Technical Data Sheet
Sigma Series EQC Meter
These meters offer several advantages in switchboards and transformers Panels,used for
measurement of electrical parameters along with the threshold settings for relay operation.
![Page 2: Technical Data Sheet Sigma Series EQC Meter · 2017. 3. 29. · Sigma Series EQC Meter ... fasteners and to sheet metal housing if non - insulated connector wires are used. 3) The](https://reader036.fdocuments.in/reader036/viewer/2022071416/6111dbe91c4fe64dc45e059b/html5/thumbnails/2.jpg)
Application
www.sifamtinsley.com Page 1 of 3 Version No. :EQC/2015/02
Application
These meters offer several advantages in switchboards and transformers Panels,used for measurement
of electrical parameters along with the threshold settings for relay operation.
ApplicationMovement
Moving iron movement has pivots of very high hardness. Movement is suspended between spring
loaded saphire jewels. Movement is critically damped by use of silicon oil.
Nominal case and cutout dimensions for indicating Electrical instruments
DIN IEC 61554
Scale and pointer for electrical measuring instruments
DIN 43802
Safety requirements and protective measures for Electrical indicating. instruments and their accessories
DIN 40050, VDE 0110, VDE 0410IEC 529, IEC 1010
Performance specications for direct acting indicating analogue electrical measuring instruments and their accessories
IEC51/DINEN60051DIN 43701
Front frames for indicating measuring instruments Principle dimensions
DIN 43718
UL Compatibility UL 94 V-0
Accuracy testforrelay IS 3231
Rated burden test for relay IS 3231
Insulation test for relay IS 3231
Vibration test for relay IS 3231
Dryheat test for relay IS 3231
Applicable Standards
Pointer Knife - edge pointer
Pointer deection 0...90°
Scale characteristics Near Linear above 10% of nominal full Scale value
Scale division Coarse - ne
Scale length EQC 96 97mm
Over range Ammeters 2 times nominal current
Voltmeters for use on Voltage transformer
1.2 times nominal voltage
Scale and Pointer
Scale Interchangeability Interchangeable
Case details
Moulded square case suitable for mounting in Control / switchgear panels Machinery consoles.
Case material Glass Polycarbonate , ame retardant and drip proof as per UL 94 V-0.
Front facia Glass
Colour of bezel Black
Position of use Vertical
Panel xing Mounting Clamp
Mounting Stackable in a single cutout
Panel thickness < 25 mm
Terminals Plug and play terminal blocks
Mechanical Data
Electrical DataMeasured quantity AC current / voltage
Aux Supply 230VAC ± 15%, 45-65Hz
Aux Power consumption < 5.5 VA
Ammeter < 15 A < 1 VA
Ammeter > 15 A < 1.5 VA
Voltmeter < 4.5 VA
Overload capacity acc. to IEC 51
Continuously 1.2 times rated voltage / current
Short durationVoltmeters Ammeter 2 times rated voltage
5 s max. 10 times (200 A max.) : 10 overloads
1 s max. 40 times (250 A max.)
Sigma Series EQC Meter
![Page 3: Technical Data Sheet Sigma Series EQC Meter · 2017. 3. 29. · Sigma Series EQC Meter ... fasteners and to sheet metal housing if non - insulated connector wires are used. 3) The](https://reader036.fdocuments.in/reader036/viewer/2022071416/6111dbe91c4fe64dc45e059b/html5/thumbnails/3.jpg)
www.sifamtinsley.com Page 2 of 3
Environmental Conditions
Climatic Suitability Climate category II as per IS : 1248 (climatic class 3 according to VDE/VDI 3540)
Operating Temperature - 10... + 55° C
Storage temperature - 25...+65° C
Relative humidity < 75% annual average, non condensing
Shock resistance 15 g. for pulse duration 11ms
Environmental Conditions
Options
Case
Front Facia Antiglare glass and polycarbonate
Color of bezel Red, yellow, blue, white
Red index pointer Front adjustable on site
position of use on request 0° ...180°
Dial
Blank dial With initial and end values marked
Special markings Numbering/Lettering
Division dials Basic divisions without numbering
Color markings/bands Red or green
Accessories
Relay contact rating 10A @ 250VAC
Time delay 0 - 30 Sec. ± 3 Sec.
Set accuracy ± 5 %
Trip Setting 0 - 100%
Set accuracy ± 5 %
Hysterisys 2% of the scale
Enclosure code IP 52 case
Insulation class Group A according to VDE 0110
Rated insulation voltage 1000 V
Proof voltage EQC 96 : 2KV
Installation category 300 V CAT III (IEC 1010)
Insulation resistance > 50 Mohm at 500 V d.c
Response time of analog < 4 sec
Accuracy at Reference Conditions
Accuracy class
Ambient temperature 23°C ± 2°C
Position of use Nominal position ±1°
Input Rated value of measured quantity
Waveform Sinewave, distortion factor < 5 %
Frequency 50 Hz +/ - 0.1%
Other Conditions IEC 51/ DIN EN 60051
Ambient Temperature 0...50 °C
Position of use Vertical ± 5°
External Magnetic Field At 0.4 kA/m
Frequency 45-65 Hz
Nominal Range of use
Vibration resistance 10-55-10Hz for ampli. 0.15mm (1.5g at50Hz)
Standard Measuring range
Current (mA) 100, 150, 250, 400, 600
Current (A) 1, 1.5, 2.5, 4.6, 10, ..../1A,..../5A
Voltage (V) 6, 10, 15, 25, 40, 60, 100, 150, 250, 300, 400, 500, 600
Safety Terminal ProtectionFull sized polycarbonate back cover to provide protection against settings of potentiometer
Dimensions
a
cd
be
fDimensions (in mm) EQC 96
Bezel a 96Case b 87.5Depth c 60 d 5 f 72
+0.8Cutout Size (e) 92Weight (approx.) 450 gms
Sigma Series EQC Meter
Version No. :EQC/2015/02
1.5 according to IEC 51/DIN EN 60051
![Page 4: Technical Data Sheet Sigma Series EQC Meter · 2017. 3. 29. · Sigma Series EQC Meter ... fasteners and to sheet metal housing if non - insulated connector wires are used. 3) The](https://reader036.fdocuments.in/reader036/viewer/2022071416/6111dbe91c4fe64dc45e059b/html5/thumbnails/4.jpg)
Version No. :EQC/2015/02www.sifamtinsley.com Page 3 of 3
Alpha 70
Schematic Diagram
1
1
2
2
3
3
=5
4
4
Aux
Current meter
~
DELAY (Sec.)
25 75 CH I
CH II DELAY (sec.)
0
20
30 0
75
0
50
10
20 10
TRIP LEVEL (%FSD)
50
100
25
0 100 30 TRIP LEVEL (%FSD)
Trip level and delay settings
Connection
NO NOC CNC NC AUX INPUT
CH-I CH-II
1) Instruments with damaged bezels or window glasses must be disconnected from the mains.
2) Adequate safety clearance must be maintained to control panel fasteners and to sheet metal housing if non - insulated connector wires are used.3) The back cover must be snapped into place after final settings.4) Scales may only be replaced under voltage - free conditions.5) Bezels and window glasses may only be replaced under voltage - free Conditions.
Relay and LED status
Relay I
Trip condition
Healthy condition
LED I Relay II LED II
OFF ON OFF ON
ON OFF ON OFF
Cascade I mode :
Cascade II mode :
Relay I
Trip condition
Healthy condition
LED I Relay II LED II
ON ON
OFF OFF
ON ON
OFF OFF
CH-I
Delay setting
Trip level setting 0 - 100%
CH-II
0 - 100%
0 - 30 sec 0 - 30 sec
Note : Trip condition will occur after the set delay.
Note : Trip condition will occur after the set delay.
Safety Precautions