August 2015 Project: Customer: Engineer: Pump Manufacturer: Model GPS Full Service Reduced Voltage Soft Start Soft Stop Electric Fire Pump Controller Technical Data Submittal Document Contents: • Data Sheets • Dimensional Data • Wiring Schematics • Field Connections Note: The drawings included in this package are for controllers covered under our standard offering. Actual AS BUILT drawings may differ from what is shown in this package. SEISMIC COMPLIANT ICC-ES AC156 IBC 2015 CBC 2013

Transcript of Technical Data Submittal Document - LiveActs · Technical Data Submittal Document Contents: •...

Page 1: Technical Data Submittal Document - LiveActs · Technical Data Submittal Document Contents: • Data Sheets ... ICC-ES AC156 IBC 2015 CBC 2013. Tecnical ata Model GP lectric Fire

August 2015

Project: Customer: Engineer: Pump Manufacturer:

Model GPS Full Service Reduced Voltage

Soft Start Soft StopElectric Fire Pump Controller

Technical Data Submittal Document

Contents:• Data Sheets • Dimensional Data• Wiring Schematics• Field Connections

Note: The drawings included in this package are for controllers covered under our standard offering. Actual AS BUILT drawings may differ from what is shown in this package.

SEISMIC COMPLIANT

ICC-ES AC156 IBC 2015CBC 2013

Page 2: Technical Data Submittal Document - LiveActs · Technical Data Submittal Document Contents: • Data Sheets ... ICC-ES AC156 IBC 2015 CBC 2013. Tecnical ata Model GP lectric Fire

Technical Data Model GPS Electric Fire Pump Controller

August 2015 2

Standard,Listings,

Approvals andCertifications

Built to NFPA 20 (latest edition)

Underwriters Laboratory (UL) • UL218 - Fire Pump Controllers• CSA C22.2 No. 14 Industrial Control Equipment

FM Global Class 1321/1323New York City Accepted for use in the City of New York by the Department of BuildingsSeismic Certification See page 5 for detailsOptional□ CE Mark Various EN, IEC & CEE directives and standards

Enclosure

Protection Rating□ Standard: NEMA 2 (IP31)Optional□ NEMA 12□ NEMA 3□ NEMA 3R□ NEMA 4

Accessories• Bottom entry gland plate• Lifting Lugs• Keylock handle

*Please see Disconnecting Means details on page 3.

□ NEMA 4X-304 sst painted□ NEMA 4X-304 sst brushed finish□ NEMA 4X-316 sst painted□ NEMA 4X-316 sst brushed finish

□ IP54□ IP55□ IP65□ IP66

Paint Specifications• Red RAL3002• Powder coating• Glossy textured finish

SEISMIC COMPLIANT

ICC-ES AC156 IBC 2015CBC 2013

MT2

T1

Soft Starter

3L1

3L2

3L3

1M

CR4

3L1

3L2

T31M

Across-the-line starting

Locked rotor current

Full load current

Percent of motor speed (%)

Line

cur

rent

% o

f ful

l loa

d

20 40 60 80 100

600

Typical soft-startcurrent range

150

GPS

From normalincoming power throughDisconnecting Means(IS/CB)*

Starting Method: Reduced Voltage Soft start soft stopTypical Voltage Applied at Start: 30%Inrush Current: 30% (adjustable)Starting Torque: 30%Motor Type: Across the line (direct on line)No. of Contactors: 1 at 100% of horsepowerMin. ampacity of motor conductors: 3 at 125% x 100% of Full Load Current (FLC)

Page 3: Technical Data Submittal Document - LiveActs · Technical Data Submittal Document Contents: • Data Sheets ... ICC-ES AC156 IBC 2015 CBC 2013. Tecnical ata Model GP lectric Fire

Technical Data Model GPS Electric Fire Pump Controller

August 2015 3

Surge Suppression Surge arrestor rated to suppress surges above line voltage

Disconnecting Means

• Isolating switch and circuit breaker assembly:- Door interlocked in the ON position - Isolating switch rated not less than 115% of motor full load current- Circuit breaker continuous rating not less than 115% of motor full load current- Overcurrent sensing non-thermal type, magnetic only- Instantaneous trip setting of not more than 20 times the motor full load current

• Common flange mounted operating handle Service Entrance

Rating Suitable as service entrance equipment

Emergency Start Handle

• Flange mounted • Integrated limit switch• Pull and latch activation • Across the line start (direct on line)

Locked Rotor Protector

• Operate shunt trip to open circuit breaker • Trip between 8 and 20 seconds• Factory set at 600% of motor full load current

Electrical Readings

• Voltage phase to phase (normal power)• Amperage of each phase when motor is running

Pressure Readings

• Continuous system pressure display• Cut-in and Cut-out pressure settings

Pressure and Event recorder

• Pressure readings with date stamp• Event recording with date stamp• Under regular maintained operation, events can be stored in memory for up to 5 years.• Data viewable on operator interface display screen• Downloadable by USB port to external memory device

Pressure Sensing

• Pressure transducer and run test solenoid valve assembly for fresh water application• Pressure sensing line connection 1/2” Female NPT• Drain connection 3/8”• Rated for 0-500PSI working pressure (calibrated at 0-300psi)• Externally mounted with protective cover

Ambient Temperature

Rating

Standard: □ 5°C to 40°C / 41°F to 104°F

Optional: □ 5°C to 50°C / 41°F to 122°F □ 5°C to 55°C / 41°F to 131°F

Shortcircuit Withstand

Rating

200V to 208V 60Hz

220V to 240V 60Hz

380V to 416V 50 Hz / 60Hz

440V to 480V 60Hz

575V to 600V 60Hz

HP (kw)

� Standard 100kA5-150 (3.7 - 110) 5-200 (3.7 - 147) 5-300 (3.7 - 220) 5-450 (3.7 - 335) n/a

� Optional 150kA

� Standard 50kA 200 (147) 250 (184) 350 - 450 (257 - 335) 500 (373) 5-500 (3.7- 373)� Optional 100kA n/a n/a n/a n/a

Page 4: Technical Data Submittal Document - LiveActs · Technical Data Submittal Document Contents: • Data Sheets ... ICC-ES AC156 IBC 2015 CBC 2013. Tecnical ata Model GP lectric Fire

Technical Data Model GPS Electric Fire Pump Controller

August 2015 4

Audible Alarm 4” alarm bell - 85 dB at 10ft. (3m)

Visual Indications & Alarms

• Power available• Phase reversal• Motor run• Pump room alarm• Motor trouble• Phase loss• Phase unbalance• Low water level

Remote Alarm Contacts

SPDT-8A-250V.AC• Power available• Phase reversal• Motor run• Common pump room alarm (field re-assignable)**

• Overvoltage • Undervoltage • Phase unbalance• Low pump room temperature • High Pump room temperature

• Common motor trouble (field re-assignable)**• Overcurrent • Fail to start• Undercurrent • Ground fault

• Free (field programmable)**

ViZiTouch Operator Interface

• Embedded microcomputer with software PLC logic• 4.2” color touch screen (HMI technology)• Upgradable software• Expandable storage• Multi-language

Communication Protocol

Capability

• Protocol: Modbus• Connection type: Shielded female connector RJ45• Frame Format: TCP/IP• Addresses: See bulletin MOD-GPx

Operation

Automatic Start • Start on pressure drop• Remote start signal from automatic device

Manual Start

• Start pushbutton• Run test pushbutton• Deluge valve start• Remote start from manual device

Stopping • Manual with Stop pushbutton• Automatic after expiration of minimum run timer ***

Timers Field Adjustable & Visual Countdown

• Minimum run timer ***(off delay)• Sequential start timer (on delay)• Periodic test timer

ActuationVisual Indication

• Pressure• Non-pressure

Mode • Automatic• Non-automatic

• Manual start • Deluge valve start• Remote automatic start• Remote manual start• Overcurrent • Undercurrent• Undervoltage• Overvoltage

• Locked rotor• Periodic test• Fail to start• Low discharge pressure• Low pump room temperature • Pump room temperature (ºF or ºC)• Pump on demand/Automatic start• Emergency start

**Tornatech reserves the right to use any of these three alarm points for special specific application requirements.***Can only be used if approved by the AHJ

Page 5: Technical Data Submittal Document - LiveActs · Technical Data Submittal Document Contents: • Data Sheets ... ICC-ES AC156 IBC 2015 CBC 2013. Tecnical ata Model GP lectric Fire

Technical Data Model GPS Electric Fire Pump Controller

August 2015 5

Seismic Certification

Seismic Certification Company

TRU Compliance, LLCA Tobalski Watkins Affiliate TWEI Project No.: 2014-0906-CO-001

Mounting details Rigid base and wall mounting

Seismic Information

Building Code

Test Criteria SDS z/h IP AFLX-H ARIG-H AFLX-V ARIG-V

IBC 2015, CBC 2013

ICC-ES AC156

2.0 1.0 1.5 3.20 2.40 1.33 0.53

3.2 0.0 1.5 3.20 1.28 2.13 0.85

0.1

1.0

10.0

0.1 1.0 10.0

Spe

ctra

l Res

pons

e A

ccel

erat

ion

(g)

Frequency, f (Hz)

RRS for Nonstructural Components Testing

Horiz. Level 1 Vert. Level 1

Note: Components are tested in accordance with ICC-ES AC156, IBC 2015 & CBC 2013. CBC compliance is not applicable to OSHPD 1 & 4 buildings.

Page 6: Technical Data Submittal Document - LiveActs · Technical Data Submittal Document Contents: • Data Sheets ... ICC-ES AC156 IBC 2015 CBC 2013. Tecnical ata Model GP lectric Fire

Technical Data Model GPS Electric Fire Pump Controller

August 2015 6

A4 Flow switch provision

A8 Foam pump application w/o pressure transducer and run test solenoid valve

A9 Low zone pump control function

A10 Middle zone pump control function

A11 High zone pump control function

A13 Non-pressure actuated controller w/o pressure transducer and run test solenoid valve

A16 Lockout/interlock circuit from equipment installed inside the pump room

B11

Built in alarm panel (120V.AC supervisory power) providing indication for:• Audible alarm & silence pushbutton for motor run, phase reversal, loss of phase.• Pilot lights for loss of phase & supervisory power available

B11BBuilt in alarm panel same as B11 but 220-240VAC supervisory power

B19 High motor temperature thermistor relay c/w visual indication and alarm contact (Form C-SPDT)

B21 Ground fault alarm detection c/w visual indication and alarm contact (Form C-SPDT)

C1 Extra motor run alarm contact (Form C-SPDT)

C4 Periodic test alarm contact (Form C-SPDT)

C6 Low discharge pressure alarm contact (Form C-SPDT)

C7 Low pump room temperature alarm contact (Form C-SPDT)

C10 Low water reservoir level alarm contact (Form C-SPDT)

C11 High electric motor temperature alarm contact (Form C-SPDT)

C12 High electric motor vibration c/w visual indication and alarm contact (Form C-SPDT)

C14 Pump on demand/automatic start alarm contact(Form C-SPDT)

C15 Pump fail to start alarm contact (Form C-SPDT)

C16 Control voltage healthy alarm contact (Form C-SPDT)

C17 Flow meter valve loop open c/w visual indication and alarm contact (Form C-SPDT)

C18 High water reservoir level c/w visual indication and alarm contact (Form C-SPDT)

C19 Emergency start alarm contact (Form C-SPDT)

C20 Manual start alarm contact (Form C-SPDT)

C21 Deluge valve start alarm contact (Form C-SPDT)

C22 Remote automatic start alarm contact (Form C-SPDT)

C23 Remote manual start alarm contact (Form C-SPDT)

C24 High pump room temperature alarm contact (Form C-SPDT)

Cx Additional visual and alarm contact (specify function) (Form C-SPDT)

D1 Low suction pressure transducer for fresh water rated at 0-300PSI with visual indication and alarm contact

D1A Low suction pressure transducer for sea water rated at 0-300PSI with visual indication and alarm contact

D5 Pressure transducer and run test solenoid valve for fresh water rated for 0-500PSI (for calibration purposes only)

D5D Pressure transducer and run test solenoid valve for sea water rated for 0-500PSI

D10 Omit mounting feet (when applicable)

D13High withstand rating for:• 208V to 480V = 150kA• 600V = 100kA

D14 Anti-condensation heater & thermostat

D14A Anti-condensation heater & humidistat

D14B Anti-condensation heater & thermostat & humidistat

D15 Tropicalization

D18 CE Mark with factory certificate

D26 Modbus with RTU frame format and RS485 connection

D27 Motor heater connection (external single phase power source and heater on/off contact)

D27A Motor heater connection (internal single phase power source and heater on/off contact)

D28 Customized drawing set

D34 Field programmable I/O board - 8 Input / 5 output

D35 Field programmable I/O board - 8 Input / 10 output

D36 Redundant pressure transducer for fresh water rated for 0-500PSI (calibrated at 0-300PSI)

D36A Redundant pressure transducer for sea water rated for 0-500PSI (calibrated at 0-300PSI)

D37 Window kit for operator interface

Note: Options chosen from this page are not electrically represented on the wiring schematics in this submittal package.

Page 7: Technical Data Submittal Document - LiveActs · Technical Data Submittal Document Contents: • Data Sheets ... ICC-ES AC156 IBC 2015 CBC 2013. Tecnical ata Model GP lectric Fire

Technical Data Model GPS Electric Fire Pump Controller

August 2015 7

L01 Other language and English (bilingual)

L02 French

L03 Spanish

L04 German

L05 Italian

L06 Polish

L07 Romanian

L08 Hungarian

L09 Slovak

L10 Croatian

L11 Czech

L12 Portuguese

L13 Dutch

L14 Russian

L15 Turkish

L16 Swedish

L17 Bulgarian

L18 Thai

L19 Indonesian

L20 Slovenian

L21 Danish

L22 Greek

L23 Arabic

L24 Hebrew

L25 Chinese

Note: Options chosen from this page are not electrically represented on the wiring schematics in this submittal package.

Page 8: Technical Data Submittal Document - LiveActs · Technical Data Submittal Document Contents: • Data Sheets ... ICC-ES AC156 IBC 2015 CBC 2013. Tecnical ata Model GP lectric Fire

Technical Data Model GPS Electric Fire Pump Controller

August 2015 8

??

4

9

11 12

10

13

5 6 7

3

2

1

88

PMS 295 PMS 361 Noir

ViZiTouch Operator Interface

1 - Power on LED2 - Color touch screen3 - Alarm LED4 - HOME page button 5 - ALARM page button6 - CONFIGURATION page button7 - HISTORY page button

8 - USB port9 - START button10 - Contextual navigation pad11 - STOP button12 - RUN TEST button13 - HELP button

Page 9: Technical Data Submittal Document - LiveActs · Technical Data Submittal Document Contents: • Data Sheets ... ICC-ES AC156 IBC 2015 CBC 2013. Tecnical ata Model GP lectric Fire

54" [1372]52 3/4" [1340]

56 3/8" [1433]57 3/8" [1456]

65 7/8" [1675]65 7/8" [1675]

Ø3/8" [Ø10] X4

68" [1727]

69 1/8" [1756]

18" [457]

21 3/4" [552]

Ø7/8" [Ø23] X2

22 5/8" [576]

62" [1575]

56" [1422]58" [1473]

11" [279]

NormalPower and

Motor LeadsEntrance

27" [686]

3 1/2" [89]

10" [255]11 5/8" [294]

1 1/4" [31]

Dimensions Built to the latest edition of the NFPA 20 standard

DD/MM/YYDESCRIPTIONREV.NYC

Dpt of BuildingApproved

Voltage Min HP Max HP

208 150

220 - 240 200

380 - 400 - 415 300

440 - 480 350 400

600 450 500

10 GENERAL REVISION 16/06/14

Drawing number

Model:GPS

Projection

Voltage / Power Table

Drawing for information only.Manufacturer reserves the right to modify this drawing without notice.Contact manufacturer for "As Built" drawing.

Electric Fire Pump Controller

16" [406]

1" [25]

1" [25]

11" [279]

See Notes

Notes:

- Protect Equipment Against Drilling Chips.- Door Swing Equal to Door Width.

- Use Watertight Conduit and Connector Only.- Bottom Conduit Entrance Through Removable Gland Plate Recommended.

- Standard Paint : Textured Red RAL 3002.- All Dimensions are in Inches [Millimeters].

- Standard NEMA: NEMA 2

- Center of ViZiTouch Screen: 62-5/8" [1589] from Bottom.

Ø1/2" [Ø13] X4

Sensing Line Connection - 1/2 " F.NPT

Drain - 3/8 " M.TUBE

1" [25] Adjustable Feet

27 5/8" [702] 21 3/4" [551]

DI331 /EGPX-11 ADDED SEISMIC LOGO 21/08/15

Page 10: Technical Data Submittal Document - LiveActs · Technical Data Submittal Document Contents: • Data Sheets ... ICC-ES AC156 IBC 2015 CBC 2013. Tecnical ata Model GP lectric Fire

3L1

3L3

3L2

Power

Available

Phase

Reversal

Common

Pump Room

Motor

Trouble

Alarm

Motor

Running

IS CB

1L1

1L2

1L3

SA

3 2

ST

CT1

CT3

CT2

* Contact closed when Emergency Start is in ON position

J40

TB14

J42

J37

J39

Common

11

12

14

J19 J18

J41

11

14

12

J36

J38

AI4-IN

(-)

(+)

J14

J15

J16

J17

PT1

Black

Red

White

SV1

N

G

J43

GND

ST2

J45

2

3

To shunt trip

+

REC

GND

J44

N

L

J47

24VAC

3

1

3L1

3L2

XTR1

X1

X2

H2

H1

3

1

J8

6

5

7

J57

3

2

4

1

6

5

7

J76

3

2

4

1

8

31

32

30

J25

34

35

33

36

29

23

27

25

21

24

22

26

28

2

1

J53

J1

I/O RELAY BOARD

P1

37

38

AI3-IN

(-)

(+)

PT1-IN

(-)

(+)

PT2-IN

(-)

(+)

TB1

TB2

TB3

TB4

TB5

Pressure

transducer

type 0-5V

P2

DI0

CO

M

CO

M

J14

DI1

CO

M

DI2

CO

M

DI3

CO

M

DI4

CO

M

DI5

CO

M

DI6

CO

M

DI7

24V

GN

D

J13

(+)

(-)

J16

J6

RS485

P1

J3

J11

MAIN BOARD

LOCKOUT

REMOTE

MANUAL START

DELUGE

VALVE

WATER RESERVOIR

LOW

REMOTE

AUTOMATIC START

TM1

VIZITOUCH

J2*

J1*

* REMOVE JUMPER TO USE THIS FEATURE

11

12

14

11

12

14

11

12

14

11

12

14

11

12

14

11

12

14

Wiring schematic

Built to the latest edition of the NFPA 20 standard

DD/MM/YYDESCRIPTIONREV.NYC

Dpt of Building

Approved

Drawing number

Electric Fire Pump Controller

Model:GPS

WS500 /EGPS-

Drawing for information only.

Manufacturer reserves the right to modify this drawing without notice.

Contact manufacturer for "As Built" drawing.

1M*

1M

3L2

3L1

17

CR5

A1

SSS 3RW4024 to 3RW4047

X2 X1

H1 H2

3L1 3L2

A2

XTR4

95

96

98

CR4

14/24

23

13

1

COMMON

BYPASS

ON / RUN

NC

NO

OVERLOAD / FAILURE

49

120V

SSS

195

198

46

47

CR5

50

198

195

47

46

Instant

Stop

SSS FAULT

Reduced Voltage / Soft Starter

11

14

12

4

Added Seismic Logo

19/08/15

3 General Revision07/01/15

To J45

Bla

ck

Wh

ite

Wh

ite

Re

d

Bla

ck

Bla

ck

Wh

ite

Wh

ite

Bla

ck

64

65

66

67

68

69

68

67

65

64

66

69

To J76

LS1*

AB1

+ -Red

SV1

Blue

Brown

Green / Yellow

SV1-1

SV1-2

LS1-2

LS1-1

To J57

To CT1-2-3

To 3L1-2-3

3L3

3L2

3L1

Black

Red

Black

CR5

CR5-1

CR5-2

CR4

CR4-1

CR4-2

Probe 1

Temperature

1M

1M

CR4

CR4

1M-1

1M-2

1M-3 1M-4

44

Page 11: Technical Data Submittal Document - LiveActs · Technical Data Submittal Document Contents: • Data Sheets ... ICC-ES AC156 IBC 2015 CBC 2013. Tecnical ata Model GP lectric Fire

Terminals Diagram and Sizing

Built to the latest edition of the NFPA 20 standard

DD/MM/YYDESCRIPTIONREV.NYC

Dpt of Building

Approved

5 General Revision09/01/15

Drawing number

Electric Fire Pump ControllerModel:GPX

TD500 1/3 /EGPX-

Drawing for information only.

Manufacturer reserves the right to modify this drawing without notice.

For drawing for approval or installation, please contact manufacturer.

GPA, GPR & GPS

M

Gnd

T1 T2 T3

1M

Incoming Power

3 Phases

Bonding

Gnd

L2L1

IS

Ground

L3

Power Terminals

Notes:

1 - For proper wire sizing, refer to NFPA70 and NEC (USA) or CEC

(Canada) or local code.

2 - Controller suitable for service entrance in USA.

3 - For more accurate motor connections refer to motor manufacturer or

motor nameplate.

4 - Controller is phase sensitive. Incoming lines must be connected in ABC

sequence.

5 - Field wiring and lug sizes base on copper conductors only.

Do not use aluminium conductors.

Models :

5 7.5 10 15 20 25

220 to 240

380 to 416

600

440 to 480

208

1x (10)

30 40 50 60

75 100 125 150 200 250 300 350 400 450 500

1x (14 to 10)

1x (14 to 10)

1x (14 to 10)

1x (12 to 10)

1x (14 to 10)

1x (14 to 10)

1x (12 to 10)

1x (10)

1x (10)

1x (14 to 10)

1x (12 to 10)

1x (10)

1x (8 to 2)

1x (8 to 2)

1x ( 10)

1x (10)

1x (8 to 2)

1x (6 to 2)

1x (6 to 2)

1x (10)

1x (8 to 2)

1x (8 to 2)

1x (4 to 1/0)

1x (4 to 1/0)

1x (8 to 2)

1x (8 to 2)

1x (6 to 2)

1x (4 to 1/0)

1x (3 to 1/0)

1x (8 to 2)

1x (6 to 2)

1x (6 to 1/0)

1x (3 to 1/0)

1x (2 to 1/0)

1x (6 to 2)

1x (6 to 2)

1x (4 to 1/0)

1x (1 to 3/0)

1x (1/0 to 3/0)

1x (6 to 2)

1x (4 to 1/0)

1x (3 to 1/0)

1x (2/0 to 3/0)

1x (3/0)

1x (4 to 1/0)

1x (3 to 1/0)

1x (3 to 1/0)

1x (3/0)

1x (4/0 to 300)

1x (3 to 1/0)

1x (1 to 2/0)

1x (1/0 to 3/0)

1x (250 to 300)

1x (300)

1x (1 to 2/0)

1x (2/0 to 3/0)

1x (3/0)

2x (2/0 to 300)

2x (2/0 to 300)

1x (3/0)

1x (2/0 to 3/0)

1x (250 to 300)

2x (3/0 to 300)

2x (4/0 to 300)

1x (3/0)

1x (4/0 to 300)

1x (300)

2x (4/0 to 300)

2x (250 to 300)

1x (250 to 300)

2x (1/0 to 300)

2x (3/0 to 300)

2x (350 to 500)

2x (2/0 to 300)

2x (3/0 to 300)

2x (4/0 to 300)

2x (3/0 to 300)

2x (4/0 to 300)

2x (300)

--------

--------

--------

2x (4/0 to 300)

2x (300)

--------

--------

2x (250 to 300)

--------

--------

2x (300)

--------

--------

--------

--------

220 to 240

380 to 416

600

440 to 480

208

5 7.5 10 15 20 25

220 to 240

380 to 416

600

440 to 480

208

1x (10 to 1/0)

30 40 50 60

75 100 125 150 200 250 300 350 400 450 500

1x (8 to 1/0)

1x (6 to 1/0)

1x (4 to 1/0)

1x (3 to 1/0)

1x (4 to 1/0)

1x (3 to 1/0)

1x (3 to 1/0)

1x (3 to 1/0)

1x (1 to 250)

1x (1/0 to 250)

1x (250 to 500)

1x (300 to 500)

1x (1 to 250)

1x (2/0 to 250)

1x (3/0 to 250)

1x (350 to 500)

1x (500)

1x (3/0 to 250)

1x (2/0 to 250)

1x (250)

2x (3/0 to 500)

2x (4/0 to 500)

1x (3/0 to 250)

1x (4/0 to 250)

1x (300 to 500)

2x (4/0 to 500)

2x (250 to 500)

1x (250 to 500)

1x (350 to 500)

2x (3/0 to 250)

1x (350 to 500)

2x (3/0 to 250)

2x (4/0 to 500)

2x (3/0 to 250)

2x (4/0 to 500)

2x (300 to 500)

--------

--------

--------

2x (4/0 to 500)

2x (300 to 500)

--------

--------

2x (250 to 500)

--------

--------

2x (300 to 500)

--------

--------

--------

--------

--------

220 to 240

380 to 416

600

440 to 480

208

5 " (127 mm) 8 " (203 mm)

12 " (305 mm)

5 " (127 mm) 8 " (203 mm) 12 " (305 mm)

1x (10 to 1/0)

1x (10 to 1/0)

1x (10 to 1/0)

1x (10 to 1/0)

1x (10 to 1/0)

1x (10 to 1/0)

1x (10 to 1/0)

1x (10 to 1/0)

1x (10 to 1/0)

1x (10 to 1/0)

1x (10 to 1/0)

1x (8 to 1/0)

1x (8 to 1/0)

1x (10 to 1/0)

1x (10 to 1/0)

1x (8 to 1/0)

1x (6 to 1/0)

1x (6 to 1/0)

1x (10 to 1/0)

1x (8 to 1/0)

1x (8 to 1/0)

1x (4 to 1/0)

1x (4 to 1/0)

1x (8 to 1/0)

1x (8 to 1/0)

1x (6 to 1/0)

1x (4 to 1/0)

1x (3 to 1/0)

1x (8 to 1/0)

1x (6 to 1/0)

1x (6 to 1/0)

1x (3 to 1/0)

1x (2 to 1/0)

1x (4 to 1/0)

1x (6 to 1/0)

1x (6 to 1/0)

1x (1 to 250)

1x (1/0 to 250)

1x (2/0 to 250)

1x (3/0 to 250)

1x (3/0 to 250)

1x (4/0 to 250)

2x (350 to 500)

2x (350 to 500)

2x (350 to 500)

2x (350 to 500)

2x (350 to 500)

Wiring Size for motor connection for Models GPA, GPR & GPS (AWG or MCM). TERMINALS T1 - T2 - T3

Voltage

Isolating Switch (IS) Field Wiring according to Bending Space (AWG or MCM). TERMINALS L1 - L2 - L3

Bending

Space

HP

HP

HP

HP

(Use Copper Conductors Only)

(Use Copper Conductors Only)

2x (400 to 500)

2x (400 to 600)

2x (500 to 600)

2x (500 to 600) 2x (600)

2x (400 to 600) 2x (500 to 600)

2x (400 to 500)

16 " (406 mm)

2x (400 to 600)

2x (400 to 500)

2x (500 to 600)

2x (500 to 600) 2x (600)

2x (400 to 600) 2x (500 to 600)

Bending

Space

Bending

Space

Voltage

Bending

Space

Voltage

Voltage

6

Added Seismic Logo

19/08/15

Page 12: Technical Data Submittal Document - LiveActs · Technical Data Submittal Document Contents: • Data Sheets ... ICC-ES AC156 IBC 2015 CBC 2013. Tecnical ata Model GP lectric Fire

Terminals Diagram and Sizing

Built to the latest edition of the NFPA 20 standard

DD/MM/YYDESCRIPTIONREV.NYC

Dpt of Building

Approved

5 General Revision09/01/15

Drawing number

Electric Fire Pump ControllerModel:GPX

TD500 2/3 /EGPX-

Drawing for information only.

Manufacturer reserves the right to modify this drawing without notice.

For drawing for approval or installation, please contact manufacturer.

GPP

Notes:

1 - For proper wire sizing, refer to NFPA70 and NEC (USA) or CEC

(Canada) or local code.

2 - Controller suitable for service entrance in USA.

3 - For more accurate motor connections refer to motor manufacturer or

motor nameplate.

4 - Controller is phase sensitive. Incoming lines must be connected in ABC

sequence.

5 - Field wiring and lug sizes base on copper conductors only.

Do not use aluminium conductors.

Models :

M

Gnd

T7 T8 T9

2M

Incoming Power

3 Phases

Bonding

Gnd

L2L1

IS

Ground

L3

T1 T2 T3

1M

M

Gnd

T6 T4 T5

2M

Incoming Power

3 Phases

Bonding

Gnd

L2L1

IS

Ground

L3

T1 T2 T3

1M

Power Terminals

GPW & GPYModels :

5 7.5 10 15 20 25

220 to 240

380 to 416

600

440 to 480

208

1x (14 to 10)

30 40 50 60

75 100 125 150 200 250 300 350 400 450 500

1x (14 to 10)

1x (14 to 10)

1x (14 to 10)

1x (14 to 10)

1x (14 to 10)

1x (14 to 10)

1x (14 to 10)

1x (12 to 10)

1x (12 to 10)

1x (14 to 10)

1x (14 to 10)

1x (14 to 10)

1x (10)

1x (10)

1x (14 to 10)

1x (12 to 10)

1x (12 to 10)

1x (8 to 2)

1x (8 to 2)

1x (12 to 10)

1x (12 to 10)

1x (10)

1x (8 to 2)

1x (8 to 2)

1x (12 to 10)

1x (10)

1x (10)

1x (6 to 2)

1x (6 to 2)

1x (10)

1x (10 to 2)

1x (8 to 2)

1x (6 to 1/0)

1x (6 to 1/0)

1x (10 to 2)

1x (8 to 2)

1x (6 to 2)

1x (4 to 2/0)

1x (4 to 2/0)

1x (8 to 2)

1x (6 to 2)

1x (6 to 2)

1x (3 to 2/0)

1x (2 to 3/0)

1x (8 to 2)

1x (6 to 2)

1x (4 to 1/0)

1x (2 to 3/0)

1x (1 to 3/0)

1x (6 to 2)

1x (4 to 2/0)

1x (4 to 2/0)

1x (1/0 to 3/0)

1x (2/0 to 3/0)

1x (4 to 2/0)

1x (3 to 2/0)

1x (2 to 2/0)

1x (3/0)

1x (3/0)

1x (2 to 3/0)

1x (3 to 2/0)

1x (1/0 to 3/0)

1x (4/0 to 300)

1x (250 to 300)

1x (2 to 3/0)

1x (1/0 to 3/0)

1x (2/0 to 3/0)

1x (300)

2x (1/0 to 300)

1x (1/0 to 3/0)

1x (2/0 to 3/0)

2x (2/0 to 300)

1x (2/0 to 3/0)

1x (300)

1x (300)

2x (2/0 to 300)

--------

--------

--------

1x (250 to 300)

2x (1/0 to 300)

--------

--------

1x (300)

2x (2/0 to 300)

--------

--------

2x (1/0 to 300)

--------

--------

2x (2/0 to 300)

--------

--------

--------

220 to 240

380 to 416

600

440 to 480

208

5 7.5 10 15 20 25

220 to 240

380 to 416

600

440 to 480

208

1x (10 to 1/0)

30 40 50 60

75 100 125 150 200 250 300 350 400 450 500

1x (8 to 1/0)

1x (6 to 1/0)

1x (4 to 1/0)

1x (3 to 1/0)

1x (4 to 1/0)

1x (3 to 1/0)

1x (3 to 1/0)

1x (3 to 1/0)

1x (1 to 250)

1x (1/0 to 250)

1x (250 to 500)

1x (300 to 500)

1x (1 to 250)

1x (2/0 to 250)

1x (3/0 to 250)

1x (350 to 500)

1x (500)

1x (3/0 to 250)

1x (2/0 to 250)

1x (250)

2x (3/0 to 500)

2x (4/0 to 500)

1x (3/0 to 250)

1x (4/0 to 250)

1x (300 to 500)

2x (4/0 to 500)

2x (250 to 500)

1x (250 to 500)

1x (350 to 500)

2x (3/0 to 250)

1x (350 to 500)

2x (3/0 to 250)

2x (4/0 to 500)

2x (3/0 to 250)

2x (4/0 to 500)

2x (300 to 500)

--------

--------

--------

2x (4/0 to 500)

2x (300 to 500)

--------

--------

2x (250 to 500)

--------

--------

2x (300 to 500)

--------

--------

--------

--------

--------

220 to 240

380 to 416

600

440 to 480

208

5 " (127 mm) 8 " (203 mm)

12 " (305 mm)

5 " (127 mm) 8 " (203 mm) 12 " (305 mm)

1x (10 to 1/0)

1x (10 to 1/0)

1x (10 to 1/0)

1x (10 to 1/0)

1x (10 to 1/0)

1x (10 to 1/0)

1x (10 to 1/0)

1x (10 to 1/0)

1x (10 to 1/0)

1x (10 to 1/0)

1x (10 to 1/0)

1x (8 to 1/0)

1x (8 to 1/0)

1x (10 to 1/0)

1x (10 to 1/0)

1x (8 to 1/0)

1x (6 to 1/0)

1x (6 to 1/0)

1x (10 to 1/0)

1x (8 to 1/0)

1x (8 to 1/0)

1x (4 to 1/0)

1x (4 to 1/0)

1x (8 to 1/0)

1x (8 to 1/0)

1x (6 to 1/0)

1x (4 to 1/0)

1x (3 to 1/0)

1x (8 to 1/0)

1x (6 to 1/0)

1x (6 to 1/0)

1x (3 to 1/0)

1x (2 to 1/0)

1x (4 to 1/0)

1x (6 to 1/0)

1x (6 to 1/0)

1x (1 to 250)

1x (1/0 to 250)

1x (2/0 to 250)

1x (3/0 to 250)

1x (3/0 to 250)

1x (4/0 to 250)

2x (350 to 500)

2x (350 to 500)

2x (350 to 500)

1x (4/0 to 300)

1x (4/0 to 300)

1x (4/0 to 300)

Wiring Size for motor connection for Models GPP, GPW & GPY (AWG or MCM). TERMINALS T1 - T2 - T3 - T4 - T5 - T6 - T7 - T8 - T9

HP

HP

HP

HP

2x (3/0 to 300)

2x (3/0 to 350)

2x (4/0 to 350)

2x (4/0 to 350) 2x (4/0 to 350)

2x (3/0 to 350) 2x (4/0 to 350)

2x (400 to 500)

2x (400 to 600)

2x (500 to 600)

2x (500 to 600) 2x (600)

2x (400 to 600) 2x (500 to 600)

2x (400 to 500)

Voltage

Isolating Switch (IS) Field Wiring according to Bending Space (AWG or MCM). TERMINALS L1 - L2 - L3

Bending

Space

(Use Copper Conductors Only)

(Use Copper Conductors Only)

Bending

Space

Bending

Space

Voltage

Bending

Space

Voltage

Voltage

16 " (406 mm)

6

Added Seismic Logo

19/08/15

Page 13: Technical Data Submittal Document - LiveActs · Technical Data Submittal Document Contents: • Data Sheets ... ICC-ES AC156 IBC 2015 CBC 2013. Tecnical ata Model GP lectric Fire

Terminals Diagram and Sizing

Built to the latest edition of the NFPA 20 standard

DD/MM/YYDESCRIPTIONREV.NYC

Dpt of Building

Approved

5 General Revision09/01/15

Drawing number

Electric Fire Pump ControllerModel:GPX

TD500 3/3 /EGPX-

Control Terminals (I/O board)

Close to start pump

23

24

J25

Remote Manual Start

Open to start pump

27

28

J25

Automatic Start

Signal

Deluge

Valve

Open to start pump

29

30

J25

Deluge Valve

Signal

Water Reservoir

Low

Close to signal alarm

31

32

J25

Water Reservoir Low

Signal

Flow / Zone

Start / Stop

33

34

J25

Flow / Zone

(I/O board)

Close to signal alarm

Signal

Lockout

Close to block start

25

26

J25

Lockout

J1

If used, remove jumper J1

J2

If used, remove jumper J2

Filed Connections for External Devices

Running

Motor

Trouble

Motor

Reversal

Phase

Available

Power

Remote Alarm Terminals (I/O board)

(Fail Safe)

Alarm

Room

Pump

J19 - 14

J19 - 11

J19 - 12

Normally closed

Opens to alarm

Closes to alarm

Normally open

J40 - 14

J40 - 11

J40 - 12

Normally open

Closes to alarm

Opens to alarm

Normally closed

J42 - 14

J42 - 11

J42 - 12

Normally closed

Opens to alarm

Closes to alarm

Normally open

J37 - 14

J37 - 11

J37 - 12

Normally closed

Opens to alarm

Closes to alarm

Normally open

J39 - 14

J39 - 11

J39 - 12

Normally closed

Opens to alarm

Closes to alarm

Normally open

TB

1T

B2

TB

3T

B4

MO

TO

R R

UN

Programmable)

(Field*

J41 - 14

J41 - 11

J41 - 12

Normally closed

Opens to alarm

Closes to alarm

Normally open

TB

5

(RE-ASSIGNABLE)

(RE-ASSIGNABLE)

*Not Available in GPS Models

Drawing for information only.

Manufacturer reserves the right to modify this drawing without notice.

For drawing for approval or installation, please contact manufacturer.

Remote

Manual

Start

Remote

Automatic

Start

6