Technical Data Sheet

Sigma Series EQC Meter

These meters offer several advantages in switchboards and transformers Panels,used for

measurement of electrical parameters along with the threshold settings for relay operation.

Page 2: Technical Data Sheet Sigma Series EQC Meter · 2017. 3. 29. · Sigma Series EQC Meter ... fasteners and to sheet metal housing if non - insulated connector wires are used. 3) The

Application

www.sifamtinsley.com Page 1 of 3 Version No. :EQC/2015/02

Application

These meters offer several advantages in switchboards and transformers Panels,used for measurement

of electrical parameters along with the threshold settings for relay operation.

ApplicationMovement

Moving iron movement has pivots of very high hardness. Movement is suspended between spring

loaded saphire jewels. Movement is critically damped by use of silicon oil.

Nominal case and cutout dimensions for indicating Electrical instruments

DIN IEC 61554

Scale and pointer for electrical measuring instruments

DIN 43802

Safety requirements and protective measures for Electrical indicating. instruments and their accessories

DIN 40050, VDE 0110, VDE 0410IEC 529, IEC 1010

Performance specications for direct acting indicating analogue electrical measuring instruments and their accessories

IEC51/DINEN60051DIN 43701

Front frames for indicating measuring instruments Principle dimensions

DIN 43718

UL Compatibility UL 94 V-0

Accuracy testforrelay IS 3231

Rated burden test for relay IS 3231

Insulation test for relay IS 3231

Vibration test for relay IS 3231

Dryheat test for relay IS 3231

Applicable Standards

Pointer Knife - edge pointer

Pointer deection 0...90°

Scale characteristics Near Linear above 10% of nominal full Scale value

Scale division Coarse - ne

Scale length EQC 96 97mm

Over range Ammeters 2 times nominal current

Voltmeters for use on Voltage transformer

1.2 times nominal voltage

Scale and Pointer

Scale Interchangeability Interchangeable

Case details

Moulded square case suitable for mounting in Control / switchgear panels Machinery consoles.

Case material Glass Polycarbonate , ame retardant and drip proof as per UL 94 V-0.

Front facia Glass

Colour of bezel Black

Position of use Vertical

Panel xing Mounting Clamp

Mounting Stackable in a single cutout

Panel thickness < 25 mm

Terminals Plug and play terminal blocks

Mechanical Data

Electrical DataMeasured quantity AC current / voltage

Aux Supply 230VAC ± 15%, 45-65Hz

Aux Power consumption < 5.5 VA

Ammeter < 15 A < 1 VA

Ammeter > 15 A < 1.5 VA

Voltmeter < 4.5 VA

Overload capacity acc. to IEC 51

Continuously 1.2 times rated voltage / current

Short durationVoltmeters Ammeter 2 times rated voltage

5 s max. 10 times (200 A max.) : 10 overloads

1 s max. 40 times (250 A max.)

Sigma Series EQC Meter

Page 3: Technical Data Sheet Sigma Series EQC Meter · 2017. 3. 29. · Sigma Series EQC Meter ... fasteners and to sheet metal housing if non - insulated connector wires are used. 3) The

www.sifamtinsley.com Page 2 of 3

Environmental Conditions

Climatic Suitability Climate category II as per IS : 1248 (climatic class 3 according to VDE/VDI 3540)

Operating Temperature - 10... + 55° C

Storage temperature - 25...+65° C

Relative humidity < 75% annual average, non condensing

Shock resistance 15 g. for pulse duration 11ms

Environmental Conditions

Options

Case

Front Facia Antiglare glass and polycarbonate

Color of bezel Red, yellow, blue, white

Red index pointer Front adjustable on site

position of use on request 0° ...180°

Dial

Blank dial With initial and end values marked

Special markings Numbering/Lettering

Division dials Basic divisions without numbering

Color markings/bands Red or green

Accessories

Relay contact rating 10A @ 250VAC

Time delay 0 - 30 Sec. ± 3 Sec.

Set accuracy ± 5 %

Trip Setting 0 - 100%

Set accuracy ± 5 %

Hysterisys 2% of the scale

Enclosure code IP 52 case

Insulation class Group A according to VDE 0110

Rated insulation voltage 1000 V

Proof voltage EQC 96 : 2KV

Installation category 300 V CAT III (IEC 1010)

Insulation resistance > 50 Mohm at 500 V d.c

Response time of analog < 4 sec

Accuracy at Reference Conditions

Accuracy class

Ambient temperature 23°C ± 2°C

Position of use Nominal position ±1°

Input Rated value of measured quantity

Waveform Sinewave, distortion factor < 5 %

Frequency 50 Hz +/ - 0.1%

Other Conditions IEC 51/ DIN EN 60051

Ambient Temperature 0...50 °C

Position of use Vertical ± 5°

External Magnetic Field At 0.4 kA/m

Frequency 45-65 Hz

Nominal Range of use

Vibration resistance 10-55-10Hz for ampli. 0.15mm (1.5g at50Hz)

Standard Measuring range

Current (mA) 100, 150, 250, 400, 600

Current (A) 1, 1.5, 2.5, 4.6, 10, ..../1A,..../5A

Voltage (V) 6, 10, 15, 25, 40, 60, 100, 150, 250, 300, 400, 500, 600

Safety Terminal ProtectionFull sized polycarbonate back cover to provide protection against settings of potentiometer

Dimensions

a

cd

be

fDimensions (in mm) EQC 96

Bezel a 96Case b 87.5Depth c 60 d 5 f 72

+0.8Cutout Size (e) 92Weight (approx.) 450 gms

Sigma Series EQC Meter

Version No. :EQC/2015/02

1.5 according to IEC 51/DIN EN 60051

Page 4: Technical Data Sheet Sigma Series EQC Meter · 2017. 3. 29. · Sigma Series EQC Meter ... fasteners and to sheet metal housing if non - insulated connector wires are used. 3) The

Version No. :EQC/2015/02www.sifamtinsley.com Page 3 of 3

Alpha 70

Schematic Diagram

1

1

2

2

3

3

=5

4

4

Aux

Current meter

~

DELAY (Sec.)

25 75 CH I

CH II DELAY (sec.)

0

20

30 0

75

0

50

10

20 10

TRIP LEVEL (%FSD)

50

100

25

0 100 30 TRIP LEVEL (%FSD)

Trip level and delay settings

Connection

NO NOC CNC NC AUX INPUT

CH-I CH-II

1) Instruments with damaged bezels or window glasses must be disconnected from the mains.

2) Adequate safety clearance must be maintained to control panel fasteners and to sheet metal housing if non - insulated connector wires are used.3) The back cover must be snapped into place after final settings.4) Scales may only be replaced under voltage - free conditions.5) Bezels and window glasses may only be replaced under voltage - free Conditions.

Relay and LED status

Relay I

Trip condition

Healthy condition

LED I Relay II LED II

OFF ON OFF ON

ON OFF ON OFF

Cascade I mode :

Cascade II mode :

Relay I

Trip condition

Healthy condition

LED I Relay II LED II

ON ON

OFF OFF

ON ON

OFF OFF

CH-I

Delay setting

Trip level setting 0 - 100%

CH-II

0 - 100%

0 - 30 sec 0 - 30 sec

Note : Trip condition will occur after the set delay.

Note : Trip condition will occur after the set delay.