP Patch Cords(5M)  50 Nos 

37  UTP Patch Cords(10M)  50 Nos 

38  Information Outlets  624 Nos 

39  Loaded 24‐port 1U Modular Patch Panel  26 Nos 

40  3”X3” Dual port Face‐Plate  312 Nos 

41  3”X3” PVC Back‐Boxes  312 Nos 

42  1‐inch PVC Casing and capping  200 metres 

43  2‐inch PVC Casing and capping  150 metres 

44  2‐inch PVC Pipe  200 metres 

45  Conduit/Elbow/Joints  300 Nos 

46 Installation and Commissioning of Network Ports.  624 Port/ Point  

47 24‐Port PoE Switches with two transceivers  12 Nos 

48 Warranty for three years

(Give break‐up for three years) Per Year 

a Warranty for first year 1

b Warranty for second year 1

c Warranty for third year 1

49 Post  warranty  Comprehensive  AMC 

rates (Exclusive of taxes) per annum Per Year 

a 4th year  1

b 5th year  1

c 6th year  1

 

 

 

 

 

 

II) Post warranty Comprehensive AMC rates (Exclusive of taxes) per annum 

Page 55: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 54 of 68

Description  Supplier’s Confirmation 

4th year Yes/No

5th year Yes/No

6th year Yes/No

III) Commercial terms: 

Sl 

No 

Requirements Compliance Reasons/Statement for  Non‐Compliance

  Yes No  

1.  Validity of the offer (Six months)  

2.  Security Deposit  

(As per Article 5.2.8 of Part‐A) 

 

3.  Advance against submission of bank guarantee 

for an equal amount. 

(As per Article 6.0 of Part‐A) 

 

4.  Performance bank guarantee valid for a period 

38 months( Warranty period) 

(As per Article 6.0 of Part‐A) 

 

5.  Warranty for three years

(As per Article 11.0 of Part‐A) 

 

6.  Annual Maintenance Contract for 3 years after 

three years warranty period. 

(As per Article 12.0 of Part‐A) 

 

7.  Liquidated Damages 

(As per Article 14.0 of Part‐A) 

 

8.  Fall Clause 

(As per Article 17.0 of Part‐A) 

 

9.  Non‐Disclosure Agreement 

(As per Article 19.0 of Part‐A) 

 

 

 

Page 56: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 55 of 68

IV) Payment terms ( Bidder to specify): 

 

Place:                                                                                                                                                  SIGNATURE 

Date:                                                                                                                                                     NAME & DESIGNATION 

                                                                                                            SEAL OF ORGANISATION 

 

 

Page 57: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 56 of 68

 Annexure‐V 

PRICE BID 

BILL OF MATERIAL AND PRICE SCHEDULE 

 

I) Items to be considered for total cost of ownership 

Sl. 

No. Description  Make

Price 

per unit GST 

Installation, 

commissioning 

and testing 

Total 

Amount 

Per unit 

Quantity  Unit Total 

Cost 

1 Biometric Smart Card Readers (One for IN and One for Out) 

         34 Nos 

 

2 Vehicle Readers cum Controller (One for IN and One for Out) 

         10 Nos 

 

3  Hand Held Biometric Readers    2 Nos   

4  Boom Barriers    5 Nos   

5  LED Panel Display for Photo Flashing (21")    8 Nos   

6 Biometric Smart Card Reader for Second Level Entry (Technical Areas) IN 

         122 Nos 

 

7 Biometric Smart Card  Reader for Second Level Entry (Technical Areas) Out 

         122 Nos 

 

8  EM Lock for Single Door with Exit Switch    16 Nos   

9  EM Lock for Double Door with Exit Switch          

95 Nos  

10 

Integrated Web based Software (Licences for software as per section 4 of RFP to meet all module requirements of SCC, MOX, IDSN, Lucknow) 

         4

Licences 

 

11 Biometric Enrolment stations at SCC, MOX, IDSN, Lucknow. (Two at each location) 

         8 Nos 

 

12 Smart Card Personalizer at SCC, MOX, IDSN, Lucknow (Two at each location) 

         6 Nos 

 

13 Web Camera at SCC, MOX, IDSN, Lucknow (One ar each location) 

         

5 Nos 

 

14 Signature Pad with Pen at SCC, MOX, IDSN, Lucknow (Two sets at each location) 

         8 Nos 

 

Page 58: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 57 of 68

15  4K Mifare Smart Cards    1700 Nos   

16  Rack Mountable Servers (1U) at SCC    2 Nos   

17 DeskTop Systems for VMS, AMS & Photoflashing Operations at SCC, MOX, IDSN, Lucknow 

         8 Nos 

 

18  Laser Printer for VMS at SCC, MOX, IDSN, Lucknow  

         

4 Nos 

 

 

 

19 Flatbed A4 Size colour Scanner at SCC, MOX, IDSN, Lucknow 

         4 Nos 

 

20  Laptop at BLR,  Lucknow   2 Nos   

21  Power Cable (in metres)          

1300Metres 

 

22  4 core shielded cable (in metres)          

1300Metres 

 

23  8 core shielded cable (in metres)          

1300Metres 

 

24  PVC Conduit for cable laying (in metres)          

1900Metres 

 

25 Supply and Installation of additional items as in Annexure III 

         2 Lot 

 

26 Uninstallation and Reinstallation of existing items as given in Part C 

         2 Lot 

 

27  Training of personnel at SCC, Bangalore and Lucknow          

2Sessions 

 

28 Hardware and Sotfware requirement during Network Failure (As per 1.8 of Part‐B) 

         2 Lot 

 

29  Vehicle RFID Tag    120 Nos   

30  SS Pole for Vehicle Readers    8 Nos   

31  ID card printer supporting lamination Interface    2 Nos   

32 Dual Lane Full height turnstile (through Buy‐Back scheme for the available turnstile gates) 

         5 Sets 

 

33  Cat 6 UTP LAN Cable Box(1000 Ft.)    100 Box   

34  UTP Patch Cords(1M)    400 Nos   

35  UTP Patch Cords(3M)    100 Nos   

36  UTP Patch Cords(5M)    50 Nos   

Page 59: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 58 of 68

37  UTP Patch Cords(10M)    50 Nos   

38  Information Outlets    624 Nos   

39  Loaded 24‐port 1U Modular Patch Panel    26 Nos   

40  3”X3” Dual port Face‐Plate    312 Nos   

41  3”X3” PVC Back‐Boxes    312 Nos   

42  1‐inch PVC Casing and capping          

200metres 

 

43  2‐inch PVC Casing and capping          

150metres 

 

44  2‐inch PVC Pipe          

200metres

 

45  Conduit/Elbow/Joints    300 Nos   

46  Installation and Commissioning of Network Ports.          

624Port/ Point 

 

47  24‐Port PoE Switches with two transceivers    12 Nos   

48 Warranty for three years 

(Give break‐up for three years)           Per Year  

a  Warranty for first year    1  

b  Warranty for second year    1  

c  Warranty for third year    1  

49 Post  warranty  Comprehensive  AMC  rates 

(Exclusive of service taxes) per annum           Per Year  

a  4th year   1  

b  5th year   1  

c  6th year   1  

       

Grand total inclusive of all taxes and transportation.

 

Page 60: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 59 of 68

 

 

 

 

II) Post warranty Comprehensive AMC rates (Exclusive of service taxes) per annum 

 

Sl. NO. Description  Comprehensive AMC charges Service taxes Total Comprehensive AMC charges

1.  4th year 

2.  5th year 

3.  6th year 

 

Note:  

1. The prices quoted are inclusive of all taxes, duties and levies. 

2. The total cost of the ACS, the warranty for three years and post warranty comprehensive AMC rates for next 3 years will be 

taken into consideration for deciding the lowest quotation.  

 

 

Place:                                                                                                                                                                 SIGNATURE 

Date:                                                                                                                                                                  NAME & DESIGNATION 

                                                                                                                                       SEAL OF ORGANISATION 

Page 61: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 60 of 68

ANNEXURE – VI

Items to be supplied and Installation to be done at Bangalore SL No  Item Description  Quantity  Unit 

1 Biometric Smart Card Readers (One for IN and One for Out)  12  Nos 

a  SCC Main Entrance : 04 Nos       

b  MOX Main Entrance: 04 Nos       

d  IDSN Main Entrance: 04 Nos   

           

2 Vehicle Readers cum Controller (One for IN and One for Out)  6  Nos 

a  SCC Main Gate: 02 Nos       

b  IDSN Main Gate: 02 Nos       

c  MOX Main Gate: 02 Nos        

           

3  Hand Held Biometric Readers  6  Nos 

a  SCC Main Gate: 02 Nos       

b  MOX Main Gate: 02 Nos        

c  IDSN Main Gate: 02 Nos       

           

4  Boom Barriers  3  Nos

a  SCC Main Gate: 01 Nos       

b  MOX Main Gate: 01 No       

c  IDSN Main Gate: 01 Nos       

           

5 LED Panel Display for Photo Flashing (21")  6  Nos 

a  MOX Main Gate: 02 Nos        

b  IDSN Main Gate: 02 Nos       

c  SCC Main Entrance: 02 Nos        

           

6 Biometric Smart Card Reader for Second Level Entry (Technical Areas) IN  102  Nos 

a  SCC Area: 29 Nos       

b  MOX Area: 27 Nos       

d  IDSN Area: 38 Nos       

e  Spares: 8 Nos       

            

Page 62: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 61 of 68

SL No  Item Description  Quantity  Unit 

7 Biometric Smart Card  Reader for Second Level Entry (Technical Areas) Out  102  Nos 

       

a  SCC Area: 29 Nos       

b  MOX Area: 27 Nos       

d  IDSN Area: 38 Nos       

e  Spares: 8 Nos       

           

8  EM Lock for Single Door with Exit Switch  14  Nos 

a  MOX Area: 9 Nos       

c  IDSN Area: 3 Nos       

d  Spares: 2 Nos       

           

9  EM Lock for Double Door with Exit Switch  79  Nos 

a  SCC Area: 18 Nos       

b  MOX Area: 18 Nos       

d  IDSN Area: 35 Nos       

e  Spares: 8 Nos       

           

10 

Integrated Web based Software (Licences for software as per section 4 of RFP to meet all module requirements of SCC, MOX, IDSN)  3  Licences

           

11 Biometric Enrolment stations at SCC, MOX, IDSN. (Two at each location)  6  Nos 

        

12 Smart Card Personalizer at SCC, MOX, IDSN (Two at each location)  6  Nos 

           

  13 

Web Camera at SCC, MOX, IDSN (One ar each location)  3  Nos 

           

14 Signature Pad with Pen at SCC, MOX, IDSN (Two sets at each location)  6  Nos 

        

15  4K Mifare Smart Cards  1500  Nos 

        

16  Rack Mountable Servers (1U) at SCC  2  Nos 

           

       

Page 63: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 62 of 68

SL No  Item Description  Quantity  Unit 

17 

DeskTop Systems for VMS, AMS & Photoflashing Operations at SCC, MOX, IDSN  6  Nos 

        

18  Laser Printer for VMS at SCC, MOX, IDSN   3  Nos 

19 Flatbed A4 Size colour Scanner at SCC, MOX, IDSN   3  Nos 

           

20  Laptop at BLR  1  Nos 

        

21  Power Cable (in metres)  1000  Metres 

        

22  4 core shielded cable (in metres)  1000  Metres 

        

23  8 core shielded cable (in metres)  1000  Metres 

        

24  PVC Conduit for cable laying (in metres)  1500  Metres 

        

25 Supply and Installation of additional items as in Annexure III  1  lot 

        

26 Uninstallation and Reinstallation of existing items as given in Part C  1  lot 

        

27  Training of personnel at SCC, Bangalore  1  lot 

        

28 

Hardware and Sotfware requirement during Network Failure (As per 1.8 of Part‐B)  1  lot 

        

29  Vehicle RFID Tag  100  Nos 

        

30  SS Pole for Vehicle Readers  4  Nos 

a  MOX Main Gate: 02 Nos       

b  IDSN Main Gate: 02 Nos       

           

31 ID card printer supporting lamination Interface  1  Nos 

           

32 

Dual Lane Full height turnstile (through Buy‐Back scheme for the available turnstile gates)  6  sets 

Page 64: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 63 of 68

        

SL No  Item Description  Quantity  Unit 

33  Networking Elements       

a  Cat 6 UTP LAN Cable Box(1000 Ft.)  70  Box 

b  UTP Patch Cords(1M)  300  Nos 

c  UTP Patch Cords(3M)  50  Nos 

d  UTP Patch Cords(5M)  25  Nos 

       

SL No  Item Description  Quantity  Unit 

e  UTP Patch Cords(10M)  25  Nos 

f  Information Outlets  480  Nos 

g  Loaded 24‐port 1U Modular Patch Panel  20  Nos 

h  3”X3” Dual port Face‐Plate  240  Nos 

i  3”X3” PVC Back‐Boxes  240  Nos 

j  1‐inch PVC Casing and capping  150 per meter 

k  2‐inch PVC Casing and capping  100 per meter  

l  2‐inch PVC Pipe  150 per meter  

m  Conduit/Elbow/Joints  200  Nos 

n Installation and Commissioning of Network Ports.  480 

Each Port/ Point  

o 24‐Port PoE Switches with two transceivers  6  Nos 

Items to be supplied and Installation to be done at Lucknow 

SL No  Item Description Qty at 

Locations  Total Quantity  Unit 

1 Biometric Smart Card Readers (One for IN and One for Out) 4  No(s)

a  CISF Main Area  4      

           

2 Vehicle Readers cum Controller (One for IN and One for Out)     2  No(s) 

           

3  Hand Held Biometric Readers     2  No(s) 

           

4  Boom Barriers     1  No(s) 

Page 65: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 64 of 68

     

SL No  Item Description Qty at 

Locations  Total Quantity  Unit 

5 LED Panel Display for Photo Flashing (21")     2  No(s) 

           

6 Biometric with smart card readers ‐ Second Level Entry        

      20  No(s) 

a  10 Mtr Antenna Room  1      

b  11 Mtr Antenna Room  1      

c  UPS Room  1      

d  LUT Pedestal Room  1      

       

SL No  Item Description     Quantity  Unit 

e  TM Hall  1      

f  LUT Room  1      

g  ASCC Room  1      

h  FDO Scheduling Room  1      

i  INC Area          

IRIMS   1      

IRNWT  1      

FDO Scheduling Room  1      

Security Surveilance Room  1      

Server Room   2      

IRDCN ‐ Terracom  1      

IRDCN ‐ Satcom  1      

IRNSS Control Room  1      

UPS Room  1      

AC Room  1      

ASCC Control Room  1      

   20      

7 Biometric with smart card daughter readers      20  No(s) 

           

a  10 Mtr Antenna Room  1      

b  11 Mtr Antenna Room  1      

c  UPS Room  1      

d  LUT Pedestal Room  1      

e  TM Hall  1      

f  LUT Room  1      

g  ASCC Room  1      

       

Page 66: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 65 of 68

SL No  Item Description Qty at 

Locations  Total Quantity  Unit 

h  FDO Scheduling Room  1      

i  INC Area          

IRIMS   1      

IRNWT  1      

FDO Scheduling Room  1      

Security Surveilance Room  1      

Server Room   2      

IRDCN ‐ Terracom  1      

IRDCN ‐ Satcom  1      

IRNSS Control Room  1      

UPS Room  1      

AC Room  1      

ASCC Control Room  1      

   20      

           

SL No  Item Description     Quantity  Unit 

8 EM Lock for Single Door with Exit Switch at INC Area     2  No(s) 

           

9 EM Lock for Double Door with Exit Switch at INC Area     7  No(s) 

           

10 

Integrated Web based Software (Licences for software as per section 4 of RFP to meet all module requirements of Lucknow)     1  Licence

           

11 Biometric Enrolment stations at Lucknow     2  No(s) 

           

12  Web Camera at Lucknow     2  No(s) 

           

13  Signature Pad with Pen at Lucknow     2  No(s) 

           

14  4K Mifare Smart Cards     200  No(s) 

           

15 DeskTop Systems for VMS, AMS & Photoflashing Operations      2  No(s) 

            

Page 67: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 66 of 68

 

SL No  Item Description Qty at 

Locations  Total Quantity  Unit 

16  Laser Printer for VMS at Lucknow      1  No(s) 

           

17 Flatbed A4 Size colour Scanner at Lucknow      1  No(s) 

           

18  Laptop for A&M     1  No(s) 

           

20  Power Cable (in metres)     300  Metres 

           

21  4 core shielded cable (in metres)     300  Metres 

           

22  8 core shielded cable (in metres)     300  Metres 

           

23  PVC Conduit for cable laying (in metres)     400  Metres 

           

24 Supply and Installation of additional items as in Annexure III     1  lot 

           

25 Uninstallation and Reinstallation of existing items as given in Part C     1  lot 

           

26  Training of personnel at Lucknow     1  lot 

           

27 

Hardware and Sotfware requirement during Netowrk Failure (As per 1.8 of Part‐B)     1  lot 

           

28  Vehicle RFID Tag     10  No(s) 

           

29  SS Pole for Vehicle Readers     2  No(s) 

30 ID card printer supporting lamination Interface     1  No(s) 

           

31 

Dual Lane Full height turnstile (through Buy‐Back scheme for the available turnstile gates)     1  sets 

           

34  Networking Elements          

a  Cat 6 UTP LAN Cable Box(1000 Ft.)     20  Box 

b  UTP Patch Cords(1M)     80  Nos 

c  UTP Patch Cords(3M)     30  Nos 

Page 68: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 67 of 68

d  UTP Patch Cords(5M) 15  Nos

SL No  Item Description     Quantity  Unit 

e  UTP Patch Cords(10M)     15  Nos 

f  Information Outlets     96  Nos 

g  Loaded 24‐port 1U Modular Patch Panel     4  Nos 

h  3”X3” Dual port Face‐Plate     48  Nos 

i  3”X3” PVC Back‐Boxes     48  Nos 

j  1‐inch PVC Casing and capping     30  meter 

k  2‐inch PVC Casing and capping     30  meter 

l  2‐inch PVC Pipe  30  meter

m  Conduit/Elbow/Joints     50  Nos 

n Installation and Commissioning of Network Ports.     96 

Each Port/ Point  

o 24‐Port PoE Switches with two transceivers     3  Nos 

 

Items to be supplied and Installation to be done at Port Blair SL No  Item Description  Quantity  Unit 

1 Biometric Smart Card Readers (One for IN and One for Out)  18  Nos 

a  Main Entry: 02 Nos   

b  TM Hall: 02 Nos       

c  Electro Mechanical Facility: 02 Nos       

d  SHAR TC Antenna Room: 02 Nos       

e  Air‐condition Room: 02 Nos       

f  11 Mtr Antenna Room: 04 Nos       

g  Panel Room: 02 Nos       

h  UPS Room: 02 Nos       

           

       

2  EM Lock for Double Door with Exit Switch  9  Nos 

a  Main Entry: 01 No       

b  TM Hall: 01 No    

c  Electro Mechanical Facility: 01 No       

d  SHAR TC Antenna Room: 01 No       

e  Air‐condition Room: 01 No       

f  11 Mtr Antenna Room: 02 No       

g  Panel Room: 01 No       

h  UPS Room: 01 No       

Page 69: TECHNICAL SPECIFICATION AND REQUIREMENTS OF … · ISRO Telemetry Tracking and Command Network (ISTRAC), BANGALORE ISRO, Department of Space August – 2017 . ... A ‘Bank Solvency

Page 68 of 68

        

SL No  Item Description  Quantity  Unit 

3  Boom Barriers  1  No 

   Road: 01 No       

           

   4  Vehicle RFID Tag  10  Nos 

           

   5  Networking Elements       

a  Cat 6 UTP LAN Cable Box(1000 Ft.)  10  Box 

b  UTP Patch Cords(1M)  20  Nos 

c  UTP Patch Cords(3M)  20  Nos 

d  UTP Patch Cords(5M)  10  Nos 

e  UTP Patch Cords(10M)  10  Nos 

f  Information Outlets  48  Nos 

g  Loaded 24‐port 1U Modular Patch Panel  2  Nos 

h  3”X3” Dual port Face‐Plate  24  Nos 

i  3”X3” PVC Back‐Boxes  24  Nos 

j  1‐inch PVC Casing and capping  20  meter

k  2‐inch PVC Casing and capping  20  meter

l  2‐inch PVC Pipe  20  meter

m  Conduit/Elbow/Joints  50  Nos 

n Installation and Commissioning of Network Ports.  48 

Each Port/ Point  

o 24‐Port PoE Switches with two transceivers  3  Nos